● The need for multiple pipe reduction is usually eliminated. aperture in the disc. The increase in flow as the valve is opened is very
slow and controlled.
● Better control prevents “hunting” of the control loop, increasing
This produces better part-load behavior and improved stability of
life span of actuator and valve.
control while also optimizing energy consumption.
FEATURES
1
Feature / Benefits
Characterized Control Valves™ (CCV)
B2 Series Two-way ½” to 3”
B3 Series Three-way ½” to 2”
Mixing*/Diverting
2
Sizing/Selection
Characterized Control Valves™ (CCV)
2-Way Valve Flow Rate for Water Applications (Gallons Per Minute, GPM)
120 2” 50 B253 120 170 208 240 268 294 318 339 360 380
240 2” 50 B254* 240 339 416 480 537 588 635 679 720 759
60 2½” 65 B261 60 85 104 120 134 147 159 170 180 190
75 2½” 65 B262 75 106 130 150 168 194 198 212 225 237
110 2½” 65 B263 110 156 191 220 246 269 291 311 330 348
150 2½” 65 B264 150 212 260 300 335 367 397 424 450 474
210 2½” 65 B265* 210 297 364 420 470 514 556 594 630 664
70 3” 80 B277 70 99 121 140 157 172 185 198 210 221
130 3” 80 B278 130 194 225 260 290 318 344 368 390 411
170 3” 80 B280* 170 240 294 340 380 416 450 481 510 538
70 2½” 65 B6250S-070 70 99 121 140 157 171 185 198 210 221
110 2½” 65 B6250S-110 110 156 191 220 244 266 282 296 312 320
110 3” 80 B6300S-110 110 156 191 220 244 266 282 296 312 320
186 4" 100 B6400S-186 186 263 322 372 416 456 492 526 558 588
290 5" 125 B6500S-290 290 410 502 580 648 710 767 820 870 917
400 6" 150 B6600S-400 400 566 693 800 894 980 1058 1131 1200 1265
GPM = Cv x ∆p
*Models with no characterizing disc.
The influence of the pipe geometry due to reduced flow is negligible for all valves 57 Cv and below with characterizing discs.
3
Sizing/Selection
Characterized Control Valves™ (CCV)
3-Way Valve Flow Rate for Water Applications (Gallons Per Minute, GPM)
4
Set-up and Wiring Instructions
Characterized Control Valves™ (CCV)
SET-UP
2-WAY VALVE 3-WAY VALVE
SPECIFY UPON ORDERING SPECIFY UPON ORDERING
TR24-SR-T US NC: Closed A to AB, will NO: Open A to AB, will close NC: Closed A to AB, will NO: Open A to AB, will close
TR24-SR US open as voltage increases. as voltage increases. open as voltage increases. as voltage increases.
Proportional (Can be chosen with (Can be chosen with
Type Actuators switch inside terminal switch inside terminal
block of actuator.) block of actuator.)
LRB24 (-3), MFT, SR Power to pin 2 will drive NO: Open A to AB, will close Power to pin 2 will drive NO: Open A to AB, will close
LRX24 (-3), MFT, SR valve CW. Power to pin 3 as voltage increases or valve CW. Power to pin 3 as voltage increases or
ARB24 (-3), MFT, SR will drive valve CCW. The power applied. (Can be will drive valve CCW. The power applied. (Can be
ARX24 (-3), MFT, SR above will function when chosen with CW/CCW above will function when chosen with CW/CCW
Floating Point or the directional switch is in switch.) the directional switch is in switch.)
Proportional Type Actuators the “1” position, to reverse the “1” position, to reverse
select the “0” position. select the “0” position.
TFRB24 NO/FO Valve: Open A to AB NC/FC Valve: Closed A to AB NO/FO Valve: Open A to AB NC/FC Valve: Closed A to AB
LF24 US will drive closed. will drive open. will drive closed. will drive open.
AFRB24 Spring Action: Spring Action: Spring Action: Spring Action:
Will spring open A to AB Will spring closed A to AB Will spring open A to AB Will spring closed A to AB
upon power loss. upon power loss. upon power loss. upon power loss.
TF (-3), MFT, SR NC/FO Valve: Closed A to AB NC/FC or NO/FC NC/FO Valve: Closed A to AB NC/FC or NO/FC
SPRING RETURN
Note Fail Position
LF (-3), MFT, SR will drive open. Valve: Closed A to AB or will drive open Valve: Closed A to AB
AF SR Spring Action: Open A to AB. Spring Action: or Open A to AB.
AFR, MFT Will spring open A to AB (Can be chosen with Will spring open A to AB (Can be chosen with
Floating Point or upon power loss. CW/CCW switch.) upon power loss. CW/CCW switch.)
Proportional Type Actuators Spring Action: Spring Action:
P10419 - 09/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
5
Flow, Operation and Installation
Characterized Control Valves™ (CCV)
FLOW PATTERNS
2-way Characterized Control Valves™ (Belimo B2 Series) (Belimo B6 Series) Flow Direction
Two-way valves
should be installed
with the disc
upstream.
Upstream A
Downstream AB
INCORRECT PIPING
Three-Way
y Diverting
Diver Valve
lve Piping Diagram WARNING! Do Not Pipe in this manner!
Three-Wa
Way
y Mixing Valvelve Piping Diagram
Diagra
(2 Inputs,
Inputs, 1 Output)
Output (1 Input, 2 Outputs) Note Valve Porting!
A
A The A-port must be piped to the coil! Not the B-port!
B
B ReturnReturn ReturnReturn Flow is not possible from A to B. If AB-port is not piped as
Coil AB
AB Coil Coil the common port, the valve must be re-piped. It is good
Coil A
A
practice to install a balancing valve in the bypass line. These
SupplySupply SupplySupply
B
B valves are intended for closed loop systems. Do not install
AB
AB in an open loop system or in an application that is open to
atmospheric pressure.
3-WAY VALVES MUST BE PIPED CORRECTLY. They can be mixing or diverting. Mixing is the preferred piping arrangement.
The BELIMO Characterized Control Valve is a CONTROL valve, not a manual valve adapted for actuation. The control port is the A-port. It is similar to the globe valve in that
the middle port is the B or bypass port. The common port AB is on the main opposite the A-port. These diagrams are for typical applications only. Consult engineering
specification and drawings for particular circumstances.
REDUCED B-PORT FLOW
Note: The B-port flow of the 3-way CCV is lower than that of the A-port. In most applications this is beneficial since the reduced flow compensates for the inexistent
pressure drop across the coil in the bypass mode. Therefore, proper sizing is important to avoid flow noise in particular when the system is designed with constant
speed pumps. Please refer to our valve sizing and selection guidelines.
The flow velocity in the pipe upstream and downstream of the valve should be considered as well. The typical HVAC design maximum flow is 4 to 8 ft/s to avoid noise
issues.
Also, the pipe reduction factor must be considered and can be found on pages 3 and 4. Pipe reducers decrease the Cv value of a valve and consequently increase the
pressure drop across the valve, a situation that could lead to noise or a lower than designed flow.
6
Nomenclature
Characterized Control Valve™ (CCV)
B2 09 +LRX 24 -MFT
Valve Valve Size Trim Material Actuator Type Power Supply Control
B2 = 2-way 07-80 = ½” to 3” B = Chrome Plated Non Fail-Safe 24 = 24 VAC/DC Blank = On/Off -S = Built-in
B3 = 3-way Brass Ball, TR 120 = 120 VAC* -3 = On/Off, Floating Point Auxiliary
Nickel Plated LRB, LRX 230 = 230 VAC -SR = 2-10 VDC Switch
Stem LRQX UP = 24 to 240 VAC -MFT = Multi-Function -T = Terminal
Blank = Stainless NRB, NRX Technology Strip
Steel Ball NRQX -MFT95 = 0-135 Ω N4 = NEMA
and Stem ARB, ARX 4/4X
-IP = Internet Protocol
ARQX N4H = NEMA
Fail-Safe 4/4X
Spring Return with
TFR, TFRX Heater
LF
AFR, AFRX
Electronic
GKR
Ordering Example
4
2 Specify preference or configuration.
Does order
require
Set-Up tagging?
7
Nomenclature
Characterized Control Valve™ (CCV)
Ordering Example
8
B2 Series, 2-Way, Characterized Control Valve
Chrome Plated Brass Ball and Brass Stem
Application
This valve is typically used in air handling units on heating or cooling coils, and
fan coil unit heating or cooling coils. Some other common applications include
Unit Ventilators, VAV box re-heat coils and bypass loops. This valve is suitable
for use in a hydronic system with variable flow.
TR Series
LR Series
4.7 ½ 15 B213B
TF Series
LF Series
Ball chrome plated brass 7.4 ½ 15 B214B
Stem nickel plated brass 10 ½ 15 B215B
Seats PTFE 16 ½ 15 B216B
Characterizing disc Tefzel® 4.7 ¾ 20 B217B
Packing 2 EPDM O-rings, lubricated
7.4 ¾ 20 B218B
Body pressure rating 600 psi
10 ¾ 20 B219B
Media temp. range 0°F to 250°F [-18°C to 120°C]
14 ¾ 20 B220B
Close off pressure 200 psi
24 ¾ 20 B221B*
Maximum differential 50 psi for typical applications
*Models without characterizing disc
pressure (∆P)
Leakage 0% for A to AB
External leakage according to EN 12266-1:2003
Cv rating A-port: see product chart for values
Tefzel® is a registered trademark of DuPont
P10419 - 09/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
Dimensions
2WayValve-B207-B220
Flow Patterns
9
B3 Series, 3-Way, Characterized Control Valve
Chrome Plated Brass Ball and Brass Stem
Application
This valve is typically used in air handling units on heating or cooling coils, and
fan coil unit heating or cooling coils. Some other common applications include
Unit Ventilators, VAV box re-heat coils and bypass loops. This valve is suitable
for use in a hydronic system with variable or constant flow.
TR Series
LR Series
TF Series
LF Series
3 ½ 15 B312B
B-port modified for constant common port 4.7 ½ 15 B313B
flow
10 ½ 15 B315B
Controllable Flow Range 75°
16 ½ 15 B316B
Sizes ½”, ¾”
4.7 ¾ 20 B317B
Type of end fitting NPT female ends
7.4 ¾ 20 B318B
Materials:
14 ¾ 20 B320B
Body forged brass, nickel plated
24 ¾ 20 B321B
Ball chrome plated brass
*Models without characterizing disc
Stem nickel plated brass
Seats PTFE
Characterizing disc Tefzel®
Packing 2 EPDM O-rings, lubricated
Body pressure rating 600 psi
Media temp. range 0°F to 250°F [-18°C to 120°C]
Close off pressure 200 psi
Maximum differential 50 psi for typical applications
pressure (∆P)
Leakage 0% for A to AB
<2.0% for B to AB
External leakage according to EN 12266-1:2003
Dimensions
3WayValve-B307-B320
Flow Patterns
“B” Port must
be piped to the
bypass leg.
10
B2 Series, 2-Way, Characterized Control Valve
Stainless Steel Ball and Stem
Application
This valve is typically used in air handling units on heating or cooling coils, and
fan coil unit heating or cooling coils. Some other common applications include
Unit Ventilators, VAV box re-heat coils and bypass loops. This valve is suitable
for use in a hydronic system with variable flow.
TR Series
TF Series
Service chilled or hot water, 60% glycol 4.7 ½ 15 B213
Flow characteristic A-port equal percentage 7.4 ½ 15 B214
Controllable Flow Range 75° 10 ½ 15 B215
NR...N4 Series
Sizes ½”, ¾”, 1”, 1¼”, 1½”, 2”, 2½”, 3”
LR Series
LF Series
16 ½ 15 B216
Type of end fitting NPT female ends 4.7 ¾ 20 B217
Materials: 7.4 ¾ 20 B218
Body forged brass, nickel plated 10 ¾ 20 B219
Ball stainless steel
14 ¾ 20 B220
Stem stainless steel
24 ¾ 20 B221*
Seats PTFE
Characterizing disc Tefzel® 7.4 1 25 B222
Packing 2 EPDM O-rings, lubricated 10 1 25 B223
Body pressure rating 19 1 25 B224
600 psi ½” - 1¼” (B230) 30 1 25 B225*
400 psi 1¼” (B231) - 3” 10 1¼ 32 B229
Media temp. range 0°F to 250°F [-18°C to 120°C] 19 1¼ 32 B230*
Close off pressure 25 1¼ 32 B231
200 psi ½” - 2” (B254) 37 1¼ 32 B232*
100 psi 2½” (B261) - 3” 19 1½ 40 B238
Maximum differential 50 psi for typical applications 29 1½ 40 B239
pressure (∆P) 37 1½ 40 B240*
Leakage 0% for A to AB 29 2 50 B248
P10419 - 09/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
AR...N4 Series
Tefzel® is a registered trademark of DuPont 65 2 50 B251
AR Series
AF Series
85 2 50 B252
Dimensions 120 2 50 B253
240 2 50 B254*
2WayValve-B207-B220
60 2½ 65 B261
75 2½ 65 B262
110 2½ 65 B263
150 2½ 65 B264
210 2½ 65 B265*
70 3 80 B277
130 3 80 B278
Valve Nominal Size Dimensions (Inches [mm]) 170 3 80 B280*
*Models without characterizing disc
Valve Body Inches DN [mm] A B
B207-B211 ½” 15 2.41” [61.1] 1.39” [35.2]
Flow Patterns
B212-B216 ½” 15 2.38” [60.4] 1.78” [45.2]
B217-B221 ¾” 20 2.73” [69.3] 1.87” [47.4]
B222-B225 1” 25 3.09” [78.4] 1.87” [47.4]
B229-B230 1¼” 32 3.72” [94.6] 1.87” [47.4]
B231-B232 1¼” 32 3.72” [94.6] 2.04” [51.9]
B238-B240 1½” 40 3.88” [98.5] 2.04” [51.9]
B248-B250 2” 50 4.21” [107.0] 2.27” [57.7]
B251-B254 2” 50 4.93” [125.2] 2.73” [69.5]
B261-B265 2½” 65 5.55” [140.9] 2.73” [69.5]
B277-B280 3” 80 5.82” [147.9] 2.73” [69.5]
11
B3 Series, Three Way, Characterized Control Valve
Stainless Steel Ball and Stem
Application
This valve is typically used in air handling units on heating or cooling coils, and
fan coil unit heating or cooling coils. Some other common applications include
Unit Ventilators, VAV box re-heat coils and bypass loops. This valve is suitable
for use in a hydronic system with variable or constant flow.
TR Series
TF Series
Technical Data 3 ½ 15 B312
NR...N4 Series
Service chilled or hot water, 60% glycol 4.7 ½ 15 B313
LR Series
LF Series
Flow characteristic A-port equal percentage 10 ½ 15 B315
B-port modified for constant common port 16 ½ 15 B316
flow 4.7 ¾ 20 B317
Controllable Flow Range 75° 7.4 ¾ 20 B318
Sizes ½”, ¾”, 1”, 1¼”, 1½”, 2” 14 ¾ 20 B320
Type of end fitting NPT female ends 24 ¾ 20 B321
Materials: 7.4 1 25 B322
Body forged brass, nickel plated 10 1 25 B323
Ball stainless steel 30 1 25 B325*
Stem stainless steel 10 1¼ 32 B329
Seats PTFE 19 1¼ 32 B330
Characterizing disc Tefzel® 25 1¼ 32 B331
Packing 2 EPDM O-rings, lubricated 19 1½ 40 B338
Body pressure rating 29 1½ 40 B339
AR...N4 Series
600 psi ½” - 1”
AR Series
AF Series
37 1½ 40 B340
400 psi 1¼” - 2”
46 1½ 40 B341
Media temp. range 0°F to 250°F [-18°C to 120°C]
29 2 50 B347
Close off pressure
37 2 50 B348
200 psi ½” - 2”
46 2 50 B349
Maximum differential 50 psi for typical applications
pressure (∆P) 57 2 50 B350
12
B6 Series, Two Way, Characterized Control Valve
Stainless Steel Ball and Stem
Application
This valve is typically used in air handling units on heating or cooling coils, and
fan coil unit heating or cooling coils. Some other common applications include
Unit Ventilators, VAV box re-heat coils and bypass loops. This valve is suitable
for use in a hydronic system with variable or constant flow.
Series
Series
AFR
110 2½" 65 B6250S-110
AR
Controllable Flow Range 75°
Sizes 2½”, 3”, 4”, 5”, 6” 110 3" 80 B6300S-110
Type of end fitting pattern to mate with ANSI 125 flange 186 4" 100 B6400S-186
Series
Series
290 5" 125 B6500S-290
GKR
Materials:
GR
Body cast iron - GG25 400 6" 150 B6600S-400
Ball stainless steel
Stem stainless steel
Seats PTFE
Characterizing disc stainless steel
Packing 2EEPDM O rings, lubricated
Body pressure rating according to ANSI 125, standard class B Flow Pattern
Media temp. range 0°F to 248°F [-18°C to +120°C]
Close off pressure 100 psi 2-way B6250 to B6600 Characterized Control Valves™
Maximum differential 50 psi
C Flow Direction
pressure (∆P)
Leakage 0% for A to AB
Cv rating A-port: see product chart for values
Dimensions B
P10419 - 09/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
Upstream A
E
Downstream AB
A
F D
NOTES:
1) Flange bolt pattern matches ANSI class 125 flanges (not ANSI/ASME rated)
2) Maximum allowable working pressure: 100 PSIG
3) It is not recommended to connect raised-face flanges to flat-faced flanges
13
Characterized Control Valve Product Range Overview
B2.., B3.., 2-way, 3-way, Stainless Steel Ball and Stem
TFR Series
TR Series
Characteristic
4.7 ½ 15 B213(B) B313(B)
7.4 ½ 15 B214(B) Mode of Operation
The Characterized Control Valve is operated by a rotary
10 ½ 15 B215(B) B315(B)
actuator. The actuators are controlled by a standard voltage
14 ½ 15 B216(B)* B316(B)* for on/off control or a proportional signal or 3-point control
system which move the ball of the valve to the position
NR Series
LR Series
LF Series
4.7 ¾ 20 B217(B) B317(B) dictated by the control system.
