Professional Documents
Culture Documents
Circuit Breaker
Circuit Breaker
Circuit Breaker
Syllabus
• Under normal conditions, these electrodes remains closed and will not
open automatically until and unless the system stability becomes
faulty.
• When ever the contacts of a circuit breaker are separated under fault
conditions an arc is struck between them.
• The current thus able to continue until the discharge ceases.
dangerous value.
Arc phenomenon
•When short circuit occurs, a heavy current flows through the contacts of the
circuit breaker before they are operated by the protection system.
•At instant when the contacts begin to separate the contact area decreases
rapidly and large fault current causes increased current density and hence rise
in temperature.
•The heat produced in the medium between contacts is sufficient to ionise the
air or vaporize and ionise the medium.
•The ionised air acts as conductor an arc struck between the contacts.
Arc phenomenon Contd…
• During the arcing period, the current flowing between the contacts
1. Degree of ionisation
2. Length of arc
• The normal frequency r.m.s voltage that appears across the breaker poles
after final arc extinction has occurred, is termed as the Recovery voltage.
The transient voltage that appears across the contacts at the instant of arc
extinction is called Restriking Voltage.
RRRV is nothing but rate which is expressed in Volts per micro-second. This will
represent the rate at which transient voltage is increasing.
With as the restriking voltage in volts then
The maximum instantaneous value attained by the restriking voltage is called the
Peak restriking voltage.
Expression for RRRV and Maximum RRRV
RRRV =
And
Average Rate of Restriking Voltage
Classification of Circuit Breakers
Based on the medium of arc
quenching circuit breakers are classified as follows,
• Only small percent (10%) of oil used for arc quenching and
remaining oil used for insulation.
Construction:
• In this two contacts are separated from each other but both filled
with oil.
• It consists of :
1.Supporting chamber
b) Moving contact
c) Turbulator
3. Top chamber
Operation of Minimum oil Circuit Breaker
• Under normal operation the moving contact remain engaged with the
upper fixed contact.
• When fault occurs the moving contact is pulled down by the tripping
strings and arc is produced.
• The arc energy vaporises the oil and produces gases under high
pressure.
• This process deposits suspended particles and makes the oil impure.
Minimum oil Circuit Breaker
Advantages:
• It requires lesser quantity of oil.
• There is a difficulty in removing the gases from the contact space in time.
• The dielectric strength of the oil detoriorated rapidly due to high degree of carbonisation.
2. For outdoor applications, minimum oil circuit breakers can be employed upto the line voltages of 220
kV.
Air-blast circuit Breaker
Air-blast circuit Breaker
• In air blast circuit breakers, compressed air at a pressure of 10-30
kg/cm is employed as an arc quenching medium.
2
• Air blast circuit breakers are suitable for operating voltages of 132 kV
and above. They have also been used in 11kV-33 kV range for certain
applications.
Axial-blast type CB
null
Cross-blast type
CB
Radial-blast type
CB
Air-blast circuit Breaker Contd...
Radial-blast
type CBnull In which the air-blast is
directed radially as shown in
Fig.null
Air-blast circuit Breaker Contd...
Advantages:
An air-blast circuit breaker has the following advantages over an oil circuit breaker:
(ii) The arcing products are completely removed by the blast whereas the oil deteriorates with successive
(iii) The growth of dielectric strength is so rapid that final contact gap needed for arc extinction is very small. This
(iv) The arcing time is very small due to the rapid build up of dielectric strength between contacts. Therefore, the
arc energy is only a fraction of that in oil circuit breakers, thus resulting in less burning of contacts.
(v) Due to lesser arc energy, air-blast circuit breakers are very suitable for conditions where frequent operation is
required.
(vi) The energy supplied for arc extinction is obtained from high pressure air and is independent of the current to
be interrupted...
Air-blast circuit Breaker Contd...
Disadvantages:
(i) The air has relatively inferior arc extinguishing properties.
(ii) The air-blast circuit breakers are very sensitive to the variations in the
Applications:
Vacuum circuit breakers are being employed for
outdoor applications ranging from 22 kV to 66 kV. Even with limited rating of say 60 to 100 MVA, they are
suitable for a majority of applications in rural areas.
Vacuum Circuit Breaker Contd…
SF6 Circuit breaker
SF is used as arc
quenching medium because it is electro negative gas and has a string tendency to absorb electrons.
Construction:
• Enclosed in a chamber
containing SF gas.
• This chamber is
connected to SF reservoir.
•The fixed hallow cylindrical current carrying contact fixed with an arcing horn.
• The high pressure SF6 gas absorbs the free electrons and arc is
extinguished.
Advantages of SF6 CB
• Very short arc quenching time
• Noiseless operation
• No moisture problem
• No risk of fire
• High cost
• More maintenance
chopping.
CURRENT CHOPPING Contd…
Theory of Current Chopping
Generally the arc extinction in a circuit breaker take place at natural current zero. But this is
true if the capacity of the breaker to extinguish the arc is varies with the level of fault current. This
means that, the arc extinction capability of breaker will always ensure that arc extinction is taking
place at natural current zero.
In Air Blast Circuit Breaker or Vacuum Circuit Breaker, the fault clearing capacity is fixed and
independent of the fault current level. In this case, when breaker is used to break the circuit of
unloaded transformer or shunt reactor, the current will be brought to zero well before the natural
current zero. This is because, the breaker is interrupting only the magnetizing current which is very
less compared to full load current or fault current. As the capability of breaker arc extinction is high
enough, therefore the low magnetizing current will be brought to zero before the natural current zero
position. This phenomena is known as Current Chopping.
CURRENT CHOPPING Contd…
Consider the circuit showing interruption of inductive currents.
Let,
L = Inductance of the system
C = Capacitance of the system
i =Instantaneous value of arc current
V = Instantaneous value of capacitor voltage (which appears across the
breaker when it opens)
CURRENT CHOPPING Contd…
Under normal condition, the current flowing through the inductor is I (say) and hence the
stored magnetic energy in it is (LI2 / 2). But as soon as the breaker is open, current chopping
will take place and the current through the reactor becomes zero. Due to this sudden drop of
current through the inductor, a high voltage will be developed across it according
to Faraday’s Law. Therefore, the voltage across the capacitor will also rise. Now, the
• The stored energy in the inductance of reactor is basically transferred to the capacitor.
LI2 / 2 = CV2 / 2
Here V = Voltage across the capacitor
Thus, V = I √(L/C)
This is the prospective voltage or Arc Voltage across the capacitor during current chopping.
Notice that this prospective voltage is above the natural voltage of the system.
CURRENT CHOPPING Contd…
If this prospective voltage is very high when compared
load and the circuit breaker. As a result, the RC combination absorbs the
overvoltages.
Resistance switching
• The interruption of low inductive currents and interruption of capacitive
contacts.
connected in parallel with the arc that is on parallel with the contacts of
• With the arc so shunted by the resistance a part of the arc current flow
• This build up of process continues until the current path through the arc
is substituted by that through resistance either wholly or in greater part.
• In later case, the small value of the current remaining in the arc path
becomes so unstable that it is easily extinguished.