KV Nano Series
Expanding Capabilities
Connector type
KEYENCE makes it
Conventional case
Normally ON CR2002
10 ms clock CR2004
Addition/ +/–
subtraction
2
All PLC models are programmed using
the same version of software.
KV Concept
Connector type Modular type
Lineup
Hardware
Conventional case Conventional case
Software
Since available software and functionality may vary PLC hardware is tied to a particular series,
depending on the PLC model, we need to keep which prevents us from using common
many versions of programming software available hardware when using a variety of PLC series.
and be mindful of the differences between them.
Specifications
KEYENCE’s
solution Same software KEYENCE’s
solution Same hardware
The KV Nano not only uses the same software as The expansion unit of the KV Nano Series can not
other KV PLCs, but it also dispels the notion that only be used for remote I/O but also works as a
programming methods cannot be consistent across shared remote I/O with the KV-8000 Series. This
different PLC models. You can still use functions like allows you to use the same parts for large and small
KV Script and real-time chart monitor, regardless of applications, resulting in cost reduction.
the PLC model.
KV-8000A KV-EP02
Real-time
chart monitor
3
Connector type: Base unit Many built-in functions
Base unit
Basic 32k Max. I/O: No. of
32-point type performance
steps 256 units: 8
Input: 16 points, output: 16 points
Transistor Built-in
3 High-speed
Interrupt
(sink) output
KV-NC32T functions positioning counter: input: 4
Logging
axes 3 channels
❚ Input unit
❚ Output unit
Transistor Transistor
KV-NC16ETE KV-NC16ET
(sink) output (sink) output
Transistor Transistor
Relay output KV-NC8ER KV-NC16ETPE KV-NC16ETP
(source) output (source) output
DC input
Transistor (sink) output
KV-NC32EXT
Input 32 points
Output 32 points
4
❚ Analog unit ❚ Temperature input unit
Thermocouple/
Voltage/current Voltage/current
KV-NC4AD KV-NC2DA platinum resistance KV-NC4TP
input output
thermometer input
KV Concept
❚ EtherNet/IPTM unit ❚ Serial adapter * Only one serial adapter can be connected to the base unit.
Lineup
Communication RS-232C × 1
RS-232C
speed KV-NC1EP KV-NC10L RS-232C/422A/ KV-NC20L
×1
100 Mbps 485 × 1
Hardware
Connection conversion unit
Connection example
For terminal block
type unit connection By using the connection
conversion unit, you can
connect terminal block type
expansion units. This allows
Software
you to select the optimum
Connector to units when designing the
KV-NC1 system.
Terminal block
KV-NC1 Terminal block type unit
❚ Communication unit
Specifications
EtherNet/IPTM compatible System configuration example
Communication unit The KV-EP02 supports both line- and star-type connections. Since there are 2 ports, the
unused port can be used as a switching hub to allow flexible wiring.
Communication
speed KV-EP02
100 Mbps Line type
8 units max.
NE-Q05(P)
Star type
5
Terminal block type: Base unit Simple lineup for easy selection
Base unit
Basic 8k Max. I/O: No. of
14-point type performance
steps 128 units: 3
Input: 8 points, output: 6 points
Relay KV-N14AR
Interface USB Serial
Base unit
Basic 8k Max. I/O: No. of
24-point type performance
steps 256 units: 8
Input: 14 points, output: 10 points
Relay KV-N24AR
Interface USB Serial
Base unit
Basic 16k Max. I/O: No. of
40-point type performance
steps 256 units: 8
Input: 24 points, output: 16 points
Relay KV-N40AR
Interface USB Serial
Base unit
Basic 16k Max. I/O: No. of
60-point type performance
steps 256 units: 8
Input: 36 points, output: 24 points
Relay KV-N60AR
AC Transistor (sink) KV-N60AT Built-in
4 High-speed
Interrupt
functions positioning counter: input: 4
Transistor (source) KV-N60ATP axes 4 channels
6
Expansion unit Optional units to expand functionality
KV Concept
Relay KV-N8EXR
DC input KV-N8EX DC input KV-N16EX Transistor
KV-N8EXT
(sink)
Lineup
8-point type 16-point type 3-point type
Screw terminal block Screw terminal block Screw terminal block
A/D conversion 2 points +
D/A conversion 1 point
* The photo shows the
KV-N8ET.
Relay KV-N8ER Relay KV-N16ER
Transistor Transistor Voltage/
KV-N8ET KV-N16ET
Hardware
(sink) (sink) current
KV-N3AM
Transistor Transistor input/
KV-N8ETP KV-N16ETP output
(source) (source)
Software
unit connection By using the connection
conversion unit, you can
connect connector type
expansion units. This allows
you to select the optimum
Terminal units when designing the
block to KV-N1 system.
KV-N1
Specifications
Connector Connector type unit
❚ Cassette
RS-232C RS-422A/485
D-sub 9-pin European terminal block
1 port 1 port
KV-N10L KV-N11L
7
Connector type
Hardware features
by type
No power supply
Space-saving while
unit required No base unit required
remaining practical
Positioning: 3 axes
High-speed counter: 3 channels
Interrupt input: 4 points
8
Terminal block More features than typical
type
small size PLC models
Built-in analog
Built-in USB port potentiometers
A standard Type B USB cable can be The base unit has 2 built-in analog
used for all KV Series models. There is potentiometers. Since their values are
no need to use different cables for assigned to specific control memories,
different series or purchase special it is easy to make fine adjustments
cables separately. during debugging.
KV Concept
Lineup
Extension cassette Expansion unit extension
attachable cable
An extension cassette can be attached The OP-87581 extension cable extends
to the 14/24-point type unit and 2 the distance between units by 1 m 3.3'.
Hardware
extension cassettes to the 40/60-point You can design your system according
type unit. to your desired layout.
Software
Specifications
Analog potentiometers
RUN-PROG selection/
error clear switch
USB port
Serial port
9
High-speed
performance
Uncompromising speed and stability
and reliability are core KV qualities
3k steps
One scan
Input
processing Interrupt input
processing
Interrupt
Program program
execution execution
(output)
10
Minimum maintenance,
maximum reliability
Overcurrent protection
Battery-less circuit for all points
The adoption of nonvolatile FeRAM To ensure high reliability, every
ensures device values and setting transistor output is equipped with an
information are retained during power overcurrent protection circuit. This
failures, without a battery. This eliminates prevents malfunction due to touching
problems due to lost device values as by mistake or damage caused by
well as battery replacement work. inrush current.
KV Concept
Lineup
Minimum installation
clearance of 30 mm 1.18" No derating in any unit
Hardware
The optimized internal structure design Derating has been eliminated by
has achieved the ability to endure high designing a housing that endures high
temperatures. The minimum installation temperatures and self-generated heat.
clearance of 30 mm 1.18" allows the This results in reliable operation for
use of smaller control panels. long periods.
