ENGINEERING

DATA
CONTENT

Introduction 1
Features & Benefits 2
Nomenclature 6
Air Flow Arrangement 7
Dimension & Weight 9
Guide Specification 11
Options ± Guide Specification 16
Remote Monitoring & Supervisory System 20
Technical Data 21
Recommended Pipe Sizes 23
Electrical Details 24
INTRODUCTION

The Company

Citec International is one of the global leaders in designing and manufacturing


Precision Air Conditioning system. Citec International places great emphasis on
achieving the highest standards and incorporates stringent quality controls throughout
its operations. Every CITEC product is designed and built within a Quality
Management System ISO9001 and Environmental Management System
ISO14001,using our unrivalled experience in Precision Air Conditioning, with
extensive testing of components and complete systems. Every aspect is engineered to
ensure maximum reliability, economy of operation and long working life, together
with ease of installation and maintenance.

The Product

The G-Volution Series is the latest Precision Air Conditioning units from Citec
International that are engineered to run seamlessly in critical environments by
delivering constant, efficient and intelligent cooling circulation consistently and
reliably for 24 hours per day, 7 days per week.

The G-Volution Series is designed for areas with limited space as well as large data
centers. The units are designed with wide range of options to meet the requirement of
precision cooling needs in various applications and environment. Typical applications
include:

o Data Centers
o Computer Rooms
o Telecommunication Rooms
o Co-location Centers
o ISP
o Hospital Operating Rooms
o Laboratories

The Range

The G-Volution EH Range is a dual coil system Precision Air Conditioning unit. It
has two sets of cooling coils, i.e. either 2 sets of chilled water coils or 1 set of chilled
water coil plus 1 set of direct expansion coil. The direct expansion part of the system
can be either a Water Cooled type with plate heat exchanger or Air Cooled according to
the site requirements. Both dual coil system comprises 4 models, in 4 cabinets
respectively with nominal capacity from 60kW to 95kW. The EH Range is designed
ZLWK&LWHF¶s vast experiences in data center and critical space cooling. The EH Range
provides high reliability and availability and thus minimizes the downtime.

The G-Volution EH Range only require front service access and can be easily
installed side by side or tucked into a corner. The EH Range units are available in
both downflow and upflow configuration.
~1~
FEATURES AND BENEFITS

Dual Cooling System

A lot of buildings are equipped with central chilled water systems to provide comfort
air conditioning. These systems are usually not design for computer rooms and similar
applications because the chilled water might be unavailable after office hours, during
weekends or during the winter months when general cooling is not needed.

The G-Volution EH Range units are designed to use such chilled water source when it
is available, but also have a direct expansion system to take over if it is not available.
Therefore lower cost chilled water can be used for most of the time, thus saving energy
costs, whilst the direct expansion system will ensure continuity and security when the
chilled water system is not required or is shut down for maintenance. The switching of
the system is control by the intelligent Genius 5+ controller to ensure seamless
operation of the units.

For sites with 2 independent chilled water sources, The EH Range unit can be fitted
with 2 independent chilled water systems. Both set of coils are having same capacity
to have 100% redundancy.

Double Skin Access Panel with Gasket Lining

The solid and rigid double skin insulated access panels on the G-Volution Series
ensure excellent sound isolation and greatly reduce the breakout noise of the unit. The
special FERMAPOR gasket on the door panels effectively eliminates air leakage from
the units. This gasket is applied to the door panels using a special machine to ensure
strong bonding between the gasket and the panels, thus increase the reliability of the
whole panel assembly.

Scroll Compressor

High efficiency hermetic scroll compressors provide reliability, quiet and superior
cooling performance. The compressors are perfect for the application of precision
cooling for data centers, laboratories and equipment rooms. All compressors are with
screw thread connection for easy service and maintenance.

2 Types of Fan Configuration

The G-Volution Series offer 2 types of fan configuration. High efficiency


Electronically Commutated (EC) Fan is offered as standard. Apart from increasing the
efficiency of the units, EC fan also enable various control strategies for data center
cooling such as underfloor pressure control and variable air flow control. For
downflow system, if the raise floor has sufficient height (>400mm), then the
efficiency of the unit can be further improved as much as 15% by locating the EC fan
below the raise floor. For underfloor EC fan option, the fans are located inside the
unit during transportation. After the unit is in position, the fans will be lower down to
underfloor. This has greatly simplified the installation process and also future service
and maintenance.
~2~
Electronic Expansion Valve

The innovative Electronic Expansion Valve (EEV) provides highly efficient control of
refrigerant flow base on real-time feedback. Unlike the conventional Thermostatic
Expansion Valve, the EEV can provide fast, stable and precise control even under low
load condition. The wide operating range of EEV allows the unit operate at lower
condensing pressure and thus increase the efficiency of the unit. The presence of the
temperature & pressure probe allows real time monitoring of suction temperature and
pressure as well as the superheat of the system. Problem such as refrigerant leakage
can be easily detected by checking the superheat & suction pressure from display.

