CUADRO DE CAÍDA DE TENSIONES

M.D. In Id L S M.D. In Id L S M.D. In Id L S Cumple <


Distancia Sum. f.p. ITM n° Ternas LT (mm2) PVC-P (mm) Caida (V%) Distancia Sum. f.p. ITM n° Ternas LT (mm2) PVC-P (mm) Caida (V%) Distancia Sum. f.p. ITM n° Ternas LT (mm2) PVC-P (mm) Caida (V%) S D V%
(kW) (A) (A) (m) (mm2) (kW) (A) (A) (m) (mm2) (kW) (A) (A) (m) (mm2) 2,5% Vn
BLOQUE A
CM1 - 001 6.00 1Ø 0.9 30.30 37.88 2x40A 10.00 1.00 6 6 20 0.80% 0.80% SI
CM1 - 101 6.00 1Ø 0.9 30.30 37.88 2x40A 14.00 1.00 6 6 20 1.12% 1.12% SI
CM1 - 102 6.00 1Ø 0.9 30.30 37.88 2x40A 10.00 1.00 6 6 20 0.80% 0.80% SI
CM1 - 201 6.00 1Ø 0.9 30.30 37.88 2x40A 17.00 1.00 6 6 20 1.37% 1.37% SI
CM1 - 202 6.00 1Ø 0.9 30.30 37.88 2x40A 13.00 1.00 6 6 20 1.04% 1.04% SI
CM1 - 301 6.00 1Ø 0.9 30.30 37.88 2x40A 20.00 1.00 6 6 20 1.61% 1.61% SI
CM1 - 302 6.00 1Ø 0.9 30.30 37.88 2x40A 16.00 1.00 6 6 20 1.29% 1.29% SI
CM1 - 401 6.00 1Ø 0.9 30.30 37.88 2x40A 23.00 1.00 6 6 20 1.85% 1.85% SI
CM1 - 402 6.00 1Ø 0.9 30.30 37.88 2x40A 19.00 1.00 6 6 20 1.53% 1.53% SI
CM1 - 501 7.00 1Ø 0.9 35.35 44.19 2x50A 26.00 1.00 10 6 25 1.46% 1.46% SI
CM1 - 502 7.00 1Ø 0.9 35.35 44.19 2x50A 22.00 1.00 10 6 25 1.24% 1.24% SI
CM2 - 103 6.00 1Ø 0.9 30.30 37.88 2x40A 10.00 1.00 6 6 20 0.80% 0.80% SI
CM2 - 104 6.00 1Ø 0.9 30.30 37.88 2x40A 15.00 1.00 6 6 20 1.21% 1.21% SI
CM2 - 203 6.00 1Ø 0.9 30.30 37.88 2x40A 13.00 1.00 6 6 20 1.04% 1.04% SI
CM2 - 204 6.00 1Ø 0.9 30.30 37.88 2x40A 18.00 1.00 6 6 20 1.45% 1.45% SI
CM2 - 303 6.00 1Ø 0.9 30.30 37.88 2x40A 16.00 1.00 6 6 20 1.29% 1.29% SI
CM2 - 304 6.00 1Ø 0.9 30.30 37.88 2x40A 21.00 1.00 6 6 20 1.69% 1.69% SI
CM2 - 403 6.00 1Ø 0.9 30.30 37.88 2x40A 19.00 1.00 6 6 20 1.53% 1.53% SI
CM2 - 404 6.00 1Ø 0.9 30.30 37.88 2x40A 24.00 1.00 6 6 20 1.93% 1.93% SI
CM2 - 503 7.00 1Ø 0.9 35.35 44.19 2x50A 22.00 1.00 10 6 25 1.24% 1.24% SI
CM2 - 504 7.00 1Ø 0.9 35.35 44.19 2x50A 27.00 1.00 10 6 25 1.52% 1.52% SI
CM3 - 002 6.00 1Ø 0.9 30.30 37.88 2x40A 10.00 1.00 6 6 20 0.80% 0.80% SI
CM3 - 105 6.00 1Ø 0.9 30.30 37.88 2x40A 10.00 1.00 6 6 20 0.80% 0.80% SI
CM3 - 106 6.00 1Ø 0.9 30.30 37.88 2x40A 15.00 1.00 6 6 20 1.21% 1.21% SI
CM3 - 205 6.00 1Ø 0.9 30.30 37.88 2x40A 13.00 1.00 6 6 20 1.04% 1.04% SI
CM3 - 206 6.00 1Ø 0.9 30.30 37.88 2x40A 18.00 1.00 6 6 20 1.45% 1.45% SI
CM3 - 305 6.00 1Ø 0.9 30.30 37.88 2x40A 16.00 1.00 6 6 20 1.29% 1.29% SI
CM3 - 306 6.00 1Ø 0.9 30.30 37.88 2x40A 21.00 1.00 6 6 20 1.69% 1.69% SI
CM3 - 405 6.00 1Ø 0.9 30.30 37.88 2x40A 19.00 1.00 6 6 20 1.53% 1.53% SI
CM3 - 406 6.00 1Ø 0.9 30.30 37.88 2x40A 24.00 1.00 6 6 20 1.93% 1.93% SI
CM3 - 505 7.00 1Ø 0.9 35.35 44.19 2x50A 22.00 1.00 10 6 25 1.24% 1.24% SI
CM3 - 506 7.00 1Ø 0.9 35.35 44.19 2x50A 27.00 1.00 10 6 25 1.52% 1.52% SI
BLOQUE B
CM4 - 001 6.00 1Ø 0.9 30.30 37.88 2x40A 10.00 1.00 6 6 20 0.80% 0.80% SI
CM4 - 101 6.00 1Ø 0.9 30.30 37.88 2x40A 14.00 1.00 6 6 20 1.12% 1.12% SI
CM4 - 102 6.00 1Ø 0.9 30.30 37.88 2x40A 19.00 1.00 6 6 20 1.53% 1.53% SI
CM4 - 103 6.00 1Ø 0.9 30.30 37.88 2x40A 11.00 1.00 6 6 20 0.88% 0.88% SI
