Professional Documents
Culture Documents
Design of Air
Design of Air
Submitted By
M Badar Ashraf Rana (F2019019039)
Hamza Ahmad (F2019019050)
M Ahmad Saeed (F2019019037)
Submitted To
Sir Hassan tariq
Abstract
In this Complex Engineering Problem We design Air-Flow Speed Measurement system using
Thermistors. We calculate the change in resistance and change in Voltage with respect to change
in temperature and measure the output voltage with respect to speed of Air (mph). Design a plot
of output voltage versus wind speed. We find the percentage error between output voltage and
wind speed using curve fitting. Design a circuit to interface the sensor with a 6-bit dual –slope
analog to digital converter with a 10V reference.
Table of Contents
Problem statement 4
Complete the table from the design result 5
Prepare a plot of output voltage versus wind speed 7
Find the basic exponential relation between output voltage and wind speed using curve fitting 8
Design a circuit to interface the sensor with a 6 bit dual slope analog to digital converter(ADC) 10
Conclusion………………………………………………………………………………………………11
References………………………………………………………………………………………………11
Problem Statement
Air-flow speed can be measured by comparing the temperatures of a shielded thermistor and one which is exposed
to the moving air. A diagram of this sensor is shown in figure below. The thermistors are used in a bridge and both
are operated at an elevated (no-wind) temperature of using self-heating. When wind blows, the exposed sensor will
cool off and the other will not.
It has been experimentally found that the temperature difference between the thermistors is as shown in the
following table for winds of 0 to 60 mph.
(1)
The thermistors have a resistance of 2.4 kΩ at 45
Slope= ‒24 Ω/°C within ±10°C
Dissipation Constant= 5.2mW/°C.
(2)
We use 20 V supply voltage for the bridge
(3)
Assume ambient temperature 21 ° C
P= 0.1248 W
P=I 2 R
Taking square root on both sides
I =√ P/ R
√
0.1248
I = 2400 ¿
¿
I=7.21 mA
V=17.304 V
The bridge is operating at 20 V supply Using the thermistor in the lower side of the bridge find
the voltage drop.
Voltage Drop (V)= 20 -17.304 = 2.696 (V)
I= 7.21mA
V
Upper Resistance= R=
I
2.696
R= = 373.92 Ohms
0.00721
After Knowing all the parameters we find the change in resistance ∆ R value with respect to
temperature. When the Air speed is 0 change in temperature and resistance is 0.
We can find the change in resistance with the following parameters
∆ R=( ∆ T ) ×(Slope)
Now we calculate the change in voltage (∆V ) by using the following relation
∆ V =E[
( Rth
Rth + Rup)(
−
Rth +∆ R
R th+∆ R+ R
up
]
)
∆ V =20[ ( 2400+373.92
2400
)−( 2400+0+373.92
2400+ 0
)] = 0V
∆ V =20[ (
2400+373.92 ) ( 2400+72+373.92 )
2400 2400+72
− ] = -0.0682 V
∆ V =20[ ( 2400+373.92
2400
)−( 2400+108+373.92
2400+108
)] = -0.101 V
∆ V =20[ ( 2400+373.92
2400
)−( 2400+132+373.92
2400+132
)] = -0.122 V
∆ V =20[ ( 2400+373.92
2400
)−( 2400+151.2+373.92
2400+151.2
)] = -0.139 V
∆ V =20[ ( 2400+373.92
2400
)−( 2400+0+373.92
2400+170.4
)] = -0.156 V
∆ V =20[ ( 2400+373.92
2400
)−( 2400+184.8+373.92
2400+184.8
)] = -0.168
After the calculation of change in voltage we calculate the output voltage by using the Gain
formula of the amplifier.
Gain= Output Voltage/ Input Voltage
Taking the output voltage 6Vand the input voltage 0.168V
V 6
G= out = =35.71
V ¿ 0.168
Calculate the output votages by using the formula of Gain
V out =Gain× V ¿ =35.71× 0.0682=2.44 V
C) What is the greatest error between voltage indicated wind speed and
actual speed?
The Greater error is in between (10 mph) and (30 mph). At 10 mph the voltage should be 1
Volt but in this case the output voltage is 2.44 V.
Mean speed=( V out ) ×(Speed)
2.44 × 10
24.4−10
Percentage Error= ×100=144 %
10
D) Find the basic exponential relation between output voltage and wind
speed using curve fitting
Let y= V out and x= Speed find the value of a and b
Let log(y)=ly(y)
x=X
Log(a)=A
b=B
∑ y=mA + B ∑ X (2)
∑ Xy=A ∑ X + B ∑ X 2 (3)
We have ¿ find ∑ y , ∑ X , ∑ X , ∑ XY
2
X=x X2 Ln(y) Xy
0 02 0 0
10 10
2
0.892 8.92
20 202 1.284 25.68
30 30
2
1.472 44.16
40 40 2 1.601 64.04
50 50
2
1.717 85.85
60 602 1.792 107.52
∑ X=210 ∑ x 2=9100 ∑ lng=8.758 ∑ Xy=336.17
∑ y=mA + B ∑ X
8.758= 7(A) + B(210)
∑ Xy=A ∑ X + B ∑ X 2
336.17= A(210)+B(9100)
8.758−210 ( B )
A=
7
A=1.251-30 (B)
Put the value of A in eq 1
336.17=(1.251-30 B)(210)+ B(9100)
336.17=262.71-6300B+9100B
2800 B=73.46
B=0.0262 (B=b)
A=1.251-30(0.0262)
A=1.251-0.786
A=0.465
A=Log(a)
0.465= log(a)
0.465
a=e
A=1.592
Exponential Equation
0.0262b
y=1.592 e
E) Design a circuit to interface the sensor with a 6 bit dual slope analog to
digital converter(ADC)
We use 6 bits analog to digital converter. The specification of the 6 bit ADC is as follow.
The sampling rate of the ADC is 90Msps and the power dissipation rate is lower which is
350mW and the bandwidth is 55 MHz. The block diagram of the ADC is as follow
Circuit Digram
Conclusion
In this complex engineering problem we design a Air flow speed measurement system using
Thermistors. We derive the relation of change in resistance change in voltage and the output
voltage. Plot the graph of output voltage versus wind speed and observe the behavior of the
graph. Further we calculate the greatest error between voltage –indicated wind speed and the
actual speed. We design a circuit to interface the sensor with a 6 bit dual slope analog to
digital converter with a 10 V reference. We develop a liner equation to give a quantity in the
program that is equal to the actual air speed in mph.
References
[1] Process Control Instrumentation Technology 8th Ed. by Curtis Johnson, Pearson
Education, 2014.
[2}Electronic Instrumentation and Measurement Techniques by Cooper, William David,
Prentice-Hall, 1985
[3]https://core.ac.uk/download/pdf/34212685.pdf
[4] Introduction to Instrumentation and Measurements by Robert B. Northrop, 2nd Ed., CRC
Press, 2005