Earthing Systems Design Steps - Pt.5
Earthing Systems Design Steps - Pt.5
Earthing Systems Design Steps - Pt.5
Search
In Article " Earthing Systems Design steps – Part One ", I indicated the following points:
In the above Article and Article " Earthing Systems Design steps – Part Two ", I explained the first step: Data Collection.
Also, in Article " Earthing Systems Design steps – Part Three ", I explained the second step: Data Analysis.
And in Article " Earthing Systems Design steps – Part Four ", I explained What we are going to design for grounding system in any building?
Grounding system in any building can be broken down into several subdivisions:
In this Article, I explained the Building Exterior Grounds and Today I will explain Other Building’s Earthing System Divisions as follows.
Article 230 of the NEC contains the requirements for installing electrical services for buildings and dwellings.
Note:
Electrical designers, however, should keep in mind that local authorities, including
local electrical utilities, often have requirements which supersede or augment the
NEC. Electrical designers should contact the local authorities and determine if
1 of 7 16/11/2021, 14:25
Earthing Systems Design steps – Part Five ~ Electrical Knowhow http://www.electrical-knowhow.com/2013/11/electrical-service-groundin...
requirements for electrical services exist which differ from the NEC.
The requirements for grounding electrical services are contained in Article 250 of the NEC as follows:
1- Section 250-24(a) requires that a grounded electrical system, which supplies a building or structure, shall have at each service a grounding electrode conductor
connected to the grounding electrode system.
2- The grounding electrode conductor shall also be connected to the grounded service conductor in order to:
Limit the voltage to ground imposed on the system by lightning, line surges, and (unintentional) high-voltage crossovers.
Stabilize the voltage to ground during normal operation, including short circuits.
3- This connection may occur at any accessible point from the load end of the service drop or service lateral to the grounded conductor (neutral) terminal block in
the service disconnecting means. There are Three locations where 250.24(A)(1) permits the grounding electrode conductor to be connected to the ground service
conductor as follows (see fig.1):
Fig-1
4- Outdoor installations (like Outdoor Transformers) must have a grounding electrode, either at the transformer or elsewhere outside the building which must be
connected to the grounded service conductor. Fig.2 illustrates two grounding electrode connections, one at the service equipment installed inside the building
and one installed at the transformer, located outside of the building.
2 of 7 16/11/2021, 14:25
Earthing Systems Design steps – Part Five ~ Electrical Knowhow http://www.electrical-knowhow.com/2013/11/electrical-service-groundin...
Fig-2
Keep in mind that the purpose of bonding is different from that of grounding as in below table:
Bonding Grounding
definition Bonding is connecting Metallic Grounding is an intentional connection to
components of electrical systems to the earth or some other conducting body
ensure electrical continuity of the that serves in place of the earth.
components and the capacity to
conduct safely any fault Current
likely to be imposed.
The purpose The purpose of bonding is to create The purpose of grounding conductive
an equipotential plane that ensures materials, such as metal raceways and
that all metallic components are at equipment enclosures, is:
the same potential to ground.
3 of 7 16/11/2021, 14:25
Earthing Systems Design steps – Part Five ~ Electrical Knowhow http://www.electrical-knowhow.com/2013/11/electrical-service-groundin...
Definition:
Service equipment is any equipment necessary for the main control and means of
cutoff of the supply of electricity to a building or structure.
Note:
Standard locknuts, sealing locknuts, and metal bushings are not acceptable as the
sole means for bonding a raceway or cable to an enclosure on the line side of the
service disconnecting means regardless of the type of or condition of the knockout
(see fig.3). Electrical continuity has to be ensured through the use of a supply-side
bonding jumper that connects the raceway to the enclosure.
Fig-3
Five basic methods are listed, any one of which can be used to bond the service equipment together:
The first method: using the grounded service conductor. On the line side of the service equipment there is no separate equipment grounding
conductor. The grounded conductor assumes this role on the line side of the service. The permissible means for any connection made to the grounded
conductor include CADWELD exothermic welded connections, listed pressure connectors (wirenuts), listed clamps, and other listed means.
The second method: using threaded connections. This includes threaded couplings or bosses. It is important that these connections be made
wrenchtight to ensure a low impedance connection.
The third method: using threadless couplings or connectors. These fittings are available for rigid metal conduit, intermediate metal conduit and EMT.
Once again it is important that the connections be made up wrenchtight to ensure the low impedance ground path. Installers should note that the NEC
specifically prohibits the use of standard locknuts or bushings, even if a double arrangement is used, (one on the inside and one on the outside) to
achieve the bonding required by this section.
4 of 7 16/11/2021, 14:25
Earthing Systems Design steps – Part Five ~ Electrical Knowhow http://www.electrical-knowhow.com/2013/11/electrical-service-groundin...
The fourth method: using bonding jumpers. Bonding jumpers ensure electrical continuity by providing a low impedance path across concentric or
eccentric knockouts that may be part of the service equipment.
The fifth method: using other approved devices. This would include fittings such as bonding-type locknuts and grounding bushings (see fig.4). These
fittings are designed to make good contact with the metal enclosure and help to ensure good electrical continuity.
Fig-4
Fig-5
There are three permissible methods to facilitate the interconnection of these systems:
5 of 7 16/11/2021, 14:25
2. The second method: is to connect to the exposed GEC.
3. The third method: is to bond a copper or other corrosion-resistant conductor of at least a No. 6 AWG copper, to the service raceway or equipment.
In addition to the service equipment enclosures, other noncurrent-carrying enclosures are also required to be bonded by the NEC. Section 250-96
requires that metal raceways, cable trays, cable armor, cable sheaths, enclosures, frames, fittings and any other metal noncurrent-carrying parts be
bonded if they are to serve as grounding conductors. This requirement applies regardless of whether a supplementary equipment grounding conductor
is present.
The purpose of this rule is to ensure that these metallic components cannot become energized because they are isolated from a low impedance ground
path. If these components were not properly bonded and they were to become energized due to some fault condition, the overcurrent device may not
operate. This would result in personnel being put at risk to serious electrical shock hazards.
Note:
In the next Article, I will continue explaining Other Building Interior Bonding Divisions. Please, keep following.