Aircon Manual 1
Aircon Manual 1
'19 • KX-T-310D
DRAFT
TECHNICAL MANUAL
Wall mounted type Ceiling suspended type Outdoor air processing unit
FDK15KXZE1 FDE36KXZE1 FDU650FKXZE1
22KXZE1 45KXZE1 1100FKXZE1
28KXZE1 56KXZE1 1800FKXZE1
36KXZE1 71KXZE1 2400FKXZE1
45KXZE1 112KXZE1
56KXZE1 140KXZE1
71KXZE1
90KXZE1
• Note:
(1) This document describes the indoor units with service code /F (with motion sensor system
function).
7. APPLICATION DATA ...................................................................................... 24
7.1 Installation of indoor unit ........................................................................................ 24
'19 • KX-T-310D
7.2 Electric wiring work instruction ......................................................................... .... 30
7.3 Installation of wired remote control (Option parts) ........................................... 34
(1) Model RC-EX3 ................................................................................
CONTENTS ......... 34
(2) Model RC-E5 ............................................................................................ 41
1.8.SPECIFICATIONS
OUTLINE OF OPERATION CONTROL BY MYCROCOMPUTER .................2 46
.............................................................................................
8.1 Remote control (Option parts) ..................................................................... 46
2. 8.2
EXTERIOR DIMENSIONS
Operation control function ...............................................................................
by the wired remote control ................................. 19 49
8.3
(1) Operation control
Indoor units function by the indoor control ..............................................
.............................................................................................. 19 52
9. (2)
SYSTEM
RemoteTROUBLESHOOTING
control (Option parts)PROCEDURE .............................................
................................................................. 42 70
9.1 Basics of troubleshooting ...................................................................................... 70
3. 9.2
ELECTRICAL
Contents ofWIRING ....................................................................................
troubleshooting 45 71
..................................................................................
4. 9.3
NOISEInstruction
LEVEL ..of how to replace PCB .......................................................................
................................................................................................ 63104
9.4 Indoor PCB setting ..................................................................................................105
5.
10.CAPACITY TABLES...............................................................................................106
OPTION PARTS ........................................................................................ 70
6.10.1 Wireless
OPTION PARTSkit (RCN-T-5AW-E2) ................................................................................
............................................................................................ 132106
10.2 Simple wired remote control (RCH-E3) ................................................................114
6.1 Motion sensor kit ....................................................................................... 132
10.3 Motion sensor kit (LB-T-5W-E) ...............................................................................120
- 1-
Models FDT28KXZE1 FDT36KXZE1 FDT45KXZE1 FDT56KXZE1 FDT71KXZE1
Standard: T-PSA-5AW-E Standard: T-PSA-5AW-E Standard: T-PSA-5AW-E Standard: T-PSA-5AW-E Standard: T-PSA-5AW-E
Panel model (Option)
Draft prevention: T-PSAE-5AW-E Draft prevention: T-PSAE-5AW-E Draft prevention: T-PSAE-5AW-E Draft prevention: T-PSAE-5AW-E Draft prevention: T-PSAE-5AW-E
Nominal cooling capacity*1 2.8 3.6 4.5 5.6 7.1
kW
Nominal heating capacity*2 3.2 4.0 5.0 6.3 8.0
Power source 1 Phase 220-240V 50Hz / 220V 60Hz 1 Phase 220-240V 50Hz / 220V 60Hz 1 Phase 220-240V 50Hz / 220V 60Hz 1 Phase 220-240V 50Hz / 220V 60Hz 1 Phase 220-240V 50Hz / 220V 60Hz
Cooling 0.04 - 0.04 / 0.04 0.04 - 0.04 / 0.04 0.04 - 0.04 / 0.04 0.07 - 0.07 / 0.07 0.08 - 0.08 / 0.08
Power consumption kW
Heating 0.04 - 0.04 / 0.04 0.04 - 0.04 / 0.04 0.04 - 0.04 / 0.04 0.07 - 0.07 / 0.07 0.08 - 0.08 / 0.08
Cooling 0.36 - 0.33 / 0.36 0.36 - 0.33 / 0.36 0.36 - 0.33 / 0.36 0.62 - 0.57 / 0.62 0.70 - 0.64 / 0.70
Running current A
Heating 0.36 - 0.33 / 0.36 0.36 - 0.33 / 0.36 0.36 - 0.33 / 0.36 0.62 - 0.57 / 0.62 0.70 - 0.64 / 0.70
Sound Pressure Level P-Hi:38 Hi:33 Me:30 Lo:28 P-Hi:38 Hi:33 Me:30 Lo:28 P-Hi:38 Hi:33 Me:31 Lo:29 P-Hi:44 Hi:33 Me:31 Lo:29 P-Hi:47 Hi:35 Me:32 Lo:28
dB(A)
Sound Power Level 55 55 55 60 62
Exterior dimensions Unit:236 × 840 × 840 Unit:236 × 840 × 840 Unit:236 × 840 × 840 Unit:236 × 840 × 840 Unit:236 × 840 × 840
mm
Height x Width x Depth Panel:35 × 950 × 950 Panel:35 × 950 × 950 Panel:35 × 950 × 950 Panel:35 × 950 × 950 Panel:35 × 950 × 950
Exterior appearance Plaster White Plaster White Plaster White Plaster White Plaster White
1. SPECIFICATIONS
(Munsell color) ( 6.8Y8.9/0.2 ) near equivalent ( 6.8Y8.9/0.2 ) near equivalent ( 6.8Y8.9/0.2 ) near equivalent ( 6.8Y8.9/0.2 ) near equivalent ( 6.8Y8.9/0.2 ) near equivalent
Net weight*3 kg Unit:20 Standard panel:5 Unit:20 Standard panel:5 Unit:20 Standard panel:5 Unit:21.5 Standard panel:5 Unit:21.5 Standard panel:5
Refrigerant equipment
Louver fin & inner grooved tubing Louver fin & inner grooved tubing Louver fin & inner grooved tubing Louver fin & inner grooved tubing Louver fin & inner grooved tubing
Heat exchanger
(1) Ceiling cassette-4 way type (FDT)
Refrigerant control Electronic Expansion Valve Electronic Expansion Valve Electronic Expansion Valve Electronic Expansion Valve Electronic Expansion Valve
Air handling equipment
Turbo fan × 1 Turbo fan × 1 Turbo fan × 1 Turbo fan × 1 Turbo fan × 1
Fan type & Q'ty
Fan motor W 58 58 58 58 58
Starting method Direct line start Direct line start Direct line start Direct line start Direct line start
Air flow (Standard) m3/min P-Hi:20 Hi:14 Me:12 Lo:10 P-Hi:20 Hi:14 Me:12 Lo:10 P-Hi:20 Hi:15 Me:13 Lo:10 P-Hi:26 Hi:16 Me:13 Lo:11 P-Hi:28 Hi:17 Me:14 Lo:12
-
Available static pressure Pa 0 0 0 0 0
Outside air intake Possible Possible Possible Possible Possible
2-
Air filter, Q'ty Pocket plastic net × 1 (Washable) Pocket plastic net× 1 (Washable) Pocket plastic net× 1 (Washable) Pocket plastic net× 1 (Washable) Pocket plastic net× 1 (Washable)
Shock & vibration absorber Rubber sleeve(for fan motor) Rubber sleeve(for fan motor) Rubber sleeve(for fan motor) Rubber sleeve(for fan motor) Rubber sleeve(for fan motor)
Insulation (noise & heat) Polyurethane form Polyurethane form Polyurethane form Polyurethane form Polyurethane form
Operation control Wired : RC-EX3A, RC-E5, RCH-E3 Wired : RC-EX3A, RC-E5, RCH-E3 Wired : RC-EX3A, RC-E5, RCH-E3 Wired : RC-EX3A, RC-E5, RCH-E3 Wired : RC-EX3A, RC-E5, RCH-E3
Remote control switch (option) Wireless : RCN-T-5AW-E2 Wireless : RCN-T-5AW-E2 Wireless : RCN-T-5AW-E2 Wireless : RCN-T-5AW-E2 Wireless : RCN-T-5AW-E2
Room temperature control Thermostat by electronics Thermostat by electronics Thermostat by electronics Thermostat by electronics Thermostat by electronics
Models FDT28KXZE1, 36KXZE1, 45KXZE1, 56KXZE1, 71KXZE1
Overload protection for fan motor Overload protection for fan motor Overload protection for fan motor Overload protection for fan motor Overload protection for fan motor
Safety equipment
Frost protection thermostat Frost protection thermostat Frost protection thermostat Frost protection thermostat Frost protection thermostat
Installation data Liquid line φ6.35 (1/4") <Flare piping> φ6.35 (1/4") <Flare piping> φ6.35 (1/4") <Flare piping> φ6.35 (1/4") <Flare piping> φ9.52 (3/8") <Flare piping>
Refrigerant piping size Gas line φ9.52 (3/8") <Flare piping> φ12.7 (1/2") <Flare piping> φ12.7 (1/2") <Flare piping> φ12.7 (1/2") <Flare piping> φ15.88 (5/8") <Flare piping>
Connecting method Flare piping Flare piping Flare piping Flare piping Flare piping
Refrigerant R410A R410A R410A R410A R410A
Drain pump Built-in Drain pump Built-in Drain pump Built-in Drain pump Built-in Drain pump Built-in Drain pump
Drain hose Connectable with VP25 Connectable with VP25 Connectable with VP25 Connectable with VP25 Connectable with VP25
Insulation for piping Necessary(both Liquid & Gas line) Necessary(both Liquid & Gas line) Necessary(both Liquid & Gas line) Necessary(both Liquid & Gas line) Necessary(both Liquid & Gas line)
Accessories Mounting kit,Drain hose Mounting kit,Drain hose Mounting kit,Drain hose Mounting kit,Drain hose Mounting kit,Drain hose
Exterior dimensions PJF000Z417 PJF000Z417 PJF000Z417 PJF000Z417 PJF000Z417
Electrical wiring PJF000Z421 PJF000Z421 PJF000Z421 PJF000Z421 PJF000Z421
Notes (1) The data are measured at the following conditions. Adapted to RoHS directive
Item Indoor air temperature Outdoor air temperature
Standards
Operation DB WB DB WB
Cooling*1 27℃ 19℃ 35℃ 24℃
ISO-T1
Heating*2 20℃ 7℃ 6℃
(2) This packaged air-conditioner is manufactured and tested in conformity with the following standard.
ISO-T1 "UNITARY AIR-CONDITIONERS"
PJF000Z416 C
(3) Draft prevention panel weight*3 : 6kg
(4) Option : Motion sensor kit (LB-T-5W-E)
'19 • KX-T-310D
Models FDT90KXZE1 FDT112KXZE1 FDT140KXZE1 FDT160KXZE1
Standard: T-PSA-5AW-E Standard: T-PSA-5AW-E Standard: T-PSA-5AW-E Standard: T-PSA-5AW-E
Panel model (Option)
Draft prevention: T-PSAE-5AW-E Draft prevention: T-PSAE-5AW-E Draft prevention: T-PSAE-5AW-E Draft prevention: T-PSAE-5AW-E
Nominal cooling capacity*1 9.0 11.2 14.0 16.0
kW
Nominal heating capacity*2 10.0 12.5 16.0 18.0
Power source 1 Phase 220-240 50Hz / 220V 60Hz 1 Phase 220-240V 50Hz / 220V 60Hz 1 Phase 220-240V 50Hz / 220V 60Hz 1 Phase 220-240V 50Hz / 220V 60Hz
Cooling 0.13 - 0.13 / 0.13 0.14 - 0.14 / 0.14 0.14 - 0.14 / 0.14 0.14 - 0.14 / 0.14
Power consumption kW
Heating 0.13 - 0.13 / 0.13 0.14 - 0.14 / 0.14 0.14 - 0.14 / 0.14 0.14 - 0.14 / 0.14
Cooling 1.04 - 0.95 / 1.04 1.12 - 1.02 / 1.12 1.12 - 1.02 / 1.12 1.12 - 1.02 / 1.12
Running current A
Heating 1.04 - 0.95 / 1.04 1.12 - 1.02 / 1.12 1.12 - 1.02 / 1.12 1.12 - 1.02 / 1.12
Sound Pressure Level P-Hi:49 Hi:38 Me:36 Lo:31 P-Hi:49 Hi:39 Me:37 Lo:31 P-Hi:49 Hi:42 Me:39 Lo:32 P-Hi:49 Hi:42 Me:39 Lo:33
dB(A)
Sound Power Level 65 66 66 66
Exterior dimensions Unit:298 × 840 × 840 Unit:298 × 840 × 840 Unit:298 × 840 × 840 Unit:298 × 840 × 840
mm
Height x Width x Depth Panel:35 × 950 × 950 Panel:35 × 950 × 950 Panel:35 × 950 × 950 Panel:35 × 950 × 950
Exterior appearance Plaster White Plaster White Plaster White Plaster White
(Munsell color) ( 6.8Y8.9/0.2 ) near equivalent ( 6.8Y8.9/0.2 ) near equivalent ( 6.8Y8.9/0.2 ) near equivalent ( 6.8Y8.9/0.2 ) near equivalent
Net weight*3 kg Unit:25 Standard panel:5 Unit:25 Standard panel:5 Unit:25 Standard panel:5 Unit:25 Standard panel:5
Refrigerant equipment
Louver fin & inner grooved tubing Louver fin & inner grooved tubing Louver fin & inner grooved tubing Louver fin & inner grooved tubing
Heat exchanger
Refrigerant control Electronic Expansion Valve Electronic Expansion Valve Electronic Expansion Valve Electronic Expansion Valve
Air handling equipment
Turbo fan × 1 Turbo fan × 1 Turbo fan × 1 Turbo fan × 1
Fan type & Q'ty
Fan motor W 120 120 120 120
Starting method Direct line start Direct line start Direct line start Direct line start
Air flow (Standard) m3/min P-Hi:37 Hi:25 Me:22 Lo:15 P-Hi:38 Hi:26 Me:23 Lo:17 P-Hi:38 Hi:28 Me:25 Lo:18 P-Hi:38 Hi:29 Me:26 Lo:19
-
Available static pressure Pa 0 0 0 0
Outside air intake Possible Possible Possible Possible
3-
Models FDT90KXZE1, 112KXZE1, 140KXZE1, 160KXZE1
Air filter, Q'ty Pocket plastic net× 1 (Washable) Pocket plastic net× 1 (Washable) Pocket plastic net× 1 (Washable) Pocket plastic net× 1 (Washable)
Shock & vibration absorber Rubber sleeve(for fan motor) Rubber sleeve(for fan motor) Rubber sleeve(for fan motor) Rubber sleeve(for fan motor)
Insulation (noise & heat) Polyurethane form Polyurethane form Polyurethane form Polyurethane form
Operation control Wired : RC-EX3A, RC-E5, RCH-E3 Wired : RC-EX3A, RC-E5, RCH-E3 Wired : RC-EX3A, RC-E5, RCH-E3 Wired : RC-EX3A, RC-E5, RCH-E3
Remote control switch (option) Wireless : RCN-T-5AW-E2 Wireless : RCN-T-5AW-E2 Wireless : RCN-T-5AW-E2 Wireless : RCN-T-5AW-E2
Room temperature control Thermostat by electronics Thermostat by electronics Thermostat by electronics Thermostat by electronics
Overload protection for fan motor Overload protection for fan motor Overload protection for fan motor Overload protection for fan motor
Safety equipment
Frost protection thermostat Frost protection thermostat Frost protection thermostat Frost protection thermostat
Installation data Liquid line φ9.52 (3/8") <Flare piping> φ9.52 (3/8") <Flare piping> φ9.52 (3/8") <Flare piping> φ9.52 (3/8") <Flare piping>
Refrigerant piping size Gas line φ15.88 (5/8") <Flare piping> φ15.88 (5/8") <Flare piping> φ15.88 (5/8") <Flare piping> φ15.88 (5/8") <Flare piping>
Connecting method Flare piping Flare piping Flare piping Flare piping
Refrigerant R410A R410A R410A R410A
Drain pump Built-in Drain pump Built-in Drain pump Built-in Drain pump Built-in Drain pump
Drain hose Connectable with VP25 Connectable with VP25 Connectable with VP25 Connectable with VP25
Insulation for piping Necessary(both Liquid & Gas line) Necessary(both Liquid & Gas line) Necessary(both Liquid & Gas line) Necessary(both Liquid & Gas line)
Accessories Mounting kit,Drain hose Mounting kit,Drain hose Mounting kit,Drain hose Mounting kit,Drain hose
Exterior dimensions PJF000Z418 PJF000Z418 PJF000Z418 PJF000Z418
Electrical wiring PJF000Z421 PJF000Z421 PJF000Z421 PJF000Z421
Notes (1) The data are measured at the following conditions. Adapted to RoHS directive
Item Indoor air temperature Outdoor air temperature
Standards
Operation DB WB DB WB
Cooling*1 27℃ 19℃ 35℃ 24℃
ISO-T1
Heating*2 20℃ 7℃ 6℃
(2) This packaged air-conditioner is manufactured and tested in conformity with the following standard.
ISO-T1 "UNITARY AIR-CONDITIONERS"
PJF000Z416 C
(3) Draft prevention panel weight*3 : 6kg
(4) Option : Motion sensor kit (LB-T-5W-E)
'19 • KX-T-310D
Models FDTC15KXZE1 FDTC22KXZE1 FDTC28KXZE1 FDTC36KXZE1 FDTC45KXZE1 FDTC56KXZE1
Standard: TC-PSA-5AW-E Standard: TC-PSA-5AW-E Standard: TC-PSA-5AW-E Standard: TC-PSA-5AW-E Standard: TC-PSA-5AW-E Standard: TC-PSA-5AW-E
Panel model (Option)
Draft prevention: TC-PSAE-5AW-E Draft prevention: TC-PSAE-5AW-E Draft prevention: TC-PSAE-5AW-E Draft prevention: TC-PSAE-5AW-E Draft prevention: TC-PSAE-5AW-E Draft prevention: TC-PSAE-5AW-E
Nominal cooling capacity*1 1.5 2.2 2.8 3.6 4.5 5.6
kW
Nominal heating capacity*2 1.7 2.5 3.2 4.0 5.0 6.3
Power source 1 Phase 220-240V 50Hz / 220V 60Hz 1 Phase 220-240V 50Hz / 220V 60Hz 1 Phase 220-240V 50Hz / 220V 60Hz 1 Phase 220-240V 50Hz / 220V 60Hz 1 Phase 220-240V 50Hz / 220V 60Hz 1 Phase 220-240V 50Hz / 220V 60Hz
Cooling 0.03 - 0.03 / 0.03 0.03 - 0.03 / 0.03 0.03 - 0.03 / 0.03 0.04 - 0.04 / 0.04 0.05 - 0.05 / 0.05 0.06 - 0.06 / 0.06
Power consumption kW
Heating 0.03 - 0.03 / 0.03 0.03 - 0.03 / 0.03 0.03 - 0.03 / 0.03 0.04 - 0.04 / 0.04 0.05 - 0.05 / 0.05 0.06 - 0.06 / 0.06
Cooling 0.25 - 0.22 / 0.25 0.25 - 0.22 / 0.25 0.25 - 0.22 / 0.25 0.38 - 0.35 / 038 0.43 - 0.40 / 0.43 0.54 - 0.50 / 0.54
Running current A
Heating 0.25 - 0.22 / 0.25 0.25 - 0.22 / 0.25 0.25 - 0.22 / 0.25 0.38 - 0.35 / 038 0.43 - 0.40 / 0.43 0.54 - 0.50 / 0.54
Cooling P-Hi: 33 Hi: 30 Me: 28 Lo: 25 P-Hi: 35 Hi: 32 Me: 29 Lo: 25 P-Hi: 35 Hi: 32 Me: 29 Lo: 25 P-Hi: 39 Hi: 36 Me: 31 Lo: 26 P-Hi: 43 Hi: 39 Me: 36 Lo: 28 P-Hi: 47 Hi: 43 Me: 39 Lo: 31
Sound Pressure Level dB(A)
Heating P-Hi: 33 Hi: 30 Me: 26 Lo: 22 P-Hi: 35 Hi: 32 Me: 29 Lo: 25 P-Hi: 35 Hi: 32 Me: 29 Lo: 25 P-Hi: 39 Hi: 36 Me: 31 Lo: 26 P-Hi: 43 Hi: 39 Me: 36 Lo: 28 P-Hi: 47 Hi: 43 Me: 39 Lo: 31
Cooling 47 49 49 54 58 60
Sound Power Level
Heating 46 49 49 53 57 60
Exterior dimensions Unit: 248 × 570 × 570 Unit: 248 × 570 × 570 Unit: 248 × 570 × 570 Unit: 248 × 570 × 570 Unit: 248 × 570 × 570 Unit: 248 × 570 × 570
mm
Height x Width x Depth Panel: 10 × 620 × 620 Panel: 10 × 620 × 620 Panel: 10 × 620 × 620 Panel: 10 × 620 × 620 Panel: 10 × 620 × 620 Panel: 10 × 620 × 620
Exterior appearance Fine snow Fine snow Fine snow Fine snow Fine snow Fine snow
( Munsell color ) ( 8.0Y9.3/0.1 )near equivalent ( 8.0Y9.3/0.1 )near equivalent ( 8.0Y9.3/0.1 )near equivalent ( 8.0Y9.3/0.1 )near equivalent ( 8.0Y9.3/0.1 )near equivalent ( 8.0Y9.3/0.1 )near equivalent
( RAL color ) ( RAL 9001 )near equivalent ( RAL 9001 )near equivalent ( RAL 9001 )near equivalent ( RAL 9001 )near equivalent ( RAL 9001 )near equivalent ( RAL 9001 )near equivalent
Net weight*3 kg Unit: 12.5 Standard panel: 2.5 Unit: 13 Standard panel: 2.5 Unit: 13 Standard panel: 2.5 Unit: 14 Standard panel: 2.5 Unit: 14 Standard panel: 2.5 Unit: 14 Standard panel: 2.5
Refrigerant equipment Heat exchanger Louver fin & inner grooved tubing Louver fin & inner grooved tubing Louver fin & inner grooved tubing Louver fin & inner grooved tubing Louver fin & inner grooved tubing Louver fin & inner grooved tubing
Refrigerant control Electronic Expansion Valve Electronic Expansion Valve Electronic Expansion Valve Electronic Expansion Valve Electronic Expansion Valve Electronic Expansion Valve
Air handling equipment Fan type & Q'ty Turbo fan ×1 Turbo fan ×1 Turbo fan ×1 Turbo fan ×1 Turbo fan ×1 Turbo fan ×1
Fan motor W 50 50 50 50 50 50
Starting method Direct line start Direct line start Direct line start Direct line start Direct line start Direct line start
Cooling 3 P-Hi: 8 Hi: 7 Me: 6 Lo: 5 P-Hi: 9 Hi: 8 Me: 7 Lo: 6 P-Hi: 9 Hi: 8 Me: 7 Lo: 6 P-Hi: 10 Hi: 9 Me: 8 Lo: 6 P-Hi: 12 Hi: 10 Me: 9 Lo: 7 P-Hi: 14 Hi: 12 Me: 10 Lo: 8
Air flow(Standard) m /min
(2) Ceiling cassette-4 way compact type (FDTC)
Heating P-Hi: 8 Hi: 7 Me: 6 Lo: 5 P-Hi: 9 Hi: 8 Me: 7 Lo: 6 P-Hi: 9 Hi: 8 Me: 7 Lo: 6 P-Hi: 10 Hi: 9 Me: 8 Lo: 6 P-Hi: 12 Hi: 10 Me: 9 Lo: 7 P-Hi: 14 Hi: 12 Me: 10 Lo: 8
-
Available static pressure Pa 0 0 0 0 0 0
Outdoor air intake Possible Possible Possible Possible Possible Possible
4-
Air filter, Q'ty Pocket plastic net ×1(Washable) Pocket plastic net ×1(Washable) Pocket plastic net ×1(Washable) Pocket plastic net ×1(Washable) Pocket plastic net ×1(Washable) Pocket plastic net ×1(Washable)
Shock & vibration absorber Rubber sleeve(for fan motor) Rubber sleeve(for fan motor) Rubber sleeve(for fan motor) Rubber sleeve(for fan motor) Rubber sleeve(for fan motor) Rubber sleeve(for fan motor)
Insulation (noise & heat) Polyurethane form Polyurethane form Polyurethane form Polyurethane form Polyurethane form Polyurethane form
Operation control Wired : RC-E5, RC-EX3A, RCH-E3 Wired : RC-E5, RC-EX3A, RCH-E3 Wired : RC-E5, RC-EX3A, RCH-E3 Wired : RC-E5, RC-EX3A, RCH-E3 Wired : RC-E5, RC-EX3A, RCH-E3 Wired : RC-E5, RC-EX3A, RCH-E3
Remote control switch ( option ) Wireless : RCN-TC-5AW-E2 Wireless : RCN-TC-5AW-E2 Wireless : RCN-TC-5AW-E2 Wireless : RCN-TC-5AW-E2 Wireless : RCN-TC-5AW-E2 Wireless : RCN-TC-5AW-E2
Room temperature control Thermostat by electronics Thermostat by electronics Thermostat by electronics Thermostat by electronics Thermostat by electronics Thermostat by electronics
Overload protection for fan motor Overload protection for fan motor Overload protection for fan motor Overload protection for fan motor Overload protection for fan motor Overload protection for fan motor
Safety equipment
Frost protection thermostat Frost protection thermostat Frost protection thermostat Frost protection thermostat Frost protection thermostat Frost protection thermostat
Installation data Liquid line φ6.35 (1/4") <Flare piping> φ6.35 (1/4") <Flare piping> φ6.35 (1/4") <Flare piping> φ6.35 (1/4") <Flare piping> φ6.35 (1/4") <Flare piping> φ6.35 (1/4") <Flare piping>
Refrigerant piping size Gas line φ9.52 (3/8") <Flare piping> φ9.52 (3/8") <Flare piping> φ9.52 (3/8") <Flare piping> φ12.7 (1/2") <Flare piping> φ12.7 (1/2") <Flare piping> φ12.7 (1/2") <Flare piping>
Connecting method Flare piping Flare piping Flare piping Flare piping Flare piping Flare piping
Refrigerant R410A R410A R410A R410A R410A R410A
Drain pump Built-in Drain pump Built-in Drain pump Built-in Drain pump Built-in Drain pump Built-in Drain pump Built-in Drain pump
Models FDTC15KXZE1, 22KXZE1, 28KXZE1, 36KXZE1, 45KXZE1, 56KXZE1
Drain hose Connectable with VP25 Connectable with VP25 Connectable with VP25 Connectable with VP25 Connectable with VP25 Connectable with VP25
Insulation for piping Necessary(both Liquid & Gas line) Necessary(both Liquid & Gas line) Necessary(both Liquid & Gas line) Necessary(both Liquid & Gas line) Necessary(both Liquid & Gas line) Necessary(both Liquid & Gas line)
Accessories Mounting kit,Drain hose Mounting kit,Drain hose Mounting kit,Drain hose Mounting kit,Drain hose Mounting kit,Drain hose Mounting kit,Drain hose
Exterior dimensions PJF000Z501 PJF000Z501 PJF000Z501 PJF000Z501 PJF000Z501 PJF000Z501
Electrical wiring PJF000Z504 PJF000Z504 PJF000Z504 PJF000Z504 PJF000Z504 PJF000Z504
Notes (1) The data are measured at the following conditions. Adapted to RoHS directive
Item Indoor air temperature Outdoor air temperature
Standards
Operation DB WB DB WB
Cooling*1 27℃ 19℃ 35℃ 24℃
ISO-T1
Heating*2 20℃ 7℃ 6℃
(2) This packaged air-conditioner is manufactured and tested in conformity with the following standard.
ISO-T1 "UNITARY AIR-CONDITIONERS"
(3) Draft prevention panel weight*3 : 3.0kg
PJF000Z498
(4) Option : Motion sensor kit (LB-TC-5W-E)
'19 • KX-T-310D
Models FDTW28KXE6F FDTW45KXE6F FDTW56KXE6F FDTW71KXE6F
Panel model (Option) TW-PSA-26W-E TW-PSA-26W-E TW-PSA-26W-E TW-PSA-26W-E
Nominal cooling capacity*1 2.8 4.5 5.6 7.1
kW
Nominal heating capacity*2 3.2 5.0 6.3 8.0
Power source 1 Phase 220 - 240V 50Hz / 220V 60Hz 1 Phase 220 - 240V 50Hz / 220V 60Hz 1 Phase 220 - 240V 50Hz / 220V 60Hz 1 Phase 220 - 240V 50Hz / 220V 60Hz
Cooling 0.090 - 0.090 / 0.090 0.100 - 0.100 / 0.100 0.100 - 0.100 / 0.100 0.140 - 0.140 / 0.140
Power consumption kW
Heating 0.090 - 0.090 / 0.090 0.100 - 0.100 / 0.100 0.100 - 0.100 / 0.100 0.140 - 0.140 / 0.140
Cooling 0.45 - 0.45 / 0.45 0.55 - 0.55 / 0.55 0.55 - 0.55 / 0.55 0.75 - 0.75 / 0.75
Running current A
Heating 0.45 - 0.45 / 0.45 0.55 - 0.55 / 0.55 0.55 - 0.55 / 0.55 0.75 - 0.75 / 0.75
Cooling 58 58 58 58
Sound Power Level
Heating 58 58 58 58
dB(A)
Cooling P-Hi:42 Hi:38 Me:34 Lo:31 P-Hi:42 Hi:38 Me:34 Lo: 31 P-Hi: 42 Hi:38 Me:34 Lo: 31 P-Hi:42 Hi:38 Me:34 Lo:31
Sound Pressure Level
Heating P-Hi:42 Hi:38 Me:34 Lo:31 P-Hi:42 Hi:38 Me:34 Lo: 31 P-Hi:42 Hi:38 Me:34 Lo: 31 P-Hi:42 Hi:38 Me:34 Lo:31
Exterior dimensions Unit: 325 × 820 × 620 Unit:325 × 820 × 620 Unit:325 × 820 × 620 Unit:325 × 820 × 620
mm
Height x Width x Depth Panel: 20 × 1,120 × 680 Panel:20 × 1,120 × 680 Panel:20 × 1,120 × 680 Panel:20 × 1,120 × 680
Exterior appearance Plaster White Plaster White Plaster White Plaster White
( Munsell color ) ( 6.8Y8.9/0.2 )near equivalent ( 6.8Y8.9/0.2 )near equivalent ( 6.8Y8.9/0.2 )near equivalent ( 6.8Y8.9/0.2 )near equivalent
Net weight kg Unit:20 Panel:8.5 Unit:21 Panel:8.5 Unit:21 Panel:8.5 Unit:23 Panel:8.5
Refrigerant equipment Heat exchanger Louver fin & inner grooved tubing Louver fin & inner grooved tubing Louver fin & inner grooved tubing Louver fin & inner grooved tubing
Refrigerant control Electronic Expansion Valve Electronic Expansion Valve Electronic Expansion Valve Electronic Expansion Valve
:
:
Air handling equipment Fan type & Q'ty Turbo fan Turbo fan Turbo fan Turbo fan
(3) Ceiling cassette-2 way type (FDTW)
Fan motor <starting method> W 30 < Direct line start > 35 < Direct line start > 35 < Direct line start > 40 < Direct line start >
Cooling 3 P-Hi:14.5 Hi:12 Me:10 Lo: 9 P-Hi:14.5 Hi:12 Me:10 Lo: 9 P-Hi:14.5 Hi:12 Me: 10 Lo: 9 P-Hi:14.5 Hi:12 Me:10 Lo: 9
Air flow(Standard) m /min
Heating P-Hi:14.5 Hi:12 Me:10 Lo: 9 P-Hi:14.5 Hi:12 Me:10 Lo: 9 P-Hi:14.5 Hi:12 Me: 10 Lo: 9 P-Hi:14.5 Hi:12 Me:10 Lo: 9
Available static pressure Pa 0 0 0 0
Outdoor air intake Possible Possible Possible Possible
-
Air filter, Q'ty Pocket plastic net ×2 (Washable) Pocket plastic net ×2 (Washable) Pocket plastic net ×2 (Washable) Pocket plastic net ×2 (Washable)
Shock & vibration absorber Rubber sleeve(for fan motor) Rubber sleeve(for fan motor) Rubber sleeve(for fan motor) Rubber sleeve(for fan motor)
Insulation (noise & heat) Polyurethane form Polyurethane form Polyurethane form Polyurethane form
5-
Operation control Wired:RC-EX3A,RC-E5 Wired : RC-EX3A,RC-E5 Wired : RC-EX3A,RC-E5 Wired : RC-EX3A,RC-E5
Remote control switch ( option ) Wireless:RCN-TW-E2 Wireless : RCN-TW-E2 Wireless : RCN-TW-E2 Wireless : RCN-TW-E2
Models FDTW28KXE6F, 45KXE6F, 56KXE6F, 71KXE6F
Room temperature control Thermostat by electronics Thermostat by electronics Thermostat by electronics Thermostat by electronics
Overload protection for fan motor Overload protection for fan motor Overload protection for fan motor Overload protection for fan motor
Safety equipment
Frost protection thermostat Frost protection thermostat Frost protection thermostat Frost protection thermostat
Installation data Liquid line φ6.35 (1/4") <Flare piping> φ6.35 (1/4") <Flare piping> φ6.35 (1/4") <Flare piping> φ9.52 (3/8") <Flare piping>
Refrigerant piping size Gas line φ9.52 (3/8") <Flare piping> φ12.7 (1/2") <Flare piping> φ12.7 (1/2") <Flare piping> φ15.88 (5/8") <Flare piping>
Refrigerant R410A R410A R410A R410A
Drain pump Built-in Drain pump Built-in Drain pump Built-in Drain pump Built-in Drain pump
Drain hose Connectable with VP25 (I.D.25,O.D.32) Connectable with VP25 (I.D.25,O.D.32) Connectable with VP25 (I.D.25,O.D.32) Connectable with VP25 (I.D.25,O.D.32)
Insulation for piping Necessary(both Liquid & Gas line) Necessary(both Liquid & Gas line) Necessary(both Liquid & Gas line) Necessary(both Liquid & Gas line)
Accessories Mounting kit, Drain hose Mounting kit, Drain hose Mounting kit, Drain hose Mounting kit, Drain hose
Exterior dimensions PJB001Z713 PJB001Z713 PJB001Z713 PJB001Z713
Electrical wiring PJB001Z830 PJB001Z830 PJB001Z830 PJB001Z830
Notes (1) The data are measured at the following conditions. OPTION Model Specification Adapted to RoHS directive
Item Indoor air temperature Outdoor air temperature Wired RC-EX3A PJZ000Z333
Standards
Operation DB WB DB WB Wired RC-E5 PJZ000Z295
Remote
Cooling*1 27℃ 19℃ 35℃ 24℃ control Wired RCH-E3 PJZ000Z272
ISO-T1
Heating*2 20℃ 7℃ 6℃
Wireless RCN-TW-E2 PJB001Z798
(2) This packaged air-conditioner is manufactured and tested in conformity with the standard.