7.4 ¾ 20 B218(B) B318(B) Product Features
The equal-percentage characteristic of the flow is ensured
10 ¾ 20 B219(B) by the integral characterizing disc. This characteristic
provides linear heating or cooling output from the coil
14 ¾ 20 B220(B)*
improving energy efficiency and comfort.
14 ¾ 20 B320(B)
Actuator Specifications
24 ¾ 20 B221(B)* B321(B)* Control type on/off, floating point, 2-10 VDC,
multi-function technology (MFT)
7.4 1 25 B222 B322 Manual override TR, LR, AR, NR, AFR series
10 1 25 B223 B323 Electrical connection 3 ft [1m] cable with ½”
conduit fitting or covered screw
19 1 25 B224 terminal strip
30 1 25 B225* B325* Valve Specifications
10 1¼ 32 B229 Service chilled or hot water, 60% glycol
Flow characteristic A-port equal percentage
19 1¼ 32 B230* B-port modified for constant
common port flow
10 1¼ 32 B329
Controllable flow range 75°
AR Series
* Models without characterizing discs. (B) Models with chrome plated brass ball and brass stem
* 3-Way Valves not for use in change over applications
14
Characterized Control Valve Product Range Overview
B6.., 2-way, Stainless Steel Ball and Stem
AFR
110 2½ 65 B6250S-110
AR
110 3 80 B6300S-110
186 4 100 B6400S-186
CCV
GKR
GR
290 5 125 B6500S-290
Equal Percentage
400 6 150 B6600S-400 Characteristic
Applications
Water-side control of heating and cooling systems for AHU supply,
cooling towers and chillers.
Mode of Operation
The Characterized Control Valve is operated by a rotary actuator. The
actuators are controlled by a standard voltage for on/off control or a
proportional signal or 3-point control system which move the ball of
the valve to the position dictated by the control system.
Product Features
The equal-percentage characteristic of the flow is ensured by the inte-
gral characterizing disc. This characteristic provides linear heating or
cooling output from the coil improving energy efficiency and comfort.
Actuator Specifications
Control type On/Off, Floating Point, 2-10 VDC,
Multi-Function Technology (MFT)
Manual override AR, GR, AFR and GKR series
Electrical connection 3 ft [1m] cable with ½”
conduit fitting or covered screw
terminal strip
Valve Specifications
Service chilled or hot water, 60% glycol
Flow characteristic A-port equal percentage
Action max 90° rotation
P10419 - 09/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
15
TR24-3 Actuators, On-Off, Floating Point
D1349
D
C
E F B
A TR
Technical Data
Control on/off, floating point Dimensions with 3-Way Valve
Nominal voltage 24 VAC 50/60 Hz
D1350
Nominal voltage range 19.2…28.8 VAC
Power consumption 1W
Transformer sizing 1VA (class 2 power source)
Electrical connection screw terminals accessible after removal of
small cover (3 ft, 10 ft, 16 ft cables optional) D C
Input impedance 0.36 kΩ
Angle of rotation 90°
Position indication integrated into handle
Manual override push down handle
Running time 90 seconds @ 60 hz, 108 seconds @ 50 hz
16
TR24-3 Actuators, On-Off, Floating Point
W187
connected to the Hot connection of the controller.
Actuators with plenum rated cable do not have numbers on wires;
3 use color codes instead.
W186
electrical components could result in death or serious injury.
On/Off Control
You may not use one wire control.
P10419 - 09/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
17
TR24-SR Actuators, Proportional
D1349
D
C
E F B
A TR
Technical Data
Control proportional Dimensions with 3-Way Valve
Nominal voltage 24 VAC 50/60 Hz, 24 VDC
D1350
Nominal voltage range 19.2…28.8 VAC, 21.6…28.8 VDC
Power consumption 0.5 W
Transformer sizing 1VA (class 2 power source)
Electrical connection screw terminals accessible after removal of
small cover (3 ft, 10 ft, 16 ft cables optional) D C
Input impedance 100 kΩ
Angle of rotation 90°
Direction of rotation reversible with switch under cover
Position indication integrated into handle
Manual override push down handle
18
TR24-SR Actuators, Proportional
Wiring Diagrams
W190
Actuators with color coded wires are optional.
2 Wire numbers are provided for reference.
CAUTION Equipment damage!
Actuators may be connected in parallel.
Power consumption and input impedance must be observed.
W191
During installation, testing, servicing and troubleshooting of this product, it may
be necessary to work with live electrical components. Have a qualified licensed electrician
or other individual who has been properly trained in handling live electrical components
perform these tasks. Failure to follow all electrical safety precautions when exposed to live
electrical components could result in death or serious injury.
4 to 20 mA Control of TR24-SR(-T) US
19
LR...24-3 Actuators, On/Off, Floating Point
D1351
D C
H1 H2
E F B
A
LRB, LRX -3, -SR
Valve Nominal Size Dimensions (Inches [mm])
Valve Body Inches DN [mm] A B
B207(B)-B211(B) ½” 15 1.39” [35.2] 1.39” [35.2]
Models B212(B)-B215(B) ½” 15 1.78” [45.2] 1.78” [45.2]
LRB24-3-T LRX24-3-T w/Terminal Block B217(B)-B221(B) ¾” 20 1.87” [47.4] 1.87” [47.4]
LRB24-3 LRX24-3 w/3 ft. cable B222-B225 1” 25 1.87” [47.4] 1.87” [47.4]
LRB24-3-S LRX24-3-S w/built-in Aux. Switch B229-B231 1¼” 32 1.87” [47.4] 1.87” [47.4]
Technical Data
Dimensions with 3-Way Valve
Control on/off, floating point
D1352
Power supply 24 VAC ± 20% 50/60 Hz
24 VDC ± 10%
Power consumption running 1.5 W
holding 0.2 W
Transformer sizing 2 VA (class 2 power source) D
Electrical connection ½” conduit connector C
18 GA, plenum rated cable H2
H1
LRB24-3 3 ft [1m]
LRX24-3 3 ft [1m], 10 ft [3m], 16 ft [5m]
Overload protection electronic throughout 0° to 95° rotation
Input impedance 600 Ω E F B
Angle of rotation 90°, adjustable with mechanical stop A
LR...24-3-T
Electrical connection screw terminal (for 26 to 14 GA wire)
protected (NEMA 2, IP20)
LR...24-3-S
Auxiliary switch 1 SPDT, 3A (0.5A) @ 250 VAC, UL Listed,
adjustable 0° to 100°
† Rated impulse voltage 800V, Control pollution degree 3, Type of action 1
(1.B for -S models)
20
LR...24-3 Actuators, On/Off, Floating Point
Wiring Diagrams
W193-LR-08
2 CAUTION Equipment damage!
Actuators may be connected in parallel.
Power consumption and input impedance must be observed.
Actuators are provided with color coded wires.
3 Wire numbers are provided for reference.
W123-LR-08
Meets cULus or UL and CSA requirements without the
need of an electrical ground connection.
W169-08
Auxiliary switch
P10419 - 09/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
21
LR...24-SR Actuators, Proportional
D1351
D C
H1 H2
E F B
A
LRB, LRX -3, -SR
Valve Nominal Size Dimensions (Inches [mm])
Valve Body Inches DN [mm] A B
B207(B)-B211(B) ½” 15 2.41” [61.1] 1.39” [35.2]
Models B212(B)-B215(B) ½” 15 2.38” [60.4] 1.78” [45.2]
LRB24-SR-T LRX24-SR-T w/Terminal Block B217(B)-B221(B) ¾” 20 2.73” [69.3] 1.87” [47.4]
LRB24-SR LRX24-SR w/3ft. cable B222-B225 1” 25 3.09” [78.4] 1.87” [47.4]
B229-B231 1¼” 32 3.72” [94.6] 1.87” [47.4]
Technical Data
Power supply 24 VAC ± 20% 50/60 Hz
24 VDC ± 10% Dimensions with 3-Way Valve
Power consumption running 1.5 W
D1352
holding 0.4 W
Transformer sizing 3 VA (class 2 power source)
Electrical connection ½” conduit connector
18 GA, plenum rated cable D
LRB24-SR 3 ft [1m] C
LRX24-SR 3 ft [1m], 10 ft [3m], 16 ft [5m]
H1 H2
Overload protection electronic throughout 0° to 95° rotation
Operating range Y 2 to 10 VDC, 4 to 20 mA
Feedback output U 1 to 10 VDC, max 0.5 mA
Input impedance 100 kΩ (0.1 mA), 500 Ω E F B
Angle of rotation 90°, adjustable with mechanical stop A
LR...24-SR-T
Electrical connection screw terminal (for 26 to 14 GA wire)
protected (NEMA 2/IP20)
† Rated impulse voltage 800V, Control pollution degree 3, Type of action 1
(1.B for -S models)
22
LR...24-SR Actuators, Proportional
Wiring Diagrams
W265-LR-08
2 CAUTION Equipment damage!
Actuators may be connected in parallel.
Power consumption and input impedance must be observed.
2 to 10 VDC control
W265-LR-08
Meets cULus or UL and CSA requirements without the
need of an electrical ground connection.
The ZG-R01 500 Ω resistor converts the 4 to 20 mA control signal to 2
to 10 VDC, up to 2 actuators may be connected in parallel.
23
LR...120-3 Actuators, On/Off, Floating Point
D1353
D C
H1 H2
E F B
A
LRB, LRX 120-3, MFT, MFT95
Valve Nominal Size Dimensions (Inches [mm])
Valve Body Inches DN [mm] A B
B207(B)-B211(B) ½” 15 2.41” [61.1] 1.39” [35.2]
Models B212(B)-B215(B) ½” 15 2.38” [60.4] 1.78” [45.2]
LRB120-3
B217(B)-B221(B) ¾” 20 2.73” [69.3] 1.87” [47.4]
LRX120-3
B222-B225 1” 25 3.09” [78.4] 1.87” [47.4]
B229-B230 1¼” 32 3.72” [94.6] 1.87” [47.4]
Technical Data
Control On/Off, Floating Point
Power supply 100 to 240 VAC, 50/60 Hz (nominal) Dimensions with 3-Way Valve
85 to 265 VAC, 50/60 Hz (tolerance)
D1354
Power consumption running 2 W
holding 0.5 W
Transformer sizing 4 VA (class 2 power source)
Electrical connection ½” conduit connector D
18 GA, plenum rated cable C
LRB120-3 3 ft [1m]
H1 H2
LRX120-3 3 ft [1m], 10 ft [3m], 16 ft [5m]
Overload protection electronic throughout 0° to 95° rotation
Input impedance 600 Ω
Angle of rotation 90°, adjustable with mechanical stop E F B
Direction of rotation reversible with protected switch A
24
LR...120-3 Actuators, On/Off, Floating Point
Wiring Diagrams
W405
2 CAUTION Equipment damage!
Actuators may be connected in parallel.
Power consumption and input impedance must be observed.
W406
During installation, testing, servicing and troubleshooting of this product, it may
be necessary to work with live electrical components. Have a qualified licensed electrician
or other individual who has been properly trained in handling live electrical components
perform these tasks. Failure to follow all electrical safety precautions when exposed to live
electrical components could result in death or serious injury.
25
LR...120-SR Actuators, Proportional
D1353
D C
H1 H2
E F B
A
LRB, LRX 120-3, MFT, MFT95
Valve Nominal Size Dimensions (Inches [mm])
Valve Body Inches DN [mm] A B
B207(B)-B211(B) ½” 15 2.41” [61.1] 1.39” [35.2]
Models B212(B)-B215(B) ½” 15 2.38” [60.4] 1.78” [45.2]
LRB120-SR B217(B)-B221(B) ¾” 20 2.73” [69.3] 1.87” [47.4]
LRX120-SR B222-B225 1” 25 3.09” [78.4] 1.87” [47.4]
B229-B230 1¼” 32 3.72” [94.6] 1.87” [47.4]
Technical Data
Power supply 100 to 240 VAC, 50/60 Hz (nominal)
85 to 265 VAC, 50/60 Hz (tolerance) Dimensions with 3-Way Valve
D1354
Power consumption running 2.5 W
holding 1 W
Transformer sizing 4.5 VA (class 2 power source)
Electrical connection ½” conduit connector
18 GA, plenum rated cable D
LRB120-SR 3 ft [1m] C
LRX120-SR 3 ft [1m], 10 ft [3m], 16 ft [5m] H2
H1
Overload protection electronic throughout 0° to 95° rotation
Operating range Y 2 to 10 VDC, 4 to 20 mA
Feedback output U 1 to 10 VDC, max 0.5 mA
Input impedance 100 kΩ (0.1 mA), 500 Ω E F B
Angle of rotation 90°, adjustable with mechanical stop A
26
WARNING
LR...120-SR Actuators, Proportional
Live Electrical Components!
During installation, testing, servicing and troubleshooting of this product, it may be
necessary to work with live electrical components. Have a qualified licensed electrician
or other individual who has been properly trained in handling live electrical components
perform these tasks. Failure to follow all electrical safety precautions when exposed
to live electrical components could result in death or serious injury.
Wiring Diagrams
W365
100 to 240 VAC
15 2 19
N L1 1 Neutral
CAUTION Equipment damage!
Cable 2
2 H L2 2 Hot +
Actuators may be connected in parallel.
Power consumption and input impedance must be observed.
6 1 Common
6 Only connect common to neg. (–) leg of control circuits.
2 Hot +
7 8
Cable 1
7 A 500 Ω resistor converts the 4 to 20 mA control signal to 2 to 10 VDC.
(–)
Control Signal
VDC/mA (+) 3 Y Input, 2 to 10V
15 LRB(X) can be supplied with both 120 VAC and 230 VAC.
2 to 10 VDC (–)
Feedback Signal (+) 5 U Output, 2 to 10V
19 All 120 VAC and 230 VAC actuators use appliance rated cables.
1 0
LR...120-SR
27
LR...24-MFT Actuators, Multi-Function Technology
D1353
D C
H1 H2
E F B
A
LRB, LRX 120-3, MFT, MFT95
Valve Nominal Size Dimensions (Inches [mm])
Valve Body Inches DN [mm] A B
B207-B211 ½” 15 2.41” [61.1] 1.39” [35.2]
Models B212-B215 ½” 15 2.38” [60.4] 1.78” [45.2]
LRX24-MFT Flexible Version B217-B221 ¾” 20 2.73” [69.3] 1.87” [47.4]
B222-B225 1” 25 3.09” [78.4] 1.87” [47.4]
B229-B230 1¼” 32 3.72” [94.6] 1.87” [47.4]
Technical Data
Power supply 24 VAC ± 20% 50/60 Hz
24 VDC ± 10% Dimensions with 3-Way Valve
Power consumption running 2 W
D1354
holding 1.2 W
Transformer sizing 6 VA (class 2 power source)
Electrical connection ½” conduit connector
18 GA, plenum rated cable D
LRX24-MFT 3 ft [1m], 10 ft [3m], 16 ft [5m] C
Overload protection electronic throughout 0° to 95° rotation
H1 H2
Operating range Y 2 to 10 VDC (default)
4 to 20 mA
variable (VDC, PWM, floating point, on/off)
Feedback output U 2 to 10 VDC, 0.5mA max E F B
VDC variable A
Input impedance 100 kΩ (0.1 mA), 500 Ω
28
LR...24-MFT Actuators, Multi-Function Technology
Wiring Diagrams
W538
2 CAUTION Equipment damage!
Actuators may be connected in parallel.
Power consumption and input impedance must be observed.
W538
8 A& B should both be closed for triac source and open for triac sink.
For triac sink the common connection from the actuator
9 must be connected to the hot connection.
W538
electrical components could result in death or serious injury.
VDC/4-20 mA
W538
P10419 - 09/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
PWM
29
LRX24-PC Actuators, 0 to 20V Phasecut, Proportional
D1353
D C
H1 H2
E F B
A
LRB, LRX 120-3, MFT, MFT95
Valve Nominal Size Dimensions (Inches [mm])
Valve Body Inches DN [mm] A B
B207-B211 ½” 15 2.41” [61.1] 1.39” [35.2]
Models B212-B215 ½” 15 2.38” [60.4] 1.78” [45.2]
LRX24-PC B217-B221 ¾” 20 2.73” [69.3] 1.87” [47.4]
B222-B225 1” 25 3.09” [78.4] 1.87” [47.4]
B229-B230 1¼” 32 3.72” [94.6] 1.87” [47.4]
Technical Data
Power supply 24 VAC ± 20% 50/60 Hz
24 VDC ± 10% Dimensions with 3-Way Valve
Power consumption running 2 W
D1354
holding 1.2 W
Transformer sizing 5 VA (Class 2 power source)
Electrical connection ½” conduit connector
18 GA plenum rated cable
3 ft [1m], 10 ft [3m], 16 ft [5m] D
C
Overload protection electronic throughout 0 to 95° rotation
Operating range Y 0 to 20V phasecut H1 H2
Feedback output U 2 to 10 VDC, 0.5mA max
Input impedance 8 kΩ (50 mW)
Angle of rotation 90°, adjustable with mechanical stop E F B
electronically variable
A
Direction of rotation reversible with switch
30
LRX24-PC Actuators, 0 to 20V Phasecut, Proportional
Wiring Diagrams
W185
1
24 VAC Transformer
W185
31
LRX24-MFT95 Actuators, 0 to 135 Ω, Proportional
D1353
D C
H1 H2
E F B
A
LRB, LRX 120-3, MFT, MFT95
Valve Nominal Size Dimensions (Inches [mm])
Valve Body Inches DN [mm] A B
B207-B211 ½” 15 2.41” [61.1] 1.39” [35.2]
Models B212-B215 ½” 15 2.38” [60.4] 1.78” [45.2]
LRX24-MFT95 B217-B221 ¾” 20 2.73” [69.3] 1.87” [47.4]
B222-B225 1” 25 3.09” [78.4] 1.87” [47.4]
B229-B230 1¼” 32 3.72” [94.6] 1.87” [47.4]
Technical Data
Power supply 24 VAC ± 20% 50/60 Hz
24 VDC ± 10% Dimensions with 3-Way Valve
Power consumption running 2 W
D1354
holding 1.2 W
Transformer sizing 5 VA (Class 2 power source)
Electrical connection ½” conduit connector
18 GA plenum rated cable
3 ft [1m], 10 ft [3m], 16 ft [5m] D
C
Overload protection electronic throughout 0 to 95° rotation
Operating range WRB 0 to 135 Ω Honeywell Electronic H1 H2
Series 90, 0 to 135 Ω input
Feedback output U 2 to 10 VDC, 0.5mA max
Input impedance 100 kΩ (0.1 mW)
E F B
Angle of rotation 90°, adjustable with mechanical stop
electronically variable A
32
24 Resistor value depends on the type of 23 Volts
22 Actuators and controller must have 22
controller and the number of
Wht (3) W Wiring Multiple Actuato
separate transformers. actuators.