Cooling Coils

Both chilled water coils and direct expansion coils are arranged in V-frame to allow
larger coil to be fitted in to the unit. Large coil face area allows more cooling capacity
at lower face velocity. Therefore, the unit can achieve better efficiency while at the
same time minimizing the air side pressure loss.

Hydrophilic fin provides additional protection to the coil and at the same time, ensure
fast removal of condensate on the coil. Thus, improves the heat transfer and
performance of the coil. Hydrophilic fin also reduce the air friction loss across the coil,
thus reduce the fan power requirement.

Modulating Ball Valves

Modulating ball valves with equal percentage characteristic is used to ensure excellent
control of water flow through the cooling coils. The flow characterised disc inside the
valve has greatly enhance the control stability especially under low load condition.
The standard valve is rated PN25 and has high closed-off pressure rating, therefore
suitable for wide range of operating condition.

Water Temperature Sensors

Inlet water temperature and outlet water temperature (optional) can be fitted to the
units to monitor the supply and return water condition. The inlet water temperature
sensor is responsible for the changeover control of the unit. If the water temperature
measurement exceeds the pre-set threshold, the system would changeover to direct
expansion operation. The unit would provide early warning if the incoming water is
out of the desired operating condition, thus enable early rectification actions and
prevent potential downtime.

Anti-Freeze Sensor

Chilled water coils and DX coils are attached to each other. In case the DX system
freeze due to system malfunction or refrigerant leak, the water inside the chilled water
coils might freeze and damage the tubes inside the coils. Therefore Anti-freeze
sensors are essential to provide protection to the chilled water coil and prevent major
downtime.

~3~
Heaters

Depends on models, single stage or multiple stages of PTC heating elements are
balanced over 3 phases and comes with safe dynamic self-regulating function. It
automatic controls the thermal power through air flow to eliminate the possibility of
overheating when air flow is low. It operates at a nearly constant temperature and fast
heat up promise an accurate control of temperature. Uniform heating without power
variation extend the life span of the elements. Proportional heating capacity is
available as an option via power regulators. All heaters are protected by thermal cut-
out switches. The heater may be interlocked with humidifier to reduce power
requirement when operating under power restricted area.

Electrical and Control Panel

High and low voltage cables are segregated and each component is protected by
individual MCB. AC3 components such as fan motors and compressors are protected
by manual motor starters. All cabling are colour coded and numbered for easy
reference.

Genius 5+ Controller

The latest Genius 5+ Controller provides intelligent and advance control for precision
cooling application. The G-Volution Series fitted with Genius 5+ controller, offered
highest flexibility and capability in mission critical cooling control, remote
monitoring and system integration. The Genius 5+ controller supports wide range of
cooling control strategies for mission critical facilities including auto-sequencing,
supply air control and containment system. Energy saving features such as EC fan
control, compressor and EEV optimization and intelligent humidity control are built-
in to the standard control program.

The Genius 5+ controller supports various communication protocols for remote


monitoring. The built-in RS485 communication port is ready for connecting to
Modbus system without needs of additional accessories. Other communication
protocols such as TCP/IP, BACnet and LonWorks are supported with additional
interface cards.

Touch Screen Display

Optional touch screen display provides informative and user-friendly interface for
easy navigation. The display can show graphical information via animated icons and
also capable of plotting trend graphs for temperature and humidity. The display can
support multiple languages such as English, Malay, Chinese, Thai and Japanese.

Humidity Control

The G-Volution Series offered 2 humidity control mode, i.e. the conventional RH
Control Mode and the ASHRAE TC9.9 compliance Dew Point Control Mode.

~4~
%
40
20 %
30
C
-° ASHRAE 2004 Recommendation
ure

Humidity Ratio - kg/kg


e rat
mp
Te 15
lb
t Bu 20%
We
10

5
10%

ASHRAE 2008 Recommendation

Dry Bulb Temperature - °C

RH Control Mode (Relative Humidity Control)

In RH Control Mode, room humidity is control in term of Relative Humidity (RH). As


RH is not directly reflexes the actual moisture content in the air, keeping constant RH
might involve adding and removing of moisture just because the change of
temperature instead of the variation in moisture content. These unintended processes
are causing unnecessary power consumption in data center cooling. However, this
humidity control mode shall be chosen for application where RH gives more impact
than the actual moisture content.

Dew Point Control Mode (Absolute Humidity Control)

Since year 2008, ASHRAE TC9.9 has specified recommended humidity in term of
dew point. It specified that the humidity level in data center environment should be
between 5.5°C and 15°C. To comply to the latest ASHRAE recommendation and also
to prevent the unnecessary humidifying and de-humidifying process. Dew Point
Control Mode is preferred over the conventional RH Control Mode.

~5~
NOMENCLATURE

E H D 60 A E

E - G-Volution Series
E ± EC Fans
H ± Dual Coil System U ± Underfloor EC Fans

D - Downflow
U - Upflow A - Air Cooled + Chilled Water
W - Water cooled + Chilled Water
C - Chilled Water + Chilled Water
Model - Nominal
Capacity in kW

~6~
AIR FLOW ARRANGEMENT

Type A:
Upflow unit, top discharge into ceiling
or duct with front return.

Type B:
Upflow unit, with horizontal discharge
plenum. Front return.