ISO-T1 "UNITARY AIR-CONDITIONERS" SPECIFICATION Motion sensor LB-TW-6W PJB001Z818
(3) Sound level indicates the value in an anechoic chamber.
During operation these value are somewhat higher due to ambient conditions.
(4) Select the breaker size according to the own national standard.
PJB001Z829
'19 • KX-T-310D
Models FDTW90KXE6F FDTW112KXE6F FDTW140KXE6F
Panel model (Option) TW-PSA-46W-E TW-PSA-46W-E TW-PSA-46W-E
Nominal cooling capacity*1 9.0 11.2 14.0
kW
Nominal heating capacity*2 10.0 12.5 16.0
Power source 1 Phase 220 - 240V 50Hz / 220V 60Hz 1 Phase 220 - 240V 50Hz / 220V 60Hz 1 Phase 240V 50Hz / 220V 60Hz
Cooling 0.190 - 0.190 / 0.190 0.190 - 0.190 / 0.190 0.190 - 0.190 / 0.190
Power consumption kW
Heating 0.190 - 0.190 / 0.190 0.190 - 0.190 / 0.190 0.190 - 0.190 / 0.190
Cooling 1.00 - 1.00 / 1.00 1.00 - 1.00 / 1.00 1.00 - 1.00 / 1.00
Running current A
Heating 1.00 - 1.00 / 1.00 1.00 - 1.00 / 1.00 1.00 - 1.00 / 1.00
Cooling 65 65 65
Sound Power Level
Heating 65 65 65
dB(A)
Cooling P-Hi:48 Hi:45 Me:41 Lo:37 P-Hi:48 Hi:45 Me:41 Lo:37 P-Hi:48 Hi:45 Me:41 Lo:37
Sound Pressure Level
Heating P-Hi:48 Hi:45 Me:41 Lo:37 P-Hi:48 Hi:45 Me:41 Lo:37 P-Hi:48 Hi:45 Me:41 Lo:37
Exterior dimensions Unit:325 × 1,535 × 620 Unit:325 × 1,535 × 620 Unit:325 × 1,535 × 620
mm
Height x Width x Depth Panel:20 × 1,835 × 680 Panel:20 × 1,835 × 680 Panel:20 × 1,835 × 680
Exterior appearance Plaster White Plaster White Plaster White
( Munsell color ) (6.8Y8.9/0.2 )near equivalent (6.8Y8.9/0.2)near equivalent (6.8Y8.9/0.2)near equivalent
Net weight kg Unit:35 Panel:13 Unit:35 Panel:13 Unit:35 Panel:13
Refrigerant equipment Heat exchanger Louver fin & inner grooved tubing Louver fin & inner grooved tubing Louver fin & inner grooved tubing
Refrigerant control Electronic Expansion Valve Electronic Expansion Valve Electronic Expansion Valve
Air handling equipment Fan type & Q'ty Turbo fan Turbo fan × 2 Turbo fan × 2
Fan motor <starting method> W 35 ×2 < Direct line start > 35 × 2 < Direct line start > 35 × 2 < Direct line start >
Cooling 3 P-Hi:31 Hi:27 Me:23 Lo:20 P-Hi:31 Hi:27 Me:23 Lo:20 P-Hi:31 Hi:27 Me:23 Lo:20
Air flow(Standard) m /min
Heating P-Hi:31 Hi:27 Me:23 Lo:20 P-Hi:31 Hi:27 Me:23 Lo:20 P-Hi:31 Hi:27 Me:23 Lo:20
Available static pressure Pa 0 0 0
Outdoor air intake Possible Possible Possible
-
Air filter, Q'ty Pocket plastic net ×3 (Washable) Pocket plastic net × 3 (Washable) Pocket plastic net × 3 (Washable)
Models FDTW90KXE6F, 112KXE6F, 140KXE6F
Shock & vibration absorber Rubber sleeve(for fan motor) Rubber sleeve(for fan motor) Rubber sleeve(for fan motor)
Insulation (noise & heat) Polyurethane form Polyurethane form Polyurethane form
6-
Operation control Wired : RC-EX3A,RC-E5 Wired : RC-EX3A,RC-E5 Wired : RC-EX3A,RC-E5
Remote control switch ( option ) Wireless : RCN-TW-E2 Wireless : RCN-TW-E2 Wireless : RCN-TW-E2
Room temperature control Thermostat by electronics Thermostat by electronics Thermostat by electronics
Overload protection for fan motor Overload protection for fan motor Overload protection for fan motor
Safety equipment
Frost protection thermostat Frost protection thermostat Frost protection thermostat
Installation data Liquid line φ9.52 (3/8") <Flare piping> φ9.52 (3/8") <Flare piping> φ9.52 (3/8”) <Flare piping>
Refrigerant piping size Gas line φ15.88 (5/8") <Flare piping> φ15.88 (5/8") <Flare piping> φ15.88 (5/8”) <Flare piping>
Refrigerant R410A R410A R410A
Drain pump Built-in Drain pump Built-in Drain pump Built-in Drain pump
Drain hose Connectable with VP25 (I.D.25,O.D.32) Connectable with VP25 (I.D.25,O.D.32) Connectable with VP25 (I.D.25,O.D.32)
Insulation for piping Necessary(both Liquid & Gas line) Necessary(both Liquid & Gas line) Necessary(both Liquid & Gas line)
Accessories Mounting kit, Drain hose Mounting kit, Drain hose Mounting kit, Drain hose
Exterior dimensions PJB001Z714 PJB001Z714 PJB001Z714
Electrical wiring PJB001Z831 PJB001Z831 PJB001Z831
Notes (1) The data are measured at the following conditions. OPTION Model Specification Adapted to RoHS directive
Item Indoor air temperature Outdoor air temperature Wired RC-EX3A PJZ000Z333
Standards
Operation DB WB DB WB Wired RC-E5 PJZ000Z295
Remote
Cooling*1 27℃ 19℃ 35℃ 24℃ control Wired RCH-E3 PJZ000Z272
ISO-T1
Heating*2 20℃ 7℃ 6℃
Wireless RCN-TW-E2 PJB001Z798
(2) This packaged air-conditioner is manufactured and tested in conformity with the standard.
ISO-T1 "UNITARY AIR-CONDITIONERS" Motion sensor LB-TW-6W PJB001Z818
(3) Sound level indicates the value in an anechoic chamber.
During operation these value are somewhat higher due to ambient conditions.
(4) Select the breaker size according to the own national standard.
PJB001Z829
'19 • KX-T-310D
Models FDTS45KXE6F FDTS71KXE6F
Panel model (Option) TS-PSA-3AW-E TS-PSA-3AW-E
Nominal cooling capacity*1 4.5 7.1
kW
Nominal heating capacity*2 5.0 8.0
Power source 1 Phase 220-240V 50Hz / 220V 60Hz 1 Phase 220-240V 50Hz / 220V 60Hz
Cooling 0.040 - 0.040 / 0.040 0.090 - 0.090 / 0.090
Power consumption kW
Heating 0.040 - 0.040 / 0.040 0.090 - 0.090 / 0.090
Cooling 0.27 - 0.25 / 0.27 0.60 - 0.55 / 0.60
Running current A
Heating 0.27 - 0.25 / 0.27 0.60 - 0.55 / 0.60
Cooling 60 61
Sound Power Level
Heating 60 61
dB(A)
Cooling P-Hi:42 Hi:40 Me:38 Lo:35 P-Hi:49 Hi:46 Me:41 Lo:36
Sound Pressure Level
Heating P-Hi:42 Hi:40 Me:38 Lo:35 P-Hi:49 Hi:46 Me:41 Lo:36
Exterior dimensions Unit:220 × 1,150 × 565 Unit:220 × 1,150 × 565
mm
Height x Width x Depth Panel:35 × 1,250 × 650 Panel:35 × 1,250 × 650
Exterior appearance Plaster White Plaster White
( Munsell color ) (6.8Y8.9/0.2)near equivalent (6.8Y8.9/0.2)near equivalent
Net weight kg Unit:27 Panel:5 Unit:28 Panel:5
Refrigerant equipment Heat exchanger Louver fin & inner grooved tubing Louver fin & inner grooved tubing
Refrigerant control Electronic Expansion Valve Electronic Expansion Valve
Air handling equipment Fan type & Q'ty Centrifugal fan ×4 Centrifugal fan ×4
Models FDTS45KXE6F, 71KXE6F
(4) Ceiling cassette-1 way type (FDTS)
Fan motor <starting method> W 35 < Direct line start > 70 < Direct line start >
Cooling 3 P-Hi:13 Hi:12 Me:11 Lo:9.5 P-Hi:17 Hi:15 Me:12 Lo:10
Air flow(Standard) m /min
Heating P-Hi:13 Hi:12 Me:11 Lo:9.5 P-Hi:17 Hi:15 Me:12 Lo:10
Available static pressure Pa 0 0
Outdoor air intake Possible Possible
-
Air filter, Q'ty Pocket plastic net ×2(Washable) Pocket plastic net ×2(Washable)
Shock & vibration absorber Rubber sleeve(for fan motor) Rubber sleeve(for fan motor)
Insulation (noise & heat) Polyurethane form Polyurethane form
7-
Operation control Wired : RC-EX3A,RC-E5 Wired : RC-EX3A,RC-E5
Remote control switch ( option ) Wireless : RCN-TS-E2 Wireless : RCN-TS-E2
Room temperature control Thermostat by electronics Thermostat by electronics
Overload protection for fan motor Overload protection for fan motor
Safety equipment
Frost protection thermostat Frost protection thermostat
Installation data Liquid line φ6.35 (1/4”) <Flare piping> φ9.52 (3/8”) <Flare piping>
Refrigerant piping size Gas line φ12.7 (1/2”) <Flare piping> φ15.88 (5/8”) <Flare piping>
Refrigerant R410A R410A
Drain hose Connectable with VP25 (I.D.25,O.D.32) Connectable with VP25 (I.D.25,O.D.32)
Insulation for piping Necessary(both Liquid & Gas line) Necessary(both Liquid & Gas line)
Accessories Mounting kit, Drain hose Mounting kit, Drain hose
Exterior dimensions PJC001Z352 PJC001Z352
Electrical wiring PJC001Z434 PJC001Z434
Notes (1) The data are measured at the following conditions. OPTION Model Specification Adapted to RoHS directive
Item Indoor air temperature Outdoor air temperature Wired RC-EX3A PJZ000Z333
Standards
Operation DB WB DB WB Remote Wired RC-E5 PJZ000Z295
Cooling*1 27℃ 19℃ 35℃ 24℃ control Wired RCH-E3 PJZ000Z272
ISO-T1
Heating*2 20℃ 7℃ 6℃
Wireless RCN-TS-E2 PJC001Z410
(2) This packaged air-conditioner is manufactured and tested in conformity with the standard.
ISO-T1 "UNITARY AIR-CONDITIONERS" Motion sensor LB-KIT PJZ000Z331
(3) Sound level indicates the value in an anechoic chamber.
During operation these value are somewhat higher due to ambient conditions.
(4) Select the breaker size according to the own national standard.
PJC001Z433
'19 • KX-T-310D
Models FDU45KXE6F FDU56KXE6F FDU71KXE6F FDU90KXE6F
Nominal cooling capacity*1 4.5 5.6 7.1 9.0
kW
Nominal heating capacity*2 5.0 6.3 8.0 10.0
Power source 1 Phase 220-240V 50Hz / 220V 60Hz 1 Phase 220-240V 50Hz / 220V 60Hz 1 Phase 220-240V 50Hz / 220V 60Hz 1 Phase 220-240V 50Hz / 220V 60Hz
Cooling 0.100 - 0.100 / 0.100 0.100 - 0.100 / 0.100 0.240 - 0.250 / 0.240 0.240 - 0.250 / 0.240
Power consumption kW
Heating 0.100 - 0.100 / 0.100 0.100 - 0.100 / 0.100 0.240 - 0.250 / 0.240 0.240 - 0.250 / 0.240
Cooling 0.63 - 0.58 / 0.63 0.63 - 0.58 / 0.63 1.80 - 1.70 / 1.80 1.80 - 1.70 / 1.80
Running current A
Heating 0.63 - 0.58 / 0.63 0.63 - 0.58 / 0.63 1.80 - 1.70 / 1.80 1.80 - 1.70 / 1.80
Cooling 60 60 65 65
Sound Power Level
Heating 60 60 65 65
dB(A)
Cooling P-Hi:37 Hi:32 Me:29 Lo:26 P-Hi:37 Hi:32 Me:29 Lo:26 P-Hi:38 Hi:33 Me:29 Lo:25 P-Hi:38 Hi:33 Me:29 Lo:25
Sound Pressure Level
Heating P-Hi:37 Hi:32 Me:29 Lo:26 P-Hi:37 Hi:32 Me:29 Lo:26 P-Hi:38 Hi:33 Me:29 Lo:25 P-Hi:38 Hi:33 Me:29 Lo:25
Exterior dimensions
mm 280 × 750 × 635 280 × 750 × 635 280 × 950 × 635 280 × 950 × 635
Height x Width x Depth
Net weight kg 29 29 34 34
Refrigerant equipment Heat exchanger Louver fin & inner grooved tubing Louver fin & inner grooved tubing Louver fin & inner grooved tubing Louver fin & inner grooved tubing
Refrigerant control Electronic Expansion Valve Electronic Expansion Valve Electronic Expansion Valve Electronic Expansion Valve
Air handling equipment Fan type & Q'ty Centrifugal fan ×1 Centrifugal fan ×1 Centrifugal fan ×2 Centrifugal fan ×2
Fan motor <starting method> W 100 < Direct line start > 100 < Direct line start > 130 < Direct line start > 130 < Direct line start >
Cooling 3 P-Hi:13 Hi:10 Me:9 Lo:8 P-Hi:13 Hi:10 Me:9 Lo:8 P-Hi:24 Hi:19 Me:15 Lo:10 P-Hi:24 Hi:19 Me:15 Lo:10
Air flow(Standard) m /min
Heating P-Hi:13 Hi:10 Me:9 Lo:8 P-Hi:13 Hi:10 Me:9 Lo:8 P-Hi:24 Hi:19 Me:15 Lo:10 P-Hi:24 Hi:19 Me:15 Lo:10
Available static pressure Pa 200 (at 13 m3/min) 200 (at 13 m3/min) 200 (at 24 m3/min) 200 (at 24 m3/min)
Outdoor air intake Possible Possible Possible Possible
Air filter, Q'ty Procure locally Procure locally Procure locally Procure locally
Shock & vibration absorber Rubber sleeve(for fan motor) Rubber sleeve(for fan motor) Rubber sleeve(for fan motor) Rubber sleeve(for fan motor)
Insulation (noise & heat) Polyurethane form Polyurethane form Polyurethane form Polyurethane form
-
Operation control Wired : RC-EX3A,RC-E5 Wired : RC-EX3A,RC-E5 Wired : RC-EX3A,RC-E5 Wired : RC-EX3A,RC-E5
(5) Duct connected-High static pressure type (FDU)
Remote control switch ( option ) Wireless : RCN-KIT4-E2 Wireless : RCN-KIT4-E2 Wireless : RCN-KIT4-E2 Wireless : RCN-KIT4-E2
Room temperature control Thermostat by electronics Thermostat by electronics Thermostat by electronics Thermostat by electronics
8-
Overload protection for fan motor Overload protection for fan motor Overload protection for fan motor Overload protection for fan motor
Safety equipment
Models FDU45KXE6F, 56KXE6F, 71KXE6F, 90KXE6F
Frost protection thermostat Frost protection thermostat Frost protection thermostat Frost protection thermostat
Installation data Liquid line φ6.35 (1/4”) <Flare piping> φ6.35 (1/4") <Flare piping> φ9.52 (3/8") <Flare piping> φ9.52 (3/8") <Flare piping>
Refrigerant piping size Gas line φ12.7 (1/2”) <Flare piping> φ12.7 (1/2") <Flare piping> φ15.88 (5/8") <Flare piping> φ15.88 (5/8") <Flare piping>
Refrigerant R410A R410A R410A R410A
Drain pump Built-in Drain pump Built-in Drain pump Built-in Drain pump Built-in Drain pump
Drain hose Connectable with VP25 (I.D.25,O.D.32) Connectable with VP25 (I.D.25,O.D.32) Connectable with VP25 (I.D.25,O.D.32) Connectable with VP25 (I.D.25,O.D.32)
Insulation for piping Necessary(both Liquid & Gas line) Necessary(both Liquid & Gas line) Necessary(both Liquid & Gas line) Necessary(both Liquid & Gas line)
Accessories Mounting kit, Drain hose Mounting kit, Drain hose Mounting kit, Drain hose Mounting kit, Drain hose
Exterior dimensions PJG000Z056 PJG000Z056 PJG000Z057 PJG000Z057
Electrical wiring PJG000Z539 PJG000Z539 PJG000Z540 PJG000Z540
Notes (1) The data are measured at the following conditions. OPTION Model Specification Adapted to RoHS directive
Item Indoor air temperature Outdoor air temperature External static pressure of Wired RC-EX3A PJZ000Z333
Standards
Operation DB WB DB WB indoor unit (Pa) Wired RC-E5 PJZ000Z295
Remote
Cooling*1 27℃ 19℃ 35℃ 24℃ control Wired RCH-E3 PJZ000Z272
ISO-T1 35
Heating*2 20℃ 7℃ 6℃
Wireless RCN-KIT4-E2 PJZ000Z323
(2) This packaged air-conditioner is manufactured and tested in conformity with the standard.
ISO-T1 "UNITARY AIR-CONDITIONERS" Motion sensor LB-KIT PJZ000Z331
(3) Sound level indicates the value in an anechoic chamber.
During operation these value are somewhat higher due to ambient conditions.
(4) The factory E.S.P. setting is set within the range of 80 - 150 Pa.If SW8-4 is turned to "ON",
E.S.P. setting range can be changed to 10 - 200 Pa.(For RC-EX3A and RC-E5 only)
(5) Select the breaker size according to the own national standard.
PJG000Z538
'19 • KX-T-310D
Models FDU112KXE6F FDU140KXE6F FDU160KXE6F
Nominal cooling capacity*1 11.2 14.0 16.0
kW
Nominal heating capacity*2 12.5 16.0 18.0
Power source 1 Phase 220-240V 50Hz / 220V 60Hz 1 Phase 220-240V 50Hz / 220V 60Hz 1 Phase 220-240V 50Hz / 220V 60Hz
Cooling 0.310 - 0.320 / 0.310 0.350 - 0.360 / 0.350 0.420 - 0.430 / 0.420
Power consumption kW
Heating 0.310 - 0.320 / 0.310 0.350 - 0.360 / 0.350 0.420 - 0.430 / 0.420
Cooling 2.00 - 2.00 / 2.00 2.30 - 2.20 / 2.30 2.70 - 2.50 / 2.70
Running current A
Heating 2.00 - 2.00 / 2.00 2.30 - 2.20 / 2.30 2.70 - 2.50 / 2.70
Cooling 71 72 74
Sound Power Level
Heating 71 72 74
dB(A)
Cooling P-Hi:44 Hi:38 Me:36 Lo:30 P-Hi:45 Hi:40 Me:34 Lo:29 P-Hi:47 Hi:40 Me:35 Lo:30
Sound Pressure Level
Heating P-Hi:44 Hi:38 Me:36 Lo:30 P-Hi:45 Hi:40 Me:34 Lo:29 P-Hi:47 Hi:40 Me:35 Lo:30
Exterior dimensions
mm 280 × 1,368 × 740 280 × 1,368 × 740 280 × 1,368 × 740
Height x Width x Depth
Net weight kg 54 54 54
Refrigerant equipment Heat exchanger Louver fin & inner grooved tubing Louver fin & inner grooved tubing Louver fin & inner grooved tubing
Refrigerant control Electronic Expansion Valve Electronic Expansion Valve Electronic Expansion Valve
Air handling equipment Fan type & Q'ty Centrifugal fan ×3 Centrifugal fan ×3 Centrifugal fan ×3
Fan motor <starting method> W 100 + 130 < Direct line start > 100 + 200 < Direct line start > 100 + 200 < Direct line start >
Cooling 3 P-Hi:36 Hi:28 Me:25 Lo:19 P-Hi:39 Hi:32 Me:26 Lo:20 P-Hi:48 Hi:35 Me:28 Lo:22
Air flow(Standard) m /min
Heating P-Hi:36 Hi:28 Me:25 Lo:19 P-Hi:39 Hi:32 Me:26 Lo:20 P-Hi:48 Hi:35 Me:28 Lo:22
Available static pressure Pa 200 (at 36 m3/min) 200 (at 39 m3/min) 200 (at 48 m3/min)
Outdoor air intake Possible Possible Possible
Air filter, Q'ty Procure locally Procure locally Procure locally
Shock & vibration absorber Rubber sleeve(for fan motor) Rubber sleeve(for fan motor) Rubber sleeve(for fan motor)
Insulation (noise & heat) Polyurethane form Polyurethane form Polyurethane form
-
Models FDU112KXE6F, 140KXE6F, 160KXE6F
9-
Overload protection for fan motor Overload protection for fan motor Overload protection for fan motor
Safety equipment
Frost protection thermostat Frost protection thermostat Frost protection thermostat
Installation data Liquid line φ9.52 (3/8”) <Flare piping> φ9.52 (3/8”) <Flare piping> φ9.52 (3/8") <Flare piping>
Refrigerant piping size Gas line φ15.88 (5/8”) <Flare piping> φ15.88 (5/8”) <Flare piping> φ15.88 (5/8") <Flare piping>
Refrigerant R410A R410A R410A
Drain pump Built-in Drain pump Built-in Drain pump Built-in Drain pump
Drain hose Connectable with VP25 (I.D.25,O.D.32) Connectable with VP25 (I.D.25,O.D.32) Connectable with VP25 (I.D.25,O.D.32)
Insulation for piping Necessary(both Liquid & Gas line) Necessary(both Liquid & Gas line) Necessary(both Liquid & Gas line)
Accessories Mounting kit, Drain hose Mounting kit, Drain hose Mounting kit, Drain hose
Exterior dimensions PJG000Z058 PJG000Z058 PJG000Z058
Electrical wiring PJG000Z541 PJG000Z541 PJG000Z541
Notes (1) The data are measured at the following conditions. OPTION Model Specification Adapted to RoHS directive
Item Indoor air temperature Outdoor air temperature External static pressure of Wired RC-EX3A PJZ000Z333
Standards
Operation DB WB DB WB indoor unit (Pa) Wired RC-E5 PJZ000Z295
Remote
Cooling*1 27℃ 19℃ 35℃ 24℃ control Wired RCH-E3 PJZ000Z272
ISO-T1 60
Heating*2 20℃ 7℃ 6℃
Wireless RCN-KIT4-E2 PJZ000Z323
(2) This packaged air-conditioner is manufactured and tested in conformity with the standard.
ISO-T1 "UNITARY AIR-CONDITIONERS" Motion sensor LB-KIT PJZ000Z331
(3) Sound level indicates the value in an anechoic chamber.
During operation these value are somewhat higher due to ambient conditions.
(4) The factory E.S.P. setting is set within the range of 80 - 150 Pa.If SW8-4 is turned to "ON",
E.S.P. setting range can be changed to 10 - 200 Pa.(For RC-EX3A and RC-E5 only)
(5) Select the breaker size according to the own national standard.
PJG000Z538
'19 • KX-T-310D
Models FDU224KXZE1 FDU280KXZE1
Nominal cooling capacity*1 22.4 28.0
kW
Nominal heating capacity*2 25.0 31.5
Power source 1 Phase 220-240V 50Hz / 220V 60Hz 1 Phase 220-240V 50Hz / 220V 60Hz
Cooling 1.160 - 1.200 / 1.160 1.160 - 1.200 / 1.160
Power consumption kW
Heating 1.160 - 1.200 / 1.160 1.160 - 1.200 / 1.160
Cooling 6.80 - 6.50 / 6.80 6.80 - 6.50 / 6.80
Running current A
Heating 6.80 - 6.50 / 6.80 6.80 - 6.50 / 6.80
Cooling 75 75
Sound Power Level
Heating 75 75
dB(A)
Cooling P-Hi:52 Hi:50 Me:47 Lo:45 P-Hi:52 Hi:50 Me:47 Lo:45
Sound Pressure Level
Heating P-Hi:52 Hi:50 Me:47 Lo:45 P-Hi:52 Hi:50 Me:47 Lo:45
Exterior dimensions
mm 379 × 1,600 × 893 379 × 1,600 × 893
Height x Width x Depth
Net weight kg 89 89
Refrigerant equipment Heat exchanger Louver fin & inner grooved tubing Louver fin & inner grooved tubing
Refrigerant control Electronic Expansion Valve Electronic Expansion Valve
Air handling equipment Fan type & Q'ty Centrifugal fan ×3 Centrifugal fan ×3
Fan motor <starting method> W 130 + 350 < Direct line start > 130 + 350 < Direct line start >
Cooling 3 P-Hi:80 Hi:72 Me:64 Lo:56 P-Hi:80 Hi:72 Me:64 Lo:56
Air flow(Standard) m /min
Heating P-Hi:80 Hi:72 Me:64 Lo:56 P-Hi:80 Hi:72 Me:64 Lo:56
Models FDU224KXZE1, 280KXZE1
-
Operation control Wired : RC-EX3A,RC-E5 Wired : RC-EX3A,RC-E5
Remote control switch ( option ) Wireless : RCN-KIT4-E2 Wireless : RCN-KIT4-E2
Room temperature control Thermostat by electronics Thermostat by electronics
10 -
Overload protection for fan motor Overload protection for fan motor
Safety equipment
Frost protection thermostat Frost protection thermostat
Installation data Liquid line φ9.52 (3/8”) <Brazing> φ9.52 (3/8”) <Brazing>
Refrigerant piping size Gas line φ19.05 (3/4”) <Brazing> φ22.22 (7/8”) <Brazing>
Refrigerant R410A R410A
Drain pump - -
Drain hose Connectable with VP25(O.D.32) Connectable with VP25(O.D.32)
Insulation for piping Necessary(both Liquid & Gas line) Necessary(both Liquid & Gas line)
Accessories Mounting kit Mounting kit
Exterior dimensions PJG000Z287 PJG000Z287
Electrical wiring PJG000Z543 PJG000Z543
Notes (1) The data are measured at the following conditions. OPTION Model Specification Adapted to RoHS directive
Item Indoor air temperature Outdoor air temperature External static pressure of Wired RC-EX3A PJZ000Z333
Standards
Operation DB WB DB WB indoor unit (Pa) Wired RC-E5 PJZ000Z295
Remote
Cooling*1 27℃ 19℃ 35℃ 24℃ control Wired RCH-E3 PJZ000Z272
ISO-T1 72
Heating*2 20℃ 7℃ 6℃
Wireless RCN-KIT4-E2 PJZ000Z323
(2) This packaged air-conditioner is manufactured and tested in conformity with the standard.
ISO-T1 "UNITARY AIR-CONDITIONERS" Motion sensor LB-KIT PJZ000Z331
(3) Sound level indicates the value in an anechoic chamber.
During operation these value are somewhat higher due to ambient conditions.
(4) The factory E.S.P. setting is set within the range of 80 - 150 Pa.If SW8-4 is turned to "ON",
E.S.P. setting range can be changed to 10 - 200 Pa.(For RC-EX3A and RC-E5 only)
(5) Select the breaker size according to the own national standard.
