HVAC Heatcalculations
Heat Load
M Area Reference Document Term
(Watt)
Length Metres 5.00
Width Metres 5.00
Height Metres 3.60
Area Sq. Metres 25.00
Window Height Metres 2.40
Design Condition
Outside Temperature °C 44.00 NBC Vol 2 Table 2 Part 8 Section 3 MCWB
Inside Temperature °C 22.00 PMV PPD Tool
Difference (ΔT) °C/ Kelvin 22.00
RH Outside % 60.00 MCWB - Corresponding RH Value
RH Inside % 45.00
RH Difference % 15.00
Exterior Wall U - Value W/Sq.m K 0.34 ECBC Design Guide & SP 41 Table 2
Window U - Value W/Sq.m K 1.70
Roof U - Value W/Sq.m K 9.41
Partition U-Value Wall W/Sq.m K 2.47
Partition U-Value roof W/Sq.m K 0.00
Exposed Wall 135.66
North Metres 5.00 6.00 45.22
South Metres 5.00 6.00 45.22
East Metres 0.00 0.00 0.00
West Metres 5.00 6.00 45.22
Window 1346.40
North Metres 5.00 12.00 448.80 200%
South Metres 5.00 12.00 448.80
East Metres 0.00 0.00 0.00
West Metres 5.00 12.00 448.80
Partition (Wall) Metres 5.00 18.00 755.16
Partition (Roof) Metres 0.00 0.00 0.00
Roof Sq. Metres 25.00 5176.05
Lighting (LPD) W/Sq.M 2.40 60.00 204.00 Appendix F
Occupancy People/ Sq.M 1.00 25.00 2929.00
Sensible 25.00 1805.25
Latent 25.00 1123.75
Equipment (EPD) W/Sq.M 25.00 625.00 2125.00
Infilteration 34.80 420.23
Sensible 294.01
Latent 126.22
Fresh Air 1404.44
CFM Per Person 5 Cubic Feet / Min
CFM Per Sq.M 0.64584
Total CFM 141.15 141.15
Sensible 982.61
Latent 421.83
Total Heat Load Kw 14.50
Total Heat Load Tr 4.06
Sq M/ TR 6.16
U Value of Wall
Thickness Conductivity
(M) (W/ M K) R- Value
Outer Plaster 0.015 0.73 0.021
Mineral wool 0.075 0.035 2.143
Brick Wall 0.23 0.31 0.742
Inner Plaster 0.01 0.73 0.014
Overall U value (W/Sq.M K) 0.342578476
U Value of Roof
Thickness Conductivity
(M) (W/ M K) R- Value
Roof Tile 0.012 0.84 0.014
Roof RCC Slab 150 mm 0.15 1.67 0.089820359
Inner Plaster 0.012 0.73 0.016
Overall U value (W/Sq.M K) 9.410992744
Space - 1
12 W LED Fixtures 5 60 3.6 W/ Sq M
Room 1 5 5 25 Sq M
LPD 2.4
Total Wattage/ Area