W No resistor is used for one 24 22
24 VAC Transformer
Series 90 actuator.
R Honeywell® resistor
Wht kits
(4) may
R 21
B
Controller
also be used.
23 Consult controller instruction data for B R W B Wht (5) B Line H205
reversing
Series 90 high switch.
limit control - 280 Ω -MFT95 US
24 Resistor value depends on the type of Shunting
W
W_new60408_5
Switch A Switch B Damper Position Resistor
Series 90
24 VAC Transformer
actuator. Honeywell® resistor kits may ControllerB
W018
21 Damper Open
also be used. Line Blk (1)Closed
Damper Common
21
Y
Line
Volts Red (2) GMX24-MFT95
+ Hot
25 To reverse control rotation, use the Actuators:
The AF24-MFT95
direction of rotation switch is set so that the failUS
safe position and the Volts
23 AMX24
R
21 Provide overload protection and disconnect as required. position of the damper is closed with no signal at wire R.
24
reversing switch. W973, W7100
W
21 24 VAC Transformer Wht (3) W 25actuators
No. of Controller
Resistance
Shunting
Actuators and controller must have separate transformers.
W015
R Wht (4) R 2 140 Ω
22 Override
Resistor
Line Blk (1) Common 3 71.5 Ω
Volts B Red (2)Wht (5) B
+ Hot High45 Limit47.5 Ω
Control
24 23 Output 2 to 10 VDC6
37.5 21
Ω
Consult controller instruction data for more detailed
Switch A Switch B Damper Position INSTALLATION
Series 90 A NOTES
Wht (6) ‘U5’ 28 Ω To oth
23 information. Controller Wht (3) W Line actua
Resistor Kit No. ZG-R03
24 24 VAC Transformer
Damper Open 135 Ω Wht (4) R
-MFT95 US 21 Volts
2121 Provide overload B Wiring Multiple Actuato
protection
Wht (5) Band using
Line a Minimum Posit
Resistor value depends on the type of controller and the Damper Closed
Line disconnect as required.
Wht (6)Blk‘U5’(1)
Output 2 toCommon
10 VDC Volts
24 number of actuators. No resistor is used for one actuator. 24 VAC Transformer
The direction of rotation switch is set so that the fail safe position and the Volts 24 VAC Transformer Red (2)US + Hot
-MFT95 No. of
22
21 Actuators and controller must have 21
23 22 W actuators R
Honeywell® resistor kits may also be used.
position of the damper is closed with no signal at wire R.
separate transformers. Line 2
Line Blk (1) Common Series 90 3
Volts R
21 24 VAC Transformer
No. of
Volts Red (2)Wht (3) W
+ Hot 25Controller 4
To reverse control rotation, use the reversing 23 Consult controller instruction
actuators Resistance data
Wht (4) R 23for Series 90 B R W
W015
Controller Resistor Kit N
140 Ω
25 Line
2
more detailed information.
A R B W
switch.2524232221 Blk (1) Common 3
Line
71.5 Ω W Wht (3)Wht
W (5) B 24
Series
B
90 high limit control -2
4 47.5 Ω R R
Volts Red (2) + Hot 24
Volts
5 Resistor
37.5 Ω value dependsB
Wht on
(4) the
Wht (6)type
R
‘U5’ of
Output 2 to 10 VDC 22
23 6 controller
28 Ω B and the number of
Wht (5) B Shunting
Resistor
W
Wiring Multiple Actuat
WARNING Live Electrical Components! A
Wht (3) W
22 Kitactuators.
Resistor No. ZG-R03 No
Controller
To other
resistorWht
actuators is(6)
used for
-MFT95
‘U5’ Output 2 toone
10 VDC US
24 23
During installation, testing, servicing and troubleshooting Override
24 actuator. Honeywell® resistor -MFT95 US kits may 21B
24 VAC Transformer
R W
135 Ω Wht (4) R also be used.
Wiring Multiple Actuators to a Series 90 Controller
of this product, it may be necessary to work with live electri- B Line
H205 Change- Occupied
cal components. Have a qualified licensed electrician or other Wht (5) B using a Minimum
Low Limit Control Position Potentiometer over Controller Contact
Volts
Wht (6) ‘U5’ Output 2 to 10 VDC 25 To reverse control rotation, use the 21 24 V
individual who has been properly trained in handling live electrical S963A
reversing switch. Minimum Position
W016
W019
components perform these tasks. Failure to follow all electrical -MFT95 US 24
24 VAC Transformer
VAC Transformer Potentiometer W
2121 Line
safety precautions when exposed to live electrical components 21 24 VAC Transformer Shunting
21
Resistor R
Override
Line
Line Blk (1)BlkCommon Volts
could result in death or serious injury. Line (1) Common Line B
Blk (1) Common Volts Red (2) + Hot 24
VoltsSwitch A Switch B Damper Position
Red (2) + Hot Volts 23
Series 90 22
Volts Red (2) + Hot 23
Series 90 25 Controller
23 22 W
Controller
Damper Open
Wht (3) W 22 24
W
A
W R B 24 21
SeriesB90 R B W (4)Wht
WhtDamper R (3) W R
Wht (3) W R Closed
Line
W 24 Controller Line
B Wht (5)Wht B (4) R B
Wht (4) R R Volts
Volts
R 22
The direction of rotation switch is set so that the fail safe position and the Shunting
Resistor
B position of the damper is closed with no signal atWht
WSeries 90 low limit control
wire(6)Wht
R. (5)
‘U5’ Output 2 B
to 10 VDC
B Wht (5) B Shunting
Resistor 135 Ω for 0 to 50% control
W973, W7100
T775 T
24280 Ω forTransformer
VAC 0 to 100% control Wht (6)US‘U5’ Output 2 to 10 VDC
-MFT95 No. of a
22 Controller Wht (6) ‘U5’ Output 2 to 10 VDC 21 23 actuators Resistance
24
W015
-MFT95 US 2 140 Ω
Line Blk (1) Common
-MFT95 US B R W
3 71.5 Ω
Volts 4 47.5 Ω
Red (2) + Hot 5 37.5 Ω
H205 Change- Occupied 23 6 28 Ω
A
over Controller Contact To ot
Low Limit Control Wht (3) W 24
Resistor Kit No. ZG-R03 actua
B
Wht (5) B using a Minimum Posi
24 VAC Transformer
21 Wht (6) ‘U5’ Output 2 to 10 VDC
21
21 -MFT95 US 24 VAC Transformer
Line Blk (1) Common 21 24 VAC Transformer 21 Line
Line Blk (1) Common
Volts Red (2) + Hot Line Volts
P10419 - 09/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
22 W W R B Wht (3) W 24 22
Series 90 Wht (4) R
R
Controller
Actuators: AF24-MFT95 US GMX24-MFT95B AMX24-MFT95
Wht (5) NMX24-MFT95
B LMX24-MFT
Series 90 low limit control Wht (6) ‘U5’ Output 2 to 10 VDC
135 Ω for 0 to 50% control T
280 Ω for 0 to 100% control -MFT95 US a
24 VAC Transformer
21
21 24 VAC Transforme
21 Provide overload protection and Line Blk (1) Common
disconnect as required. Volts Red (2) + Hot Line
23 Volts
22 Actuators and controller must have 22 Wht (3) W
W 24
separate transformers. Series 90 Wht (4) R
22 B R W
R
Controller
23 Consult controller instruction data for B R W B Wht (5) B H205
Changeover W R B
more detailed information. Wht (6) ‘U5’ Output 2 to 10 VDC
Controller
21
also be used. Line Blk (1) Common Y
800-543-9038 USA 866-805-7089 CANADA Volts 203-791-8396 LATIN AMERICA / CARIBBEAN
Red (2) + Hot
25 To reverse control rotation, use the 23 R R W
24
reversing switch.
W Wht (3) W 25 W973, W7100
Controller
33
Shunting
Resistor R Wht (4) R
LRQ...24-1 Quick Running Actuators, On/Off
D1355
D C
H1 H2
E F B
A
LRQB, LRQX
Valve Nominal Size Dimensions (Inches [mm])
Valve Body Inches DN [mm] A B
B207-B211 ½” 15 2.41” [61.1] 1.39” [35.2]
Models B212-B215 ½” 15 2.38” [60.4] 1.78” [45.2]
LRQB24-1 Basic Version B217-B221 ¾” 20 2.73” [69.3] 1.87” [47.4]
LRQX24-1 Flexible Version B222-B225 1” 25 3.09” [78.4] 1.87” [47.4]
B229-B230 1¼” 32 3.72” [94.6] 1.87” [47.4]
Technical Data
Control on/off Dimensions with 3-Way Valve
Power supply 24 VAC ± 20% 50/60 Hz
D1356
24 VDC ± 10%
Power consumption running 12 W
holding 1.5 W
Transformer sizing 18 VA (Class 2 power source)
20A @ 5ms max D
Electrical connection ½” conduit connector C
18 GA plenum rated cable H2
H1
LRQB24-1 3 ft [1m]
LRQX24-1 3 ft [1m], 10 ft [3m], 16 ft [5m]
Overload protection electronic throughout 0 to 95° rotation
Input impedance 600 Ω E F B
Angle of rotation max 95°, adjustable with mechanical stop A
34
LRQ...24-1 Quick Running Actuators, On/Off
Wiring Diagrams
W403-LRQ-08
1 Provide overload protection and disconnect as required.
35
LRQ...24-MFT Quick Running Actuators, Multi-Function Technology
D1371
D C
H1 H2
E F B
A
LRQB, LRQX
Valve Nominal Size Dimensions (Inches [mm])
Valve Body Inches DN [mm] A B
B207-B211 ½” 15 2.41” [61.1] 1.39” [35.2]
Models B212-B215 ½” 15 2.38” [60.4] 1.78” [45.2]
LRQB24-MFT Basic Version B217-B221 ¾” 20 2.73” [69.3] 1.87” [47.4]
LRQX24-MFT Flexible Version B222-B225 1” 25 3.09” [78.4] 1.87” [47.4]
B229-B230 1¼” 32 3.72” [94.6] 1.87” [47.4]
Technical Data
Power supply 24 VAC ± 20% 50/60 Hz
Dimensions with 3-Way Valve
24 VDC ± 10%
D1372
Power consumption running 12 W
holding 1.5 W
Transformer sizing 18 VA (Class 2 power source)
20A @ 5ms max
Electrical connection ½” conduit connector D
18 GA plenum rated cable C
LRQB24-MFT 3 ft [1m] H2
H1
LRQX24-MFT 3 ft [1m], 10 ft [3m], 16 ft [5m]
Overload protection electronic throughout 0 to 95° rotation
Operating range Y 2 to 10 VDC, 4 to 20 mA (default)
variable (VDC, on/off) E F B
Feedback output U 2 to 10 VDC, 0.5mA max A
36
LRQ...24-MFT Quick Running Actuators, Multi-Function Technology
Wiring Diagrams
W399_08
1 Provide overload protection and disconnect as required.
2
CAUTION Equipment damage!
Actuators may be connected in parallel.
Power consumption and input impedance must be observed.
VDC/4-20 mA
W399_08
The ZG-R01 500 Ω resistor may be used.
On/Off control
P10419 - 09/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
37
NRQ...24-1 Quick Running Actuators, On/Off
D1357
D C
H1 H2
E F B
A
NRQB, NRQX
Valve Nominal Size Dimensions (Inches [mm])
Valve Body Inches DN [mm] A B
B231-B232 1¼” 32 3.72” [94.6] 2.04” [51.9]
Models
NRQB24-1 Basic Version B238-B240 1½” 40 3.88” [98.5] 2.04” [51.9]
NRQX24-1 Flexible Version B248-B250 2” 50 4.21” [107] 2.27” [57.7]
D1358
Power supply 24 VAC ± 20% 50/60 Hz
24 VDC ± 10%
Power consumption running 12 W
holding 1.5 W
D
Transformer sizing 18 VA (Class 2 power source) C
Electrical connection ½” conduit connector,
18 GA plenum rated cable H1 H2
NRQB24-1 3 ft [1m]
NRQX24-1 3 ft [1m], 10 ft [3m], 16 ft [5m]
Overload protection electronic throughout 0 to 95° rotation
E F B
Input impedance 600 Ω
Angle of rotation max 95°, adjustable with mechanical stop A
Direction of rotation reversible with switch NRQB, NRQX
Valve Nominal Size Dimensions (Inches [mm])
38
NRQ...24-1 Quick Running Actuators, On/Off
Wiring Diagrams
W403-NRQ-08
1 Provide overload protection and disconnect as required.
39
NRQ...24-MFT Quick Running Actuators, Multi-Function Technology
D1357
D C
H1 H2
E F B
A
NRQB, NRQX
Valve Nominal Size Dimensions (Inches [mm])
Valve Body Inches DN [mm] A B
B231-B232 1¼” 32 3.72” [94.6] 2.04” [51.9]
Models B238-B240 1½” 40 3.88” [98.5] 2.04” [51.9]
NRQB24-MFT Basic Version B248-B250 2” 50 4.21” [107] 2.27” [57.7]
NRQX24-MFT Flexible Version
D1358
Power supply 24 VAC ± 20% 50/60 Hz
24 VDC ± 10%
Power consumption running 12 W
holding 1.5 W
Transformer sizing 18 VA (Class 2 power source) D
C
Electrical connection ½” conduit connector,
18 GA plenum rated cable H1 H2
NRQB24-MFT 3 ft [1m]
NRQX24-MFT 3 ft [1m], 10 ft [3m], 16 ft [5m]
Overload protection electronic throughout 0 to 95° rotation
Operating range Y 2 to 10 VDC, 4 to 20 mA (default) E F B
variable (VDC, on/off) A
Feedback output U 2 to 10 VDC, 0.5mA max NRQB, NRQX
VDC variable Valve Nominal Size Dimensions (Inches [mm])
40
NRQ...24-MFT Quick Running Actuators, Multi-Function Technology
Wiring Diagrams
W399_08
1 Provide overload protection and disconnect as required.
2
CAUTION Equipment damage!
Actuators may be connected in parallel.
Power consumption and input impedance must be observed.
VDC/4-20 mA
W399_08
The ZG-R01 500 Ω resistor may be used.
On/Off control
P10419 - 09/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
41
NRB24-3-T N4, NRX24-3-T N4 NEMA 4X Actuators, On/Off, Floating Point
D1363
D C
E F B
A
ARB N4, ARX N4, NRB N4, NRX N4
Valve Nominal Size Dimensions (Inches [mm])
Valve Body Inches DN [mm] A B
Models B207-B211 ½” 15 2.41” [61.1] 1.39” [35.2]
NRB24-3-T N4 B212-B215 ½” 15 2.38” [60.4] 1.78” [45.2]
NRB24-3-T N4H w/built in heater B217-B221 ¾” 20 2.73” [69.3] 1.87” [47.4]
NRX24-3-T N4
B222-B225 1” 25 3.09” [78.4] 1.87” [47.4]
NRX24-3-T N4H w/built in heater
B229-B230 1¼” 32 3.72” [94.6] 1.87” [47.4]
Technical Data
Control on/off, floating point Dimensions with 3-Way Valve
Power supply 24 VAC ± 20% 50/60 Hz
D1364
24 VDC ± 10%
Power consumption running 2.0 W / heater 24 W
holding 0.2 W
Transformer sizing 4 VA (class 2 power source) / heater 19 VA
Electrical connection screw terminal (for 26 to 14 GA wire) D C
Overload protection electronic throughout 0° to 95° rotation
Input impedance 600 Ω
Angle of rotation 90°, adjustable with mechanical stop
Direction of rotation reversible with switch
Position indication visual pointer E F B
42
NRB24-3-T N4, NRX24-3-T N4 NEMA 4X Actuators, On/Off, Floating Point
Wiring Diagrams
W193-NR-08
2 CAUTION Equipment damage!
Actuators may be connected in parallel. N
Power consumption and input impedance must be observed.
Actuators are provided with color coded wires. 1
3 Wire numbers are provided for reference.
W123-NR-08
Meets cULus or UL and CSA requirements without the
need of an electrical ground connection.
1
T
Floating Point control H
(°C)
M
m with actuator types ..-3
Legend:
1
N L L N L M = actuator
2 T (°C) = Thermostat
1 2 3 H = Heating
N L L N L
T H
1 2 3 (°C) S1 S2 S3 S4 S5 S6
M
T
1 <x <x
>x >x
2 1 2
T H x = 0 ... 100%
(°C)
P10419 - 09/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
Note
M
1 The ffollowing points must be taken into account
N L L N L
with independent, external wiring:
2
• All contact between the cables or wires that
1 2 3 S1 S2 isS3
are introduced and the heating element to beS4 S5 S6
avoided.
• Where necessary, use cables with sufficient
<x
T numbers of wires, e.g. so that the heating and the <x
N L N L >x
actuator can be supplied separately with voltage.