PJG000Z542
'19 • KX-T-310D
Models FDUM22KXE6F FDUM28KXE6F FDUM36KXE6F FDUM45KXE6F FDUM56KXE6F
Nominal cooling capacity*1 2.2 2.8 3.6 4.5 5.6
kW
Nominal heating capacity*2 2.5 3.2 4.0 5.0 6.3
Power source 1 Phase 220-240V 50Hz / 220V 60Hz 1 Phase 220-240V 50Hz / 220V 60Hz 1 Phase 220-240V 50Hz / 220V 60Hz 1 Phase 220-240V 50Hz / 220V 60Hz 1 Phase 220-240V 50Hz / 220V 60Hz
Cooling 0.100 - 0.100 / 0.100 0.100 - 0.100 / 0.100 0.100 - 0.100 / 0.100 0.100 - 0.100 / 0.100 0.100 - 0.100 / 0.100
Power consumption kW
Heating 0.100 - 0.100 / 0.100 0.100 - 0.100 / 0.100 0.100 - 0.100 / 0.100 0.100 - 0.100 / 0.100 0.100 - 0.100 / 0.100
Cooling 0.46 - 0.42 / 0.46 0.46 - 0.42 / 0.46 0.46 - 0.42 / 0.46 0.46 - 0.42 / 0.46 0.46 - 0.42 / 0.46
Running current A
Heating 0.46 - 0.42 / 0.46 0.46 - 0.42 / 0.46 0.46 - 0.42 / 0.46 0.46 - 0.42 / 0.46 0.46 - 0.42 / 0.46
Cooling 60 60 60 60 60
Sound Power Level
Heating 60 60 60 60 60
dB(A)
Cooling P-Hi:37 Hi:32 Me:29 Lo:26 P-Hi:37 Hi:32 Me:29 Lo:26 P-Hi:37 Hi:32 Me:29 Lo:26 P-Hi:37 Hi:32 Me:29 Lo:26 P-Hi:37 Hi:32 Me:29 Lo:26
Sound Pressure Level
Heating P-Hi:37 Hi:32 Me:29 Lo:26 P-Hi:37 Hi:32 Me:29 Lo:26 P-Hi:37 Hi:32 Me:29 Lo:26 P-Hi:37 Hi:32 Me:29 Lo:26 P-Hi:37 Hi:32 Me:29 Lo:26
Exterior dimensions
mm 280 × 750 × 635 280 × 750 × 635 280 × 750 × 635 280 × 750 × 635 280 × 750 × 635
Height x Width x Depth
Net weight kg 29 29 29 29 29
Refrigerant equipment Heat exchanger Louver fin & inner grooved tubing Louver fin & inner grooved tubing Louver fin & inner grooved tubing Louver fin & inner grooved tubing Louver fin & inner grooved tubing
Refrigerant control Electronic Expansion Valve Electronic Expansion Valve Electronic Expansion Valve Electronic Expansion Valve Electronic Expansion Valve
Air handling equipment Fan type & Q'ty Centrifugal fan ×1 Centrifugal fan ×1 Centrifugal fan ×1 Centrifugal fan ×1 Centrifugal fan ×1
Fan motor <starting method> W 100 < Direct line start > 100 < Direct line start > 100 < Direct line start > 100 < Direct line start > 100 < Direct line start >
Cooling 3 P-Hi:13 Hi:10 Me:9 Lo:8 P-Hi:13 Hi:10 Me:9 Lo:8 P-Hi:13 Hi:10 Me:9 Lo:8 P-Hi:13 Hi:10 Me:9 Lo:8 P-Hi:13 Hi:10 Me:9 Lo:8
Air flow(Standard) m /min
Heating P-Hi:13 Hi:10 Me:9 Lo:8 P-Hi:13 Hi:10 Me:9 Lo:8 P-Hi:13 Hi:10 Me:9 Lo:8 P-Hi:13 Hi:10 Me:9 Lo:8 P-Hi:13 Hi:10 Me:9 Lo:8
Available static pressure Pa 100 (at 13 m3/min) 100 (at 13 m3/min) 100 (at 13 m3/min) 100 (at 13 m3/min) 100 (at 13 m3/min)
Outdoor air intake Possible Possible Possible Possible Possible
Air filter, Q'ty Procure locally Procure locally Procure locally Procure locally Procure locally
Shock & vibration absorber Rubber sleeve(for fan motor) Rubber sleeve(for fan motor) Rubber sleeve(for fan motor) Rubber sleeve(for fan motor) Rubber sleeve(for fan motor)
Insulation (noise & heat) Polyurethane form Polyurethane form Polyurethane form Polyurethane form Polyurethane form
-
Operation control Wired : RC-EX3A,RC-E5 Wired : RC-EX3A,RC-E5 Wired : RC-EX3A,RC-E5 Wired : RC-EX3A,RC-E5 Wired : RC-EX3A,RC-E5
Remote control switch ( option ) Wireless : RCN-KIT4-E2 Wireless : RCN-KIT4-E2 Wireless : RCN-KIT4-E2 Wireless : RCN-KIT4-E2 Wireless : RCN-KIT4-E2
Room temperature control Thermostat by electronics Thermostat by electronics Thermostat by electronics Thermostat by electronics Thermostat by electronics
11 -
Overload protection for fan motor Overload protection for fan motor Overload protection for fan motor Overload protection for fan motor Overload protection for fan motor
Safety equipment
Frost protection thermostat Frost protection thermostat Frost protection thermostat Frost protection thermostat Frost protection thermostat
Installation data Liquid line φ6.35 (1/4") <Flare piping> φ6.35 (1/4") <Flare piping> φ6.35 (1/4") <Flare piping> φ6.35 (1/4") <Flare piping> φ6.35 (1/4") <Flare piping>
(6) Duct connected Low/Middle static pressure type (FDUM)
Refrigerant piping size Gas line φ9.52 (3/8") <Flare piping> φ9.52 (3/8") <Flare piping> φ12.7 (1/2") <Flare piping> φ12.7 (1/2") <Flare piping> φ12.7 (1/2") <Flare piping>
Refrigerant R410A R410A R410A R410A R410A
Drain pump Built-in Drain pump Built-in Drain pump Built-in Drain pump Built-in Drain pump Built-in Drain pump
Drain hose Connectable with VP25 (I.D.25,O.D.32) Connectable with VP25 (I.D.25,O.D.32) Connectable with VP25 (I.D.25,O.D.32) Connectable with VP25 (I.D.25,O.D.32) Connectable with VP25 (I.D.25,O.D.32)
Models FDUM22KXE6F, 28KXE6F, 36KXE6F, 45KXE6F, 56KXE6F
Insulation for piping Necessary(both Liquid & Gas line) Necessary(both Liquid & Gas line) Necessary(both Liquid & Gas line) Necessary(both Liquid & Gas line) Necessary(both Liquid & Gas line)
Accessories Mounting kit, Drain hose Mounting kit, Drain hose Mounting kit, Drain hose Mounting kit, Drain hose Mounting kit, Drain hose
Exterior dimensions PJG000Z016 PJG000Z016 PJG000Z016 PJG000Z016 PJG000Z016
Electrical wiring PJG000Z526 PJG000Z526 PJG000Z526 PJG000Z526 PJG000Z526
Notes (1) The data are measured at the following conditions. OPTION Model Specification Adapted to RoHS directive
Item Indoor air temperature Outdoor air temperature External static pressure of Wired RC-EX3A PJZ000Z333
Standards
Operation DB WB DB WB indoor unit (Pa) Wired RC-E5 PJZ000Z295
Remote
Cooling*1 27℃ 19℃ 35℃ 24℃ control Wired RCH-E3 PJZ000Z272
ISO-T1 35
Heating*2 20℃ 7℃ 6℃
Wireless RCN-KIT4-E2 PJZ000Z323
(2) This packaged air-conditioner is manufactured and tested in conformity with the standard.
ISO-T1 "UNITARY AIR-CONDITIONERS" Motion sensor LB-KIT PJZ000Z331
(3) Sound level indicates the value in an anechoic chamber. Air filter (For 22-56) UM-FL1EF -
During operation these value are somewhat higher due to ambient conditions.
(4) Initial static pressure values of optional air filter "UM-FL□EF" are 5Pa.
(5) Select the breaker size according to the own national standard.
PJG000Z525
'19 • KX-T-310D
Models FDUM71KXE6F FDUM90KXE6F FDUM112KXE6F FDUM140KXE6F FDUM160KXE6F
Nominal cooling capacity*1 7.1 9.0 11.2 14.0 16.0
kW
Nominal heating capacity*2 8.0 10.0 12.5 16.0 18.0
Power source 1 Phase 220-240V 50Hz / 220V 60Hz 1 Phase 220-240V 50Hz / 220V 60Hz 1 Phase 220-240V 50Hz / 220V 60Hz 1 Phase 220-240V 50Hz / 220V 60Hz 1 Phase 220-240V 50Hz / 220V 60Hz
Cooling 0.200 - 0.200 / 0.200 0.200 - 0.200 / 0.200 0.290 - 0.290 / 0.290 0.330 - 0.330 / 0.330 0.450 - 0.450 / 0.450
Power consumption kW
Heating 0.200 - 0.200 / 0.200 0.200 - 0.200 / 0.200 0.290 - 0.290 / 0.290 0.330 - 0.330 / 0.330 0.450 - 0.450 / 0.450
Cooling 0.91 - 0.83 / 0.91 0.91 - 0.83 / 0.91 1.32 - 1.21 / 1.32 1.50 - 1.38 / 1.50 2.05 - 1.88 / 2.05
Running current A
Heating 0.91 - 0.83 / 0.91 0.91 - 0.83 / 0.91 1.32 - 1.21 / 1.32 1.50 - 1.38 / 1.50 2.05 - 1.88 / 2.05
Cooling 65 65 71 72 74
Sound Power Level
Heating 65 65 71 72 74
dB(A)
Cooling P-Hi:38 Hi:33 Me:29 Lo:25 P-Hi:38 Hi:33 Me:29 Lo:25 P-Hi:44 Hi:38 Me:36 Lo:30 P-Hi:45 Hi:40 Me:34 Lo:29 P-Hi:47 Hi:40 Me:35 Lo:30
Sound Pressure Level
Heating P-Hi:38 Hi:33 Me:29 Lo:25 P-Hi:38 Hi:33 Me:29 Lo:25 P-Hi:44 Hi:38 Me:36 Lo:30 P-Hi:45 Hi:40 Me:34 Lo:29 P-Hi:47 Hi:40 Me:35 Lo:30
Exterior dimensions
mm 280 × 950 × 635 280 × 950 × 635 280 × 1,368 × 740 280 × 1,368 × 740 280 × 1,368 × 740
Height x Width x Depth
Net weight kg 34 34 54 54 54
Refrigerant equipment Heat exchanger Louver fin & inner grooved tubing Louver fin & inner grooved tubing Louver fin & inner grooved tubing Louver fin & inner grooved tubing Louver fin & inner grooved tubing
Refrigerant control Electronic Expansion Valve Electronic Expansion Valve Electronic Expansion Valve Electronic Expansion Valve Electronic Expansion Valve
Air handling equipment Fan type & Q'ty Centrifugal fan ×2 Centrifugal fan ×2 Centrifugal fan ×3 Centrifugal fan ×3 Centrifugal fan ×3
Fan motor <starting method> W 130 < Direct line start > 130 < Direct line start > 100 + 130 < Direct line start > 100 + 200 < Direct line start > 100 + 200 < Direct line start >
Cooling 3 P-Hi:24 Hi:19 Me:15 Lo:10 P-Hi:24 Hi:19 Me:15 Lo:10 P-Hi:36 Hi:28 Me:25 Lo:19 P-Hi:39 Hi:32 Me:26 Lo:20 P-Hi:48 Hi:35 Me:28 Lo:22
Air flow(Standard) m /min
Heating P-Hi:24 Hi:19 Me:15 Lo:10 P-Hi:24 Hi:19 Me:15 Lo:10 P-Hi:36 Hi:28 Me:25 Lo:19 P-Hi:39 Hi:32 Me:26 Lo:20 P-Hi:48 Hi:35 Me:28 Lo:22
Available static pressure Pa 100 (at 24 m3/min) 100 (at 24 m3/min) 100 (at 36 m3/min) 100 (at 39 m3/min) 100 (at 48 m3/min)
Outdoor air intake Possible Possible Possible Possible Possible
Air filter, Q'ty Procure locally Procure locally Procure locally Procure locally Procure locally
Shock & vibration absorber Rubber sleeve(for fan motor) Rubber sleeve(for fan motor) Rubber sleeve(for fan motor) Rubber sleeve(for fan motor) Rubber sleeve(for fan motor)
Insulation (noise & heat) Polyurethane form Polyurethane form Polyurethane form Polyurethane form Polyurethane form
-
Operation control Wired : RC-EX3A,RC-E5 Wired : RC-EX3A,RC-E5 Wired : RC-EX3A,RC-E5 Wired : RC-EX3A,RC-E5 Wired : RC-EX3A,RC-E5
Remote control switch ( option ) Wireless : RCN-KIT4-E2 Wireless : RCN-KIT4-E2 Wireless : RCN-KIT4-E2 Wireless : RCN-KIT4-E2 Wireless : RCN-KIT4-E2
Room temperature control Thermostat by electronics Thermostat by electronics Thermostat by electronics Thermostat by electronics Thermostat by electronics
12 -
Overload protection for fan motor Overload protection for fan motor Overload protection for fan motor Overload protection for fan motor Overload protection for fan motor
Safety equipment
Frost protection thermostat Frost protection thermostat Frost protection thermostat Frost protection thermostat Frost protection thermostat
Installation data Liquid line φ9.52 (3/8") <Flare piping> φ9.52 (3/8") <Flare piping> φ9.52 (3/8") <Flare piping> φ9.52 (3/8") <Flare piping> φ9.52 (3/8") <Flare piping>
Refrigerant piping size Gas line φ15.88 (5/8") <Flare piping> φ15.88 (5/8") <Flare piping> φ15.88 (5/8") <Flare piping> φ15.88 (5/8") <Flare piping> φ15.88 (5/8") <Flare piping>
Refrigerant R410A R410A R410A R410A R410A
Drain pump Built-in Drain pump Built-in Drain pump Built-in Drain pump Built-in Drain pump Built-in Drain pump
Drain hose Connectable with VP25 (I.D.25,O.D.32) Connectable with VP25 (I.D.25,O.D.32) Connectable with VP25 (I.D.25,O.D.32) Connectable with VP25 (I.D.25,O.D.32) Connectable with VP25 (I.D.25,O.D.32)
Insulation for piping Necessary(both Liquid & Gas line) Necessary(both Liquid & Gas line) Necessary(both Liquid & Gas line) Necessary(both Liquid & Gas line) Necessary(both Liquid & Gas line)
Accessories Mounting kit, Drain hose Mounting kit, Drain hose Mounting kit, Drain hose Mounting kit, Drain hose Mounting kit, Drain hose
Models FDUM71KXE6F, 90KXE6F, 112KXE6F, 140KXE6F, 160KXE6F
PJG000Z525
'19 • KX-T-310D
Models FDUT71KXE6F-E
Panel model (Option) Rear air return
Nominal cooling capacity*1 7.1
kW
Nominal heating capacity*2 8.0
Power source 1 Phase 220-240V 50Hz / 220V 60Hz
Cooling 0.080 - 0.080 / 0.080
Power consumption kW
Heating 0.070 - 0.070 / 0.070
Cooling 0.42 - 0.42 / 0.42
Running current A
Heating 0.46 - 0.46 / 0.46
Sound Power Level Hi:59
Sound Pressure Level ① dB(A) Hi:35 Me:31 Lo:28
Sound Pressure Level ② Hi:41 Me:37 Lo:32
Exterior dimensions
mm 220 × 1,150 × 565
Height x Width x Depth
Net weight kg 31
Refrigerant equipment Heat exchanger Louver fin & inner grooved tubing
Model FDUT71KXE6F-E
-
Operation control Wired : RC-EX3A,RC-E5
Remote control switch ( option ) Wireless : RCN-KIT4-E2
Room temperature control Thermostat by electronics
13 -
Overload protection for fan motor
Safety equipment
Frost protection thermostat
(7) Duct connected (thin) -Low static pressure type (FDUT)
PJH000Z022
'19 • KX-T-310D
Models FDK15KXZE1 FDK22KXZE1 FDK28KXZE1 FDK36KXZE1 FDK45KXZE1
Nominal cooling capacity*1 1.5 2.2 2.8 3.6 4.5
kW
Nominal heating capacity*2 1.7 2.5 3.2 4.0 5.0
Power source 1 Phase 220-240V 50Hz / 220V 60Hz 1 Phase 220-240V 50Hz / 220V 60Hz 1 Phase 220-240V 50Hz / 220V 60Hz 1 Phase 220-240V 50Hz / 220V 60Hz 1 Phase 220-240V 50Hz / 220V 60Hz
Cooling 0.020 - 0.020 / 0.020 0.020 - 0.020 / 0.020 0.020 - 0.020 / 0.020 0.030 - 0.030 / 0.030 0.030 - 0.030 / 0.030
Power consumption kW
Heating 0.020 - 0.020 / 0.020 0.020 - 0.020 / 0.020 0.020 - 0.020 / 0.020 0.030 - 0.030 / 0.030 0.030 - 0.030 / 0.030
Cooling 0.18 - 0.16 / 0.18 0.18 - 0.16 / 0.18 0.18 - 0.16 / 0.18 0.27 - 0.25 / 0.27 0.27 - 0.25 / 0.27
Running current A
Heating 0.18 - 0.16 / 0.18 0.18 - 0.16 / 0.18 0.18 - 0.16 / 0.18 0.27 - 0.25 / 0.27 0.27 - 0.25 / 0.27
Cooling 54 55 55 58 58
Sound Power Level
Heating 54 55 55 58 58
dB(A)
Cooling P-Hi:38 Hi:34 Me:31 Lo:28 P-Hi:38 Hi:36 Me:32 Lo:28 P-Hi:38 Hi:36 Me:32 Lo:28 P-Hi:40 Hi:38 Me:33 Lo:28 P-Hi:43 Hi:41 Me:36 Lo:33
Sound Pressure Level
Heating P-Hi:38 Hi:34 Me:31 Lo:28 P-Hi:38 Hi:36 Me:32 Lo:28 P-Hi:38 Hi:36 Me:32 Lo:28 P-Hi:40 Hi:38 Me:33 Lo:28 P-Hi:43 Hi:41 Me:36 Lo:33
Exterior dimensions
mm 290 × 870 × 230 290 × 870 × 230 290 × 870 × 230 290 × 870 × 230 290 × 870 × 230
Height x Width x Depth
Exterior appearance Fine Snow Fine Snow Fine Snow Fine Snow Fine Snow
(Munsell color) ( 9.3G8.7/0.1 )near equivalent ( 9.3G8.7/0.1 )near equivalent ( 9.3G8.7/0.1 )near equivalent ( 9.3G8.7/0.1 )near equivalent ( 9.3G8.7/0.1 )near equivalent
(8) Wall mounted type (FDK)
-
Shock & vibration absorber Rubber sleeve(for fan motor) Rubber sleeve(for fan motor) Rubber sleeve(for fan motor) Rubber sleeve(for fan motor) Rubber sleeve(for fan motor)
Insulation (noise & heat) Polyurethane form Polyurethane form Polyurethane form Polyurethane form Polyurethane form
Operation control Wired : RC-EX3A Wired : RC-EX3A Wired : RC-EX3A Wired : RC-EX3A Wired : RC-EX3A
14 -
Remote control switch ( option ) Wireless : RCN-K-E2 Wireless : RCN-K-E2 Wireless : RCN-K-E2 Wireless : RCN-K-E2 Wireless : RCN-K-E2
Room temperature control Thermostat by electronics Thermostat by electronics Thermostat by electronics Thermostat by electronics Thermostat by electronics
Overload protection for fan motor Overload protection for fan motor Overload protection for fan motor Overload protection for fan motor Overload protection for fan motor
Safety equipment
Frost protection thermostat Frost protection thermostat Frost protection thermostat Frost protection thermostat Frost protection thermostat
Installation data Liquid line φ6.35 (1/4") <Flare piping> φ6.35 (1/4") <Flare piping> φ6.35 (1/4") <Flare piping> φ6.35 (1/4") <Flare piping> φ6.35 (1/4") <Flare piping>
Refrigerant piping size Gas line φ9.52 (3/8") <Flare piping> φ9.52 (3/8") <Flare piping> φ9.52 (3/8") <Flare piping> φ12.7 (1/2") <Flare piping> φ12.7 (1/2") <Flare piping>
Refrigerant R410A R410A R410A R410A R410A
Models FDK15KXZE1, 22KXZE1, 28KXZE1, 36KXZE1, 45KXZE1
Drain hose Connectable with VP16(I.D.16) Connectable with VP16(I.D.16) Connectable with VP16(I.D.16) Connectable with VP16(I.D.16) Connectable with VP16(I.D.16)
Insulation for piping Necessary(both Liquid & Gas line) Necessary(both Liquid & Gas line) Necessary(both Liquid & Gas line) Necessary(both Liquid & Gas line) Necessary(both Liquid & Gas line)
Accessories Mounting kit, Drain hose Mounting kit, Drain hose Mounting kit, Drain hose Mounting kit, Drain hose Mounting kit, Drain hose
Exterior dimensions PHA001Z105 PHA001Z105 PHA001Z105 PHA001Z105 PHA001Z105
Electrical wiring PHA001Z142 PHA001Z142 PHA001Z142 PHA001Z142 PHA001Z142
Notes (1) The data are measured at the following conditions. OPTION Model Specification Adapted to RoHS directive
Item Indoor air temperature Outdoor air temperature Wired RC-EX3A PJZ000Z333
Standards Remote
Operation DB WB DB WB Wired RC-E5 PJZ000Z295
control
Cooling*1 27℃ 19℃ 35℃ 24℃ Wired RCH-E3 PJZ000Z272
ISO-T1
Heating*2 20℃ 7℃ 6℃ Wireless FDK15-56 RCN-K-E2 PHA001Z123
(2) This packaged air-conditioner is manufactured and tested in conformity with the standard. Wireless FDK71-90 RCN-K71-E2 PHA001Z124
ISO-T1 "UNITARY AIR-CONDITIONERS" Motion sensor LB-KIT PJZ000Z331
(3) Sound level indicates the value in an anechoic chamber.
During operation these value are somewhat higher due to ambient conditions.
(4) Select the breaker size according to the own national standard.
PHA001Z141
'19 • KX-T-310D
Models FDK56KXZE1 FDK71KXZE1 FDK90KXZE1
Nominal cooling capacity*1 5.6 7.1 9.0
kW
Nominal heating capacity*2 6.3 8.0 10.0
Power source 1 Phase 220-240V 50Hz / 220V 60Hz 1 Phase 220-240V 50Hz / 220V 60Hz 1 Phase 220-240V 50Hz / 220V 60Hz
Cooling 0.030 - 0.030 / 0.030 0.040 - 0.040 / 0.040 0.050 - 0.050 / 0.050
Power consumption kW
Heating 0.030 - 0.030 / 0.030 0.040 - 0.040 / 0.040 0.050 - 0.050 / 0.050
Cooling 0.27 - 0.25 / 0.27 0.34 - 0.31 / 0.34 0.42 - 0.39 / 0.42
Running current A
Heating 0.27 - 0.25 / 0.27 0.34 - 0.31 / 0.34 0.42 - 0.39 / 0.42
Cooling 58 59 61
Sound Power Level
Heating 61 59 61
dB(A)
Cooling P-Hi:43 Hi:41 Me:36 Lo:33 P-Hi:42 Hi:40 Me:37 Lo:35 P-Hi:44 Hi:42 Me:39 Lo:35
Sound Pressure Level
Heating P-Hi:44 Hi:42 Me:37 Lo:33 P-Hi:42 Hi:40 Me:37 Lo:35 P-Hi:44 Hi:42 Me:39 Lo:35
Exterior dimensions
mm 290 × 870 × 230 339 × 1,197 × 262 339 × 1,197 × 262
Height x Width x Depth
Exterior appearance Fine Snow Fine Snow Fine Snow
(Munsell color) ( 9.3G8.7/0.1 )near equivalent ( 9.3G8.7/0.1 )near equivalent ( 9.3G8.7/0.1 )near equivalent
Net weight kg 11.5 17 17
Refrigerant equipment Heat exchanger Louver fin & inner grooved tubing Louver fin & inner grooved tubing Louver fin & inner grooved tubing
Refrigerant control Electronic Expansion Valve Electronic Expansion Valve Electronic Expansion Valve
Air handling equipment Fan type & Q'ty Tangential fan ×1 Tangential fan ×1 Tangential fan ×1
Fan motor <starting method> W 42 < Direct line start > 56 < Direct line start > 56 < Direct line start >
Cooling 3 P-Hi:12 Hi:11 Me:9 Lo:8 P-Hi:21 Hi:19 Me:16 Lo:14 P-Hi:23 Hi:21 Me:19 Lo:16
Air flow(Standard) m /min
Heating P-Hi:13 Hi:12 Me:10 Lo:8 P-Hi:21 Hi:19 Me:16 Lo:14 P-Hi:23 Hi:21 Me:19 Lo:16
Available static pressure Pa 0 0 0
Outdoor air intake Not Possible Not Possible Not Possible
Models FDK56KXZE1, 71KXZE1, 90KXZE1
Air filter, Q'ty Polypropylene net ×2 (Washable) Polypropylene net ×2 (Washable) Polypropylene net ×2 (Washable)
-
Shock & vibration absorber Rubber sleeve(for fan motor) Rubber sleeve(for fan motor) Rubber sleeve(for fan motor)
Insulation (noise & heat) Polyurethane form Polyurethane form Polyurethane form
Operation control Wired : RC-EX3A Wired : RC-EX3A Wired : RC-EX3A
15 -
Remote control switch ( option ) Wireless : RCN-K-E2 Wireless : RCN-K71-E2 Wireless : RCN-K71-E2
Room temperature control Thermostat by electronics Thermostat by electronics Thermostat by electronics
Overload protection for fan motor Overload protection for fan motor Overload protection for fan motor
Safety equipment
Frost protection thermostat Frost protection thermostat Frost protection thermostat
Installation data Liquid line φ6.35 (1/4") <Flare piping> φ9.52 (3/8") <Flare piping> φ9.52 (3/8") < Flare piping >
Refrigerant piping size Gas line φ12.7 (1/2") <Flare piping> φ15.88 (5/8") <Flare piping> φ15.88 (5/8") < Flare piping >
Refrigerant R410A R410A R410A
Drain hose Connectable with VP16(I.D.16) Connectable with VP16(I.D.16) Connectable with VP16(I.D.16)
Insulation for piping Necessary(both Liquid & Gas line) Necessary(both Liquid & Gas line) Necessary(both Liquid & Gas line)
Accessories Mounting kit, Drain hose Mounting kit, Drain hose Mounting kit, Drain hose
Exterior dimensions PHA001Z105 PHA001Z106 PHA001Z106
Electrical wiring PHA001Z142 PHA001Z142 PHA001Z142
Notes (1) The data are measured at the following conditions. OPTION Model Specification Adapted to RoHS directive
Item Indoor air temperature Outdoor air temperature Wired RC-EX3A PJZ000Z333
Standards Remote
Operation DB WB DB WB Wired RC-E5 PJZ000Z295
control
Cooling*1 27℃ 19℃ 35℃ 24℃ Wired RCH-E3 PJZ000Z272
ISO-T1
Heating*2 20℃ 7℃ 6℃ Wireless FDK15-56 RCN-K-E2 PHA001Z123
(2) This packaged air-conditioner is manufactured and tested in conformity with the standard. Wireless FDK71-90 RCN-K71-E2 PHA001Z124
ISO-T1 "UNITARY AIR-CONDITIONERS" Motion sensor LB-KIT PJZ000Z331
(3) S ound level indicates the value in an anechoic chamber.
During operation these value are somewhat higher due to ambient conditions.
(4) S elect the breaker size according to the own national standard.
PHA001Z141
'19 • KX-T-310D
Models FDE36KXZE1 FDE45KXZE1 FDE56KXZE1 FDE71KXZE1
Nominal cooling capacity*1 3.6 4.5 5.6 7.1
kW
Nominal heating capacity*2 4.0 5.0 6.3 8.0
Power source 1 Phase 220-240V 50Hz / 220V 60Hz 1 Phase 220-240V 50Hz / 220V 60Hz 1 Phase 220-240V 50Hz / 220V 60Hz 1 Phase 220-240V 50Hz / 220V 60Hz
Cooling 0.050 - 0.050 / 0.050 0.050 - 0.050 / 0.050 0.050 - 0.050 / 0.050 0.070 - 0.070 / 0.070
Power consumption kW
Heating 0.050 - 0.050 / 0.050 0.050 - 0.050 / 0.050 0.050 - 0.050 / 0.050 0.070 - 0.070 / 0.070
Cooling 0.45 - 0.45 / 0.45 0.45 - 0.45 / 0.45 0.45 - 0.45 / 0.45 0.65 - 0.65 / 0.65
Running current A
Heating 0.45 - 0.45 / 0.45 0.45 - 0.45 / 0.45 0.45 - 0.45 / 0.45 0.65 - 0.65 / 0.65
Cooling 60 60 60 62
Sound Power Level
Heating 60 60 60 62
dB(A)
Cooling P-Hi:46 Hi:38 Me:31 Lo:26 P-Hi:46 Hi:38 Me:36 Lo:31 P-Hi:46 Hi:38 Me:36 Lo:31 P-Hi:47 Hi:39 Me:37 Lo:32
Sound Pressure Level
Heating P-Hi:46 Hi:38 Me:31 Lo:26 P-Hi:46 Hi:38 Me:36 Lo:31 P-Hi:46 Hi:38 Me:36 Lo:31 P-Hi:47 Hi:39 Me:37 Lo:32
Exterior dimensions
mm 210 × 1,070 × 690 210 × 1,070 × 690 210 × 1,070 × 690 210 × 1,320 × 690
Height x Width x Depth
Exterior appearance Plaster White Plaster White Plaster White Plaster White
(Munsell color) ( 6.8Y8.9/0.2 )near equivalent ( 6.8Y8.9/0.2 )near equivalent ( 6.8Y8.9/0.2 )near equivalent ( 6.8Y8.9/0.2 )near equivalent
Net weight kg 28 28 28 33
Refrigerant equipment Heat exchanger Louver fin & inner grooved tubing Louver fin & inner grooved tubing Louver fin & inner grooved tubing Louver fin & inner grooved tubing
Refrigerant control Electronic Expansion Valve Electronic Expansion Valve Electronic Expansion Valve Electronic Expansion Valve
(9) Ceiling suspended type (FDE)
Air handling equipment Fan type & Q'ty Centrifugal fan ×2 Centrifugal fan ×2 Centrifugal fan ×2 Centrifugal fan ×4
Fan motor <starting method> W 30 < Direct line start > 30 < Direct line start > 30 < Direct line start > 50 < Direct line start >
Cooling 3 P-Hi:13 Hi:10 Me:7 Lo:5.5 P-Hi:13 Hi:10 Me:9 Lo:7 P-Hi:13 Hi:10 Me:9 Lo:7 P-Hi:20 Hi:15 Me:13 Lo:10
Air flow(Standard) m /min
Heating P-Hi:13 Hi:10 Me:7 Lo:5.5 P-Hi:13 Hi:10 Me:9 Lo:7 P-Hi:13 Hi:10 Me:9 Lo:7 P-Hi:20 Hi:15 Me:13 Lo:10
Available static pressure Pa 0 0 0 0
Outdoor air intake Not possible Not possible Not possible Not possible
Air filter, Q'ty Pocket plastic net ×2 (Washable) Pocket plastic net ×2 (Washable) Pocket plastic net ×2 (Washable) Pocket plastic net ×2 (Washable)
-
Shock & vibration absorber Rubber sleeve(for fan motor) Rubber sleeve(for fan motor) Rubber sleeve(for fan motor) Rubber sleeve(for fan motor)
Insulation (noise & heat) Polyurethane form Polyurethane form Polyurethane form Polyurethane form
Operation control Wired : RC-EX3A,RC-E5 Wired : RC-EX3A,RC-E5 Wired : RC-EX3A,RC-E5 Wired : RC-EX3A,RC-E5
16 -
Remote control switch ( option ) Wireless : RCN-E-E3 Wireless : RCN-E-E3 Wireless : RCN-E-E3 Wireless : RCN-E-E3
Models FDE36KXZE1, 45KXZE1, 56KXZE1, 71KXZE1
Room temperature control Thermostat by electronics Thermostat by electronics Thermostat by electronics Thermostat by electronics
Overload protection for fan motor Overload protection for fan motor Overload protection for fan motor Overload protection for fan motor
Safety equipment
Frost protection thermostat Frost protection thermostat Frost protection thermostat Frost protection thermostat
Installation data Liquid line φ6.35 (1/4") <Flare piping> φ6.35 (1/4") <Flare piping> φ6.35 (1/4") <Flare piping> φ9.52 (3/8") <Flare piping>
Refrigerant piping size Gas line φ12.7 (1/2") <Flare piping> φ12.7 (1/2") <Flare piping> φ12.7 (1/2") <Flare piping> φ15.88 (5/8") <Flare piping>
Refrigerant R410A R410A R410A R410A
Drain hose Hose Connectable with VP20(O.D.26) Hose Connectable with VP20(O.D.26) Hose Connectable with VP20(O.D.26) Hose Connectable with VP20(O.D.26)
Insulation for piping Necessary(both Liquid & Gas line) Necessary(both Liquid & Gas line) Necessary(both Liquid & Gas line) Necessary(both Liquid & Gas line)
Accessories Mounting kit, Drain hose Mounting kit, Drain hose Mounting kit, Drain hose Mounting kit, Drain hose
Exterior dimensions PFA004Z036 PFA004Z036 PFA004Z036 PFA004Z037
Electrical wiring PFA004Z096 PFA004Z096 PFA004Z096 PFA004Z096
Notes (1) The data are measured at the following conditions. OPTION Model Specification Adapted to RoHS directive
Item Indoor air temperature Outdoor air temperature Wired RC-EX3A PJZ000Z333
Standards
Operation DB WB DB WB Wired RC-E5 PJZ000Z295
Remote
Cooling*1 27℃ 19℃ 35℃ 24℃ control Wired RCH-E3 PJZ000Z272
ISO-T1
Heating*2 20℃ 7℃ 6℃
Wireless RCN-E-E3 PFA004Z079
(2) This packaged air-conditioner is manufactured and tested in conformity with the standard.
