Professional Documents
Culture Documents
Shakya Rabin Thesis 2018
Shakya Rabin Thesis 2018
By
Rabin Shakya
May 2018
The graduate project of Rabin Shakya is approved:
ii
Table of Contents
Signature Page ii
List of Figure iv
Tables v
Abbreviation vi
Abstract vii
Chapter 1 Introduction 1
Chapter 2 Theory 2
2.1 Power system network 2
2.2 Load flow analysis 2
2.3 Faults analysis in power system 3
2.4 Power system protection 4
2.4.1 Current transformer 7
2.4.2 Over current relay 8
2.4.3 Circuit breaker 10
2.4.4 Line protection with OCR and relay coordination 11
2.5 Nonlinear loads and harmonics 13
2.6 Effect of harmonics in different component in power system 14
2.7 Effect of harmonics on power system protection 15
2.8 Filters 16
2.8.1 Single Tuned Filter 16
Chapter 3 Simulation and Results 17
3.1 IEEE 9 bus test system 17
3.2 Components of IEEE 9 bus in ETAP 17
3.2.1 Generators 17
3.2.2 Buses 19
3.2.3 Transformer 19
3.2.4 Transmission lines 19
3.2.5 Current transformer 19
3.2.6 Circuit breaker 20
3.2.7 Relays 20
3.2.8 Static load 22
3.3 Load flow study in ETAP 23
3.4 Short circuit study in ETAP 25
3.5 Relay coordination study in ETAP 27
3.6 Harmonic study in ETAP 29
3.7 Effect of harmonic on relay mis-coordination in ETAP 30
3.8 Harmonic filter and relay coordination in ETAP 30
3.9 Design of single tuned filter and comparasion with ETAP 33
Conclusion 35
Reference 36
iii
List of Figures
Figure 1 Zone of Protection 5
Figure 2 Basic Diagram of CT 7
Figure 3 Time-current characteristic of different relay 9
Figure 4 Basic Action of CB 10
Figure 5 Operating time of OCR with inverse time characteristics 12
Figure 6 Adjusting relay in a simple loop 12
Figure 7 Voltage and current waveform of a non-linear load 13
Figure 8 IEEE 9 bus system 17
Figure 9 Synchronous generator 1 rating in ETAP 18
Figure 10 Circuit breaker 2 rating in ETAP 20
Figure 11 Overcurrent Relay 19 input rating in ETAP 21
Figure 12 Overcurrent Relay 19 output rating in ETAP 22
Figure 13 Static load C ETAP rating 23
Figure 14 Single line diagram of IEEE 9 bus system in ETAP 24
Figure 15 Load flow study in ETAP 24
Figure 16 Short circuit analysis in ETAP with fault in bus 5 26
Figure 17 Short Circuit Analysis report in ETAP with fault in bus 5 26
Figure 18 Sequence of operation with fault at line 1 28
Figure 19 Star Time curve characteristics at line 1 protection 28
Figure 20 Harmonic Spectrum at line 1 29
Figure 21 Current Waveform at line 1 29
Figure 22 Sequence of operation during fault at line 1 with harmonic 30
Figure 23 Harmonic Filter 1 rating in ETAP 31
Figure 24 Harmonic Spectrum at line 1 with harmonic filter 32
Figure 25 Current Waveform at line 1 with harmonic filter 32
Figure 26 Sequence of operation during fault at line 1 with harmonic filter 33
iv
List of Tables
Table 1 Data of Synchronous generator in IEEE bus 18
Table 2 Transformer rating in IEEE 9 bus 19
Table 3 CT rating 19
Table 4 Load flow bus results 25
Table 5 Load flow branch results 25
Table 6 Load flow load results 25
Table 7 Load flow source results 25
Table 8 Operating time of over current relays 25
Table 9 Comparison of filter design calculated and ETAP 34
v
Abbreviations
CT Current Transformer
PT Potential Transformer
OCR Over Current Relay
V Voltage
δ Power angle
P Real power
Q Reactive power
Φ Phase
CB Circuit Breaker
ac Alternating current
emf Electromotive force
VA Volt-Ampere
kV Kilo-Volt
MW Mega-Watt
Mvar Mega-Var
pf Power factor
MVA Mega-Voltampere
A Ampere
Qc Reactive power installed for filter
Xc Capacitive reactance
C Capacitance
f Frequency
XL Inductive reactance
hn Harmonic order
L Inductance
Xn Characteristics reactance
R Resistance
Q Quality factor
THD Total harmonic distortion
IEEE Institute of Electrical and Electronics Engineers
WSCC Western System Coordinating Council
vi
Abstract
By
Rabin Shakya
This paper investigates the effect of harmonics in the performance of over current relay in
a power system. The simulation is carried in ETAP software which has an IEEE 9 bus
system containing nonlinear loads. The load flow analysis, short circuit analysis,
sequence of operation of relays and harmonic analysis and filter design was carried out in
ETAP. ETAP because of its graphical interface and speed of operation and generation of
reports is preferred for simulation study. The paper includes load flow analysis at every
branch, which provides voltage, active power flow, and reactive power flow and power
angle. The paper also includes the short circuit analysis and the protective device
sequence of operation in the system. The current waveform and the harmonic spectrum
are also analyzed for nonlinear loads without harmonic and with harmonics and harmonic
filter. The calculation was done using formula and cross verified with the calculation
received from ETAP.
vii
Chapter 1: Introduction
An electric network consists of large number of generators, transmission and distribution
systems which are interconnected, thus protecting it is a vital part of any power system.
Faults can happen in any portion of the power system. Protective relays and circuit
breaker protect the healthy part of the power system by disconnecting the faulted or
abnormal part form the system. The protective system must be reliable, selective,
minimizes fault duration, simple and economic. A proper coordination is required to
disconnect the faulted part of the system. Relay coordination is done, such that during
fault these devices will only isolate the faulty section of the power system network.
Use of renewable energy, variable frequency drive, rectifiers, and inverters has led to
increase in the use of a large number of power electronics components which as a result
have led to mis-operation of transformers, capacitors, machines and power system as a
whole. The power system is greatly affected if the total harmonics distortion is greater
than 20%. Current transformers are used in power system to measure alternating current
flowing through the system. These transformers reduce the large current flowing in the
system to a value that can be easily handled by the protective relays. Over Current Relay
gets the signal required to operate through CT. These relay can malfunction if the CT gets
saturated during the fault condition which can affect the OCR operation. This can be
avoided by the proper selection of CT. But these current transformers may get saturated
due to presence of harmonics and can distort the waveform of current resulting in
malfunction of OCRs [1]. Also the other cause if harmonics is it deteriorates the power
factor of the power system. Current distortions are able to produce voltage distortion in
power system and when the harmonic current flow in the power system network with
impedance additional harmonic distortion occurs. Also, harmonic lowers the power factor
of the system thus more current flows in the system which results in relay mis-
coordination.
Power system are designed with fundamental frequency and thus if the system contains
harmonics due to non-linear loads the system malfunctions. Due to harmonic the skin
effect is more pronounced and thus increases the resistance and also cause the abnormal
neutral ground current [12]. Also, the harmonics can damage the electrical components or
record a false measurement. Higher harmonic distortion in the power network lowers the
power factor of the system thus the relays react to this and trips unconditionally.
There are many ways to reduce the harmonics content in the power system but
completely removing it is difficult and expensive. The harmonic content may be reduced
by using 200% neutral conductor or a separate neutral conductor or using K-factor
transformer or phase shifting transformer or harmonic filter. In our study we use
harmonics filters to reduce the harmonic content of our system. Filters also improve the
power factor of the system. Passive filters were used because of it is affordable and
simple to use. Recently, active filters are used because they are more flexible and are able
to continuously compensate harmonics regardless of the change in the systems loading.
1
Chapter 2: Theory
2
2.2 Load flow analysis
Load flow analysis is done to get the voltage magnitude |V|, real power P, reactive power
Q and phase angle δ flowing in the line. During the normal operation the load flow
analysis is carried out or it is done in normal steady state. To find the best operating
condition of an existing system load flow is carried out. It is also used for planning and
future development of power system [3]. Numerical analysis of electrical system can be
described as load flow analysis. There are four quantities at each bus which may be
known or unknown. They are voltage magnitude, phase angle, real power and reactive
power. These quantities depend on the type of bus they are and described in brief below.
a. Load Bus: Load bus is the load associated with the power system or in other
words it is the non-generator connected bus. The real power P and reactive power
Q are known in load bus and the unknown quantities are phase angle δ and
voltage magnitude |V|. It is also called as PQ bus.
b. Voltage Controlled Bus: It is a bus that is connected with the generator. In this
bus the magnitude of voltage is fixed and the real power generation is governed
by the prime mover. Thus the quantity known at this bus is voltage magnitude |V|
and real power P. The unknown quantities are phase angle δ and reactive power
Q. It is also called as generator bus or PV bus.
c. Slack Bus: This bus is also known as reference bus or swing bus. It serves as the
reference for all the other bus. The quantities specified are voltage magnitude |V|
and power angle δ. In slack bus the voltage magnitude is considered to be 1 p.u
and power angle to be 0°. The undetermined quantity is the active power P and
reactive power Q.
After we know the type of bus a set of nonlinear equation can be obtain. This requires an
iterative process to solve. There are various algorithm used to solve these nonlinear
equation. Some of which are Gauss Seidal method, Newton Raphson method and Fast
Decoupled Load flow method.
3
impedance [2]. This heavy fault current may damage equipment, disturb stability etc.
This fault current must be disconnected with the help circuit breaker and protective relays
as soon as possible i.e. within few cycles. The fault current the circuit breaker has to
interrupt and the time when the fault occurs determines the selection of circuit breaker. In
fault analysis fault is calculated at different location of the system and this data is used to
set the capacity of the circuit breaker and setting the relay. The faults can be classified as
a. Balanced fault: A three phase fault is called the balanced fault. It is also termed as
symmetrical fault because all the three phase are short-circuited with or without
ground. A balanced fault is the maximum fault that occurs in a power system and
is used to determine the system fault level.
b. Unbalanced fault: Unbalanced fault are any other fault that does include balanced
fault. The unbalanced fault can be classified as follows:
i. Single phase to ground fault: If a single phase conductor touches a ground then
it is termed as single phase to ground fault or single line to ground fault. It is
the most common type of fault. It occurs due to failure of insulation between
conductor and earth or due to broken phase conductor falling in the ground.
ii. Two phase to ground fault: If any two phase of a three phase system touches a
ground then it is termed as two phase to ground fault or double line to ground
fault.
iii. Phase to phase fault: If two phase touches each other it is termed as phase to
phase fault or line to line fault.
iv. Open circuited phases: If a phase becomes open circuited by breakage of the
conductor then is termed as open circuited phase. This type of fault occurs
when conductor breaks. Unbalanced current flow in system.
v. Winding faults: If faults occurs in transformer or rotating machine it is termed
as winding fault.
b. Primary and backup protection: Power system protection is divided into different
zones for its protection. A primary relay is the first line of defense [4]. If a fault
occurs in a particular zone the relay of that zone isolates the faulty section this is
called as primary protection. If this relay fails then there is a backup relay
protection scheme that isolates the fault. The protective scheme can fail due to
failure of relays, circuit breakers, breaker trip mechanism, current transformer, dc
supply etc. Backup relay must operate with a time delay so that the primary relay
has sufficient time to operate or react to the fault but the delay should not be too
long such that the fault deteriorates the power system.
5
i. Selectivity: Selectivity is the quality of a relay to be able to maintain
continuous supply by disconnecting minimum section of power system to
isolate the fault. Also it should distinguish if the fault lies inside its section of
protection or outside its section and distinguish between fault and transient
condition.
ii. Reliability: Reliability is the ability of the power system protection to operate
accurately when the fault occurs in its zone of protection. Any elements used in
protection like CT, PT, CB, protective relay, battery etc. may fail. To achieve
high degree of reliability regular maintenance and testing of this equipment
should be carried out. Also, proper attention should be given to design and
installation of this equipment as well. Protective systems reliability should be
greater than 95% [4].
iii. Sensitivity: If the current’s magnitude is greater than the preset value the
protective relay operates. This preset value is called pickup current. A
protective relay should be sensitive enough to operate when the current just
exceeds this pick up value.
iv. Stability: A protection system should remain stable within a set of defined fault
current that is flowing through its protective zone due to external fault. If the
protective device that is in its protective zone does not operate then after a
preset delay the protective relay that is affected by this fault current should
operate to disconnect the fault.
v. Speed of operation: To avoid any damage to the equipment in power system
the speed of operation of protective device should be as quick as possible so it
can clear or isolate the fault. From the stability point of view, to avoid losing
synchronism the operating time of protective relay must not be greater that the
critical clearing time [4]. Protective device should generally operate in a single
cycle of current but for distribution system it may operate few cycles of fault
current.
6
operation, less maintenance, longer lifespan and absence of mechanical
inertia.
III. Microprocessor based relays: Microprocessor based relay uses
microprocessor to analyze voltage, current and other electrical quantities.
These relay not only gives command signal to trip coil of circuit breaker but
can also record the event.
A current transformer (CT) is a transformer that measures the current of high magnitude
in an ac circuit which produces a secondary current which is proportional to primary
current flowing through the circuit [7]. CT is utilized to bring down the large current
flowing in power system to a lower value that is appropriate for relay operation. A CT
mostly has only one turn or few numbers of primary turns. CT also isolates the relay
circuit from high primary circuit.
7
The CT used in power system protection is different than those used for measurement.
The CT needs to give a correct ratio at normal rated current as well as when a large fault
occurs which are several times higher than normal rated current. In other words, CT of
power system protection is designed much below the saturation point or knee point to
avoid saturation. The core material used for CT is generally cold rolled silicon steel as it
has high permeability, high saturation level, small exciting current and low error [4].
Generally CT have 5A as its secondary rating whereas other rating like 1A also exists.
The accuracy of CT can be described as the difference of its ratio from its true ratio. This
ratio error in CT depends on its exciting current. When the primary current increases, CT
tries to produce the corresponding secondary current and this generates a secondary emf,
core flux density and exciting current [4]. A stage comes when the secondary current
hardly increase because any increase in the primary current is absorbed in increasing the
exciting current. This stage is called CT saturation. So, in power system protection the
CT should not saturate.
The load connected across the secondary of the CT is called as CT burden or it can be
defined as the power that is required to operate the relay. The CT burden is expressed in
volt-ampere (VA) or can be defined in terms of impedance calculated at rated secondary
current at specific pf. Connecting leads and resistance at secondary of CT results in total
CT burden for relays. The leads burden depends on the resistance of the secondary of CT
and current flowing in the secondary of CT.
Over current relay (OCR) are those relay that functions or picks up when it’s current
exceed a predetermined value. OCR protects the power system against large current
caused due to short circuit, ground fault, phase fault or winding fault. The OCR relay can
be used to different section of power system like generators, transmission lines,
transformer etc. OCR operates when the current is above a preset value and is called as
pickup current. There is more than one OCR at different section of feeder for feeder
protection by over current relay. The relay needs to coordinate with each other. The relay
that is closest to the fault should operate first followed by the secondary relay that is
closer. This is done by using time or current or combination both time and current
characteristics of OCR. A time delay is provided in the OCR so that it does not operate
when there is a surge current, starting current etc. Depending on the time-current
characteristics the OCR may be classified as follows.
a. Definite-time over current relay: These relay operate at a fixed time when the
current passes beyond its pickup value. The operating time of this relay is
constant regardless to the size of fault current. The time-current characteristic is
shown in figure 3 for this relay.
8
b. Instantaneous over current relay: These relay operate immediately when the
current surpasses its pickup value. There is no any deliberate time delay applied.
c. Inverse-time over current relay: These relay operate when the current passes
beyond its pickup value. The operating time decreases as the current increases.
We can see inverse-time characteristic of this type of relay in figure 3.
d. Inverse definite minimum time over current relay: These relay works as inverse
time relay at lesser fault current and as definite time relay at higher of fault
current.
e. Very inverse-time over current relay: These relay operate more inversely than
inverse time OCR or inverse definite minimum time OCR. As the length from the
power source rises the fault current lessens so these relay are used where there is
significant reduction of fault [4]. We can see the time-current characteristic of this
type of relay in Figure 3.
f. Extremely inverse-time over current relay: These relay operate more inversely
than very inverse time OCR. These relay are suitable to protect machine from
overheating. The time-current characteristic is shown in figure 3 for this type of
relay.
g. Directional over current relay: On a non-radial power system these relay are used.
These relay operates in only a single direction of current flow.
In order for OCR to operate properly they should be selected properly and also they
should have the following characteristics
a. Voltages rating: For the OCR to function appropriately the OCR must be over or
at least equal to the circuit voltage.
9
b. Ampere rating: For the OCR to function appropriately the OCR should not be
greater than the current carrying capacity of conductor.
Over current relays are utilized as a part to detect the abnormal condition in the power
network and isolate the faulty section in the power system. Its operation minimizes the
damage and danger. These are also able to discriminate and isolate the faulty section. The
relay should be dependable and reliable so that the stability of the power system network
ensured.
The function of circuit breaker (CB) is to cut off the faulty part of the system. So a CB
makes or breaks a circuit either automatically or manually under various conditions [6].
Earlier fuse was used but nowadays it has been replaced by CB because fuse has to be
replaced every time when it operates. In a protection system the relay senses fault
condition and CB operates thus removing the faulty section. The circuit breaker should
carry the normal load current without excessive heat. The CB should isolate the faulty
section as quickly as possible.
The basic diagram of CB is given above. It consists of two contacts a fixed and a moving
contact. The handle is also there which can be operated manually or automatically, for the
automatic operation an automatic mechanism with trip coil is there. The trip coil is
energized by secondary of CT. Under normal condition the emf generated by the CT is
not sufficient to energize the trip coil for its operation and thus the contact remains
closed. When there is abnormal or fault condition the emf generated by the CT will be
enough to energize the trip coil and thus the contact gets open thereby disconnecting the
fault. During this action arc is produced between the contacts and thus arc should also be
extinguished as quickly as possible so that the heat produced will lie within the allowable
limit. The time required between energization of the trip coil to contact separation is
called opening current level and depends on fault current [6]. The time required for arc
10
extinction is called arcing time. This time depends on fault current as well as voltage for
the maintenance of arc [6]. The important characteristics or rating of the CB include
a. Rated short circuit breaking capacity: The maximum rms short circuit current that
a CB is capable of breaking [6].
b. Rated short circuit making capacity: It can be described as the maximum value of
1st current loop of short circuit current which CB is able to make at its rated
voltage [6].
c. Rated operating sequence of CB: It is the sequence of operation of which a CB
performs.
d. Rated short time current: It can be described as the maximum rms short circuit
current that the CB can safely handle for a certain fixed time without damage.
Overcurrent relay, distance relay etc. are used to protect transmission or distribution
lines. Overcurrent relaying is simplest and cheapest system for line protection but it is
difficult to apply. Overcurrent relaying is quick to readjust or replace if power system
requirement changes. Commonly, OCR is used in phase and ground fault protection. In
transmission line we generally use OCR for ground fault protection whereas distance
relays are implemented for phase fault [7]. OCR is also used in power transformer
protection. OCR is mainly used in distribution system protection as it is simple,
inexpensive and no ac voltage source is required. The fault current in power system
mostly depends on position of fault and is generally unaltered by change in generation so
the inverse time characteristic of relay can be used for protection of lines of power
system.
To set the OCR the pickup current of the relay is chosen first such that it operates for all
short circuit currents in its line and also provides the backup protection for short circuit
protection to the immediate adjoining system under certain circumstance. For phase fault,
fault current is supposed to be less than with fault involving ground. The sensitivity of
phase relay need not be too sensitive such that it picks up the maximum load current that
flows in the power line. To use the inverse time characteristics of relay the pickup current
that flows in the line should be large enough and also be low enough such that relay
operates reliably under this least fault condition [7]. To be confident that the relay in the
fault line operates the pickup of this relay in this zone should be slightly higher than that
of other relays.
After setting the pickup current the time delay of OCR is adjusted to obtain selectivity
with the relays in the immediate neighboring elements. This is done for the maximum
fault current that will flow in the line. A three phase fault is assumed to adjust phase relay
11
and a single Φ to ground fault is assumed to adjust ground relay. If we adjust the
selectivity of relay using maximum fault current it is certain that it is assumed for lower
current too.
After setting the pickup current and selectivity we must find the difference of time
between operating time of two relays. Similarly, it done for other relays in the selectivity
order.
The time v/s distance curve is shown in figure 5 which follows the relay operation
sequence. The time S is “selective time interval” and can be defined as breaker over
travel plus the safety factor. A fault location is assumed and a vertical line is drawn. This
vertical line intersects the operating time curve of various relays. The length of this line is
the time required for the relay to operate if there is a short circuit current that flows in the
system [7]. Relay are adjusted by farthest relay from power source first and then work
backward to the relay near to the power source in any radial power system. It can be seen
from figure 5 that relay 1 is adjusted first and then relay 2, relay 3 and at last relay 4.
The figure 5 only represents an example of relay coordination in radial system power
system. The relay that was far from the generation was calibrated first and then worked
backward towards the generator. A similar methodology is followed in loop system as
well.
If there is more than one generator that is located at various points in the loop then
adjusting the OCR will be difficult because the problem will be where to start our
coordination. And if the circuit of one loop forms a part of other loop then it will be more
troublesome. The trial and error will be the only method to carry on with such power
system.
If the impedance of the load changes with the applied voltage the load may be assumed as
non-linear load. Current drawn by non-linear load is non-linear too because it has
changing impedance i.e. even if the non-linear load are connected to a sinusoidal source
like utility or generator set the current drawn will be non-sinusoidal [8]. For resistive,
inductive and or capacitive load the current is also sinusoidal. The example of non-linear
loads can be computers, variable frequency drive, SMPS etc. The figure below shows the
waveform of voltage and current of non-linear loads.
Due to this the original sinusoidal wave from the source becomes distorted. This
introduction of distortion can be called as harmonic distortion. So a harmonics can be
interpreted as deviation from the fundamental sine wave frequency. It can be
demonstrated as additional sine waves of frequencies that are a multiple of original
frequency [8]. So for a fundamental frequency of 60Hz, the 2nd harmonic is 120Hz and
13
3rd harmonics is 180Hz and so on. Harmonics is a problem because lots of non-linear
loads are being used now.
