V.252 Series Addressable

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 3

V.252.1X & V.252.

2X
Addressable Fire Alarm
Protocol
Control Panel

Product Overview Special Features:


V.252 Series is EN-54-2 and EN-54-4 Certified product with a
cost effective, intelligent addressable fire alarm control panel EN-54-2 and EN-54-4 Certified
Switched Mode Power Supply.
having an extensive list of powerful features. The panel has two Modular Construction, Serviceability.
models V.252.1X single loop panel and V.252.2X two loop Networkable through software.
Auto Resettable Fuse.
panel. Higher loop requirements can be catered to using the Surge Protection.
networking feature of the panel upto 64. There is an option for Battery cut off indication.
Unique protocol feature for fast alarm
remote and local programming of the control panel using response.
configuration software / download utility. 2 Inbuilt conventional circuit.
Tactile Keypad for user-friendly operation.
Auto learning facility.

Features:
User-friendly circuit.
Inbuilt Modbus facility
2100 Event Storage with Real Time Clock.
Couse and Effect upto 99 grouping facility.
Pre Alarm Action.
All field wiring are power limited and supervised.
Programmable detector sensitivity.
Device type verification.
Earth fault annunciation facility at 0 ohms.
Walk test
Loop wise test
Lamp (LED) test.
128 X 64 Characters LCD display
Maximum 2 numbers of loops
Maximum 252 devices per loop.
Micro USB Interface for PC connectivity.
RS 485 Communication facility for Network / Repeater.
Auto Silence Facility. V.252- Series
One inbuilt Digital input.
Programmable AC Loos Delay.
Programmable Silence Inhibit.
2 Conventional Zones with LED indication
Two no’s of programmable inputs.
Battery low audio, visual warning.
Three Form C relay for Fire, Fault and Supervisory.
One Notification Appliance Circuits.
Electrical Specification:
Primary Power Relays
180 / 265VAC + 10% -15%, 60 / 50 Hz. Type : Form C
No of Relays 3
Standby Power Relay Contact Rating : 2A @ 30 VDC,
24V D.C (2 No’s of 12V, 7.2Ah) Sealed Lead acid battery 0.5A @ 125VAC.

Operating Condition Signaling Line Circuits


Operating Temperature -10 - 55° C. Loop card : 1 or 2 Nos.
Relative Humidity 93 ± 2% RH (non-condensing) at 32 No Devices per loop 252 Max
±2° C / 90 ±3° F. Loop resistance : 40 (Max.).
Loop capacitance : 0.6 µf (Max.).
Charging Circuit Loop Current : 500mA (Max.).
Charging Voltage 28 V, ±0.2V Nominal Charging
Current 1.2A (Max.). Initiating Device Circuits
Class B Style B/C Operation.
No of Conventional Zone 2
Normal Operating Voltage : 14 - 21 VDC.
Alarm Current : 15 - 30mA.
Mechanical Specification: Short Circuit Current : 45mA Maximum.
Dimensions : (480W X 340H X 100D)mm Loop resistance : 100 Maximum.
End-Of-Line Resistor : 4K7, 1/2watt
Color : White
Standby Current : 7mA (2mA for Detectors)

Programmable Input Circuit


Input type : Normal
Short Circuit Current : 10mA Max.

Construction : 16 Gauge (1.6 mm) CRCA sheet with powder-coated Finish IP


Rating : IP50
Cable Entry : 9xø19mm Knockout in top of the cabinet
9xø22.25mm Knockout in top of the cabinet
Weight : 7 Kg

Mounting Detail:
Available models

MODELS DESCRIPTION
V.252.1X Single loop panel
V.252.2X Two loop panel

Compatible Devices:

MODELS DESCRIPTION
Apollo XP 95 Addressable Series
Apollo XP 95 IS addressable Intrinsically safe series
Apollo Discovery Addressable Series
Apollo Soteria Addressable Series