Description

1   Section 6 Rule 3(6): Furnish compliance report of condition imposed while approving the
plans
2   Section 6 Rule 3(1)(b): (Hp>=30) ------------Plot no 37 G+2 construction is taken in to
use for stores (ground floor), canteen (first floor) and goods storage (second floor) without
approval of plans This is irregular
3  Sec 41 Rule 61F(2) ---------------- Ensure Functioning of interlocks provided to the
machinery by effective maintenance schedule
4     Section 28 Rule 55 ----------------- Get the hoist/Lift examined by a competent person
once in a Six months, submit a copy of such examination in from No. 38. Produce the record
immediately
5      Sec 31 Rule 56 ----------------------Autoclaves are also pressure vessels. They shall be
tested by competent person as per Rules along with air receivers All the pressure vessels shall
be hydrostatically examined once in four years Produce the record immediately
6    Sec 32 RW Sec 38 Rule 61 -----------Provide emergency staircase connecting all the floors
without obstruction for both buildings in Plot 2 and 3 and also canteen It shall be provided
immediately as the order is repeated from previous orders
7   Section 38 Rule 61 Ensure that each room in the factor premises where manufacturing
process is carried on or hazardous material is handled is having two doors
8        Section 38 and Rule 61: Failed to provide pressurized fire hydrant system with
sufficient storage of water fire pump and jockey pump inside the factory premises and
ensure that 7 Kg/cm2 pressure is maintained in the fire hydrant line.
9        Section 38 Rule 61 read with Section 7A(2): Provide Automatic fire extinguishing
appliances, fire resisting dampers electrically interlocked with heal sensitive f smoke
detectors.
10    Section 38 and Rule 61(2)(a)· Provide Unobstructed access for
fire lighting with proper provision and maintenance of Roads.
11    Section 46 and Rule 65-71: Canteen shall be maintained as per Rules. The
cost of food served to workers including contract workers shall be as per Rules
12    Section 46 and Rule 68(3): Display price list of food stuffs
being supplied in canteen al a conspicuous place in dining hall.
13    Section 47 and Rule 72: Provide and maintain adequate and suitable
sheller or rest room for the use of !he workers
14    1. Section 48 & Rule 73-76: provide and malntain a creche for the use of children of
women workers working in the faclory as more than 30 women workers are working.
15    Section 49 and Rule 76(8): . Appoint a qualified welfare officer in the factory tn
accordance with the provisions of Rule 76{8).

16    Section 45(4) and Rule 64: (i) Provide and maintain in the factory an ambulance room in
accordance with the provisions by Rule 64(1 )(2)(3}&(4 ).under the charge of a whole time
rnedlcal officer assisted by a!least one qualified nurse or dresser a cum a compounder. The
rnedlcal officer shall be readily available on call during the working hours of the factory. ·

(i1) The arnbutance room shall be ot atleast 24 Sq.Mt's floor area, wiih smooth hard and
impervious walls with good ventilation and shall be equipped with the articles as listed under
rule 64.(3).(iii) Provide in the premises and maintain in good condition a suitable conveyance
for the purpose of removing serious cases of accident. sickness.
17    . Section 45 4) and Rule 64:Provide and maintain in good condition a suitable
conveyance for the purpose of removing serious cases of accident sickness.
18    Section 59 Rule 78 C: Produce overtime payment record of all the employees within a
week or receipt of this order
19    Section 83 Rule 87 read with Rule 102-A: Produce the record of leave with wages
allowed to contract workers within a week of receipt of this order
20    Section 7 Rule 12-C: Submit the Building Stability Certificate issued by competent
Person in respect of buildings in plots 2 and 3
21    Sec 38 Rule 61 RW Sec 7A(2.): (Mockdrill) Organise evacuation drills for readiness in
emergency, Provide PA System/Alarm to warn employee in all the floors during Emergency

22    Section 87 and Rule 95: SCH XXIX : (LPG) Para 4 and 5: LPG shall be conveyed n a closed
circuit to prevent escape of the same and formation of flammable mixture of air and LPG
Para 6: Effective measures shall be taken to prevent sources or ignition like electrical
system. static charge .frtction etc Para 8: Provide appropriate and adequate means of
fighting !he fire in ihe premises.Provide LPG leakage detector and alarm to warn leakage of
LPG in usage area.

23    Sec 7A(2):Recheck and confirm availability of oxygen sensors with alarm in all the rooms
where Nitrogen connectinos are available. The alarms shall be regularly examined to ensure
their functioning.
ACTION PLAN