❚ Derating of the KV-24AR in front mounting
Effective for use in
30 mm smaller control panels 120
Continuous simultaneous ON ratio (%)
Software
30 At maximum
55°C
mm 80 load current
131°F
1.18" At maximum load current 100%
60
56%
30 40 Base unit only 44%
mm
1.18" 20 With expansion unit
30 mm 0
1.18" 30 35 40 45 50 55
86 95 104 113 122 131
Ambient temperature (°C °F)
Specifications
11
Simple but full scale motor control now possible
Built-in
positioning function
positioning function
. axes
12
Easy programming and serious debugging
Dedicated point
parameters
All positioning-related settings can be
specified easily by just selecting
parameters. Since all parameters have
been assigned to CMs (control
memories), they can be changed with
KV Concept
a ladder program.
Lineup
Many dedicated
instructions Built-in function monitor Real-time chart monitor
Instructions frequently used for A special monitoring window is You can monitor various items
positioning control have been provided available that can be used for simultaneously on one screen,
Hardware
as dedicated instructions. debugging positioning control. The including the current coordinates,
Programming can be finished easily in window shows device comments as speed, and a positioning complete
one line only, reducing programming well which greatly improves debugging flag. When the real-time chart monitor
man-hours. efficiency. is opened from the built-in function
monitor, related devices are registered
automatically.
PSTRT Positioning
Software
JOG JOG Operation
TCH Teaching
Specifications
RFSPS Current value refresh
13
High-speed counter
and
SD card application Highly-functional and wizard-
driven high-speed counter,
similar to module-type PLCs
100 kHz
Interrupt based on comparator coincidence
100 kHz
Comparator coincidence output
100 kHz
Direct clock pulse output
Frequency counter
function Cam switch function
Input pulses are automatically A rotary encoder can be connected to
converted into frequency (Hz) or provide an output at a specified
rotational speed (rpm) and then stored position (angle). Up to 32 points of
into a DM (data memory). This output positions can be set in units of
eliminates the need for calculations 0.1 degrees. Both absolute and
using a ladder program, simplifying incremental encoders are supported.
operation.
14
Logging function Trace function
Device data can be logged to an SD The data before and after the
card by completing just 2 steps. occurrence of an event can be saved,
Logging triggers are flexible and can which makes troubleshooting easy. The
be issued not only periodically but also trace function can be used easily even
based on specific instructions. without an SD card.
KV Concept
Set a device
to be logged and
a trigger.
Lineup
Auto loading function FTP client/server function
Programs can be saved to or loaded By using the KV-NC1EP, you can
from an SD card. This allows for upload the data on an SD card to a PC
program changes to be made off-site in CSV format. This allows you to
and then transferred via the SD card. establish a traceability system easily.
Hardware
Uploading of PLC internal data
Updated (Logging data such as temperature data)
when the power is
turned on/off
Software
Also possible by turning the device (CR) on/off KV-NC1EP (PLC data such as parameters)
Easy-to-use applications
Specifications
enabled by the SD card
* The SD card slot is provided on the KV-NC32T only.
15
Ethernet/
KV sensor network
* Possible with the KV-NC32T only * Possible with the KV-NC32T only
Simple PLC link PLC link with units from Easy setup with the
function other manufacturers dedicated setting window
In the past, linking to another PLC Not only is easy PLC link possible The PLC link can be established easily
typically required a socket between KV models, but also with MC by just setting items in dedicated
communication program. But now, an protocol-compatible PLCs from other window. No ladder program is required
Ethernet-based PLC link can be manufacturers. This makes it easy to for the link.
established easily. establish communication with an
existing system.
Bit devices of 4096 bits or word devices of 256 words Bit devices of 4096 bits or word devices of 256 words
can be communicated per setting can be communicated per setting
16
Sensor
Remote I/O
KV Nano Series
Sensors and remote I/O
KV Concept
* Illustrative drawing
Lineup
Simplified wiring with Connection without Various dedicated
a LAN cable programming monitors
Unlike with previous models, the PLC Communication setup can be Dedicated remote I/O and sensor
and a sensor can be connected quickly completed by just connecting the monitors are provided. KEYENCE’s VT5
with a commercial LAN cable, saving equipment, supplying power, and touch panel allows monitoring of
Hardware
hours normally spent on cable creation clicking the Auto Configuration button. equipment in a list without creating a
and wiring. There is no need for complicated screen. It is useful for identifying the
communication programs or individual cause of problems.
unit setup, saving many hours of work.
Software
LAN
cable
Specifications
IP address setting with Device comment
Space saving a rotary switch registration unnecessary
The industry’s lowest profile case IP addresses can be set with a built-in The comment information of configured
requires a minimal installation space. rotary switch on the communication devices is automatically registered. You
European terminal block-type models unit. This ensures easy setting for can retrieve comments without using
have an all-point common terminal. No anyone, using either software or device numbers, resulting in a
external terminal block is necessary hardware. reduction of programming hours.
which leads to further space saving.
Can be sorted
48.9 mm Just open the lid and set the IP address
by model
17
Analog/
temperature control
-10 to 10 V
0 to 10 V 0 to 20 mA
High-speed conversion 80 µs/channel
0 to 5 V 4 to 20 mA
High resolution 1/4000
1 to 5 V
Overall accuracy ±0.3%
Thermocouple
Zero clip
Thermocouple
18
KV Concept
Unit Editor for easy
For higher speed and
configuration Scaling function higher accuracy
All of the settings, such as the range of Values loaded from external equipment analog control
I/O signals and averaging, can be can be converted (scaled) to the
Lineup
specified with the Unit Editor. No desired values. This eliminates the
setting program is required. need for a calculation program in the
ladder program.
Ultra-high-speed
sampling of 10 µs
In accordance with the high-
Hardware
speed performance of the CPU
unit, the conversion speed has
been increased greatly to
10 µs/channel. The resolution
has also been improved to
1/20000 to ensure high
precision. This leads to higher
production efficiency and
Software
improved quality.
Useful instructions
Real-time chart monitor provided
During debugging, you can monitor the Many useful instructions for analog
change in values as a waveform. Data control and temperature control have
Specifications
can be acquired for each scan time, been provided to allow a wider range
which enables identification of of controls.
instantaneous changes.
PID with auto-tuning KV-SAD04 KV-SDA04
19
Serial Use serial for PLC link
communication
and Modbus communication
Link up to 16 units,
96 words Serial PLC link setting
Distributed control or PLC link can be The dedicated setting window allows
achieved through serial for setup of the serial PLC link without
communication. An algorithm for needing to reference the manuals. The
minimizing the influence of ladder setup items are shown in a list so that
execution on serial communication they can be easily checked.
processing ensures delays are
eliminated in PLC links.