A non-linear load draws non-sinusoidal current which induce the harmonics in the power
system. The different effect of harmonics in different element of power system is
discussed below.
14
2.7 Effect of harmonics on power system protection
The harmonics distort the fundamental sinusoidal frequency and thus due to this
harmonic distortion it degrade the operating characteristics of CT and protective relay. If
the harmonic distortion is less than 20% in the power system then most types of relay are
not significantly effected but if the harmonics in the power system gets greater than 20%
then the relay malfunction and the CT tends to saturate faster, losses increases and giving
false reading.
Protection devices are generally developed in terms of fundamental voltage or current or
both and any harmonics present in the system are ignored [9]. This is the case for over
current relay. The presence of harmonic current in fault situation causes considerable
measurement errors relative to fundamental based setting. Maloperation of relays is
common when the fault current containing high harmonics flows through high resistance
ground. The presence of harmonics in secondary of CT will cause a big problem because
the CT tends to gets saturate quickly and due to this it is difficult to recover the
fundamental current waveform. If high secondary emf exists during steady state condition
the CT excitation causes odd harmonics distortion and during transient condition any
harmonics can be produced but with higher order of second and third harmonics. If the
faults are outside the main protection zone of the relay the relays may be insensitive for
backup protection. Correct choice of equipment is required to eliminate the harmonics.
Also different filtering technique can be used to recover the fundamental frequency from
the harmonic content in power system.
2.8 Filters
Due to high use of non-linear loads the harmonics level in the power system has
increased. Also due to the injection of renewable energy that uses semiconductor and
thyristors are injecting the harmonics to the system [10]. The non-linear loads induce
harmonics and draws reactive power due to which the system has low efficiency, high
losses, relay malfunction and low power factor. Also the due to harmonics
electromagnetic interference occurs in near communication system. So, filters are used to
lower the harmonics component and improve the power factor of the power system.
Filters are thus the device that eliminates the harmonic distortion. A harmonic filter is
build using resistors, capacitors and or inductors that deflect the harmonic to the ground.
The filters may be classified into 3 types:
a. Passive filters: The passive filters are used to reduce current harmonics and also
for to improve the pf by reactive power compensation. These are installed at the
load side since current harmonics are usually introduced by non-linear loads [10].
These filters introduce similar compensating currents and are tuned to every
harmonic order that is to be filtered and this is opposite in phase to cancel the
harmonics of the non-linear load. They are connected in parallel with the non-
linear load. The filters also improve the voltage profile because it improves the
power factor. Several parallel connections of filters can be made to get notable
reduction in harmonics order. There are many kind of passive filters based on the
configuration of capacitors inductors and resistors. These are single tuned filters,
by-pass filter, high-pass filter, 3rd order C type filters etc.
15
b. Active filters: The passive filter reduces the harmonics and improves the power
factor but they have a demerit of fixed compensation, large size and resonance.
So, a dynamic and adjustable filter is needed to filter the harmonic. These filters
consist of power electronic component. They are placed in parallel or series with
non-linear load. These filters injects opposite phase current that is reverse of
harmonics injected due to non-linear load thus the harmonics gets filtered.
c. Hybrid filters: The active filters are costly and thus not cost effective. So a hybrid
filters are used to get a practical cost effective solution. This is done by reducing
the rating of the active filter and adding passive filter to form a hybrid filter which
allows reduced cost. This filter offers advantage of both active and passive filter
and covers broad range of capacity and performance level.
𝐿 𝑋
𝐿 = 2𝜋𝑓 (4)
Where ℎ𝑛 is the harmonic order that we want to eliminate.
The resistance required is calculated by specifying the quality factor (Q) which lies in the
range of 30 to 50 and 𝑋𝑛 is the characteristics reactance.
𝑋𝑛 = √𝑋𝑐 𝑋𝐿 (5)
𝑋𝑛
𝑅= (6)
𝑄
16
Chapter 3: Simulation and Results
The simulation was carried on ETAP using IEEE 9 bus system to get the miscordination
of the relay due to the presence of harmonic in electrical network. The IEEE 9 bus system
is also called as WSCC 9 bus system as it is a basic comprasion of Western System
Coordinating Council. ETAP software is utilized as a part in examination, analysis,
simulation, control, optimization and automation of electrical power system network. The
ETAP software is used as it has capability of complex power system computation with
flexible and user friendly interface. Along with the anaysis of our network the design of
harmonic filter was calculated using formula and also using the ETAP software and the
results were compared.
17
power limit of 100 Mvar to -50 Mvar. Generator 3 is also connected to a voltage control
bus and this has a rating of 108.8 MW and 13.8kV operating at 102.5% of rated voltage.