Type C:
Upflow unit, top discharge into ceiling
or duct. Bottom return.

~7~
Type D:
Downflow unit, discharge into raise
floor. Top return.

Type E:
Downflow unit, with bottom discharge
plenum. Top return.

Type F:
Downflow unit, with underfloor EC
Fans. Top return.

~8~
DIMENSION & WEIGHT

EH Range ³A/W Version´

Model 60 70 85 95
Gross Weight (kg): A Version 802 898 1010 1098

Gross Weight (kg): W Version 817 918 1030 1128

~9~
EH Range ³C Version´

Model 60 70 85 95
Gross Weight (kg) 535 625 885 965

~ 10 ~
GUIDE SPECIFICATION

Cabinet and Frame Construction

The frame shall be constructed of 2mm steel for strength and durability. The exterior
panels shall be powder coated with a textured finish and shall be insulated with a
minimum 1 inch (25.4mm) thick PE foam insulation with minimum 40kg/m3 density
lined with aluminium foil rated to class O rating. All front panels shall have double
skinned construction with FERMAPOR gasket for better sound proofing and thermal
insulation. All front panels shall be locked with compression latches to prevent
unauthorized access. All front panels shall be provided with removable hinge to allow
easy access for installation and maintenance.

Air Filtration

The air filters shall be located within the cabinet of the unit and shall be serviceable
from the front of the unit. The filters shall be rated not less than 30% efficiency
(based on ASHRAE 52.1) or MERV 8 (based on ASHRAE 52.2) and shall be of
100mm depth. A differential pressure switch shall be fitted to indicate the filters need
changing through a service alarm from the controller.

Electric Reheat

Electrical heaters shall be provided in one or two stages depend on models. The PTC
heating elements shall be made of PTC thermistor and aluminium fin housing with
safe dynamic self-regulating function. The heating elements shall include a high
temperature safety cut-out. Heater may be interlocked with humidifier (if present) to
prevent simultaneous operation for sites with limited power supply.

Refrigeration Circuit

Standard Compressor

The refrigeration system shall be of direct expansion type and shall utilize high
efficiency hermetic scroll compressors. The system shall include high pressure and
low pressure protection for the compressor, a sight glass with moisture indicator, an
Electronic Expansion Valve (EEV) and a high capacity filter drier. The compressor
shall be fitted with thread connection for easy disassembly when replacement is
necessary without the need for brazing. The EEV shall have PID modulation control
and is capable of reacting quickly to system changes in order to ensure a stable
superheat. A pressure transducer and a temperature sensor shall be provided on the
low side to monitor evaporating pressure and superheat, which allows easy
monitoring of the system performance without additional tools.

DC Inverter Compressor Option

The refrigeration system shall be of direct expansion type and shall be fitted with high
efficiency DC inverter variable speed hermetic scroll compressors. Each refrigeration
circuit shall include high pressure and low pressure protection for the compressor, a
~ 11 ~
sight glass with moisture indicator, an Electronic Expansion Valve (EEV) and a high
capacity filter drier. The compressor shall be fitted with thread connection for easy
disassembly when replacement is necessary without the need for brazing. The EEV
shall have PID modulation control and is capable of reacting quickly to system
changes in order to ensure a stable superheat. A pressure transducer and a temperature
sensor shall be provided on the low side to monitor evaporating pressure and
superheat, which allows easy monitoring of the system performance without
additional tools.

Dehumidification

Dehumidification cycle shall be via different superheat control setting of the


electronic expansion valve. During dehumidification, the evaporating temperature of
the coil is reduced to provide better moisture removal capability to the evaporator coil
and at the same time, reduce the cooling capacity and thus reduce the need for reheat.
Full air flow shall be maintained at all times to ensure consistent air distribution to the
conditioned space.

Fans

Electronically Commutated (EC) Fan (Standard)

Fans shall be of backward curved plug fan type which is direct-driven by an


Electronically Commutated (EC) motor. The EC fan shall be capable of variable
speed control without use of VFD and can be set by the user to operate within a
certain range of fan speed and shall also be capable of being set to automatically
adjust its fan speed according to the air temperature of the room to provide energy
saving during periods of low load.

Alternatively, it should also be possible to automatically regulate the fan speed to


maintain a certain level of positive pressure in the room. User should be able to
override and manually set the fan speed if required.

The EC fan should be capable of ramping slowly to the desired speed & shall not have
any high inrush current. The fan shall be accessible from the front of the unit and be
of draw through type located after the cooling coil to ensure even air distribution and
maximum coil performance. A differential pressure switch shall be provided to detect
air flow failure.

Underfloor EC Fan (Option, Downflow Models Only)

Fans shall be of backward curved plug fan type which is direct-driven by an


Electronically Commutated (EC) motor. Fans shall be pre-wired and placed within the
unit for delivery, ready to be lowered into position at site. Fan mounting assembly
shall be enclosed and provided with a perforated plate to prevent any accidental direct
contact with the fan when it is in operation.