KV-8000A KV Nano
Write
Read
Master unit Other
unit
512 bits, 96 words
Modbus master/slave
function Modbus trace function
Open network Modbus communication A dedicated Modbus communication
can be established easily. The function debugging function has been
supports both the master function for provided. The contents of commands
controlling temperature controllers, etc. and responses can be monitored
and the slave function for controlling without a protocol analyzer, so that
touch panels or other equipment many startup hours can be reduced.
connected to the master.
Temperature
KV Nano
Changing a controller
setting value
Reading a
current value
* Also possible with the KV Nano (connector type)
link
communication
20
Ladder support software that can be operated intuitively
Easy-to-use
The KV Nano is compatible with KV STUDIO, the configuration software for the KV Series.
software interface
This allows you to utilize the same software for simple or complicated applications, making startup easier.
KV Concept
AND searches.
AND
searching
is possible. Candidate
display
Lineup
Unused device search Customizable keys Windows®-style operation
When “?” is added after a device Even if you are used to using different The basic operation follows Windows®-
number, unused devices on the ladder software, switching to this style operation. Programming proceeds
Hardware
program are displayed as input software is easy and intuitive. Users in a familiar way.
candidates. This eliminates the need to can specify their own keyboard
check usage status. operations by assigning unique
shortcut keys.
Software
Paste Ctrl + V
Find Ctrl + F
Replace Ctrl + H
Specifications
Comfortable operation
based on your intuition
and style
21
Even instantaneous changes will not be
Real-time missed by Real-time chart monitor
chart monitor
Instantaneous changes
detectable Trace function
Device data is stored in the CPU The trace function captures data before
memory and then loaded to a PC. Even and after the occurrence of an event,
instantaneous changes which are which is useful for troubleshooting. The
normally overlooked can be recognized cycle can be set for each scan.
reliably.
Stored as
a graphic
Stored as a
CSV file
22
Real-time chart monitor applications
Erroneous sensor
output detection
Erroneous sensor
In the event of a problem output detection
with a sensor signal count,
symptoms that previously
required an oscilloscope to
check can now be identified.
KV Concept
Simultaneous monitoring of count values
Lineup
Detection of
malfunctions due
Hardware
to the influence of Fluctuating analog values during
operation of other devices
other devices
When a problem occurs with
a captured analog value,
monitoring the bit and word
data at the same time makes
it easy to determine the
Software
cause.
Specifications
Timing deviation
detection
Timing sensor rising
Even if a malfunction occurs edge and offset
due to timing discrepancies
between bits or with controls
that use bit signals to
acquire analog values,
finding the cause is easy.
23
KV Script allows for easy programming of calculations,
conditional branching, and more
KV Script
Box script
Condition execution script
that allows execution conditions
to be described with a ladder.
Area script
Regular execution
script with no
execution conditions.
Ladder-based description
KV Script-based programming
Execution Algorithms
conditions are can be directly
programmed in programmed
a ladder
24
Function Input Guidance Usable operators and control statements in KV Script
Even if you can’t remember a function,
simply press the shortcut keys (Ctrl + Operator
Space) and enter a few letters to show Type Operator Description
a list of functions starting with the + Calculate summation of 2 values (addition)
entered text. − Calculate difference of 2 values (subtraction)
Arithmetic
* Calculate product of 2 values (multiplication)
/ Calculate quotient of 2 values (division)
[Enter] ^ Calculate the power
Entry guidance MOD Divide 2 values, return remainder
is displayed. < Less than
<= Less than or equal to (or less)
> Greater than
Compare
>= Greater than or equal to (above)
= Equal to (equivalent)
[Ctrl]+[Space] <> Unequal to (non-equivalent)
A list of functions is displayed. (When an alphabetical letter is
= Substitute the right into the left
entered, a narrowing-down search is carried out.)
+= Right plus Left
Assign –= Right minus Left
* = Right multiplied by Left
/= Left is divided by Right
Character string +, & Connect 2 character strings
Manual Search Function AND Logical multiplication of 2 values (AND)
KV Concept
OR Logical addition of 2 values (OR)
Logic
XOR EOR logic of 2 values
To provide quick access to information NOT Calculate logical not value
on how to use an inserted function,
press the shortcut key (F1) to view the
Control Statement
manual of the relevant function.
Control
Type Description
statement
Lineup
brings up the Help display. ELSE IF <Conditional equation 2> THEN
(If the condition 2 is true, executed)
IF statement ELSE IF <Conditional equation 3> THEN
(If the condition 3 is true, executed)
ELSE
(If all the conditions are not true, executed)
END IF
Hardware
SELECT CASE <Device comparison>
Conditional
CASE <Condition 1>
Tool tip monitor branch
(When equal to condition 1, executed)
CASE <Condition 2><Condition 3>
(When equal to condition 2 or condition 3, executed)
Simply placing the cursor over the CASE <Condition 4> T0 <Condition 5>
SELECT statement
device during monitoring displays the (When condition 4 and condition 5 are met, executed)
CASE IS <Comparison> <Condition 6>
device comments and current values, (When the comparison with 6 is true, executed)
so monitoring a device is easy. CASE ELSE
(When equal to none of the conditions, executed)
END SELECT
Software
Placing the cursor over a device displays MC <Conditional equation> THEN
MC statement (If the condition is true, executed)
the device comments and the current MCR
value (during monitoring)
Specifications
FOR statement (When the loop condition is met, loop is executed)
NEXT
Data Type
Suffix Description
(Device) .U Processed as unsigned 16-bit data* (0 to 65535)
(Device) .S Processed as signed 16-bit data (-32768 to 32767)
(Device) .D Processed as unsigned 32-bit data (0 to 4294967295)
(Device) .L Processed as signed 32-bit data (-2147483648 to 2147483647)
Processed as floating real number data
-3.4E+38 ≤ n ≤ -1.2E-38
Click! (Device) .F
n=0
+1.2E-38 ≤ n ≤ +3.4E+38 (Significant digits: Approx. 7 digits)
Handled as double precision floating point actual number data
-1.79E+308 ≤ n ≤ -2.23E-308
(Device) .DF
n=0
+2.23E-308 ≤ n ≤ +1.79E+308 (Significant digits: Approx. 16 digits)
(Device) .B Processed as bit data (ON: TRUE, OFF: FALSE)
(Device) .T Processed as text string data
* .U can be omitted when programming.
Word device without postfixes handled as 16-bit unsigned data.
25
Efficient
debugging
Efficient debugging
by visualizing
everything you
want to see
Up to four
devices can be
monitored.
26
More comfortable debugging environment
Simulation function
You can simulate operation on the PC
without using an actual PLC. The
registration monitor and batch monitor
can also be used to perform
debugging.
