Centeral Hot Water Calculation Sheet

Calculation Will be According to Type of The Building & Fixture Unit Methods:-

Choose the Type of Your Building private residence

Type of Pipes will be used Insulated pipe

Type of Pipes will be used

In Case of insulated pipe u don’t need to choise type of pipe used

Fixture QTY Total Gallon/Hr

private lav. 32 2 64
public lav. 0 4 0
bathtub 1 20 20
dishwasher 0 15 0
foot basin 0 3 0
kitchen sink 5 10 50
laundry 1 20 20
pantry sink 0 5 0
shower 8 30 240
service sink 0 20 0
hydrotherapentic shower 0 0 0
hubbard bath 0 0 0
leg bath 0 0 0
arm bath 0 0 0
sitz bath 0 0 0
continuous flow bath 0 0 0
circular wash sink 0 0 0
semicircular wash sink 0 0 0
394
DEMAND FACTOR 0.3
Probable Maximum Demand 118.2
Heater or coil Capacity 118.2
STORAGE CAPACITY Factor 0.7
Storage Tank Capacity GALLONS 82.74

Heat loss in Hot Water Pipes :-

Q loss/Ft Total Qloss


Pipe length in
Nominal pipe size
meter BTU/HR
1/2" 0 15 0
3/4" 0 17 0
1" 6 19 373.92
1-1/4" 18 21 1239.84
1-/2" 0 25 0
2" 40 28 3673.6
2-1/2" 45 32 4723.2
3" 0 38 0
4" 0 46 0
5" 0 55 0
6" 0 63 0
8" 0 80 0
Total Qloss for Hot Water Network 10010.6

Get Total heat loss in the system = 10010.56 Btu/hr

For each 10,000 BTU/HR Need 1 GPM


Required GPM for heat loss make up = Total heat loss in the system / 10,000
= 1 GPM

Total Farther Pipe length Supply & Return = 109 m


to get pump head the only loss we have in the line friction loss in all pipes and fitting
get pump head = 1.5*(friction loss)
= 1.5 * ( 4/100 * Total pipe length )
= 6.54 meter head
9.3 Psi
Conclusion for Centeral Water System

Heat or coil Capacity 118.2 Gallon / Hour


Storage Tank Capacity 82.74 Gallon

Circulation Pump Selection : -

Pump Flow 1 GPM


Pump Head+S.F 12.09 PSI
Pump HP 0.1 HP