It has a reactive power limit of 100 Mvar to -50 Mvar. The table below gives the data of
the all 3 generators.
18
3.2.2 Buses
The IEEE 9 bus system has a total of 9 bus which has four different voltage levels. Bus 1,
bus 2 and bus 3 has voltage of 16.5kV, 18kV and 13.8kV respectively. All the other bus 4
through 9 has a rating of 230kV.
3.2.3 Transformer
The IEEE 9 bus system consists of 3 100 MVA transformer connected between bus 1 and
bus 4, bus 2 and bus 7, bus 3 and bus 9 respectively. The table below gives the rating of
the transformer used in the simulation.
19
CT 21 30000 5
CT 22 35000 5
Table 3: CT rating
3.2.7 Relays
The relays are configured with the CB and CT. ETAP has a library of different relay
manufactures and a suitable relay was selected through this library. In this simulation
20
there are 21 relays of which 12 are directional and rest of the others are non-directional.
The relay used in this study is ABB manufactured and model 51I with 50 which is
applied for phase and ground protection and has a function of overcurrent. For the
operation of the CB respective CT is configured as an input to the relay. This can be seen
in the figure below.
21
Figure 12: Overcurrent Relay 19 output rating in ETAP
22
Figure 13: Static load C ETAP rating
23
Figure 14: Single line diagram of IEEE 9 bus system in ETAP
24
ID Nominal kV Voltage (%) MW loading
Bus 1 16.5 104 71.337
Bus 2 18 102.5 163
Bus 3 13.8 102.5 85
Bus 4 230 102.58 71.334
Bus 5 230 99.57 124.761
Bus 6 230 101.27 89.939
Bus 7 230 102.57 162.984
Bus 8 230 101.59 99.975
Bus 9 230 103.23 84.996
Table 4: Load flow Bus results
25
generators and machine. After this data are provided the fault bus has to be specified in
order to get the fault current. Short circuit analyis report of fault at bus 5 can be seen in
the ETAP report in the figure 17 below.Similarly the fault can be achieved at different
fault at different bus.
Figure 17: Short Circuit Analysis report in ETAP with fault in bus 5
26
3.5 Relay coordination study in ETAP
Relay coordination study is used in power system to selectively isolate the faults. ETAP
Star-Protective device cordination program is used for this section of study. It has a Time
Current characteristics curve with graphical user interface, extensive device library
etc.With this study we can troubleshoot false trips, relay miscoordinaton etc. Also,
graphical adjustment can be done in this part of study with section of ETAP.
For this section of study we need to provide the settings of CTs and CBs and know the
fault current flowing in the line. Using these values relays characteristics is choosen and
is setup. After this the fault is applied to the line or bus and the relay operation is looked
at. If the relay operation is not coordinating then the TCC curve is adjusted to get the
relay coordination. Since, it has a loop system the relay in the loop has a directional
element. Below is the table of the operation of OCR along with its backup relay at fault at
different line.
27
Figure 18: Sequence of operation with fault at line 1
28
3.6 Harmonic study in ETAP
Non linear loads were included in this system which are the source of harmonic current in
this IEEE 9 bus system. Harmonics are the deviation of the current from its fundamental
frequency. The total harmonic in power system should be kept low as possible to have
good power factor, lower peak current and higher efficicncy. The frequency spectrum is a
medium of showing the harmonics comprised in a periodic signal and specifies the
amplitude of each harmonic order.
ETAP harmonic frequency scan module computes and plots the magnitudes and phase
angles of bus driving point impedance over a frequency range listed by the user.
Previsously the system has no harmonic and the current is sinusodial wave with no
distortion. On this study the current harmonic was inserted in the static load C from the
harmonic library. Then the harmonics spectrum and waveform was observed in the line 1
which can be seen in the figure below.
29
3.7 Effect of harmonic on relay mis-coordination in ETAP
In a power system network if the total harmonic distortion is high then the power factor
of the system is low due to which large load current flows in the system and due to this
the relay that were coordination sequencely with our system would malfuction there by
loosing the coordination. In this study if we apply the same fault in the same line 1 which
has a harmonic content would operate in different order than what is desired. The figure
below shows the miscoordination when the fault occurs in the system which has a
harmonic current.
30
diagram. Thus we need to suppress this harmonic in order to filter the harmonic from our
system. Two single tuned filter were used in bus 6 and bus 8 to reduce the total harmonic
distortion in our study. The figure below shows the parameter of single tuned filter in
ETAP reduction of total harmonic distortion.