ISO-T1 "UNITARY AIR-CONDITIONERS" Motion sensor LB-E PFA004Z077
(3) S ound level indicates the value in an anechoic chamber.
During operation these value are somewhat higher due to ambient conditions.
(4) S elect the breaker size according to the own national standard.
PFA004Z095
'19 • KX-T-310D
Models FDE112KXZE1 FDE140KXZE1
Nominal cooling capacity*1 11.2 14.0
kW
Nominal heating capacity*2 12.5 16.0
Power source 1 Phase 220-240V 50Hz / 220V 60Hz 1 Phase 220-240V 50Hz / 220V 60Hz
Cooling 0.100 - 0.100 / 0.100 0.130 - 0.130 / 0.130
Power consumption kW
Heating 0.100 - 0.100 / 0.100 0.130 - 0.130 / 0.130
Cooling 0.90 - 0.90 / 0.90 1.20 - 1.20 / 1.20
Running current A
Heating 0.90 - 0.90 / 0.90 1.20 - 1.20 / 1.20
Cooling 61 64
Sound Power Level
Heating 61 64
dB(A)
Cooling P-Hi:45 Hi:42 Me:38 Lo:34 P-Hi:48 Hi:43 Me:40 Lo:35
Sound Pressure Level
Heating P-Hi:45 Hi:42 Me:38 Lo:34 P-Hi:48 Hi:43 Me:40 Lo:35
Exterior dimensions
mm 250 × 1,620 × 690 250 × 1,620 × 690
Height x Width x Depth
Exterior appearance Plaster White Plaster White
(Munsell color) ( 6.8Y8.9/0.2 )near equivalent ( 6.8Y8.9/0.2 )near equivalent
Net weight kg 43 43
Refrigerant equipment Heat exchanger Louver fin & inner grooved tubing Louver fin & inner grooved tubing
Refrigerant control Electronic Expansion Valve Electronic Expansion Valve
Air handling equipment Fan type & Q'ty Centrifugal fan ×4 Centrifugal fan ×4
Fan motor <starting method> W 65 < Direct line start > 80 < Direct line start >
Models FDE112KXZE1, 140KXZE1
-
Shock & vibration absorber Rubber sleeve(for fan motor) Rubber sleeve(for fan motor)
Insulation (noise & heat) Polyurethane form Polyurethane form
Operation control Wired : RC-EX3A,RC-E5 Wired : RC-EX3A,RC-E5
17 -
Remote control switch ( option ) Wireless : RCN-E-E3 Wireless : RCN-E-E3
Room temperature control Thermostat by electronics Thermostat by electronics
Overload protection for fan motor Overload protection for fan motor
Safety equipment
Frost protection thermostat Frost protection thermostat
Installation data Liquid line φ9.52 (3/8") <Flare piping> φ9.52 (3/8") < Flare piping >
Refrigerant piping size Gas line φ15.88 (5/8") <Flare piping> φ15.88 (5/8") < Flare piping >
Refrigerant R410A R410A
Drain hose Hose Connectable with VP20(O.D.26) Hose Connectable with VP20(O.D.26)
Insulation for piping Necessary(both Liquid & Gas line) Necessary(both Liquid & Gas line)
Accessories Mounting kit, Drain hose Mounting kit, Drain hose
Exterior dimensions PFA004Z038 PFA004Z038
Electrical wiring PFA004Z096 PFA004Z096
Notes (1) The data are measured at the following conditions. OPTION Model Specification Adapted to RoHS directive
Item Indoor air temperature Outdoor air temperature Wired RC-EX3A PJZ000Z333
Standards
Operation DB WB DB WB Wired RC-E5 PJZ000Z295
Remote
Cooling*1 27℃ 19℃ 35℃ 24℃ control
ISO-T1 Wired RCH-E3 PJZ000Z272
Heating*2 20℃ 7℃ 6℃
Wireless RCN-E-E3 PFA004Z079
(2) This packaged air-conditioner is manufactured and tested in conformity with the standard.
ISO-T1 "UNITARY AIR-CONDITIONERS" Motion sensor LB-E PFA004Z077
(3) S ound level indicates the value in an anechoic chamber.
During operation these value are somewhat higher due to ambient conditions.
(4) S elect the breaker size according to the own national standard.
PFA004Z095
'19 • KX-T-310D
Models FDU650FKXZE1 FDU1100FKXZE1 FDU1800FKXZE1 FDU2400FKXZE1
Nominal cooling capacity*1 9.0 14.0 22.4 28.0
kW
Nominal heating capacity*2 6.5 10.5 16.0 21.5
Power source 1 Phase 220-240V 50Hz / 220V 60Hz 1 Phase 220-240V 50Hz / 220V 60Hz 1 Phase 220-240V 50Hz / 220V 60Hz 1 Phase 220-240V 50Hz / 220V 60Hz
Cooling 0.240 - 0.250 / 0.240 0.350 - 0.360 / 0.350 1.160 - 1.200 / 1.160 1.160 - 1.200 / 1.160
Power consumption kW
Heating 0.240 - 0.250 / 0.240 0.350 - 0.360 / 0.350 1.160 - 1.200 / 1.160 1.160 - 1.200 / 1.160
Cooling 1.80 - 1.70 / 1.80 2.30 - 2.20 / 2.30 6.80 - 6.50 / 6.80 6.80 - 6.50 / 6.80
Running current A
Heating 1.80 - 1.70 / 1.80 2.30 - 2.20 / 2.30 6.80 - 6.50 / 6.80 6.80 - 6.50 / 6.80
Cooling Hi:55 Hi:62 Hi:68 Hi:70
Sound Power Level
Heating Hi:55 Hi:62 Hi:68 Hi:70
dB(A)
Cooling Hi:31 Hi:37 Hi:42 Hi:45
Sound Pressure Level
Heating Hi:31 Hi:37 Hi:42 Hi:45
Exterior dimensions
mm 280 × 950 × 635 280 × 1,368 × 740 379 × 1,600 × 893 379 × 1,600 × 893
Height x Width x Depth
Net weight kg 34 54 89 89
Refrigerant equipment Heat exchanger Louver fin & inner grooved tubing Louver fin & inner grooved tubing Louver fin & inner grooved tubing Louver fin & inner grooved tubing
Refrigerant control Electronic Expansion Valve Electronic Expansion Valve Electronic Expansion Valve Electronic Expansion Valve
Air handling equipment Fan type & Q'ty Centrifugal fan ×2 Centrifugal fan ×3 Centrifugal fan ×3 Centrifugal fan ×3
Fan motor <starting method> W 130 < Direct line start > 100 + 200 < Direct line start > 130 + 350 < Direct line start > 130 + 350 < Direct line start >
Cooling 3 Hi:11 Hi:18 Hi:30 Hi:40
Air flow(Standard) m /min
Heating Hi:11 Hi:18 Hi:30 Hi:40
Available static pressure Pa 200 (at 11 m3/min) 200 (at 18 m3/min) 200 (at 30 m3/min) 200 (at 40 m3/min)
(10) Outdoor air processing unit (FDU-F)
-
Operation control Wired : RC-EX3A,RC-E5 Wired : RC-EX3A,RC-E5 Wired : RC-EX3A,RC-E5 Wired : RC-EX3A,RC-E5
Remote control switch ( option ) Wireless : RCN-KIT4-E2 Wireless : RCN-KIT4-E2 Wireless : RCN-KIT4-E2 Wireless : RCN-KIT4-E2
Room temperature control Thermostat by electronics Thermostat by electronics Thermostat by electronics Thermostat by electronics
18 -
Overload protection for fan motor Overload protection for fan motor Overload protection for fan motor Overload protection for fan motor
Safety equipment
Frost protection thermostat Frost protection thermostat Frost protection thermostat Frost protection thermostat
Installation data Liquid line φ9.52 (3/8") <Flare piping> φ9.52 (3/8") <Flare piping> φ9.52 (3/8") <Brazing> φ9.52 (3/8") <Brazing>
Refrigerant piping size Gas line φ15.88 (5/8") <Flare piping> φ15.88 (5/8") <Flare piping> φ19.05 (3/4") <Brazing> φ22.22 (7/8") <Brazing>
Refrigerant R410A R410A R410A R410A
Drain pump Built-in Drain pump Built-in Drain pump - -
Drain hose Hose Connectable VP25(I.D.25,O.D.32) Hose Connectable VP25(I.D.25,O.D.32) Connectable with VP25(O.D.32) Connectable with VP25(O.D.32)
Insulation for piping Necessary(both Liquid & Gas line) Necessary(both Liquid & Gas line) Necessary(both Liquid & Gas line) Necessary(both Liquid & Gas line)
Models FDU650FKXZE1, 1100FKXZE1, 1800FKXZE1, 2400FKXZE1
Accessories Mounting kit, Drain hose Mounting kit, Drain hose Mounting kit Mounting kit
Exterior dimensions PJG000Z295 PJG000Z296 PJG000Z297 PJG000Z297
Electrical wiring PJG000Z563 PJG000Z564 PJG000Z565 PJG000Z565
Notes (1) The data are measured at 33ºCDB 28ºCWB (68%RH) during cooling and 0ºCDB-2.9ºCWB (50%RH) during heating (no frost). Adapted to RoHS directive
(2) Temperature range of outdoor air must be 20 ~ 40ºCDB (32ºCWB or less) during cooling and -10℃~ 24ºCDB during heating.
(3) Sound level indicates the value in an anechoic chamber.
OPTION Model Specification
During operation these value are somewhat higher due to ambient conditions.
(4) The factory E.S.P. setting is set within the range of 10 - 120Pa.When SW8-4 is turned to "ON", Wired RC-EX3A PJZ000Z333
E.S.P. setting range can be changed to 10 - 200 Pa.(For RC-EX3A and RC-E5 only) Wired RC-E5 PJZ000Z295
Remote
(5) Select the breaker size according to the own national standard. control Wired RCH-E3 PJZ000Z272
Wireless RCN-KIT4-E2 PJZ000Z323
Motion sensor LB-KIT PJZ000Z331
PJG000Z562
'19 • KX-T-310D
Decorative panel
Content
860-910(Ceiling hole size) □950 Symbol
Model 28 36,45,56 71
Suspension bolts pitch:P1(778) □630 φ9.52(3/8")(Flare) φ12.7(1/2")(Flare) φ15.88(5/8")(Flare)
A Gas piping
B Liquid piping φ6.35(1/4")
(Flare) φ9.52(3/8")(Flare)
H1,2
C Drain piping VP25(O.D.32)
(1) Indoor unit
1000
420
420
or more
2. EXTERIOR DIMENSIONS
568
or more
Obstacle
-
Make a space of 4000 or more between
the units when installing more than one.
Air return grille Air supply
19 -
Drain hose piece H1,2 5-φ4
(Accessory)
245 Holes for
50 38 tapping screws
(Installed on site) 333 303
37
67
105
□840
Models FDT28KXZE1, 36KXZE1, 45KXZE1, 56KXZE1, 71KXZE1
137
40
suspension bolt
F C B A
76 215-245
Hole
65
236
44 13
188
173
140
131
G
140 240
850 or less
35
Control box 60 130
(Max. Drain lift)
88
88
50 or more
140
100
140
100
Notes(1)The model name label is attached to the Pitch area table of suspension bolt
control box lid. Symbol
(2)Suspension bolt pitch P1,P2 is adjustable Pattern P1 P2 Hole
by a pattern of the right table. 6-φ4 Hole 200 6-φ4
1 770 725-770 100 Holes for Holes for
(3)Section 1(※1)is provided on the panel Unit:mm
tapping screws tapping screws
PJF000Z417 A
2 770-800 725
T-PSAE-5AW-E only. H1 H2
'19 • KX-T-310D
Decorative panel Symbol Content
860-910(Ceiling hole size) □950 φ15.88(5/8")
(Flare)
A Gas piping
Suspension bolts pitch:P1(778) □630 B Liquid piping φ9.52(3/8")
(Flare)
H1,2 C Drain piping VP25(O.D.32)
G D Hole for wiring
F Suspension bolts (M10 or M8)
Outside air opening
G for ducting (Knock out)
Control
box H1 Air outlet opening φ125(Knock out)
H2 for ducting φ200(Knock out)
H1,2 H1,2
Space for installation and service
1000
420
420
or more
568
or more
Obstacle
-
Make a space of 5000 or more between
the units when installing more than one.
Air return grille Air supply
20 -
Drain hose piece H1,2 245 5-φ4
(Accessory) Holes for
333 303 50 38
(Installed on site) tapping screws
Models FDT90KXZE1, 112KXZE1, 140KXZE1, 160KXZE1
99
□840
129
F C B A 167
112
137
40
Hanger plate for
suspension bolt
76
215-245
Hole
65
298
44 13
188
173
140
131
140 G 240
60 130
850 or less
35
(Max. Drain lift)
Control box
140
140
50 or more
140
100
140
100
Notes(1)The model name label is attached to the Pitch area table of suspension bolt
control box lid. Symbol
Pattern P1 P2 Hole 6-φ4 Unit:mm
(2)Suspension bolt pitch P1,P2 is adjustable Hole 200 6-φ4
1 770 725-770 100 Holes for Holes for
by a pattern of the right table.
tapping screws tapping screws
PJF000Z418 A
(3)Section 1(※1)is provided on the panel 2 770-800 725
H1 H2
'19 • KX-T-310D
T-PSAE-5AW-E only.
□576-610( System ceiling hole size ) Content
Decorative panel Symbol
□576-600( Ceiling hole size ) Model 15,22,28 36,45,56
A Gas piping φ9.52(3/8") φ12.7(1/2")
530 ( Suspension bolts pitch ) □620 (Flare) (Flare)
G H □400 B Liquid piping φ6.35(1/4")(Flare)
C Drain piping VP25(O.D.32)
D1 Power source connection
All models
325
1000
Control or more
Air return grille Air supply Obstacle
-
175 box
(b) Ceiling cassette-4 way compact type (FDTC)
21 -
Inspection opening(Refer to note(2))
(Installed on site) 88
□570
215 - 245
150-200
A B 288
140
100
C F
110 Control box
6-φ4 J
100 Holes for
850 or less
248
tapping screws
210
190
H
130
130
Hole 89
10
or more
77
50
Draft prevention function(※) suspension bolt Unit:mm
φ10
0
Notes(1)The model name label is attached to the control box lid.
(2)This unit is designed for 2×2 grid ceiling. 4-φ4
158
If it is installed on a ceiling other than 2×2 grid ceiling, Holes for
provide an inspection opening on the control box side. tapping screws
(3)Draft prevention function(※)is provided on the panel TC-PSAE-5AW-E only.
D1 G
PJF000Z501 A
'19 • KX-T-310D
1080(Ceiling hole size) Drain hose piece Content
Symbol
97.5 885(Suspension bolts pitch) 97.5 (Accessory) Model 28 45,56 71
(Installed on site) A Gas piping φ9.52(3/8")(Flare) φ12.7(1/2")(Flare) φ15.88(5/8")(Flare)
G B Liquid piping φ6.35(1/4")(Flare) φ9.52(3/8")(Flare)
102
C Drain piping VP25(0.D.32)
Control D Hole for wiring
box
F E Suspension bolts (M10)
67 Outside air opening
240 F (Knock out)
650
446
Center of for ducting
200 6-φ4 panel 69 Air outlet opening
pitch)
G (Knock out)
(Suspension bolts
130 Holes for for ducting
102
G
450
20 130 820 130 20 310
187
137 100
117 140
Hole
53 53 295-325 10 230 10
(c) Ceiling cassette-2 way type (FDTW)
F 20
(Max.Drain lift)
20
E B A C
Hanger plate for
suspension bolt
-
325
262
750 orless
214
22 -
160
95
Control
20
D
Models FDTW28KXE6F, 45KXE6F, 56KXE6F, 71KXE6F
box
Decorative panel
Note(1)The model name label is attached on the lid of the control box.
1120
240 6-φ4 Air supply Air return Space for installation and service
200 Holes for
tapping screws
100 100
160
1000
or more
or more or more
Obstacle
680
360
137 100
Make a space of 4000 or more between
187
117 140
the units when installing more than one.
Hole G Unit:mm
160
172.5 775 172.5
36 1048 36
PJB001Z713 A
'19 • KX-T-310D
1795(Ceiling hole size) Symbol Content
Drain hose piece
97.5 1600(Suspension bolts pitch) 97.5 (Accessory) A Gas piping φ15.88(5/8")(Flare)
(Installed on site) B Liquid piping φ9.52(3/8")(Flare)
G C Drain piping VP25(O.D.32)
102
D Hole for wiring
Control E Suspension bolts (M10)
box Outside air opening
F F (Knock out)
for ducting
240 Air outlet opening
446
650
Center of G (Knock out)
200 panel for ducting
pitch)
6-φ4
(Suspension bolts
(Ceiling hole size)
130 Holes for
tapping screws
70
102
G 620
450
20 130 1535 130 20 310
187
137 100
117 140
Hole
53 53 295-325 10 230 10
F (Max. Drain lift) 20 20
Hanger plate for E B A C
suspension bolt
-
Models FDTW90KXE6F,112KXE6F,140KXE6F
325
262
23 -
750 or less
214
160
95
Control
20
D
box
Decorative panel Note(1)The model name label is attached on the lid of the control box.
1835
480 Air supply
10-φ4 Air return Space for installation and service
440 Holes for
tapping screws
100 100
or more
1000
160
or more
or more or more
Obstacle
Make a space of 5000 or more between
137 100
187
117 140
680
360
the units when installing more than one.
Hole
G
160
Unit:mm
172.5 1490 172.5
36 1763 36
PJB001Z714 A
'19 • KX-T-310D
1190(Suspension bolts pitch) Content
Symbol
595 595 Model 45 71
20 1150 20 A Gas piping φ12.7(1/2")(Flare) φ15.88(5/8")(Flare)
B Liquid piping φ6.35(1/4")(Flare) φ9.52(3/8")(Flare)
21
G Control box C Drain piping VP25(I.D.25, O.D.32)Note (2)
D Hole for wiring
Panel center F Suspension bolts (M10)
297
G
Outside air opening
518
for ducting (Knock out)
Drain hose piece
253.5 264.5
(Accessory) H
Drain piping VP25(I.D.25, O.D.32)
26
58 290 6-φ4
71 Holes for
200 tapping screws
Models FDTS45KXE6F, 71KXE6F
(d) Ceiling cassette-1 way type (FDTS)
565
100
295-325 415 Hole
140
C
372 F
A
-
250
112
328
437
D
24 -
220
G
35
B
382
H
Decorative panel Air supply Air supply
55 514 112 514 55
650
(3)This unit is designed for 2×4 grid ceiling.
100
45 or more
22.5 580 580 22.5 Obstacle
1250
Make a space of 4000 or more between
Air return grille Air return grille the units when installing more than one.
PJC001Z352
'19 • KX-T-310D
Symbol Content
A Gas piping φ12.7(1/2")(Flare)
(Duct dimension) B Liquid piping φ6.35(1/4")(Flare)
C1 Drain piping VP25(O.D.32)
Drain piping
185 420 185 C2 VP20
(Gravity drainage)
D Hole for wiring
41
Drain hose piece E Suspension bolts (M10)
200(Duct dimension)
(Accessory) Outside air opening
F (Knock out)
(Installed on site) for ducting
Air outlet opening
G (Knock out)
for ducting
39
Return air duct H Inspection opening (450×450)
100
-
tapping screws H
or more
28
200
150-
F Fan unit
25 -
100-200
139
Notes (a) There must not be obstacle to draw
472
113
69 C1 out fan unit. For fan unit maintenance,
G φ170 φ170 refer to page 41.
(b) Install refrigerant pipes,
Hole □90 drain pipe, and wiring so as Note (a)
B not to cross marked area.
135
F G
A (c) The case that pipes are installed to upper (bottom) of fan unit,
58 View M keep space of 60mm or more to upper (bottom) of unit.
(Case 2) From bottom of unit Note
67 (1) The model name label
295-325
1100
471
opening
43
15
105
or more
620
Unit:mm
175
76
50
600 or less
280
D
C2 467
55 680(Duct dimension) 55
PJG000Z056 B
'19 • KX-T-310D
Symbol Content
A Gas piping φ15.88(5/8")(Flare)
B Liquid piping φ9.52(3/8")(Flare)
65 740(Duct dimension) 185 C1 Drain piping VP25(O.D.32)
Drain piping
C2 (Gravity drainage) VP20
41
Hole for wiring
200(Duct dimension)
D
E Suspension bolts (M10)
Outside air opening
F for ducting (Knock out)
Air outlet opening
G for ducting (Knock out)
39
Return air duct Drain hose piece
(Accessory) H Inspection opening (450×450)
(Installed on site) Space for installation and service
986(Suspension bolts pitch) 4-φ4 Select either of two cases to keep space for installation and services.
4-φ4 (Case 1) From side of unit
Hanger plate for 18 950 18 Holes for
tapping screws 152 262 Holes for
suspension bolt Note (b)
Models FDU71KXE6F, 90KXE6F
100
or more
φ124
or more
86 Slab
28
139
Control box H Ceiling
20
370
200
150-
or more
113
Pipe (c)
-
Note (a)
1000 or more
φ170
φ170 Fan unit
472
69 C1 □90 100-200
Hole
26 -
G G Notes (a) There must not be obstacle to draw
F out fan unit. For fan unit maintenance,
B View M refer to page 41.
135
(b) Install refrigerant pipes,
A drain pipe,and wiring so as Note (a)
58 not to cross marked area.
(c) The case that pipes are installed to upper (bottom) of fan unit,
67 30 635 30 keep space of 60mm or more to upper (bottom) of unit.
1300
15
43
105
Inspection
600
opening
175
or more
620
76
250
50
280
600 or less
D
C2 467 Unit:mm
55 880(Duct dimension) 55
PJG000Z057 B
'19 • KX-T-310D
Symbol Content
A Gas piping φ15.88(5/8")(Flare)
B Liquid piping φ9.52(3/8")(Flare)
64 1280(Duct dimension) 64 C1 Drain piping VP25(O.D.32)
Drain piping
C2 (Gravity drainage) VP20
23.5
235(Duct dimension)
Drain hose piece D Hole for wiring
(Accessory) (M10)
E Suspension bolts
(Installed on site) Outside air opening
F for ducting (Knock out)
Air outlet opening
Return air duct G for ducting (Knock out)
21.5
H Inspection opening (450×450)
Space for installation and service
Select either of two cases to keep space for installation and services.
(Case 1) From side of unit
1404(Suspension bolts pitch) Note (b)
20
1368
100
18 18
or more
or more
28
tapping screws 285 Ceiling
20
-
150-
1000 or more
F
100-200 Fan unit
27 -
139
B Notes (a) There must not be obstacle to draw
530
out 2 fan unit. For fan units maintenance,
113
180
F (c) The case that pipes are installed to upper (bottom) of fan unit,
View M keep space of 60mm or more to upper (bottom) of unit.
59 (Case 2) From bottom of unit Note
69 (1) The model name label
30 738 30 is attached on the lid
100
or more
E 295-325 468
43
15
184.5
or more
134.5
725
Unit:mm
250
50
92
280
600 or less
D
C2 467
104 1200(Duct dimension) 104
PJG000Z058 B
'19 • KX-T-310D
Content
Symbol
MODEL 224 280
A Gas piping φ19.05(3/4") (Brazing)
(Brazing) φ22.22(7/8")
75 1450 (Duct dimension) 75 B Liquid piping φ9.52(3/8") (Brazing)
Drain piping
C VP25(O.D.32)
79
(Gravity drainage)
250(Duct dimension)
D D Hole for wiring
E Suspension bolts M10
F Inspection opening (450×450)
50
Return air duct
Space for installation and service
Select either of two cases to keep space for installation and services.
Hanger plate for (Case 1) From side of unit
suspension bolt
1634 (Suspension bolts pitch) Note (b)
Models FDU224KXZE1, 280KXZE1
20
100
or more
or more
17 1600 17 Slab
85
31
20
Ceiling
-
Control box F 480
200
or more
150-
Fan unit
28 -
100-200
831
(b) Install refrigerant pipes,
drain pipe,and wiring so as
not to cross marked area. Note (a)
B (c) The case that pipes are installed to upper(bottom)of fan unit,
31
Notes(1)The model name label
80 is attached on the lid
100
or more
50
6
50
or more
880
250(Duct dimension)
133
165
Unit:mm
349
379
PJG000Z287
'19 • KX-T-310D
'19 • KX-T-310D
Content
Symbol
200(Duct dimension)
(Accessory)
31
139
472
69 C1
113
G
(Suspension bolts pitch)
φ170
φ170
B □90
135
Hole
A F G
58 View M
(Max. drain lift)
67
30 635 30
170 (Duct dimension)
510
E 295-325 471
Air supply duct
413
105
43
15
600 or less
175
M
250
280
76
50
D
C2 467
55 680(Duct dimension) 55
Unit:mm
Space for installation and service
Select either of two cases to keep space for installation and services.
(Case 1) From side of unit (Case 2) From bottom of unit
or more
Note (b)
20
or more
or more
100
100
Slab
1100
Inspection
1000 or more
or more
or more
Ceiling
H 370
20
opening
600
150-
200
620
Note (a) Pipe (c)
Fan unit
100-200
PJG000Z016 B
- 29 -
'19 • KX-T-310D
Symbol Content
200(Duct dimension)
Control box
139
F
113
472
69 C1 φ170
φ170
G □90
(Suspension bolts pitch)
Hole
B F G
135
A View M
58
(Max. drain lift)
67 30 635 30
170 (Duct dimension)
510
E 295-325 471
Air supply duct 413
105
43
15
or less
175
M
250
600
280
76
50
D
C2 467
55 880(Duct dimension) 55
Unit:mm
Note (b)
20
or more
or more
100
100
Slab
1300
Inspection
1000 or more
or more
or more
Ceiling
H 370
20
opening
600
150-
200
620
Note (a) Pipe (c)
Fan unit
100-200
PJG000Z017 B
- 30 -
'19 • KX-T-310D
Symbol Content
64 1280(Duct dimension) 64
A Gas piping φ15.88(5/8")(Flare)
100 4×280=1120 100 B Liquid piping φ9.52(3/8")(Flare)
280
23.5
14-φ4
21.5
F φ124
139
530
G A
113
71 φ170
C1 φ170
Hole □90
180
F G
59 View M
600 or less (Max. drain lift)
69
30 738 30
170 (Duct dimension)
635
E 295-325 468
Air supply duct
405
184.5
134.5
43
15
M
250
280
45
92
D
C2 467
104 1200(Duct dimension) 104
Unit:mm
Space for installation and service
Select either of two cases to keep space for installation and services.
(Case 1) From side of unit (Case 2) From bottom of unit
or more
Note (b)
20
or more
or more
100
100
Slab
1720
Inspection
1000 or more
or more
or more
Ceiling
H 370
20
opening
600
150-
200
725
Note (a) Pipe (c)
Fan unit
100-200
PJG000Z018 B
- 31 -
Space for installation and service
Content
69 1060(Duct dimension) 69 Symbol 270 or more
Model 71
30
A Gas piping φ15.88(5/8")(Flare) Obstacle
100
D
B Liquid piping φ9.52(3/8")(Flare)
160
C1 Drain piping VP25(I.D.25 , O.D.32) Note (2)
Drain piping
C2 VP25(I.D.25 , O.D.32)
30
Return air duct (Gravity drainage)
D Hole for wiring φ25 × 2
1190(Suspension bolts pitch) E Suspension bolts (M10)
F Inspection opening (450×450), (270×1170)
1150
1170
20 1150 20
Model FDUT71KXE6F-E
297
(Duct dimension)
156
21
Control box
200
69
F
518
750
450
-
(Installed on site)
Obstacle
26
100
32 -
suspension bolt 71 30 565 30 View from top
side of the unit
415 Rear-intake type
(g) Duct connected (thin) -Low static pressure type (FDUT)
35
50
59
77
C1
99
127
190
220
600 or less
(Max. drain lift)
Obstacle Obstacle
69 1060(Duct dimension) 69 382
A B C2
100 or more
100 or more
1000 1000
or more
or more or more
or more
1000
1000
(Duct dimension)
of the control box.
(2) Prepare the connecting socket (VP25)
on site. Unit:mm
PJH000Z012 B
'19 • KX-T-310D
Content
F 35 60 F 60 35 Symbol
Model 15,22,28 36,45,56
A Gas piping φ9.52(3/8")(Flare) φ12.7(1/2") (Flare)
45
45
B Liquid piping φ6.35(1/4")
(Flare)
C Hole on wall for right rear piping (φ65)
D Hole on wall for left rear piping (φ65)
E Drain hose VP16
F Outlet for wiring(on both side)
870 230 3
(h) Wall mounted type (FDK)
290
Terminal block
60
13
Outlet for downward piping 45 F
-
(Refer to the top view)
33 -
Installation board Unit (Service space) 150
(Service space) 50 142.5 585 142.5
170 530 170
210 450 210
435 435
(Service space)
100
9
Unit:mm
43
Models FDK15KXZE1, 22KXZE1, 28KXZE1, 36KXZE1, 45KXZE1, 56KXZE1
185
190
268
47
on the right side of the unit.
13
55 15,22,28 469 55
D B E A 36,45,56 475 C
528
537
80(Service space)
PHA001Z105 A
Space for installation and service when viewing from the front
'19 • KX-T-310D
Symbol Content
G 19 64 G 64 43.5 A Gas piping φ15.88(5/8")
(Flare)
B Liquid piping φ9.52(3/8")(Flare)
55
55
C Hole on wall for right rear piping (φ65)
D Hole on wall for left rear piping (φ65)
E Drain hose VP16
F Outlet for wiring(on both side)
G Outlet for piping(on both side)
1197
262 3
Models FDK71KXZE1, 90KXZE1
339
G
Terminal block
60
11
-
Outlet for down piping
55
(Refer to the above view) F
34 -
Installation plate Unit (Service space) 150
(Service space) 50 157 883 157
214.5 768 214.5
363.5 470 363.5
568.5 60 568.5
Unit:mm
10
48
43 100 (Service space)
240
240
322.4
47
6.7
D 53 B E A C 77
715
759
PHA001Z106 A
783
15(Service space) 47
'19 • KX-T-310D
Space for installation and service when viewing from the front
C 1, C 2
10
53
290(Suspension bolts pitch) D
135 410 145 Note) The slope of drain piping inside the
24 1022(Suspension bolts pitch) 24 unit must take decline of 10mm.
68 52
B
5
A
40
31
215
210
173
53
27 108
27
40 990 40 15 60 7
109
690
1070 20 100
195
(i) Ceiling suspended type (FDE)
C 1, C 2
Air supply 235 Drain hose piece(Accesory,0.3m)
(Installed on site)
271
Models FDE36KXZE1, 45KXZE1, 56KXZE1
-
Symbol Content
35 -
A Gas piping φ12.7(1/2")(Flare)
B Liquid piping φ6.35(1/4")(Flare)
C1,2 Drain piping VP20
308
D Hole for suspension bolt (M10 or M8)
E Back cutout PE cover
75 F Top cutout Plate cover
C2
76 A C1 110 B G Hole for drain piping(for left back) (Knock out)
Air return grille
135
Space for installation and service Position of top cutout and back cutout
Hole for Note (1) The model name label is attached on the
175 drain piping
120 19 fan cosing inside the air return grille.
(for left)
20
F Unit:mm
100or more
G
300 or more
150 or more 5or more Right side cutout
E
Piping can be connected from 3 different direction.
Obstacle
Remove the cutout using side cutter or similar tool.
Make a space of 4000 or more between the units when installing more than one.