CM4 - 201 6.00 1Ø 0.9 30.30 37.88 2x40A 17.00 1.00 6 6 20 1.37% 1.37% SI
CM4 - 202 6.00 1Ø 0.9 30.30 37.88 2x40A 22.00 1.00 6 6 20 1.77% 1.77% SI
CM4 - 203 6.00 1Ø 0.9 30.30 37.88 2x40A 14.00 1.00 6 6 20 1.12% 1.12% SI
CM4 - 301 6.00 1Ø 0.9 30.30 37.88 2x40A 20.00 1.00 6 6 20 1.61% 1.61% SI
CM4 - 302 6.00 1Ø 0.9 30.30 37.88 2x40A 25.00 1.00 6 6 20 2.01% 2.01% SI
CM4 - 303 6.00 1Ø 0.9 30.30 37.88 2x40A 17.00 1.00 6 6 20 1.37% 1.37% SI
CM4 - 401 6.00 1Ø 0.9 30.30 37.88 2x40A 23.00 1.00 6 6 20 1.85% 1.85% SI
CM4 - 402 6.00 1Ø 0.9 30.30 37.88 2x40A 28.00 1.00 6 6 20 2.25% 2.25% SI
CM4 - 403 6.00 1Ø 0.9 30.30 37.88 2x40A 20.00 1.00 6 6 20 1.61% 1.61% SI
CM4 - 501 7.00 1Ø 0.9 35.35 44.19 2x50A 26.00 1.00 10 6 25 1.46% 1.46% SI
CM4 - 502 7.00 1Ø 0.9 35.35 44.19 2x50A 31.00 1.00 10 6 25 1.74% 1.74% SI
CM4 - 503 7.00 1Ø 0.9 35.35 44.19 2x50A 23.00 1.00 10 6 25 1.29% 1.29% SI
CM5 - 104 6.00 1Ø 0.9 30.30 37.88 2x40A 10.00 1.00 6 6 20 0.80% 0.80% SI
CM5 - 105 6.00 1Ø 0.9 30.30 37.88 2x40A 15.00 1.00 6 6 20 1.21% 1.21% SI
CM5 - 204 6.00 1Ø 0.9 30.30 37.88 2x40A 13.00 1.00 6 6 20 1.04% 1.04% SI
CM5 - 205 6.00 1Ø 0.9 30.30 37.88 2x40A 18.00 1.00 6 6 20 1.45% 1.45% SI
CM5 - 304 6.00 1Ø 0.9 30.30 37.88 2x40A 16.00 1.00 6 6 20 1.29% 1.29% SI
CM5 - 305 6.00 1Ø 0.9 30.30 37.88 2x40A 21.00 1.00 6 6 20 1.69% 1.69% SI
CM5 - 404 6.00 1Ø 0.9 30.30 37.88 2x40A 19.00 1.00 6 6 20 1.53% 1.53% SI
CM5 - 405 6.00 1Ø 0.9 30.30 37.88 2x40A 24.00 1.00 6 6 20 1.93% 1.93% SI
CM5 - 504 7.00 1Ø 0.9 35.35 44.19 2x50A 22.00 1.00 10 6 25 1.24% 1.24% SI
CM5 - 505 7.00 1Ø 0.9 35.35 44.19 2x50A 27.00 1.00 10 6 25 1.52% 1.52% SI
CM6 - 002 6.00 1Ø 0.9 30.30 37.88 2x40A 10.00 1.00 6 6 20 0.80% 0.80% SI
CM6 - 106 6.00 1Ø 0.9 30.30 37.88 2x40A 10.00 1.00 6 6 20 0.80% 0.80% SI
CM6 - 107 6.00 1Ø 0.9 30.30 37.88 2x40A 15.00 1.00 6 6 20 1.21% 1.21% SI
CM6 - 206 6.00 1Ø 0.9 30.30 37.88 2x40A 13.00 1.00 6 6 20 1.04% 1.04% SI
CM6 - 207 6.00 1Ø 0.9 30.30 37.88 2x40A 18.00 1.00 6 6 20 1.45% 1.45% SI
CM6 - 306 6.00 1Ø 0.9 30.30 37.88 2x40A 16.00 1.00 6 6 20 1.29% 1.29% SI
CM6 - 307 6.00 1Ø 0.9 30.30 37.88 2x40A 21.00 1.00 6 6 20 1.69% 1.69% SI
CM6 - 406 6.00 1Ø 0.9 30.30 37.88 2x40A 19.00 1.00 6 6 20 1.53% 1.53% SI
CM6 - 407 6.00 1Ø 0.9 30.30 37.88 2x40A 24.00 1.00 6 6 20 1.93% 1.93% SI
CM6 - 506 7.00 1Ø 0.9 35.35 44.19 2x50A 22.00 1.00 10 6 25 1.24% 1.24% SI
CM6 - 507 7.00 1Ø 0.9 35.35 44.19 2x50A 27.00 1.00 10 6 25 1.52% 1.52% SI
(T-B) - (TC-BS) 1.49 3Ø 0.80 4.89 6.12 3x25A 4.00 1.00 4 4 20 0.07% 1.97% SI
(T-SG) - (T-B) 11.13 3Ø 0.80 36.50 45.62 3x50A 36.00 1.00 16 6 35 1.13%
(T-B) - (TC-BA) 6.00 3Ø 0.80 19.68 24.10 3x32A 4.00 1.00 6 6 25 0.18% 2.08% SI
(T-SG) - (T-GYM) 2.60 1Ø 0.85 13.88 17.35 2x25A 20.00 1.00 4 4 20 1.10% 1.87% SI
(T-SG) - (TC-EXTS1) 3.00 3Ø 0.80 9.84 12.30 3x25A 36.00 1.00 4 4 20 1.22% 1.99% SI
(T-SG) - (TC-INYS1) 3.23 1Ø 0.80 18.34 22.92 2x25A 8.00 1.00 4 4 20 0.58% 1.35% SI
