GENERAL CONSTRUCTION NOTES

GENERAL NOTES NOTES ON CONCRETE MIXES & PLACING


1. ALL CONCRETE SHALL DEVELOP A MIN. COMPRESSIVE STRENGTH AT THE END OF TWENTY EIGHT 3. IF SLABS AR E REINFORCED BOTHWAYS BARS ALONG THE SHORTER SPAN SHALL BE PLACED
1.0 STANDARDS AND REFERENCES
(28) DAYS W/ CORRESPONDING MAXIMUM SIZE AGGREGATE & SLUMP AS FOLLOWS. BELOW THOSE ALONE THE LONG SPAN AT THE CENTER AND OVER THE LONGER SPAN FOR
THE FOLLOWING SHALL GOVERN THE DESIGN FABRICATION AND CONSTRUCTION OF THE PROJECT.
MAX. SIZE OF REINFORCING BARS NEAR THE SUPPORTS. THE SPACING OF THE BARS AT THE COLUMN STRIPS
1.1 NATIONAL STRUCTURAL CODE OF THE PHILIPPINES (N.S.C.P 2015) VOL. 1, SEVENTH EDITION. LOCATION 28 DAYS STRENGTH MAX SLUMP SHALL NOT BE MORE THAN ONE AND A HALF ( 1 21 ) SLAB THICKNESS.
AGGREGATE
2.0 DESIGN CRITERIA ALL OTHERS, INCLUDING 20 mm 100mm 4. TEMPERATURE BARS FOR SLAB SHALL BE GENERALLY PLACED NEAR THE FACE IN TENSION AND
3000 PSI (20.7 MPa)
2.1 LOADINGS SHALL NOT BE LESS THAN 0.0025 X GROSS-SECTIONAL AREA (Ag) OF THE SLAB.

CONF. REINF.
SUSPENDED SLABS JOINT HOOP SPACE @ "2Sh" WHEN
COLUMNS 3000 PSI (20.7 MPa) 20 mm 100mm ( SEE SCHEDULE BELOW)
A. DEAD LOAD THERE ARE BEAMS HAVING WIDTH OF
3000 PSI (20.7 MPa) 20 mm 100mm

D JOINT REINF. D
CONCRETE 23.56 kN/m3 BEAMS ,SLABS AT LEAST ONE-HALF THE COLUMN
SLAB ON FILL 2500 PSI (17.5 MPa) 20 mm 100mm SCHEDULE OF MINIMUM SLAB REINFORCEMENT WIDTH & DEPTHS NOT LESS THAN
STEEL 76.93 kN/m3
THREE QUARTERS OF THE DEEPEST
150 mm THK. CHB WALL 2.73 kPa 2. MAINTAIN MINIMUM CONCRETE COVER FOR REINFORCING STEEL AS FOLLOWS. MINIMUM TEMPERATURE BARS BEAM THAT FRAME INTO FOUR

CONF. REINF.
100 mm THK. CHB WALL 2.11 kPa SUSPENDED SLABS 20mm 100 mm 10mm Ø @ 250mm EACH WAY SIDES OF THE COLUMN. ALL OTHER
B. LIVE LOAD SLAB ON GRADE 40mm 125 mm 10mm Ø @ 250mm EACH WAY CONDITIONS USE HOOPS @ "Sh" CENTERS.

Sh
WALLS ABOVE THE GRADE 25mm
ROOF 1.00 kPa 150 mm 10mm Ø @ 250mm EACH WAY
BEAM STIRRUPS AND COLUMN TIES 40mm

COLUMN TIES AS
CLASSROOMS 1.90 kPa

PER SCHEDULE
WHERE CONCRETE IS EXPOSED TO 175 mm 10mm Ø @ 250mm EACH WAY
TOILETS 1.90 kPa FOR COL. BAR SPLICES SEE TABLE
EARTH BUT POURED AGAINST FORMS 200 mm 10mm Ø @ 250mm EACH WAY OF MIN. LAP SPLICE LENGTH OF
CORRIDORS ABOVE, STAIRS 3.80 kPa 50mm
WHERE CONCRETE IS DEPOSITED COLUMN REINFORCEMENT
CORRIDORS ON GROUND 4.80 kPa 75mm 5. UNLESS OTHERWISE NOTED IN THE PLANS ALL BEDDED SLABS SHALL BE REINFORCED WITH 10mm Ø
DIRECTLY AGAINST EARTH

CONF. REINF.
C. WIND LOAD AT 250mm O.C. EACH WAY TO CENTER OF SLAB AND CONSTRUCTION JOINTS FOR SAME SHALL
NOT BE LESS THAN 3.65 METER APART.

Sh
BUILDING CATEGORY = 1 (ESSENTIAL FACILITIES) 3. CONCRETE SHALL BE DEPOSITED IN ITS FINAL POSISITON WITHOUT SEGREGATION. RE-HANDLING

D JOINT REINF. D
EXPOSURE = B (URBAN OR SUBURBAN AREAS WITH OR PLACING SHALL BE DONE PREFERABLY WITH BUGGIES , BUCKETS OR WHEELBARROWS, 6. PROVIDE EXTRA REINFORCEMENTS FOR CORNER SLAB ( TWO ADJACENT DISCONTINUOES EDGES) NOTE:
NUMEROUS CLOSELY SPACED OBSTRUCTION) NO CHUTES WILL BE ALLOWED EXCEPT TO TRANSFER CONCRETE FROM HOPPERS TO BUIGGIES, AS SHOWN BELOW. ALL CONCRETE REINF. DETAIL SHOULD
MAXIMUM WIND VELOCITY, V = 270 KPH WHEELBARROWS OR BUCKETS IN WHICH CASE THEY SHALL NOT EXCEED SIX (6) METERS 7. CONCRETE SLAB REINFORCEMENT BE PROPERLY SUPPORTED WITH 10mm STEEL CHAIR BE DONE IN ACCORDANCE WITH ACI
DETAILING MANUAL (LATEST EDITION)

CONF. REINF.
P = qh [(GCpf)-(GCpi)] (DESIGN WIND PRESSURE) IN AGGREGATE LENGTH. OR APPROVED EQUIVALENT SPACED AT 1.0 METER ON CENTER BOTHWAYS.
WHERE: qh = VELOCITY PRESSURE (kPa) 4. NO DEPOSITING OF CONCRETE SHALL BE ALLOWED WITHOUT THE USE OF VIBRATORS UNLESS
GCpf = EXTERNAL PRESSURE COFFECIENT AUTHORIZED IN WRITING DESIGNER AND ONLY FOR UNUSUAL CONDITIONS WHERE VIBRATIONS
Ø12x1000 LONG AT
GCpf = INTERNAL PRESSURE COFFECIENT ARE EXTREMELY DIFFICULT TO ACCOMPLISH. MID-DEPTH OF SLAB
D. SEISMIC LOAD TYPICAL COLUMN ELEV. SHOWING
5. ALL ANCHOR BOLTS, DOWELS, AND OTHER INSERTS SHALL BE PROPERLY POSITIONED & SECURED
Cvl W IN PLACE PRIOR TO PLACING OF CONCRETE. DOWN INTO EDGE BEAM. EXTENDED AT EACH CORNER
V=
RT
(DESIGN BASE SHEAR)
4-Ø 12@ 1800 LONG TOP BARS BEND 1-Ø12 TOP &
DOWELS AND TIES SPACING
6. ALL CONCRETE SHALL BE KEPT MOST FOR A MINIMUM OF SEVEN CONSECUTIVE DAYS IMMEDIATELY BARS MIN. OF 1,200 (4'-0") INTO BARS. BOTT. BARS
Vmax = 2.50CaI W Vmin = 0.11 CalW AFTER POURING BY THE USE O WET BURLAP, FOG SPRAYING, CURING COMPOUNDS OR OTHER
RT APPROVED METHODS. 4-Ø12 BOTT. BARS
Vmin = 0.80 ZNvI W (ZONE 4)

400
R 7. STRIPPING OF FORMS AND SHORES: LAP SPLICE LENGTH:
WHERE: W = TOTAL DEAD LOAD FOUNDATION 24 HOURS AT ANY LEVEL NO MORE THAN

0
SLAB ALTERNATE BARS SHOULD BE

60
SUSPENDED SLAB EXCEPT WHEN 8 DAYS 38mm
T = NATURAL PERIOD = Ct (h)

0
OPENING CLEAR SPLICED. MIN. DISTANCE BET.

60
WHERE: C = NUMERICAL COEFFICIENT ADDITIONAL LOADS ARE IMPOSED
21 DAYS TWO ADJACENT BARS SPLICES
h = BUILDING HEIGHT WALLS SHALL BE 600mm.

CONF. REINF. TIES LAT. TIES H (CLEAR HEIGHT OF COL.)


