Professional Documents
Culture Documents
Installation Guidelines - Steam Conditioning Valves
Installation Guidelines - Steam Conditioning Valves
Installation Guidelines
Steam conditioning valves
List of revisions
Rev. Description of change Date Changed by Reviewed by Approved by
1 Revised information. 2014-10-06 TFD
GAN
Applicable products
VLB steam conditioning valve
VST-SE steam conditioning valve
Dump tube
While this information is presented in good faith and believed to be accurate, CCI does not guarantee
satisfactory results from reliance upon such information. Nothing contained herein is to be construed as a
warranty or guarantee, express or implied, regarding the performance, merchantability, fitness, or any other
matter with respect to the products, nor as a recommendation to use any product or process in conflict with
any patent. CCI reserves the right, without notice, to alter or improve the designs or specifications of the
products described herein.
Table of Contents
1. GENERAL 5
1.1. Inlet pipe recommendations ......................................................................................................................................... 6
1.2. Straight pipe run upstream recommendations .............................................................................................................. 8
1.3. Distance to the first downstream bend ......................................................................................................................... 8
1.3.1. Distance to the first bend for special cases...................................................................................................... 9
1.3.2. Dump to condenser with wet steam before dump device ................................................................................ 9
1.4. Distance to the temperature sensor ........................................................................................................................... 11
1.4.1. Minimum distance to temperature sensor ...................................................................................................... 11
1.4.2. Distance to the temperature sensor in special cases ..................................................................................... 12
1.4.3. Minimum degree of superheat ....................................................................................................................... 13
1.5. Distance to flow dividers............................................................................................................................................. 14
1.6. Distance to pressure sensor ....................................................................................................................................... 14
1.7. Downstream piping material ....................................................................................................................................... 15
1.8. Additional comments .................................................................................................................................................. 17
1.9. Diffusers and plates.................................................................................................................................................... 18
1.10. Drains / vent to atmosphere ..................................................................................................................................... 18
1.11. Pipe preheating ........................................................................................................................................................ 20
1.12. Water valve location ................................................................................................................................................. 24
1.13. Water pipe ................................................................................................................................................................ 24
1.14. Control system ......................................................................................................................................................... 25
1.15. Pressure control ....................................................................................................................................................... 26
1.16. Temperature control ................................................................................................................................................. 26
1.17. Special considerations for feed water with dump to condenser ................................................................................ 30
1.18. Actuation .................................................................................................................................................................. 30
1.19. Preheating arrangement of the upstream piping ...................................................................................................... 30
1.20. Temperature sensors ............................................................................................................................................... 33
1.21. Special applications where saturation is required after process / bypass valves ..................................................... 34
2. FIX POINTS AND SUPPORT 34
3. ACCESSIBILITY 36
List of figures
Figure 1: Pipe elbow upstream from the valve .................................................................................................................... 6
Figure 2: XYZ installation with T-piece ................................................................................................................................ 6
Figure 3: XY installation with T-piece .................................................................................................................................. 7
Figure 4: Installation with a stop valve welded unto a control valve .................................................................................... 7
Figure 5: Straight pipe runs upstream and downstream the valve ...................................................................................... 8
Figure 6: Downstream temperature vs time in a dump to condenser, or a similar process application using diffuser
technology ......................................................................................................................................................................... 10
Figure 7: Downstream temperature vs time in a HP to cold reheat or similar process application .................................... 10
Figure 8: Distance to temperature and pressure sensors.................................................................................................. 11
Figure 9: Downstream temperature vs time in a dump to condenser or similar process application ................................. 13
Figure 10: Protective shield ............................................................................................................................................... 13
Figure 11: Definitions ........................................................................................................................................................ 15
Figure 12: HP plots............................................................................................................................................................ 16
