DIESEL 

GENERATOR
10kVA (or) MORE, 50HZ A
415V L-L (or) 230V L-N
NEUTRAL UNGROUNDED V
I
R
Y I
B

N
SUITABLE CABLE

Meas. MEASUREMENT OF
A
Direction-1 GROUND POTENTIAL RISE
SUITABLE CABLE
V
     POTENTIAL ELECTRODE TEMPORARY
EP‐04 REMOTE CURRENT ELECTRODE

P3 P2 P1
EP‐01
Depth should be
TP-04/TP-B2  EARTH GRID ≈ 64m (5xD(12.8m))

Direction-2
5m 5m 5m same as earth rod
≈ 1 under test

≈ 6.6m
2.

Meas.
8m

EP‐02
≈ 11m EP‐03

Fig­1: TEST ARRANGEMENT SKETCH FOR COMBINED GRID Rg MEASUREMENT

DIESEL GENERATOR
10kVA (or) MORE, 50HZ
415V L-L (or) 230V L-N
NEUTRAL UNGROUNDED

R
Y I
B

N
SUITABLE CABLE

Meas. MEASUREMENT OF
A
Direction-1 GROUND POTENTIAL RISE
SUITABLE CABLE
V
     POTENTIAL ELECTRODE TEMPORARY
EARTH ROD ISOLATED
EP‐04 REMOTE CURRENT ELECTRODE
FROM GRID

P3 P2 P1
EP‐01
Depth should be
≈ 42m (5xD(8.4m))
Direction-2

5m 5m 5m same as earth rod


under test
TP-04/TP-B2  EARTH GRID
Meas.

EP‐02 EP‐03

Fig­2: TEST ARRANGEMENT SKETCH FOR INDIVIDUAL EARTH ROD Rg MEASUREMENT

TEST FORMAT: