Professional Documents
Culture Documents
Storm Water Drainage System-3
Storm Water Drainage System-3
A × P× R
Q= [ m 3 / s]
3600 × 1000
4×Q 4 × 0.09
Q = A×V , d = = = 0.386 m
V×π 0.8 × π
Roof Drainage Design Procedure
The following procedure should be used in designing a roof drainage
system:
(1) Lay out the position of the roof drains, deck drains and rainwater
leaders. Consideration should be given to placing an overflow drain
adjacent to each roof drain.
(2) Determine the area to each roof drain, deck drain, gutter, or
rainwater leader. The area is the surface area of roof that drains towards a
specific drain. This area should include the effects of runoff from
adjacent walls which drain onto the walls, fig (R-1) indicates the wall
area that should be added to roof area to determine the total area for each
drain.
(3) Determine the routing and slope of the storm-water conductors. First,
determine the points from which, and to which, the conductors must be
installed. Then determine the space available for installing the storm-
water conductors. Finally, the routing and slope of the storm-water
conductors. An acceptable slope of roof concert is 0.5 % .
Fig (R-1)
Ref [2]
(4) Determine the rainfall rate to be used in sizing of the roof drainage
system. The rainfall rate (also known as the rainfall intensity) is a term
that relates the quantity of rainfall to a unit of time. Such rainfall rates
are usually expressed in inches per hour or centimeters per hour.
(5) Determine the flow rate (volume per unit time) of equipment such
as pumps, air-conditioning equipment, and similar equipment which
discharge into the roof drainage piping. Then convert these flow rates
into equivalent roof area. Flow rate is a term expressing a volume of
water over a period of time such as cubic feet per second (cubic meters
per hour), and gallons per minute (liters per second). The following
equations determine the roof area which will produce runoff at a flow
rate equal to the flow rate of the equipment:
Equivalent roof area = 96/R x flow r ate of the equipment ft²
Equivalent roof area = 359/R x flow r ate of the equipment m²
where R is the rainfall rate used in the design of the roof drainage
system in inches per hour (centimeters per hour). The flow rate of the
equipment is expressed in gallons per minute (liters per second).
For continuous or semi continuous flow : 1 gpm equivalent are is 24 ft 2 or 2 DFU
(6) Calculate the total roof area drained by each segment of the roof
drainage system. This calculation should include all roof areas
calculated in step (2) and the equivalent roof area calculated in step (5).
Express the total area in square feet (square meters).
(7) Determine the size of the roof drains and storm-water conductors or
the gutters and rainwater leaders. Sizes can be determined using table 5
through table 6. These tables list the maximum roof
area in square feet (square meters) which can be handled by
storm-water drainage piping of different sizes and slopes
for various rainfall rates.
An example of Roof rain water distribution is shown in figure
(R-2)
Area supplied by a drain pipe =
= (Area of the balcony) +(Effective area of the adjacent wall)
+ Part of the roof area.
Table 5 Rain water vertical pipe size
Size of drain pipe or leader (inch)
2 3 4 5 6
Ref [2]
Horizontal pipe size (table 6)
Figure ( R-2)
Example : “Sizing Rain water pipe”