>x
T H x = 0 ... 100%
(°C)
1 2 3 5 1 2
Heater wiring
M
1
2
T H
(°C)
M T 1
N L N L
2
1 2 3 5 1 2
T H
(°C)
M
1
2
43
NRB24-SR-T N4, NRX24-SR-T N4 NEMA 4X Actuators, Proportional
D1363
D C
E F B
A
ARB N4, ARX N4, NRB N4, NRX N4
Valve Nominal Size Dimensions (Inches [mm])
Valve Body Inches DN [mm] A B
Models B207-B211 ½” 15 2.41” [61.1] 1.39” [35.2]
NRB24-SR-T N4 B212-B215 ½” 15 2.38” [60.4] 1.78” [45.2]
NRB24-SR-T N4H w/built in heater B217-B221 ¾” 20 2.73” [69.3] 1.87” [47.4]
NRX24-SR-T N4 B222-B225 1” 25 3.09” [78.4] 1.87” [47.4]
NRX24-SR-T N4H w/built in heater B229-B230 1¼” 32 3.72” [94.6] 1.87” [47.4]
D1364
Power supply 24 VAC ± 20% 50/60 Hz
24 VDC ± 10%
Power consumption running 2.5 W / heater 24 W
holding 0.4 W
Transformer sizing 5 VA (class 2 power source) / heater 20 VA C
D
Electrical connection screw terminal (for 26 to 14 GA wire)
Overload protection electronic throughout 0° to 95° rotation
Input impedance 100 kΩ (0.1mA), 500Ω
Angle of rotation 90°, adjustable with mechanical stop
Direction of rotation reversible with switch E F B
Position indication visual pointer A
44
NRB24-SR-T N4, NRX24-SR-T N4 NEMA 4X Actuators, Proportional
Wiring Diagrams
W265-NR-08
2 CAUTION Equipment damage! N L L N L
Actuators may be connected in parallel.
Power consumption and input impedance must be observed. 1 2 3
2 to 10 VDC control
The ZG-R01 500 Ω resistor converts the 4 to 20 mA control signal to 2 M
to 10 VDC, up to 2 actuators may be connected in parallel. 1
W265-NR-08
2
N L L N WARNING
L Live Electrical Components!
During installation, testing, servicing and troubleshooting of this product, it may
1 2 3 be necessary to work with live electrical components. Have a qualified licensed electrician
or other individual who has been properly trained in handling live electrical components
perform these tasks. Failure to follow all electrical safety precautions when exposed to live N L L N L
electrical components could result in death or serious injury.
1 2 3 S1 S2 S3 S4 S5 S6
T H
Wiring Diagrams (°C)
<x <x
M
m with actuator types ..-3
Legend: >x >x
1
N L L N L M = actuator T H x = 0 ... 100%
4 to 20 mA control
2 T (°C) = Thermostat (°C)
1 2 3 H = Heating
M
1
2
N L L N L
T H
1 2 3 (°C) S1 S2 S3 S4 S5 S6
M
T
N L N L
1 <x <x
>x >x
2 1 2 3 5 1 2
T H x = 0 ... 100%
(°C)
P10419 - 09/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
Note
M
1 The ffollowing points must be taken into account
N L L N L T H
with independent, external wiring:
2 (°C)
• All contact between the cables or wires that
1 2 3 S1 S2 isS3
are introduced and the heating element to beS4 S5 S6
avoided. M
• Where necessary, use cables with sufficient 1
<x
T numbers of wires, e.g. so that the heating and the <x 2
N L N L >x
actuator can be supplied separately with voltage.
>x
T H x = 0 ... 100%
(°C)
1 2 3 5 1 2
Heater wiring
M
1
2
T H
(°C)
M T 1
N L N L
2
1 2 3 5 1 2
T H
(°C)
M
1
2
45
NRX24-MFT-T N4 NEMA 4X Actuators, Multi-Function Technology
D1363
D C
E F B
A
ARB N4, ARX N4, NRB N4, NRX N4
Valve Nominal Size Dimensions (Inches [mm])
Valve Body Inches DN [mm] A B
Models B207-B211 ½” 15 2.41” [61.1] 1.39” [35.2]
NRX24-MFT-T N4 B212-B215 ½” 15 2.38” [60.4] 1.78” [45.2]
NRX24-MFT-T N4H w/built in heater B217-B221 ¾” 20 2.73” [69.3] 1.87” [47.4]
B222-B225 1” 25 3.09” [78.4] 1.87” [47.4]
Technical Data B229-B230 1¼” 32 3.72” [94.6] 1.87” [47.4]
Control 2 to 10 VDC, 4 to 20 mA (default)
variable (VDC, PWM, floating point, on/off)
Dimensions with 3-Way Valve1363
Power supply 24 VAC ± 20% 50/60 Hz
D1364
24 VDC ± 10%
Power consumption running 3.5 W (1.25 W) / heater 24 W
holding 1.25 W
Transformer sizing 6 VA (class 2 power source) / heater 21 VA
Electrical connection screw terminal (for 26 to 14 GA wire)
Overload protection electronic throughout 0° to 95° rotation D C
Input impedance 100 kΩ (0.1 mA), 500 Ω
1500 Ω (PWM, floating point, on/off)
Angle of rotation 95°, adjustable with mechanical stop
electronically variable
Direction of rotation reversible with switch E F B
46
NRX24-MFT-T N4 NEMA 4X Actuators, Multi-Function Technology
Wiring Diagrams
W538
2 CAUTION Equipment damage!
Actuators may be connected in parallel.
Power consumption and input impedance must be observed.
W538
Contact closures A & B also can be triacs.
8 A& B should both be closed for triac source and open for triac sink.
For triac sink the common connection from the actuator
9 must be connected to the hot connection.
T H
(°C)
W538
perform these tasks. Failure to follow all electrical safety precautions when exposed to live N L L N L
electrical components could result in death or serious injury.
1 2 3 S1 S2 S3 S4 S5 S6
T H
(°C)
<x <x
M
m with actuator types ..-3
Legend: >x >x
1
N L L N L M = actuator T H x = 0 ... 100%
2 T (°C) = Thermostat (°C)
1 2 3 H = Heating
M
VDC/4-20 mA 1
2
N L L N L
W538
T H
P10419 - 09/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
1 2 3 (°C) S1 S2 S3 S4 S5 S6
M
T
N L N L
1 <x <x
>x >x
2 1 2 3 5 1 2
T H x = 0 ... 100%
(°C)
Note
M
1 The ffollowing points must be taken into account
N L L N L T H
with independent, external wiring:
2 PWM (°C)
• All contact between the cables or wires that
1 2 3 S1 S2 isS3
are introduced and the heating element to beS4 S5 S6
avoided. M
• Where necessary, use cables with sufficient 1
<x
T numbers of wires, e.g. so that the heating and the <x 2
N L N L >x
actuator can be supplied separately with voltage.
>x
T H x = 0 ... 100%
(°C)
1 2 3 5 1 2
Heater wiring
M
1
2
T H
(°C)
M T 1
N L N L
2
1 2 3 5 1 2
T H
(°C)
800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA / CARIBBEAN
M
1 47
2
AR...24-3 Actuators, On/Off, Floating Point
D1359
D C
H1 H2
E F B
A
ARB, ARX
Valve Nominal Size Dimensions (Inches [mm])
Valve Body Inches DN [mm] A B
B231-B232 1¼” 32 3.72” [94.6] 1.98” [50.4]
B238-B240 1½” 40 3.88” [98.5] 1.98” [50.4]
Models B248-B250 2” 50 4.21” [107.0] 2.21” [56.2]
ARB24-3 B251-B254 2” 50 4.93” [125.2] 2.68” [68.0]
ARB24-3-S w/built-in Aux. Switch B261-B265 2½” 65 5.55” [140.9] 2.68” [68.0]
ARX24-3 Flexible B277-B280 3” 80 5.82” [147.9] 2.68” [68.0]
ARX24-3-S Flexible w/built-in Aux. Switch
ARB24-3-5-14
ARX24-3-5-14 Dimensions with 3-Way Valve
D1360
Technical Data
Control on/off, floating point
Power supply 24 VAC ± 20% 50/60 Hz
24 VDC ± 10% D C
Power consumption running 2.5 W
holding 0.2 W H1 H2
Transformer sizing 5.5 VA (class 2 power source)
Electrical connection ½” conduit connector
18 GA plenum rated cable E F B
ARB24-3... 3 ft. [1m] A
AR...24-3-S
Auxiliary switch (-S models) 1 x SPDT, 3A (0.5A) @ 250 VAC, UL Listed,
adjustable 0 to 90°
† Rated impulse voltage 800V, Control pollution degree 3, Type of action 1
(1.B for -S models)
48
AR...24-3 Actuators, On/Off, Floating Point
D1373
2 CAUTION Equipment damage!
D Actuators may be connected in parallel.
I Power consumption and input impedance must be observed.
C For end position indication, interlock control, etc.,
3 ARB24-3-S incorporates one built-in auxiliary switches:
1 x SPDT, 3A (0.5A) @250 VAC, UL listed, adjustable 0° to 95°.
4 Actuators may also be powered by 24 VDC.
G
B
E F A Meets cULus or UL and CSA requirements without the
need of an
On-off electrical
control ground connection.
of ARB24-3
ARB, ARX
WARNING Live Electrical Components!
Nominal Top During installation, testing, servicing and troubleshooting of this product, it may
Valve Flange Face-to-Face be necessary to work with live electrical components. Have a qualified licensed electrician
Pipe Flange Height
Body Diameter Length or other individual who has been properly trained in handling live electrical components
Size Design
perform these tasks. Failure to follow all electrical safety precautions when exposed to live
A B C electrical components could result in death or serious injury.
B6250 2½" [65] 7.50" [190.5] 5.50" [139.7] 8.10" [205.4]
WARNING
B6300 3" [80] F05 8.00" [203.2] 6.60" [167.6] 8.40" [213.1] Live Electrical Components!
During installation, testing, servicing and troubleshooting of this product, it maybe
necessary to work with live electrical components. Have a qualified licensed electrician
B6400 4" [100] 9.00" [228.6] 8.30" [210.8] 9.30" [235.9] or other individual who has been properly trained in handling live electrical components
Floating pointperform
or on-off control
these tasks. Failure of ARB24-3
to follow all electrical safety precautions when exposed
to live electrical components could result in death or serious injury.
W409
24 VAC Transformer 2
4
Line Blk (1) Common –
Volts Red (2) +
a open a
Wht (3) +
a closed
perform these tasks. Failure to follow all electrical safety precautions when exposed
to live electrical components could result in death or serious injury.
W411
24 VAC Transformer 2
4
Notes:
Wht (3) +
1 Provide overload protection and disconnect as required.
The indication
2 Actuators may alsoof direction
be powered by 24 VDC.
1 0
Auxiliary switch
Notes:
D1359
D C
H1 H2
E F B
A
ARB, ARX
Valve Nominal Size Dimensions (Inches [mm])
Valve Body Inches DN [mm] A B
B231-B232 1¼” 32 3.72” [94.6] 2.04” [51.9]
B238-B240 1½” 40 3.88” [98.5] 2.04” [51.9]
B248-B250 2” 50 4.21” [107.0] 2.27” [57.7]
Models
ARB24-SR
ARX24-SR Flexible Version Dimensions with 3-Way Valve
D1360
Technical Data
Power supply 24 VAC ± 20% 50/60 Hz
24 VDC ± 10%
Power consumption running 2.5 W C
D
holding 0.4 W
Transformer sizing 5 VA (class 2 power source) H1 H2
Electrical connection ½” conduit connector
18 GA plenum rated cable
3 ft [1m], 10 ft [3m], 16 ft [5m]
E F B
Overload protection electronic throughout 0° to 95° rotation
A
Operating range Y 2 to 10 VDC, 4 to 20 mA
Feedback output U 1 to 10 VDC, max 0.5 mA ARB, ARX
Input impedance 100 kΩ (0.1 mA), 500 Ω Valve Nominal Size Dimensions (Inches [mm])
Angle of rotation 90°, adjustable with mechanical stop Valve Body Inches DN [mm] A B C
50
AR...24-SR
WARNING
Actuators, Proportional
Live Electrical Components!
During installation, testing, servicing and troubleshooting of this product, it maybe
necessary to work with live electrical components. Have a qualified licensed electrician
or other individual who has been properly trained in handling live electrical components
perform these tasks. Failure to follow all electrical safety precautions when exposed
to live electrical components could result in death or serious injury.
Wiring Diagrams
W408
24 VAC Transformer 2
2 to 10 VDC control
or other individual who has been properly trained in handling live electrical components
perform these tasks. Failure to follow all electrical safety precautions when exposed
or other individual who has been properly trained in handling live electrical components
perform these tasks. Failure to follow all electrical safety precautions when exposed
to live electrical components could result in death or serious injury. to live electrical components could result in death or serious injury.
The ZG-R01 500 Ω resistor converts the 4 to 20 mA control signal to
W408
2 to 10 VDC, up to 2 actuators may be connected
24 VACinTransformer
parallel. 2 24 VAC Transformer 2
5 To other ARB24-SR
actuators
Notes:
4 to 20 mA control 1 Provide overload protection and d
Actuators may be connected in pa
2 consumption and input impedanc
3 Actuator may also be powered by
The ZG-R01 500Ω resistor conve
4 control signal to 2 to 10 VDC, up
be connected in parallel.
5 Only connect common to neg. (–)
Notes:
W408
51
AR...120-3 Actuators, On/Off, Floating Point
D1361
D C
H1 H2
E F B
A
D1362
Power supply 100 to 240 VAC, 50/60 Hz (nominal)
85 to 265 VAC, 50/60 Hz (tolerance)
Power consumption running 3 W
holding 0.6 W
D C
Transformer sizing 7 VA (class 2 power source)
Electrical connection ½” conduit connector H1 H2
18 GA appliance rated cable
ARB120-3 3 ft [1m]
ARX120-3 3 ft [1m], 10 ft [3m], 16 ft [5m]
Overload protection electronic throughout 0° to 95° rotation E F B
A
Input impedance 600 Ω
52
AR...120-3 Actuators, On/Off, Floating Point
D1373
1 Provide overload protection and disconnect as required.
D
I
2 CAUTION Equipment damage!
C Actuators may be connected in parallel.
Power consumption and input impedance must be observed.
W414
B6250 2½" [65] 7.50" [190.5] 5.50" [139.7] 8.10" [205.4]
B6300 3" [80] F05 8.00" [203.2] 6.60" [167.6] 8.40" [213.1]
B6400 4" [100] 9.00" [228.6] 8.30" [210.8] 9.30" [235.9]
On/Off control
W415
P10419 - 09/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
53
AR...120-SR Actuators
D1361
D C
H1 H2
E F B
A
Models
ARB120-SR Dimensions with 3-Way Valve
ARX120-SR Flexible Version
D1362
Technical Data
Control on/off, floating point
Power supply 100 to 240 VAC, 50/60 Hz (nominal) D C
85 to 265 VAC, 50/60 Hz (tolerance)
Power consumption running 3 W H1 H2
holding 0.6 W
Transformer sizing 7.5 VA (class 2 power source)
Electrical connection ½” conduit connector E F B
18 GA plenum rated cable A
ARB120-SR 3 ft [1m]
ARX120-SR 3 ft [1m], 10 ft [3m], 16 ft [5m] ARB, ARX
Valve Nominal Size Dimensions (Inches [mm])
Overload protection electronic throughout 0° to 95° rotation
Valve Body Inches DN [mm] A B C
Feedback output U 1 to 10 VDC, max 0.5 mA
B329-B331 1¼” 32 3.96” [100.6] 2.27” [57.7] 2.14” [54.3]
54
WARNING
Live Electrical Components!
AR...120-SR Actuators
During installation, testing, servicing and troubleshooting of this product, it may be
necessary to work with live electrical components. Have a qualified licensed electrician
or other individual who has been properly trained in handling live electrical components
perform these tasks. Failure to follow all electrical safety precautions when exposed
to live electrical components could result in death or serious injury.
Wiring Diagrams
W365
100 to 240 VAC
15 2 19
N L1 1 Neutral
CAUTION Equipment damage!
Cable 2
2 H L2 2 Hot +
Actuators may be connected in parallel.
Power consumption and input impedance must be observed.
6 1 Common
6 Only connect common to neg. (–) leg of control circuits.
2 Hot +
7 8
Cable 1
7 A 500 Ω resistor converts the 4 to 20 mA control signal to 2 to 10 VDC.
(–)
Control Signal
VDC/mA (+) 3 Y Input, 2 to 10V
15 ARB(X) can be supplied with both 120 VAC and 230 VAC.
2 to 10 VDC (–)
Feedback Signal (+) 5 U Output, 2 to 10V
19 All 120 VAC and 230 VAC actuators use appliance rated cables.
1 0
55
AR...24-MFT Actuators, Multi-Function Technology
D1361
D C
H1 H2
E F B
A
D1362
Power supply 24 VAC ± 20% 50/60 Hz
24 VDC ± 10%
Power consumption running 4 W
holding 1.25 W
Transformer sizing 6 VA (class 2 power source) D C
Electrical connection ½” conduit connector
18 GA plenum rated cable H1 H2
ARX24-MFT 3 ft. [1m], 10 ft. [3m], 16 ft. [5m]
Overload protection electronic throughout 0° to 95° rotation
Operating range Y 2 to 10 VDC, 4 to 20 mA (default) E F B
variable (VDC, PWM, floating point, on/off) A
Feedback output U 2 to 10 VDC, 0.5 mA max
56
AR...24-MFT Actuators, Multi-Function Technology
Dimensions
W538
D1374
D
I
C
G On/Off control
W538
B
E F A
ARB, ARX
Nominal Top
Valve Flange Face-to-Face
Pipe Flange Height
Body Diameter Length
Size Design
A B C
B6250 2½" [65] 7.50" [190.5] 5.50" [139.7] 8.10" [205.4]
Floating Point
B6300 3" [80] F05 8.00" [203.2] 6.60" [167.6] 8.40" [213.1]
W538
B6400 4" [100] 9.00" [228.6] 8.30" [210.8] 9.30" [235.9]
Wiring Diagrams
W538
Position feedback cannot be used with Triac sink controller.
