Download as pdf or txt
Download as pdf or txt
You are on page 1of 10

ICC-ES Evaluation Report ESR-3878

Issued August 2016.


This report is subject to renewal August 2017.

www.icc-es.org | (800) 423-6587 | (562) 699-0543 A Subsidiary of the International Code Council ®

DIVISION: 03 00 00—CONCRETE 3.0 DESCRIPTION


Section: 03 16 00—Concrete Anchors 3.1 HMU-PF:
DIVISION: 05 00 00—METALS The Hilti HMU-PF Carbon Steel Undercut Anchors, are self-
Section: 05 05 19—Post-Installed Concrete Anchors undercutting undercut anchors. The HMU-PF is comprised
of four components as shown in Figures 1 and 2 of this
REPORT HOLDER: report.
All carbon steel parts are Hot Dip Galvanised (HDG) to
HILTI, INC. minimum of 0.002-inch-thick (50 μm). Dimensions and
7250 DALLAS PARKWAY, SUITE 1000 installation criteria are set forth in Tables 1 through 4 of this
PLANO, TEXAS 75024 report. This anchor is manufactured using metric units.
(800) 879-8000 Strength design information is provided in Table 5 of this
www.us.hilti.com report.
HiltiTechEng@us.hilti.com
3.2 Carbon Steel HMU-PF:
EVALUATION SUBJECT: 3.2.1 Cone Bolt: The cone bolt for the M12 and M16 sizes
is cold-formed heat treated steel. The cone bolt is equipped
HILTI HMU-PF CARBON STEEL UNDERCUT ANCHORS on one end with rolled threads . A parabolic cone is formed
FOR CRACKED AND UNCRACKED CONCRETE on the other end. A gap is provided in the thread for a
painted red setting mark (used for visual setting control).
1.0 EVALUATION SCOPE This mark becomes visible only when complete installation
Compliance with the following codes: of the anchor has been achieved.. An alphabetic length
code as listed in Table 1 of this report is stamped on the end
 2015, 2012, 2009 and 2006 International Building Code®
of the rod to permit determination of the nominal
(IBC)
embedment depth of the installed anchor. To prevent
 2015, 2012, 2009 and 2006 International Residential disassembly and possible improper installation of the
Code® (IRC) anchor, the cone bolt is locked into the sleeve by means of
 2013 Abu Dhabi International Building Code (ADIBC)+ an indentation in the sleeve.
+The ADIBC is based on the 2009 IBC. 2009 IBC code sections 3.2.2 Sleeve: The sleeve is machined from precision steel
referenced in this report are the same sections in the ADIBC tubing. At the installed end of the anchor, the sleeve is
equipped with six hinged bearing elements in a radial array.
Property evaluated:
The Hinged bearing elements are designed with special
Structural profile to facilitate undercutting process during setting of the
2.0 USES anchor. In the fully installed position, the bearing elements
rest on the parabolic curve of the cone and bear on a form-
The Hilti HMU-PF Undercut Anchor is used to resist static, fit undercut in the concrete.
wind, and seismic tension and shear loads in cracked and
uncracked normal-weight and sand-lightweight concrete 3.2.3 Washer: The M12 and M16 sizes are equipped with
having a specified compressive strength, f′c, of 2,500 psi to a washer confirming to DIN 125-1.
8,500 psi (17.2 MPa to 58.6 MPa). The anchoring system 3.2.4 Hex Nut: The M12 and M16 sizes are equipped with
complies with anchors as described in Section 1901.3 of the a special hexagonal nut with threads coated with zinc as
2015 IBC, Section 1909 of the 2012 IBC, and Section 1912 well for superior corrosion protection . SW ( Across Flat ) &
of the 2009 and 2006 IBC. The anchoring system is an Mechanical properties of Nut conform to DIN 934.
alternative to cast-in-place anchors described in Section
1908 of the 2012 IBC, and Section 1911 of the 2009 and 3.3 Concrete:
2006 IBC. The anchors may also be used where an Normal-weight and sand-lightweight concrete must conform
engineered design is submitted in accordance with Section to Sections 1903 and 1905 of the IBC.
R301.1.3 of the IRC.
4.0 DESIGN AND INSTALLATION
4.1 Strength Design:

