Professional Documents
Culture Documents
CD M&W 2008 Ed - Sect 3 - Gas Filters
CD M&W 2008 Ed - Sect 3 - Gas Filters
CD M&W 2008 Ed - Sect 3 - Gas Filters
GAS FILTERS
3.1 General
3.1.1 Purpose
The nominal performance viz. the air flow quantity of the gas filter shall be
600 cubic metres per hour (CMH), for which the gas filters shall be
designed, fabricated, assembled and tested.
The gas filter shall be designed and constructed for 2 modes of operation
namely, the gas filtration mode and the filter by-pass mode. In the gas
filtration mode, all outdoor air for shelter ventilation purposes shall pass
through the gas filter and filtered by the aerosol and activated carbon
filters. In the filter by-pass mode, the outdoor air bypasses the gas filter
and is supplied direct to the shelter air handling unit.
In relation to blast, the gas filter shall be able to withstand the shelter blast
valve peak pass-through free field overpressure and impulse. The blast
pass-through pressure and impulse shall be no less than 2 bars and 1.5
bar-millisecond (bar ms) respectively. The shock resistance of the gas
filter shall be no less than 12.5 g’s in either direction along each of the 3
major axes.
May 2008
MW/3/2
All parts of the gas filter shall be made of materials which shall possess
properties suitable for its use in a hostile environment such as long-term
durability, high resistance to heat, humidity and dust, fire resistant and
high resistance to the biological-chemical agents stated above.
An air inlet and an air outlet tube each with a gas-tight blank-off disc shall
be provided with the container. To ensure gas-tightness, the blank-off disc
shall consist of a metal shut-off plate, rubber seals and suitable number of
bolts and nuts to attach the shut-off plate to the tubes. Only when the
shut-off discs are removed for contaminated air to pass into the gas filter
during the air filtration shall then the gas-tightness be broken.
The gas filter cover(s), the blank-off discs, the compensating screw and
any container locking ring shall be sealed by the manufacturer at the
factory. Every gas filter shall be checked for air-tightness and sealing
before leaving the factory.
May 2008
MW/3/3
Each gas filter shall be fastened to the concrete plinth on the platform floor
at a minimum of four (4) mounting points using four (4) base frames or
one (1) common base frame. The base frame(s) shall be made of welded
steel members hot dipped galvanized for corrosion protection. The design
of the base frame(s) and fasteners shall comply with the specified shock
requirements.
The filter container shall be provided with at least two handles for lifting
and transportation.
The gas filter shall be marked with a durable and water resistant label
which reads “Keep upright at all times. Do not tilt”. The air flow directions
shall be clearly marked with arrows using water resistant paint on the
container air inlet and outlet tubes.
May 2008
MW/3/4
The function of the aerosol filter is to retain the fine solid suspended
particles and aerosols through separation achieved by the effects of
inertia, interception and diffusion.
The filter element material shall have high separation capacity, high fire
retardance, low flow resistance, high aerosol storage capacity, high water,
chemical and putrefaction resistances.
Each aerosol filter shall have a nominal air flow rating of 600 CMH. The
nominal air flow velocity through the aerosol filter surface shall not exceed
1.5 cm per sec. Each filter shall be individually tested and certified to
have an efficiency of not less than 99.9995 % when tested with particles of
0.1 to 0.3 microns. This efficiency shall be maintained for the range of
particle sizes even after the blast and shock tests as specified herein.
Filter style code and performance shall be printed on each filter cell.
The aerosol filter shall be provided with a gas-tight seal such that no
leakage shall occur around its perimeter and all intake air has to pass
through the filter medium. The sealing material shall be ageing resistant
and stable within a range from 0oC to +60oC and shall be resistant against
all types of war biological and chemical agents.
The following are additional requirements for the aerosol filter and the
mechanical values are applicable for both the longitudinal and traverse
directions:-
The permeability for particle size ranging from 0.1 to 0.3 µm shall
be:-
May 2008
MW/3/5
v) Chemical stability
May 2008
MW/3/6
The test requirements shall comply with ISO 535 - 1991 or approved
equivalent. The water capacity of absorption shall be less than 10 gm
-2
.