PFA004Z036
'19 • KX-T-310D
C 1, C 2
53
10
290(Suspension bolts pitch) D
135 410 145
24 1272(Suspension bolts pitch) 24 Note) The slope of drain piping inside the
68 52 unit must take decline of 10mm.
B
5
A
40
31
215
210
Model FDE71KXZE1
173
53
27 108
27
40 1240 40 15 60 7
109
690
1320 20 100
195 C 1, C 2
Air supply 235 Drain hose piece(Accesory,0.3m)
(Installed on site)
271
Symbol Content
A Gas piping φ15.88(5/8")(Flare)
B Liquid piping φ9.52(3/8")(Flare)
-
C1,2 Drain piping VP20
D Hole for suspension bolt (M10 or M8)
36 -
E Back cutout PE cover
F Top cutout Plate cover
G Hole for drain piping(for left back) (Knock out)
308
C2 75
76 Air return grille A C1 110 B
135
Space for installation and service Position of top cutout and back cutout
Hole for
175 drain piping
120 19 (for left)
20 Note (1) The model name label is attached on the
fan cosing inside the air return grille.
F Unit:mm
100or more
G
Right side cutout
300 or more
150 or more 5or more
E
Piping can be connected from 3 different direction.
Obstacle
Remove the cutout using side cutter or similar tool.
Make a space of 4500 or more between the units when installing more than one.
PFA004Z037
'19 • KX-T-310D
C 1, C 2
53
10
290(Suspension bolts pitch) D
135 410 145
24 1572(Suspension bolts pitch) 24
68 52 Note) The slope of drain piping inside the
B unit must take decline of 10mm.
5
A
40
31
255
250
173
53
27 108
27
40 1540 40 15 60 7
109
690
1620 20 100
195 C1, C2
Air supply 235 Drain hose piece(Accesory,0.3m)
Models FDE112KXZE1, 140KXZE1
-
C1,2 Drain piping VP20
D Hole for suspension bolt (M10 or M8)
E Back cutout
37 -
PE cover
F Top cutout Plate cover
G Hole for drain piping(for left back) (Knock out)
308
75
C2 76 A C1 110 B
Air return grille
135
Space for installation and service Position of top cutout and back cutout
Hole for
175 drain piping
120 19 (for left)
20 Note (1) The model name label is attached on the
fan cosing inside the air return grille.
F Unit:mm
100or more
G
300 or more
150 or more 5 or more Right side cutout
E
Piping can be connected from 3 different direction.
Obstacle
Remove the cutout using side cutter or similar tool.
Make a space of 5000 or more between the units when installing more than one.
PFA004Z038
'19 • KX-T-310D
Symbol Content
A Gas piping φ15.88(5/8")(Flare)
B Liquid piping φ9.52(3/8") (Flare)
65 740(Duct dimension) 185 C1 Drain piping VP25(O.D.32)
Drain piping VP20(O.D.26)(Standard)or
C2
(Gravity drainage) VP25(O.D.32)(Used with attached socket)
41
D Hole for wiring
39
Return air duct Drain hose piece
Model FDU650FKXZE1
100
( j ) Outdoor air processing unit (FDU-F)
or more
86 φ124 Slab
28
139
Control box Ceiling
20
370
-
H
200
or more
F
150-
113
Note (a) Pipe(c)
1000 or more
φ170
φ170 Fan unit
472
100-200
38 -
69 C1 Hole 90
G Notes(a)There must not be obstacle to draw
F G out fan unit. For fan unit maintenance,
View M refer to page 41.
B (b)Install refrigerant pipes,
135
A drain pipe,and wiring so as Note(a)
58 not to cross marked area.
(c)The case that pipes are installed to upper(bottom)of fan unit,
67 30 635 30 keep space of 60mm or more to upper(bottom)of unit.
413
1300
43
15
105
Inspection
or less
opening
600
175
or more
620
76
50
M
250
PJG000Z295 A
'19 • KX-T-310D
Symbol Content
A Gas piping φ15.88(5/8")(Flare)
B Liquid piping φ9.52(3/8")(Flare)
64 1280(Duct dimension) 64 C1 Drain piping VP25(O.D.32)
Drain piping VP20(O.D.26)
(Standard)or
C2
(Used with attached socket)
(Gravity drainage) VP25(O.D.32)
24
235(Duct dimension)
Drain hose piece D Hole for wiring
(Accessory)
E Suspension bolts M10
(Installed on site) Outside air opening
F ( Knock out)
for ducting
Air outlet opening
G ( Knock out)
22
Return air duct for ducting
H Inspection opening (450×450)
Model FDU1100FKXZE1
100
18 1368 18
or more
or more
28
20
-
tapping screws 370
H
200
or more
150-
F
Fan unit
39 -
100-200
139
B Notes(a)There must not be obstacle to draw
530
out 2 fan units. For fan units maintenance,
113
G A φ170 refer to page 41.
71 φ170 (b)Install refrigerant pipes,
180
F (c)The case that pipes are installed to upper(bottom)of fan unit,
View M keep space of 60mm or more to upper(bottom)of unit.
59 (Case 2) From bottom of unit Note
69 (1)The model name label
30 738 30 is attached on the lid
100
or more
295-325 468
43
or more
15
725
Unit:mm
135
185
50
M
250
PJG000Z296 A
'19 • KX-T-310D
Content
Symbol
MODEL 1800 2400
A Gas piping φ19.05(3/4")
(Brazing)φ22.22(7/8")
(Brazing)
75 1450(Duct dimension) 75 B Liquid piping φ9.52(3/8")
(Brazing)
Drain piping
C VP25(O.D.32)
79
(Gravity drainage)
250(Duct dimension)
D D Hole for wiring
E Suspension bolts M10
F Inspection opening (450×450)
50
Return air duct Space for installation and service
Select either of two cases to keep space for installation and services.
Hanger plate for (Case 1) From side of unit
suspension bolt
1634(Suspension bolts pitch) Note(b)
20
100
or more
or more
17 1600 17 Slab
85
Models FDU1800FKXZE1, 2400FKXZE1
31
20
F Ceiling
Control box 480
-
or more
200
150-
Note.(a) Pipe(c)
1500 or more
40 -
Notes(a)There must not be obstacle to draw
A out 2 fan units.
(b)Install refrigerant pipes,
831
drain pipe,and wiring so as
not to cross marked area.
(c)The case that pipes are installed to upper Note(a)
B
31
Notes(1)The model name label
80 is attached on the lid
100
or more
50
6
50
or more
880
250(Duct dimension)
133
165 Unit:mm
349
379
PJG000Z297 A
'19 • KX-T-310D
'19 • KX-T-310D
Screw
Screw
Screw
- 41 -
'19 • KX-T-310D
18.3
18.3
30mm
30mm
Wiring
配線
30mm
30mm 30mm
30mm
83.5
120
83.5
Fixing固定穴
holes
120
37
37 23
23 23
23 19
19 R/C temperature sensor
120
120
Secure minimum spaces for disassembling the case.
120mm
120mm
Upper left and Upper right sides
……30mm or more
Bottom side…120mm or more
If using L-shaped screwdriver, 50mm or more is
available.
・Where the ambient temperature becomes 0 °C or below, or 40 °C or above When the cable length is longer than 100 m,
・Where the surface is not flat the max size for wires used in the R/C case
・Where the strength of installation area is insufficient is 0.5 mm2 . Connect them to wires of larger
size near the outside of R/C. When wires are
(2) Moisture may be attached to internal parts of the remote control, resulting in a display failure.
connected, take measures to prevent water,
・Place with high humidity where condensation occurs on the remote control etc. from entering inside.
・Where the remote control gets wet
(3) Accurate room temperature may not be detected using the temperature sensor of the remote ≦ 200 m 0.5 mm2 x 2 cores
control. ≦ 300m 0.75 mm2 x 2 cores
・Where the average room temperature cannot be detected ≦ 400m 1.25 mm2 x 2 cores
・Place near the equipment to generate heat
≦ 600m 2.0 mm2 x 2 cores
・Place affected by outside air in opening/closing the door
・Place exposed to direct sunlight or wind from air-conditioner
・Where the difference between wall and room temperature is large
(4) When you are using the automatic grille up and down panel in the IU, you may not be able to
confirm the up and down motion.
・Where the IU cannot be visually confirmed
PJZ000Z333
- 42 -
'19 • KX-T-310D
Lower case
LCD
Lower part
TEMP ON/OFF
Upper Sheath Upper Sheath
Board Board
X Y X Y
120
44
42
45
11.5 11
Wiring oulet
Electrical box 12×7 slot hole
䠄Not included䠅 Installation hole
9.5×5 slot hole䠄4places䠅
Unit:mm
Wiring specifications
(1) If the prolongation is over 100m, change to the size below.
But, wiring in the remote control case should be under 0.5mm 2. Change the wire size outside of
the case according to wire connecting. Waterproof treatment is necessary at the wire connecting
section. Be careful about contact failure.
- 43 -
'19 • KX-T-310D
Unit: mm
60 24 167
- 44 -
Meaning of marks
Mark Parts name
AM1-4 Air flex motor
Connector for branching control CNA-Z Connector
of heat recovery 3-pipe systems
CNU
DM Drain motor
220-240V 50Hz Thi-A Remote operation input
220V 60Hz BL FMi DM (volt-free contact) F1,2 Fuse
RD YE/GN
Power source M
1 Phase TB1 WH M t° FMi Fan motor
All models
L FS Float switch
Power source line
N RD WH RD BL BR OR WH WH RD BK BK Humidity sensor
YE/GN HS
Power source line
between indoor units CNWO 5 3 1 1 4 5 6 7 2 1+12 4 3 2 1 1 2 3 4 5 6 2 1 2 1 +12 Option JSL1 Live Superlink terminal setting(For spare)
WH E1 CNR CNV2 CNV CNH BK
CNM1 CNTA 3
F1 F2 WH WH BK WH BK BL BK LED・2 Indication lamp(Green-Normal operation)
(3.15A) (2.0A) CNL 21 BK P IS
YE/GN SW1 SW2 BK LED・3 Indication lamp(Red-Inspection)
Earth LM1-4 Louver motor
Power circuit 2 BK
S +12 For heat recovery 3-pipe systems CNC HS P IS Motion sensor
W SW3 SW4 1 BK
WH 1
5 2 XB1 (20S) SM Stepping motor(For electronic expansion valve)
CNT2 3 XB2 (SVH)
RD SW1 Indoor unit address:tens place
4
3. ELECTRICAL WIRING
XB3 (SVG)
(1) Ceiling cassette-4 way type (FDT)
-
5 XR4 (Inspection) YE 3
RD t° SW5-2 Indoor unit address:hundreds place
JSL1 6 2
XR5 Remote operation input RD Thi-R1 SW6 Model capacity setting
1 CNK1
Superlink(spare) (volt-free contact) 1
45 -
2 WH t° SW7-1 Operation check,drain motor test run
TB2 CNK2 BK
X X WH 1 CNB RD
FS TB1 Terminal block(Power source)
Remote control CNI 2
Thc t° Y Y BK 2 BK CNA CNJ2 CNJ1 BL TB2 Terminal block(Signal line)
RD GY WH 1 RD
A BL 1 2 3 4 5 6 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 Thc Temperature sensor(Remote control)
Signal line B RD WH YEORBL RD WH WHWHWHWHWHWHWHWHWH BL BL BL BL BL BL BL BL BL BL BK BK BK BK BK BK BK BK BK BK RD RD RD RD RD RD RD RD RD RD Thi-A Temperature sensor(Return air)
(Shielded cord)
1 2 3 4 5 1 2 3 4 5 1 2 3 4 5 1 2 3 4 5 1 2 3 4 5 1 2 3 4 5 1 2 3 4 5 1 2 3 4 5 Thi-R1,2,3 Temperature sensor(Heat exchanger)
Signal line M M M M M M M M M
between indoor units Color marks
SM ※1 AM1 AM2 AM3 AM4 LM1 LM2 LM3 LM4
Mark Color Mark Color
BK Black WH White
BL Blue YE Yellow
BR Brown GY Gray
Notes OR Orange YE/GN Yellow/Green
1. indicates wiring on site. RD Red
2.Use twin core shielded cord(0.75-1.25mm2 )at signal line between
indoor unit and outdoor unit, and signal line between indoor units.
2
3.Use twin core cord(0.3mm )at remote control line.
See spec sheet of remote control in case that the total length is more
than 100m.
4.Do not put signal line and remote control line alongside power source line.
5.Section 1(※1)is provided on the panel T-PSAE-5AW-E only.
PJF000Z421
'19 • KX-T-310D
Connector for branching control Meaning of marks
220-240V 50Hz of heat recovery 3-pipe systems FMi
220V 60Hz CNU M Remote operation input Item Description
BL Thi-A
Power source RD DM (volt-free contact)
YE/GN AM1-4 Draft prevention function motor
1Phase WH M Prepare on site
TB1 t°
L
RD BL BR OR WH CNM2 CNA-Z Connector
Power source line WH
N DM Drain motor
RD WH RD BL BR OR WH YE/GN WH RD BK BK
All models
RD
B
-
(Shielded cord) SW5-1 Automatic adjustment / Fixed previous
JSL1 +12
For heat recovery 3-pipe systems
1 version of Superlink protocol
Signal line 2
Superlink(spare) XB1 (20S) Indoor unit address:hundreds place
between indoor units CNT2 3
SW5-2
46 -
RD XB2 (SVH)
4 XB3 (SVG) Model capacity setting
CNK2 BK SW6,SW7-2
5 XB4 (SVE)
SW7-1 Operation check,drain motor test run
+12 Prepare on site TB1 Terminal block(Power source)
(□mark)
1
2 XR1 (Operation) TB2 Terminal block(Signal line)(□mark)
CNT 3 XR2 (Heating)
BL 4 XR3 (Thermo ON) Thc Temperature sensor(Remote control)
5 XR4 (Inspection)
6 Thi-A Temperature sensor(Return air)
CNA CNJ2 CNJ1 XR5 Remote operation input Thi-R1,2,3 Temperature sensor(Heat exchanger)
RD GY WH (volt-free contact)
1 2 3 4 5 6 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
WHYE OR BL RD WH WH WH WH WH BL BL BL BL BL BL BL BL BL BL WH WH WH WH WH BK BK BK BK BK BK BK BK BK BK RD RD RD RD RD RD RD RD RD RD Color marks
Mark Color Mark Color
WH WH WH WH WH BL BL BL BL BL BL BL BL BL BL WH WH WH WH WH CNJ4 BK BK BK BK BK BK BK BK BK BK RD RD RD RD RD RD RD RD RD RD CNJ3
M BK Black WH White
WH WH
1 2 3 4 5 1 2 3 4 5 1 2 3 4 5 1 2 3 4 5 1 2 3 4 5 1 2 3 4 5 1 2 3 4 5 1 2 3 4 5 BL Blue YE Yellow
SM
M M M M M M M M BR Brown GY Gray
OR Orange YE/GN Yellow/Green
※1 AM1 AM2 AM3 AM4 LM1 LM2 LM3 LM4 RD Red
Notes
1. indicates wiring on site.
2.Use twin core shielded cord(0.75-1.25mm 2 )at signal line between
indoor unit and outdoor unit, and signal line between indoor units.
3.Use twin core cord(0.3mm 2 )at remote control line.
See spec sheet of remote control in case that the total length is more than 100m.
4.Do not put signal line and remote control line alongside power source line.
5.Draft prevention function(※1)is provided on the panel TC-PSAE-5AW-E only.
PJF000Z504
'19 • KX-T-310D
Meaning of marks
Item Description
CNA-Z Connector
Control PCB DM Drain motor
1 RD
Thi-R1
F1,3 Fuse
Remote control TB2 2 RD
WH FMi1 Fan motor
X X 1 CNB YE
3
ThC BK CNN
Y Y 3 WH Thi-R2 FS Float switch
BL YE 4 YE
A
RD 1 5 BK JSL1
B CNK1
3-pipe systems 2 WH SW5 BK
Thi-R3 Indication lamp
6
between indoor units
CNU SW6
BL
WH Power PCB 1 WH 1
1
CNW0 2 WH 2
RD WH SW7 1 BK
Power source 3 WH 3
RD 3 4 WH 4 CNH Thi -A LM1- 4
1 Phase Power source L 5 WH 5 BK 2 BK
line WH 5 Power circuit 6 WH
N 6 PIS Motion sensor
CNW1 7 WH 7 CNW2 FS
WH 8 WH 8 WH RD
Power source line 1 SM
9 WH 9
between indoor units 10 WH 10
CNI
BL 2 RD
11 WH 11
TB1 F3 12 WH 12
RD
SW1
Earth 1 4 5 6 7 CNR 1 M DM
WH
(3) Ceiling cassette-2 way type (FDTW)
WH 2
SW2
RD BL BR OR WH
CNM1 1 BL 1 BK Prepare on site SW3
WH LM1 1
2 BL 2 BK
2 CNTA 1
3 BL 3 BK SW4
M 3 BL 2
M 4 BL 4 BK
FMi1 4 SW5-1
5 BL 5 BK SW1 SW2 SW3 SW4
5
1 OR 6 BK WH
LM2 6 1
5 OR 7 BK YE
7 2
-
4 OR 8 BK OR
M 8 3 SW5-2
3 OR 9 BK BL
9 CNA 4 M SM
2 OR 10 BK CNJ RD
10 5
SW6
1 BK 11 BK WH
LM3 11 RD
5 BK 12 BK 6
12 SW7-1
4 BK 13 BK
47 -
M 13 For HA
3 BK 14 BK Prepare on site TB1
14 1
2 BK 15 BK CNZ WH
15 2
Models FDTW28KXE6F, 45KXE6F, 56KXE6F, 71KXE6F
1 RD 16 BK XR1 TB2
LM4 16
2 RD 17 BK 3 XR2
17 CNT
3 RD 18 BK BL 4 XR3 ThC Temperature sensor(Remote control)
M 18 CND BK
4 RD 19 BK 5 XR4
19 Thi-A Temperature sensor(Return air)
5 RD 20 BK 6
20
CNJ2 Thi-R1,2,3 Temperature sensor(Heat exchanger)
WH JSL1
1
3-pipe systems Color marks
CNK2 BK
2 XB1
CNT2 3 XB2
Color
RD 4 XB3 BK
5 XB4
BL Blue
WH
1 1 BR Brown
CNG 2 2 PIS
BL 3 3 OR
BK
Notes 4
1
RD Red
1. ----- indicates wiring on site. CNV2 2 WH White
RD
BK 3
2. Use twin core shielded cord(0.75 - 1.25mm2) at signal line between 4 Option YE Yellow
indoor unit and outdoor unit, and signal line between indoor units.
3. Use twin core cord(0.3mm2) at remote control line.
See spec sheet of remote control in case that the total length is more than
100m.
4. Do not put signal line and remote control line alongside power source line.
5. Section 1(※1)shows electric circuit of motion sensor(option).
PJB001Z830
'19 • KX-T-310D
Meaning of marks
Item Description
CNA-Z Connector
Control PCB DM Drain motor
1 RD
Thi-R1 F1,3,4 Fuse
Remote control TB2 2 RD
WH
X X 1 CNB YE
FMi1,2 Fan motor
3
Thc BK CNN
Y Y 3 WH Thi-R2 FS Float switch
BL YE 4 YE
A
RD 1 5 BK JSL1
B CNK1
3-pipe systems 2 WH SW5 BK
Thi-R3 Indication lamp
6
between indoor units
CNU SW6
BL
WH Power PCB 1 WH 1
1
CNW0 2 WH 2
RD WH SW7 1 BK
Power source 3 WH 3
RD 3 4 WH 4 CNH Thi -A LM1- 4
1 Phase Power source L 5 WH 5 BK 2 BK
line WH 5 Power circuit 6 WH 6
N CNW1 CNW2 PIS Motion sensor
7 WH 7 FS
WH 8 WH 8 WH RD
Power source line 1 SM
9 WH 9
between indoor units 10 WH 10
CNI
BL 2 RD
11 WH 11
TB1 F3 F4 12 WH 12
RD
SW1
Earth 1 4 5 6 7 1 4 5 6 7 CNR 1 M DM
WH SW2
WH 2
RD BL BR OR WH RD BL BR OR WH
CNM1 CNM2 1 BL 1 BK Prepare on site
WH BK LM1 1 SW3
2 BL 2 BK
2 CNTA 1
3 BL 3 BK SW4
M 3 BL 2
RD BL BR OR WH CNF1 RD BL BR OR WH CNF2 4 BL 4 BK
4
WH WH 5 BL 5 BK SW1 SW2 SW3 SW4 SW5-1
5
1 OR 6 BK WH
6 1
-
LM2 5 OR 7 BK YE
7 2
Models FDTW90KXE6F, 112KXE6F, 140KXE6F
M M 4 OR 8 BK OR
FMi1 FMi2 M 8 3 SW5-2
3 OR 9 BK BL
9 CNA 4 M SM
2 OR 10 BK CNJ RD
10 5 SW6
1 BK 11 BK WH
LM3 11 RD
6
48 -
5 BK 12 BK
12 SW7-1
4 BK 13 BK
M 13 For HA
3 BK 14 BK Prepare on site
14 1
TB1
2 BK 15 BK CNZ WH
15 2 XR1
1 RD 16 BK TB2
LM4 16
2 RD 17 BK 3 XR2
17 CNT
3 RD 18 BK 4 XR3 Thc Temperature sensor(Remote control)
M 18 CND BK BL
4 RD 19 BK 5 XR4
19
5 RD 20 BK 6 Thi-A Temperature sensor(Return air)
20
CNJ2 Thi-R1,2,3 Temperature sensor(Heat exchanger)
WH JSL1
1
3-pipe systems
CNK2 BK
2 XB1
CNT2 3 XB2 Color
RD 4 XB3
5 XB4
BK
BL Blue
WH
1 1 BR Brown
CNG 2 2 PIS
BL 3 3 OR
BK
Notes 4
1
RD Red
1. ----- indicates wiring on site. CNV2 2
RD WH White
BK 3
2. Use twin core shielded cord(0.75 - 1.25mm2) at signal line between 4 Option YE Yellow
indoor unit and outdoor unit, and signal line between indoor units.
3. Use twin core cord(0.3mm2) at remote control line.
See spec sheet of remote control in case that the total length is more than
100m.
4. Do not put signal line and remote control line alongside power source line.
5. Section 1(※1)shows electric circuit of motion sensor(option).
PJB001Z831
'19 • KX-T-310D
Meaning of marks
Item Description
CNA-Z Connector
1 RD
DM Drain motor
Remote control RD
Thi-R1
2 Fuse
WH F1-3
X X 1 YE
3
Thc 3 WH CNN FMi Fan motor
Y Y YE 4 YE
Thi-R2
A FS Float switch
RD 1 5
CNK1 JSL1
Power source 3-pipe systems 2 WH Thi-R3
6 Indication lamp
1 Phase between indoor units
CNU
WH 1 WH 1 1
RD 1 2 WH 2 CNH Thi-A
3 WH 3 SW5 2
RD 3 4 WH 4 LM1,2
L 5 WH 5
Power source line WH 5 Power circuit SW6 FS
N 6 WH 6 RD PIS Motion sensor
CNW1 CNW2 1
7 WH 7
CNW0 WH 8 WH 8 WH CNI
WH SW7 2 RD SM
9 WH 9
Models FDTS45KXE6F, 71KXE6F
Earth
10 WH 10
(4) Ceiling cassette-1 way type (FDTS)
F3 11 WH 11
Power source line 12 WH 12 1
RD
SW1 SW2 SW3 SW4 CNR
SW1
between indoor units WH M DM
WH 2 SW2
1 4 5 6 7
RD OR WH
Prepare on site SW3
CNM1 CNJ3 CNTA 1
WH 2
SW4
-
1 1 For HA
LM1 1 SW5-1
2 2
M 2 CNZ WH WH
FMi 3 3 1
M 3 YE
4 4 2
4 OR
5 5 3 SW5-2
49 -
5
CNJ CND CNA 4 M SM
1 1 WH RD SW6
LM2 6 5
2 2
7 RD SW7-1
3 3 6
M 8
4 4
9
5 5 Prepare on site
10 1
CNJ2 11 2 XR1
WH 12 3 XR2
13
CNT 4 XR3
14 5 XR4
15 JSL1 6 Thc Temperature sensor(Remote control)
16
17 Thi-A Temperature sensor(Return air)
18 Thi-R1,2,3 Temperature sensor(Heat exchanger)
19 CNK2
20 3-pipe systems Closed-end connector
1
2
CNT2 3 Color marks
RD 4 Color Color
Notes 5
RD Red
1. ----- indicates wiring on site. 1 WH WH 1 WH White
2. Use twin core shielded cord(0.75 - 1.25mm2) at signal line between CNG 2 RD 2
PIS
3 3 YE Yellow
indoor unit and outdoor unit, and signal line between indoor units. 4
OR
1
3. Use twin core cord(0.3mm2) at remote control line. CNV2 2
RD
3
See spec sheet of remote control in case that the total length is more than 4 Option
100m.
4. Do not put signal line and remote control line alongside power source line.
5. Section 1(※1)shows electric circuit of motion sensor(option).
PJC001Z434
'19 • KX-T-310D
Meaning of marks
Item Description
CNA-Z Connector
DM Drain motor
Control PCB F1,3 Fuse
RD
Remote control 1
t° Thi -R1 FMi1 Fan motor
TB2 RD
ThC 2
WH
X X 1 LED・2 LED・3 YE FS Float switch
CNB 3
BK WH
Y Y 3 CNN t° Thi -R2
t° YE JSL1 Spare Superlink connector change
BL YE 4
A BK
Signal line RD 5 L Reactor
B
Connector for branching (Shielded cord) 1 BK
t° Thi -R3
CNK1 SW5 6 LED・2 Indication lamp(Green-Normal operation)
control of heat recovery 2 WH
Power source line 3-pipe systems Signal line SW6 BK
LED・3 Indication lamp(Red-Inspection)
1
between indoor units between indoor units CNH
CNU BK BK
t° Thi -A PIS Motion sensor
Power source RD WH BL SW7 2
Models FDU45KXE6F, 56KXE6F
-
8 WH FS
TB1 YE/GN 9 WH RD SW4
9 1 Outdoor unit address:ones place
10 WH
10
(5) Duct connected-High static pressure type (FDU)
11 WH
CNI
11 BL RD SW5-1 Automatic adjustment/Fixed
12 WH 2
12
50 -
F3
(2A) For HA Prepare on site previous version of Superlink protocol
WH +12 1
CNWR CNZ SW5-2 Indoor unit address:hundreds place
2 XR1 (Operation)
WH 1 4 5 6 7
CNT 3 XR2 (Heating) SW6
CNC RD BL 4 XR3 Model capacity setting
RD BK WH YE BL (Thermo ON)
CNM1 5 XR4 (Inspection)
WH SW7-1 Operation check, Drain motor test run
L 6
JSL1 XR5(Remote operation TB1 Terminal block(Power source)(□mark)
input:volt-free contact)
FMi1 M Superlink(spare) TB2 Terminal block(Signal line)(□mark)
CNK2 Thc Temperature sensor(Remote control)
For heat recovery 3-pipe systems
+12 BK +12 1
RD 1 2 XB1 (20S) Thi-A Temperature sensor(Return air)
DM M WH
CNR CNT2 3 XB2
2 WH (SVH)
RD Thi-R1,2,3 Temperature sensor(Heat exchanger)
4 XB3 (SVG)
5 XB4 (SVE) ■mark Closed-end connector
1 WH WH 1 Color marks
CNG 2 RD 2
PIS Mark Color Mark Color
BL 3 BK 3
4 BK
Notes 1. ----- indicates wiring on site. BK Black WH White
1 BL Blue YE Yellow
2. Use twin core cable(0.75 - 1.25mm2) at signal line between indoor unit CNV2 2
RD
and outdoor unit, and signal line between indoor units. CNTA BK 3 OR Orange YE/GN Yellow/Green
4 Option
3. Use twin core cable(0.3mm2) at remote control line. BL ※1 RD Red
1 2
See spec sheet of remote control in case that the total length is more than 100m.
4. Do not put signal line and remote control line alongside power source line.
5. Section 1(※1)shows electric circuit of motion sensor(option). Prepare on site
PJG000Z539
'19 • KX-T-310D
Meaning of marks
Item Description
CNA-Z Connector
DM Drain motor
Control PCB F1,4 Fuse
RD
Remote control 1
t° Thi -R1 FMi2 Fan motor
TB2 RD
ThC 2
WH
X X 1 LED・2 LED・3 YE FS Float switch
CNB 3
BK WH
Y Y 3 CNN t° Thi -R2
t° YE JSL1 Spare Superlink connector change
BL YE 4
A BK
Signal line RD 5 L Reactor
B
Connector for branching (Shielded cord) 1 BK
t° Thi-R3
CNK1 SW5 6 LED・2 Indication lamp(Green-Normal operation)
control of heat recovery 2 WH
Power source line 3-pipe systems Signal line SW6 BK
LED・3 Indication lamp(Red-Inspection)
1
between indoor units between indoor units CNH
CNU BK BK
t° Thi -A PIS Motion sensor
Power source RD WH BL SW7 2
Models FDU71KXE6F, 90KXE6F
-
8 WH
8 WH FS
TB1 YE/GN 9 WH RD SW4
9 1 Outdoor unit address:ones place
10 WH CNI
10
11 WH BL
11 RD SW5-1 Automatic adjustment/Fixed
12 WH 2
12
51 -
F4 For HA
(2A) Prepare on site previous version of Superlink protocol
WH +12 1
CNWR CNZ SW5-2 Indoor unit address:hundreds place
2 XR1 (Operation)
WH 1 4 5 6 7
CNT 3 XR2 (Heating) SW6
CNC RD BL 4
Model capacity setting
RD BK WH YE BL XR3 (Thermo ON)
CNM2 5 XR4 (Inspection)
BK SW7-1 Operation check, Drain motor test run
L 6
JSL1 XR5(Remote operation TB1 Terminal block(Power source)(□mark)
input:volt-free contact)
FMi2 M Superlink(spare) TB2 Terminal block(Signal line)(□mark)
CNK2 Thc Temperature sensor(Remote control)
For heat recovery 3-pipe systems
BK +12 1
RD +12
1 2 XB1 (20S) Thi-A Temperature sensor(Return air)
DM M WH
CNR CNT2 3 XB2 (SVH)
2 WH RD Thi-R1,2,3 Temperature sensor(Heat exchanger)
4 XB3 (SVG)
5 XB4 (SVE) ■mark Closed-end connector
1 WH WH 1 Color marks
CNG 2 RD 2
PIS
BL 3 BK 3 Mark Color Mark Color
4 BK
Notes 1. ----- indicates wiring on site. BK Black WH White
1
2. Use twin core shielded cord(0.75 - 1.25mm2) at signal line between indoor unit CNV2 2
BL Blue YE Yellow
RD
and outdoor unit, and signal line between indoor units. CNTA BK 3 OR Orange YE/GN Yellow/Green
BL 4 Option ※1
3. Use twin core cord(0.3mm2) at remote control line. 1 2 RD Red
See spec sheet of remote control in case that the total length is more than 100m.