ICC-ES Evaluation Reports are not to be construed as representing aesthetics or any other attributes not specifically addressed, nor are they to be construed
as an endorsement of the subject of the report or a recommendation for its use. There is no warranty by ICC Evaluation Service, LLC, express or implied, as
to any finding or other matter in this report, or as to any product covered by the report.
1000

Copyright © 2015 Page 1 of 10


ESR-3878 | Most Widely Accepted and Trusted Page 2 of 10

4.1.1 General: Design Strength of anchors complying with 𝑓𝑐′


the 2015 IBC, as well as Section R301.1.3 of the 2015 IRC 𝑁𝑝,𝑓′𝑐 = 𝑁𝑝,𝑐𝑟 √ (lb, psi) (Eq-1)
2,500
must be determined in accordance with ACI 318-14 Chapter
17 and this report. 𝑓𝑐′
𝑁𝑝,𝑓′𝑐 = 𝑁𝑝,𝑐𝑟 √ (N, MPa)
Design strength of anchors complying with the 2012 IBC 17.2
as well as Section R301.1.3 of the 2012 IRC, must be In uncracked concrete, pullout failure does not control and
determined in accordance with ACI 318-11 Appendix D and therefore need not be evaluated.
this report.
4.1.5 Requirements for Static Steel Strength in Shear
Design strength of anchors complying with the 2009 IBC Vsa: The nominal steel strength in shear, Vsa, of a single
and Section R301.1.3 of the 2009 IRC must be in anchor in accordance with ACI 318-14 17.5.1.2 or ACI 318-
accordance with ACI 318-08 Appendix D and this report. 11 D.6.1.2, as applicable, is given in Table 5 and Table 6
Design strength of anchors complying with the 2006 IBC and must be used in lieu of the values derived by calculation
and Section R301.1.3 of the 2006 IRC must be in from ACI 318-14 Eq. 17.5.1.2b or ACI 318-11, Eq. D-29, as
accordance with ACI 318-05 Appendix D and this report. applicable. The strength reduction factor, , corresponding
to ductile steel elements may be used.
A design example in accordance with the 2015 IBC and
2012 IBC is provided in Figure 4 of this report. 4.1.6 Requirements for Static Concrete Breakout
Strength in Shear, Vcb or Vcbg: The nominal concrete
Design parameters provided in Table 5 and references to
breakout strength of a single anchor or group of anchors in
ACI 318 are based on the 2015 IBC
shear, Vcb or Vcbg, respectively must be calculated in
(ACI 318-14) and the 2012 IBC (ACI 318-11) unless noted
accordance with ACI 318-14 17.5.2 or ACI 318-11 D.6.2, as
otherwise in Sections 4.1.1 through 4.1.12 of this report. The
applicable, with modifications as described in this section.
strength design of anchors must comply with ACI
The basic concrete breakout strength in shear, Vb, must be
318-14 17.3.1 or ACI 318-11 D.4.1, as applicable, except as
calculated in accordance with ACI 318-14 17.5.2.2 or ACI
required in ACI 318-14 17.2.3 or ACI 318-11 D.3.3, as
318-11 D.6.2.2, as applicable, using the value of le and da
applicable. Strength reduction factors, , as given in ACI
given in Table 5. In no case shall le be taken as greater than
318-14 17.3.3 or ACI 318-11 D.4.3, as applicable, must be
8da in the calculation of Vcb or Vcbg.
used for load combinations calculated in accordance with
Section 1605.2 of the IBC and Section 5.3 of ACI 318-14 or 4.1.7 Requirements for Static Concrete Pryout
Section 9.2 of ACI 318-11, as applicable. Strength reduction Strength in Shear, Vcp or Vcpg: The nominal concrete
factors, , as given in ACI 318-11 D.4.4 must be used for pryout strength of a single anchor or group of anchors, Vcp
load combinations calculated in accordance with ACI 318- or Vcpg, respectively, must be calculated in accordance with
11 Appendix C. ACI 318-14 17.5.3 or ACI 318-11 D.6.3, as applicable,
modified by using the value of kcp provided in Table 5 and
