EPI-BUS devices

8.7 B5-EPI-PCM partial indication and control map


Via the Extended Bus (EPI-BUS) by means of a patch cable and an
8-pin RJ45 plug, the partial indication and control map can be con-
nected to any SecuriFire MIC11 / MIC711 as well as to the B5-MMI-
FIP and B5-MMI-IPS devices.
Additional EPI devices can be connected to the second RJ45.
The B5-EPI-PCM is mounted either on the door of the SecuriFire or
immediately next to a remote SecuriFire indication and control
map.
Via the hex coding switch you can set one of the three possible
EPI-BUS addresses. For each MMI-BUS participant with an EPI-
BUS interface, up to three EPI devices can be connected.
More information about the B5-EPI-PCM can be found in the Tech-
nical Description T 811 085.

Fig. 102 B5-EPI-PCM

8.7.1 Interfaces
EPI Port A “INCOMING”
EPI Port B “OUTGOING”
Designation Terminal Terminal Designation Notice
GNDP 1 2 VP
From which side the EPI bus “INCOMING” or
EXTBUS+ 3 4 EXTBUS-
“OUTGOING” is connected is not relevant.
+3V3 5 6 +3V3
GNE 7 8 GND
For purposes of clarity, however, we recommend
continuing with one connection system once be-
gun.
8.7.2 Technical data
Operating voltage: 3.3 V
Quiescent current: 5 mA
Data transmission: EPI bus
Electrical: RS485
Distance to the MIC main indication and control map: max. 1 m
Protection class: IP30
Ambient temperature: -5°C to +50°C
Dimensions: 170 x 138 x 48 mm (W x H x D)
Dimensions without map case: 85 x 70 x 20 mm (W x H x D)
Map case colour: grey

8.7.3 Compatibility information


SecuriFire Studio from release 1.2
EPI interface B5-MIC (all versions), B6-MIC (all versions)
B5-MMI-FIP, B5-MMI-IPS

80 / 128 Mounting and installation, Technical Description, T 811 086 en e


EPI-BUS devices

8.8 B5-EPI-PIM partial indication map


Via the Extended Bus (EPI-BUS) by means of a patch cable and an
8-pin RJ45 plug, the partial indication map can be connected to any
SecuriFire MIC11 / MIC711 as well as to the B5-MMI-FIP and B5-
MMI-IPS devices.
Additional EPI devices can be connected to the second RJ45.
The B5-EPI-PIM is mounted either on the door of the SecuriFire or
immediately next to a remote SecuriFire indication and control
map.
Via the hex coding switch you can set one of the three possible
EPI-BUS addresses. For each MMI-BUS participant with an EPI-
BUS interface, up to three EPI devices can be connected.
More information about the B5-EPI-PCM can be found in the Tech-
nical Description T 811 084.

Fig. 103 B5-EPI-PIM

8.8.1 Interfaces
EPI Port A “INCOMING”
EPI Port B “OUTGOING”
Designation Terminal Terminal Designation Notice
GNDP 1 2 VP
From which side the EPI bus “INCOMING” or
EXTBUS+ 3 4 EXTBUS-
“OUTGOING” is connected is not relevant.
+3V3 5 6 +3V3
GNE 7 8 GND For purposes of clarity, however, we recommend
continuing with one connection system once be-
gun.
8.8.2 Technical data
Operating voltage: 3,3 V
Quiescent current: 5 mA
Data transmission: EPI-BUS
Electrical: RS485
Distance to the MIC main indication and control map: max. 1 m
Protection class: IP 30
Ambient temperature: -5 °C to +50 °C
Dimensions: 170 x 138 x 48 mm (W x H x D)
Dimensions without map case: 85 x 70 x 20 mm (W x H x D)
Map case colour: grey

8.8.3 Compatibility information


SecuriFire Studio from release 1.2
EPI interface B5-MIC (all versions), B6-MIC (all versions)
B5-MMI-FIP, B5-MMI-IPS

Mounting and installation, Technical Description, T 811 086 en e 81 / 128