Service Entrance Cap – 25mm dia. (20 and 15) preffered 25** apat na metro
pataas galing lupa
Rigid Steel Conduit – 25mm dia. matched in service entrance cap
G.I. Conduit U Clamp – 25mm dia. usually in spacing 1m to 1.5m
Service Equipment – Disconnect – 30amp circuit breaker/disconnect switch in
NEMA 3R enclosure(rain type)
PVC Conduit – 20mm dia.
Ground Clamp – 16mm dia. (brass/copper)
Bare Copper Wire – 8.0 sq. mm (8.0 sq. mm green TW wire *insulated)
Ground Rod – 16mm dia. 2.4m long steel copper clad (steel grounding
electrode)
Oval eyebolt - 16mm dia.
Service entrance conductor - 8.0 sq. mm THW wire (Black/Red/White) min.
exception: 50sqm below house can minimize the diameter of the minimum given.
For the Service entrance pole, it should be a concrete or a solid wood that has a
dimension of (6"x6") minimum. It is not advisable to use cocolumber and used scraps
as a replacement.
The service drop should be attach to the service entrance pole or a wall. The
clearance from the window, door and other openings in the wall shall not less than
1 meter.
Fasten the third wire (Grounded Service Conductor) colored with white/grey.
Attached the Loadside conduit in the meter base with right fittings.
Attach the Ground Service Conductor in the ground terminal/bus of the service
equipment
From the ground terminal/bus, place the Grounding Electrode conductor into the
Ground rod.
Insert the Ground electrode conductor into the RMC or PVC pipe.
Bury the ground rod that has a 5/8" dia. with 8 feet long. Use the hot dip,
galvanized steed rod or copper coated.