4
The actuator internal common reference is not compatible.
P10419 - 09/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
PWM
The ZG-R01 500 Ω resistor converts the 4 to 20 mA control signal to
2 to 10 VDC, up to 2 actuators may be connected in parallel.
57
ARX24-PC Actuators, Phasecut
D1361
D C
H1 H2
E F B
A
D1362
24 VDC ± 10%
Power consumption running 4 W
holding 1.25 W
Transformer sizing 5.5 VA (Class 2 power source)
Electrical connection ½” conduit connector D C
18 GA plenum rated cable
3 ft. [1m], 10 ft. [3m], 16 ft. [5m] H1 H2
Overload protection electronic throughout 0 to 95° rotation
Operating range Y 0 to 20V phasecut
Feedback output U 2 to 10 VDC, 0.5mA max E F B
VDC variable A
Input impedance 8 kΩ (50 mW)
ARB, ARX
58
ARX24-PC Actuators, Phasecut
Wiring Diagrams
W185
1
24 VAC Transformer
W185
59
ARX24-MFT95 Actuators, 0 to 135 Ω
D1361
D C
H1 H2
E F B
A
D1362
24 VDC ± 10%
Power consumption running 4 W
holding 1.25 W
Transformer sizing 6 VA (Class 2 power source) D C
Electrical connection ½” conduit connector
18 GA plenum rated cable H1 H2
3 ft [1m], 10 ft [3m], 16 ft [5m]
Overload protection electronic throughout 0 to 95° rotation
Operating range WRB 0 to 135 Ω Honeywell Electronic E F B
Series 90, 0 to 135 Ω input A
Feedback output U 2 to 10 VDC, 0.5mA max
Input impedance 100 kΩ (0.1 mW) ARB, ARX
Valve Nominal Size Dimensions (Inches [mm])
60
ARX24-MFT95 Actuators, 0 to 135 Ω
S963A
24 VAC Minimum Pos
Transformer Potentiome
1
Wiring Diagrams Switch A Switch B Damper Position
Line
Damper Open
Volts
Damper Closed Series 90
Controller
The direction of rotation switch is set so that the fail safe position and the
B R B W
position of the damper is closed with no signal at wire R.
3 135 4 R
B
information. 5 B
…MFT95 1
4 actuators. No resistor is used for one actuator. Honeywell resistor 1
24 VAC Transformer
Line
kits may also be used. Line 1 Common Volts
Volts 2 + Hot 3
2
5 To reverse control rotation, use the reversing switch. A 4
W 3 W
Line R 4 R
or other individual who has been properly trained in handling live electrical components
perform these tasks. Failure to follow all electrical safety precautions when exposed to live Override Wiring multiple actuato
Series 90 controller usi
electrical components could result in death or serious injury.
minimum position pote
S963A
24 VAC Minimum Position
Transformer Potentiometer
1 24 VAC Transformer
1
Switch A Switch B Damper Position
Line
Notes: 1 Common Line
Damper Open
Volts 2 + Hot Volts
Damper Closed Series 90
1
Controller
Provide overload protection and
5
disconnect as required.
R B W 2
The direction of rotation switch is set so that the fail safe position and the
B 3 W W W B R
position of the damper is closed with no signal at wire R.
R
2 Actuators and controller
4 R must have separate transformers
Series 90 R
2
24 VAC Transformer 5 B Controller
W B
1 Shunting
Resistor
6 ‘U5’ Output 2-10 VDC
1 Common 3 Series 90 low limit contro
3 Consult controller instruction data for more135detailed
Line
4 for 0 to 50% control
Volts 2 + Hot 3 …MFT95 280 for 0 to 100% control
B R Winstallation information.
A 4
H205 Change- Occupied
3 W
over Controller Contact Low Limit Contro
135 4 R
B
5 B
6 ‘U5’ Output 2-10 VDC
24 VAC Transformer
1 1
24 VAC Transformer …MFT95
1 Line 1 Common Line
3
Line 1 Common Volts 2 + Hot Volts
Volts 2 + Hot 3 5
2
4 2
A 3 W W
W 3 W
Line 4 R Series 90 R
R 4 R
Volts B 5 B Controller R W B
B
P10419 - 09/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
B 5 B
2 Controller 6 ‘U5’ Output 2-10 VDC 6 ‘U5’ Output 2-10 VDC
To other Series 90 high limit control - 2
…MFT95 actuators …MFT95
Notes:
S963A
24 VAC Minimum Position
Potentiometer
1
Transformer
1 Provide overload protection and disconnect
1
24 VACas required.
Transformer 4 Resistor value depends on the
Switch A Switch B Damper Position
Line 1 Common 1 Common
the number of actuators. No r
Line
Damper Open
Volts 2 Actuators and controller
2 + Hot must have Volts
separate transformers. 2 + Hot actuator.
3 Honeywell resistor k
Damper Closed Series 90 5
Controller 5
R B W 2
The direction of rotation switch is set so that the fail safe position and the
position of the damper is closed with no signal at wire R.
B
Consult controller
3 W
instruction data for more Rdetailed
W W B R 3 W
5 To reverse control rotation, use
R 3 4 R
Series 90
4 R
2
24 VAC Transformer W
installation information.
5 B Controller
B 5 B
1 Shunting
Resistor
6 ‘U5’ Output 2-10 VDC 6 ‘U5’ Output 2-10 VDC
Line 1 Common 3 Series 90 low limit control
4 135 for 0 to 50% control
Volts 2 + Hot 3 …MFT95 280 for 0 to 100% control …MFT95
B R W
A 4
H205 Change- Occupied
3 W
over Controller Contact Low Limit Control
135 4 R
B
5 B
6 ‘U5’ Output 2-10 VDC
24 VAC Transformer
1 1
24 VAC Transformer …MFT95
1 Line 1 Common Line 1 Common
3
Line 1 Common Volts 2 + Hot Volts 2 + Hot 3
Volts 2 + Hot 3 5
2 5
4 2
A 3 W W 3 W
W 3 W
Line 4 R R 4 R
R 4 R Series 90
Volts B 5 B Controller R W B 5 B
B 5 B B
2 Controller 6 ‘U5’ Output 2-10 VDC 6 ‘U5’ Output 2-10 VDC 6 ‘U5’ Output 2-10 VDC
To other Series 90 high limit control - 280
…MFT95 actuators …MFT95 …MFT95
D1363
D C
E F B
A
ARB N4, ARX N4, NRB N4, NRX N4
Valve Nominal Size Dimensions (Inches [mm])
Valve Body Inches DN [mm] A B
Models B231-B232 1¼” 32 3.72” [94.6] 2.04” [51.9]
ARB24-3-T N4 B238-B240 1½” 40 3.88” [98.5] 2.04” [51.9]
ARB24-3-T N4H w/built in heater B248-B250 2” 50 4.21” [107.0] 2.27” [57.7]
ARX24-3-T N4 B251-B254 2” 50 4.93” [125.2] 2.73” [69.5]
ARX24-3-T N4H w/built in heater B261-B265 2½” 65 5.55” [140.9] 2.73” [69.5]
B277-B280 3” 80 5.82” [147.9] 2.73” [69.5]
Technical Data
Control on/off, floating point
Dimensions with 3-Way Valve1363
Power supply 24 VAC ± 20% 50/60 Hz
D1364
24 VDC ± 10%
Power consumption running 2.5 W / heater 23 W
holding 0.5 W
Transformer sizing 5.5 VA (class 2 power source) / heater 20.5 VA
Electrical connection screw terminal (for 26 to 14 GA wire)
Overload protection electronic throughout 0° to 95° rotation D C
Input impedance 600 Ω
Angle of rotation 90°, adjustable with mechanical stop
Direction of rotation reversible with switch
Position indication visual pointer
62
ARB24-3-T N4, ARX24-3-T N4 NEMA 4X Actuators,
WARNING
On/Off, Floating Point Live Electrical Components!
During installation, testing, servicing and troubleshooting of this product, it maybe
necessary to work with live electrical components. Have a qualified licensed electrician
or other individual who has been properly trained in handling live electrical components
Floating pointperform
or on-offthese tasks. Failure to follow all electrical safety precautions when exposed
control of ARB24-3
to live electrical components could result in death or serious injury.
Wiring Diagrams
W409
24 VAC Transformer 2
4
Line Blk (1) Common –
On/Off control or other individual who has been properly trained in handling live electrical components
perform these tasks. Failure to follow all electrical safety precautions when exposed
to live electrical components could result in death or serious injury.
W411
Meets cULus or UL and CSA requirements without the 24 VAC Transformer 2
4
need of an electrical ground connection.
Line Blk (1) Common –
M
m with actuator types ..-3
Notes: Legend:
1
N L L N L M = actuator
1 Provide overload protection and disconnect as required.
2 T (°C) = Thermostat
1 2 3 2 Actuators may also be powered byH24
= Heating
VDC.
M
T
1 <x <x
>x >x
2
P10419 - 09/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
x = 0 ... 100% 1 2
T H
(°C)
Note
M
1 The ffollowing points must be taken into account
N L L N L
with independent, external wiring:
2
• All contact between the cables or wires that
1 2 3 S1 S2 isS3
are introduced and the heating element
W411
to beS4 S5 S6
avoided.
• Where necessary, use cables with sufficient
<x
T numbers of wires, e.g. so that the heating and the <x
N L N L >x
actuator can be supplied separately with voltage.
>x
T H x = 0 ... 100%
(°C)
1 2 3 5 1 2
Heater wiring
M
1
2
T H
(°C)
M T 1
N L N L
2
1 2 3 5 1 2
T H
(°C)
M
1
2
800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA / CARIBBEAN
63
ARB24-SR-T N4, ARX24-SR-T N4 NEMA 4X Actuators, Proportional
D1363
D C
E F B
A
ARB N4, ARX N4, NRB N4, NRX N4
Valve Nominal Size Dimensions (Inches [mm])
Valve Body Inches DN [mm] A B
Models B231-B232 1¼” 32 3.72” [94.6] 2.04” [51.9]
ARB24-SR-T N4 B238-B240 1½” 40 3.88” [98.5] 2.04” [51.9]
ARB24-SR-T N4H w/built in heater B248-B250 2” 50 4.21” [107.0] 2.27” [57.7]
ARX24-SR-T N4 B251-B254 2” 50 4.93” [125.2] 2.73” [69.5]
ARX24-SR-T N4H w/built in heater B261-B265 2½” 65 5.55” [140.9] 2.73” [69.5]
B277-B280 3” 80 5.82” [147.9] 2.73” [69.5]
Technical Data
Power supply 24 VAC ± 20% 50/60 Hz Dimensions with 3-Way Valve1363
24 VDC ± 10%
D1364
Power consumption running 2.5 W / heater 23 W
holding 0.4 W
Transformer sizing 5 VA (class 2 power source) / heater 20 VA
Electrical connection screw terminal (for 26 tp 14 GA wire)
Overload protection electronic throughout 0° to 95° rotation D C
Operating range Y 2 to 10 VDC, 4 to 20 mA
Input impedance 600 Ω
Angle of rotation 90°, adjustable with mechanical stop
Direction of rotation reversible with switch
Position indication visual pointer E F B
64
N L L N L
1 2 3
ARB24-SR-T N4, ARX24-SR-T N4 NEMA 4X Actuators, Proportional
N
1
Wiring Diagrams Wiring Diagrams(°C)T H
M
m with actuator types ..-3
Legend:
1
2 CAUTION Equipment damage! N L L N L M = actuator
Actuators may be connected in parallel. 2 T (°C) = Thermostat
Power consumption and input impedance must be observed. 1 2 3 H = Heating
W408-SR-T
2
T H
(°C)
M T 1
N L N L
2
1 2 3 5 1 2
P10419 - 09/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
2 to 10 VDC control
T H
W408-SR-T
(°C)
M
1
2
4 to 20 mA control
65
ARX24-MFT-T N4 NEMA 4X Actuators, Multi-Function Technology
D1363
D C
E F B
A
ARB N4, ARX N4, NRB N4, NRX N4
Valve Nominal Size Dimensions (Inches [mm])
Valve Body Inches DN [mm] A B
B231-B232 1¼” 32 3.72” [94.6] 2.04” [51.9]
Models
ARX24-MFT-T N4 B238-B240 1½” 40 3.88” [98.5] 2.04” [51.9]
ARX24-MFT-T N4H w/built in heater B248-B250 2” 50 4.21” [107.0] 2.27” [57.7]
B251-B254 2” 50 4.93” [125.2] 2.73” [69.5]
B261-B265 2½” 65 5.55” [140.9] 2.73” [69.5]
Technical Data B277-B280 3” 80 5.82” [147.9] 2.73” [69.5]
Control 2 to 10 VDC, 4 to 20 mA (default)
variable (VDC, PWM, floating point, on/off)
Power supply 24 VAC ± 20% 50/60 Hz Dimensions with 3-Way Valve1363
24 VDC ± 10%
D1364
Power consumption running 3.5 W / heater 24 W
holding 1.25 W
Transformer sizing 6 VA (class 2 power source) / heater 21 VA
Electrical connection screw terminal (for 26 tp 14 GA wire)
Overload protection electronic throughout 0° to 95° rotation
D C
Input impedance 100 kΩ for 2 to 10 VDC (0.1 mA)
500 Ω for 4 to 20 mA
1500 Ω for PWM, floating point and
on/off control
Angle of rotation 95°, adjustable with mechanical stop
E F B
66
ARX24-MFT-T N4 NEMA 4X Actuators, Multi-Function Technology
Wiring Diagrams
W538
2 CAUTION Equipment damage!
Actuators may be connected in parallel.
Power consumption and input impedance must be observed.
W538
Contact closures A & B also can be triacs.
8 A& B should both be closed for triac source and open for triac sink.
For triac sink the common connection from the actuator
9 must be connected to the hot connection.
T H
(°C)
W538
perform these tasks. Failure to follow all electrical safety precautions when exposed to live N L L N L
electrical components could result in death or serious injury.
1 2 3 S1 S2 S3 S4 S5 S6
T H
(°C)
<x <x
M
m with actuator types ..-3
Legend: >x >x
1
N L L N L M = actuator T H x = 0 ... 100%
2 T (°C) = Thermostat (°C)
1 2 3 H = Heating
M
VDC/4-20 mA 1
2
W538
N L L N L
T H
P10419 - 09/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
1 2 3 (°C) S1 S2 S3 S4 S5 S6
M
T
N L N L
1 <x <x
>x >x
2 1 2 3 5 1 2
T H x = 0 ... 100%
(°C)
Note
M
1 The ffollowing points must be taken into account
N L L N L T H
with independent, external wiring:
2 PWM (°C)
• All contact between the cables or wires that
1 2 3 S1 S2 isS3
are introduced and the heating element to beS4 S5 S6
avoided. M
• Where necessary, use cables with sufficient 1
<x
T numbers of wires, e.g. so that the heating and the <x 2
N L N L >x
actuator can be supplied separately with voltage.
>x
T H x = 0 ... 100%
(°C)
1 2 3 5 1 2
Heater wiring
M
1
2
T H
(°C)
M T 1
N L N L
2
1 2 3 5 1 2
T H
(°C)
800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA / CARIBBEAN
M
1 67
ARQX24-1 Quick Running Actuators, On/Off
D1375
D C
H1 H2
E F B
A
ARQB, ARQX
Valve Nominal Size Dimensions (Inches [mm])
Valve Body Inches DN [mm] A B
B248-B280 2” 50 4.21” [107] 2.27” [57.7]
Models
ARQX24-1 Flexible Version Dimensions with 3-Way Valve
D1376
Technical Data
Control on/off
Power supply 24 VAC ± 20% 50/60 Hz
24 VDC ± 10% D
C
Power consumption running 15 W
holding 1.5 W H1 H2
Transformer sizing 26 VA (Class 2 power source)
Electrical connection ½” conduit connector,
18 GA plenum rated cable
3 ft [1m], 10 ft [3m], 16 ft [5m] E F B
Overload protection electronic throughout 0 to 95° rotation A
Input impedance 100 Ω ARQB, ARQX
Angle of rotation max 95°, adjustable with mechanical stop Valve Nominal Size Dimensions (Inches [mm])
Direction of rotation reversible with switch Valve Body Inches DN [mm] A B C
Position indication reflective visual indicator (snap-on) B330-B332 1¼” 32 3.96” [100.6] 2.27” [57.7] 2.14” [54.3]
Manual override external push button B338-B340 1½” 40 4.39” [111.6] 2.51” [63.7] 2.90” [61.1]
68
ARQ...24-1
Wiring Diagrams
W403-ARQ-08
1 Provide overload protection and disconnect as required.
ARQ...24-1
Meets cULus or UL and CSA requirements without the
need of an electrical ground connection.
ARQX24-1
WARNING Live Electrical Components!
During installation, testing, servicing and troubleshooting of this product, it may
be necessary to work with live electrical components. Have a qualified licensed electrician
or other individual who has been properly trained in handling live electrical components
perform these tasks. Failure to follow all electrical safety precautions when exposed to live
electrical components could result in death or serious injury.