Figure 13: LP plots ............................................................................................................................................................ 16
Figure 14: Typical temperature decrease (HP to cold reheat) ........................................................................................... 17
Figure 15: Typical temperature decrease (dump to condenser) ........................................................................................ 17
Figure 16: Drain/preheat system ....................................................................................................................................... 19
Figure 17: Horizontal inlet/vertical outlet ........................................................................................................................... 19
Figure 18: Drainage system .............................................................................................................................................. 19
Figure 19: Vertical inlet and horizontal outlet .................................................................................................................... 20
Figure 20: Horizontal inlet and outlet ................................................................................................................................. 20
Figure 21: Vertical inlet and horizontal outlet .................................................................................................................... 21
Figure 22: Horizontal inlet, outlet upwards and actuator downwards ................................................................................ 21
Figure 23: Drain in downstream piping .............................................................................................................................. 21
Figure 24: Valve in low installation .................................................................................................................................... 22
Figure 25: Installation with bend welded directly to outlet ................................................................................................. 23
Figure 26: Expansion welded direct to outlet or closer than 0.1s x V max............................................................................ 23
Figure 27: Installation with an expansion cone in the outlet .............................................................................................. 24
Figure 28: Feed forward control ........................................................................................................................................ 27
Figure 29: Feedback control.............................................................................................................................................. 28
Figure 30: Feed forward when dump with dump device .................................................................................................... 28
Figure 31: Recommended installation for bypass to condenser ........................................................................................ 29
Figure 32: Pressure control valve with separate desuperheater ....................................................................................... 29
Figure 33: Preheating arrangement utilizing the natural pressure drop in the steam pipe................................................. 31
Figure 34: Preheating arrangement bypassing the control valve ...................................................................................... 32
Figure 35: Preheating arrangement utilizing a higher pressure level than the valve inlet pressure ................................... 32
Figure 36: Recommended locations of temperature sensors ............................................................................................ 33
Figure 37: Vertical installation ........................................................................................................................................... 34
Figure 38: Inlet pipe from above with spring hanger.......................................................................................................... 35
Figure 39: Inlet pipe from below with spring hanger .......................................................................................................... 35
Figure 40: Inlet pipe from below with sliding support ......................................................................................................... 35
Figure 41: Inlet pipe from above with sliding support ........................................................................................................ 35
1. General
The steam conditioning valve is an important part of the system. Parameters such as placement of
instrumentation, configuration of steam pipes and spray water temperatures can have a significant impact on
the performance of the valve. This document will describe different important factors involved in installation as
well as provide guidelines on how to achieve a proper system design.
All steam valves are designed for dry and clean steam. Exposure to wet steam or condensate will cause
damage and is not covered by any warranties. Vent valves and drains must be used to facilitate pipe pre-
warming until those conditions are fulfilled.
High contents of magnetite and other particles in the steam is a growing problem. This contaminated
steam causes erosion damages that are similar to that of wet steam. Damages to valve owing to
contaminated steam are also not covered by warranties, unless otherwise specified or agreed upon prior
to order.
L1 Elbow
The orientation of the closest pipe bend in respect to the valves rotation is also very important. An installation
as the one shown in Figure 1 is far better than what is shown in Figure 2. An installation like the one shown in
Figure 2 is known to create rotational forces in the valve plug. If this type of installation is unavoidable, CCI
has to be informed of this before the valve design specification is made.
A T-piece as shown in Figure 3 is also known to cause vibrations and other problems, and should always be
avoided. So must upstream S-pipes. If a T-piece is used, a straight pipe length of at least 20x pipe diameter
should be used before the valve.
Undersized stop valves with reduced bore upstream of a bypass valve are known to cause noise and
vibrations due to high vena contracta velocities and non-uniform velocity distribution.
Undersized stop valves also result in a nonlinear characteristic in the bypass valve, due to the strong
influence of the pressure drop on in the stop valve. Stop valves like these must be installed as far upstream as
required to ensure a uniform flow pattern in the bypass valve inlet. It is the responsible of the supplier of the
stop valve to inform CCI of the necessary distance.
An angle-style stop valve and a control valve can be assembled as one unit, with the stop valve outlet welded
directly to the control valve inlet.
L3
L2
L4
PT
TT
Steam pipe DN Distance from valve inlet to first upstream bend [L1]
Ø < 200 mm / <8” 1m / 3.28 ft or longer
If multiple pipe bends are located upstream, the straight pipe length [L1 in Figure 5] before the valve must be
increased, and that distance must be estimated for each case.
There should always be a temperature sensor installed upstream from the steam conditioning valve, to ensure
that the steam is dry before the valve opens. If an algorithm is used for controlling the valve, a pressure
sensor is also required.
