Energy Efficient Residential Building Code For Arab Countries
Energy Efficient Residential Building Code For Arab Countries
George B. HANNA
ABSTRACT: This paper presents an energy analysis to efficiency measures suitable for Arab regions. Building
support the Egyptian efforts to develop a New Energy envelope and fenestration components are considered
Code for New Residential Buildings in the Arab one of the fundamental design features of energy-
Countries. Also, the paper represents a brief summary efficient buildings.
of the code contents specially, the effectiveness of
building envelope and weather data in reducing RESIDENTIAL BUILDING CODES
electrical energy consumption. The impacts of the The Final Draft of the New Arab Building Energy
following parameters were studied namely; walls and Codes was approved by the League of Arab States
roof constructions, window size and glazing type for (2010). The code contains 12 Chapters and 7
different geographical locations in the Arab Countries. Appendices. It contains the following chapters:
Two different distinguish weather classification were
developed and analyzed and presented in this study, the 1. SCOPE AND COMPLIANCE
DDC18.3& DDH 25. The first was developed by the 2. GENERAL REQUIREMENTS
Author to calculate DD using a mathematical model on
electronic spread sheet. The second depends on the 3. BUILDING ENVELOPE
hourly values for each geographical location. The 4. NATURAL VENTILATION
analysis includes the capitals and major cities
representing most of the Arab countries. It was 5. HEATING VENTILATION & AIR
determined that the window to wall ratio (WWR) of 6. CONDITIONING
15% minimizes the total annual electricity use for the
buildings. The Solar Factors (SF) and Window 7. SERVICE WATER HEATING SYSTEM
Orientation Factors (OF) were calculated for the eight 8. DAY LIGHTING
wall orientations. The Over All Transfer Value (OTTV)
was calculated for each orientation for different 9. LIGHTING
variables, e.g. WWR, Glazing Type, Shading, wall
10. ELECTRICAL POWER
color and mid and top floor. The results show that the
mass and types of building materials; WWR (15%), 11. WHOLE BUILDING PERFORMANCE
glass type and shutters; orientation; wall insulation
12. DEFINITIONS, ABBREVIATIONS &
(25mm), wall solar absorptivity (α=.3); roof insulation
and shading effect enhance the thermal performance ACRONYM.
and reduces the cooling load by 60%.
ENERGY IN ARAB COUNTRIES
From the 1970s many countries throughout the world
INTRODUCTION introduced building regulations aimed at reducing
energy consumption in residential and commercial
Residential buildings consume more than 50% of the buildings, see table (1). Typically, these regulations
total electricity consumption. Artificial lighting is concentrate on aspects of heat loss through the building
estimated to account about 40% of the electricity used envelope with minimum levels of insulation required
in the residential sector and 35% of the electricity used being stated. Worldwide these regulations encompass
for HVAC system. A significant increase in electricity resistance for individual opaque building elements. The
demand is expected over the next few years with a simple prescriptive nature of most of the regulations
growth rate over 10%. To improve the energy efficiency reduces the need for complex calculation methods.
in residential buildings, a New Arab energy Building Tables (2 & 3) show the crude oil and natural gas
Code had been developed for new residential buildings consumption during 2007 and the electricity
[1]. As part of the development of the energy code, consumption in most of the Arab Countries.
simulation analysis has been carried for new residential
buildings to determine the most cost-effective energy
1
Proceedings of the Tenth International Conference for Enhanced Building Operations, Kuwait, October 26-28, 2010
ESL-IC-10-10-62
ICEBO2010, October 26-28, 2010, Kuwait
3 9 .2 %
Iraq 596.00 --
Jordan 106.00 79
Kuwait 325.00 441 Agric ulture
4 .1 %
Gove rnm e nta l Utilitie s
Entitie s 4 .2 %
Lebanon 94.00 0
P ublic Lighting
5 .0 % 6 .2 %
Indus try A gric ulture Utilities P ublic Lighting G overnm ental E ntities Res idential C om m erc ia & O thers
2
Proceedings of the Tenth International Conference for Enhanced Building Operations, Kuwait, October 26-28, 2010
ESL-IC-10-10-62
ICEBO2010, October 26-28, 2010, Kuwait
CDD25, and the heating degree-days based on Whole-Building Performance: The proposed
18.3 oC, HDD 18.3. Three methods should be used design must comply with, if the annual (8760
to meet the building envelope requirements, hours) energy costs comply with the Standard
namely; perspective, trade-off compliance and design. The proposed design and the standard
whole building performance. design must each be determined using the same
approved energy analysis simulation tool, such as
Perspective Requirements: the sum of the R- VDOE or Energy+.
