Download as pdf or txt
Download as pdf or txt
You are on page 1of 11

MDC

Makati Development Corporation


Electro-Mechanical & Commissioning Division
Standards and Guidelines

Section: Design Standard Bulletin No. BL-06-EMCD-01-026-rev.0


Subject: Installation of Fire Detection and Alarm System Revision Code: 1 I Page 1 of 11
Devices
Effectivity: August 2017
Prepare Review◄ d By: Approved By:

� �
ACPugat Jr. WSPer do RpMenp/n Jr.

Responsible:
1. Construction Management, Project-in-charge, Electro-Mechanical & Commissioning Division
2. Electro-Mechanical Consultants

I. Implementation:
• Designated personnel listed above are responsible for the full implementation of these guidelines
II. Objective:
• To comply with the code provisions for fire detection and alarm system devices:

Intent Code Reference


To enforce the code require- NFPA 72 (2016), Chapter 17.7 Smoke-Sensing Fire Detectors
ments for the correct location
A.17.7.4.1 Detectors should not be located in a direct airflow or closer than 36
and spacing of SMOKE DE-
in. (910 mm) from an air supply diffuser or return air opening.
TECTORS.
17.7.3.2.3.1* In the absence of specific performance-based design criteria, one
of the following requirements shall apply:
(1) The distance between smoke detectors shall not exceed a nominal spacing
of 30 ft (9.1 m) and there shall be detectors within a distance of one-half the
nominal spacing, measured at right angles from all walls or partitions ex-
tending upward to within the top 15 percent of the ceiling height.

To enforce the code require- NFPA 72 (2016), Chapter 17.6 Heat-Sensing Fire Detectors
ments for the correct spacing
A.17.6.3.1.1 The use of a detector with a listed spacing of 9.1 m x 9.1 m should
of HEAT DETECTORS
be considered.
To enforce the code require- NFPA 72 (2016), Chapter 17.7.3.7 Projected Beam-Type Smoke Detectors
ments for the correct location
17.7.3.7.1 Projected beam-type smoke detectors shall be located in accor-
and spacing of PROJECTED
dance with the manufacturer's published instructions.
-BEAM TYPE SMOKE DE-
A.17.7.3.7 On smooth ceilings, a spacing of not more than 18.3 m between pro-
TECTORS.
jected beams and not more than one-half that spacing between a projected
beam and a sidewall (wall parallel to the beam travel) should be used as a
guide.
A.17.7.1.10 See Figure A.17.7.1.10 Smoke Detector Layout Accounting for
Stratification
B.3.2.3.1 A detector ordinarily operates sooner if it is nearer to the fire. Where
ceiling heights exceed 4.9 m (16 ft), ceiling height is the dominant factor in the
detection system response.

You might also like