4. Do not put signal line and remote control line alongside power source line. Prepare on site
5. Section 1(※1)shows electric circuit of motion sensor(option).
(Remote operation input:
volt-free contact)
PJG000Z540
'19 • KX-T-310D
Meaning of marks
Item Description
CNA-Z Connector
DM Drain motor
Control PCB F1,3,4 Fuse
RD
Remote control 1
t° Thi -R1 FMi1,2 Fan motor
TB2 RD
ThC 2
WH
X X 1 LED・2 LED・3 YE FS Float switch
CNB 3
BK WH
Y Y 3 CNN t° Thi -R2
t° YE JSL1 Spare Superlink connector change
BL YE 4
A BK
Signal line RD 5 L Reactor
B
Connector for branching (Shielded cord) 1 BK
t° Thi -R3
CNK1 SW5 6 LED・2 Indication lamp(Green-Normal operation)
control of heat recovery 2 WH
Power source line 3-pipe systems Signal line SW6 BK
LED・3 Indication lamp(Red-Inspection)
1
between indoor units between indoor units CNH
CNU BK BK
t° Thi -A PIS Motion sensor
Power source RD WH BL SW7 2
1 Phase SM Stepping motor
CNW0 Power PCB SW1 SW2 SW3 SW4 WH
YE/GN 1 WH 1
YE (For electronic expansion valve)
F1(6.3A) 1 WH 2
RD 3 1 OR
Power source L 2 WH 3 SW1
2 Indoor unit address:tens place
WH 5 Power circuit 3 WH BL M SM
line N 3 CNA 4
4 WH
4 SW2 Indoor unit address:ones place
WH RD 5
CNW1 56 5 RD
WH 6
WH 7 6
Earth WH CNW2 SW3 Outdoor unit address:tens place
7
8 WH
-
8 WH FS
9 WH
Models FDU112KXE6F, 140KXE6F, 160KXE6F
52 -
F3 F4
(2A) (2A) For HA Prepare on site previous version of Superlink protocol
WH +12 1
CNWR CNZ SW5-2 Indoor unit address:hundreds place
2 XR1 (Operation)
WH 1 4 5 6 7 1 4 5 6 7
CNT 3 XR2 (Heating) SW6
CNC RD BL 4 XR3 Model capacity setting
RD BK WH YE BL RD BK WH YE BL (Thermo ON)
CNM1 CNM2 5 XR4 (Inspection)
WH BK SW7-1 Operation check, Drain motor test run
L 6
JSL1 XR5(Remote operation TB1 Terminal block(Power source)(□mark)
input:volt-free contact)
FMi1 M FMi2 M Superlink(spare) TB2 Terminal block(Signal line)(□mark)
CNK2 Thc Temperature sensor(Remote control)
For heat recovery 3-pipe systems
BK +12 1
RD +12
1 2 XB1 (20S) Thi-A Temperature sensor(Return air)
DM M WH
CNR CNT2 3 XB2 (SVH)
2 WH RD Thi-R1,2,3 Temperature sensor(Heat exchanger)
4 XB3 (SVG)
5 XB4 (SVE) ■mark Closed-end connector
1 WH WH 1 Color marks
CNG 2 RD 2
PIS
BL 3 BK 3 Mark Color Mark Color
4 BK
Notes 1. ----- indicates wiring on site. BK Black WH White
1
2. Use twin core shielded cord(0.75 - 1.25mm2) at signal line between indoor unit CNV2 2
BL Blue YE Yellow
RD
and outdoor unit, and signal line between indoor units. CNTA BK 3 OR Orange YE/GN Yellow/Green
BL 4 Option ※1
3. Use twin core cord(0.3mm2) at remote control line. 1 2 RD Red
See spec sheet of remote control in case that the total length is more than 100m.
4. Do not put signal line and remote control line alongside power source line. Prepare on site
5. Section 1(※1)shows electric circuit of motion sensor(option).
(Remote operation input:
volt-free contact)
PJG000Z541
'19 • KX-T-310D
Meaning of marks
Item Description
CNA-Z Connector
DM Drain motor
F1-3 Fuse
FMi1,2 Fan motor
Remote control RD
1 FS Float switch
ThC WH
X X 1 RD
Thi -R1
2 JSL1
Y Y 3 WH YE
CNN 3 L Reactor
A YE Thi -R2
YE Indication lamp
1 4
RD
CNK1
2 WH 5
Power source line 3-pipe systems Thi -R3 PIS Motion sensor
6
between indoor units CNU SW5
between indoor units SM
Power source RD WH 1
1 Phase SW6 CNH Thi -A SW1
2
SW2
SW7 1
WH
1 WH SW3
RD RD T1 1 YE
L 2 WH 2
2 SW1 SW2 SW3 SW4
Models FDU224KXZE1, 280KXZE1
-
12
CNZ WH 2 SW7- 1
F1 F2 Prepare on site
1
2 XR1
6 4 3 2 1 1 4 5 6 7
CND
53 -
T3 T4 CNT 3 XR2 Thc Temperature sensor(Remote control)
YE YE 4 XR3
YE WH RD CNM1 RD WH YE CNM2 Thi-A Temperature sensor(Return air)
5 XR4
WH 6 Thi-R1,2,3 Temperature sensor(Heat exchanger)
L JSL1 Closed-end connector
M FMi2
CNK2 1
Color marks
CNM 6 4 3 2 1 Option 2
RD 1 CNT2 Color
WH 3
DM M WH CNR RD 4
CNFM 2 WH
1 3 5 5
WH
WH RD
1 WH WH 1 OR
CNFM2 CNG 2 RD 2
PIS RD Red
WH RD WH 3 3
4 WH White
1
FMi1 M CNV2 2
YE Yellow
RD
3
4 Option
Notes 1. ----- indicates wiring on site.
2. Use twin core shielded cord(0.75 - 1.25mm2) at signal line between indoor unit CNTA
and outdoor unit, and signal line between indoor units. 1 2
PJG000Z543
'19 • KX-T-310D
Meaning of marks
Item Description
CNA-Z Connector
DM Drain motor
Control PCB F1-3 Fuse
RD
Remote control 1
TB2 RD
t° Thi -R1 FMi1 Fan motor
ThC 2
WH
X X 1 LED・2 LED・3 YE FS
CNB 3 Float switch
BK WH
Y Y 3 CNN t° Thi -R2
t° YE
BL YE 4 JSL1 Spare Superlink connector change
A BK
Signal line RD 5
B LED・2 Indication lamp(Green-Normal operation)
Connector for branching (Shielded cord) 1 BK
t° Thi -R3
CNK1 SW5 6
control of heat recovery 2 WH LED・3 Indication lamp(Red-Inspection)
Power source line 3-pipe systems Signal line SW6 BK
1 PIS Motion sensor
between indoor units between indoor units CNH
CNU BK BK
t° Thi -A
Power source RD WH BL SW7 2 SM Stepping motor
1 Phase
CNW0 Power PCB SW1 SW2 SW3 SW4 WH
(For electronic expansion valve)
YE/GN 1 WH 1
YE SW1
F1(3.15A) 1 WH 2 Indoor unit address:tens place
RD 3 1 OR
Power source L 2 WH 3
2
WH 5 Power circuit 3 WH BL M SM SW2
line N 3 CNA 4 Indoor unit address:ones place
4 WH
F2(3.15A) 4
WH RD 5
CNW1 56 5 RD SW3 Outdoor unit address:tens place
WH 6
WH 7 6
Earth WH CNW2
7
8 WH SW4
-
8 WH FS Outdoor unit address:ones place
TB1 YE/GN 9 WH RD
9 1
10 WH CNI SW5-1
10 Automatic adjustment/Fixed
11 WH
11 BL RD
12 WH 2
12 previous version of Superlink protocol
54 -
F3
(2A) For HA Prepare on site
WH +12 1 SW5-2 Indoor unit address:hundreds place
CNZ
2 XR1 (Operation)
1 4 5 6 7 SW6 Model capacity setting
(6) Duct connected Low/Middle static pressure type (FDUM)
FMi1 M Superlink(spare)
CNK2 Thc Temperature sensor(Remote control)
For heat recovery 3-pipe systems
+12 BK +12 1 Thi-A
RD
Temperature sensor(Return air)
1 2 XB1 (20S)
DM M WH
CNR CNT2 3 XB2 Thi-R1,2,3
2 WH (SVH) Temperature sensor(Heat exchanger)
RD
4 XB3 (SVG)
5 XB4 (SVE) ■mark Closed-end connector
Color marks
1 WH WH 1
CNG 2 RD 2
PIS Mark Color Mark Color
BL 3 BK 3
4 BK BK Black RD Red
Notes 1. ----- indicates wiring on site.
1 BL Blue WH White
2. Use twin core cable(0.75 - 1.25mm2) at signal line between indoor unit CNV2 2
CNTA RD BR Brown YE Yellow
and outdoor unit, and signal line between indoor units. BK 3
BL 4 Option
1 2 ※1 OR Orange YE/GN Yellow/Green
3. Use twin core cable(0.3mm2) at remote control line.
See spec sheet of remote control in case that the total length is more than 100m.
4. Do not put signal line and remote control line alongside power source line. Prepare on site
5. Section 1(※1)shows electric circuit of motion sensor(option).
(Remote operation input:
volt-free contact)
PJG000Z526
'19 • KX-T-310D
Meaning of marks
Item Description
CNA-Z Connector
DM Drain motor
Control PCB F1,4 Fuse
RD
Remote control 1
TB2 RD
t° Thi -R1 FMi2 Fan motor
ThC 2
WH
X X 1 LED・2 LED・3 YE FS Float switch
CNB 3
BK WH
Y Y 3 CNN t° Thi -R2
t° YE JSL1 Spare Superlink connector change
BL YE 4
A BK
Signal line RD 5 LED・2
B Indication lamp(Green-Normal operation)
Connector for branching (Shielded cord) 1 BK
t° Thi -R3
CNK1 SW5 6 LED・3
control of heat recovery 2 WH
Indication lamp(Red-Inspection)
Power source line 3-pipe systems Signal line SW6 BK PIS Motion sensor
1
between indoor units between indoor units CNH
CNU BK BK
t° Thi -A SM Stepping motor
Power source RD WH BL SW7 2
1 Phase (For electronic expansion valve)
CNW0 Power PCB SW1 SW2 SW3 SW4 WH
YE/GN 1 WH 1
YE SW1 Indoor unit address:tens place
F1(5A) 1 WH 2
Models FDUM71KXE6F, 90KXE6F
RD 3 1 OR
Power source L 2 WH 3
2
WH 5 Power circuit 3 WH BL M SM SW2 Indoor unit address:ones place
line N 3 CNA 4
4 WH
4
WH RD 5
CNW1 56 5 RD
SW3 Outdoor unit address:tens place
WH 6
WH 7 6
Earth WH CNW2
7 SW4
8 WH Outdoor unit address:ones place
8 WH FS
TB1 YE/GN 9 WH RD
9 1
10 WH CNI SW5-1 Automatic adjustment/Fixed
10
-
11 WH
11 BL RD
12 WH 2
12 previous version of Superlink protocol
F4 For HA
(2A) Prepare on site SW5-2 Indoor unit address:hundreds place
WH +12 1
55 -
CNZ
2 XR1 (Operation)
1 4 5 6 7 SW6 Model capacity setting
CNT 3 XR2 (Heating)
RD BK WH YE BL CNC RD BL 4 XR3 (Thermo ON) SW7-1 Operation check, Drain motor test run
CNM2 5 XR4 (Inspection)
BK
6 TB1 Terminal block(Power source)(□mark)
JSL1 XR5(Remote operation
input:volt-free contact) TB2 Terminal block(Signal line)(□mark)
FMi2 M Superlink(spare)
CNK2 Thc Temperature sensor(Remote control)
For heat recovery 3-pipe systems
BK +12 1 Thi-A Temperature sensor(Return air)
RD +12
1 2 XB1 (20S)
DM M WH
CNR CNT2 3 XB2 (SVH) Thi-R1,2,3 Temperature sensor(Heat exchanger)
2 WH RD
4 XB3 (SVG)
5 XB4 (SVE)
■mark Closed-end connector
Color marks
1 WH WH 1
CNG 2 RD 2
PIS Mark Color Mark Color
BL 3 BK 3
4 BK BK Black RD Red
Notes 1. ----- indicates wiring on site. BL Blue WH White
1
2. Use twin core shielded cord(0.75 - 1.25mm2) at signal line between indoor unit CNV2 2
CNTA RD BR Brown YE Yellow
and outdoor unit, and signal line between indoor units. BK 3
BL 4 Option
1 2 ※1 OR Orange YE/GN Yellow/Green
3. Use twin core cord(0.3mm2) at remote control line.
See spec sheet of remote control in case that the total length is more than 100m.
4. Do not put signal line and remote control line alongside power source line. Prepare on site
5. Section 1(※1)shows electric circuit of motion sensor(option).
(Remote operation input:
volt-free contact)
PJG000Z527
'19 • KX-T-310D
Meaning of marks
Item Description
CNA-Z Connector
DM Drain motor
Control PCB F1,3,4 Fuse
RD
Remote control 1
t° Thi -R1 FMi1,2 Fan motor
TB2 RD
ThC 2
WH
X X 1 LED・2 LED・3 YE FS Float switch
CNB 3
BK WH
Y Y 3 CNN t° Thi -R2
t° YE JSL1 Spare Superlink connector change
BL YE 4
A BK
Signal line RD 5 L Reactor
B
Connector for branching (Shielded cord) 1 BK
t° Thi -R3
CNK1 SW5 6 LED・2 Indication lamp(Green-Normal operation)
control of heat recovery 2 WH
Power source line 3-pipe systems Signal line SW6 BK LED・3 Indication lamp(Red-Inspection)
1
between indoor units between indoor units CNH
CNU BK BK
t° Thi -A PIS Motion sensor
Power source RD WH BL SW7 2
1 Phase SM Stepping motor
CNW0 Power PCB SW1 SW2 SW3 SW4 WH
YE/GN 1 WH 1
YE (For electronic expansion valve)
F1(5A) 1 WH 2
RD 3 1 OR
Power source L 2 WH 3
2 SW1 Indoor unit address:tens place
WH 5 Power circuit 3 WH BL M SM
line N 3 CNA 4
4 WH
4 SW2
WH RD 5 Indoor unit address:ones place
CNW1 56 5 RD
WH 6
WH 7 6
Earth WH CNW2 SW3 Outdoor unit address:tens place
7
8 WH
-
8 WH FS
TB1 YE/GN 9 WH RD
9 1 SW4 Outdoor unit address:ones place
10 WH
10
Models FDUM112KXE6F, 140KXE6F, 160KXE6F
11 WH
CNI
11 BL RD SW5-1
12 WH 2 Automatic adjustment/Fixed
12
56 -
F3 F4
(2A) (2A) For HA Prepare on site previous version of Superlink protocol
WH +12 1
CNWR CNZ SW5-2
2 XR1 (Operation) Indoor unit address:hundreds place
WH 1 4 5 6 7 1 4 5 6 7
CNT 3 XR2 (Heating) SW6
RD BK WH YE BL RD BK WH YE BL CNC RD BL 4 XR3 (Thermo ON) Model capacity setting
CNM1 CNM2 5 XR4 (Inspection)
L WH BK SW7-1 Operation check, Drain motor test run
6
JSL1 XR5(Remote operation TB1 Terminal block(Power source)(□mark)
input:volt-free contact)
FMi1 M FMi2 M Superlink(spare) TB2 Terminal block(Signal line)(□mark)
CNK2 Thc
For heat recovery 3-pipe systems Temperature sensor(Remote control)
BK +12 1
RD +12
1 2 XB1 (20S) Thi-A Temperature sensor(Return air)
DM M WH
CNR CNT2 3 XB2 (SVH)
2 WH RD Thi-R1,2,3 Temperature sensor(Heat exchanger)
4 XB3 (SVG)
5 XB4 (SVE) ■mark Closed-end connector
1 WH WH 1 Color marks
CNG 2 RD 2
PIS Mark Color Mark Color
BL 3 BK 3
4 BK
BK Black RD Red
Notes 1. ----- indicates wiring on site.
1 BL Blue WH White
2. Use twin core shielded cord(0.75 - 1.25mm2) at signal line between indoor unit CNV2 2
CNTA RD
and outdoor unit, and signal line between indoor units. BK 3 BR Brown YE Yellow
BL 4 Option
1 2 ※1
3. Use twin core cord(0.3mm2) at remote control line. OR Orange YE/GN Yellow/Green
See spec sheet of remote control in case that the total length is more than 100m.
4. Do not put signal line and remote control line alongside power source line. Prepare on site
5. Section 1(※1)shows electric circuit of motion sensor(option).
(Remote operation input:
volt-free contact)
PJG000Z528
'19 • KX-T-310D
Meaning of marks
Item Description
CNA-Z Connector
Control PCB DM Drain motor
Remote control 1 RD
TB2 F1-3 Fuse
WH RD
t° Thi-R1
X X 1 CNB 2 FMi Fan motor
ThC BK 3 YE FS Float switch
t° Y Y 3 WH
BL CNN t° Thi-R2 JSL1 Spare Superlink connector change
A YE 4 YE
Signal line (Shielded cord) RD 1
Connector for branching B CNK1 5 BK LED・2 Indication lamp(Green-Normal operation)
Power source control of heat recovery 2 WH LED・3 Indication lamp(Red-Inspection)
3-pipe systems
LED・2 LED・3 t° Thi-R3
1 Phase Signal line between indoor units 6 BK
PIS Motion sensor
CNU SM Stepping motor(for electronic expansion valve)
BL 1 BK
WH CNW0 Power PCB 1 WH 1 SW1 Indoor unit address:tens place
YE/GN 2 WH 2 CNH t° Thi -A
Model FDUT71KXE6F-E
RD 1 WH BK
3 WH 3 SW5 BK 2 SW2 Indoor unit address:ones place
RD 3
F1(3.15A)
L 4 WH 4
Power source line Power circuit 5 WH 5 FS SW3 Outdoor unit address:tens place
WH 5 SW6 RD
N WH 6 1 SW4 Outdoor unit address:ones place
F2(3.15A) CNW1 76 WH 7 CNW2 CNI
WH 8 WH 8 WH BL 2 RD SW5-1 Automatic adjustment/Fixed previous
Earth 9 WH 9 SW7
10 WH 10
+12
version of Superlink protocol
YE/GN 11 WH 11 RD SW5-2 Indoor unit address:hundreds place
Power source line TB1 F3 12 WH 12 CNR 1
(2.0A) WH M DM
between indoor units WH 2 SW6 Model capacity setting
1 4 5 6 7 SW7-1 Operation check, Drain motor test run
Prepare on site
RD BL BR OR WH CNTA 1 TB1 Terminal block(Power source)(□ mark)
CNM1
WH BL 2 TB2 Terminal block(Signal line)(□ mark)
SW1 SW2 SW3 SW4
ThC Temperature sensor(Remote control)
M WH
-
FMi 1 Thi-A Temperature sensor(Return air)
YE
2
OR Thi-R1,2,3 Temperature sensor(Heat exchanger)
For HA 3
CNA 4 BL M SM ■mark Closed-end connector
CNZ WH RD
5
57 -
RD Color marks
6
Mark Color
BK Prepare on site
(7) Duct connected (thin) -Low static pressure type (FDUT)
1 WH WH 1
CNG 2 RD 2
PIS
BL 3 BK 3
4 BK
CNV2 1
BK 2
RD
3
4 Option ※1
Notes 1. ----- indicates wiring on site.
2. Use twin core shielded cord(0.75 - 1.25mm2) at signal line between indoor unit
and outdoor unit, and signal line between indoor units.
3. Use twin core cord(0.3mm2) at remote control line.
See spec sheet of remote control in case that the total length is more than 100m.
4. Do not put signal line and remote control line alongside power source line.
5. Section 1(※1)shows electric circuit of motion sensor(option).
PJH000Z023
'19 • KX-T-310D
Meaning of marks
For heat recovery Item Description
3-pipe systems
Power source (SVH) (SVE) CNA-Z Connector
FMi (20S) (SVG)
All models
-
CNK2 BK
version of Superlink protocol
SW5 -2 Indoor unit address:hundreds place
TB2
58 -
BL SW6,SW7-2 Model capacity setting
Signal line A 1 CNK1
RD SW7 -1 Operation check
(Shielded cord) B 2 WH
CNA CNN CNC CNH CNB CNT +12 CNL TB1 Terminal block(Power source)(□ mark)
YE/GN RD YE WH BK GN BL BK
1 2 3 4 5 6 1 2 3 4 5 6 1 2 1 2 1 2 6 5 4 3 2 1 1 2 3 TB2 Terminal block(Signal line)(□ mark)
Signal line Thc Temperature sensor(Remote control)
between indoor units WY O B R B B B B B B B B B B W B W R B
H E R L D K K K K K K K K K K H K H D K Thi-A Temperature sensor(Return air)
t° t° t° t°
TB2 X Y Thi-R1,2,3 Temperature sensor(Heat exchanger)
HS ■mark Closed-end connector
M W R B
Thi-R1 Thi-R2 Thi-R3 Thi-A X Y H D K
SM XR3 XR1 Color marks
Thc 1 2 3
t°
Remote control PIS Mark Color Mark Color
XR4 XR2 BK Black RD Red
Option
XR5 BL Blue WH White
(Remote operation input ※2
Notes :volt-free contact) (Thermo ON) (Operation) BR Brown YE Yellow
(Inspection) (Heating) OR Orange YE/GN Yellow/Green
1. ----- indicates wiring on site.
Prepare on site PK Pink
2. Use twin core shielded cord(0.75 - 1.25mm2) at signal line between indoor unit
and outdoor unit, and signal line between indoor units.
3. Use twin core cord(0.3mm2) at remote control line.
See spec sheet of remote control in case that the total length is more than 100m.
4. Do not put signal line and remote control line alongside power source line.
5. Fuse(F1)(※1)is 3.15A in case of FDK15~56 ,and 5A in case of FDK71,90.
6. Section 1(※2)shows electric circuit of motion sensor(option).
PHA001Z142
'19 • KX-T-310D
Remote WH 1
X X 1
control Thi
Y Y 3 WH 2
Thc
A 3
CNN Thi
1 YE 4
All models
RD
CNK1
2 WH 5
between indoor units
Thi
Power source 6
1 Phase CNU
1
WH CNW0 1 WH 1 SW5 CNH
RD 1 WH 2 WH 2 Thi
3 WH 3 2
RD 3 4 WH 4 SW6
Power L 5 WH 5
WH 5 Power circuit CNI 1
source line N WH 6 WH
CNW1 76 WH 7 CNW2 SW7 2
WH 8 WH 8 WH
9 WH 9 Prepare on site
Earth 10 WH 10 1
11 WH 11 SW1 SW2 SW3 SW4 CNTA
(9) Ceiling suspended type (FDE)
-
6
M 7
CND 2 XR1
FMi 8 3 XR2
9
CNT 4 XR3
10 5 XR4
59 -
11 WH 6
Meaning of marks 12
13
Item Description 14
15 1
CNA-Z Connector
16 2
F1-3 Fuse 17 CNK2 CNT2 3
FMi Fan motor 18 RD 4
19 5
20
WH WH WH
1 1
CNG 2 RD RD
LM 3 2 PIS
PIS Motion sensor 4 3
SM 1
CNV2 2
RD
CNL1 CNL2
SW1 3 WH WH
SW2 4
Option
SW3
SW4
Color marks
Color
Notes 1. ----- indicates wiring on site. SW6
2. Use twin core cable(0.75 - 1.25mm2)at signal line between indoor unit
and outdoor unit, and signal line between indoor units. OR
3. Use twin core cable(0.3mm2) at remote control. PK
See spec sheet of remote control in case that the total length is more than 100m. Thc Temperature sensor(Remote control) RD Red
4. Do not put signal line and remote control line alongside power source line. Thi-A Temperature sensor(Return air) WH White
5. Section 1(※1) is provided on the models 112,140 only. Thi-R1,2,3 Temperature sensor(Heat exchanger) YE Yellow
6. Section 2(※2)shows electric circuit of motion sensor(option).
PFA004Z096
'19 • KX-T-310D
Meaning of marks
Item Description
CNA-Z Connector
DM Drain motor
Control PCB F1,4 Fuse
RD
Remote control 1
t° Thi -R1 FMi2 Fan motor
TB2 RD
ThC 2
WH
X X 1 LED・2 LED・3 YE FS Float switch
CNB 3
BK WH
Y Y 3 CNN t° Thi -R2
t° YE JSL1 Spare Superlink connector change
BL YE 4
A BK
Signal line RD 5 L Reactor
Model FDU650FKXZE1
B
Connector for branching (Shielded cord) 1 BK
t° Thi -R3
CNK1 SW5 6 LED・2 Indication lamp(Green-Normal operation)
control of heat recovery 2 WH
Power source line 3-pipe systems Signal line BK
LED・3 Indication lamp(Red-Inspection)
SW6 1
between indoor units between indoor units CNH PIS
CNU BK BK
t° Thi -A Motion sensor
Power source RD WH BL SW7 2
1 Phase SM Stepping motor
CNW0 Power PCB SW1 SW2 SW3 SW4 WH
YE/GN 1 WH 1 (For electronic expansion valve)
(10) Outdoor air processing unit (FDU-F)
YE
F1(5A) 1 WH 2
RD 3 1 OR
Power source L 2 WH 3 SW1 Indoor unit address:tens place
2
WH 5 Power circuit 3 WH BL M SM
line N 3 CNA 4
4 WH
4 SW2 Indoor unit address:ones place
WH RD 5
CNW1 56 5 RD
WH 6
WH 7 6 SW3
Earth WH CNW2 Outdoor unit address:tens place
7
-
8 WH
8 WH FS
TB1 YE/GN 9 WH RD SW4 Outdoor unit address:ones place
9 1
10 WH
10 CNI
11 WH
11 BL RD SW5-1 Automatic adjustment/Fixed
12 WH 2
12
60 -
F4 For HA previous version of Superlink protocol
(2A) Prepare on site
WH +12 1
CNWR CNZ SW5-2 Indoor unit address:hundreds place
2 XR1 (Operation)
WH 1 4 5 6 7
CNT 3 XR2 (Heating) SW6 Model capacity setting
RD BK WH YE BL BL 4 XR3 (Thermo ON)
CNM2 CND BK
5 XR4 (Inspection) SW7-1 Operation check, Drain motor test run
BK
L 6
JSL1 XR5(Remote operation TB1 Terminal block(Power source)(□mark)
input:volt-free contact) TB2
FMi2 M Superlink(spare) Terminal block(Signal line)(□mark)
CNK2 Thc Temperature sensor(Remote control)
BK
For heat recovery 3-pipe systems
+12 1
RD +12 Thi-A Temperature sensor(Return air)
1 2 XB1 (20S)
DM M WH
CNR CNT2 3 XB2 (SVH)
2 WH RD Thi-R1,2,3 Temperature sensor(Heat exchanger)
4 XB3 (SVG)
5 XB4 (SVE) ■mark Closed-end connector
1 WH WH 1 Color marks
CNG 2 RD 2
PIS Mark Color Mark Color
BL 3 BK 3
4 BK
BK Black WH White
Notes 1. ----- indicates wiring on site.
1 BL Blue YE Yellow
2. Use twin core shielded cord(0.75 - 1.25mm2) at signal line between indoor unit CNV2 2
RD
and outdoor unit, and signal line between indoor units. CNTA BK 3 OR Orange YE/GN Yellow/Green
BL 4 Option ※1
3. Use twin core cord(0.3mm2) at remote control line. 1 2 RD Red
See spec sheet of remote control in case that the total length is more than 100m.
4. Do not put signal line and remote control line alongside power source line. Prepare on site
5. Section 1(※1)shows electric circuit of motion sensor(option).
(Remote operation input:
volt-free contact)
PJG000Z563
'19 • KX-T-310D
Meaning of marks
Item Description
CNA-Z Connector
DM Drain motor
Control PCB F1,3,4 Fuse
RD
Remote control 1
t° Thi -R1 FMi1,2 Fan motor
TB2 RD
ThC 2
WH
X X 1 LED・2 LED・3 YE FS Float switch
CNB 3
BK WH
Y Y 3 CNN t° Thi -R2
t° YE JSL1 Spare Superlink connector change
BL YE 4
A BK
Signal line RD 5 L Reactor
B
Connector for branching (Shielded cord) 1 BK
t° Thi -R3
CNK1 SW5 6
Model FDU 1100FKXZE1
-
8 WH
8 WH FS
TB1 YE/GN 9 WH RD SW4 Outdoor unit address:ones place
9 1
10 WH CNI
10
11 WH
11 BL RD SW5-1 Automatic adjustment/Fixed
12 WH 2
12
61 -
F3 F4 previous version of Superlink protocol
(2A) (2A) For HA Prepare on site
WH +12 1
CNWR CNZ SW5-2 Indoor unit address:hundreds place
2 XR1 (Operation)
WH 1 4 5 6 7 1 4 5 6 7
CNT 3 XR2 (Heating) SW6 Model capacity setting
RD BK WH YE BL RD BK WH YE BL CND BK BL 4 XR3 (Thermo ON)
CNM1 CNM2 5 XR4 (Inspection) SW7-1 Operation check, Drain motor test run
WH BK
L 6
JSL1 XR5(Remote operation TB1 Terminal block (Power source)(□mark)
input:volt-free contact) TB2
FMi1 M FMi2 M Superlink(spare) Terminal block (Signal line)(□mark)
CNK2 Thc Temperature sensor (Remote control)
For heat recovery 3-pipe systems
BK +12 1
RD +12 Thi-A Temperature sensor (Return air)
1 2 XB1 (20S)
DM M WH
CNR CNT2 3 XB2 (SVH)
2 WH RD Thi-R1,2,3 Temperature sensor (Heat exchanger)
4 XB3 (SVG)
5 XB4 (SVE) ■mark Closed-end connector
1 WH WH 1 Color marks
CNG 2 RD 2
PIS Mark Color Mark Color
BL 3 BK 3
4 BK
BK Black WH White
Notes 1. ----- indicates wiring on site. 1 BL Blue YE Yellow
2. Use twin core shielded cord(0.75 - 1.25mm2) at signal line between indoor unit CNV2 2
RD
and outdoor unit, and signal line between indoor units. CNTA BK 3 OR Orange YE/GN Yellow/Green
BL 4 Option ※1
3. Use twin core cord(0.3mm2) at remote control line. 1 2 RD Red
See spec sheet of remote control in case that the total length is more than 100m.
4. Do not put signal line and remote control line alongside power source line. Prepare on site
5. Section 1(※1)shows electric circuit of motion sensor(option).
(Remote operation input:
volt-free contact)
PJG000Z564
'19 • KX-T-310D
Meaning of marks
Item Description
CNA-Z Connector
DM Drain motor
F1-3 Fuse
FMi1,2 Fan motor
FS Float switch
Remote control RD
1 JSL1
ThC WH
X X 1 RD
Thi -R1
2 L Reactor
Y Y 3 WH YE
CNN 3 Indication lamp
A YE Thi -R2
YE
1 4
RD
CNK1
2 WH 5 PIS Motion sensor
Power source line 3-pipe systems Thi -R3 SM
6
between indoor units CNU SW5
RD WH between indoor units SW1
Power source 1
1 Phase SW6 CNH Thi -A SW2
2
SW3
SW7 1
WH SW4
1 WH
RD RD T1 1 YE
L 2 WH 2
Power source line 2 SW1 SW2 SW3 SW4 SW5-1
WH T2 Power circuit 3 WH OR
N 3 3
4 WH
4 4
M SM
5 WH CNA
Models FDU1800FKXZE1, 2400FKXZE1
CNW1 5
6 WH RD 5
WH 6 SW5-2
Earth 7 WH RD
7 CNW2 6
8 WH
8 WH SW6
9 WH FS
9 RD
10 WH For HA 1
-
10 SW7-1
11 WH CNI
11
12 WH CNZ WH RD
12 2
F1 F2 Prepare on site
1
62 -
2 XR1 Thc Temperature sensor(Remote control)
T3 T4 6 4 3 2 1 1 4 5 6 7
CND 3
CNT XR2 Thi-A Temperature sensor(Return air)
YE YE 4 XR3
YE WH RD CNM1 RD WH YE CNM2 Thi-R1,2,3 Temperature sensor(Heat exchanger)
5 XR4
WH 6 Closed-end connector
L JSL1
M FM2 Color marks
CNK2 1 Color
CNM 6 4 3 2 1 Option 2
WH RD 1 CNT2 3
DM M WH CNR RD 4
CNFM 2 WH
1 3 5 5
WH OR
WH RD
1 WH WH 1 RD Red
CNFM2 CNG 2 RD 2
PIS
WH RD WH 3 3
WH White
4
YE Yellow
1
FMi1 M CNV2 2
RD
CNTA 3
4 Option
1 2
Notes 1. ----- indicates wiring on site.
2. Use twin core shielded cord(0.75 - 1.25mm2) at signal line between indoor unit
and outdoor unit, and signal line between indoor units. Prepare on site
3. Use twin core cord(0.3mm2) at remote control line.
See spec sheet of remote control in case that the total length is more than 100m.