3x400A (T-SG) - (T-AC1) 8.26 3Ø 0.85 25.50 51.00 3x63A 28.00 1.00 16 10 35 0.61% (T-AC1) - (TC-ASC1) 8.00 3Ø 0.85 24.70 49.40 3x50A 4.00 1.00 10 6 25 0.14% 1.52% SI
BM - (T-SGA) 71.26 3Ø 0.85 220.02 275.03 38.00 1.00 150 25 100 0.77%
Reg. 280 A (T-SG) - (T-AC2) 8.26 3Ø 0.85 25.50 51.00 3x63A 16.00 1.00 16 10 35 0.35% (T-AC2) - (TC-ASC2) 8.00 3Ø 0.85 24.70 49.40 3x50A 4.00 1.00 10 6 25 0.14% 1.26% SI
(T-SG) - (T-AC3) 8.26 3Ø 0.85 25.50 51.00 3x63A 30.00 1.00 16 10 35 0.66% (T-AC3) - (TC-ASC3) 8.00 3Ø 0.85 24.70 49.40 3x50A 4.00 1.00 10 6 25 0.14% 1.56% SI
(T-SG) - (T-RE) 5.70 3Ø 0.85 17.60 22.00 3x25A 32.00 1.00 6 4 25 1.29% 2.06% SI
(T-S2) - (TC-EXTS2) 3.00 3Ø 0.85 9.26 11.58 3x25A 36.00 1.00 4 4 20 1.15% 2.32% SI
(T-SG) - (T-S2) 13.67 3Ø 0.85 42.21 52.76 3x50A 7.00 1.00 10 6 25 0.41%
(T-S2) - (TC-INYS2) 3.23 1Ø 0.85 17.26 21.57 2x25A 8.00 1.00 4 4 20 0.55% 1.72% SI
(T-SG) - (T-GE) 10.26 3Ø 0.80 33.67 42.08 3x50A 8.00 1.00 10 6 25 0.37% (T-GE) - (TC-BD) 8.86 3Ø 0.80 29.07 36.34 3x40A 5.00 1.00 10 6 25 0.20% 1.34% SI
(T-B) - (TC-BS) 1.49 3Ø 0.80 4.89 6.12 3x25A 4.00 1.00 4 4 20 0.07% 1.97% SI
(T-SG) - (T-B) 11.13 3Ø 0.80 36.50 45.62 3x50A 36.00 1.00 16 6 35 1.13%
(T-B) - (TC-BA) 6.00 3Ø 0.80 19.68 24.10 3x32A 4.00 1.00 6 6 25 0.18% 2.08% SI
(T-SG) - (T-GYM) 2.60 1Ø 0.85 13.88 17.35 2x25A 20.00 1.00 4 4 20 1.10% 1.87% SI
(T-SG) - (TC-EXTS1) 3.00 3Ø 0.80 9.84 12.30 3x25A 36.00 1.00 4 4 20 1.22% 1.99% SI
(T-SG) - (TC-INYS1) 3.23 1Ø 0.80 18.34 22.92 2x25A 8.00 1.00 4 4 20 0.58% 1.35% SI
3x400A (T-SG) - (T-AC1) 8.26 3Ø 0.85 25.50 51.00 3x63A 28.00 1.00 16 10 35 0.61% (T-AC1) - (TC-ASC1) 8.00 3Ø 0.85 24.70 49.40 3x50A 4.00 1.00 10 6 25 0.14% 1.52% SI
BM - (T-SGB) 74.01 3Ø 0.85 228.51 285.64 37.00 1.00 150 25 100 0.78%
Reg. 320 A (T-SG) - (T-AC2) 8.26 3Ø 0.85 25.50 51.00 3x63A 16.00 1.00 16 10 35 0.35% (T-AC2) - (TC-ASC2) 8.00 3Ø 0.85 24.70 49.40 3x50A 4.00 1.00 10 6 25 0.14% 1.26% SI
(T-SG) - (T-AC3) 8.26 3Ø 0.85 25.50 51.00 3x63A 30.00 1.00 16 10 35 0.66% (T-AC3) - (TC-ASC3) 8.00 3Ø 0.85 24.70 49.40 3x50A 4.00 1.00 10 6 25 0.14% 1.56% SI
(T-SG) - (T-RE) 5.70 3Ø 0.85 17.60 22.00 3x25A 32.00 1.00 6 4 25 1.29% 2.06% SI
(T-S2) - (TC-EXTS2) 3.00 3Ø 0.85 9.26 11.58 3x25A 36.00 1.00 4 4 20 1.15% 2.32% SI
(T-SG) - (T-S2) 13.67 3Ø 0.85 42.21 52.76 3x50A 7.00 1.00 10 6 25 0.41%
(T-S2) - (TC-INYS2) 3.23 1Ø 0.85 17.26 21.57 2x25A 8.00 1.00 4 4 20 0.55% 1.72% SI
(T-SG) - (T-GE) 10.26 3Ø 0.80 33.67 42.08 3x50A 8.00 1.00 10 6 25 0.37% (T-GE) - (TC-BD) 8.86 3Ø 0.80 29.07 36.34 3x40A 5.00 1.00 10 6 25 0.20% 1.34% SI
3x200A
(TT-BACI) - (TC-BACI) 22.38 3Ø 0.85 69.10 172.74 4.00 1.00 95 16 80 0.04% 0.81% SI
BM - (TF-BACI)-A 23.87 3Ø 0.85 73.70 184.26 3x200A 26.00 1.00 95 16 80 0.28% REG.180A
(TT-BACI) - (TC-BJ) 1.49 3Ø 0.85 4.61 10.36 3x20A 4.00 1.00 4 4 20 0.06% 0.83% SI
3x200A
(TT-BACI) - (TC-BACI) 22.38 3Ø 0.85 69.10 172.74 4.00 1.00 95 16 80 0.04% 0.81% SI
BM - (TF-BACI)-B 23.87 3Ø 0.85 73.70 184.26 3x200A 24.00 1.00 95 16 80 0.26% REG.180A
(TT-BACI) - (TC-BJ) 1.49 3Ø 0.85 4.61 10.36 3x20A 4.00 1.00 4 4 20 0.06% 0.83% SI