400
BEAMS 14 DAYS
I = IMPORTANCE FACTOR = 1.50 L
COLUMNS 21 DAYS
R = NUMERICAL FACTOR = 8.50

WITHIN CENTER
SEISMIC COEFFICIENT Cv = 0.44 Nv IN TWO WAY SLAB EXTEND
8. THE CONTRACTOR SHALL SUBMIT THE SCHEDULE OF POURING AND THE LOCATION OF THE

HALF OF "H"
60 BARS UP TO BEAM SUPPORT
Ca = 0.64 Nv 0
CONSTRUCTION JOINTS TO THE STRUCTURAL ENGINEER AT LEAST (4) DAYS PRIOR TO THE 0.25L
NEAR SOURCE FACTOR (5 km) Nv = 1.6 POURING FOR APPROVAL. OMIT TRIMMER BARS WHERE
Na = 1.2 OPENING IS FRAMED BY BEAM TOP BARS @ SUPPORT (CONT.)
9. THE CONTRACTOR SHALL FURNISH AND MAITAIN ADEQUATE FORMS AND SHORINGS UNTIL THE TYPICAL CORNER SLAB DETAIL REQ'D. BOTT. BARS @ SUPPORT
Z = SEISMIC ZONE = 0.40 (ZONE 4) CONCRETE MEMBERS HAVE ATTAINED THEIR WORKING CONDITION AND STRENGTH. TYPICAL SLAB