values of the insulation materials installed in
the wall, Table (5): Glass Types Characteristics [4]
cavities and insulating sheeting (where used)
must meet or exceed the minimum required Name
U SC SHGC TVIS
"Wall R-value" for the appropriate climatic Single
6.17 .95 .81 .88
region, see tables 4. Glazing_Clear
Single Glazing_Blue 6.17 .71 .61 .57
Table (4) Recommended Thermal Resistance Single Glazing_Grey 6.17 .69 .59 .43
[2] for Different Arab Countries compared with
leading Countries (m2.oC/W). Single Reflective
(Class A) 1 Clear 5.41 .36 .31 .20
Country Roof Walls Floors
High Emissivity
Single Reflective (A)
Austria 3.3 2.0-1.4 2.3-1.6 Tint Medium 5.11 .29 .25 .09
Belgium 2.4-1.3 1.5-1.0 - Emissivity
Egypt 1.67 1.0 ---- Double Glazing
France
2.74 .57 .49 .47
4.0-2.5 2.0-1.5 1.3-1.0 BronzeTint
Jordon 1.0 0.56 -- Double Glazing
2.74 .57 .49 .66
Kuwait 2.5 1.75 -- GreenTint
Greece Double Glazing Tint
2.0 0.9 2.0-0.3 1.78 .37 .28 .44
Italy 2.6 1.7 --
Low Emissivity
New Zealand 3.0-1.5 1.7-0.6 1.7-0.9 Double Glazing,
painS 1.4-0.7 0.7-0.6 1.4-1.0 Reflective (A) Clear
Turkey
2.35 .20 .17 .13
2.63 1.7 -- Medium Emissivity
UK 2.9 1.0 -- (IG)2
USA (various) 7.0-3.5 3.5-2.0 3.5-0.0 Double Glazing,
West Germany 3.3-2.2 1.2-0.7 1.8-0.8 Reflective (A)Tint,
2.35 .18 .15 .08
Saudi Arabia 1.754 1.3 -- Medium Emissivity
Republic of (IG)
2.27-1.75 1.85- 0.48 ---
Lebanon
Natural Ventilation
Envelope Trade-Off Compliance: The
calculated Overall Thermal Transfer Value The requirements in this section represent the
(OTTV, W/m2) requirements [4] for minimum design parameters. It is
conditioned buildings may be used in the recommended that the designer evaluate other
Prescriptive requirements. energy conservation measures that may be
applicable to all residential buildings.
To calculate the OTTV, the Solar Factors (SF)
and the Orientation Factors (OF) must be The building form and external envelope must
calculated from the hourly, monthly and be designed and constructed to be able to
annual averages direct and diffuse solar satisfy the Natural Ventilation requirements,
radiations. The solar data were calculated for see table (8), in order to provide thermal
the eight orientations. were derived by comfort in occupied spaces and to reduce the
normalizing the Maximum Solar Heat Gain energy consumption. These requirements are
Factors for June for each selected city in the intended to reduce the energy consumption for
Arab region [5]. conditioned spaces and to improve the thermal
comfort of unconditioned spaces.
3
Proceedings of the Tenth International Conference for Enhanced Building Operations, Kuwait, October 26-28, 2010
ESL-IC-10-10-62
ICEBO2010, October 26-28, 2010, Kuwait
Table (6) OTTV, Degree Days Heating and Cooling for ten Climatic Regions for Arab Countries
Table (7): Degree Day Heating and Cooling for Selected Arab Cities for Different Categories.