In: CORRIENTE NOMINAL (A)


Id: CORRIENTE DE DISEÑO (A)
L: DISTANCIA (m)
S: SECCIÓN DEL CONDUCTOR (mm²)
LT: SECCIÓN DEL CABLE DE ENLACE EQUIPOTENCIAL (mm²)
CUADRO DE CARGAS
Proyecto : Edificio Multifamiliar "Los Viñedos"
Propietario : Inmobiliario los Saucos S.A.C.

I. Departamentos Típicos

Cuadro de Cargas Departamento T-D1 ( 90m²) Densidad Carga unitaria C.Instalada M.Demanda
Area (m2) Cantidad F.D.
(Flats) (56 DPTOS) (W/m2) (kW) (kW) (kW)
1.00 Carga básica por área techada
1.01 Carga básica primeros 45 m2 (Sección 050-202(1)(a)(i) CNE-U) 1.50 1.00 1.50 100% 1.50
1.02 Carga adicional segundos 45 m2 (Sección 050-202(1)(a)(ii) CNE-U) 1.00 1.00 1.00 100% 1.00
2.00 Secadora eléctrica de ropa 4000 W
2.01 Potencia asignada (Sección 050-202(1)(a)(vi) CNE-U) 4.00 1.00 4.00 25% 1.00
3.00 Calentador eléctrico 1500 W
3.01 Potencia asignada (Sección 050-202(1)(a)(vi) CNE-U) 1.50 1.00 1.50 100% 1.50
4.00 Horno Electrico
4.01 Potencia asignada 2.00 1.00 2.00 50% 1.00
TOTAL : 10.00 6.00