4. Do not put signal line and remote control line alongside power source line.
5. Circuit option in (※1) is not included as standard from factory.
This circuit is an option when using drain up kit.
6. Section 1(※2)shows electric circuit of motion sensor(option).
PJG000Z565
'19 • KX-T-310D
'19 • KX-T-310D
4. NOISE LEVEL
Note (1) The data are based on the following conditions.
Ambient air tempetature: Indoor unit 27˚C DB, 19˚C WB. Outdoor unit 35˚C DB
(2) The data in the chart are measuted in an unechonic room.
(3) The noise levels measured in the field are usually higher than the data because of reflection.
(1) Ceiling cassette-4 way (FDT)
1.5m
Measured based on JIS B 8616 Mike (center & low points)
Mike position as right
40 40 40 40 40 40
N40 N40 N40
30 30 30 30 30 30
N30 N30 N30
20 20 20 20 20 20
N20 N20 N20
10 10 10 10 10 10
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
Mid octave band frequency (Hz) Mid octave band frequency (Hz) Mid octave band frequency (Hz)
FDT90KXZE1 FDT112,140,160KXZE1
Noise level 49dB(A) at P-Hi Noise level 49dB(A) at P-Hi
Sound pressure level (dB)
60 60 60 60
N60 N60
(Standard 2×10 -5 Pa)
50 50 50 50
N50 N50
40 40 40 40
N40 N40
30 30 30 30
N30 N30
20 20 20 20
N20 N20
10 10 10 10
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
Mid octave band frequency (Hz) Mid octave band frequency (Hz)
- 63 -
'19 • KX-T-310D
1.5m
Measured based on JIS B 8616 Mike (Center & low points)
Mike position as right
40 40 40 40 40 40
N40 N40 N40
30 30 30 30 30 30
N30 N30 N30
20 20 20 20 20 20
N20 N20 N20
10 10 10 10 10 10
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
Mid octave band frequency (Hz) Mid octave band frequency (Hz) Mid octave band frequency (Hz)
FDTC45KXZE1 FDTC56KXZE1
Noise level 43dB(A) at P-Hi Noise level 47dB(A) at P-Hi
Sound pressure level (dB)
Sound pressure level (dB)
60 60 60 60
N60 N60
(Standard 2×10-5 Pa)
(Standard 2×10 -5 Pa)
50 50 50 50
N50 N50
40 40 40 40
N40 N40
30 30 30 30
N30 N30
20 20 20 20
N20 N20
10 10 10 10
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
Mid octave band frequency (Hz) Mid octave band frequency (Hz)
50 50 50 50 50 50
N50 N50 N50
(Standard 2×10-5 Pa)
(Standard 2×10 -5 Pa)
40 40 40 40 40 40
N40 N40 N40
30 30 30 30 30 30
N30 N30 N30
20 20 20 20 20 20
N10 N20 N10 N20 N20
N10
10 10 10 10 10 10
0 0 0 0 0 0
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
Mid octave band frequency (Hz) Mid octave band frequency (Hz) Mid octave band frequency (Hz)
- 64 -
'19 • KX-T-310D
level (dB)
(dB)
5050
(dB)
(dB)
5050 5050
N5
N500 N5
N500
2×10-5 Pa)
Pa)
2×10-5 Pa)
Pa)
1.5m
pressure level
4040 4040
pressure level
level
4040 4040
Mike (Center & low point)
-5
-5
N4
N400 N4
N400
(Standard 2×10
(Standard 2×10
3030 3030 3030 3030
Sound pressure
Sound pressure
N3
N300 N3
N300
(Standard
(Standard
2020 2020 2020 2020
NN
1010 N2
N200 NN
1010 N2
N200
Sound
Sound 00 00 00 00
1m
1m
6363 125
125 250
250
Measured
Measured
500
500
2000
based
1000
based
1000
2000 4000
4000 8000
8000
on
on JIS
JIS B
B638616
63 8616
125
125 250
250 500
500 1000
1000 2000
2000 4000
4000 8000
8000Air
Air Unit
Unit
Mid
Midoctave
octaveband
bandfrequency
frequency (Hz)
(Hz) as Mid
Midoctave
octaveband
bandfrequency
frequency(Hz) (Hz) Return
Returnduct
duct Su
Su
Mike
Mike position
position as right
right 1.5m
1.5m
Mike
Mike
(5) Duct connected-High static pressure type (FDU)
FDU45,56KXE6F
FDU45,56KXE6F
FDUM22,28,36,45,56KXE6F
FDUM22,28,36,45,56KXE6F FDU71KXE6F,90KXE6F
FDU71KXE6F,90KXE6F
FDU71,90KXE6F
FDU71,90KXE6F FDU112K
FDU112
Measured based on JIS B 8616
Noise
Noiselevel
Noise
Noise 3737
level
level
leveldBdB
37
37(A)
(A)
dB
dB at
(A)at
P-HIGH
(A) P-HIGH
at
at P-HIGH
P-HIGH Noise
Noise
Noise
Noise level
level
level 38
level38
38dB
38 dB
dB
dB(A)
(A)atat
(A)
(A) P-HIGH
at
at P-HIGH
P-HIGH
P-HIGH Noise
Noise lev
le
Mike position as below
3232
dBdB
32
32(A)
(A)
dB
dB at
(A)at
HIGH
(A) HIGH
at
at HIGH
HIGH 3333
33dBdB(A)
dB (A)atat
(A) atHIGH
HIGH
HIGH
1m 2m 2929
dBdB
29
29(A)
(A)
dB
dB at
(A)at
MEDIUM
(A) MEDIUM
at
at MEDIUM
MEDIUM 2929
29dBdB(A)
dB (A)atat
(A) atMEDIUM
MEDIUM
MEDIUM
Air
2626
dBdB
26
26(A)
(A)
dB
dB at
(A)at
LOW
(A) LOW
at
at LOW
LOW 2525
25dBdB(A)
dB (A)atat
(A) atLOW
LOW
LOW
Unit 60 60
60 60
60 60 606060
(dB)
-5-5 (dB)
(dB)
(dB)
60 60
6060 60 60 60
60
(dB)
level (dB)
60
(dB)
level (dB)
level (dB)
-5 (dB)
N
NN 60N60 NNN60
60 N
6060
Return duct Supply duct 6060
Pa)
(Standard 2×10 Pa)
Pa)
-5 Pa)
Pa)
2×10-5-5 Pa)
'121.5m
• KX-DB-175
Pa)
-5Pa)
Pa)
(standard 2×10 Pa)
50 50
50 5050 50 50
50 50 505050
pressure level
level
50 50
level
pressure level
50 50 50
50
pressure level
level
-5-5
N
NN
5050N50
50 NN
50 N
N50
5050
-5
1.5m
2×10
2×10
2×10
(Standard 2×10
2×10
2×10
2×10
40 40
40
40 4040 40
40 40
40 40
40 404040
40
Mike (Center & low point) 40
40
pressure
Sound pressure
pressure
pressure
pressure
Sound pressure
Sound pressure
N
NN
4040N40
40 NN
40 N
4040
N40
M)
(Standard
(Standard
(Standard
(Standard
(standard
(standard
(standard
30
30 30
30 30
3030 30 30
30 30
30 303030
30 30
30
1m 2m NN NN
30 N
N
3030N30
30 3030
N30
Air Unit 20
20 20
20 20
2020 20 20 20 20 20
20
20 20
20 20
20
Sound
Sound
Sound
Sound
Sound
Sound
Sound
Return duct Supply duct N2
N2
N2000N20 N2
N20N2
N200 0
1.5m 10 10
10
10 10
1010 10 10
10 10
10 1010
10
10 10
10
63 63 125 125 250 250 500 500 10001000 20002000 40004000 80008000
Mike (at center & below unit) 63
63 63 125
63 125 125 250
125 250
250 250 500
500
500 5001000
1000
100010002000
2000 4000
200020004000 8000
8000
40004000 80008000 63
63 125
125 250
250 500
500 1000
1000 2000
2000 4000
4000 8000
8000 63
63 125
125
Mid
Mid
Mid octave
octave
octave
octave band
band
band
band frequency
frequency
frequency
frequency (Hz)
(Hz)(Hz)
(Hz) Mid
Mid
Mid
Mid octave
octave
octave
octaveband
band
band
bandfrequency
frequency
frequency
frequency(Hz)
(Hz)
(Hz)
(Hz) Mid
Mid oc
oc
FDU112KXE6F
FDU112KXE6F
FDU112KXE6F FDU140KXE6F
FDU140KXE6F
FDU140KXE6F
FDU140KXE6F FDU160KXE6F
FDU160KXE6F
FDU160KXE6F
FDU160KXE6F
B (A) at P-HIGH Noise
Noise
Noise level 44
level
level dB
4444
dB (A)
dB (A)
(A) at P-HIGH
atat P-HIGH
P-HIGH Noise
Noise
Noise
Noise level
level
level
level 4545
45dBdB(A)
dB (A)atat
(A) atP-HIGH
P-HIGH
P-HIGH Noise
Noise
Noise
Noise level
level
level
level 4747
47dBdB(A)
dB (A)atat
(A) atP-HIGH
P-HIGH
P-HIGH
B (A) at HIGH 38 dB
38 (A)
dB (A)at HIGH
at
38 dB (A) at HIGHHIGH 4040dB
40 dB
dB(A)
(A)atatat
(A) HIGH
HIGH
HIGH 4040dB
40 dB
dB(A)
(A)atatat
(A) HIGH
HIGH
HIGH
B (A) at MEDIUM 36 dB
3636
dB (A)
dB (A)
(A) at MEDIUM
atat MEDIUM
MEDIUM 3434
34dBdB
dB(A)
(A)atat
(A) MEDIUM
at MEDIUM
MEDIUM 3535
35dBdB
dB(A)
(A)atat
(A) MEDIUM
at MEDIUM
MEDIUM
B (A) at LOW 30 dB
3030
dB (A)
dB (A)
(A) at LOW
atat LOW
LOW 2929
29dBdB
dB(A)
(A)atat
(A) LOW
at LOW
LOW 3030
30dBdB
dB(A)
(A)atat
(A) LOW
at LOW
LOW
60 60 60 60
60 60 60
60 60 60 60
60 60
60 60 60 60
60
(dB)
60 60
(dB)
(dB)
(dB)
(dB)
60 60 60
level (dB)
(dB)
level (dB)
-5 (dB)
level (dB)
-5 (dB)
N60 N60
60N60 NN60
N60N60
60 N
NN60
60N60
60
Pa)
Pa)
'14 • KX-T-222
Pa)
Pa)
-5 Pa)
Pa)
(standard 2×10-5 Pa)
Pa)
(standard 2×10 Pa)
Pa)
(standard 2×10 Pa)
50 50 50 50
50 50 50
50 50 50 50
50 50 50 50 50
50
50
'14 • KX-T-222
50 50 50 50
50
pressure level
pressure level
pressure level
level
level
level
-5
N 50N50
-5-5
-5-5
-5
2×10
2×10
2×10
2×10
2×10
2×10
2×10
2×10
40 40 40 40 40
40 40 40
40 40
40 40 40
40
40 40
40 40
40 40 40
40
40
Sound pressure
pressure
pressure
pressure
pressure
pressure
Sound pressure
Sound pressure
N
N40 N N40N40 N N40
N40 40 40 NN4040 NN40
40
40
5.5.NOISE
NOISE LEVEL
(Standard
(Standard
(Standard
(Standard
(Standard
(standard
(standard
(standard
30 30 30 30 30
30 30 30
30 30
30 30 30
30
30 30
30 30
30 30 30
30
30
N30
LEVEL
Notes(1)
20 The data
20 20
20 are based on the following conditions. 20
20 20
20
20
N30N30
N30
20 20
20 20
20
20
N30
NNN3330
00
20
20
20 20
N
NN330N030
30
20 20
20
20
Sound
Sound
Sound
Sound
Sound
Sound
Sound
Sound
N20 Notes(1) The data are based on the following conditions. N2 N2 N20N20 N2 0N2
Ambient air temperature: Indoor unit 27℃WB. Outdoor N200 0 unit 35℃DB. N2
N200 N2 0 0
Ambient air temperature: Indoor unit 27℃WB. Outdoor unit 35℃DB.
10
(2) The data
10 10 in
63 the
10
chart
63 125 are measured
125 250 in an2000
anechoic
2000 40004000room.
10
10 10 10
10 10 10 10
10
10 10
10 10 10 10
10
10
1000 2000 4000 8000 (2) The data63in the125 chart are250
250
500 500 1000
measured
500 in1000
1000 an anechoic
2000 room.
4000
80008000
8000 636363 125
63 125125 250
125 250 500
250
250 500 1000
500
500 1000 2000
1000
1000 2000 4000
2000
2000 4000 8000
4000
4000 8000
8000
8000 63
6363 125
63 125125 250
125 250250 500
250 500 1000
500
500 1000 2000
1000
1000 2000 4000
2000
2000 4000 8000
4000
4000 8000
8000
8000
(3) The noise levels
(3) The noise Mid Mid measured
octave
octave bandinthe
thefrequency
inband
field are usually
frequency (Hz)(Hz)higher than the dataMid because
Midoctave of reflection.
ofoctave band
band frequency
frequency (Hz)
(Hz) Mid
Midoctave
octave
band
band
frequency
frequency
(Hz)
(Hz)
d frequency (Hz) levels measured field Mid octave band frequency (Hz)
are usually higher than the data because reflection. Mid
Mid octave
octave band
band frequency
frequency (Hz)
(Hz) Mid
Mid octave
octave band
band frequency
frequency (Hz)
(Hz)
5.1
5.1 Duct
Duct connected-High staticpressure
connected-High static pressure type
type (FDU)
(FDU)
B (A) at P-HIGH FDU224, 280KXZE1
FDU224KXZE1, 280KXZE1
FDU224KXZE1, 280KXZE1
B (A) at HIGH
Noise
Noise level 52dB(A)
level 52dB (A)atatP-High
P-High Power
Power levellevel
B (A) at MEDIUM Measurement conditions
Measurement : JIS B: 8616
conditions JIS B 8616
50dB
50dB(A)
(A)atatHigh
High
B (A) at LOW 47dB
Measurement location
Measurement : reverberation
location chamber
: reverberation chamber
60
47dB(A)
(A)atatMedium
Medium
45dB (A) atatLow MODEL
MODEL dB(A)dB(A)
N60
45dB (A) Low 60
60
FDU224KXZE1
(dB)
60
FDU224KXZE1
level(dB)
50 N60 60
75
Pa)
N60
N50
FDU280KXZE1 75
2×10 -5Pa)
50
50 50
50
FDU280KXZE1
pressurelevel
40 N50
Note (1) Values are for external static pressure of 200Pa.
-5
N50
N40 Note (1) Values are for external static pressure of 200Pa.
(Standard2×10
40 40
30 40 40
Soundpressure
N40
N3 0 N40 Measured based on JIS B 8616
30 30
Measured
position based on JIS B 8616
(Standard
20 30 N30 30 Mike
N20
20 N30 20 Mike position
1m 2m
10 20 N20 20 1m 2m
Sound
(6) Duct
(7) Duct connected-Low/Middle
connected-Low/Middle staticstatic pressure
pressure type (FDUM)
type (FDUM)
1m 2m
Air Unit
Return duct Supply duct
Measured based on JIS B 8616 1.5m
Mike position as right Mike (Center & below unit)
40 40 40 40 40 40
N40 N40 N40
30 30 30 30 30 30
N30 N30 N30
20 20 20 20 20 20
N20 N20 N20
10 10 10 10 10 10
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
Mid octave band frequency (Hz) Mid octave band frequency (Hz) Mid octave band frequency (Hz)
FDUM140KXE6F FDUM160KXE6F
Noise level 45 dB (A) at P-HIGH Noise level 47 dB (A) at P-HIGH
40 dB (A) at HIGH 40 dB (A) at HIGH
34 dB (A) at MEDIUM 35 dB (A) at MEDIUM
29 dB (A) at LOW 30 dB (A) at LOW
60 60
Sound pressure level (dB)
60 60
N60 N60
(Standard 2×10 -5 Pa)
50 50 50 50
N50 N50
40 40 40 40
N40 N40
30 30 30 30
N 30 N3 0
20 20 20 20
N20 N20
10 10 10 10
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
Mid octave band frequency (Hz) Mid octave band frequency (Hz)
(a) Mike position : 1.5m bwlow the unit FDUT71KXE6F-E
Measured based on JIS B 8616 ANNEX3 (Duct setting) Noise level 35 dB (A) at HIGH
Mike position as right 31 dB (A) at MEDIUM
28 dB (A) at LOW
1m 2m
60
Sound pressure level (dB)
60
N60
(Standard 2×10 -5 Pa)
Air Unit
50 50
Return duct Supply duct N50
1.5m
40 40
N40
30 30
N30
20 20
N10 N20
10 10
63 125 250 500 1000 2000 4000 8000
(b) Mike position : 1m in front and 1m below of the air supply duct FDUT71KXE6F-E
Measured based on JIS B 8616 ANNEX3 (Duct setting) Noise level 41 dB (A) at HIGH
Mike position as right 37 dB (A) at MEDIUM
32 dB (A) at LOW
50
Sound pressure level (dB)
1m 2m 1m 50
N50
(Standard 2×10 -5 Pa)
Air Unit 40 40
N40
1m
20 20
N10 N20
- 90 - 10 10
0 0
63 125 250 500 1000 2000 4000 8000
(Standard
souud press
30 30
N30
20 20
N20
10
N10
10
'19 • KX-T-310D
63 125 250 500 1000 2000 4000 8000
1m
Mike
Measured based on JIS B 8616 (Center & low points)
1m
1m
Mike
Mike position (Center & low point)
FDK22,28KXE6F FDK36KXE6F FDK45KXE6F
Noise level 38〔38〕dB (A) at P-HIGH Noise level 48〔42〕dB (A) at P-HIGH Noise level 48〔43〕dB (A) at P-HIGH
FDK15KXZE1 35〔35〕dB (A) at HIGH FDK22,28KXZE1 41〔39〕dB (A) at HIGH FDK36KXZE1 42〔42〕dB (A) at HIGH
Noise level 38dB(A) at P-Hi
33〔33〕dB (A) at MEDIUM Noise level Cooling 38dB(A)
35〔35〕dB (A) atatMEDIUM
P-Hi Noise level Cooling 40dB(A)
37〔37〕dB at P-Hi
(A) at MEDIUM
31〔31〕dB (A) at LOW Heating 38dB(A)
31〔31〕dB (A) at LOW Heating 40dB(A)
33〔33〕dB (A) at LOW
70 70 70 × cooling ○ heating
70 70 × cooling ○ heating
70
60 60 60 60 60 60
souud pressure level (dB)
N7 0
(dB)
N7 0 N7 0
N60 N60 N60
-5 Pa)
(Standard 2×10-5 Pa)
level
50 N50
50 50 N5500 50 N50 50
2×10
N50 N5 0 N50
40 40 40 40 40 40
pressure
40
40 N40 40
N4400 40
N40 40
N40 N4 0 N40
(Standard
30 30 30 30 30 30 30 30 30 30 30 30
N 30 N30 N3 0 N30 N30N30
20 20 20 20 20 20 20 20
20 20 20 20
souud
N 20 N2 0
N10 N20 N10 N20 N10 N20
N2 0
10 10 10 10 10 10
63 10125 250 500 1000 2000 4000 8000 10 63 10 125 250 500 1000 2000 4000 8000
10 63
10 125 250 500 1000 2000 4000 8000
10
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
Mid octave band frequency (Hz) Mid octave band frequency (Hz) Mid octave band frequency (Hz)
Mid octave band frequency (Hz) Mid octave band frequency (Hz) Mid octave band frequency (Hz)
FDK56KXE6F FDK71KXE6F
Note (1) Value in 〔 〕are for the heating mode.
Noise level 48〔47〕dB (A) at P-HIGH Noise level 48〔48〕dB (A) at P-HIGH
46〔46〕dB (A) at HIGH 47〔47〕dB (A) at HIGH
FDK45KXZE1 42〔42〕dB (A) at MEDIUM FDK56KXZE143〔43〕dB (A) at MEDIUM FDK71KXZE1
37〔37〕dB
Noise level Cooling (A) at LOW
43dB(A) P-Hi 39〔39〕dB
Noise level Cooling (A) atatLOW
43dB(A) P-Hi Noise level Cooling 42dB(A) at P-Hi
60 Heating
× 43dB(A)
cooling ○ heating
60 60 Heating 44dB(A) 60
Heating 42dB(A)
souud pressure level (dB)
N60 N60
Sound pressure level (dB)
70 70 70 70 70 70
(Standard 2×10-5 Pa)
N7 0 N7 0
(Standard 2×10-5 Pa)
40 30 40 30 40 30 40 30 40 40
N40 N30 N4 0 N3 N40
0
30 30 30 30 30 30
20 N3 0 20 20 N3 0 20 N3 0
N10 N20 N10 N20
20 20 20 20 20 20
10 N20
10 10 N 20 10 N2 0
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
10 10 10 10 10 10
63 125 Mid250octave
500 band
1000 frequency
2000 4000 (Hz) 8000 63 Mid octave
125 250 500 band
1000 frequency
2000 4000 (Hz) 8000 63 125 250 500 1000 2000 4000 8000
Mid octave band frequency (Hz) Mid octave band frequency (Hz) Mid octave band frequency (Hz)
FDK90KXZE1
Noise level Cooling 44dB(A) at P-Hi
Heating 44dB(A)
Sound pressure level (dB)
70 70
N70
(Standard 2×10-5 Pa)
60
N60
60 - 93 -
50 50
N 50
40 40
N 40
30 30
N30
20 20
N20
10 10
63 125 250 500 1000 2000 4000 8000
- 67 -
L '19 • KX-T-310D
e following conditions.
L 4. NOISE
: Indoor unit 27℃WB. Outdoor unit 35℃DB. LEVEL
measured in an anechoic room. (9) Ceiling suspended type (FDE) Unit
ed in the field
e following are usually higher
conditions. than theThe
Notes(1) data because
data of reflection.
are based on the following conditions.
1m
: Indoor unit 27℃WB. Outdoor unit 35℃DB. Ambient air temperature: Indoor unit 27℃WB. Outdoor unit 35℃DB.
Measured based on JIS
on B 8616 1m
measured in an anechoic room. (2) TheMeasured
data in the chartbased
are measured JIS B 8616room.Unit
in an anechoic Unit
(3) Mike
TheMike
ed in the field are usually higher than the data
position
noise position
levels
because
as right
as right
measured in
of reflection. the field are usually higher than the data because of reflection.
1m
1m
Mike (in1m
front & below unit) 1m
Measured based on JIS B 8616 Measured based on JIS B 8616
(1) Indoor units Mike position as right
FDE45, 56KXZE1
Mike position as right FDE71KXZE1
Mike (in front47
& dB
below Mike (in front & below unit)
A) at P-HIGH Noise level 46 dB (A) at P-HIGH Noise level (A)unit)
at P-HIGH
A) at HIGH FDE36KXZE1
FDE45, 38 dB (A) at HIGH
56KXZE1 FDE45,
FDE71KXZE1 39
56KXZE1 dB (A) at HIGH FDE71KXZE1
A) at MEDIUM 36 dB
Noise level (A)(A)
46 dB at MEDIUM
at P-HIGH Noise level 37 46dB
dB(A)
(A) at
at MEDIUM
P-HIGH Noise level 47 dB (A) at P-HIGH
A) at P-HIGH Noise level 46 dB (A) at P-HIGH Noise level 47 dB (A) at P-HIGH
A) at LOW 31 dB (A)(A)
38 dB at LOW
at HIGH 32
38dB
dB(A)
(A) at
at LOW
HIGH 39 dB (A) at HIGH
A) at HIGH 60 38 dB (A) at HIGH 60 39 dB (A) at HIGH 60
60
31 dB (A) at MEDIUM 60
36 dB (A) at MEDIUM 37 dB (A) at MEDIUM
level (dB)
level (dB)
A) at MEDIUM
N60
36 dB (A) at MEDIUMN60
37 dB (A) at MEDIUMN60
10 Pa)
2×10-5 Pa)
(dB)-5
60 60
N50 N
(Standard 2× 10 -5 Pa)
60 60
(Standard 2× 10-5 Pa)
60 60 60
2× 10 -5 Pa)
2×10-5 Pa)
40 40 40 40 50 40
2×
50 50 50 50 50
pressure
pressure
(Standard
(Standard
Sound Sound
Sound Sound
N60
A) at MEDIUM
N60
40 dB (A) at MEDIUM
2× 10-5 Pa)
60 60 60 60
Sound pressure level (dB)
Sound pressure level (dB)
50 50
60 60 50 60 50 50 50
level (dB)
40 40
pressure
N40 50 50 40
N40 50 40 40
40
(Standard
N20 30 30 20 N20 30 20 20 20
10 10 N30N2010 N20
N30
000 2000 4000 8000 63 10 125 250 500 1000 2000 4000 8000 10 10 10
20 20 20
equency (Hz)
N20 Mid63octave
125
band
250
frequency
500 1000 2000
(Hz)
N20
4000 8000 63 125 250 500 1000 2000 4000 8000
Mid octave band frequency (Hz) Mid octave band frequency (Hz)
10 10 10
000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
- 68 -
0 40
40 40 40 Note (1) Values are for external static pressure of 200Pa.
(Standard 2
(Standard 2×1
Sound pressur
Sound pressur
pressure 2l
N40 40 N40
40
Measured
Measured
based onbased
JIS Bon
8616
JIS B 8616
Sound(Standard
30 30 N40 30 30
N30 30 N30
Measured
Mike based
position
Mike on JIS B 8616
position
30
20 20 N30 20 20
Mike position 1m 1m 2m 2m
20 N20 20 N20 1m 2m '19 • KX-T-310D
10 10 N2010 10 Air Air Unit Unit
63 10 125 63250 125500 250
1000 500
2000 1000
4000 20008000 4000
10 8000 Air Unit
Mid
63 octave
125Mid250
band
octave
500frequency
band frequency
(Hz) (Hz) 1000 2000 4000 8000 Return duct
Return duct
Supply duct
Supply duct
Mid octave band frequency (Hz) Return duct Supply duct
(10) Outdoor Air Processing unit (FDU-F) 1.5m 1.5m
Mike (at center
Mike (at
& below
center unit)
& below unit)
1.5m Mike (at center & below unit)
5.25.2Outdoor
5.2
OutdoorOutdoor airair processing
air processing
processing unit
unit(FDU-F)
unit (FDU-F)
(FDU-F)
Notes(1) Values
Notes(1)
are Values
for external
are for
static
external
pressure
staticofpressure
200Pa. of 200Pa.
Notes(1) Values are for external static pressure of 200Pa.
FDU650FKXZE1
FDU650FKXZE1 FDU1100FKXZE1
FDU1100FKXZE1
FDU650FKXZE1 FDU1100FKXZE1
Noise level
Noise31dB
level(A)31dB
at High
(A) at High Noise level
Noise37dB
level(A)37dB
at High
(A) at High
Noise level 31dB (A) at High Noise level 37dB (A) at High
60 60 60 60
Sound pressure level (dB)
60 60 60 60
60 60
(Standard 2×10-5Pa)
(Standard 2×10-5Pa)
(Standard 2×10-5Pa)
(Standard 2×10-5Pa)
50 50 50 50 50 50 50 50
50 50
-5
N50 N50
40 40 40 40 40 40 40 40
40 40 40 40
N40 N40 N40 N40
N40 N40
(Standard
30 30 30 30 30 30 30 30
30 30 30 30
N30N N30 NN30 N30
30 30
20 20 20 20 20 20 20 20
20 20 20 20
Sound
FDU1800FKXZE1
FDU1800FKXZE1
FDU1800FKXZE1 FDU2400FKXZE1
FDU2400FKXZE1
FDU2400FKXZE1
Noise level
NoiseNoise level
level42dB (A)42dB
42dB at High
(A) at(A) at High
High Noise
Noiselevel
Noise level
level 45dB
45dB(A)45dB
(A)atatHigh
(A) at High
High
60 60 60 60 60
Sound pressure level (dB)
60
60 60 60
(dB)
60
60 60
N60N60 N60 NN6600 N60
(Standard 2×10-5-5Pa)
(Standard 2×10-5Pa)
-5Pa)
(Standard 2×10-5Pa)
50 50 50 50 50 50 50
50 50
level
40 40 40 40 40 40 40 40 40 40
40 40
pressure
30 30 30 30 30 30 30 30 30 30
30 30
N30N30 N30
NN3300 N30
20 20 20 20 20 20 20 20 20 20
20 20
Sound
1m
FDU1100FKXZE1 62 FDU2400FKXZE1 70 Return ductReturn duct Supply duct
Supply duct
FDU1100FKXZE1
FDU1100FKXZE1 62 FDU2400FKXZE1
62 FDU2400FKXZE170 70
Note (1) Values are for external static pressure of 200Pa.
Note (1) Values
Note (1)
areValues
for external
are for
static
external
pressure
staticofpressure
200Pa. of 200Pa.
- 18 -
- 18 - 18 -
-
- 69 -
'19 • KT-T-310D
5. CAPACITY TABLES
Caution: In case that the cooling operation during low outdoor air temperature below -5°C is expected, install the outdoor unit
where it is not influenced by natural wind. Otherwise protection control by low pressure will be activated much more
frequently and it will cause insufficient capacity or breakdown of the compressor in worst case.
(1) Ceiling cassette-4 way type (FDT)
FDT28KXZE1 (kW) (kW)
Notes(1) This data shows average statuses out of those possible to occur in the system control.
(Depending on controls, there may be ranges where the operation is not conducted continuously.
(2)
Symbols are as follows
TC :Total cooling capacity(kW)
SHC :Sensible heat capacity(kW)
PJF000Z452 A
- 71 -
'19 • KT-T-310D
Notes(1)
This data shows average statuses out of those possible to occur in the system control.
(Depending on controls, there may be ranges where the operation is not conducted continuously.
(2)
Symbols are as follows
TC :Total cooling capacity(kW)
SHC :Sensible heat capacity(kW)
PJF000Z452 A
- 72 -
'19 • KT-T-310D
Notes(1) This data shows average statuses out of those possible to occur in the system control.
(Depending on controls, there may be ranges where the operation is not conducted continuously.
Symbols are as follows
(2)
TC :Total cooling capacity(kW)
SHC :Sensible heat capacity(kW)
PJF000Z452 A
- 73 -
'19 • KT-T-310D
Notes(1) This data shows average statuses out of those possible to occur in the system control.
(Depending on controls, there may be ranges where the operation is not conducted continuously.
Symbols are as follows
(2)
TC :Total cooling capacity(kW)
SHC :Sensible heat capacity(kW)
PJF000Z452 A
- 74 -
'19 • KT-T-310D
Notes(1) This data shows average statuses out of those possible to occur in the system control.
(Depending on controls, there may be ranges where the operation is not conducted continuously.
Symbols are as follows
(2)
TC :Total cooling capacity(kW)
SHC :Sensible heat capacity(kW)
PJF000Z452 A
- 75 -
'19 • KT-T-310D
Notes(1) This data shows average statuses out of those possible to occur in the system control.
(Depending on controls, there may be ranges where the operation is not conducted continuously.
Symbols are as follows
(2)
TC :Total cooling capacity(kW)
SHC :Sensible heat capacity(kW)
PJF000Z452 A
- 76 -
'19 • KT-T-310D
Notes(1) This data shows average statuses out of those possible to occur in the system control.
(Depending on controls, there may be ranges where the operation is not conducted continuously.
Symbols are as follows
(2)
TC :Total cooling capacity(kW)
SHC :Sensible heat capacity(kW)
PJF000Z452 A
- 77 -
'19 • KT-T-310D
Notes(1) This data shows average statuses out of those possible to occur in the system control.
(Depending on controls, there may be ranges where the operation is not conducted continuously.
Symbols are as follows
(2)
TC :Total cooling capacity(kW)
SHC :Sensible heat capacity(kW)
PJF000Z452 A
- 78 -
'19 • KT-T-310D
Notes(1)
This data shows average statuses out of those possible to occur in the system control.
(Depending on controls, there may be ranges where the operation is not conducted continuously.)