Line invalidation
KV Concept
A section of code that you want to
disable temporarily during debugging
can be invalidated with a single
operation. Re-enabling the code is also
accomplished easily.
Lineup
F12: Contact coil jump
Every time the F12 key is pressed, the
Hardware
cursor jumps to the next contact (coil) F12
of the same device number. This is
useful for troubleshooting during
debugging.
Software
F1: Instruction help
function
Specifications
The description of a selected
instruction can be displayed with a
single button-press. This allows you to
quickly find information without
searching through multiple documents.
F1
27
SPECIFICATIONS (Connector type)
1500 VAC for 1 minute, between power supply terminal and I/O terminals and between all external terminals and case
Withstand voltage
(1000 VAC for 1 minute, between power supply terminal and output terminals for the transistor output type expansion I/O unit)
28
Input specifications - Base unit
Model KV-NC32T
Input type General input High-speed A-phase and B-phase input
Relay number R000 to R009 (10 points) R010 to R015 (6 points)
Input mode 24 VDC input (open collector)
Maximum input voltage 26.4 VDC
Rated input voltage 24 VDC (5.3 mA*1) 24 VDC (6.5 mA*1)
Minimum ON voltage 19 VDC
Maximum OFF current 1.5 mA
Common point mode All points/1 common (1 terminal)
OFF to ON: Max. 30 μs (Typ. 3.5 μs) OFF to ON: Max. 2 μs (Typ. 1.1 μs)
Circuit delay time*2
ON to OFF: Max. 50 μs (Typ. 15 μs) ON to OFF: Max. 2 μs (Typ. 0.3 μs)
Normal: 10 ms, When the HSP instruction is used: 10 μs
When CR2305 is turned ON: 10 μs to 10 ms, eight-level switching is possible (set with CM1620). Can also be set from the Unit Editor.
Delay by input time constant
Input time constant setting Digital filter
10 μs 1.6 to 2 μs
20 μs 9 to 12 μs
Input time constant*2
110 μs 90 to 93 μs
500 μs 300 to 400 μs
1 ms 800 to 900 μs
KV Concept
2.5 ms 2.3 to 2.4 ms
5 ms 4.0 to 4.5 ms
10 ms 9 to 9.5 ms
Response frequency − Single phase: 100 kHz, phase difference: 50 kHz, 24 V ±10%, Duty 50%
*1 Reference value of input current.
*2 T he input response time corresponding to the input time constant can be calculated as shown below.
(Response time) = (Circuit delay of the input circuit) + (Delay by the digital filter)
Example: Maximum response time when the input time constant is set to 10 μs OFF to ON: 2 μs (circuit delay) + 2 μs (digital filter) = 4 μs
ON to OFF: 2 μs (circuit delay) + 2 μs (digital filter) = 4 μs
Example: Maximum response time when the input time constant is set to 500 μs OFF to ON: 30 μs (circuit delay) + 400 μs (digital filter) = 430 μs
ON to OFF: 50 μs (circuit delay) + 400 μs (digital filter) = 450 μs
Lineup
Output specifications - Base unit Specifications - Built-in serial port
Model KV-NC32T Type Built-in port
Input type General output High-speed output Communication standard RS-232C
Interface
Relay number R506 to R515 (10 points) R500 to R505 (6 points) Connection Modular connector
Output mode MOSFET (N-ch) output 1200, 2400, 4800, 9600, 19200,
Transmission rate
Rated load 30 VDC, 0.2 A (1.6 A/common) 30 VDC, 0.3 A (1.6 A/common) 38400, 57600, 115200 bps
Hardware
Maximum OFF voltage 30 VDC Transmission method Full duplex
Leakage current when OFF 100 μA or less Start bit 1 bit
Transmission
Residual voltage when ON 0.6 VDC or less Data format Data bit 7 bits, 8 bits
specifications
16 points/1 common 16 points/1 common Stop bit 1 bit, 2 bits
Common point mode
(Common to high-speed output) (Common to general output) Error detection Parity Even, odd, none
OFF to ON: 100 μs OFF to ON: 2 μs Transmission distance 15 m 49.2'
(load of 1 mA or more) (load of 7 mA or more) Number of transmission units 1
ON/OFF response time
ON to OFF: 200 μs ON to OFF: 5 μs Common between SD/RD
(load of 1 mA or more) (load of 7 mA or more) SD: (green)
Indication
Software
Overcurrent protection Protection provided for each common* 1 RD: (red)
100 kHz The color may appear as orange during transmission.
Output frequency −
(7 to 100 mA load)
*1 If an overcurrent occurs, protection operation (output turned OFF) and automatic recovery are repeated for all
outputs within the shared common until the cause of the problem is removed.
Specifications
Model Model
(16 points) (16 points) (32 points) (8 points) (16 points) (16 points) (32 points)
European Output mode Relay MOSFET (With overcurrent protection function)*1 *6
External connection method Connector Connector
terminal block External connection European
European terminal block Connector Connector
24 VDC 5 VDC 24 VDC 5 VDC 24 VDC 5 VDC method terminal block
Input terminals
mode mode mode mode mode mode Rated load 250 VAC/30 VDC, 2 A 30 VDC. 0.2 A*7
Maximum input voltage 26.4 VDC Leakage current when OFF − 100 µA or less
24 VDC, 5 VDC 24 VDC, 5 VDC 24 VDC, 5 VDC Residual voltage when ON − 0.6 VDC or less
Rated input voltage
5.2 mA 1 mA 5.2 mA 1 mA 5.2 mA 1 mA ON resistance 50 mΩ or less −
Minimum ON voltage 19 V 3.5 V 19 V 3.5 V 19 V 3.5 V 4 points/1 common 16 points/1 common 16 points/1 common 32 points/1 common
Common point mode
Maximum OFF current 1.5 mA − 1.5 mA − 1.5 mA − (8 terminals)*3 (2 terminals)*2 *4 (16 terminals)*2 (2 terminals)*2 *5
Maximum OFF voltage − 1.5 V − 1.5 V − 1.5 V Response OFF to ON 100 μs or less (with a load of 1 mA or more)
10 ms or less
16 points/1 common 16 points/1 common 32 points/1 common time ON to OFF 200 μs or less (with a load of 1 mA or more)
Common point mode
(2 terminals)*1 (2 terminals)*2 (2 terminals)*1 Internal current consumption 70 mA or less 30 mA or less 30 mA or less 50 mA or less
Weight Approx. 130 g Approx. 100 g Approx. 120 g Approx. 110 g
Input time OFF to ON ON to OFF
constant setting Typ. Electrical: 100000 cycles
Max. Typ. Max.
or more (20 cycles/minute)
Input time constant 25 μs 10 μs 50 μs 50 μs 150 μs Relay life −
Mechanical: 20000000
(four-level switching) 300 μs 240 μs 290 μs 280 μs 390 μs
cycles or more
1 ms 1 ms 1.2 ms 1 ms 1.2 ms
Relay replacement Impossible −
10 ms 10 ms 11 ms 10 ms 11 ms
*1 If even a single overcurrent is detected, the protection operation (output turned OFF) and automatic recovery are repeated for
Input impedance 4.4 kΩ all outputs within the shared common*4 *5, until the cause of the problem is removed.