Cuadro de Cargas Departamento T-D2 ( 180m²) Densidad Carga unitaria C.Instalada M.Demanda
Area (m2) Cantidad F.D.
(Flats) (13 DPTOS) (W/m2) (kW) (kW) (kW)
1.00 Carga básica por área techada
1.01 Carga básica primeros 45 m2 (Sección 050-202(1)(a)(i) CNE-U) 1.50 1.00 1.50 100% 1.50
1.02 Carga adicional segundos 45 m2 (Sección 050-202(1)(a)(ii) CNE-U) 1.00 1.00 1.00 100% 1.00
1.03 Carga básica los siguientes 90 m2 (Sección 050-202(1)(a)(iii) CNE-U) 1.00 1.00 1.00 100% 1.00
2.00 Secadora eléctrica de ropa 4000 W
2.01 Potencia asignada (Sección 050-202(1)(a)(vi) CNE-U) 4.00 1.00 4.00 25% 1.00
3.00 Calentador eléctrico 1500 W
3.01 Potencia asignada (Sección 050-202(1)(a)(vi) CNE-U) 1.50 1.00 1.50 100% 1.50
4.00 Horno Electrico
4.01 Potencia asignada 2.00 1.00 2.00 50% 1.00
TOTAL : 11.00 7.00

II. Cuadro de Cargas de Servicios Generales

Densidad Carga unitaria C.Instalada M.Demanda


Cuadro de Cargas - Servicios Generales del Edificio (T-SGA) Area (m2) Cantidad F.D.
(W/m2) (kW) (kW) (kW)
1.00 Alumbrado y Tomacorrientes (Sección 50-202(3)(d) CNE-U)
1.01 Estacionamiento,Circulación, Depositos y Hall, (x 10W/m2) 10.00 825.00 8.25 1.00 8.25 100% 8.25
2.00 Sub Tableros
2.01 Tablero Cuarto de Bomba (T-B) 11.13 1.00 11.13 90% 10.01
2.02 Tablero de Sotano 2 (T-S2) 13.67 1.00 13.67 70% 9.57
2.03 Tablero gymnasio (T-GYM) 2.60 1.00 2.60 70% 1.82
2.04 Tablero Extracción de Monoxido (TC-EXT1) 3.00 1.00 3.00 75% 2.25
2.05 Tablero Control Inyección deAire (TC-INYS1) 3.23 1.00 3.23 75% 2.42
2.06 Tablero de Grupo Electrogeno (T-GE) 10.26 1.00 10.26 90% 9.24
2.07 Tablero Areas comunes 1, 2 y 3 (T-AC1/ AC2 / AC3) 8.26 3.00 24.78 85% 21.06
2.08 Tablero Recepcion del Edificio (T-RE) 5.70 1.00 5.70 85% 4.85
2.09 Puerta Ingreso Vehicular 1.00 2.00 2.00 90% 1.80
TOTAL : 84.61 71.26

Densidad Carga unitaria C.Instalada M.Demanda


Cuadro de Cargas - Servicios Generales del Edificio (T-SGB) Area (m2) Cantidad (kW)
F.D.
(kW)
(W/m2) (kW)
1.00 Alumbrado y Tomacorrientes (Sección 50-202(3)(d) CNE-U)
1.01 Estacionamiento,Circulación, Depositos y Hall, (x 10W/m2) 10.00 1,100.00 11.00 1.00 11.00 100% 11.00
2.00 Sub Tableros
2.01 Tablero Cuarto de Bomba (T-B) 11.13 1.00 11.13 90% 10.01
2.02 Tablero de Sotano 2 (T-S2) 13.67 1.00 13.67 70% 9.57
2.03 Tablero gymnasio (T-GYM) 2.60 1.00 2.60 70% 1.82
2.04 Tablero Extracción de Monoxido (TC-EXT1) 3.00 1.00 3.00 75% 2.25
2.05 Tablero Control Inyección deAire (TC-INYS1) 3.23 1.00 3.23 75% 2.42
2.06 Tablero de Grupo Electrogeno (T-GE) 10.26 1.00 10.26 90% 9.24
2.07 Tablero Areas comunes 1, 2 y 3 (T-AC1/ AC2 / AC3) 8.26 3.00 24.78 85% 21.06
2.08 Tablero Recepcion del Edificio (T-RE) 5.70 1.00 5.70 85% 4.85
2.09 Puerta Ingreso Vehicular 1.00 2.00 2.00 90% 1.80
TOTAL : 87.36 74.01

Cuadro de Cargas - Grupo Electrogeno (T-GE) Densidad Carga unitaria C.Instalada M.Demanda
Area (m2) Cantidad F.D.
Tipico bloque "A y B" (W/m2) (kW) (kW) (kW)
1.00 Caamara de desague
1.01 Tablero de control bombas de desague (TC-BD) 8.86 1.00 8.86 100% 8.86
2.00 Equipos Electricos Especiales - Sistema de Grupo Electrogeno
2.01 Cargador de Baterias (1.00kW, 220V, 1F, 60hz) - 01 Undidad 1.00 1.00 1.00 70% 0.70
2.02 Calentador de aceite (1.00kW, 220V, 1F, 60hz) - 01 Undidad 1.00 1.00 1.00 70% 0.70

TOTAL : 10.86 10.26

Para el Diseño del Grupo Electrogeno dejamos una reserva de carga del 10.00%, con f.p. = 0.8 01 Grupo Electrogeno (kW)= 12.00