The value of f′c used in the calculations must be limited to the value of Ncb or Ncbg as calculated in Section 4.1.3 of this
8,000 psi (55.2 MPa), maximum, in accordance with ACI report.
318-14 17.2.7 or ACI 318-11 D.3.7, as applicable.
4.1.8 Requirements for Seismic Design: For load
4.1.2 Requirements for Static Steel Strength in combinations including seismic, the design must be
Tension: The nominal static steel strength, Nsa, of a single performed in accordance with ACI 318-14 17.2.3 or ACI
anchor in tension calculated in accordance with ACI 318-11 D.3.3, as applicable. Modifications to ACI 318-14
318-14 17.4.1.2 or ACI 318-11 D.5.1.2, as applicable, is 17.2.3 shall be applied under Section 1905.1.8 of the 2015
given in Table 5 of this report. Strength reduction factors, , IBC. For the 2012 IBC, Section 1905.1.9 shall be omitted.
corresponding to ductile steel elements may be used. Modifications to ACI 318 (-08, -05) D.3.3 shall be applied
4.1.3 Requirements for Static Concrete Breakout under Section 1908.1.9 of the 2009 IBC, or Section
Strength in Tension: The nominal static concrete breakout 1908.1.16 of the 2006 IBC, as applicable.
strength of a single anchor or group of anchors in tension, The nominal steel strength, the nominal concrete breakout
Ncb or Ncbg, respectively, must be calculated in accordance strength and the nominal pullout strength for anchors in
with ACI 318-14 17.4.2 or ACI 318-11 D.5.2, as applicable, tension and the nominal concrete breakout strength and
with modifications as described in this section. The basic pryout strength for anchors in shear are the same for
concrete breakout strength, Nb, must be calculated in seismic and static loading. They must be calculated in
accordance with ACI 318-14 17.4.2.2 or ACI 318 D.5.2.2, as accordance with ACI 318-14 17.4 and 17.5 or ACI 318-11
applicable, using the values of hef and kcr as given in Table D.5 and D.6, as applicable, for tension and shear,
5 of this report. The nominal concrete breakout strength in respectively, taking into account the corresponding values
tension in regions where analysis indicates no cracking in given in Table 5 of this report. The nominal steel strength for
accordance with ACI 318-14 17.4.2.6 or ACI 318 D.5.2.6, as seismic loads, Vsa,eq for anchors in shear must be taken
applicable, must be calculated with kuncr as given in Table 5 from Table 5 of this report.
with Ψc,N = 1.0.
4.1.9 Requirements for Interaction of Tensile and
Shear Forces: The effects of combined tensile and shear
4.1.4 Requirements for Static Pullout Strength in forces must be determined in accordance with ACI 318-14
Tension: The nominal pullout strength of a single anchor in 17.6 or ACI 318-11 D.7, as applicable.
tension in accordance with ACI 318-14 17.4.3.1 and 4.1.10 Requirements for Minimum Member Thickness,
17.4.3.2 or ACI 318-11 D.5.3.1 and D.5.3.2, as applicable, Minimum Anchor Spacing and Minimum Edge Distance:
in cracked concrete Np,cr is given in Table 5. In lieu of ACI In lieu of ACI 318-14 17.7.1 and 17.7.3 or ACI 318-11 D.8.1
318-14 17.4.3.6 or ACI 318-11 D.5.3.6, as applicable, Ψc,P and D.8.3, as applicable, values of smin and cmin,
= 1.0 for all design cases. In accordance with ACI 318-14 respectively, as given in Table 5 of this report must be used.
17.4.3.2 or ACI 318-11 D.5.3.2, as applicable, the nominal
pullout strength in tension in cracked concrete must be 4.1.11 Requirements for Critical Edge Distance, cac: In
adjusted by calculation in accordance with Eq-1: applications where c < cac and supplemental reinforcement
to control splitting of the concrete is not present, the
ESR-3878 | Most Widely Accepted and Trusted Page 3 of 10