*2 T he COM terminals of the KV-NC16ET(P), KV-NC16ET(P)E and KV-NC32ET(P) are shorted internally.
Internal current consumption 20 mA or less 20 mA or less 20 mA or less *3 T he KV-NC8ER has four terminals for each of C0 and C1 respectively, which are shorted internally. (C0 and C1 are
Weight Approx. 100 g Approx. 120 g Approx. 110 g independent.)
*1 T he KV-NC16EX and KV-NC32EX have 2 COM terminals, but these are shared internally. *4 The outputs within the shared common that are protected when an overcurrent is detected are outputs 000 to 007 or 008 to 015 for the
*2 The KV-NC16EXE has 16 COM terminals, but these are shared internally. KV-NC16ET(P) or KV-NC16ET(P)E.
*5 T he outputs within the shared common that are protected when an overcurrent is detected are outputs 000 to 015 or 100 to
115 for the KV-NC32ET(P).
*6 M OSFET (N-ch) output for the sink output type; and MOSFET (P-ch) output for the source output type.
*7 T he rated load per common terminal is 1.6 A for the KV-NC16ET(P) or KV-NC32ET(P) and 3.2 A for the KV-NC16ET(P)E.
29
SPECIFICATIONS (Connector type)
*1 When the temperature fluctuation compensation is used, the temperature fluctuation compensation time of 80 μs will be added regardless of the number of channels being used.
30
Specifications - EtherNet/IPTM unit (communication specifications)
Model KV-NC1EP
No. of connections 64*5
0.5 to 10000 ms (0.5 ms increments) Setting is possible for each connection.
RPI (communication cycle)
(Data is updated on the line at specified cycles, independent of the number of nodes.)
Output to adapter Cyclic
Transmission trigger
Input from adapter Cyclic/Change Of State*1
Cyclic
(at 504 Byte) 6000 (pps)*2
communication Allowable band for cyclic communication
CIP (at 1444 Byte) 3000 (pps)*2
service Maximum number of refresh words 8000 words
KV Concept
Specifications - EtherNet/IPTM unit (performance specifications)
Model KV-NC1EP
Lineup
No. of sockets
Function name Port No.
TCP UDP
PC application*1 8 0 8500 (can be set within the range between 1 and 65535)
Upper link communication*2 *3 1 8501 (can be set within the range between 1 and 65535)
Total: 15
MC protocol communication*2 *3 1 5000 (can be set within the range between 1 and 65535)*4
VT5/VT3 connection 0 1 8502 (can be set within the range between 1 and 65535)
FTP server 4 − 20, 21
Automatic clock data adjustment − 1 123
Hardware
DNS − 1 53
FTP client 2 − 20, 21 (can be set within the range between 1 and 65535)
Simple PLC link − 1 5001 (can be set within the range between 1 and 65535)
EtherNet/IPTM cyclic communication function 1 2222
Total: 320
EtherNet/IPTM message communication function 1 44818
Internal current consumption 90 mA or less
Weight Approx. 110 g
*1 KV STUDIO
*2 TCP sockets and UDP socket can be used simultaneously.
*3 Up to 15 TCP sockets can be used in total.
Software
*4 Port numbers can be assigned individually to TCP and UDP sockets.
Specifications
Specifications - Serial communication adapter
Model KV-NC10L KV-NC20L
Port − Port1 Port2
RS-422A
Communication standard RS-232C RS-485 (2-wire)
Interface RS-485 (4-wire)
Connection D-sub 9-pin European terminal block
Transmission rate 1200, 2400, 4800, 9600, 19200, 38400, 57600, 115200 bps
Transmission method Full duplex Half duplex
Start bit 1 bit
Data format Data bits 7 bits, 8 bits
Transmission Stop bits 1 bits, 2 bits
specifications Error detection Parity Even, odd, none
RS/CS flow control Enabled, disabled −
Transmission distance 15 m 49.2' Extendable up to 1200 m 3937.0'
Number of transmission units 1 32
Electrical termination (Terminator) − Set with the switch on the front panel of the main unit
Indication SD (orange), RD (orange)
Weight Approx. 100 g Approx. 110 g
31
SPECIFICATIONS (Terminal block type)
High-speed counter 4 points (CTC0 to CTC3) 6 points (CTC0 to CTC5) 8 points (CTC0 to CTC7)
CTC
comparator 32 bits, two points per high-speed counter
Index register Z 12 points 32 bit (Z01 to Z12)
Control memory CM 9000 points 16 bit (CM0 to CM8999)
2 axes 3 axes 4 axes
Positioning pulse output*3
Maximum output frequency: 100 kHz (KV-NxxxT(P) only)
Input: 8 points, output: 6 points Input: 14 points, output: 10 points Input: 24 points, output: 16 points Input: 36 points, output: 24 points
Input common: 1 point Input common: 1 point Input common: 1 point Input common: 1 point
Base unit I/O
Output common: 4 points (R type) Output common: 5 points (R type) Output common: 6 points (R type) Output common: 8 points (R type)
1 point (T/TP type) 1 point (T/TP type) 2 points (T/TP type) 3 points (T/TP type)
10000 20000
Number of comments/ Device comment
When a maximum-length ladder program is written with no labels.
labels
14000 28000
stored in main unit Label
When a maximum-length ladder program is written with no device comments.
Power off hold Program memory Flash ROM can be rewritten 10000 times
function Device*4 Nonvolatile RAM
Self-diagnosis function CPU error, RAM error, and other problems
*1 You can also configure the settings so that automatic reset is not used.
*2 Only open collectors are supported. Line drivers are not supported.
*3 The relay output types (KV-NxxxR) do not have the positioning pulse output function.
*4 You can set the target device by clicking “CPU system setting” and then “Power off holding” in KV STUDIO.