Cuadro de Cargas -Camara Bombas de desague (TC-BD) Densidad Carga unitaria C.Instalada M.Demanda
Area (m2) Cantidad F.D.
Tipico bloque "A y B" (W/m2) (kW) (kW) (kW)
1.00 Sistema Bomba de Desagüe (02 En funcionamiento alternado y 01 en Stand By)
1.01 Equipos de Bomba de Desagüe (3 unds x 6.00 HP) 4.48 3.00 13.43 66% 8.86
TOTAL : 13.43 8.86

Cuadro de Cargas - Areas Comunes 1, 2 y 3 (T-AC1/ AC2/ AC3) Densidad Carga unitaria C.Instalada M.Demanda
Area (m2) Cantidad (kW)
F.D.
(kW)
Tipico bloque "A y B" (W/m2) (kW)
1.00 Alumbrado y Tomacorrientes (Sección 50-202(3)(d) CNE-U)
1.01 Estacionamiento,Circulación, Depositos y Hall, (x 10W/m2) 10.00 106.00 1.06 1.00 1.06 100% 1.06
2.00 Sub Tableros
2.04 Tablero de control Cuarto de ascensor (TC-ASC1/2/3) 8.00 1.00 8.00 90% 7.20
TOTAL : 9.06 8.26

Cuadro de Cargas - Cuarto de Ascensores (TC-ASC1/2/3) Densidad Carga unitaria C.Instalada M.Demanda
Area (m2) Cantidad (kW)
F.D.
(kW)
Tipico bloque "A y B" (W/m2) (kW)
1.00 Sistema de Ascensor
1.02 Salida de Fuerza para Ascensores (8.00 kW) 8.00 1.00 8.00 100% 8.00
TOTAL : 8.00 8.00

Cuadro de Cargas - Recepcion del Edificio (T-RE) Densidad Carga unitaria C.Instalada M.Demanda
Area (m2) Cantidad (kW)
F.D.
(kW)
Tipico bloque "A y B" (W/m2) (kW)
1.00 Alumbrado y Tomacorrientes (Sección 50-202(3)(d) CNE-U)
1.01 Estacionamiento,Circulación, Depositos y Hall, (x 10W/m2) 10.00 30.00 0.30 1.00 0.30 100% 0.30
2.00 Sistemas Eléctricos Especiales
2.01 CACI 1.00 1.00 1.00 90% 0.90
2.02 Intercomunicador portero y Chapa Eléctrica 1.00 1.00 1.00 90% 0.90
2.03 Salida para ascensor Discapacitados 4.00 1.00 4.00 90% 3.60
TOTAL : 6.30 5.70

Cuadro de Cargas - Sótano 02 (T-S2) Densidad Carga unitaria C.Instalada M.Demanda


Area (m2) Cantidad F.D.
Tipico bloque "A y B" (W/m2) (kW) (kW) (kW)
1.00 Alumbrado y Tomacorrientes (Sección 50-202(3)(d) CNE-U)
1.01 Estacionamiento,Circulación y Depositos (x 10W/m2) 10.00 900.00 9.00 1.00 9.00 100% 9.00
2.00 Sistema de Extracción de Monoxido
2.01 Tablero Control Inyección deAire (TC-INYS2) 3.23 1.00 3.23 75% 2.42
2.02 Tablero Extracción de Monoxido (T-EXTS2) 3.00 1.00 3.00 75% 2.25
TOTAL : 15.23 13.67

Cuadro de Cargas TC-EXS1/ EXTS2 Densidad Area C.U. C.I. M.D.


Cantidad F.D.
Tipico bloque "A y B" (W/m2) (m2) (kW) (kW) (kW)
1.00 Sistema de Extracción de Monóxido de Sótanos
1.01 Equipo Extractor EM1-01 (5.00 HP) 3.75 1.00 3.75 80% 3.00
TOTAL : 3.75 3.00

Cuadro de Cargas - Sistemas de Inyección de Aire (TC-INYS1/S2) Densidad Carga unitaria C.Instalada M.Demanda
Area (m2) Cantidad F.D.
Tipico bloque "A y B" (W/m2) (kW) (kW) (kW)
1.00 Equipo Inyector
1.01 Equipo Inyector Axial (0.50HP) 0.37 2.00 0.75 90% 0.67
1.02 Jet Fan JF-S1-01 Al 04 (0.71 Kw) 0.71 4.00 2.84 90% 2.56

TOTAL : 3.59 3.23

Cuadro de Cargas - Gimnasio (T-GYM) Densidad Carga unitaria P.Instalada M.Demanda


Area (m2) Cantidad (kW)
F.D.
(kW)
Tipico bloque "A y B" (W/m2) (kW)
1.00 Alumbrado y Tomacorrientes (Sección 50-202(3)(d) CNE-U)
1.01 Alumbrado y Tomacorrientes (Sección 50-202(3)(d) CNE-U) 25.00 45.00 1.13 1.00 1.13 100% 1.13
2.00 Cargas Electricas Especiales
2.01 Reserva para Aire Acondicionado (0.070kW/m2) 70.00 30.00 2.10 1.00 2.10 70% 1.47
TOTAL : 3.23 2.60