concrete breakout strength in tension for uncracked 4.2.2 Interaction of Tensile and Shear Forces: The
concrete, calculated in accordance with ACI 318-14 17.4.2 interaction shall be calculated in compliance with ACI
or ACI 318-11 D.5.2, as applicable, must be further 318-14 17.6 or ACI 318 (-11, -08, -05) D.7, as applicable, as
multiplied by the factor Ψcp,N as given by Eq-2: follows:
𝑐
𝛹𝑐𝑝,𝑁 = 𝑐 (Eq-2) For shear loads Vapplied ≤ 0.2Vallowable,ASD, the full allowable
𝑎𝑐
load in tension Tallowable,ASD shall be permitted.
whereby the factor Ψ cp,N need not be taken as less than
1.5 hef . For all other cases, Ψ
For tension loads Tapplied ≤ 0.2Tallowable,ASD, the full allowable
cp,N = 1.0. In lieu of using ACI load in shear Vallowable,ASD shall be permitted.
cac
318-14 17.7.6 or ACI 318-11 D.8.6, as applicable, values of For all other cases:
cac must comply with 𝑇𝑎𝑝𝑝𝑙𝑖𝑒𝑑 𝑉𝑎𝑝𝑝𝑙𝑖𝑒𝑑
Table 5. + ≤ 1.2 (Eq-5)
𝑇𝑎𝑙𝑙𝑜𝑤𝑎𝑏𝑙𝑒,𝐴𝑆𝐷 𝑉𝑎𝑙𝑙𝑜𝑤𝑎𝑏𝑙𝑒,𝐴𝑆𝐷
4.1.12 Sand-lightweight Concrete: For ACI 318-14, ACI
4.3 Installation:
318-11 and ACI 318-08, when anchors are used in
sand-lightweight concrete, the modification factor for Installation parameters are provided in Tables 1 through 4
concrete breakout, λa or λ, respectively, must be taken as of this report and in Figures 1 and 2 of this report. Anchors
0.6 in lieu of ACI 318-14 17.2.6 (2015 IBC), ACI 318-11 must be installed per the manufacturer’s instructions. (See
D.3.6 (2012 IBC) or ACI 318-08 D.3.4 (2009 IBC), as Figure 3.) Anchor locations must comply with this report and
applicable. In addition, the pullout strength Np,cr, must be the plans and specifications approved by the code official.
multiplied by 0.6, as applicable. Required stop drill bits and setting tools as indicated in
Table 4 are provided by the manufacturer. Required
For ACI 318-05 the values Nb, Np,cr, and Vb determined in
hammer drill specifications are provided in Table 3 of this
accordance with this report must be multiplied by 0.60, in
report.
lieu of ACI 318-05 D.3.4.
4.4 Special Inspection:
4.2 Allowable Stress Design (ASD):
4.2.1 General: Design values for use with allowable stress Special inspection is required in accordance with Section
design (working stress design) load combinations 1705.1.1 and Table 1705.3 of the 2015 IBC and 2012 IBC;
calculated in accordance with Section 1605.3 of the IBC, Section 1704.15 and Table 1704.4 of the 2009 IBC; or
must be established using Eq-3 and Eq-4: Section 1704.13 of the 2006, as applicable. The special
inspector must make periodic inspections during anchor
𝜙𝑁𝑛 installation to verify anchor type, anchor dimensions,
𝑇𝑎𝑙𝑙𝑜𝑤𝑎𝑏𝑙𝑒,𝐴𝑆𝐷 = concrete type, concrete compressive strength, hole
𝛼 (Eq-3)
dimensions, hole cleaning procedures, anchor spacing,
𝜙𝑉𝑛 edge distances, concrete thickness, anchor embedment,
𝑉𝑎𝑙𝑙𝑜𝑤𝑎𝑏𝑙𝑒,𝐴𝑆𝐷 =
𝛼 (Eq-4) tightening torque and adherence to the manufacturer's
published installation instructions. The special inspector
where: must be present as often as required in accordance with the
Tallowable, ASD = Allowable tension load (lbf or kN) “statement of special inspection.” Additional requirements
as set forth in Sections 1705, 1706 and 1707 of the IBC must
Vallowable, ASD = Allowable shear load (lbf or kN) be observed, where applicable.
Nn = Lowest design strength of an anchor or 5.0 CONDITIONS OF USE
anchor group in tension as determined in
accordance with ACI 318-14 Chapter 17 The Hilti HMU-PF anchors described in this report comply
and 2015 IBC Section 1905.1.8, ACI with, or are suitable alternatives to what is specified in, those
318-11 Appendix D, ACI 318-08 Appendix codes listed in Section 1.0 of this report, subject to the
D and 2009 IBC Section 1908.1.9, ACI following conditions:
318-05 Appendix D and 2006 IBC Section 5.1 Anchor sizes, dimensions and minimum embedment
1908.1.16, and Section 4.1 of this report, depths are as set forth in the tables of this report.
as applicable.
5.2 The anchors must be installed in accordance with the
Vn = Lowest design strength of an anchor or manufacturer’s published installation instructions and
anchor group in shear as determined in this report. In case of conflict, this report governs
accordance with ACI 318-14 Chapter 17
and 2015 IBC Section 1905.1.8, ACI 5.3 Anchors must be limited to use in concrete with a
318-11 Appendix D, ACI 318-08 Appendix specified strength of f′c = 2,500 psi to 8,500 psi
D and 2009 IBC Section 1908.1.9, ACI (17.2 to 58.6 MPa).
318-05 Appendix D and 2006 IBC Section 5.4 The values of f′c used for calculation purposes must not
1908.1.16, and Section 4.1 of this report, exceed 8,000 psi (55.2 MPa).
as applicable.
5.5 Loads applied to the anchors are adjusted in
α = Conversion factor calculated as a accordance with Section 1605.2 of the IBC for strength
weighted average of the load factors for design and in accordance with Section 1605.3 of the
the controlling load combination. In IBC for allowable stress design.
addition, α shall include all applicable
factors to account for nonductile failure 5.6 Strength design values are established in accordance
modes and required over-strength. with Section 4.1 of this report.