The EC fan shall be capable of variable speed control without use of VFD and can be
set by the user to operate within a certain range of fan speed and shall also be capable

~ 12 ~
of being set to automatically adjust its fan speed according to the air temperature of
the room to provide energy saving during periods of low load.

Alternatively, it should also be possible to automatically regulate the fan speed to


maintain a certain level of positive pressure in the room. User should be able to
override and manually set the fan speed if required.

The EC fan should be capable of ramping slowly to the desired speed & shall not have
any high inrush current. The fan shall be accessible from the front of the unit and be
of draw through type located after the cooling coil to ensure even air distribution and
maximum coil performance. A differential pressure switch shall be provided to detect
air flow failure.

Cooling Coil

The cooling coils shall be V-frame coils with draw through air design for uniform air
distribution & superior heat transfer. Coil for direct expansion system shall be
constructed of inner grooved copper tubes and corrugated aluminium fins while
chilled water system shall be constructed of plain copper tubes and corrugated
aluminium fins. All coils shall have hydrophilic coating for better water removal and
improved heat transfer. The cooling coil shall be a maximum of 4 rows and 12 fins
per inch and face velocity shall not exceed 2.5m/s. Condensate tray for the cooling
coil shall be made of stainless steel.

2-Way Chilled Water Control Valve

The chilled water circuit shall include a 2-way modulating valve and actuator with
manual override facility. Cooling capacity shall be controlled by modulating the
volume of chilled water into the cooling coil via the modulating valve. The valve shall
be equal percentage characterised ball valve in order to have better control stability.
The controller shall position the valve opening in response to return air or supply air
condition.

Inlet Water Temperature Sensor

A water temperature sensor shall be placed at the chilled water inlet piping to detect
incoming chilled water temperature. An alarm signal shall be raised if the chilled
water temperature is above a user defined setpoint. Upon issuing alarm, the system
shall switch over to direct expansion mode for continuous operation.

Anti-Freeze Sensor (For ³A/W Version´ Only)

Anti-freeze sensor shall be fitted to the unit to prevent direct expansion coils from
freezing. Upon detecting the possibility of coil freeze, the control system shall cut off
the compressors to prevent damage occurred to the chilled water coils.

~ 13 ~
Air Cooled Condenser (For ³A Version´ Only)

Air Cooled condenser shall incorporate high efficiency direct driven axial fan with
external rotor motors with IP54 enclosure rating and class F insulation. The condenser
body shall be of powder coated steel for corrosion protection and all components used
shall be weatherproof and suitable for outdoor operation. Condenser coil shall be
constructed of rifled copper tube with corrugated aluminium fins. The condenser shall
be capable of either vertical or horizontal air discharge to suit site space limitations.
The condenser shall operate on power supply provided from the indoor unit and
include an isolation switch.

Water Cooled Condenser (For ³W Version´ Only)

Unit shall include a brazed plate type heat exchanger that operates as the condenser
and a liquid receiver to hold the refrigerant charge, including all refrigerant pipework
to the condenser. Water Cooled models are supplied with a nitrogen holding charge
and isolation valves shall be field supplied and fitted by others. A strainer must be
installed on the supply side of the water circuit to the condenser by the contractor/
installer to prevent entry of impurities into the heat exchanger.

Electrical and Control Cabinet

High voltage compartment shall contain contactors, miniature circuit breakers,


transformer and terminal isolator while the low voltage section shall include the
controller, EEV driver and all other additional add-on control interface and terminal
blocks. Each component shall be protected by an individual MCB while fan motor
and compressors shall be protected by motor starters. Low voltage circuit shall be
protected by fuse. All high and low voltage cables shall be segregated and placed in
cable trunking. All cabling shall be colour coded and numbered for easy referencing.

Microprocessor Control System with LCD Display

a) The control system shall be able to maintain the temperature and humidity to a
tolerance of ±1.0°C and ±5 %RH.
b) The control system shall have a fascia with 132 x 64 pixel resolution LCD display
located on the front panel of the unit for display and programming functions. The
display shall show current modes of operation, current return air temperature and
relative humidity, target set point temperature & relative humidity as well as the
evaporating pressure and superheat of each refrigeration circuit for each
troubleshooting and commissioning.
c) System configuration and setting shall be stored in non-volatile memory and
safeguard in the event of power failure.
d) The system shall have at least three levels of programmable password access to
prevent any unauthorized changes of the system configurations.
e) The system shall have programmable selections: manual or automatic restart
option. A programmable start-up delay shall be provided for the automatic restart
option which allows multiple units to restart progressively when power resumes
after a power failure.