[ C]
500
400
300
200
160
4 bar
143,6
Figure 6: Downstream temperature vs time in a dump to condenser, or a similar process application using
diffuser technology
The chart above shows the typical temperature downstream of water injection of a steam conditioning valve in
a dump to condenser application as a function of time when steam is minimum 10°C superheated.
[ C]
500
480
460
440
420
400
380
360
340
250,3
0 0,02 0,04 0,06 0,08 0,10 0,12 [s]
The chart above shows the typical temperature downstream of water injection of a steam conditioning valve in
an HP to cold reheat application as a function of time.
L1
L3
L2
L4
PT
TT
400
300
200
160
4 bar
143,6
As can be seen from the chart above, the temperature will decrease very quickly when water is injected, and
will then decrease slower and slower.
The reason for this is that the droplets will be exactly at saturation temperature, after a very short time after
they have been injected into the flow. Heat transfers from the surrounding steam to the droplets with
temperature differences as the driving force. The closer to the steam is to saturation temperature, the slower
the process, thus allowing more time for the droplets to fall out.
This typically begins to be a problem when the degree of superheat goes down to 20-30°, and become quite
difficult when degree of superheat goes down to 10° or lower.
Another problem associated with this is one droplet or more hitting the sensor. If one (or more) droplets hits
the sensor, it will cause a misreading, which is unpredictable and impossible to calculate.
During transients when the temperature swings around the set-point, this problem can increase beyond
stability and the system will not be possible to control with severe water fall outs and temperature swings as a
result.
A protective shield should be used for 10° superheat or less.
Flow direction
To avoid misreading, a protective shield must be used for 5-7°C / 9-11°F superheat in order to minimize the
effect of water hitting the sensor.
Below 5° superheat is not acceptable and no warranties will be granted. Exceptions are however, possible in
certain cases. Therefore please contact the factory. Problems like these are always minimized with a valve
like VST-SE with built in mechanical water proportioning. For less than 7°C / 11°F, special control and extra
instrumentation often must be used, and the factory must always be contacted for approval.
For dump to condenser applications where cold water (typically less than 50°C /122°F) is used for
desuperheating, the degree of superheat should be at least 20°C / 68°F, to avoid long evaporation time. 30°C
/ 86°F superheat is recommended. CCI strongly recommend that you avoid feedback control for dump to
condenser applications due to major risks for thermal fatigue damages related to difficulties in control. CCI
always recommend feed forward control for dump to condenser applications.
Table 1: Definitions
Variable Description Unit
Pd1 Design pressure at valve inlet bar(a)
Example:
HP bypass LP bypass
Pd1 = 264 bar(a) Pd1 = 64 bar(a)
Td1 = 610°C Td1 = 608°C
Pd2 = 64 bar(a) Pd2 = 16 bar(a)
This results in the design temperature td2 ≈ 533°C This results in the design temperature td2 ≈ 591°C
CCI valve outlets (material and thickness) are designed for Pd2 and td2, i.e. only the isenthalpic expansion
governed by thermodynamic laws, is taken into consideration.
Even though the stated design temperatures downstream (t2max) are 385°C (HP) and 250°C (LP) (points 3),
this cannot be achieved until a minimum of 5 meters downstream of the valve outlet, due to the time it takes
for the water to evaporate and cool down the steam.
Therefore the pipe (material and thickness) connected to the valve outlet and <5 meters downstream
must also must be designed for Pd2 and td2, even though the stated downstream maximum
temperature is t2max. This can be reduced in certain cases after factory written approval.
As can be seen in the examples below, the temperature decreases fairly quickly in the beginning after spray
water injection. Within 5 meters, most of the temperature decrease will have taken place, allowing material
and/or thickness to change according to the pressure Pd2 and temperature t2max.
Also, when welding a thin pipe to a thicker valve outlet, it creates a weak point in the piping system due to the
abrupt transition and variations during expansion caused by differences in material thickness. Therefore,
welding a thinner pipe directly to the valve outlet is not allowed. This transition can be done after 5
meters.
An abrupt transition in material thickness at the valve outlet where there is still high temperature will be
exposed to a high risk of thermal shock and stress at the weld, whereas > 5 meters downstream, the
temperature as well as the risk of thermal stress is much lower. See the temperature reduction in the charts
below.