JT. REINF.
S = SOIL TYPE = D OPENING DET.
2.2 DESIGN STRESSES NOTES ON FOOTINGS
A. CONCRETE COMPRESSIVE STRENGTH @ 28 DAYS: 1. FOOTINGS ARE DESIGNED FOR AN ALLOWANCE SOIL BEARING PRESSURE OF 96 KPa (2000psf).
a. FOOTINGS, COLUMNS, BEAMS AND SLABS f'c = 20.7 MPa (3,000 psi) CONTRACTOR SHALL REPORT TO THE ENGINEER, IN WRITING ,THE ACTUAL SOIL CONDITIONS
NOTES ON COLUMNS 0.165L SPLICE BOTTOM BARS
AT MID SPAN
b. SLAB ON FILL f'c = 17.5 MPa (2,500 psi) UNCOVERED AND CONFIRM ACTUAL BEARING CAPACITY OF SOIL BEFORE DEPOSITING CONCRETE. 1. PROVIDE EXTRA SETS OF TIES AT 100 O.C. FOR TIED COLUMN REINFORCEMENT ABOVE 0.22L EXTRA TOP BARS
B. REINFORCING STEEL BARS 2. FOOTING SHALL REST AT LEAST 1500mm BELOW NATURAL GRADE LINE UNLESS OTHERWISE AND BELOW BEAM-COLUMN CONNECTIONS FOR A DISTANCE FROM FACE OF CONNECTION @ SUPPORT
a. FOR BARS 16mm AND GREATER (INTERMEDIATE GRADE DEFORMED BAR) fy = 275 MPa (40,000 psi) INDICATED IN PLANS. NO FOOTING SHALL REST ON FILL EQUAL TO GREATER OF THE OVERALL THICKNESS OF COLUMN, 1/6 THE CLEAR HEIGHT OF
b. FOR BARS LESS THAN 16mm (STRUCTURAL GRADE DEFORMED BAR) fy = 230 MPa (33,000 psi) 3. MINIMUM CONCRETE PROTECTION FOR REINFORCEMENT SHALL BE 75mm CLEAR FOR CONCRETE COLUMN OR 450mm.
C. STRUCTURAL STEEL ASTM-A36 DEPOSITED THE GROUND AND 50mm FOR CONCRETE DEPOSITED AGAINST A FORMWORK.
FOR TRUSSES, BRACINGS , & STRUTS fy = 248 MPa (36,000 psi) 4. IN CASES WHERE THE SOIL CONDITION IS SUCH THAT THE MINIMUM ALLOWABLE SOIL PRESSURE
2. COLUMN TIES SHALL BE PROTECTED EVERYWHERE BY A COVERING OF CONCRETE CAST
MONOLITHICALLY WIT HTHE CORE WITH A MINIMUM THICKNESS OF 40mm AND NOT LESS
TYP. DETAIL OF COL. LAP SPLICE
D. PURLINS OF 96KPa (2000 psf) CAN NOT BE ATTAINED AT A PRACTICAL DEPTHS THE USE OF MICROPILES ,
COLD FORMED LIGHT fy = 248 MPa (36,000 psi) BORED PILES, OR DRIVEN PILES MAY BE ADOPTED IN LIEU OF STANDARD ISOLATED FOOTINGS. THAN 40 TIMES THE MAXIMUM SIZE OF COARSE AGGREGATE IN MILLIMETERS. & EXT. GIRDER TO COL. CONNECT.
E. MASONRY UNIT (CHB) 3. WHERE COLUMNS CHANGE IN SIZE ,VERTICAL REINFORCEMENT SHALL BE OFFSET AT A
NON - LOADING BEARING CHB WALLS fm' = 3.45 MPa (500 psi) SLOPE MONOLITHICALLY WITH THE CORE WITH MINIMUM THICKNESS OF 40mm AND
F. WELDS E - 60XX ELECTRODE NOTES ON REINFORCEMENT NOT LESS THAN 40 TIMES THE MAXIMUM SIZE COARSE AGGREGATE IN MILLIMETERS
G. STRUCTURAL BOLTS ASTM- A307 a. Ft = 96.60 mPa (14, 000 psi) 1. UNLESS OTHERWISE NOTED IN PLANS, THE YIELD STRENGTH OF REINFORCING BARS SHALL BE: 4. UNLESS OTHERWISE INDICATED IN THE PLANS, LAP SPLICES FOR VERTICAL COLUMN NOTES ON BEAMS AND GIRDERS
b. Fv= 69.00 mPa (10, 000 psi) A. FOOTINGS , FOOTING BEAMS AND GIRDERS fy = 275 MPa ( 40,000 psi ) REINFORCEMENT SHALL BE MADE WITHIN THE CENTER HALF OF COLUMN HEIGHT, AND
B. COLUMNS AND SHEAR WALLS fy = 275 MPa ( 40,000 psi ) THE SPLICE LENGTH SHALL BE LESS THAN 40 BAR DIAMETERS. WELDING OR APPROVED 1. UNLESS, OTHERWISE NOTED IN PLANS , CAMBER ALL BEAMS AND GIRDER AT
3.0 IN THE INTERPRETATION OF THE DRAWING, INDICATED DIMENSIONS SHALL GOVERN. C. BEAMS AND GIRDER fy = 275 MPa ( 40,000 psi ) LEAST 6mmØ FOR EVERY 4.5O M OF SPAN , EXCEPT CANTILEVERS FOR WHICH
MECHANICAL DEVICES MAY BE USED PROVIDED THAT NOT MORE THAN ALTERNATE BARS
DISTANCES AND SIZES SHALL NOT BE SCALED FOR CONSTRUCTIONS PURPOSES D. NON-LOAD BEARING WALL PARTITIONS ,BEDDED SLABS , FLOOR & ROOF SLABS, THE CAMBER SHALL BE AS NOTED IN PLANS OR AS ORDERED BY THE ENGINEER
PARAPETS ,CATCH BASIN,SIDE WALK fy = 275 MPa ( 40,000 psi ) ARE WELDED OR MECHANICALLY SPLICED AT ANY LEVEL AND THE VERTICAL DISTANCES
4.0 IN REFERENCES TO OTHER DRAWINGS, SEE ARCHITECTURAL DRAWINGS FOR DEPRESSIONS IN FLOOR BETWEEN THESE WELDS OR SPLICES OF ADJACENT BARS IS NOT LESS THAN 600mm. BUT IN NO CASE LESS THAN 20 mm FOR EVERY 3.0 M OF FREE SPAN.
SLABS , OPENINGS IN THE WALLS AND SLABS , INTERIOR PARTITIONS , LOCATIONS OF DRAINS ETC. 2. ALL REINFORCING BARS SIZE 10mm OR LARGER SHALL BE DEFORMED IN ACCORDANCE WITH THE ASTM A-706
2. TYPICAL BARS BENDING AND CUTTING DETAILS FOR BEAMS SHALL BE AS
BARS SMALLER THAN 10mm MAY BE PLAIN.
5.0 IN CASE OF DISCREPANCIES AS TO THE LAYOUT, DIMENSIONS AND ELEVATIONS BETWEEN THE SHOWN IN FIG. B-1
3. SPLICES SHALL BE SECURELY WIRED TOGETHER & SHALL LAP OR EXTEND IN ACCORDANCE w/ TABLE B
STRUCTURAL PLANS AND ARCHITECTURAL DRAWINGS, THE CONTRACTORS SHALL NOTIFY BOTH THE (TABLE OF LAP SPLICE & ANCHORAGE LENGTH) UNLESS OTHERWISE SHOWNON DRAWINGS , SPLICES SHALL BE H
STRUCTURAL ENGINEER AND ARCHITECTS. STAGGERED WHENEVER POSSIBLE.
6.0 ALL CONCRETE WORKS AND CONCRETE REINFORCEMENTS SHALL BE DONE IN ACCORDANCE WITH THE CROSS-TIE
NOTES ON CONCRETE SLABS