~ 14 ~
f) The accumulated run time of the following components shall be logged.
1. Fan
2. Heater
3. Compressor
4. Humidifier
g) Components shall be scheduled to activate sequentially to minimize inrush current.
h) The control system shall have but not limited to the following alarms.
1. High / low temperature
2. High / low humidity
3. Filter clogged
4. Compressor low pressure
5. Compressor high pressure
6. Loss of air flow
7. Water in high temperature (Water-cooled unit Only)
8. Heater overheat
9. Humidifier fault (if humidifier present)
10. Humidifier cylinder change (if humidifier present)
11. Drip tray full (if water detection option present)
12. Water on floor (if water detection option present)
i) When an alarm condition exists, the common alarm output shall be energized until
acknowledged. Active alarm record shall remain until the alarm condition is
cleared.
j) A historical event log shall record up to 100 alarm events. The text description
and occurrence time of the all alarms shall be logged and shall be displayed in
order of occurrence for ease of troubleshooting.
k) The units shall have built-in master and slave inter-networking capability and
auto-sequencing which allow a combination of all units to form a local area
network. The control of a slave unit shall not be limited to any particular master
unit. In case of a master unit failure, the remaining units in the same network shall
automatically take over the control and act as master unit.
l) The controller shall be compatible with most remote monitoring and control
devices. Controller shall have built-in RS485 port ready for Modbus connection.
Options shall be available for other BMS interface via BACnet, LonWorks and
SNMP.

~ 15 ~
OPTIONS ʹ GUIDE SPECIFICATION

Humidifier

Humidification shall be via an electrode boiler type humidifier with disposable


cylinder complete with feed and drain valves and overflow indicator. The humidifier
control shall include proportional steam output and an auto flush cycle, which is user
adjustable from the front display. Power supply shall be disconnected from the
electrodes when humidifier is in drain mode to prevent earth leakage.

Serviceable Humidifier

Humidification shall be via an electrode boiler type humidifier complete with feed
and drain valves and overflow indicator. The humidifier cylinder shall be serviceable
with cleanable electrodes. The humidifier control shall include proportional steam
output and an auto flush cycle, which is user adjustable from the front display. Power
supply shall be disconnected from the electrodes when humidifier is in drain mode to
prevent earth leakage.

Water Detection Kits

Water level sensors shall be located at the condensate tray to detect undue water
levels at the drain pan. A water sensing tape shall also be provided (supplied loose
with sufficient length to cover entire length of the respective unit) to detect presence
of water on the floor. When water is detected, an alarm shall be triggered and user
may set to stop or continue unit operation.

Fan Speed Control (IRU³A Version´ Only)

Air Cooled condenser shall be equipped with fan speed control. The fan speed
controller shall include a high side pressure transducer and electronic fan speed
control module at the indoor unit. The control module shall regulate the fan speed
based on the condensing pressure and the control setpoint by regulating the voltage to
the fan.

3-Way Chilled Water Control Valve

The chilled water circuit shall include a 3-way modulating valve and actuator with
manual override facility. Cooling capacity shall be controlled by modulating the
volume of chilled water into the cooling coil via the modulating valve. The valve shall
be equal percentage characterised ball valve in order to have better control stability.
The controller shall position the valve opening in response to return air or supply air
condition.

Outlet Water Temperature Sensor

A water temperature sensor shall be placed at the chilled water outlet piping to
monitor the leaving chilled water temperature. The temperature reading shall be
shown on the unit display and can be logged for graph trending.
~ 16 ~
Horizontal Discharge Section (Upflow Unit Only)

Horizontal discharge section shall consist of a double deflection grille fitted into a
rigid sheet metal box. The complete assembly shall be bolted to the top of the unit on
site. The grille shall have two sets of blades, which allow for both vertical and
horizontal directional adjustment of air flow. The standard height for this section shall
be 500mm.

Ceiling Discharge Section (Upflow Unit Only)

The ceiling discharge section shall consist of rigid riveted sheet metal assembly
comprising of unit matched front, rear and end panels lined with 25mm thick
insulation. The extension shall be bolted to the top of the unit on site. The section
height shall be suitable for the distance between the top of the unit and the underside
of the suspended ceiling. The overall height of the section shall be this dimension plus
50mm.

Ceiling Return Duct (Downflow Unit Only)

Ceiling return duct shall comprise of unit matched panels lined with 25mm thick
insulation bolted to the top of the unit on site. The height of the duct shall be suitable
for the distance between the top of the unit and the underside of the suspended ceiling.
The overall height of the duct shall be this dimension plus 50mm.

High Efficiency Filter

The air filters shall be located within the cabinet of the unit and shall be serviceable
from the front of the unit. The filters shall be rated not less than 80% efficiency
(based on ASHRAE 52.1) or MERV 13 (based on ASHRAE 52.2) and shall be of
100mm depth. A differential pressure switch shall be fitted to indicate the filters need
changing through a service alarm from the controller. Air filter shall be of disposable
type & with cardboard frame.

Differential Pressure Transmitter for Underfloor Pressure Control

Differential Pressure Transmitter shall be used to detect pressure difference between


the room and the underfloor in order to maintain a constant differential pressure when
using EC fan. The EC fan shall regulate its speed in order to maintain the pre-set
differential pressure. This differential pressure setting shall be set via the controller
display interface.

Fire Alarm Relay

A 24VDC relay shall be provided to receive an external signal from the fire control
panel or detection system. When the external signal is received, the unit shall stop
operation.

~ 17 ~
Supply Temperature and Humidity Sensor

An additional Temperature and Humidity Sensor shall be provided to measure the


supply air condition of the unit. User shall be able to set to either control the unit via
supply air condition or return air condition.