The activated carbon bed shall be the gas absorption element in the gas
filter when the contaminated air is channelled through it. The activated
carbon shall be microporosity carbon of a good grade and impregnated
with chromium salt, silver and copper such that it is suitable for use to
neutralise war agents. The activated carbon has to be filled in compactly
and maintained under compaction by compression springs. After filling in
the activated carbon, the carbon humidity shall not exceed 5 % by weight.
The activated carbon bed shall have a specific volume of at least 0.45 litre
of activated coal for every cubic metre per hour of air flow rate i.e.
0.45x600 = 270 litres (minimum) of activated carbon in the filter. The
minimum carbon bed thickness shall be 150 mm.
The complete assembly of gas filter subjected to test with the nominal flow
capacity shall provide at least the same holding time as a reference
carbon column tested at the same time for comparison purposes. This
May 2008
MW/3/7
The filter gas absorption capacity shall be maintained after the specified
shock and blast pressure tests.
A pressure drop simulator shall be provided across the intake and outlet
air tubes. The pressure drop simulator is used in normal times to simulate
the designed pressure drop across the gas filter at an air flow of 600 CMH
without the need to pass the intake air through the activated carbon bed of
the gas filter. A differential pressure manometer shall be provided on the
simulator and marked appropriately such that at the nominal air flow rate
the pressure drop across the gas filter shall not exceed its nominal value
which in any case shall not be more than 1000 Pa. It shall be possible to
read the actual pressure drop across the gas filter at the nominal air flow
rate by using gradations marked at 100 Pa intervals on the manometer.
The respective levels of the liquid in the simulator shall not exceed or drop
below the range of design pressure drop of the gas filter.
May 2008
MW/3/8
The activated carbon bed shall be protected at the air inlet and outlet
sides of the bed with dust protective filters to remove dust with a filter
efficiency of 90 to 95% arrestance ASHRAE 52-76 or approved equivalent
standard.
All metal parts of the gas filter shall be properly treated for corrosion
protection such as use of hot dipped galvanized complying with EN ISO
1461 or approved equivalent or epoxy powder coating or a surface
treatment and painting scheme approved by Authority.
3.2.10 Packing
3.2.11 Weighing
Each gas filter assembly shall be weighed in the factory and weighed
again after delivered to site. The gas filter weighing machine shall be able
to provide on weight measurement in kg up to two (2) decimaql points. A
valid calibration certificate shall be submitted for Authority’s review prior to
carrying out the weighing process. The 2 weights shall be recorded on
labels affixed to the gas filter container and compared to see whether
there is any weight gained. The tolerance of the gas filter weighing
machine shall not be exceed 0.3kg. If the on-site weight gain/ loss of a gas
filter is more than 0.3kg compared to the factory weight then that gas filter
will be rejected and has to be replaced at no cost to the Authority.
May 2008
MW/3/9
Only gas filters which have successfully passed such type tests will be
considered.
For the submission of the type test results, the following documents shall
be submitted:-
The Contractor shall propose the make and model of gas filters supplied
under the contract. In addition to the detailed specifications for the
equipment proposed, the Contractor, as part of tender submission, shall
submit test results or test certificates issued by an independent testing
authority for the following:-
May 2008
MW/3/10
Upon award of the tender, 1 batch test shall be carried out by the
Contractor on a gas filter randomly selected from each batch of gas filters
supplied with a distinct activated carbon production lot. The tests shall be
carried out by an independent testing authority proposed by the
Contractor. In this connection, the Contractor shall propose at least two
independent testing authorities for consideration by the Engineer. All costs
related to such test(s) shall be deemed to have been included in the
contract price.
a) pressure drop across gas filter test at airflows of 400 to 800 CMH
b) shock test on mechanical test bed at 12.5 g’s in both directions along
the 3 major axes
For each batch test, one gas filter shall be tested. The gas filter shall be
selected by the Engineer at random from the batch of gas filter at the
manufacturer’s factory. The exact timing and dates of the tests shall be
proposed by the Contractor subjected to the acceptance of the Engineer.