Cuadro de Cargas -Cuarto de Bombas (T-B) Densidad Carga unitaria C.Instalada M.Demanda
Area (m2) Cantidad F.D.
Tipico bloque "A y B" (W/m2) (kW) (kW) (kW)
1.00 Alumbrado y Tomacorrientes (Sección 50-202(3)(d) CNE-U)
1.01 Cuarto de Bombas (x 10 W/m2) 10.00 33.00 0.33 1.00 0.33 100% 0.33
2.00 Sistemas Eléctricos Especiales
2.01 Tablero de Bombas de Agua (TC-BA) 6.00 1.00 6.00 90% 5.40
2.01 Tablero de Bombas sumidero (TC-BS) 1.49 1.00 6.00 90% 5.40
TOTAL : 12.33 11.13

Cuadro de Cargas - Tablero Control Bombas de Agua (TC-BA) Densidad Carga unitaria C.Instalada M.Demanda
Area (m2) Cantidad F.D.
Tipico bloque "A y B" (W/m2) (kW) (kW) (kW)
1.00 Sistema de Bomba de Agua (02 En funcionamiento alternado y 01 en stand by)
1.01 Equipos de Bomba de agua (3 unds x4.00 HP) 2.98 3.00 8.95 67% 6.00
TOTAL : 8.95 6.00

Cuadro de Cargas - Tablero Control Bombas Sumidero (TC-BS) Densidad Carga unitaria C.Instalada M.Demanda
Area (m2) Cantidad F.D.
Tipico bloque "A y B" (W/m2) (kW) (kW) (kW)
1.00 Sistema de Bomba de Desagüe (02 En funcionamiento alternado)
1.01 Equipos de Bomba de Desagüe (2 unds x 2.00 HP) 1.49 2.00 2.98 50% 1.49
TOTAL : 2.98 1.49

III. Cuadro de Cargas de Sistema Contra Incendio Tipico bloque "A y B"

Densidad Carga unitaria C.Instalada M.Demanda


Cuadro de Cargas - Sistema Contra Incendio (TF-BACI) Area (m2) Cantidad (kW)
F.D.
(kW)
(W/m2) (kW)
1.00 Tablero de Control de Bomba Contra Incendio (TC-BACI) 22.38 1.00 22.38 100% 22.38
2.00 Tablero de Control de Bomba Jockey (TC-BJ) 1.49 1.00 1.49 100% 1.49

TOTAL : 23.87 23.87

Densidad Carga unitaria C.Instalada M.Demanda


Cuadro de Cargas - Bomba Contra Incendio (TC-BACI) Area (m2) Cantidad (kW)
F.D.
(kW)
(W/m2) (kW)
1.00 Tablero de Control de Bomba Contra Incendio
1.01 Electrobomba (30.00 HP) 22.38 1.00 22.38 100% 22.38

TOTAL : 22.38 22.38

Densidad Carga unitaria C.Instalada M.Demanda


Cuadro de Cargas - Bomba Jockey (TC-BJ) Area (m2) Cantidad (kW)
F.D.
(kW)
(W/m2) (kW)
1.00 Tablero de Control de Bomba Jockey
1.01 Electrobomba (2.0 HP) 1.49 1.00 1.49 100% 1.49

TOTAL : 1.49 1.49

IV. Resumen Nivel Edificio

Densidad Carga unitaria C.Instalada M.Demanda


Cuadro de Maxima Demanda Nivel Edificio (69 DPTOS) Area (m2) Cantidad F.D.
(W/m2) (kW) (kW) (kW)
1.00 Cargas debido a los Departamentos
1.01 01 Dpto. de mayor carga (Sección 50-202(3)(a)(i) CNE-U) 7.00 1.00 7.00 100% 7.00
1.02 02 Dptos. siguientes de menor carga (Sección 50-202(3)(a)(ii) CNE-U) 7.00 2.00 14.00 65% 9.10
1.03 02 Dptos. siguientes de menor carga (Sección 50-202(3)(a)(iii) CNE-U) 7.00 2.00 14.00 40% 5.60
1.04 08 Dptos. siguientes de menor carga (Sección 50-202(3)(a)(iv) CNE-U) 7.00 8.00 56.00 30% 16.80
1.05 07 Dptos. siguientes de menor carga (Sección 50-202(3)(a)(iv) CNE-U) 6.00 7.00 42.00 30% 12.60
1.06 49 Dptos. siguientes de menor carga (Sección 50-202(3)(a)(v) CNE-U) 6.00 49.00 294.00 25% 73.50
2.00 Servicios Generales
2.01 Cargas de Servicios generales edificio A (Sección 50-202(3)(d) CNE-U) 71.26 1.00 71.26 75% 53.45
2.02 Cargas de Servicios generales edificio B (Sección 50-202(3)(d) CNE-U) 74.01 1.00 74.01 75% 55.51