350mm. MAX.
ACI.318-14M BUILDING CODE REQUIREMENT AND ALL STRUCTURAL STEEL WORKS ACCORDING WITH THE L1 L2
WITH THE AISC-05 IN SOFAR AS THEY DO NOT CONFLICT WITH THE LOCAL BUILDING CODE REQUIREMENT. 1. ALL SLAB REINFORCEMENTS SHALL BE 20mm CLEAR MINIMUM FROM BOTTOM AND FROM THE TOP OF SLAB. 1
L1 3
1
L1 3 L2 3
1 1
L2 3
7.0 ACI REFERS TO AMERICAN CONCRETE INSTITUTE, AISC REFERS TO AMERICAN INSTITUTE OF STEEL 2. UNLESS OTHERWISE SHOWN, REINFORCEMENT IN CONTINUOUS ELEVETED SLAB SHALL BE CUT AS FOLLOWS: 10
dm

H
CONSTRUCTION AND ASTM REFERS TO AMERICAN SOCIETY FOR TESTING MATERIALS. in.
8.0 CONSTURCTION NOTES AND TYPICAL DETAILS APPLY TO ALL DRAWINGS UNLESS OTHERWISE SHOWN OR
BENT BAR
NOTED. MODIFY TYPICAL DETAILS AS DIRECTED TO MEET SPECIAL CONDITIONS.
L1 L2 1 1 1 1
9.0 SHOP DRAWING WITH ERECTION AND PLACING DIAGRAMS OF ALL STRUCTURAL STEELS, MISCELLANEOUS L1 5 L1 5 L2 5 L2 5
L1/4 L1/4 L2/4 TOP BARS
IRON, PRE-CAST CONCRETE, ETC. SHALL BE SUBMITTED FOR ENGINEERS APPROVAL BEFORE FABRICATION. TOP BAR 2 Ø 12mm SIDE BARS WEB BARS
10. CONTRACTOR SHALL NOTE AND PROVIDE ALL MISCELLANEUOS CURBS, SILLS , STOOLS EQUIPMENT AND BOTTOM BARS
MECHANICAL BASES THAT ARE REQUIRED BY THE ARCHITECTURAL , ELECTRICAL AND MECHANICAL DRAWINGS. FIGURE B-1
11. ALL RESULTS OF THE MATERIAL TESTING FOR CONCRETE, REINFORCING BARS & STRUCTURAL STEEL MUST
BE NOTED & APPROVED BY THE MATERIALS ENGINEER/STRUCTURAL DESIGNER. BOTTOM BAR

DESIGN CONCEPT: APPROVED: CONCURRED:


PROJECT AND LOCATION: SHEET CONTENTS: SUBMITTED: RECOMMENDING APPROVAL: SET NO. SHEET NO.
STRUCTURAL SECTION
DEPARTMENT OF PUBLIC WORKS AND HIGHWAYS MODFIEIDSTANDARDDPWHD
-EPE
-D DESIGN CRITERIA
ONE(1)STOREY,FIVE(5)CLASSROOM GENERAL CONSTRUCTION NOTES DRAWN/AUTOCAD: SIGNED
BUREAU OF DESIGN SCHOOLBUILDING K.A.C.M. / M.A.H.A.
STRUCTURAL
SIGNED
JOSEPHINE P. ISTURIS
SEE COVER SHEET FOR SIGNATURE
LEA N. DELFINADO, CESO IV
SEE COVER SHEET FOR SIGNATURE

EMIL K. SADAIN
SEE COVER SHEET FOR SIGNATURE

LEONOR M. BRIONES
BOD
S-1
BUILDINGS DIVISION N
(OTOLIETATTACHED)
O
(PTO
IN2) CHECKED: SIGNED UNDERSECRETARY FOR UPMO OPERATIONS B 6 7
OFFICER IN-CHARGE, BOD
BONIFACIO DRIVE PORT AREA, MANILA KATHRINE ANNE C. MACOY CHIEF, BUILDINGS DIVISION
AND TECHNICAL SERVICES
SECRETARY, DEPED
SUPPLEMENTALPLANS081/52/018 ENGINEER IV