32
Input specifications - Base unit
Model KV-N14xx KV-N24xx KV-N40xx KV-N60xx KV-N14xx KV-N24xx KV-N40xx KV-N60xx
Input type General input High-speed A-phase and B-phase input
R000 to R003, R008 R000 to R007, R014 R000 to R007, R100 R004 to R007 R004 to R007 R008 to R013 R008 to R015
R000 to R003
Relay number to R013 to R107 to R203 (2 channels, (2 channels, (3 channels, (4 channels,
(4 points)
(10 points) (18 points) (28 points)*1 4 points in total) 4 points in total) 6 points in total) 8 points in total)
Input mode 24 VDC input (open collector)
Maximum input voltage 26.4 VDC
Rated input voltage 24 VDC (5.3 mA*2) 24 VDC (6.5 mA*2)
Minimum ON voltage 19 VDC
Maximum OFF current 1.5 mA
Maximum OFF voltage −
Common point mode All points/1 common (1 terminal) Shared common for all points (shared with general input)
OFF to ON: Max. 30 μs (Typ. 3.5 μs)
ON to OFF: Max. 50 μs (Typ. 15 μs)
OFF to ON: Max. 2 μs (Typ. 1.1 μs)
Circuit delay time*3 * The values are as shown below for R108 to R203 of the KV-N60xx.
ON to OFF: Max. 2 μs (Typ. 0.3 μs)
OFF to ON: Max. 50 μs (Typ. 7 μs)
ON to OFF: Max. 150 μs (Typ. 70 μs)
Normal: 10 ms, When the HSP instruction is used: 10 μs
When CR2305 is turned ON: 10 μs to 10 ms, eight-level switching is possible (set with CM1620). Can also be set from the Unit Editor.
Input time constant setting Digital filter
KV Concept
10 µs 1.6 to 2 µs
20 µs 9 to 12 µs
Input time constant*3 110 µs 90 to 93 µs
500 µs 300 to 400 µs
1 ms 800 to 900 µs
2.5 ms 2.3 to 2.4 ms
5 ms 4.0 to 4.5 ms
10 ms 9 to 9.5 ms
Response frequency − Single phase: 100 kHz, phase difference: 50 kHz, 24 V ±10%, Duty 50%
Lineup
*1 The response time increases for R108 to R203.
*2 Reference value of input current.
*3 T he input response time corresponding to the input time constant can be calculated as shown below. (Response time) = (Circuit delay of the input circuit) + (Delay by the digital filter)
Example: Maximum response time when the input time constant is set to 500 μs
OFF to ON: 30 μs (circuit delay) + 400 μs (digital filter) = 430 μs
ON to OFF: 50 μs (circuit delay) + 400 μs (digital filter) = 450 μs
Hardware
Output specifications - Base unit (Transistor output type)
Model KV-N14xT(P) KV-N24xT(P) KV-N40xT(P) KV-N60xT(P) KV-N14xT(P) KV-N24xT(P) KV-N40xT(P) KV-N60xT(P)
Output type General output High-speed output
R504 to R505 R504 to R509 R506 to R515 R508 to R607 R500 to R503 R500 to R503 R500 to R505 R500 to R507
Relay number
(2 points) (6 points) (10 points) (16 points) (4 points) (4 points) (6 points) (8 points)
Output mode MOSFET* 1
Software
Residual voltage when ON 0.8 VDC or less (with 0.5 A output), 0.6 VDC or less (with 0.3 A output)
Common point mode 8 to 10 points/1 common
OFF to ON: 100 μs (load of 1 mA or more) OFF to ON: 2 μs (7 to 100 mA load)
ON/OFF response time
ON to OFF: 200 μs (load of 1 mA or more) ON to OFF: 5 μs (7 to 100 mA load)
Overcurrent protection Protection provided for each common* 2
Specifications
*2 If an overcurrent occurs, the protection operation (output turned OFF) and automatic recovery are repeated for all outputs within the shared common until the cause of the problem is removed.
Output specifications - Base unit (Relay output type) Specifications - Built-in serial port
Model KV-N14xR KV-N24xR KV-N40xR KV-N60xR Type Built-in port
R500 to R505 R500 to R509 R500 to R515 R500 to R607 Communication standard RS-232C
Relay number Interface
(6 points) (10 points) (16 points) (24 points) Connection Modular connector
Output mode Relay 1200, 2400, 4800, 9600,
Rated load 250 VAC/30 VDC, 2 A Transmission rate 19200, 38400, 57600,
ON resistance 50 mΩ or less 115200 bps
Minimum applicable load 100 μA/100 mVDC Transmission method Full duplex
Common point mode 2 to 4 points/1 common Start bit 1 bit
Data
ON/OFF response time 10 ms or less Transmission Data bit 7 bits, 8 bits
RS-232C format
Electrical: 100000 cycles or more (20 cycles/minute) specifications Stop bit 1 bit, 2 bits
Relay life
Mechanical: 20000000 cycles or more Error
Parity Even, odd, none
Relay replacement Impossible detection
Transmission distance 15 m 49.2'
Number of
1
transmission units
Indication SD (green), RD (red)
33
SPECIFICATIONS (Terminal block type/communication unit)
Input
constant setting Typ. Max. Typ. Max. Common point mode 8 points/1 common (1 terminal)*1
Output
Leakage current when OFF − 100 µA or less Common point mode
(2 terminals)*1 *2 (4 terminals)*1 *3
0.8 VDC or less (with 0.5 A output)
Residual voltage when ON − 100 μs or less
0.6 VDC or less (with 0.3 A output) OFF to ON
ON resistance 50 mΩ or less − Operation (with a load of 1 mA or more)
10 ms or less
4 points/1 common 8 points/1 common 16 points/1 common time 200 μs or less
Common point mode Independent ON to OFF
(8 terminals)*1 (4 terminals)*2 (8 terminals)*2 *4 (with a load of 1 mA or more)
100 μs or less Electrical: 100000 cycles
OFF to ON
Response (with a load of 1 mA or more) or more (20 cycles/minute),
10 ms or less
time 200 μs or less Relay life −
ON to OFF Mechanical: 20000000 cycles
(with a load of 1 mA or more)
or more
Electrical: 100000 cycles
Relay life or more (20 cycles/minute) − Relay replacement Impossible −
Mechanical: 20000000 cycles or more Internal current consumption 60 mA or less 30 mA or less
Relay replacement Impossible − Weight Approx. 230 g Approx. 210 g
Internal current consumption 60 mA or less 100 mA or less 30 mA or less 40 mA or less *1 The input COM and output COM terminals are independent.
Weight Approx. 230 g Approx. 260 g Approx. 160 g Approx. 210 g *2 The KV-N8EXR has two output terminals for each of C1 and C2 respectively, but each pair of these terminals is
shared internally. (C1 and C2 are isolated.)
*1 T he KV-N16ER has two terminals for each of C0, C1, C2, and C3 respectively, which are shorted internally. *3 The KV-N8EXT has four COM output terminals, but these terminals are shared internally.
(C0, C1, C2, and C3 are independent.) *4 If even a single overcurrent is detected, the protection operation (output turned OFF) and automatic recovery are
*2 T he KV-N8ET(P) and KV-N16ET(P) COM terminals are shorted internally. repeated for all outputs within the shared common, until the cause of the problem is removed.