Figure 14: Typical temperature decrease (HP to cold Figure 15: Typical temperature decrease (dump to
reheat) condenser)
Free water in the steam system causes noise, mechanical damage and makes temperature
measurement difficult.
The steam conditioning valve performs an important function in the steam system. It is therefore essential to
protect the valve from damage that might occur if water enters the valve. It is equally important to protect the
downstream system from damage caused by a malfunctioning temperature control system (see separate
section). It is therefore necessary to have drains both upstream and downstream of the valve.
Maximum condensate normally occurs during cold startup. This must be considered already at the design
stage for sizing of the drainage system. Condensate volume that must be removed during start up should of
course be calculated each time based on real data but as an estimate, a mass of typically 7-14 % of the
upstream piping weight needs to be removed through the condensate system. To prevent damages, there
should always be a temperature sensor to confirm that the upstream piping is dry before the valve is opened.
The illustrations in Figure 16 to Figure 18 show examples of drain arrangements for different valve positions,
etc.
Note! In case of a valve position according to fig. 10 and 11, the position of the drain connection must be
exactly defined.
CCI
From DCS on/off Customer
Preheat flow
To handle
start up
condensate Drain of level
removal control type
L1
L2 LIC
Manual or on/off
from DCS
Y
Drain
On when contaminated
condensate
On when clean
condensate
To hotwell/condensate
recovery system
Figure 16: Drain/preheat system
The inlet steam pipe shall have a drain connection at the low point close to the valve.
D
L
Locate the drain (D) on the downstream side at the lowest point after the valve. Weld a drip leg (L) to the pipe,
and connect the drain to the bottom of the drip leg.
The drip leg shall have a diameter of 0.5 x pipe diameter. The depth of the drip leg shall be between 300 and
600 mm / 1-2 ft.
If possible, always avoid an installation where the valve outlet is at a low point. If the drain is undersized or not
working, water can accumulate and cause many serious problems.
CCI is only responsible for problems related to the equipment that is included in CCI’s scope of supply.
CCI can under no conditions be responsible for poor functionality caused by installations that do not
comply with CCI Installation Guidelines.
The weight of the accumulated water can seriously damage piping and supports.
Free water at the bottom of the piping can cause very serious vibrations and pressure transients in the
piping.
Downstream temperature sensor can be hit by non-evaporated water causing severe control problems.
Minimum slope to drain at a low point should never be less than 100:1.
Water hammers.
A simple closed temperature control loop is in most cases too slow for this type of installation. A feed
forward system is always required to minimize the effect of transients recommended for this
installation.
Transient analysis is necessary and must always be performed before designing the control system.
An installation (like shown below) with a bend directly after the outlet is very dangerous and is therefore
ALWAYS FORBIDDEN.
An installation (like shown below) with an expansion directly after the outlet will in most cases not work or
cause severe water fallout.
An expansion welded directly to the outlet or closer than 0.1s x Vmax IS NEVER ALLOWED.
Figure 26: Expansion welded direct to outlet or closer than 0.1s x Vmax
Exception: In certain cases, the design below can be used after written confirmation from the factory.
Not providing correct information may lead to capacity / control problems for which CCI cannot be held
responsible.
Systems with a low degree of superheat (especially at low pressures) often require enthalpy-based feed
forward control to be able to operate correctly.
In order to achieve good performance, the control loop itself must also be analyzed to find out, within which
exactness the water flow can be controlled by the complete control loop. The most important parameters are:
Sensor response time
Controller response time and accuracy
Positioner accuracy
Valve accuracy
Valve characteristic
Valve position accuracy
Dead band
Maximum transients
Actuator accuracy and stiffness
This analysis also provides the answer regarding sizing of the drainage system downstream of a
desuperheater or steam conditioning valve.
The algorithm is based on the dump device used as a flow meter and a heat balance using inlet pressure and
temperature:
PT
PT TT DCS
Steam
FT
Spray water
Figure 28: Feed forward control
Used when a dump device cannot be used as a flow meter. Algorithm based on valve position with
compensation for variations in inlet pressure and temperature. Pin and Tin are also used in the heat balance:
Steam
PT
PS
DCS TT
FT
Spray water
When the valve is very large, the below installation helps simplify maintenance:
Desuperheater
Dump Tube Condenser
1.18. Actuation
The choice of actuator type is important for performance, especially where temperatures close to saturation
are required. Transients are heavily amplified if the actuator makes overshoots, which may result in wet steam
hitting the temperature sensor, further worsening temperature control.