Water Regulating Valve (For ³W Version´ Only)

Water Cooled units shall incorporate 2-way water regulating valve to controls the
condensing pressure of the system by regulating water flow to the plate heat
exchanger.

Compressor Crankcase Heater

The compressors shall be fitted with crankcase heaters to prevent refrigerant


migration and oil mixing when the compressors are off. The crankcase heaters shall
be turned off when the units are not running.

Wooden Crate

A plywood and timber enclosure shall be provided to protect the unit from damage
during transportation to site.

Automatic Transfer Switch (ATS)

ATS shall be provided to handle the transfer of incoming power source for dual power
system. The ATS shall be factory installed and wired and integrated the switching
signal to the controller.

Microprocessor Control System with Touch Screen Display

a) The control system shall be able to maintain the temperature and humidity to a
tolerance of ±1.0°C and ±5 %RH.
b) The control system shall have a fascia with 480 x 272 pixel resolution TFT touch
screen graphical display located on the front panel of the unit for display and
programming functions. The display shall show current modes of operation,
current return air temperature and relative humidity, target set point temperature &
relative humidity as well as the evaporating pressure and superheat of each
refrigeration circuit for each troubleshooting and commissioning.
c) System configuration and setting shall be stored in non-volatile memory and
safeguard in the event of power failure.
d) The system shall have at least three levels of programmable password access to
prevent any unauthorized changes of the system configurations.
e) The display shall have multi language support with option to select between
English, Malay, Chinese, Japanese and Thai languages.
f) The system shall have a temperature and humidity graph which shows data up to 4
weeks duration. The data of the graph shall be logged in one minute intervals. An
option to show the temperature graph of the chilled water system (inlet and outlet
if applicable) shall be available.

~ 18 ~
g) The system shall have programmable selections: manual or automatic restart
option. A programmable start-up delay shall be provided for the automatic restart
option which allows multiple units to restart progressively when power resumes
after a power failure.
h) The accumulated run time of the following components shall be logged.
a. Fan
b. Heater
c. Compressor
d. Humidifier
i) Components shall be scheduled to activate sequentially to minimize inrush current.
j) The control system shall have but not limited to the following alarms.
a. High / low temperature
b. High / low humidity
c. Filter clogged
d. Compressor low pressure
e. Compressor high pressure
f. Loss of air flow
g. Water in high temperature
h. Heater overheat
i. Humidifier fault (if humidifier present)
j. Humidifier cylinder change (if humidifier present)
k. Drip tray full (if water detection option present)
l. Water on floor (if water detection option present)
k) When an alarm condition exists, the common alarm output shall be energized until
acknowledged. Active alarm record shall remain until the alarm condition is
cleared.
l) A historical event log which maintains the latest events of up to 4 weeks shall be
provided. The text description and occurrence time of the all alarms shall be
logged and shall be displayed in order of occurrence for ease of troubleshooting.
m) The units shall have built-in master and slave inter-networking capability and
auto-sequencing which allow a combination of all units to form a local area
network. The control of a slave unit shall not be limited to any particular master
unit. In case of a master unit failure, the remaining units in the same network shall
automatically take over the control and act as master.
n) The controller shall be compatible with most remote monitoring and control
devices. Controller shall have built-in RS485 port ready for Modbus connection.
Options shall be available for other BMS interface via BACnet, LonWorks and
SNMP.

~ 19 ~
REMOTE MONITORING AND SUPERVISORY SYSTEM

Several remote monitoring, control and supervisory systems are available as add-ons
to the controller to enable user to access data and make settings changes to the units
without having to be physically present in front of the unit.

WebGate

To connect controller to a local network based on standard Ethernet & TCP/IP


protocol. The device functions as a web server with a fixed IP which can be accessed
via a LAN or through the Internet.

pCOWeb

Allows communication between controller with BACnet Ethernet, BACnet over IP,
SNMP protocol (v1 & v2c), HTTP protocol, FTP and DHCP protocol. The device
functions as a web server with a fixed IP which can be accessed via a LAN or through
the Internet.

pCOnet

Allows communication with BACnet MS/TP protocol.

LonWorks Interface Card

Allows controller to interface directly with a LonWorks network.

G-Visor

Manage CRAC operation to optimise cooling efficiency.

Notes:
1. For more detailed information on these options, please refer to the Genius Controller Engineering Data.
2. Please note that certain combinations of options are not available with other options while other combinations
might require further upgrades or additional accessories to be added. To check whether a certain combination
of options is available, please consult factory. For availability of other special options & accessories not listed
above, please also check with factory.