*3 If even a single overcurrent is detected, the protection operation (output turned OFF) and automatic recovery are repeated for all
outputs within the shared common*4, until the cause of the problem is removed.
*4 The outputs within the shared common that are protected when an overcurrent is detected are outputs 000 to 007 or 008 to 015
for the case of the KV-N16ET(P).
*5 MOSFET (N-ch) output for the sink output type; and MOSFET (P-ch) output for the source output type.
34
Specifications - Extension serial communication cassette
Model KV-N10L KV-N11L
Communication standard RS-232C RS-422A/RS-485 (4-wire) RS-485 (2-wire)
Interface
Connection D-sub 9-pin European terminal block (cannot be removed or reconnected)
Transmission rate 1200, 2400, 4800, 9600, 19200, 38400, 57600, 115200 bps
Transmission method Full duplex Full duplex Half duplex
Start bit 1 bit
Data format Data bit 7 bits, 8 bits
Transmission Stop bit 1 bit, 2 bits
specifications Error detection Parity Even, odd, none
RS/CS flow control Enabled, disabled −
Transmission distance 15 m 49.2' Extendable up to 1200 m 3937.0'*1
Number of transmission units 1 32*1
Electrical termination (Terminator) − Set with the switch on the front panel of the main unit
Indication SD (orange), RD (orange)
Weight Approx. 30 g
*1 This varies depending on the model. For details, see the KV Nano Series “Serial Communication Function User’s Manual.”
KV Concept
Ambient temperature 0 to +55°C 32 to 131°F (no freezing)*1 *2 Message communication
Ambient humidity 5 to 95% RH (no condensation)*1 Supported functions
(Explicit message communication)
Ambient storage EtherNet/IPTM UCMM and Class 3 supported
−25 to 75°C −13 to +167°F
temperature specifications Number of connections 64
Ambient storage humidity 5 to 95% RH (no condensation)*1 RPI (communication cycle) 0.5 to 10000 ms (0.5 ms increments)
Operating environment As little dust and corrosive gas as possible
Trigger Cyclic
Operating altitude 2000 m 6561.7' or less
Conformance test Conforming to CT14
Pollution degree 2
Overvoltage category I * EtherNet/IPTM is a registered trademark or a trademark of ODVA.
Lineup
1500 VAC for 1 minute, between power supply terminal and I/O terminals and
Withstand voltage between all external terminals and case (1000 VAC for 1 minute, between power supply terminal and Performance specifications - KV-EP02
output terminals for the transistor output type expansion I/O unit)
Specifications
50 MΩ or more (500 VDC megger used to perform measurements between power supply terminal and Item
Insulation resistance 10BASE-T 100BASE-TX
input terminals, and between all external terminals and case)
Connection interface RJ-45 8-pole modular connector × 2 ports
Intermittent vibration Scan times
Transmission rate*1 10 Mbps 100 Mbps
Frequency Acceleration Half amplitude
5 to 9 Hz - 3.5 mm 0.14" UTP or STP UTP or STP
Conforms 10 times Transmission media*2 of category 3 or higher of category 5 or higher
9 to 150 Hz 9.8 m/s2 32.2'/s2 -
Vibration resistance*3 to JIS B 3502 (100 minutes) (STP is recommended) (STP is recommended)
Hardware
Continuous vibration
and IEC61131-2 in each of the X, Y,
Frequency Acceleration Half amplitude and Z directions Maximum cable length*3 100 m 328.1' 100 m 328.1'
5 to 9 Hz - 1.75 mm 0.07"
Maximum number of
9 to 150 Hz 4.9 m/s2 16.1'/s2 - 4 2
connectable hubs*4
Shock resistance*3 Acceleration: 150 m/s2 492.1'/s2, application time: 11 ms, three times in each of the X, Y, and Z directions
*1 The 10 Mbps/100 Mbps MDI/MDI-X automatic switching function is supported.
Internal current *2 STP: Shielded twisted-pair cable, UTP: Unshielded twisted-pair cable
120 mA or less
consumption*4 *3 The maximum cable length refers to the distance between the KV-EP02 and Ethernet switch.
Weight Approx. 130 g *4 The number of connectable hubs is unlimited when an Ethernet switch is used.
*1 The range guaranteed as a system.
*2 The temperature below the unit center (30 mm 1.18") inside a control panel.
Software
*3 When mounted on a DIN rail
*4 The maximum current consumption when expansion units are included is 1.8 A.
Operating environment
Item name/category KV STUDIO
OS Windows® 10/8 (including 8.1)/7(SP1 or higher)
Specifications
Hard disk free space 3200 MB or more
35
1.07"
DIMENSIONS 90
3.54"
35.9
1.41"
80.4 3.17"
KV-NC32T 43.6 1.72" 3.8 0.15"
KV-EP02 96.5 3.80"
(125) (4.92")
85 3.35"
85 3.35" (20.3) (0.80")
16.6
0.65"
27.3 27.3 27.3
1.07"1.07" 1.07"
12.9
0.51"
90 90 35.935.9 90 35.9
3.54"3.54" 1.41"1.41" 3.54" (37.6) 1.41"
(1.48")
80.480.4
3.17"3.17" 14.6 0.57"
3.8
1.72"1.72"3.8 0.15"
43.6 43.6 3.8 0.15" 96.596.5
3.80"3.80" 5.2 7.8 0.31" 0.15" 24.4 0.96"
3.17" (0.81") (20.7)
(125)(125)
(4.92")
(4.92") 0.20" 80.4
26.7
16.616.6 (135.4) (5.33")
1.05"
0.65"0.65"
12.912.9
0.51"0.51"
Expansion unit (European terminal block/MIL connector type)
80.4 80.4
3.17"3.17" 3.8 0.15"
3.8 0.15" 80.4 80.4
3.17"3.17" 3.8 80.4 3.17"
5.6 5.6 3.8 0.15"
22.2 22.2 3.8 0.15" 5.6 5.622.2 22.2
90.2 90.2
3.55"3.55" 97 3.82"
97 3.82" 0.15"
0.22"0.22"
0.87"0.87" 0.22"0.22"
0.87"0.87" 96.5 3.80"
5.6 22.2 (130) (5.12")
0.22" 0.87"
KV-NC32EX/ET(P) KV-NC32EXT
KV-NC16EXT
27.3 27.3
1.07" 1.07"
90 35.9 90 35.9
3.54" 1.41" 3.54" 1.41"
36
Unit: mm inch
Base unit
KV-N14AR/AT(P)/DR/DT(P) KV-N40AR/AT(P)/DR/DT(P)
KV-N24AR/AT(P)/DR/DT(P)
82 3.23" 122 4.80"
2-ø4.5 ø0.18" 2-ø4.5 ø0.18"
27.3 27.3
1.07" 1.07"
90 82 90 82 35.9
35.9
3.54" 3.23" 3.54" 3.23" 1.41"
1.41"
17 17
0.67" 0.67"
KV Concept
Connection conversion unit
KV-N60AR/AT(P) KV-N1
167 6.57"
2-ø4.5 ø0.18"
27.3 27.3
1.07" 1.07"
Lineup
90 82 35.9 90 35.9
3.54" 3.23" 1.41" 3.54" 1.41"
3.8
0.15" 44 (87) 44
83.7 3.30" 22.2
1.73" (3.43") 1.73" 3.8 0.15" 80.4 3.17"
17.2 0.87"
175 6.89"
0.68"
KV-NC1
11 3.6 0.14"
Hardware
0.43"
17 27.3
0.67" 1.07"
90 35.9
3.54" 1.41"
5.6 22.2
Software
0.87" 3.8 0.15" 80.4 3.17"
Expansion unit
37 57 2.24" 47 1.85"
1.46"
2-ø4.5 ø0.18" 2-ø4.5 ø0.18" 2-ø4.5 ø0.18"
Specifications
27.3 27.3 27.3
1.07" 1.07" 1.07"
90 82 90 82 35.9 90 82 35.9
35.9
3.54" 3.23" 3.54" 3.23" 1.41" 3.54" 3.23" 1.41"
1.41"
2-ø4.6 ø0.18"
(142) (5.59")
C A D D ATA D O W N L O A D www.keyence.com/CADG
37
< Navigator >
* To use the samples and manuals, select “Help (H)” > “Navigator (reference programs and technical information) (D)” in KV STUDIO.