Limits on edge distance, anchor spacing and member 5.7 Allowable design values are established in accordance
thickness as given in this report must apply. An example of with Section 4.2 of this report.
Allowable Stress Design tension values is given in Table 6
of this report.
ESR-3878 | Most Widely Accepted and Trusted Page 4 of 10

5.8 Anchor spacing(s) and edge distance(s) as well as protected by approved fire-resistance-rated
minimum member thickness comply with Table 5 of this materials, or have been evaluated for resistance to
report. fire exposure in accordance with recognized
standards.
5.9 Prior to installation, calculations and details
demonstrating compliance with this report must be  Anchors are used to support nonstructural
submitted to the code official for approval. The elements.
calculations and details must be prepared by a
5.14 Use of HDG carbon steel anchors is limited to dry,
registered design professional where required by the
interior locations, indoor with temporary condensation
statues of the jurisdiction in which the project is to be
constructed. 5.15 Special inspection must be provided in accordance
with Section 4.4 of this report.
5.10 Since an ICC-ES acceptance criteria for evaluating
data to determine the performance of anchors 5.16 Anchors are manufactured by Hilti AG under an
subjected to fatigue or shock loading is unavailable at approved quality control program with inspections by
this time, the use of these anchors under such ICC-ES.
conditions is beyond the scope of this report.
6.0 EVIDENCE SUBMITTED
5.11 Anchors may be installed in regions of concrete where
Data in accordance with the ICC-ES Acceptance Criteria for
cracking has occurred or where analysis indicates
Mechanical Anchors in Concrete Elements (AC193), dated
cracking may occur (ft > fr), subject to the conditions of
February 2016, which incorporates requirements in ACI
this report.
355.2-07 , for use in cracked and uncracked concrete; and
5.12 Anchors may be used to resist short-term loading due quality control documentation.
to wind or seismic forces, subject to the conditions of
7.0 IDENTIFICATION
this report.
The anchors are identified by packaging labeled with the
5.13 Where not otherwise prohibited in the code, anchors
manufacturer's name (Hilti, Inc.) and address, anchor name,
are permitted for use with fire-resistance-rated
anchor size, and evaluation report number (ICC-ES ESR-
construction provided that at least one of the following
3878).
conditions is fulfilled:
 Anchors are used to resist wind or seismic forces
only.
 Anchors that support a fire-resistance-rated
envelope or a fire-resistance-rated membrane are

