BD TIS-1 Sound
SOUND INSULATION
CRITERIA
Approved Document E, 2003 Edition: Floor Types 1 or 2 (Page 38 Diagram 3-1) requires a solid concrete slab (cast
2
in-situ or with permanent shuttering) to have a minimum mass of either 365 kg/m (Clause 3.29 Floor Type 1.1C), or
2
300 kg/m (Clause 3.67 Floor Types 2.1C and 2.1C(b)).
Reinforcement
Voids formed by
Plastic ball former
Volume of solid slab = 1x1x0.23 = 0.23 m 3. Volume of air voids = 25 no 180mm diameter balls per m 2
. Volume of
sphere is diameter x 0.5236. Therefore volume of each ball is (0.18x0.18x0.18) x 0.5236 = 0.0030536 m3 x 25no.
3
per m 2 = 0.07634 m3. Net volume of 230mm thick BubbleDeck slab is therefore 0.23 m 3
, minus 0.07634 m3 =
0.15366 m3. Mass of 230mm thick BubbleDeck slab is therefore 0.15366 m 3
x 2400 kg/m 2 (Weight of concrete with
2% reinforcement) = 368.8 kg/m2.
Mass of 368.8 kg/m 2 for 230mm thick BubbleDeck slab exceeds Approved Document Part E
requirement for Floor Types 1 or 2.