Log, Eleva
City Lat, oN o Tao,avg RH(%) Ws(m/s) DDC18.3 DDH25 Classification Category
E ,m
Doha 25.2 51.6 12.0 28 56 2.9 92 1802
Dubai 25.3 55.3 5.0 28.1 51 3.0 27 1660
Dhahran 26.3 50.2 17.0 27.4 50 3.4 205 1840
Khartoum 15.6 32.5 382 28.6 21 4.1 2 1520 DDC10> 6000 A
Kuwait 29.2 48.0 55.0 26.3 39 3.1 487 1912
Manama 26.3 50.7 2.0 26.9 60 3.6 151 1537
Jeddah 21.7 39.2 12.0 28.3 59 2.8 0 1370
Aswan 24.0 32..8 194.0 26.2 27 3.3 165 1385
Riyadh 24.7 46.7 612.0 26.2 29 2.7 340 1161 4000<DDC10
B
Laxer 25.7 32.7 88.0 24.7 40 1.8 270 1107 <5000
Baghdad 33.2 44.2 34 23.9 39 2.4 680 1495
Cairo 30.1 31.4 74.0 21.9 58 2.9 397 409 3000< DDC10
C
Mousel 36.3 43.2 216 21.1 47 1.7 1153 1122 <4000
Alexandria 31.2 30.0 7.0 19.9 67 3.2 561 153
Beirut 33.8 35.5 19.0 20.1 62 2.6 536 174
Agadir 30.3 9.6W 74.0 19.3 71 2.1 529 26
Sana'a 15.5 44.2 2190.0 18.4 39 1.5 503 4 3000<DDC10<
D
Tunis 36.8 10.2 4.0 19.4 69 2.7 809 202 4000
Tripoli 32.7 13.1 81.0 20.5 57 2.4 686 337
Latakia 35.5 35.8 7.0 18.4 67 2.3 904 100
Aleppo 36.2 37.2 393.0 17.6 58 3.6 1570 342
Algeria 36.7 3.2 25.0 17.9 71 2.6 977 51
Damascus 33.5 36.5 609.0 16.7 53 4.6 1596 172 DDC10< 3000 E
Amman 32.0 36.0 773.0 17.1 47 1.9 1504 127
4
Proceedings of the Tenth International Conference for Enhanced Building Operations, Kuwait, October 26-28, 2010
ESL-IC-10-10-62
ICEBO2010, October 26-28, 2010, Kuwait
Table (8) Ventilation Requirements (1), dwelling unit and for each specific space
within the dwelling unit. The minimum
Requirement requirements for Energy efficiency (EER) for
Requirements For s To
Meta- window or split units is 10 for cooling and 11
respiration: O2 maintain
Activity bolic
concentration of CO2 at 0.5% for cooling greater than 10 kW.
(adult rate,
16.3% in assuming
male) M HOT WATER SYSTEM
Expired air 0.04% CO2
(W)
(s-1) In fresh air
(1 s-1) Service water heaters, domestic boilers,
Seated storage tanks and pool heaters that are
100 0.1 0.8 included in table 10 must comply with the
quietly
Light 160 -
0.2 – 0.3 1.3 – 2.6 relevant municipal codes.
work 320
Moderat 320 - Table (10) Minimum Pipe insulation thickness
0.3 – 0.5 2.6 – 3.9
e work 480 (mm)
Heavy 480 - Types of Pipes
Range of Fluid Pipe Diameter (mm)
0.5 – 0.7 3.9 – 5.3 Temperature < 25- 63.5- 127
work 650 systems
(oC) 25 35
50
102 &>
Very Heating Systems
650 -
heavy 0.7 – 0.9 5.3 – 6.4 Hot water &
800 steam
work Pressure/High
152-232 63.5 63.5 38.1 76.2 88.9
Temperature
Pressure/
Medium 121-151 50.8 63.5 38.1 63.5 76.2
Temperature
LIGHTING Pressure/Low
121-93 38.1 38.1 25.4 50.8 50.8
Temperature
Table (9) shows the maximum allowable Low
Temperature
93-48 25.4 25.4 12,7 38.1 38.1
Table (10) shows the minimum pipe Efficiency not Gas Fired less than 38 liters
Δ T = 50 oC
insulation thickness in mm. Piping shall be less than 80% storage
designed and installed in accordance to table
5
Proceedings of the Tenth International Conference for Enhanced Building Operations, Kuwait, October 26-28, 2010
ESL-IC-10-10-62
ICEBO2010, October 26-28, 2010, Kuwait
All piping forming part of a service water The Overall Total Thermal Transfer Value
heating system and located outside the (OTTV) for the building envelope indicates
building envelope must be insulated to the the amount of heat transferred into building
level specified in the Insulation Code for through the building façades and roof per unit
heating system pipes. Where the pipe building envelope area. The OTTV equations
insulation has a thermal conductivity of more for the walls and the roof were programmed
than, or less than, the range of the tables sited into an Excel spreadsheet, developed by the
in the Insulation Code, thickness correction author.