FIGURE 1—THE HILTI HMU-PF UNDERCUT ANCHOR


ESR-3878 | Most Widely Accepted and Trusted Page 5 of 10

TABLE 1—ANCHOR DIMENSIONAL CHARACTERISTICS

tfix1 lB 2
lS dS
[mm] [mm] SW
Anchor type [mm] [mm]
min-max
HMU-PF- M12x80/20 2-20 133 80.6 17.5 19
HMU-PF- M12x80/35 2-35 146 80.6 17.5 19
HMU-PF- M12x80/65 2-65 176 80.6 17.5 19
HMU-PF- M16x100/30 5-30 167 100 21.6 24
HMU-PF- M16x100/60 5-60 197 100 21.6 24
HMU-PF- M16x125/30 5-30 192 125 21.6 24
HMU-PF- M16x125/60 5-60 222 125 21.6 24
HMU-PF- M16x125/75 5-75 239 125 21.6 24
For in-lb units: 1 mm = 0.03937 inches
1
first value: tfix,min minimum fixture thickness for pure tension load, second value: tfix,max maximum fixture thickness.
2
first value: lB anchor bolt length.

FIGURE 2—HMU-PF INSTALLED


ESR-3878 | Most Widely Accepted and Trusted Page 6 of 10

TABLE 2—CHARACTERISTIC VALUES OF ANCHORS AND SETTING INFORMATION1

HMU-PF M12x80 M16x100 M16x125

Nominal drill bit


d0 mm 18 23 23
diameter1

Minimum hole mm 92 115 140


hhole
depth1 (in.) (3-5/8) (4-1/2) (5-1/2)

Maximum clearance mm 14 18 18
hole diameter in df
fastened part (in.) (1/2) (3/4) (3/4)

Nm 45 120 120
Installation torque Tinst
(ft-lb) (33) (89) (89)

For in-lb units: 1mm = 0.03937 inches, 1 Nm = 0.7376 ft-lb


1
Use required stop drill bits only. See Table 4

TABLE 3—REQUIRED HAMMER DRILLS FOR SETTING

HMU-PF M12 M16

TE 40 TE 40
Hilti hammer-drill for anchor setting
TE 30 A36 TE 50

TABLE 4—REQUIRED STOP DRILL BIT AND SETTING TOOL

Anchor type Stop drill bit Setting tool

HMU-PF- M12x80/20 TE-C-HMU-B M12x80

HMU-PF- M12x80/35 TE-C-HMU-B M12x80 TE-C-HMU -ST-M12

HMU-PF- M12x80/65 TE-C-HMU-B M12x80

TE-C–HMU-B M16x100
HMU-PF- M16x100/30
or TE-Y-HMU-B M16x100 TE-C-HMU -ST-M16
HMU-PF- M16x100/60 TE-C-HMU-B M16x100 or TE-Y-HMU -ST M16
or TE-Y-HMU-B M16x100
HMU-PF- M16x125/30 TE-C-HMU-B M16x125
or TE-Y-HMU-B M16x125
HMU-PF- M16x125/60 TE-C-HMU-B M16x125 TE-C-HMU -ST-M16
or TE-Y-HMU-B M16x125 or TE-Y-HMU -ST M16
HMU-PF- M16x125/75
TE-C-HMU-B M16x125
or TE-Y-HMU-B M16x125
ESR-3878 | Most Widely Accepted and Trusted Page 7 of 10

TABLE 5—DESIGN INFORMATION, HILTI HMU-PF UNDERCUT ANCHORS

Nominal anchor diameter


Design Parameter Symbol Units
M12x80 M16x100 M16x125

Anchor O.D. da (d0)8 mm 17.5 21.6 21.6

Effective minimum hef,min mm 80 100 125


embedment depth l e9 (in.) (3.15) (3.94) (4.92)
mm 100 120 120
Minimum edge distance cmin
(in.) (3.94) (4.72) (4.72)
mm 120 200 200
Minimum anchor spacing smin
(in.) (4.72) (7.87) (7.87)
mm 200 250 312.5
Critical edge distance1 cac
(in.) (7.87) (9.84) (12.30)
Minimum thickness of. mm 160 200 250
hmin
concrete member (in.) (6.30) (7.87) (9.84)
Anchor category2 1,2 or 3 - 1 1 1
Strength reduction factor for
 - 0.75
tension, steel failure modes3
Strength reduction factor for
 - 0.65
shear, steel failure modes3
Strength reduction factor for Cond. A 0.75
tension, concrete failure 
modes3 Cond. B 0.65