W403-ARQ-08
P10419 - 09/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
69
ARQX24-MFT Quick Running Actuators, Multi-Function Technology
D149-2A
Valve Nominal Size Dimensions (Inches [mm])
Valve Body Inches DN [mm] A B
B231-B232 1¼” 32 3.72” [94.6] 2.04” [51.9]
Models B238-B240 1½” 40 3.88” [98.5] 2.04” [51.9]
ARQX24-MFT Flexible Version B248-B250 2” 50 4.21” [107.0] 2.21” [56.2]
B251-B254 2” 50 4.93” [125.2] 2.68” [68.0]
B261-B265 2½” 65 5.55” [140.9] 2.68” [68.0]
Technical Data
B277-B280 3” 80 5.82” [147.9] 2.68” [68.0]
Power supply 24 VAC ± 20% 50/60 Hz
24 VDC ± 10%
Power consumption running 15 W Dimensions with 3-Way Valve
holding 1.5 W
D149A
Transformer sizing 26 VA (Class 2 power source)
Electrical connection ½” conduit connector,
18 GA plenum rated cable
3 ft [1m], 10 ft [3m], 16 ft [5m]
Overload protection electronic throughout 0 to 95° rotation
Operating range Y 2 to 10 VDC, 4 to 20 mA (default)
variable (VDC, on/off)
Feedback output U 2 to 10 VDC, 0.5mA max
VDC variable
Input impedance 100 kΩ (0.1 mA), 500 Ω, 1500 Ω
(on/off)
70
ARQX24-MFT Quick Running Actuators, Multi-Function Technology
Wiring Diagrams
W399_08
1 Provide overload protection and disconnect as required.
2
CAUTION Equipment damage!
Actuators may be connected in parallel.
Power consumption and input impedance must be observed.
VDC/4-20 mA
W399_08
The ZG-R01 500 Ω resistor may be used.
On/Off control
P10419 - 09/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
71
GRB24-3, GRX24-3 Actuators, On/Off, Floating Point
Dimensions
D1377
D
I C
B
E F A
GRB, GRX
Nominal Top
Valve Flange Face-to-Face
Pipe Flange Height
Models Body
Size Design
Diameter Length
GRB24-3-5-14
GRX24-3-5-14 A B C
B6400 4” [100] 9.00” [228.6] 8.30” [210.8] 9.30” [235.9]
B6500 5" [125] 10.00" [254] 10.30" [261.6] 10.50" [266.4]
Technical Data F05
B6600 6" [150] 11.00" [279.4] 12.50" [317.5] 11.70" [296.9]
Control on/off, floating point
Power supply 24 VAC ± 20% 50/60 Hz
Power consumption running 4 W
holding 2 W
Transformer sizing 6 VA (Class 2 power source)
Electrical connection 3 ft,18 GA plenum rated cable
½” conduit connector
GRX 3 ft. [1m], 10 ft. [3m], 16 ft. [5m]
Overload protection electronic throughout 0° to 95° rotation
Input impedance 600 Ω
Angle of rotation max. 95°, adjustable with mechanical stop
72
GRB24-3, GRX24-3 Actuators, On/Off, Floating Point
Wiring Diagrams
W254_08
1 Provide overload protection and disconnect as required.
W255_08
perform these tasks. Failure to follow all electrical safety precautions when exposed to live
electrical components could result in death or serious injury.
73
GRB120-3, GRX120-3
Dimensions
D1377
D
I C
B
E F A
GRB, GRX
Nominal Top
Valve Flange Face-to-Face
Pipe Flange Height
Models Body
Size Design
Diameter Length
GRB120-3
GRX120-3 A B C
B6400 4” [100] 9.00” [228.6] 8.30” [210.8] 9.30” [235.9]
B6500 5" [125] 10.00" [254] 10.30" [261.6] 10.50" [266.4]
Technical Data F05
B6600 6" [150] 11.00" [279.4] 12.50" [317.5] 11.70" [296.9]
Power Supply 100 to 240 VAC, 50/60 Hz (nominal)
85 to 265 VAC, 50/60 Hz (tolerance)
Power consumption running 4 W
holding 2 W
Transformer sizing 7 VA (Class 2 power source)
Electrical connection 18 GA appliance rated cable
½” conduit connector
3 ft. [1m], 10 ft. [3m], 16 ft. [5m]
Overload protection electronic throughout 0° to 95° rotation
Control on/off, floating point
Input impedance 600 Ω
74
GRB120-3, GRX120-3
Wiring Diagrams
W375_08
1 Provide overload protection and disconnect as required.
Actuators may be connected in parallel.
2 Power consumption and input impedance must be observed.
W376_08
perform these tasks. Failure to follow all electrical safety precautions when exposed to live
electrical components could result in death or serious injury.
75
GRX24-MFT Actuators, Multi-Function Technology
Dimensions
D1377
D
I C
B
E F A
GRB, GRX
Nominal Top
Valve Flange Face-to-Face
Pipe Flange Height
Body Diameter Length
Size Design
Models A B C
GRX24-MFT-5-14 B6400 4” [100] 9.00” [228.6] 8.30” [210.8] 9.30” [235.9]
B6500 5" [125] 10.00" [254] 10.30" [261.6] 10.50" [266.4]
Technical Data F05
B6600 6" [150] 11.00" [279.4] 12.50" [317.5] 11.70" [296.9]
Control 2 to 10 VDC, 4 to 40 mA (default)
variable (VDC, PWM, floating point, on/off)
Power supply 24 VAC ± 20% 50/60 Hz
24 VDC ± 10%
Power consumption running 4.5 W
holding 1.5 W
Transformer sizing 7 VA (Class 2 power source)
Electrical connection 3 ft,18 GA plenum rated cable
½” conduit connector
3 ft. [1m], 10 ft. [3m], 16 ft. [5m]
Overload protection electronic throughout 0° to 95° rotation
76
GRX24-MFT Actuators, Multi-Function Technology
Wiring Diagrams
W399_08
1 Provide overload protection and disconnect as required.
W399_08
Contact closures A & B also can be triacs.
8 A & B should both be closed for triac source and open for triac sink.
For triac sink the common connection from the actuator
9 must be connected to the hot connection of the controller.
W399_08
or other individual who has been properly trained in handling live electrical components
perform these tasks. Failure to follow all electrical safety precautions when exposed to live
electrical components could result in death or serious injury.
P10419 - 09/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
On/Off control
W399_08
77
TFRB(X) Actuators, On/Off
D1365
D C
E F
B
A
TFRB, TFRX
Valve Nominal Size Dimensions (Inches [mm])
Valve Body Inches DN [mm] A B
B207(B)-B211(B) ½” 15 2.41” [61.1] 1.39” [35.2]
B212(B)-B215(B) ½” 15 2.38” [60.4] 1.78” [45.2]
B217(B)-B221(B) ¾” 20 2.73” [69.3] 1.87” [47.4]
Models
TFRB(X)24 TFRB(X)120
TFRB(X)24-S TFRB(X)120-S w/built-in Aux. Switch
Dimensions with 3-Way Valve
Technical Data
D1366
Control on/off
Power supply
TFRB(X)24(-S) 24VAC ± 20%, 50/60Hz
24VDC ± 10%
TFRB(X)120(-S) (nominal) 100 to 240 VAC, 50/60 Hz D
(tolerance) 85 to 265 VAC, 50/60 Hz C
Power consumption running 2.5 W
holding 1.3 W
Transformer sizing
TFRB(X)24(-S) 5 VA (class 2 power source) E F B
TFRB(X)120(-S) 5 VA (class 2 power source) A
Electrical connection ½” conduit connector TFRB, TFRX
(-S models have 2 cables) 18 GA appliance cable Valve Nominal Size Dimensions (Inches [mm])
TFRB(X)...-S
Auxiliary switch 1 x SPDT, 3A (0.5A) @ 250 VAC, UL Listed
adjustable 0° to 95°
† Rated impulse voltage 800V (4kV for 120V model), Control pollution degree 3,
Type of action 1.AA (1.AA.B for -S models)
78
TFRB(X)
WARNING
Actuators, On/Off
Live Electrical Components!
During installation, testing, servicing and troubleshooting of this product, it maybe
necessary to work with live electrical components. Have a qualified licensed electrician
or other individual who has been properly trained in handling live electrical components
perform these tasks. Failure to follow all electrical safety precautions when exposed
to live electrical components could result in death or serious injury.
W237
24 VAC Transformer
1 Common
2 + Hot 3
2 CAUTION Equipment damage!
Actuators may be connected in parallel. WARNING
TFX24 US 2
Power consumption and input impedance must be observed. Live Electrical Components!
During installation, testing, servicing and troubleshooting of this product, it maybe
necessary to work with live electrical components. Have a qualified licensed electrician
3 Actuators may also be powered by 24 VDC. On/Off Wiring or other individual who has been properly trained in handling live electrical components
perform these tasks. Failure to follow all electrical safety precautions when exposed
to live electrical components could result in death or serious injury.
W217
100 to 240 VAC
Meets cULus or UL and CSA requirements without the N L1 1 Neutral
need of an electrical ground connection. 1 Provide
H L2 2 Hot as required.
overload protection and disconnect
W248
WARNING
1 Components!
Live Electrical
Provide overload protection and disconnect as required.
During installation, testing, servicing and S1
troubleshooting Actuators may
of this product, be connected in parallel. Power
it maybe
necessary2to work with live electrical
consumption must be observed.
NC
components. Have a qualified licensed S2
electrician or other individual who has been
Meets cULus requirements without S3 the need0°oftoan95°
3 electrical
properly trained in handling live electrical
ground connection. NO
components perform these tasks. Failure to
follow all electrical safety precautions when
exposed to live electrical components could TFX…-S US 2
result in death or serious injury.
Auxiliary Switch
W237
W248
79
TFRB(X)24-3 Actuators, Floating Point
D1365
D C
E F
B
A
TFRB, TFRX
Valve Nominal Size Dimensions (Inches [mm])
Valve Body Inches DN [mm] A B
B207(B)-B211(B) ½” 15 2.41” [61.1] 1.39” [35.2]
B212(B)-B215(B) ½” 15 2.38” [60.4] 1.78” [45.2]
B217(B)-B221(B) ¾” 20 2.73” [69.3] 1.87” [47.4]
Models
TFRB(X)24-3
TFRB(X)24-3-S w/built-in Aux. Switch
Dimensions with 3-Way Valve
D1366
Technical Data
Control floating point
Power supply 24VAC ± 20%, 50/60Hz
Power consumption running 2.5 W
holding 1.0 W D
Transformer sizing 4 VA (class 2 power source) C
Electrical connection ½” conduit connector
(-S models have 2 cables) 18 GA plenum rated cable
TFRB(X)24-3... 3 ft [1m]
10 ft [3m]
E F B
16 ft [5m]
A
Overload protection electronic throughout 0° to 95° rotation
TFRB, TFRX
Input impedance 1000 Ω (0.6w) control inputs
Valve Nominal Size Dimensions (Inches [mm])
Angle of rotation 95°
TFRB(X)24-3-S US
Auxiliary switch 1 x SPDT, 3A (0.5A) @ 250 VAC, UL Listed,
adjustable 0° to 95°
† Rated impulse voltage 800V (4kV for 120V model), Control pollution degree 3,
Type of action 1.AA (1.AA.B for -S models)
80
Floating point control of TF24-3 (-S) US
W240
24 VAC Transformer 7
xx
xx
xx
xx
xx
xx
~
xx
xx
xx
xx
Or (W4)
xx xx
b
xx xx
xx xx
x x
CCW CW
3 connected to the Hot connection of the controller.
Switch
Positions
a b
Direction of Rotation Switch
For end position indication, interlock control, fan startup, etc., The indication of direction is valid
for switch position CW.
5 TF24-3-S US incorporates one built-in auxiliary switch: 1 x SPDT, 3A
(0.5A) @250 VAC, UL listed, adjustable 0° to 95°. Floating point control
Actuators with plenum rated cable do not have numbers on wires; use
7
W242
color coded instead. Actuators with appliance rated cable use numbers. 24 VAC Transformer
WARNING Line
Live Electrical Components! Volts
During installation, testing,
servicing and troubleshooting
Meets cULus or UL and CSA requirements without the of this product, it maybe
2 7
need of an electrical ground connection. necessary to work with live
electrical components.Notes:
Have
Hot Com
a qualified licensed electrician
Blk (1) Common
WARNING Live Electrical Components! or other individual who has
been properly trained in 1 Provide overload protection and disconnect as required. Red (2) Hot ~
During installation, testing, servicing and troubleshooting of this product, it mayhandling live electrical
Triac Wht (W3) ~
components perform these sink
be necessary to work with live electrical components. Have a qualified licensed electrician tasks. Failure to follow all2 Actuators may be connected in parallel. Power consumption
Or must
(W4) be observed. ~
or other individual who has been properly trained in handling live electrical componentselectrical safety precautions
when exposed to live electrical
perform these tasks. Failure to follow all electrical safety precautions when exposed to live
components could result in
death or serious injury. 7
Actuators with plenum rated cable do not have numbers on wires;TF24-3
use (-S)
color
US codes instead.
electrical components could result in death or serious injury.
Controller The indication of direction
is valid for switch position CW.
Triac source
W243
24 VAC Transformer
WARNING Line
Live Electrical Components! Volts
During installation, testing,
servicing and troubleshooting
2 7
of this product, it maybe W240
necessary to work with live
electrical components. Have
Hot Com
a qualified licensed electrician
Blk (1) Common
or other individual who has
been properly trained in
Red (2) ~ Hot 3
handling live electrical
components perform these Notes: Wht (W3) ~ 4
tasks. Failure to follow all
Or (W4) ~
P10419 - 09/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
W241
WARNING
Live Electrical Components!
During installation, testing, servicing and S1 5
troubleshooting of this product, it maybe
NC
necessary to work with live electrical
components. Have a qualified licensed S2
electrician or other individual who has been
S3
properly trained in handling live electrical
NO W242
0° to 95°
Notes: components perform these tasks. Failure to
follow all electrical safety precautions when
exposed to live electrical components could TF24-3-S US
result in death or serious injury.
1 Provide overload protection and disconnect as required.
Auxiliary switch
Actuators may be connected in parallel. Power consumption
2 must be observed.
W243
800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA / CARIBBEAN
81
TFRB(X)24-SR Actuators, Proportional
D1365
D C
E F
B
A
TFRB, TFRX
Valve Nominal Size Dimensions (Inches [mm])
Valve Body Inches DN [mm] A B
B207(B)-B211(B) ½” 15 2.41” [61.1] 1.39” [35.2]
B212(B)-B215(B) ½” 15 2.38” [60.4] 1.78” [45.2]
B217(B)-B221(B) ¾” 20 2.73” [69.3] 1.87” [47.4]
Models
TFRB(X)24-SR
TFRB(X)24-SR-S w/built-in Aux. Switch
Dimensions with 3-Way Valve
D1366
Technical Data
Control proportional
Power supply 24 VAC ± 20%, 50/60 Hz
24 VDC ± 10%
Power consumption running 2.5 W D
holding 1.0 W C
Transformer sizing 4 VA (class 2 power source)
Electrical connection ½” conduit connector
(-S models have 2 cables) 18 GA plenum rated cable
TFRB(X)24-SR... 3 ft [1m]
10 ft [3m] E F B
16 ft [5m] A
Electrical protection actuators are double insulated TFRB, TFRX
Overload protection electronic throughout 0° to 95° rotation Valve Nominal Size Dimensions (Inches [mm])
TFRB(X)24-SR-S
Auxiliary switch 1 x SPDT, 3A (0.5A) @ 250 VAC, UL Listed,
adjustable 0° to 95°
† Rated impulse voltage 800V (4kV for 120V model), Control pollution degree 3,
Type of action 1.AA (1.AA.B for -S models)
82
TFRB(X)24-SR
WARNING
Actuators, Proportional
Live Electrical Components!
During installation, testing, servicing and troubleshooting of this product, it maybe
necessary to work with live electrical components. Have a qualified licensed electrician
or other individual who has been properly trained in handling live electrical components
perform these tasks. Failure to follow all electrical safety precautions when exposed
to live electrical components could result in death or serious injury.
Wiring Diagrams
W245
24 VAC Transformer 6
W246
24 VAC Transformer 6
Actuators with plenum rated cable do not have numbers on wires;
6 use color codes instead. Notes:
Line Blk (1) Common
3
For end position indication, interlock control, fan startup, etc., Volts Red (2) + Hot
1 Provide overload Ωprotection and disconnect as required.
7 TF24-SR-S US incorporates one built-in auxiliary switch: 1 x SPDT, 3A
4 to 20 mA (–) 500Ω
(0.5A ) @250 VAC, UL listed, adjustable 0° to 95°. Actuators may be connected in
2 Signal (+)
Control
parallel. Power consumption
Wht (3) Y1 Input, 2 to 10V
and input impedance must be observed.
4
Auxiliary switches of TF24-SR-S US
3 Actuator may also be powered by 24 VDC.
Meets cULus or UL and CSA requirements without the 5 2
To other
Actuators with actuators
plenum rated cable do not have numbers on
need of an electrical ground connection. 6 TF24-SR US
wires; use color codes instead.
W246
be necessary to work with live electrical components. Have a qualified licensed electrician
or other individual who has been properly trained in handling live electrical components
perform these tasks. Failure to follow all electrical safety precautions when exposed to live WARNING
electrical components could result in death or serious injury. Live Electrical Components!
Notes:During installation, testing, servicing and S1 7
troubleshooting of this product, it maybe
necessary to work with live electrical NC
1 Provide overload
components. protection
Have a qualified licensed S2 as required.
and disconnect
electrician or other individual who has been
Up totrained
properly 4 actuators
in handling may be connected in S3
live electrical parallel.
NO
0° to 95°
With
components perform these tasks. Failure to
2 4 actuators
follow all electrical wired to one 500Ω
safety precautions when resistor, a +2% shift of
controlto live
exposed signal may
electrical be required.
components could TF24-SR-S US
Power consumption
must
result be observed.
in death or serious injury. W245
Auxiliary switch3 Actuator may also be powered by 24 VDC.