31
Figure 24: Harmonic Spectrum at line 1 with harmonic filter
32
Figure 26: Sequence of operation during fault at line 1 with harmonic filter
A single tuned filter was designed using the formula 1 through 6. To start with the
calculation we need to select the bus on which we want to put our filter. In our case
choose bus 6 and bus 8. The load MVA and the power factor was found using the ETAP
software and the data are given in table 4 through 7. Then the harmonic analysis is
carried out in the ETAP software and then harmonic which contributes most to distort the
waveform is found.
In our test case the 5th and the 7th harmonic is contributing most to distort the wavefrom.
We used two filter at bus 6 bus 8 in our test case. The load MVA from load flow is found
to be 94.8 MVA and 105.9 MVA repectively. The power factor at these bus is 94.9% and
94.4% respectively. We want to increase the power factor to 99% at each bus. So, using
the formula discussed in chapter 2.8.1 the calculation is done below to decrease the 5th
order harmonic at bus6.
33
2302
𝑋𝑐 =
17056
𝑋𝑐 = 3.1016𝑋103 Ω per single phase
1
𝐶=
2𝜋𝑓𝑋𝑐
𝐶 = 0.855 μF per phase
𝑋𝑐
𝑋𝐿 = 2
ℎ𝑛
𝑋𝐿 = 124.06 Ω per single phase
𝑋𝐿
𝐿=
2𝜋𝑓
𝐿 = 0.3291 H
𝑋𝑛 = √𝑋𝑐 𝑋𝐿
𝑋𝑛 = 620.31
𝑋𝑛
𝑅=
𝑄
Calculated ETAP
Bus 6, 5 harmonic Bus 8, 7 harmonic Bus 6, 5th harmonic Bus 8, 7th harmonic
th th
There is a slight variation in the values of calculated and ETAP due to rounding off error
in hand calculation.
34
Conclusion
In this study IEEE 9 bus system was created and simulated using ETAP. The studied
system contained 9 bus, 6 lines, 3 generators, 3 loads, 3 transformer, CTs, CBs and
relays. The load flow analysis, short circuit study, star coordination of protection was
performed, harmonic analysis and harmonic filter design was performed using ETAP.
The simulation results shows how we can get a proper sequence of operation with ETAP
star coordination and also see the effect of harmonic on the sequence of operation when
the THD is high and design the filter to reduce this harmonic distortion to get a proper
relay coordination. Also, hand calculation of single tuned filter design was done and
compared with ETAP calculation.
35
Reference
[1] Hilary Tin, A. Abu-Siada and M.S. Masoum, “Impact of Harmonics on the
Performance of Over Current Relays”, IEEE 2011
[2] H. Saadat, “Power System Analysis”, New York: McGraw-Hills Inc., 2002
[3] G. Stevenson, “Power System Analysis”, McGraw-Hills Inc, 1994
[4] Badri Ram, “Power System Protection and Switchgear”, Tata McGraw Hill, 2007
[5] J. Lewis Blackburn, “Protective Relaying Principles and Application”, CRC Press,
2014
[6] U. A. Bakshi and M.V. Bakshi,” Protection and Switchgear”, Technical Publication,
2007
[7] C. Russell Mason, “Line Protection with Overcurrent Relays”, Wiley, 1956
[8] Nikunj Shah, “DRV-WP drive in power system”, Siemens Industry Inc
[9] Jos Arrillaga and Neville R. Watson, “Power System Harmonics”, John Wiley &
Sons, 2003
[10] B. Singh, A. Chandra, K. Al-Haddad, “Power Quality Powers and Mitigation
Techniques”, John Wiley & Sons, 2015
[11] P. M. Anderson and A. A. Fouad, “Power System Control and Stability”, 2nd ed.
New York: IEEE Press, 2003.
[12] HOEVENAARS, T. How the Harmonic Mitigating Transformer Outperforms the K-
Rated Transformer. MIRUS International Inc.1999
[13] Young-Sik Cho and Hanju Cha, “Single-tuned Passive Harmonic Filter Design
Considering Variances of Tuning and Quality factor”, Journal of International Council on
Electrical Engineering, 2011
[14] Mohamed Awadalla, Mohamed Omer, Ahmed Mohamed, “Single-tuned Filter
Design for Harmonic Mitigation and Optimization with Capacitor Banks”, International
Conference on Computing, Networking, Electronics and Embedded Systems
Engineering, 2015.
[15] D.M. Soomro and M.M. Almelian, “Optimal Design of a Single Tuned Passive Filter
to Mitigate Harmonics in Power frequency”, APRN Journal of Engineering and Applied
Sciences, 2015
36