Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

Design Conditions Datasheet

Net Cooling Nominal Refrigerant


Unit Tag Qty Model No
Capacity (kW) Voltage Type
CH-2 2 YVFA0259-OL-50 800.0 380-415/3/50.0 R-134a

PIN:
YVFA0259CS X50AAVBXXX SAKGXXXX41 54XDFXXV17 3W1SXSG2BT XCXRNOXXXX XXXFX
....5...10 ....5...20 ....5...30 ....5...40 ....5...50 ....5...60 ....5...70 ....5...80 ....5...90

Evaporator Data Free Cooling Data Performance Data


EWT (°C) 18.50 Free Cooling Type Open Loop EER (kW/kW) 3.384
LWT (°C) 12.00 Fluid Concentration N/A IPLV.IP (kW/kW) 5.390
Design Flow Rate (L/s) 31.37 NPLV.IP (kW/kW) 6.280
Total Press. Drop (kPa) 66.5
Mechanical Mode Press.
Drop (kPa)
29.4 Condenser Data Physical Data
Ethylene
Fluid 20 Ambient Temp. Design (°C) 36.2 Rigging Wt. (kg) 9820
Glycol (%)
Fouling Factor (m²K/kW) 0.0176 Altitude (m) 490 Operating Wt. (kg) 10667
VSD Screw - Semi
Fluid Volume (L) 269.0 Compressor Type Refrigerant Charge (kg) 216
Hermetic
Min. Flow Rate (L/s) 18.93
Max. Flow Rate (L/s) 51.10

Electrical Data
Circuit 1 2 3 4
Compressor kW 118.5 98
Compressor RLA 210 176
Fan QTY/FLA (each) 8 / 3.7 6 / 3.7

Single Point
Min. Circuit Ampacity 495
Max. Fuse / CB Rating (A) 700
Unit Short Circuit Withstand (STD) 65 [kA]
Wires Per Phase 3
Wire Range (Lug Size) 3/0 - 400 kcmil
Operating Condition Electrical Data
Compressor kW 216.5
Total kW 236.4

Notes:

Certified in accordance with the AHRI Air-Cooled Water-Chilling Packages Certification


Program, which is based on AHRI Standard 550/590 (I-P) and AHRI Standard 551/591 (SI).
Certified units may be found in the AHRI Directory at www.ahridirectory.org.
Unit contains freeze protection fluids in the evaporator with a leaving chilled fluid temperature
above 32 DEG F [0 DEG C] and is certified when rated per the Standard with water. Auxiliary
components included in total KW - Oil heaters, Chiller controls. Auxiliary power is already
included in the compressor and fan power

Min DSD (Factory Purpose/Use only): 91 psig


Displacement Power Factor refers to compressor only. Unit Power Factor depends on fan
option selected. Calculated value is available by request.

* 100% Free Cooling Ambient Temperature is provided for comparison purposes only. For maximum efficiency, energy optimization controls may
utilize mechanical cooling below this temperature.
Minimum and maximum evaporator flow information are for full load ratings with Ethylene Glycol.
Evaporator Passes: 2, Condenser Type: T, Fan Type: C
Total Pressure Drop includes evaporator and free cooling heat exchangers and is to be used for pump sizing.
Mechanical mode pressure drop includes the evaporator and factory provided pipework inside the chiller frame.

ASHRAE Standard 90.1-2010 and ASHRAE Standard 90.1-2013 & 2016 Compliant.

IECC 2012 and IECC 2015/2018 Compliant.

MLP Effective Date:15/11/2021 O Data STC2


Generated on2022-01-05 E.21.4.27286.0-D.93.0007(REV. v8_29.idd) Datasheet Spec
Unit Folder: CH-2 Software Version: YW21.04a Page_1_of_2
Design Conditions Datasheet

Part Load Rating Data


Unit Efficiency
Load % Ambient (°C) Capacity (kW) Total kW
(kW/kW)
100 36.2 800.0 236.4 3.384
75 27.5 600.0 125.7 4.772
50 18.7 400.0 55.28 7.237
25 12.8 200.0 * 25.04 * 7.989 *

* Values are time-averaged and include the effect of compressor cycling

Sound Power Levels (In Accordance with AHRI 370)


Ambient 63 Hz 125 Hz 250 Hz 500 Hz 1 kHz 2 kHz 4 kHz 8 kHz
Load % LWA
(°C) (dB) (dB) (dB) (dB) (dB) (dB) (dB) (dB)
100 36.2 93 91 90 89 86 82 76 70 91
75 27.5 89 88 88 88 85 79 74 69 89
50 18.7 86 87 84 87 84 75 70 64 88
25 12.8 86 86 85 86 81 74 69 63 87

Note: Unit is equipped with Low Sound Kit (Level 1 Reduction) and Low Profile High Efficiency Fans with Variable Speed EC motor NOTE: SQ and
Additional Lead Time Required.
Measurement of sound pressure used to obtain the sound power data presented is based on AHRI-370.
Air-cooled chillers are rated in terms of sound power not sound pressure. Johnson Controls provides estimates of sound pressure, but this is not the
rating metric.
For an air-cooled chiller, sound pressure calculated from sound power varies depending on how the chiller is assumed to behave, i.e. the radiation
model. In other words, determining sound pressure from sound power requires making assumptions that result in different answers at a given
distance from the chiller. The environment also influences sound pressure in the field installation. Sound pressure estimation radiation models
pertaining to air-cooled chillers include the ‘traditional’ hemispherical model, parallelepiped model and equivalent hemispherical model.
Regarding sound power, Johnson Controls references tolerance limits based on ASHRAE guidelines. These are +/- 6dB in the 63Hz octave band,
+/- 4dB in all other octave bands and +/- 3dB for the overall dBA.
Tolerance limits are based on uncertainties associated with:
1. Measurement Test Procedure
2. Repeatability
3. Production / Manufacturing Variability
Standard deviation associated with air-cooled chiller sound data is a measure of spread i.e. it indicates the range of probability of sound levels.
Note that for operating conditions other than AHRI’s Standard Rating Condition, higher levels of uncertainty can be expected.
Lead times for factory performance testing depend on test laboratory availability. Please confirm with Johnson Controls Customer Service.

Performance at AHRI Conditions


Evaporator Data Condenser Data Performance Data
EWT (°C) 12.22 Ambient Temp. (°C) 35.0 EER (kW/kW) 3.079
LWT (°C) 6.67 Altitude (m) 0.000 IPLV.IP (kW/kW) 5.390
Net Cooling Capacity
Flow Rate (L/s) 34.35 800.0
(kW)
Pressure Drop (kPa) 32.2
Fluid Water
Fouling Factor (m²K/kW) 0.0176
Fluid Volume (L) 269.0

Note: Unit rated at design condition capacity.


Note: YVFA with open loop requires use of glycol for freeze protection. IPLV information is provided for comparison purposes only.

MLP Effective Date:15/11/2021 O Data STC2


Generated on2022-01-05 E.21.4.27286.0-D.93.0007(REV. v8_29.idd) Datasheet Spec
Unit Folder: CH-2 Software Version: YW21.04a Page_2_of_2

You might also like