A 500Ω resistor converts the 4… 20mA control
4 signal to 2 to 10 VDC. (ZG-R01)
For end position indication, interlock control, fan startup, etc.,
5 Only connect common toUS
7 TF24-SR-S neg. (–) leg of control
incorporates circuits.
one built-in auxiliary switch: 1 x
P10419 - 09/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
W247
W246
83
TFRX24-MFT Actuators, Multi-Function Technology
D1365
D C
E F
B
A
TFRB, TFRX
Valve Nominal Size Dimensions (Inches [mm])
Valve Body Inches DN [mm] A B
B207-B211 ½” 15 2.41” [61.1] 1.39” [35.2]
B212-B215 ½” 15 2.38” [60.4] 1.78” [45.2]
B217-B221 ¾” 20 2.73” [69.3] 1.87” [47.4]
Models
TFRX24-MFT
Dimensions with 3-Way Valve
Technical Data
D1366
Control MFT
Power supply 24 VAC ± 20% 50/60 Hz
24 VDC ± 10%
Power consumption running 2.5 W
holding 1.0 W D
Transformer sizing 4 VA (class 2 power source) C
Electrical connection ½” conduit connector
3 ft [1m], 18 GA plenum rated cable
Overload protection electronic throughout 0° to 95° rotation
Operating range Y* 2 to 10 VDC, 4 to 20 mA (default)
variable (VDC, PWM, floating point, on/off) E F B
Feedback output U* 2 to 10 VDC, 0.5 mA max A
Input impedance 100 kΩ for 2 to 10 VDC (0.1 mA) TFRB, TFRX
Valve Nominal Size Dimensions (Inches [mm])
84
TFRX24-MFT Actuators, Multi-Function Technology
Wiring Diagrams
W024
1 Provide overload protection and disconnect as required.
W025
P10419 - 09/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
4 to 20 mA Control Signal
85
LF Actuators, On/Off
D1367
D
C
E F B
A
LF
Valve Nominal Size Dimensions (Inches [mm])
Valve Body Inches DN [mm] A B
B207(B)-B211(B) ½” 15 2.41” [61.1] 1.39” [35.2]
Models
LF24 US B212(B)-B215(B) ½” 15 2.38” [60.4] 1.78” [45.2]
LF24-S US w/built-in Aux. Switch B217(B)-B220(B) ¾” 20 2.73” [69.3] 1.87” [47.4]
LF120 US B222-B225 1” 25 3.09” [78.4] 1.87” [47.4]
LF120-S US w/built-in Aux. Switch B229-B230 1¼” 32 3.72” [94.6] 1.87” [47.4]
D1368
Power supply
LF24(-S) US 24 VAC ± 20% 50/60 Hz
24 VDC ± 10%
LF120(-S) US 120 VAC ± 10% 50/60 Hz
Power consumption
LF24(-S) US running 5W D C
holding 2.5 W
LF120(-S) US running 5.5 W
holding 3.5 W
Transformer sizing
LF24(-S) US 7 VA, class 2 power source
E F B
LF...-S US
Auxiliary switch 1 x SPDT, 6A (1.5A) @ 250 VAC, UL Listed,
adjustable 0° to 95° (double insulated)
† Rated impulse voltage 800V (4kV for 120V model), Control pollution degree 3,
Type of action 1.AA (1.AA.B for -S models)
86
WARNING
Live Electrical Components!
LF Actuators, On/Off
During installation, testing, servicing and troubleshooting of this product, it maybe
necessary to work with live electrical components. Have a qualified licensed electrician
or other individual who has been properly trained in handling live electrical components
perform these tasks. Failure to follow all electrical safety precautions when exposed
to live electrical components could result in death or serious injury.
Wiring Diagrams
W047
24 VAC Transformer
Line 1 Common
Volts 2 + Hot 3
1 Provide overload protection and disconnect as required.
W049-LF-08
For end position indication, interlock control, fan startup, etc.,
4 LF24-S US and LF120-S US incorporates a built-in auxiliary switch:
1 x SPDT, 6A (1.5A) @ 250 VAC, UL listed, adjustable 0° to 95°.
W048-AUX
perform these tasks. Failure to follow all electrical safety precautions when exposed to live
electrical components could result in death or serious injury.
Auxiliary Switch
W047
P10419 - 09/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
87
LF24-3 Actuators, Floating Point
D1367
D
C
E F B
A
LF
Valve Nominal Size Dimensions (Inches [mm])
Valve Body Inches DN [mm] A B
Models B207(B)-B211(B) ½” 15 2.41” [61.1] 1.39” [35.2]
LF24-3 US B212(B)-B215(B) ½” 15 2.38” [60.4] 1.78” [45.2]
LF24-3-S US w/built-in Aux. Switch B217(B)-B220(B) ¾” 20 2.73” [69.3] 1.87” [47.4]
B222-B225 1” 25 3.09” [78.4] 1.87” [47.4]
B229-B230 1¼” 32 3.72” [94.6] 1.87” [47.4]
Technical Data
Power supply 24 VAC ± 20% 50/60 Hz
24 VDC ± 10% Dimensions with 3-Way Valve
Power consumption running 2.5 W
D1368
holding 1W
Transformer sizing 5 VA (class 2 power source)
Electrical connection ½” conduit connector
(-S models have 2 cables) 3 ft [1m], 18 GA appliance cable
Overload protection electronic throughout 0° to 95° rotation
Input impedance 1000 Ω (0.6w) control inputs D C
Angle of rotation 95°
Direction of rotation spring reversible with CW/CCW mounting
motor reversible with built-in switch
Position indication visual indicator 0° to 90°
Running time motor 150 seconds constant independent of load E F
LF24-3-S US
Auxiliary switch 1 x SPDT, 6A (1.5A) @ 250 VAC, UL Listed,
adjustable 0° to 95° (double insulated)
88
LF24-3 Actuators, Floating Point
Wiring Diagrams
W054
24 VAC Transformer
Line
Volts
5 The actuator Hot must be connected to the control board common. electrical safety precautions
when exposed to live electrical
components could result in Controller The indication of direction is
For end position indication, interlock control, fan startup, etc., death or serious injury.
valid for switch position CW.
W055
Actuators with plenum rated cable do not have numbers on wires; 24 VAC Transformer
Line
8 use color coded instead. Actuators with appliance rated cable use Volts
numbers. WARNING 2 8
Live Electrical Components!
During installation, testing, Hot Com
Triac sinkandwith
servicing separate transformers
troubleshooting Blk (1) Common 4
of this product, it maybe
Red (2) + Hot
Meets cULus or UL and CSA requirements without the necessary to work with live
Notes:
electrical components. Have 5
On-Off control ofneed of an
LF24-3 (-S)electrical
US ground connection. a qualified licensed electrician Wht (3) +
or other individual who has
been properly trained in Actuators may be connected in parallel. Power Grn consumption
(4) +
2
WARNING Live Electrical Components! handling live electrical
components perform these
must be observed.
CW CCW
During installation, testing, servicing and troubleshooting of this product, it may tasks. Failure to follow all
8 Actuators with plenum rated cable do not have numbersLF24-3(-S)
electrical safety precautions
on wires;US use color codes
be necessary to work with live electrical components. Have a qualified licensed electrician when exposed to live electricalActuators with appliance rated cable use numbers.
Controller
components could result in
or other individual who has been properly trained in handling live electrical components death or serious injury.
The indication of direction is valid for switch position CW.
perform these tasks. Failure to follow all electrical safety precautions when exposed to live
electrical components could result in death or serious injury.
Triac sink
W056
24 VAC Transformer 24 VAC Transformer
W061
24 VAC Transformer 8
8 Actuators with plenum rated cable do not have numbers on wires; use color codes instead.
WARNING Actuators with appliance rated cable use numbers.
Live Electrical Components!
Line Blk (1) Common
During installation, testing,
servicing and troubleshooting Volts Red (2) +
of this product, it maybe Notes:
necessary to work with live a Wht (3) +
Notes: electrical components. Have Installation Side
Actuators may be connected in parallel. Power consumption
a qualified licensed electrician
2 must be observed.
xx
xx
xx
xx
xx
xx xx
xx
Grn (4) +
xx xx
xx
b
xx
xx xx
x x
2 Actuators may
been properly be inconnected
trained
handling live electrical
in parallel.
Switch
CCW Power
CW consumption must be observed.
Direction of Rotation Switch
Positions
components perform these a b CW CCW 5 The actuator Hot must be connected to the control board Common.
tasks. Failure to follow all Auxiliary
(3) (4)switch
CW CC CCW ofCW LF24-3
CCW
CC (-S) US
3 Mayelectrical
also be powered by 24 VDC.
safety precautions LF24-3(-S) US
when exposed to live electrical stop stop stop stop
8
W055
Actuators with plenum rated cable do not have numbers on wires; use color codes instead.
components could result in
8 Actuators with plenum rated cable do not have numbers on wires; use color codes instead.
death or serious injury. The indication of direction
Actuators with appliance rated cable use numbers.
Actuators with appliance rated cable use numbers.
is valid for switch position CW.
WARNING
Live Electrical Components!
Notes: During installation, testing, servicing and S1 6
troubleshooting of this product, it maybe NC
necessary to work with live electrical
S2
2 Actuators may components.
be connected Have a qualified licensed
in parallel. Power
electrician or other individual who has been
consumption must be observed.
properly trained in handling live electrical
S3 0° to 95°
NO
components perform these tasks. Failure to
3 May also be powered by 24 VDC.
follow all electrical safety precautions when
LF24-3-S US W056
exposed to live electrical components could
result in death or serious injury. W051
8Actuators with plenum rated cable do not have numbers on wires; use color codes instead.
Auxiliary switchwith appliance rated cable use numbers.
Actuators
D1367
D
C
E F B
A
LF
Valve Nominal Size Dimensions (Inches [mm])
Valve Body Inches DN [mm] A B
B207(B)-B211(B) ½” 15 2.41” [61.1] 1.39” [35.2]
Models B212(B)-B215(B) ½” 15 2.38” [60.4] 1.78” [45.2]
LF24-SR US
LF24-SR-S US w/built-in Aux. Switch B217(B)-B220(B) ¾” 20 2.73” [69.3] 1.87” [47.4]
B222-B225 1” 25 3.09” [78.4] 1.87” [47.4]
B229-B230 1¼” 32 3.72” [94.6] 1.87” [47.4]
Technical Data
Control proportional
Control signal 2 to 10 VDC Dimensions with 3-Way Valve
4 to 20 mA (with 500 Ω resistor)
D1368
Power consumption running 2.5 W
holding 1W
Transformer sizing 5 VA, class 2 power
Electrical connection ½” conduit connector
(-S models have 2 cables) 3 ft [1m], 18 GA appliance cable
D C
Overload protection electronic throughout 0° to 95° rotation
Feedback output 2 to 10 VDC
Input impedance 100 kΩ
Angle of rotation 95°
Direction of rotation spring reversible with CW/CCW mounting
motor reversible with built-in switch E F B
LF24-SR-S US
Auxiliary switch 1 x SPDT, 6A (1.5A) @ 250 VAC, UL Listed,
adjustable 0° to 95° (double insulated)
90
LF24-SR
WARNING
Actuators, Proportional
Live Electrical Components!
During installation, testing, servicing and troubleshooting of this product, it maybe
necessary to work with live electrical components. Have a qualified licensed electrician
or other individual who has been properly trained in handling live electrical components
perform these tasks. Failure to follow all electrical safety precautions when exposed
to live electrical components could result in death or serious injury.
Wiring Diagrams
W057
4 to 20 mA control LF24-SR (-S) US with 2 to410 VDC feedback output
24 VACofTransformer
Actuators with plenum rated cable do not have numbers on wires; necessary to work with live electrical components. Have a qualified licensed electrician
4 2 to 10 VDC control or other individual who has been properly trained in handling live electrical components
use color codes instead. perform these tasks. Failure to follow all electrical safety precautions when exposed
to live electrical components could result in death or serious injury.
W059
5 Only connect common to neg. (–) leg of control circuits. 24 VAC Transformer 4
For end position indication, interlock control, fan startup, etc., Line Blk (1) Common
6 LF24-SR-S US incorporates one built-in auxiliary switch: 1 x SPDT, 6A Volts
3
Red (2) + Hot
(1.5A) @ 250 VAC, UL listed, adjustable 0° to 95°. Ω
Notes: 500Ω
4 to 20 mA (–)
7 The LF24-SR-S US wire 5 is white. Wht (3) Y1 Input, 2 to 10V
Signal (+) may be connected in
Control Actuators parallel. Power consumption
2
2 to 10and
VDCinput
(–) impedance must be observed.
Feedback Signal (+) Grn (5) U Output, 2 to 10V
3 Actuator may also be powered by 24 VDC.
5 CW CCW
The ZG-R01 500 Ω resistor converts the 4 to 20 mA control signal to To other
actuators 2
2 to 10 VDC, up to 2 actuators may be connected in parallel. Actuators with plenum rated cable do not have numbers on
Auxiliary switches of LF24-SR-S US
4 wires; use color codes instead. LF24-SR US
Meets cULus or UL and CSA requirements without the
need of an electrical ground connection. 4 to 20 mA control 7 The LF24-SR-S US wire 5 is white.
W058
WARNING Live Electrical Components!
During installation, testing, servicing and troubleshooting of this product, it may
WARNING
be necessary to work with live electrical components. Have a qualified licensed electrician Live Electrical Components!
or other individual who has been properly trained in handling live electrical components During installation, testing, servicing and S1 6
perform these tasks. Failure to follow all electrical safety precautions when exposed to live Notes:
troubleshooting of this product, it maybe
NC
necessary to work with live electrical
electrical components could result in death or serious injury. components. Have a qualified licensed S2
Up to 4 actuators may be connected in parallel. With
electrician or other individual who has been
2 properly
4 actuators wiredlive
trained in handling one 500Ω resistor, S3
to electrical a +2% shift0°
of to 95°
NO
control perform
components signalthesemay beFailure
tasks. required.
to Power consumption
follow all electrical safety precautions when
must be observed. W057
exposed to live electrical components could LF24-SR-S US
result in death or serious injury.
3 Actuator may also be powered by 24 VDC.
Auxiliary switch
Actuators with plenum rated cable do not have numbers
4 on wires; use color codes instead.
W059
W058
91
LF24-MFT Actuators, Multi-Function Technology
D1367
D
C
E F B
A
LF
Valve Nominal Size Dimensions (Inches [mm])
Valve Body Inches DN [mm] A B
B207-B211 ½” 15 2.41” [61.1] 1.39” [35.2]
Models
LF24-MFT US B212-B215 ½” 15 2.38” [60.4] 1.78” [45.2]
LF24-MFT-S US w/built-in Aux. Switch B217-B220 ¾” 20 2.73” [69.3] 1.87” [47.4]
B222-B225 1” 25 3.09” [78.4] 1.87” [47.4]
B229-B230 1¼” 32 3.72” [94.6] 1.87” [47.4]
Technical Data
Control MFT
Control signal 2 to 10 VDC Dimensions with 3-Way Valve
Power consumption running 2.5 W
D1368
holding 1W
Transformer sizing 5 VA (class 2 power source)
Electrical connection ½” conduit connector
(-S models have 2 cables) 3 ft [1m], 18 GA appliance cable
Overload protection electronic throughout 0° to 95° rotation
Feedback output 2 to 10 VDC, 0.5 mA max D C
Input impedance 100 kΩ for 2 to 10 VDC (0.1 mA)
500 Ω for 4 to 20mA
750 Ω for PWM
500 Ω for on/off and floating point
Angle of rotation 95°
E F
LF24-MFT-S US
Auxiliary switch 1 x SPDT, 6A (1.5A) @ 250 VAC, UL Listed,
adjustable 0° to 95° (double insulated)
92
LF24-MFT Actuators,
Wiring Multi-Function
– PWM, triacTechnology
WARNING
source and s
Live Electrical Components!
During installation, testing, servicing and troubleshooting of this product, it maybe
necessary to work with live electrical components. Have a qualified licensed electrician
or other individual who has been properly trained in handling live electrical components
perform these tasks. Failure to follow all electrical safety precautions when exposed
to live electrical components could result in death or serious injury.
Wiring Diagrams
W043
24 VAC/DC Transformer
W041
24 VAC Transformer (AC only)
Control signal may be pulsed from either the Hot (Source) or
6 Common (Sink) 24 VAC line. Line (1) Common
Volts 6
(2) + Hot
Position feedback cannot be used with Triac sink controller.
7 The actuators internal common reference is not compatible. (3) Y Input
7 Position (–)
Feedback VDC (+) (5) U Output
CCW CW
The ZG-R01 500 Ω resistor converts the 4 to 20 mA control signal to …MFT
2 to 10 VDC, up to 2 actuators may be connected in parallel.
PWM, triac source and sink
WARNING Live Electrical Components!
During installation, testing, servicing and troubleshooting of this product, it may
W302
be necessary to work with live electrical components. Have a qualified licensed electrician
or other individual who has been properly trained in handling live electrical components
perform these tasks. Failure to follow all electrical safety precautions when exposed to live
electrical components could result in death or serious injury.
P10419 - 09/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
W303
93
AFRB24(-S), AFRX24(-S) Actuators, On/Off AFRB24(-S), AFRX24(-S) Actuators, On/Off
Dimensions
Dimensions
D1369
D C
E F B
A
Models AFRB, AFRX
AFRB24
Valve Nominal Size Dimensions (Inches [mm])
AFRB24-S
Valve Body Inches DN [mm] A B
AFRX24
AFRX24-S B212-B216 ½” 15 2.38” [60.4] 1.72” [43.7]
B217-B221 ¾” 20 2.73” [69.3] 1.81” [45.9]
B222-B225 1” 25 3.09” [78.4] 1.81” [45.9]
Technical Data B229-B230 1¼” 32 3.72” [94.6] 1.81” [45.9]
Power supply 24 VAC ± 20% 50/60 Hz B231-B232 1¼” 32 3.72” [94.6] 1.98” [50.4]
24 VDC +20% / -10% B238-B240 1½” 40 3.88” [98.5] 1.98” [50.4]
Power consumption running 5 W B248-B250 2” 50 4.21” [107.0] 2.21” [56.2]
holding 2.5 W B251-B254 2” 50 4.93” [125.2] 2.68” [68.0]
Transformer sizing 7.5 VA (class 2 power source) B261-B265 2½” 65 5.55” [140.9] 2.68” [68.0]
Electrical connection B277-B280 3” 80 5.82” [147.9] 2.68” [68.0]
AFRB24... 3 ft., 18 GA appliance cable, 1/2" conduit
connector
-S models: two 3 ft., 18 gauge appliance
cables with 1/2” conduit connectors
AFRX24... 3 ft. [1m], 10 ft. [3m] or 16 ft. [5m] 18 GA
appliance or plenum cables, with or without
Dimensions
1/2” conduit connector
D1370
-S models: two 3 ft. [1m], 10 ft. [3m] or
16 ft. [5m] appliance cables, with or without
1/2" conduit connectors
Overload protection electronic throughout 0 to 95° rotation
AFRB24-S, AFRX24-S
Auxiliary switches 2 x SPDT 3A (0.5A) @ 250 VAC, UL approved
one set at +10°, one adjustable 10° to 90°
800-543-9038
800-543-9038USA
USA 866-805-7089
866-805-7089CANADA
CANADA 203-791-8396 LATIN AMERICA
203-791-8396 / CARIBBEAN
LATIN AMERICA
94 97
AFRB24(-S), AFRX24(-S) Actuators, On/Off AFRB24(-S), AFRX24(-S) Actuators, On/Off
Wiring Diagrams
W063_AFB(X)
1 24 VAC Transformer
W064_AFB(X)_-S
+10°, one is adjustable 10° to 90°.