Electrical, hydraulic or double-acting piston actuators with a high performance smart positioner must be used.
To avoid problems the actuator on the water valve must be slower than the actuator on the steam valve.
Figure 33 to Figure 35 show a few arrangements that can be used. The piping layout will determine the
preheating arrangement that will be the most effective for a specific application.
Note! CCI can give advice on the best solutions for different types of plants; e.g. conventional reheaters,
combined cycle, cogeneration plants and others.
Typical pipe dimensions for the preheating line are in the range of 25 - 50 mm / 1 – 2 inches. The preheating
line must be equipped with an isolation valve, which also can be used for manual flow control of the steam
flow for preheating.
The preheating sizing is based on:
Length of pipe between valve and main line
Δt between surface temperature outside the insulation and the environment.
Indoor or outdoor installation.
A heat balance based on this information will provide the necessary preheating flow.
1 2
B
A. Main steam line
B. Preheating flow
C. Bypass line
Figure 33: Preheating arrangement utilizing the natural pressure drop in the steam pipe
The method above is the most energy effective, but requires a suitable system design.
When the steam flows from (1 to 2) there will be a pressure drop Δp in the line. With proper sizing of the
preheating piping (1 to 3), it is possible to have a sufficiently large flow to keep the piping (3 to 2) free of
water.
The required pressure drop is often practically difficult to achieve and often requires both a big preheating
pipe and a restriction in the main line. A reasonable pressure drop is 0.2 – 0.5 bar.
The method shown in above is the easiest and most common way of preheating upstream piping. Here you
simply connect the inlet with the outlet and use a restriction to limit the steam flow.
The steam flow used for preheating shall be moderated according to required pipe / valve temperature to
reduce energy loss. In most cases, normal preheating flow is 50 - 200 Kg/h / 134 - 535 lbs/h.
This preheating with connecting inlet to outlet can cause very high temperatures downstream. Special springs
made of Nimonic or similar must therefore be used. The factory must also be informed prior to manufacturing
if this method is used. Normally, the downstream connecting point must be used after the valve to prevent
hotspots that may cause deformation of the valve outlet.
Preheating flow
Bypass line
Preheating line
Hot reheat line
Main steam line
Figure 35: Preheating arrangement utilizing a higher pressure level than the valve inlet pressure
The solution shown in above image is energy efficient, but may sometimes require a long preheating line.
As can be seen at Time 4, temperature sensor t1 is very far from the average of the three temperature
sensors. If the average of all three is used for temperature control, one faulty sensor will give a misreading of
the temperature. When only using the two sensor readings closest to the average of all three and calculating a
new average with these two values, the temperature reading is more likely to be correct. With 3 sensors the
probability of getting incorrect measurements is decreased.
If one sensor consistently is far from average, an automatic warning can be set in the DCS informing that the
sensor needs calibration or replacement.
12:00
10:00 14:00
Crane
for lifting
L1
Steam
Inlet Platform
Nozzle
L2
Dump
Tube
Duct
Horizontal installations
Spring Spring
hanger
hanger
Figure 38: Inlet pipe from above with spring hanger Figure 39: Inlet pipe from below with spring hanger
Sliding
support
Sliding
support
Vibration
absorber
Vibration
absorber
Figure 40: Inlet pipe from below with sliding support Figure 41: Inlet pipe from above with sliding support
Due to their weight, actuators with springs must always be supported to avoid excessive forces on yoke and
mounting details. This is especially important when an actuator is mounted horizontally. Spring hangers are
always required when actuators with springs are used.
3. Accessibility
Space must be provided for service and maintenance of the valve. If the valve is installed in a pipe rack or any
other location which is difficult to reach, you need to provide a platform around the valve and a safe route to it.
The platform shall be sufficiently large to accept a minimum of two persons and temporary storage of valve
internals.
Note! Consider also transportation of heavy spare parts.
A bracket or other arrangement for a lifting device shall also be available. The capacity shall be at least 5
tons. To facilitate maintenance within scheduled time, lifting equipment and a working platform must be
provided. Planning for future maintenance is a very good investment and should always be taken into
consideration.