GENERAL DIRECTORATE OF CIVIL DEFENCE
MINISTRY OF THE INTERIOR, STATE OF QATAR
PLAN SUBMISSION – COMPLIANCE REPORT
‐ Comment complied for kitchen hood. It is just a
note in our drawings and will be done by
manufacturer recommendation.
10. Please provide information on the
automatic sprinkler protection for the high Side wall sprinklers provided in ground floor to protect this
ceiling main entrance. No sprinklers cover area.
the area.
11. Check and verify design criteria. Light
hazard is declared but 0.15 gpm/ft2 is
used. Include in design criteria for
basement parking.
The following calculation are provided:
12. Providing separate hydraulic calculation
Sprinkler calculation for roof floor (light hazard).
for sprinklers in basement (ordinary
Sprinkler calculation for basement floor (ordinary hazard).
hazard), upper floors (light hazard) and for
Fire hose reels at roof floor.
fire hose reel system. Show results in the
summary of hydraulic calculation. Identify
in plans sprinklers considered for hydraulic
calculation.
13. Update affected drawings. Submit Noted.
compliance report signed by consultant
with clarifications to comments
14. Update detailed design report accordingly Noted.
and include other automatic fire
extinguishing system (if provided). Have it
signed by consultant and owner.
Page 2