Download as pdf or txt
Download as pdf or txt
You are on page 1of 6

3412 Generator Set 4BZ00001-UP(SEBP2785 - 34) - Documentation Page 1 of 6

Shutdown SIS

Previous Screen

Product:  GENERATOR SET 
Model:  3412C GENERATOR SET 4BZ 
Configuration: 3412 Generator Set 4BZ00001-UP 

Testing and Adjusting


SR4B Generator
Media Number -SENR5359-11 Publication Date -01/05/2009 Date Updated -11/05/2009

i02440023

Varistor - Test
SMCS - 4466-081

Table 1
TOOLS NEEDED
Part Number Tool Quantity
6V-7070 Digital Multimeter 1
243-3134 (1)
Tester Group 1
(1)
Or equivalent.

https://127.0.0.1/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisweb/sis... 2020-04-11
3412 Generator Set 4BZ00001-UP(SEBP2785 - 34) - Documentation Page 2 of 6

Illustration 1 g00610379

Varistor CR7

Varistor CR7 can be checked with a megohmmeter or equivalent meter. Use the megohmmeter in
order to measure the clamping voltage between the terminals.

Note: For testing rectifier blocks with integral varistor CR7, refer to Testing and Adjusting,
"Rotating Rectifier - Test".

Personal injury or death can result from improper troubleshooting and


repair procedures.

The following troubleshooting and repair procedures should only be


performed by qualified personnel familiar with this equipment.

https://127.0.0.1/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisweb/sis... 2020-04-11
3412 Generator Set 4BZ00001-UP(SEBP2785 - 34) - Documentation Page 3 of 6

Personal injury or death can result from high voltage.

When power generation equipment must be in operation to make tests


and/or adjustments, high voltage and current are present.

Improper test equipment can fail and present a high voltage shock
hazard to its user.

Make sure the testing equipment is designed for and correctly operated
for high voltage and current tests being made.

When servicing or repairing electric power generation equipment:

• Make sure the unit is off-line (disconnected from utility and/or


other generators power service), and either locked out or tagged
DO NOT OPERATE.

• Make sure the generator engine is stopped.

• Make sure all batteries are disconnected.

• Make sure all capacitors are discharged.

Shut off engine and remove key before performing maintenance or


repair work. Failure to do so may result in personal injury due to
inadvertant machine operation.

Do not start the engine or move any of the controls if there is a "Do Not
Operate" or similar warning tag attached to the start switch or
controls.

Do not connect generator to a utility electrical distribution system


unless it is isolated from the system. Electrical feedback into the
distribution system can occur and could cause personal injury or death.

Open and secure main distribution system switch, or if the connection is


permanent, install a double throw transfer switch to prevent electrical
feedback. Some generators are specifically approved by a utility to run
in parallel with the distribution system and isolation may not be
required. Always check with your utility as to the applicable
circumstances.

https://127.0.0.1/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisweb/sis... 2020-04-11
3412 Generator Set 4BZ00001-UP(SEBP2785 - 34) - Documentation Page 4 of 6

Procedure
The two following procedures test the ability of the normal state of two different varistors. The
following procedures are to be used for the 9Y-9412 Varistor (CR7) and the 4P-6009 Varistor
(CR7. Determine which varistor is being used in your application, then use the appropriate
procedure. If any meter reading does not fall within the given ranges, replace the varistor (CR7).

9Y-9412 Varistor (CR7)

1. Remove all of the leads that are connected to varistor (CR7) block.

2. Place the 500 VDC or the 1000 VDC megohmmeter test leads on the varistor (CR7). The
varistor (CR7) device is not polarity sensitive.

3. If the megohmmeter is not capable of reading DC voltage, then hook up a 500 VDC
voltmeter across the CR7 terminals.

4. Select either 500 VDC or 1000 VDC setting of the megohmmeter. Apply the voltage to the
varistor (CR7).

Note: Do not apply voltage to the varistor for more than three seconds. .

5. Megohmmeter readings should be between 354 VDC and 429 VDC.

◦ If the readings are greater than 430 VDC, the varistor (CR7) is OPEN.

◦ If the readings are less than 353 VDC, the varistor (CR7) is SHORTED or
DEGRADED.

NOTICE

Do not over torque. Applying torques greater than the listed torques
may cause damage to the components.

6. Install leads. Apply the following torques.

◦ Terminal connections - 1.4 N·m (12 lb in) to 1.7 N·m (15 lb in)

◦ Varistor mounting to heat sink - 8.1 N·m (72 lb in) to 16.3 N·m (144 lb in)

Note: If the varistor (CR7) is found to be faulty, then the varistor (CR7) most likely failed
due to a transient voltage surge on the main rotor. Varistor failure is not usually a
component failure. Root causes of varistor (CR7) failure include:

◦ Incorrect paralleling or loss of synchronism

◦ Reverse VAR or reverse power event

https://127.0.0.1/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisweb/sis... 2020-04-11
3412 Generator Set 4BZ00001-UP(SEBP2785 - 34) - Documentation Page 5 of 6

◦ High ambient temperature (or other application error)

◦ Large sudden load application

4P-6009 Varistor (CR7)

1. Remove all of the leads from the varistor (CR7) block.

2. Place 1000 VDC megohmmeter test leads on the varistor (CR7). The varistor (CR7) device
is not polarity sensitive.

3. If the megohmmeter is not capable of reading DC voltage, then use a voltmeter that is able
to check 1000 VDC. Connect the voltmeter across the CR7 terminals.

4. Select the 1000 VDC setting of the megohmmeter. Apply the voltage to the varistor (CR7).

Note: Do not apply voltage to the varistor (CR7) for greater than 3 seconds..

5. Megohmmeter readings should range from 735 VDC to 910 VDC.

◦ If the readings are greater than 911 VDC, the varistor (CR7) is OPEN.

◦ If the readings are less than 735 VDC, the varistor (CR7) is SHORTED or
DEGRADED.

NOTICE

Do not over torque. Applying torques greater than the listed torques
may cause damage to the components.

6. Install leads. Apply the following torques.

◦ Terminal connections - 1.4 N·m (12 lb in) to 1.7 N·m (15 lb in)

◦ Varistor mounting to heat sink - 8.1 N·m (72 lb in) to 16.3 N·m (144 lb in)

Note: If the varistor (CR7) is found to be faulty, the varistor (CR7) most likely failed due to
a transient voltage surge on the main rotor. Varistor failure is not usually a component
failure. Root causes of varistor (CR7) failure include:

◦ Incorrect paralleling or loss of synchronism

◦ Reverse VAR or reverse power event

◦ High ambient temperature (or other application error)

◦ Large sudden load application

Copyright 1993 - 2020 Caterpillar Inc. Sat Apr 11 09:41:33 UTC+0200 2020 
All Rights Reserved.

https://127.0.0.1/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisweb/sis... 2020-04-11
3412 Generator Set 4BZ00001-UP(SEBP2785 - 34) - Documentation Page 6 of 6

Private Network For SIS Licensees.

https://127.0.0.1/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisweb/sis... 2020-04-11

You might also like