~ 20 ~
TECHNICAL DATA

EH Range ³$/W Version´


Unit Model 60 70 85 95
Direct Expansion Circuit
Gross Total Capacity (Downfow/Upflow) kW 64.16/63.47 75.13/74.12 84.24/83.16 98.27/96.54
Gross Sensible Capacity (Downflow/Upflow) kW 55.92/54.72 67.10/65.16 77.65/75.58 91.72/87.73
S.H.R. (Downflow/Upflow) 0.87/0.86 0.89/0.88 0.92/0.91 0.93/0.91
Chilled Water Circuit
Gross Total Capacity (Downfow/Upflow) kW 61.77/59.80 74.50/70.99 91.62/87.77 102.09/95.37
Gross Sensible Capacity (Downflow/Upflow) kW 54.75/53.04 66.63/63.62 80.81/77.57 92.75/86.64
S.H.R. (Downflow/Upflow) 0.89/0.89 0.89/0.90 0.88/0.88 0.91/0.91
General Data
Nominal Air Flow (Downflow/Upflow) m³/s 4.2/4.1 5.2/5.0 6.2/6.0 7.5/7.0
No. of Fan(s) 2 2 3 3
No. of Compressor(s) 2 2 2 2
No. of Refrigerant Circuit(s) 2 2 2 2
Sound Level dBA 67 67 68 68
Condenser
Nominal Air Cooled Condenser HEC 2 x 374 2 x 374 2 x 574 2 x 574
Nominal Water Cooled Model 2 x WB60 2 x WB80 2 x WB80 2 x WB80
Nominal Water Flow (Downflow/Upflow) l/s 3.72/3.69 4.34/4.29 4.84/4.80 5.65/5.57
Waterside P.D. of Condenser (Downflow/Upflow) kPa 24.7/24.3 24.0/23.6 29.9/29.4 40.7/39.7
Chilled Water Coil
Nominal Water Flow (Downflow/Upflow) l/s 2.95/2.86 3.56/3.39 4.38/4.19 4.88/4.56
Water P.D. (Downflow/Upflow) kPa 99.7/99.3 68.5/65.2 110.3/106.2 84.4/77.0
Electric Re-heater
Nominal Heater Capacity kW 12 12 12 12
No. of Heater Step(s) 2 2 2 2
Electrode Humidifier
Nominal Humidifier Capacity kg/hr 5 5 5 8
Air Filter
Type G4, MERV8, Disposable
Downflow: WxHxD (Qty) mm 421x800x100(3) 504x800x100(3) 444x800x100(4) 504x800x100(4)
633X582X100(2) 540X582X100(4)
Upflow: WxHxD (Qty) mm 633X582X100(4) 633X582X100(6)
384X582X100(4) 633X582X100(2)
Unit Piping Connection
Discharge 7/8" x 2 7/8" x 2 7/8" x 2 1 1/8" x 2
Liquid 5/8" x 2 5/8" x 2 3/4" x 2 3/4" x 2
Chilled Water Pipe mm 54 54 54 54
Drain mm 22 22 22 22
Humidifier Feed 3/4" G(M) 3/4" G(M) 3/4" G(M) 3/4" G(M)
Humidifier Drain mm 32 32 32 32
Condenser Water In/Out mm 54 54 54 54
Unit Dimension
Width mm 2050 2300 2565 2800
Depth mm 991 991 991 991
Height mm 1985 1985 1985 1985
Min. Service Allowance mm 725 725 725 725

Notes:
1. Cooling capacity is based on 24ºC, 45%RH, R407C refrigerant, 45ºC condensing temperature for DX system, chilled water in/out based on
7/12ºC, 400V/3ph/50Hz power supply, 50Pa ESP.
2. Sound level is for downflow models measured at 1m in free ¿eld conditions.
3. Nominal air cooled condenser sizing is suggestion only based on 35ºC ambient & nominal operating condition. Other sizes may be selected to
suit requirement as necessary.
4. Nominal water cooled condenser sizing is based on 30/35ºC condensing water & nominal operating condition. Other sizes may be selected to suit
requirement as necessary.
5. Only EC fan is available.
6. For underfloor EC fan option, raise floor height must be >400mm.

~ 21 ~
EH Range ³& Version´

Unit Model 60 70 85 95
Gross Total Capacity - Downflow kW 60.16 72.79 90.08 96.94
Gross Sensible Capacity - Downflow kW 53.68 65.49 79.77 88.47
S.H.R. 0.89 0.90 0.89 0.91
Gross Total Capacity - Upflow kW 58.23 69.34 86.28 91.42
Gross Sensible Capacity - Upflow kW 51.99 62.51 76.55 83.44
S.H.R. 0.89 0.90 0.89 0.91
General Data
Nominal Air Flow - Downflow m³/s 4.2 5.2 6.2 7.2
Nominal Air Flow - Upflow m³/s 4.1 5.0 6.0 6.8
No. of Fan(s) 2 2 3 3
Sound Level dBA 67 67 68 68
Chilled Water Coil
Nominal Water Flow (Downflow/Upflow) l/s 2.87/2.78 3.48/3.31 4.30/4.12 4.63/4.37
Waterside P.D. (Downflow/Upflow) kPa 92.1/91.6 63.8/60.6 104.3/100.3 75.4/70.0
Electric Re-heater
Nominal Heater Capacity kW 12 12 12 12
No. of Heater Step(s) 2 2 2 2
Electrode Humidifier
Nominal Humidifier Capacity kg/hr 5 5 5 8
Air Filter
Type G4, MERV8, Disposable

Downflow: WxHxD (Qty) mm 421x800x100(3) 504x800x100(3) 444x800x100(4) 504x800x100(4)