Samples of the gas filters shall be tested for compliance with the
requirements of the respective tests as specified herein. In the event that
any one of the gas filter should fail the test, the whole batch of the gas
filters from which the sample is taken will be rejected. A new batch of gas
filters shall be supplied and a sample from the batch shall be selected at
random for a re-test. The batch of gas filters shall be accepted only after
the tests on the sample selected from the batch are successful. The
Contractor shall bear all necessary costs for the successful completion of
the batch tests or any re-tests as specified.
The Contractor shall be deemed to have allowed for all costs for all the
abovementioned tests and witnessing visits and no claims whatsoever
shall be entertained in this respect.
3.3.3 Testing
a) Shock test
The gas filter shall be tested for its mechanical shock resistance.
The gas filter shall be fixed onto a mechanical test bed and subject to
a shock of no less than 12.5 g’s in both directions (one at a time)
May 2008
MW/3/12
along each of the 3 major axes. After the blast, the gas filter shall be
inspected visually for any damage or loosening of its components.
b) Blast test
The gas filter shall be mounted behind a shock tube and subject to a
blast wave for the purpose of verifying its ability to withstand a blast
and retain its performance effectiveness thereafter. The shock shall
generate a shock wave to simulate a test blast of over-pressure and
impulse at no less than 2 bars and 1.5 bar-millisecond (bar ms)
respectively. The blast pressure and impulse shall be measured at a
distance of 300 mm from the position of the air intake side blank-off
disc along its axis with the blank-off disc removed. See sketch below
for test arrangement of shock tube and gas filter.
c) Leakage test
May 2008
MW/3/13
Diaphragm
Booster
Chamber
Pressure Tank
At
Expansion
Chamber
SHOCK
TUBE
Air Compressor
AI
Pressure Gauge to measure blast
overpressure and impulse
300mm
Position of gas
filter blank-off
disc
Position of gas
GAS FILTER filter blank-off
disc
May 2008
MW/3/14
The aerosol filter shall be removed from the gas filter after the blast
resistance and shock tests and a aerosol test conducted on it.
Filters with efficiency less than 99.9995 % for test aerosol size
ranging from 0.1 to 0.3 microns arising from this test shall deem to
have failed the test and shall be rejected. The filter efficiency for the
range of particle sizes as specified shall be determined by a
fractionating particle counting method subject to approval of the
Authority.
The test set-up shall be able to record the concentrations of the test
gas, at regular time intervals, at the inlets and outlets of the gas filter
May 2008
MW/3/15
and reference carbon column such that the break-through times for
both gas filter and the column could be measured and compared.
i). The test gas flow rate shall be linear and at about 100 mm/s
corresponding to the specific carbon volume of 0.45
litres/CMH of nominal air-flow and a minimum contact time of
1.5 seconds of gas filter.
May 2008
MW/3/16
Legend:
Test conditions:
Notes:
May 2008
MW/3/17
Notes:
May 2008
MW/3/18
Each batch of gas filters supplied shall be provided with a set of operation
and maintenance manuals in English. The manuals shall contain operation
and maintenance instructions supplemented with illustrative drawings and
shall include inter alia description of operational requirements and
procedure, maintenance requirements and procedure, complete parts list,
list of special operation and maintenance tools, procedure for use of
pressure drop simulator, etc.
The maximum permissible weight increase of the complete gas filter due
to moisture absorption by the activated carbon shall not be exceeded. This
permissible weight increase shall be clearly labelled on the gas filter
container and included in the operations and maintenance manuals.
3.4.3 Labelling
The Contractor shall adopt a quality plan and quality manual for the
manufacture of gas filters. The documents shall include all quality control
systems, work procedures, check-lists and an inspection and test plan for
the manufacture of all components in accordance with the specifications.
May 2008