38
LIST OF COMPONENTS
KV Concept
DL-EP1 D-bus supported
Network
NE-Q05 24 VDC, QoS supported
EtherNet/IPTM supported, 5 ports
NE-Q05P 24 VDC, QoS supported, PoE function
KV-M16G 16 GB
SD memory card KV-M4G 4 GB
KV-M1G 1 GB
20-pin MIL connector OP-22185 For KV-NC16Ex, standard contact included
OP-23139 For KV-NC32T/KV-NC32Ex/KV-NCxxEXT, standard contact included, vertical
34-pin MIL connector
Option OP-42224 For KV-NC32T/KV-NC32Ex/KV-NCxxEXT, standard contact included, slanted
Contacts OP-22186 For standard AWG22-24, 200 pieces
Thin-wire contacts OP-30594 For standard AWG26-28, 200 pieces
Special crimping tool for MIL connectors OP-21734
Lineup
USB cable OP-35331 Cable length 3 m 9.8'
External USB port adapter KV-S2 Cable length 1 m 3.3'
Hardware
KV-N14ATP Input 8 points/output 6 points, transistor (source) output, program capacity 8k steps
KV-N14DR Input 8 points/output 6 points, relay output, program capacity 8k steps
14-point DC power supply type KV-N14DT Input 8 points/output 6 points, transistor (sink) output, program capacity 8k steps
KV-N14DTP Input 8 points/output 6 points, transistor (source) output, program capacity 8k steps
KV-N24AR Input 14 points/output 10 points, relay output, program capacity 8k steps
24-point AC power supply type KV-N24AT Input 14 points/output 10 points, transistor (sink) output, program capacity 8k steps
KV-N24ATP Input 14 points/output 10 points, transistor (source) output, program capacity 8k steps
KV-N24DR Input 14 points/output 10 points, relay output, program capacity 8k steps
Base unit 24-point DC power supply type KV-N24DT Input 14 points/output 10 points, transistor (sink) output, program capacity 8k steps
KV-N24DTP Input 14 points/output 10 points, transistor (source) output, program capacity 8k steps
Software
KV-N40AR Input 24 points/output 16 points, relay output, program capacity 16k steps
40-point AC power supply type KV-N40AT Input 24 points/output 16 points, transistor (sink) output, program capacity 16k steps
KV-N40ATP Input 24 points/output 16 points, transistor (source) output, program capacity 16k steps
KV-N40DR Input 24 points/output 16 points, relay output, program capacity 16k steps
40-point DC power supply type KV-N40DT Input 24 points/output 16 points, transistor (sink) output, program capacity 16k steps
KV-N40DTP Input 24 points/output 16 points, transistor (source) output, program capacity 16k steps
KV-N60AR Input 36 points/output 24 points, relay output, program capacity 16k steps
60-point AC power supply type KV-N60AT Input 36 points/output 24 points, transistor (sink) output, program capacity 16k steps
KV-N60ATP Input 36 points/output 24 points, transistor (source) output, program capacity 16k steps
Specifications
KV-N8EX 8 points, 5/24 VDC switchable, screw terminal block
Input
KV-N16EX 16 points, 5/24 VDC switchable, screw terminal block
KV-N8ER 8 points, relay output, screw terminal block
KV-N8ET 8 points, transistor (sink) output, screw terminal block
KV-N8ETP 8 points, transistor (source) output, screw terminal block
Output
KV-N16ER 16 points, relay output, screw terminal block
Expansion unit
KV-N16ET 16 points, transistor (sink) output, screw terminal block
KV-N16ETP 16 points, transistor (source) output, screw terminal block
KV-N8EXR Input 8 points/output 8 points, relay output, screw terminal block
Input/output
KV-N8EXT Input 8 points/output 8 points, transistor (sink) output, screw terminal block
A/D conversion, D/A conversion KV-N3AM Voltage/current input 2 channels + Voltage/current output 1 channel
Connection conversion unit KV-N1 For connecting connector type expansion units
KV-N10L 1 port (RS-232C × 1 channel)
Extension cassette Serial communication
KV-N11L 1 port (RS-422A/RS-485 (4-wire)/RS-485 (2-wire) × 1 channel), European terminal block
Extension cable OP-87581 Cable length 1 m 3.3', width 2 cm 0.79"
Option
USB cable OP-35331 Cable length 3 m 9.8'
Software
Classification Item name Model Functions/Specifications
Programming support
KV STUDIO Ver. 11 (US version) KV-H1A-DL Download version, Windows® 10/8/7-compatible, site license*
software
* Through user registration, the software can be used by multiple persons associated with the office (including factories, business offices, and sales offices) that purchased the software.
• Microsoft, Windows, Excel and PowerPoint are either registered trademarks or trademarks of Microsoft Corporation in the United States and/or other countries
39
Related Products
Programmable logic controller
CALL T O C O N TA C T Y O U R L O C A L O F F I C E
TOLL
FREE
1-888-KEYENCE
1 - 8 8 8 - 5 3 9 - 3 6 2 3
www.keyence.com SAFETY INFORMATION
Please read the instruction manual carefully in
order to safely operate any KEYENCE product.