should be carried out in linear extrapolation of
the table range. DISUCION AND RESULTS
ELECTRICAL POWER Table (6) classified the Arab countries into 10
regions and every region have the CDD25,
The nominal cross-sectional area of wires and HDD18.3 and OTTV (W/m2). CDD range
cables must be determined according to the between 500 and 2000 while HDD ranges
Code of each Arab country of electrical between 1500 and 500. The OTTV ranges
installations in buildings, taking into between 30 and 70.
consideration, the design current, ambient
temperature, type of cable, type of insulation Table (7) classifies the Arab countries into
of cables, method of installation and grouping five regions according to the DDC10,
of cables. DDC18.3 and DDH25. For example, the first
WHOLE-BUILDING PERFORMANCE region contains Doha, Dubai and Kuwait
where DDC10 > 6000 where the outdoor
Annual energy costs analysis for the Standard weather is very hot and humid. The second
Design and the Proposed Design must each be region includes Riyadh and Aswan where
determined using the same approved energy 4000 <DDC10 < 6000 and the weather is
analysis simulation tool. The climate data used recognized as very hot and dry. The OTTV
in the energy analysis must cover a full analysis was applied to each city. The effect of
calendar year (8,760 hours) and must reflect the WWR was analyzed from 0.1 to 0.9.
approved coincident hourly data for
temperature, solar radiation, humidity and Figure (2) shows the variation between
wind speed for the building location. OTTVw and WWR. The variation is linear
STUDY CASE when WWR increases the OTTVw increases.
WWR ≤ 30% satisfy the complied OTTV for
An apartment building was used as a base case Energy Efficiency. The regression analysis
(BC) for this study. The residential building is was applied to get a general linear equation
a five-story building facing the NW between OTTV and WWR for Cairo and
direction. The apartment unit, Middle- Kuwait.
income, Mid-rise (the floor area is 105 m2).
OTTV=296.8*WWR+28.4 (KUW) (1)
The dimension of the building is 24m by 16m OTTV=323.9*WWR+21.3 (CAI) (2)
with a floor-to-floor height of 3.0 m. There Cairo Damascus Riyadh Baghdad Amman Beirut
300.00
100.00
6
Proceedings of the Tenth International Conference for Enhanced Building Operations, Kuwait, October 26-28, 2010
ESL-IC-10-10-62
ICEBO2010, October 26-28, 2010, Kuwait
Conclusion
It has been proven that increasing the glazing
area of the façade, i.e. increasing the WWR,
the OTTV increases, the building thermal
efficiency decreases. The Total Overall
Thermal Transfer value (OTTVw) for the
exterior walls should not exceed 90 W/m2,
ranges from 60 W/m2 to 90 W/m2. The
OTTVr should not exceed 12W/m2 and could
be taken as 10 W/m2
Acknowledgement
The author wishes to acknowledge the Chair
person of the Arab Energy building Codes
Prof. Dr. Omima A.S. Eldin.
References
1. Energy Efficiency Residential Building
Draft Code (2010), Final Draft the Arab
Countries by the Ministry of Housing,
HBRC, Egypt.
2. Energy Efficiency Commercial Building
Code of Vietnam (2002). Second Draft.
3. Robertson G.L. (1998). Residential
Energy Code-A New Zealand Proposal,
Proceeding Clean and Safe Energy
Forever, VOL.2, pp. 926-930.
4. ASHRAE (1997). Hand Book of
Fundamentals, ASHRAE, Atlanta, GA.
5. Energy Efficiency Residential Building
Code (2003), Ministry of Housing, HBRC,
Egypt.