Strength reduction factor for Cond. A 0.75



shear, concrete failure modes3 Cond. B 0.70
2
Yield strength of anchor N/mm 640
fya
carbon steel (psi) (92,800)
Ultimate strength of anchor N/mm2 800
futa
carbon steel (psi) (116,000)
mm2 84.3 157 157
Tensile stress area Ase
(in2) (0.130) (0.243) (0.243)
kN 67,4 125,6 125,6
Steel strength in tension Nsa
(lb) (15,150) (28,235) (28,235)
Effectiveness factor 10 12.6 11.3
kuncr -
uncracked concrete (24) (30) (27)
Effectiveness factor cracked 8.8 10 7.1
kcr -
concrete4 (21) (24) (17)
Ψc,N = kuncr/kcr 5
- - 1
Pullout strength uncracked kN
Np,uncr N.A. N.A. N.A.
concrete6 (lb)
Pullout strength cracked kN
Np,cr N.A. N.A. N.A.
concrete6 (lb)
kN 23.7 35.8 41.3
Pullout strength, seismic6 Np,eq
(lb) (5,331) (8,050) (9,280)
Coefficient for pryout kcp - 2.00 2.00 2.00
kN 28.6 56.5 56.5
Steel strength in shear static Vsa
(lb) (6,426) (12,709) (12,709)
Steel strength in shear, kN 28.6 56.5 56.5
Vsa,eq
seismic7 (lb) (6,426) (12,709) (12,709)
Axial stiffness in service load
range in cracked / uncracked  kN/mm 24 / 239
concrete
1
See Section 4.1.11 of this report.
2
See ACI 318-14 17.3.3 or ACI 318-11 D.4.3, as applicable.
3
For use with the load combinations of ACI 318-14 Section 5.3 or ACI 318-11 Section 9.2, as applicable. Condition A applies where the potential
concrete failure surfaces are crossed by supplementary reinforcement proportioned to tie the potential concrete failure prism into the structural
member. Condition B applies where such supplementary reinforcement is not provided, or where pullout or pryout governs.
4
See ACI 318-14 17.4.2.2 or ACI 318-11 D.5.2.2, as applicable, and Section 4.1.3 of this report.
5
For all design cases, Ψc,N=1. The appropriate effectiveness factor for cracked concrete (kcr) or uncracked concrete (kuncr) must be used.
6
See Section 4.1.4 of this report.
7
See Section 4.1.8 of this report.
8
The notation in parenthesis is for the 2006 IBC.
9
To calculate the basic concrete breakout strength in shear, Vb, l e equals hef . In no cases shall le exceed 8da. See ACI 318-14 17.5.2.2 or ACI 318-
11 D.6.2.2, as applicable.
ESR-3878 | Most Widely Accepted and Trusted Page 8 of 10

TABLE 6—EXAMPLE ALLOWABLE STRESS DESIGN VALUES FOR ILLUSTRATIVE PURPOSES

Nominal Effective Allowable


anchor embedment tension load
diameter depth f’c kuncr α ϕ Nn ϕNn/α

da hef

(mm) (in.) (psi) (-) (-) (-) (lb) (lb)

M12 3.15 2,500 24 1.48 0.65 8,386 2,946

M16 3.94 2,500 30 1.48 0.65 11,731 5,152*

M16 4.92 2,500 27 1.48 0.65 16,370 6,470

For SI: 1 lb = 4.45 kN, 1 psi = 0.00689 MPa, 1 in. = 25.4 mm.

Design Assumptions:

1. Single anchor with static tension only.

2. Concrete determined to remain uncracked for the life of the anchorage.

3. Load combinations are taken from ACI 318-14 Section 5.3 or ACI 318-11 Section 9.2, as applicable (no seismic
loading).

4. 30% Dead Load (D) and 70% Live Load (L); Controlling load combination 1.2 D + 1.6 L.