TOTAL : 572.3 233.56


CÁLCULO DE CAIDA DE TENSIÓN - RED PARTICULAR DE BAJA TENSIÓN

CARGA
CARGA PUNTUAL INTENSIDAD LONGITUD CAÌDA DE % DE CAÌDA TENSIÓN EL FU de Cable Estado de Cable
CIRCUITO 01 ACUMULADA TENSION TIPO COS j CABLE K
(KW) (AMP) (Mts) TENSIÒN (V) DE TENSIÒN EL BANCO
(KW)
TOT - CM1 #NAME? #NAME? 220 Trifásico 0.90 #NAME? 37.75 13.00 #NAME? #NAME? #NAME? #NAME? #NAME? #NAME?
CM1 - CM2 #NAME? #NAME? 220 Trifásico 0.90 #NAME? 46.75 13.00 #NAME? #NAME? #NAME? #NAME? #NAME? #NAME?
CM2 - CM3 #NAME? #NAME? 220 Trifásico 0.90 #NAME? 55.75 13.00 #NAME? #NAME? #NAME? #NAME? #NAME? #NAME?
TOTAL: #NAME? #NAME? #NAME?

CARGA
CARGA PUNTUAL INTENSIDAD LONGITUD CAÌDA DE % DE CAÌDA TENSIÓN EL FU de Cable Estado de Cable
CIRCUITO 02 ACUMULADA TENSION TIPO COS j CABLE K
(KW) (AMP) (Mts) TENSIÒN (V) DE TENSIÒN EL BANCO
(KW)
Nodo 0 - 1 #NAME? #NAME? 220 Trifásico 0.90 #NAME? 205.00 12.00 #NAME? #NAME? #NAME? #NAME? #NAME? #NAME?
TOTAL: #NAME? #NAME? #NAME?

CARGA
CARGA PUNTUAL INTENSIDAD LONGITUD CAÌDA DE % DE CAÌDA TENSIÓN EL FU de Cable Estado de Cable
CIRCUITO 03 ACUMULADA TENSION TIPO COS j CABLE K
(KW) (AMP) (Mts) TENSIÒN (V) DE TENSIÒN EL BANCO
(KW)
Nodo 0 - 1 #NAME? #NAME? 220 Trifásico 0.90 #NAME? 278.75 12.00 #NAME? #NAME? #NAME? #NAME? #NAME? #NAME?
TOTAL: #NAME? #NAME? #NAME?
BAJA TENSIÓN
CALCULO DEL SISTEMA DE PUESTA A TIERRA
Según IEEE Std 142 - 1991 - Tabla 13

A. SISTEMA DE PUESTA A TIERRA Nº1 (contrapeso )

1. Datos :

Resistividad del terreno (GP) 1000 ohm - m


Longitud de contrapeso ( L ) 8.00 m
Profundidad (s/2) 0.60 cm
Sección del conductor 70.00 mm2
Radio del conductor 0.00489 m

2. Cálculo de la resistencia (R1)

2 4
   4L   4L   s   s   s  
R1   Ln    Ln  2    0, 5   
4 L   a   s   2L   4L   2 L  
R1 = 101.67 ohm

B. SISTEMA DE PUESTA A TIERRA Nº2 (vertical)

1. Datos :

Resistividad del terreno 1000 ohm - m


Longitud de varilla ( L ) 2.40 m
Cantidad de sistemas verticales 1.00
Radio de varilla (5/8") 0.0079 m

2. Cálculo de la resistencia (R2)

   4L  
R2  Ln   1
4L   a  
R2 = 202.19 ohm

La resistencia total será entonces:

1
RT 
 1 4 
  
 R1 R 2 
RT = 67.65 ohm

Si se considera aditivos para reducción del valor de la resistenica al 30%

RT = 20.30 ohm

NOTA: Para ascensores y Servidores la resistencia minima es de 5.00 Ohm.


SISTEMA DE ASCENSORES
CALCULO DEL SISTEMA DE PUESTA A TIERRA
Según IEEE Std 142 - 1991 - Tabla 13

A. SISTEMA DE PUESTA A TIERRA Nº1 (contrapeso )

1. Datos :

Resistividad del terreno 1000 ohm - m


Longitud de contrapeso ( L ) 45.00 m
Profundidad (s/2) 0.60 cm
Sección del conductor 70.00 mm2
Radio del conductor 0.00489 m

2. Cálculo de la resistencia (R1)

2 4
   4L   4L   s   s   s  
R1   Ln    Ln    2        0,5   
4 L   a   s   2L   4 L   2 L  

R1 = 23.96 ohm

B. SISTEMA DE PUESTA A TIERRA Nº2 (vertical)

1. Datos :

Resistividad del terreno 1000 ohm - m


Longitud de varilla ( L ) 2.40 m
Cantidad de sistemas verticales 4.00
Radio de varilla (5/8") 0.0079 m

2. Cálculo de la resistencia (R3)

   4L  
R2  Ln   1
4L   a  
R2 = 202.19 ohm

La resistencia total será entonces:

1
RT 
 1 4 
  
 R1 R 2 
RT = 16.26 ohm

Si se considera aditivos para reducción del valor de la resistenica al 30%

RT = 4.88 ohm

NOTA: Las Tierras de los equipos de MT y Neutros de los transformadores no deben superar los 25.00 Ohm.