633X582X100(2) 540X582X100(4)
Upflow: WxHxD (Qty) mm 633X582X100(4)
384X582X100(4) 633X582X100(2)
633X582X100(6)

Unit Piping Connection


Water In/Out mm 54 54 54 54
Drain mm 22 22 22 22
Humidifier Feed 3/4" G(M) 3/4" G(M) 3/4" G(M) 3/4" G(M)
Humidifier Drain mm 32 32 32 32
Unit Dimension
Width mm 1550 1800 2065 2300
Depth mm 991 991 991 991
Height mm 1985 1985 1985 1985
Min. Service Allowance mm 725 725 725 725

Notes:
1. Cooling capacity is based on 24ºC, 45%RH, Chilled Water in/out based on 7/12ºC, 50Hz, 50Pa ESP.
2. Sound level is for downflow models measured at 1m in free ¿eld conditions.
3. Only EC fan is available.
4. For underfloor EC fan option, raise floor height must be >400mm.

~ 22 ~
RECOMMENDED PIPE SIZE

EH Range ³A Version´

Recommended Discharge Pipe Size


Equi. Length Model 60 70 85 95
10m All 7/8" 7/8" 7/8" 1 1/8"
20m All ´ 7/8" 1 1/8" 1 1/8"
30m All ´ 1 1/8" 1 1/8" 1 1/8"
Hor. 1 1/8" 1 1/8" 1 1/8" 1 1/8"
40m
Vert. ´ 1 1/8" 1 1/8" 1 1/8"
Hor. 1 1/8" 1 1/8" 1 1/8" 1 3/8"
50m
Vert. ´ 1 1/8" 1 1/8" 1 1/8"
Hor. 1 1/8" 1 1/8" 1 1/8" 1 3/8"
60m
Vert. 7/´ 1 1/8" 1 1/8" 1 1/8"
Hor. 1 1/8" 1 1/8" 1 3/8" 1 3/8"
70m
Vert. ´ 1 1/8" 1 1/8" 1 1/8"
Recommended Liquid Pipe Size
Equi. Length Model 60 70 85 95
10m All 5/8" 5/8" 3/4" 3/4"
20m All 5/8" 5/8" 3/4" 3/4"
30m All 5/8" 3/4" 3/4" 3/4"
40m All 3/4" 3/4" 3/4" 3/4"
50m All 3/4" 3/4" 3/4" 7/8"
60m All 3/4" 3/4" 7/8" 7/8"
70m All 3/4" 7/8" 7/8" 7/8"

~ 23 ~
ELECTRICAL DETAIL

EH Range ³A/W Version´

Unit Model 60 70 85 95

Operating Current A 35.4 39.3 43.9 56.6


Operating Power kW 18.3 20.5 23.5 28.3
With Humidifier:
Rated Load Amps A 52.7 57.9 63.8 83.8
Max. Inrush Amps A 159.2 162.4 207.4 252.1
Rated Load kW kW 31.5 35.0 37.9 47.9
Without Humidifier:
Rated Load Amps A 46.2 50.8 56.8 72.5
Max. Inrush Amps A 152.8 155.4 200.4 240.8
Rated Load kW kW 29.1 31.2 33.0 40.1

Notes:
1. Operating current and power stated for unit running in cooling mode under nominal conditions.
2. Unit rated load power and current is calculated based on worst possible combination of components operating at the
same tLPH8QLWDVVXPHGWRKDYHQRPLQDOKHDWHUDQGKXPLGL¿HU
3. Power and current for heat rejection equipment is not included.
4. Electrical data is based on 400V/3ph/50Hz power supply.

EH Range ³C Version´

Unit Model 60 70 85 95
Operating Current A 8.0 8.9 9.0 11.8
Operating Power kW 3.5 3.7 4.7 5.7
With Humidifier:
Rated Load Amps A 34.8 35.9 35.9 43.4
Max. Starting Amps A 14.0 15.8 15.8 20.9
Rated Load kW kW 23.2 23.9 23.9 28.6
Without Humidifier:
Rated Load Amps A 27.8 28.9 28.9 32.1
Max. Starting Amps A 14.0 15.8 15.8 20.9
Rated Load kW kW 18.3 19.0 19.0 20.8

Notes:
1. Operating current and power stated for unit running in cooling mode under nominal conditions.
2. Unit rated load power and current is calculated based on worst possible combination of components operating at the same
WLPH8QLWDVVXPHGWRKDYHQRPLQDOKHDWHUDQGKXPLGL¿HU
3. Power and current for heat rejection equipment is not included.
4. Electrical data is based on 400V/3ph/50Hz power supply.

Due to our policy of continues development aQGLPSURYHPHQWWKHVSHFL¿FDWLRQVDQGGDWDKHUHLQDUHVXEMHFWWRFKDQJHZLWKRXWSULRU


notice. We must therefore reserve the right to supply equipment that may differ from that described and illustrated herein. All
information, including illustrations, contained in this brochure, is believed to be accurate and reliable. Users, however, should
independently evaluate the suitability of each product for their own application. CITEC makes no warranties as to the accuracy or
completeness of the information, and disclaims any liability regarding its use.

~ 24 ~