5. Calculation of weighted average for conversion factor α =0.3(1.2) + 0.7(1.6) = 1.48

6. Normal weight concrete: f’c = 2,500 psi.

7. Edge distance ca1 = ca2 ≥ cac.

8. Member thickness h ≥ hmin.

9. Values are for Condition B (supplementary reinforcement in accordance with ACI 318-11 D.4.4 is not provided).

* Verify capacity
ACI 318- ACI 318-
Capacity 14 11 Formula Calculation ϕ ϕNn
reference reference
Nsa = Nsa = 0.243 ·
Steel 17.4.1 D.5.1 0.75 21,141 lb
nAse,Nfuta 116,000
Ncb = k (f’c)0. 5 Ncb = 30 ·
Concrete 17.4.2 D.5.2 0.65 7,625 lb
hef 1. 5 (2,500)0.5 · 3.941.5

Pull out 17.4.3 D.5.3 Not Decisive

7,625
→ concrete is decisive hence the ASD value will be calculated as = 5,152 lb
1.48
ESR-3878 | Most Widely Accepted and Trusted Page 9 of 10

FIGURE 3—INSTALLATION INSTRUCTIONS HMU-PF


ESR-3878 | Most Widely Accepted and Trusted Page 10 of 10

Given
(2) HMU-PF- M12
anchors
static tension load
hef = 3.15 in. (80 mm)
f ’c = 3,000 psi

Assume
1. uncracked concrete
2. ACI 318-14 17.3.3(c)
or ACI 318-11 D.4.3(c),
Condition B
No supplementary
reinforcing

Calculate
Controlling design
strength in tension
Calculation per ACI 318-14 Chapter 17, ACI 318-14 ACI 318-11 Report
ACI 318-11 Appendix D and this report. Ref. Ref. Ref.
Step 1. Calculate steel strength of anchor in tension
17.4.1.2 D.5.1.2 Table 5
Nsa =n Ase futa =2(0.13)(116,000)=30,160 lb
Step 2. Calculate steel capacity ϕNs =0.75 x 30,160=22,620 lb 17.3.3(a) D.4.3(a) Table 5
Step 3. Calculate concrete breakout strength of anchor in tension §4.1.1
A 17.4.2.1 D.5.2.1
Ncbg = A 𝑁𝑐 ψec,N ψed,N ψc,N ψcp,N Nb § 4.1.3
𝑁𝑐0

Step 3a. Check 1.5hef = 1.5(3.15) = 4.725 in. > c 3.0hef = 3(3.15) = 9.45 in. > s 17.4.2.1 D.5.2.1 Table 5

Step 3b. Check smin = 4.72 in. < 6 in., cmin = 3.94 in. < 4 in., hmin = 6 1/4 in. < 7 in
17.7 D.8 Table 5
 ok
2 2
Step 3c. Calculate ANco and ANc for the anchorage: ANc0 =9hef =9(3.15) =89.3 in2
2
17.4.2.1 D.5.2.1 Table 5
ANc =(1.5hef + c)(3hef + s)=[1.5(3.15)+ 4][3(3.15)+ 6]= 134.8 in <2ANc0 ∴ ok

Step 3d. e'N = 0, therefore ψec,N = 1 17.4.2.4 D.5.2.4 Table 5


1.5
Step 3e. Calculate Nb =λkc √f'c h1.5
ef = (1.0)24√3,000(3.15) =7,349 lb 17.4.2.2 D.5.2.2 Table 5
Step 3f. Calculate modification factor for edge distance:
4
ψed,N =0.7+0.3 1.5(3.15) =0.95 17.4.2.5 D.5.2.5 Table 5

Step 3g. ψc,N =1.0 17.4.2.6 D.5.2.6 Table 5

Step 3h. ψcp,N =1.0 - - § 4.1.3


134.8 § 4.1.3
Step 3i. Calculate Ncbg = x 1.00 x 0.95 x 1.00 x 1.00 x 7,349=6,982 lb 17.4.2.1 D.5.2.1
89.3
Table 5
Step 4. Controlling design strength: ϕNcbg =0.65 x 6,982 lb = 4,538 lb < ϕNs ∴
17.3.3(c) D.4.3(c) Table 5
ϕNcbg controls

FIGURE 4—EXAMPLE CALCULATION

You might also like