(2) Symbols are as follows
TC :Total cooling capacity(kW)
SHC :Sensible heat capacity(kW)
PJF000Z513
- 79 -
'19 • KT-T-310D
Notes(1)
This data shows average statuses out of those possible to occur in the system control.
(Depending on controls, there may be ranges where the operation is not conducted continuously.)
(2) Symbols are as follows
TC :Total cooling capacity(kW)
SHC :Sensible heat capacity(kW)
PJF000Z513
- 80 -
'19 • KT-T-310D
Notes(1)
This data shows average statuses out of those possible to occur in the system control.
(Depending on controls, there may be ranges where the operation is not conducted continuously.)
(2) Symbols are as follows
TC :Total cooling capacity(kW)
SHC :Sensible heat capacity(kW)
PJF000Z513
- 81 -
'19 • KT-T-310D
Notes(1)
This data shows average statuses out of those possible to occur in the system control.
(Depending on controls, there may be ranges where the operation is not conducted continuously.)
(2) Symbols are as follows
TC :Total cooling capacity(kW)
SHC :Sensible heat capacity(kW)
PJF000Z513
- 82 -
'19 • KT-T-310D
Notes(1)
This data shows average statuses out of those possible to occur in the system control.
(Depending on controls, there may be ranges where the operation is not conducted continuously.)
(2) Symbols are as follows
TC :Total cooling capacity(kW)
SHC :Sensible heat capacity(kW)
PJF000Z513
- 83 -
'19 • KT-T-310D
Notes(1)
This data shows average statuses out of those possible to occur in the system control.
(Depending on controls, there may be ranges where the operation is not conducted continuously.)
(2) Symbols are as follows
TC :Total cooling capacity(kW)
SHC :Sensible heat capacity(kW)
PJF000Z513
- 84 -
'19 • KT-T-310D
PJB001Z731
- 85 -
'19 • KT-T-310D
PJB001Z731
- 86 -
'19 • KT-T-310D
PJB001Z731
- 87 -
'19 • KT-T-310D
PJB001Z731
- 88 -
'19 • KT-T-310D
PJB001Z731
- 89 -
'19 • KT-T-310D
PJB001Z731
- 90 -
'19 • KT-T-310D
PJB001Z731
- 91 -
'19 • KT-T-310D
PJC001Z355
- 92 -
'19 • KT-T-310D
PJC001Z355
- 93 -
'19 • KT-T-310D
Notes (1)
This data shows average statuses out of those possible to occur in the system control.
(Depending on controls, there may be ranges where the operation is not conducted continuously.)
(2)
Symbols are as follows
TC :Total cooling capacity(kW)
SHC :Sensible heat capacity(kW)
PJG000Z054
- 94 -
'19 • KT-T-310D
Notes(1) This data shows average statuses out of those possible to occur in the system control.
(Depending on controls, there may be ranges where the operation is not conducted continuously.)
(2) Symbols are as follows
TC :Total cooling capacity(kW)
SHC :Sensible heat capacity(kW)
PJG000Z054
- 95 -
'19 • KT-T-310D
Notes(1) This data shows average statuses out of those possible to occur in the system control.
(Depending on controls, there may be ranges where the operation is not conducted continuously.)
(2) Symbols are as follows
TC :Total cooling capacity(kW)
SHC :Sensible heat capacity(kW)
PJG000Z054
- 96 -
'19 • KT-T-310D
Notes(1) This data shows average statuses out of those possible to occur in the system control.
(Depending on controls, there may be ranges where the operation is not conducted continuously.)
(2) Symbols are as follows
TC :Total cooling capacity(kW)
SHC :Sensible heat capacity(kW)
PJG000Z054
- 97 -
'19 • KT-T-310D
Notes(1) This data shows average statuses out of those possible to occur in the system control.
(Depending on controls, there may be ranges where the operation is not conducted continuously.)
(2) Symbols are as follows
TC :Total cooling capacity(kW)
SHC :Sensible heat capacity(kW)
PJG000Z054
- 98 -
'19 • KT-T-310D
Notes(1) This data shows average statuses out of those possible to occur in the system control.
(Depending on controls, there may be ranges where the operation is not conducted continuously.)
(2) Symbols are as follows
TC :Total cooling capacity(kW)
SHC :Sensible heat capacity(kW)
PJG000Z054
- 99 -
'19 • KT-T-310D
Notes(1) This data shows average statuses out of those possible to occur in the system control.
(Depending on controls, there may be ranges where the operation is not conducted continuously.)
(2) Symbols are as follows
TC :Total cooling capacity(kW)
SHC :Sensible heat capacity(kW)
PJG000Z054
- 100 -
'19 • KT-T-310D
Notes (1) These data show average statuses out of those possible to occur in the system control.
(Depending on controls, there may be ranges where the operation is not conducted continuously.)
(2) Symbols are as follows
TC :Total cooling capacity (kW)
SHC :Sensible heat capacity (kW)
PJG000Z303
- 101 -
'19 • KT-T-310D
Notes (1) These data show average statuses out of those possible to occur in the system control.
(Depending on controls, there may be ranges where the operation is not conducted continuously.)
(2) Symbols are as follows
TC :Total cooling capacity (kW)
SHC :Sensible heat capacity (kW)
PJG000Z303
- 102 -
'11 • KX-T-165
'19 • KT-T-310D
6 CAPACITY TABLES
(6) Duct connected-Low/Middle static pressure type (FDUM)
PJG000Z022
- 14 -
- 103 -
'11 • KX-T-165
'19 • KT-T-310D
PJG000Z022
- 15 -
- 104 -
'11 • KX-T-165
'19 • KT-T-310D
PJG000Z022
- 16 -
- 105 -
'11 • KX-T-165
'19 • KT-T-310D
PJG000Z022
- 17 -
- 106 -
'11 • KX-T-165
'19 • KT-T-310D
PJG000Z022
- 18 -
- 107 -
'11 • KX-T-165
'19 • KT-T-310D
PJG000Z022
- 19 -
- 108 -
'11 • KX-T-165
'19 • KT-T-310D
PJG000Z022
- 20 -
- 109 -
'11 • KX-T-165
'19 • KT-T-310D
PJG000Z022
- 21 -
- 110 -
'11 • KX-T-165
'19 • KT-T-310D
PJG000Z022
- 22 -
- 111 -
'11 • KX-T-165
'19 • KT-T-310D
PJG000Z022
- 23 -
- 112 -
'19 • KT-T-310D
PJH000Z019
- 113 -
'19 • KT-T-310D
Notes(1) This data show average statuses out of those possible to occur in the system control.
(Depending on controls, there may be ranges where the operation is not conducted continuously.)
(2) Symbols are as follows
TC :Total cooling capacity(kW)
SHC :Sensible heat capacity(kW)
PHA001Z125 B
- 114 -
'19 • KT-T-310D
Notes(1) This data show average statuses out of those possible to occur in the system control.
(Depending on controls, there may be ranges where the operation is not conducted continuously.)
(2) Symbols are as follows
TC :Total cooling capacity(kW)
SHC :Sensible heat capacity(kW)
PHA001Z125 B
- 115 -
'19 • KT-T-310D
Notes(1) This data show average statuses out of those possible to occur in the system control.
(Depending on controls, there may be ranges where the operation is not conducted continuously.)
(2) Symbols are as follows
TC :Total cooling capacity(kW)
SHC :Sensible heat capacity(kW)
PHA001Z125 B
- 116 -
'19 • KT-T-310D
Notes(1) This data show average statuses out of those possible to occur in the system control.
(Depending on controls, there may be ranges where the operation is not conducted continuously.)
(2) Symbols are as follows
TC :Total cooling capacity(kW)
SHC :Sensible heat capacity(kW)
PHA001Z125 B
- 117 -
'19 • KT-T-310D
Notes(1) This data show average statuses out of those possible to occur in the system control.
(Depending on controls, there may be ranges where the operation is not conducted continuously.)
(2) Symbols are as follows
TC :Total cooling capacity(kW)
SHC :Sensible heat capacity(kW)
PHA001Z125 B
- 118 -
'19 • KT-T-310D
Notes(1) This data show average statuses out of those possible to occur in the system control.
(Depending on controls, there may be ranges where the operation is not conducted continuously.)
(2) Symbols are as follows
TC :Total cooling capacity(kW)
SHC :Sensible heat capacity(kW)
PHA001Z125 B
- 119 -
'19 • KT-T-310D
Notes(1) This data show average statuses out of those possible to occur in the system control.
(Depending on controls, there may be ranges where the operation is not conducted continuously.)
(2) Symbols are as follows
TC :Total cooling capacity(kW)
SHC :Sensible heat capacity(kW)
PHA001Z125 B
- 120 -
'19 • KT-T-310D
Notes(1) This data show average statuses out of those possible to occur in the system control.
(Depending on controls, there may be ranges where the operation is not conducted continuously.)
(2) Symbols are as follows
TC :Total cooling capacity(kW)
SHC :Sensible heat capacity(kW)
PHA001Z125 B
- 121 -
'19 • KT-T-310D
Notes(1) This data shows average statuses out of those possible to occur in the system control.
(Depending on controls, there may be ranges where the operation is not conducted continuously.)
(2) Symbols are as follows
TC :Total cooling capacity(kW) PFA004Z045-02
SHC :Sensible heat capacity(kW)
PFA004Z045
- 122 -
'19 • KT-T-310D
Notes(1) This data shows average statuses out of those possible to occur in the system control.
(Depending on controls, there may be ranges where the operation is not conducted continuously.)
(2) Symbols are as follows
TC :Total cooling capacity(kW) PFA004Z045-03
SHC :Sensible heat capacity(kW)
PFA004Z045
- 123 -
'19 • KT-T-310D
Notes(1) This data shows average statuses out of those possible to occur in the system control.
(Depending on controls, there may be ranges where the operation is not conducted continuously.)
(2) Symbols are as follows
TC :Total cooling capacity(kW) PFA004Z045-04
SHC :Sensible heat capacity(kW)
PFA004Z045
- 124 -
'19 • KT-T-310D
Notes(1) This data shows average statuses out of those possible to occur in the system control.
(Depending on controls, there may be ranges where the operation is not conducted continuously.)
(2) Symbols are as follows
TC :Total cooling capacity(kW) PFA004Z045-05
SHC :Sensible heat capacity(kW)
PFA004Z045
- 125 -
'19 • KT-T-310D
Notes(1) This data shows average statuses out of those possible to occur in the system control.
(Depending on controls, there may be ranges where the operation is not conducted continuously.)
(2) Symbols are as follows
TC :Total cooling capacity(kW) PFA004Z045-06
SHC :Sensible heat capacity(kW)
PFA004Z045
- 126 -
'19 • KT-T-310D
Notes(1) This data shows average statuses out of those possible to occur in the system control.
(Depending on controls, there may be ranges where the operation is not conducted continuously.)
(2) Symbols are as follows
TC :Total cooling capacity(kW) PFA004Z045-07
SHC :Sensible heat capacity(kW)
PFA004Z045
- 127 -
'19 • KT-T-310D
Notes(1) These data show average statuses out of those possible to occur in the system control.
(Depending on controls, there may be ranges where the operation is not conducted continuously.)
(2) Symbols are as follows
TC :Total cooling capacity (kW)
SHC :Sensible heat capacity (kW)
(3) When outdoor air temperature is -5℃DB--10℃DB in heating, the supply air temperature
become 10℃ or lower for 5-10minutes after the defrost operation.
PJG000Z312
- 128 -
'19 • KT-T-310D
Notes(1) These data show average statuses out of those possible to occur in the system control.
(Depending on controls, there may be ranges where the operation is not conducted continuously.)
(2) Symbols are as follows
TC :Total cooling capacity (kW)
SHC :Sensible heat capacity (kW)
(3) At heating operation outdoor temperature -5℃DB--10℃DB,a wind of 10℃ or lower in
temperature is blown out for 5-10minutes when starting a outdoor air processing unit after ending
a defrost operation.
PJG000Z312
- 129 -
'19 • KT-T-310D
Notes(1) These data show average statuses out of those possible to occur in the system control.
(Depending on controls, there may be ranges where the operation is not conducted continuously.)
(2) Symbols are as follows
TC :Total cooling capacity (kW)
SHC :Sensible heat capacity (kW)
(3) At heating operation outdoor temperature -5℃DB--10℃DB,a wind of 10℃ or lower in
temperature is blown out for 5-10minutes when starting a outdoor air processing unit after ending
a defrost operation.
PJG000Z312
- 130 -
'19 • KT-T-310D
Notes(1) These data show average statuses out of those possible to occur in the system control.
(Depending on controls, there may be ranges where the operation is not conducted continuously.)
(2) Symbols are as follows
TC :Total cooling capacity (kW)
SHC :Sensible heat capacity (kW)
(3) At heating operation outdoor temperature -5℃DB--10℃DB,a wind of 10℃ or lower in
temperature is blown out for 5-10minutes when starting a outdoor air processing unit after ending
a defrost operation.
PJG000Z312
- 131 -
'19 • KT-T-310D
PJF012D036
201609
6. OPTION PARTS
6.1 Motion sensor kit
(1) FDT series (LB-T-5W-E) PJF012D036 A
WARNING Inst
● Connect the wiring to the PCB in the control box on the indoor unit and hold the wiring ① Loo
securely so as not to apply unexpected stress on the PCB. ② Pas
Loose connection or hold will cause abnormal heat generation or fire. ③ Han
● Make sure the power source is turned off when electric wiring work. ④ Pas
Otherwise, electric shock, malfunction and improper running may occur. ⑤ Con
⑥ Tigh
⑦ Inst
CAUTION ⑧
⑨
Fix
Rein
● Do not install the motion sensor kit at the following places in order to aboid malfunction.
(1) Places exposed to direct sunlight (7) Places where the motion sensor is
(2) Places near heat devices influenced by the fluorescent lamp or
(3) High humidity places sunlight
(4) Hot surface or cold surface enough to (8) Places where the motion sensor is affected
generate condensation by infrared rays of any other
(5) Places exposed to oil mist or steam directly communication devices
(6) Places affected by the direct air flow of the (9) Places where some object may obstruct
Indoor unit. the motion sensor
Attention
Instruct the customer how to operate it correctly referring to the instruction manual.
For the installation method of the air-conditioner itself, refer to the installation manual enclosed in the
package.
Accessories
Please make sure that you have the motion sensor.
Motion sensor
800mm
(A)
- 133 -
D036
201609
'19 • KT-T-310D
6
ed
ct
sed in the
Note: It is not possible to set by the following remote control models or older.
Wired:RC-EX1A, RC-E5, RCH-E3
Wireless: RCN-E1R
- 134 -
'19 • KT-T-310D
PJF012D504
(2) FDTC series (LB-TC-5W-E)
PJF012D504
WARNING Ins
● Connect the wiring to the PCB in the control box on the indoor unit and fix the wiring
① Cu
securely so as not to apply unexpected stress on the PCB.
② Pa
Loose connection or fixing will cause abnormal heat generation or fire.
③ Co
● Make sure the power source is turned off during electrical wiring work. ④ Fix
Otherwise, electric shock, malfunction and abnomal operation may occur. ⑤ Ins
⑥ Ins
CAUTION
● Do not install the motion sensor kit at the following places in order to avoid malfunction.
(1) Places exposed to direct sunlight (8) Places where the motion sensor may be
(2) Places near heat-generating devices affected by infrared rays of any other
(3) High humidity places communication devices
(4) Hot surface or cold surface enough to (9) Places where some object may
generate condensation obstruct the motion sensor
(5) Places directly exposed to oil mist or (10) Places where there may be impact on
steam the motion sensor
(6) Places affected by the direct air flow of (11) Places with strong radio wave or
the indoor unit static electricity
(7) Places where the motion sensor may be (12) Dusty place where the motion sensor
influenced by fluorescent lamp or sunlight lens may become tainted or be damaged
Attention
Instruct the customer how to operate the motion sensor kit correctly by referring to the instruction
manual.
For the installation method of the air-conditioner itself, refer to the installation manual enclosed in
the package.
Accessories
Please make sure that all components are in the package.
Motion sensor
Indoor unit
Motion sensor
'19 • KT-T-310D
800mm
Set
The motion
Set the func
Refer to the
Note: It is no
Wired
Wirele
Height of the ceiling 2.7 3.5 4.0
Slide
② ④
Drain pipe Refrigerant pipes
- 136 -
12D504
'19 • KT-T-310D
n.
may be
other
pact on
or
nsor
amaged
r bag
①
Cut off
at 4 places ②
Hook
Hook
e instruction ③
enclosed in
137 - -
Setting the motion sensor
The motion sensor will not function if it is only installed.
'19 • KT-T-310D
Note: It is not possible to set by the following remote control models or older ones.
Wired:RC-EX1A, RC-E5, RCH-E3
Wireless: RCN-E1R
.0
ut 7.6
ut 9.5
he screws.)
- 138 -
'19 • KT-T-310D
PJB012D311 A
WARNING
● Connect the wiring to the PCB in the control box on the indoor unit and hold the wiring
securely so as not to apply unexpected stress on the PCB.
● Make sure the power supply is turned off when electric wiring work.
Otherwise, electric shock, malfunction and improper running may occur.
CAUTION
● DO NOT install the motion sensor kit at the following places in order to avoid malfunction.
(1) Places exposed to direct sunlight (8) Places where the motion sensor is affected
(2) Places near heat devices by infrared rays of any other communication
(3) High humidity places devices.
(4) Hot surface or cold surface enough to (9) Places where some object may obstruct the
generate condensation motion sensor
(5) Places exposed to oil mist or steam directly (10) Place that the motion sensor have a shock
(6) Places affected by the direct airflow of the (11) Place with the strong radio wave or Static
Indoor unit. electricity
(7) Places where the motion sensor is (12) Place that motion sensor lens become
influenced by the fluorescent lamp or tainted or have damaged. Dusty place.
sunlight.
Attention
• This manual describes how to install the motion sensor kit.
• Instruct the customer how to operate it correctly referring to the instruction manual.
• For the installation method of the air conditioner itself, refer to the installation manual enclosed in the
package.
Accessories
Please make sure that all components are in the package.
- 139 -
'19 • KT-T-310D
Motion sensor
Refrigerant pipe
Drain pipe
Ceiling plane
h
Floor face
0.8
φA
φB
- 140 -
'19 • KT-T-310D
① Remove the corner lid at the location where the motion sensor is to be installed.
Insert a tool into the dented part and turn the tool wrench slightly not to damage the frame.
② Cut off the slit on the side of the panel (round hole (φ25), B side), install the grommet in the accessories.
③ After inserting the wiring of the motion sensor at hole (B side), install the motion sensor by snapping the
hook (2 places) from outer edge into the frame.
④ Insert the wiring as shown in the panel ceiling rear side drawing and secure the wiring with the wiring clamps
in the accessories and screws.
Piping side
Hole (B side)
Hole (B side)
- 141 -
'19 • KT-T-310D
Clip
Note: It is not possible to set by the following remote control models or older.
Wired:RC-EX1A, RC-E5, RCH-E3
Wireless: RCN-E1R
- 142 -
PFA012D633
'19 • KT-T-310D
201802
WARNING Insta
● Connect the wiring to the PCB in the control box on the indoor unit and hold the wiring Motion se
securely so as not to apply unexpected stress on the PCB. CAUTION
Loose connection or hold will cause abnormal heat generation or fire.
● Make sure the power source is turned off when electric wiring work. ① Remo
Otherwise, electric shock, malfunction and improper running may occur.
CAUTION
● Do not install the motion sensor kit at the following places in order to avoid malfunction. ② Insert
(1) Places exposed to direct sunlight (8)
(8) Places
Placeswhere
wherethethemotion
motionsensor
sensorisisaffected
affected paintw
(2)
(2) Places
Placesnear
nearheat
heatdevices
devices by
byinfrared
infraredrays
raysofofany
anyother
othercommunication
communication ③ Conn
(3)
(3) High
Highhumidity
humidityplaces
places devices.
devices conne
(4) Hot surface or cold surface enough to (9)
(9) Places
Placeswhere
wheresome
someobject
objectmay
mayobstruct
obstructthe
the correc
generate condensation motion
motionsensor
sensor
CAUTION
(5) Places exposed to oil mist or steam directly (10) Place
Placethat
thatthe
themotion
motionsensor
sensorhave
haveaashock
shock
(6) Places affected by the direct air flow of (11) Place
Placewith
withthe
thestrong
strongradio
radiowave
waveororStatic
Static
unit.
the Indoor unit electricity
electricity
(7) Places where the motion sensor is (12) Place
Placethat
thatmotion
motionsensor
sensorlens
lensbecome
become
influenced by the fluorescent lamp or tainted
taintedororhave
havedamaged.
damaged.Dusty
Dustyplace.
place
sunlight.
sunlight
● Do not leave the motion sensor without the cover.
In case the cover needs to be detached, protect the motion sensor with a packaging or bag.
bag
In order
in order to
to keep
keep itit away
away from water and dust.
Attention
• This manual describes how to install the motion sensor kit.
• Instruct the customer how to operate it correctly referring to the instruction manual. ④ Instal
Place
• For the installation method of the air-conditioner itself, refer to the installation manual enclosed in the
package. motio
CAUTION
Accessories
Please make sure that all components are in the package.
Wirin
Motion sensor (ø) Manual
① Conn
and b
Attached wiring to the motion sensor kit
② Fix th
③ Conn
④ Conn
ø Wiring from the motion sensor and the attached wiring to the
motion sensor kit have been connected when shipped from the
factory.
Remove the connector at the position of mark and connect it
to the attached wiring to the indoor unit before use.
Note
Ceiling plane
Wall
surface
h
Floor
face
0.8
A
φA
B
φB
- 144 -
33 '19 • KT-T-310D
01802
② Insert a tool into the dented part (2 places) of the panel cover, and wrench slightly not to damage the
paintwork of the panel to remove the cover.
③ Connect the wiring from the panel’s hole (attached to the indoor unit, color of the wiring: white, red and black,
connector: 3P, white) to the wiring from the motion sensor. Make sure to install the motion sensor in the
correct direction.
CAUTION: Do not remove the clamp fixed the wiring.
Note: It is not possible to set by the following remote control models or older.
Wired:RC-EX1A, RC-E5, RCH-E3
Wireless: RCN-E1R
- 146 -
PJZ012D122
PJZ012D122
'19 • KT-T-310D
201802
201802
Attention
Attention
• This manual describes how to install the motion sensor kit.
• This manual describes how to install the motion sensor kit.
• Instruct the customer how to operate it correctly referring to the instruction manual.
• Instruct the customer how to operate it correctly referring to the instruction manual.
• For the installation method of the air-conditioner itself, refer to the installation manual enclosed in the
• For the installation method of the air-conditioner itself, refer to the installation manual enclosed in the
package.
package.
⑥U
⑥U
Accessories
Accessories
w
w
Op
Installing the
Installing the motion
motion sensor
sensor Op
▶ Sel
▶ Sel
scre
• The recommended height is lower than 4000 mm for motion sensor. When the installation height is higher,
• The recommended height is lower than 4000 mm for motion sensor. When the installation height is higher, scre
motion detection accuracy might be reduced. - 147 -
motion detection accuracy might be reduced. ①R
• Sensor will detect the object with a different temperature from the surrounding. ①R
• Sensor will detect the object with a different temperature from the surrounding. (T
• Motion sensor is more sensitive to motions in the direction of
• Motion sensor is more sensitive to motions in the direction of
mark.
mark. ② (T
Pu
② Pu
In case of CnL connector In case of CnL connector
on the indoor unit PCB is not on the indoor unit
(FDT/FDK/FDTC) PCB ⑦P
'19 • KT-T-310D c
⑧S
w
ø Please prepare a relay wiring for connecting the motion sensor and indoor unit on site. (0.2 mm2 or ⑨T
thicker, triplex (red, white and black) cable for communication, with the maximum length of 8 m.) s
a
Op
Installing the motion sensor
▶ Se
• The recommended height is lower than 4000 mm for motion sensor. When the installation height is higher, scr
motion detection accuracy might be reduced.
• Sensor will detect the object with a different temperature from the surrounding. ①R
(
• Motion sensor is more sensitive to motions in the direction of mark. ②P
• Sensor may not detect small children or infants with little motion.
• Although motion sensor can be installed on a wall, it is recommended to install it on the ceiling plane.
• If the sensor is installed on the wall, the sensing distance in the front direction is about 5 m, covering the
angle of about 100 degrees.
Op
Floor face
①S
Height of the ceiling h (m) 2.7 3.5 4.0 r
0.8
a
φA Detectable area φ A (m) 4.5 6.4 7.6 S
Detectable area φ B (m) 6.4 8.3 9.5 p
φB
- 148 -
122
'19 • KT-T-310D
201802
Option (A)
Lower case
Upper case
Screw
Ceiling plane
Relay wiring
Lower case Installing hole
Installing hole
Screws
⑥ Using a crimping terminal, etc., connect the same color to the relay wiring (prepare on site) and the
wiring of motion sensor.
White White
Red Connect Red
wirings with the
Black same colors Black
l Relay wiring Wiring from the
motion sensor Sensor board
Option (B)
▶ Select this method if the ceiling plane has sufficient strength to install the motion sensor directly with
gher, screws.
- 149 -
① Remove the screw at the side of the motion sensor and slide the upper case in the direction of the arrow.
(The same as ② of Option (A))
② Pull the wiring of the motion sensor toward the side. Cut off the thinner part of the upper case.
⑦ Place the connecting part inside of the Relay wiring Caution:
ceiling space. Connecting part In order to prevent
⑧ Seal the wiring hole on the lower case tracking,'19
be sure to
• KT-T-310D
with putty. perform construction
⑨ Taking care not to pinch the wirings, so as not to clog up
slip the upper case into the lower case, the connecting part
and tighten the screws. with dust, etc.
Option (B)
▶ Select this method if the ceiling plane has sufficient strength to install the motion sensor directly with
igher, screws.
① Remove the screw at the side of the motion sensor and slide the upper case in the direction of the arrow.
(The same as ② of Option (A))
② Pull the wiring of the motion sensor toward the side. Cut off the thinner part of the upper case.
Lower case Thinner part
e.
g the
Upper case
- 150 -
'19 • KT-T-310D
●
Installing hole
⑤ Fix the lower case to switch box using the installing Switch box installing hole
hole (1 place).
Fix to the
switch box
Lower case
Installing hole
Install to the
Switch box ceiling plane
Installing hole
⑧ Taking care not to pinch the wirings, slip the upper Indo
case into the lower case, and tighten the screws.
(The same as ⑨ of Option (A))
①P
② Au
①+
All d
(defa
If the
Wiring connection in the control box of indoor unit
Refer
CAUTION: Attached wirings to the motion sensor vary depending on the model of the indoor unit.
20:20 (Tu
Make sure your model before installing.
Heating
<In case of the CnL connector is on the indoor unit PCB (FDT/FDK/FDTC)>
① Connect the same color to the relay wiring (prepare on site) and the attached wiring <1>.
Timer
CnL connector
White White (3P, black)
Connect 16:32 (M
Red wirings with the Red
Black same colors Black Cooling
●R
■ I
P
■ W
Infrare
Power c
Auto-of
CNG connector
(4P, blue)
CnL connector
(3P, black) Co
CNV2 connector
●R
(4P, black) Ind
1. H
①
②
③
④
Note: It is not possible to set by the following remote control models or older. HI P
Wired:RC-EX1A, RC-E5, RCH-E3
Wireless: RCN-E1R
- 152 -
'19 • KT-T-310D
SAFETY PRECAUTIONS
WARNING
hole
● If a child, person with disease or other persons needed for
assist uses this product, people around the person should
le
take sufficient care.
A halt of the air-conditioner due to abnormal situation or motion
e
e
sensor’s control may cause a feeling of sickness or accident.
ole
ATTENTION
• The sensor may not detect a person near the border of detection range.
• Installation near an object with a different temperature from the surrounding
may cause a false detection of human.
• Due to correction of temperature setting, some people may feel chilly.
This product uses infrared sensor to detect person’s activity level to support control of air-conditioner.
Please set the control you like from the remote control.
Indoor unit control Detective situation Description of control Display of eco touch
remote control
Activity level is large Lower the indoor temperature Power control ON
setting for comfort.
① Power control
Activity level is small Raise the indoor temperature Power control ON
setting for energy-saving.
No one is detected for 1 hour Stop operation and stand by In auto-off mode
② Auto-off
No one is detected for 12 hours Stop operation -
①+② Any combination of the above Any of the above Any of the above
All disabled - Standard control -
(default setting)
If the sensor is disconnected or defective, the control will be set as if it no detects (or less) activity level.
20:20 (Tue)
Menu • When power control is enabled
Direction
The amount of human motion is detected by a motion sensor to adjust the Set
Heating Set temp
temp.
Timer
During power control, “Power control ON” will be displayed on the message
display.
Power control ON
F1: High power F2: Energy-saving
16:32 (Mon)
Menu
• When auto-off is enabled
The unit will enter the “Operation wait” state when an hour has elapsed since
Direction
Cooling Set temp
the last time a human presence was detected and will be in “Complete stop”
state after another 12 hours.
Timer
“Operation wait”...The unit stops but will resume operation when human presence
is detected. When the unit is in “Complete stop”, “In auto-off
In auto-off mode
F1: High power F2: Energy-saving
mode” will be displayed on the message display.
“Complete stop”...When auto-off is enabled, the unit stops. The unit will not
resume operation even when human presence is detected.
The message “In auto-off mode” will disappear from the message
display, and the operation lamp will turn off.
Previous Back
Back
Select the item. Select the item.
● Refer to the installation manual for eco touch remote control to set control mode.
■ Infrared sensor (motion sensor) control (for IUs with motion sensors)
Presence of humans and the amount of motion are detected by a motion sensor to perform various controls.
■ When the R/C is set as the sub R/C, the infrared sensor (motion sensor) control cannot be set.
Infrared sensor control Tap the Menu button on the TOP screen and select Energy-saving setting
Power control Disable Enable
_ Infrared sensor control or Motion sensor control .
Auto-off Disable Enable
The Infrared sensor control screen and contents of the current settings are displayed.
1
Set Back
2 ① Enable/disable power control.
Select the item.
② Enable/disable auto-off.
③ After you set each item, tap the Set button.
3 The display returns to the Energy-saving setting menu screen.
ctor
)
Control setting (from wireless remote control)
ctor
● Refer to the installation manual for wireless remote control to enable motion sensor in Indoor function settings
) Indoor function settings
1. How to set indoor functions
① Press the ON/OFF button to stop the unit.
1
② Press the desired one of the buttons shown item 2. while holding down the 2
FUNCTION SETTING switch. 2
③ Use the selection buttons, ▲ and ▼, to change the setting.
④ Press the SET button.
The buzzer on the remote control signal receiver beeps twice, and the LED 3 4
lamp flashes four times at two-second intervals.
2
2. Setting details
Number
Button Function setting
indicator
00 Infrared sensor setting (Motion sensor setting) : Disable
SILENT
01 Infrared sensor setting (Motion sensor setting) : Enable
00 Infrared sensor control (Motion sensor control) : Disable
01 Infrared sensor control (Motion sensor control) : Power control only
HI POWER
02 Infrared sensor control (Motion sensor control) : Auto OFF only
03 Infrared sensor control (Motion sensor control) : Power control and Auto OFF
- 154 -
VRF INVERTER MULTI-SYSTEM AIR-CONDITIONERS
Air-Conditioning
MITSUBISHI HEAVY&INDUSTRIES
Refrigeration Division
THERMAL SYSTEMS, LTD.
16-5 Konan 2-chome, Minato-ku, Tokyo,
16-5, Konan 2-chome, Minato-ku, Tokyo,108-8215, Japan
108-8215 Japan
http://www.mhi.-mth.co.jp/en/
http://www.mhi.co.jp/en/
Because of our
Because policy
of our of of
policy continuous
continuousimprovement, wereserve
improvement, we reservethethe right
right to make
to make changes
changes in all in all specifications
specifications withoutwithout
notice. notice.
c Copyright
C Copyright MITSUBISHI HEAVY INDUSTRIES
MITSUBISHITHERMAL SYSTEMS,
HEAVY INDUSTRIES, LTD. LTD.