WARNING
G Live Electrical Components!
During installation, testing, servicing and troubleshooting of this product, it may
be necessary to work with live electrical components. Have a qualified licensed electrician
or other individual who has been properly trained in handling live electrical components
perform these tasks. Failure to follow all electrical safety precautions when exposed to live
electrical components could result in death or serious injury.
AFB24-S
AFX24-S
98 95
AFRBUP(-S), AFRXUP(-S) Actuators, On/Off AFRBUP(-S), AFRXUP(-S) Actuators, On/Off
Dimensions
Dimensions
D1369
D C
E F B
A
AFRB, AFRX
Models Valve Nominal Size Dimensions (Inches [mm])
AFRBUP Valve Body Inches DN [mm] A B
AFRBUP-S
B212-B216 ½” 15 2.38” [60.4] 1.72” [43.7]
AFRXUP
B217-B221 ¾” 20 2.73” [69.3] 1.81” [45.9]
AFRXUP-S
B222-B225 1” 25 3.09” [78.4] 1.81” [45.9]
B229-B230 1¼” 32 3.72” [94.6] 1.81” [45.9]
Technical Data B231-B232 1¼” 32 3.72” [94.6] 1.98” [50.4]
Power supply 24 to 240 VAC -20% / +10%, 50/60 Hz B238-B240 1½” 40 3.88” [98.5] 1.98” [50.4]
24 to 125 VDC +10% B248-B250 2” 50 4.21” [107.0] 2.21” [56.2]
Power consumption running 7 W B251-B254 2” 50 4.93” [125.2] 2.68” [68.0]
holding 3.5 W B261-B265 2½” 65 5.55” [140.9] 2.68” [68.0]
Transformer sizing 7 VA @ 24 VAC (class 2 power source) B277-B280 3” 80 5.82” [147.9] 2.68” [68.0]
8.5 VA @ 120 VAC
18 VA @ 240 VAC
Electrical connection
AFRBUP... 3 ft., 18 GA appliance cable, 1/2" conduit
connector
-S models: two 3 ft., 18 gauge appliance Dimensions
cables with 1/2” conduit connectors
D1370
AFRXUP... 3 ft. [1m], 10 ft. [3m] or 16 ft. [5m] 18 GA
appliance or plenum cables, with or without
1/2” conduit connector
AFRBUP-S, AFRXUP-S
Auxiliary switches 2 x SPDT 3A (0.5A) @ 250 VAC, UL approved
one set at +10°, one adjustable 10° to 90°
96
AFRBUP(-S), AFRXUP(-S) Actuators, On/Off AFRBUP(-S), AFRXUP(-S) Actuators, On/Off
Wiring Diagrams
W066_AFB(X)UP
1 Provide overload protection and disconnect as required.
W067_AFB(X)UP-S
Meets cULus requirements without the need of an electrical ground
connection. Wht
Blk
WARNING
G Live Electrical Components!
During installation, testing, servicing and troubleshooting of this product, it may
be necessary to work with live electrical components. Have a qualified licensed electrician
or other individual who has been properly trained in handling live electrical components
perform these tasks. Failure to follow all electrical safety precautions when exposed to live
electrical components could result in death or serious injury.
AFBUP-S
AFXUP-S
P10419 - 09/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
800-543-9038USA
800-543-9038 USA 866-805-7089CANADA
866-805-7089 CANADA 203-791-8396
203-791-8396 LATIN AMERICA
LATIN AMERICA / CARIBBEAN
100 97
AFRB24-SR, AFRX24-SR
Proportional, Spring Return, 24 V, for 2 to 10 VDC or 4 to 20 mA Control Signal
Dimensions
D1369
Dimensions (Inches [mm])
D C
AFR_DIM
E F B
A
AFRB, AFRX
Valve Nominal Size Dimensions (Inches [mm])
Technical Data Valve Body Inches DN [mm] A B
Power supply 24 VAC ±20%, 50/60 Hz B212-B216 ½” 15 2.38” [60.4] 1.72” [43.7]
24 VDC +20% / -10% B217-B221 ¾” 20 2.73” [69.3] 1.81” [45.9]
Power consumption running 5.5 W B222-B225 1” 25 3.09” [78.4] 1.81” [45.9]
holding 3 W B229-B230 1¼” 32 3.72” [94.6] 1.81” [45.9]
Transformer sizing 8.5 VA (class 2 power source) B231-B232 1¼” 32 3.72” [94.6] 1.98” [50.4]
Electrical connection B238-B240 1½” 40 3.88” [98.5] 1.98” [50.4]
AFRB... 3 ft, 18 GA appliance cable, 1/2" conduit B248-B250 2” 50 4.21” [107.0] 2.21” [56.2]
connector B251-B254 2” 50 4.93” [125.2] 2.68” [68.0]
-S models: two 3 ft, 18 gauge appliance cables B261-B265 2½” 65 5.55” [140.9] 2.68” [68.0]
with 1/2” conduit connectors B277-B280 3” 80 5.82” [147.9] 2.68” [68.0]
AFX... 3 ft [1m], 10 ft [3m] or 16 ft [5m] 18 GA
appliance or plenum cables, with or without 1/2”
conduit connector
-S models: Two 3 ft [1m], 10 ft [3m] or
16 ft [5m] appliance cables, with or without 1/2"
conduit connectors Dimensions
Overload protection electronic throughout 0 to 95° rotation
D1370
Operating range Y 2 to 10 VDC, 4 to 20mA
Input impedance 100 kΩ for 2 to 10 VDC (0.1 mA)
500 Ω for 4 to 20 mA
Feedback output U 2 to 10 VDC (max. 0.5 mA)
800-543-9038
800-543-9038USA
USA 866-805-7089
866-805-7089 CANADA
CANADA 203-791-8396
203-791-8396LATIN AMERICA/ CARIBBEAN
LATIN AMERICA / CARIBBEAN
98
57
AFRB24-SR, AFRX24-SR
Proportional, Spring Return, 24 V, for 2 to 10 VDC to 4 to 20 mA Control Signal
Accessories WARNING
G Live Electrical Components!
AV 8-25 Shaft extension During installation, testing, servicing and troubleshooting of this product, it may be
IND-AFB Damper position indicator necessary to work with live electrical components. Have a qualified licensed electrician or other
individual who has been properly trained in handling live electrical components perform these
KH-AFB Crank arm
tasks. Failure to follow all electrical safety precautions when exposed to live electrical compo-
K7-2 Universal clamp for up to 1.05” dia jackshafts nents could result in death or serious injury.
TF-CC US Conduit fitting
Tool-06 8mm and 10 mm wrench
W068_AFB(X)24-SR
1 24 VAC Transformer
ZG-100 Universal mounting bracket
ZG-101 Universal mounting bracket
Line 1 Common
ZG-118 Mounting bracket for Barber Colman® MA 3../4.., Honeywell® 3
Volts
Mod III or IV or Johnson® Series 100 replacement or new crank 2 + Hot
arm type installations 3 Y1 Input, 2 to 10V
ZG-AFB Crank arm adaptor kit Control Signal (–)
ZG-AFB118 Crank arm adaptor kit 2 to 10 VDC (+)
ZS-100 Weather shield (metal) 5 U Output 2 to 10V
ZS-150 Weather shield (polycarbonate)
AFB24-SR, AFB24-SR-S
ZS-260 Explosion-proof housing AFX24-SR, AFX24-SR-S
2
ZS-300 NEMA 4X housing
NOTE: When using AFRB24-SR, AFRB24-SR-S, AFRX24-SR and AFRX24-SR-S actuators, only use
2 to 10 VDC control of AFRB24-SR and AFRX24-SR
accessories listed on this page.
For actuator wiring information and diagrams, refer to Belimo Wiring Guide.
W069_AFB(X)24-SR
Typical Specification
Spring return control damper actuators shall be direct coupled type which require no
crank arm and linkage and be capable of direct mounting to a jackshaft up to a 1.05”
diameter. The actuator must provide proportional damper control in response to a 2 to
10 VDC or, with the addition of a 500Ω resistor, a 4 to 20 mA control input from an
electronic controller or positioner. The actuators must be designed so that they may be
used for either clockwise or counterclockwise fail-safe operation. Actuators shall use
a brushless DC motor controlled by a microprocessor and be protected from overload
at all angles of rotation. Run time shall be constant, and independent of torque. A 2 to
10 VDC feedback signal shall be provided for position feedback. Actuators shall be
cULus Approved and have a 5 year warranty, and be manufactured under ISO 9001 AFB24-SR, AFB24-SR-S
International Quality Control Standards. Actuators shall be as manufactured by Belimo. AFX24-SR, AFX24-SR-S
W064_AFB(X)24_SR_-S
N40103 - 09/11 - Subject to change. © Belimo Aircontrols (USA), Inc.
ATTENTION:
ATTENTION AFRB24-SR(-S)
AFRB24 AFRX24 SR( S) cannott bbe tandem
SR( S) andd AFRX24-SR(-S) t d mounted t d
on the same damper or valve shaft. Only On/Off and MFT AF models can be used
for tandem mount applications.
800-543-9038USA
800-543-9038 USA 866-805-7089CANADA
866-805-7089 CANADA 203-791-8396LATIN
203-791-8396 LATIN AMERICA
AMERICA / /CARIBBEAN
CARIBBEAN
58
99
AFRX Actuators, Multi-Function Technology
Dimensions
D1369
D C
E F B
A
Models AFRB, AFRX
AFRX24-MFT
AFRX24-MFT-S Valve Nominal Size Dimensions (Inches [mm])
Valve Body Inches DN [mm] A B
Technical Data B212-B216 ½” 15 2.38” [60.4] 1.72” [43.7]
Control MFT B217-B221 ¾” 20 2.73” [69.3] 1.81” [45.9]
Control signal 2 to 10 VDC, 4 to 20 mA (default) B222-B225 1” 25 3.09” [78.4] 1.81” [45.9]
variable (VDC, PWM, floating point, on/off) B229-B230 1¼” 32 3.72” [94.6] 1.81” [45.9]
Power supply 24 VAC, +/- 20%, 50/60 Hz B231-B232 1¼” 32 3.72” [94.6] 1.98” [50.4]
24 VDC, +20% / -10% B238-B240 1½” 40 3.88” [98.5] 1.98” [50.4]
Power consumption† running 7.5 W B248-B250 2” 50 4.21” [107.0] 2.21” [56.2]
holding 3W B251-B254 2” 50 4.93” [125.2] 2.68” [68.0]
Transformer sizing† 10 VA (Class 2 power source) B261-B265 2½” 65 5.55” [140.9] 2.68” [68.0]
Electrical connection 3 ft. [1m], 10 ft. [3m] or 16 ft. [5m] 18 GA B277-B280 3” 80 5.82” [147.9] 2.68” [68.0]
appliance or plenum cables, with or without
1/2" conduit connector
-S models: two 3 ft. [1m], 10 ft. [3m] or 16
ft. [5m] appliance cables with or without 1/2”
conduit connectors
Overload protection electronic throughout 0 to 90° rotation Dimensions
Feedback output* 2 to 10 VDC, 0.5 mA max (variable)
D1370
Input impedance 100 kΩ for 2 to 10 VDC (0.1 mA)
500 Ω for 4 to 20 mA
1500 Ω for on/off and floating point
Angle of rotation 95°
AFRX24-MFT-S
Auxiliary switches 2 x SPDT 3A (0.5A) @ 250 VAC, UL approved
one set at +10° to 90°
100
AFRX Actuators, Multi-Function Technology
Dimensions
W600_AFB_AFX
AFR_LGCCV
D
I
C
G AFB24-MFT-S
AFX24-MFT-S
B
E F A Auxiliary Switches for AFRX24-MFT
AFRB, AFRX
W399_08
Nominal Top
Valve Flange Face-to-Face
Pipe Flange Height
Body Diameter Length
Size Design
A B C
B6250 2½" [65] 7.50" [190.5] 5.50" [139.7] 8.10" [205.4]
B6300 3" [80] F05 8.00" [203.2] 6.60" [167.6] 8.40" [213.1]
B6400 4" [100] 9.00" [228.6] 8.30" [210.8] 9.30" [235.9]
VDC/4-20 mA
Wiring Diagrams
W399_08
1 Provide overload protection and disconnect as required.
W399_08
or the Common (sink) 24 VAC line.
Contact closures A & B also can be triacs.
8 A & B should both be closed for triac source and open for triac sink.
For triac sink the common connection from the actuator
9 must be connected to the hot connection of the controller.
101
AFRX24-MFT95 Actuator, Proportional Potentiometric Control
Dimensions
D1369
D C
E F B
A
Models AFRB, AFRX
AFRX24-MFT95
Valve Nominal Size Dimensions (Inches [mm])
Valve Body Inches DN [mm] A B
Technical Data B212-B215 ½” 15 2.38” [60.4] 1.72” [43.7]
Control MFT B217-B221 ¾” 20 2.73” [69.3] 1.81” [45.9]
Control signal 0 to 135 Ω Honeywell Electronic Series 90, B222-B225 1” 25 3.09” [78.4] 1.81” [45.9]
0 to 135 Ω input B229-B230 1¼” 32 3.72” [94.6] 1.81” [45.9]
Power supply 24 VAC, +/- 20%, 50/60 Hz B231-B232 1¼” 32 3.72” [94.6] 1.98” [50.4]
24 VDC, +20% / -10% B238-B240 1½” 40 3.88” [98.5] 1.98” [50.4]
Power consumption† running 7.5 W B248-B250 2” 50 4.21” [107.0] 2.21” [56.2]
holding 3W B251-B254 2” 50 4.93” [125.2] 2.68” [68.0]
Transformer sizing† 10 VA (Class 2 power source) B261-B265 2½” 65 5.55” [140.9] 2.68” [68.0]
Electrical connection 3 ft. [1m], 10 ft. [3m] or 16 ft. [5m] 18 GA B277-B280 3” 80 5.82” [147.9] 2.68” [68.0]
plenum cables, with or without 1/2" conduit
connector
Overload protection electronic throughout 0 to 90° rotation
Feedback output* 2 to 10 VDC, 0.5 mA max (variable)
Angle of rotation 95°
Direction of rotation* spring reversible with CW/CCW mounting Dimensions
motor reversible with built-in switch
D1370
Position indication visual indicator 0° to 95°(0° is spring return
position)
Manual override 5 mm hex crank (3/16” Allen), supplied
Running time motor* 150 seconds (default),
102
AFRX24-MFT95 Actuator, Proportional Potentiometric Control
Override of AF24-MFT95 US
Dimensions
W015_AFRX
D1378
Switch A Switch B Damper Position
Damper Open
Damper Closed
D The direction of rotation switch is set so that the fail safe position and the
position of the damper is closed with no signal at wire R.
I
24 VAC Transformer
C 1
A 4
G 3 W, Wht
135 4 R, Wht
B B
E F A
5 B, Wht
6 ‘U5’ Output 2-10 VDC
AFRB, AFRX AFRX24-MFT95
24 VAC Transformer
1
Nominal Top Line 1 Common, Blk
Valve Flange Face-to-Face
Pipe Flange Height Volts 2 + Hot, Red 3
Body Diameter Length
Size Design 4
A
A B C W 3 W, Wht
Line R 4 R, Wht
B6250 2½" [65] 7.50" [190.5] 5.50" [139.7] 8.10" [205.4] Volts B
B 5 B, Wht
B6300 3" [80] F05 8.00" [203.2] 6.60" [167.6] 8.40" [213.1] 2 Controller 6 ‘U5’ Output 2-10 VDC
B6400 4" [100] 9.00" [228.6] 8.30" [210.8] 9.30" [235.9] AF24-MFT95 US used with AFRX24-MFT95
a Series 90
controller and a Series 90 low limit control
Override of AFRX24-MFT95
Wiring Diagrams 1 Provide overload protection and disconnect as required.
W016
2 Actuators and controller must have separate transformers.
24 VAC Transformer
1 Consult controller instruction data for more detailed
3
Line installation information. 1 Common, Blk
1 Provide overload protection and disconnect as required. 4 To reverse control rotation, use the
Volts 2 + 3
Hot, Redswitch.
reversing
4
2 Actuators and controller must have separate transformers. 2
W W B R 3 W, Wht
4 R, Wht
Consult controller instruction data for more detailed installation Series 90 R
3 information.
Controller
B 5 B, Wht
4 To reverse control rotation, use the reversing switch. 135 for 0 to 50% control
AFRX24-MFT95
280 for 0 to 100% control
controller and a Series 90 high limit control
Resistor value depends on the type of controller and the number of
actuators. No resistor is used for one actuator. Honeywell resistor
W017
5 1 Provide
kits may also be used. 24 VACoverload protection and disconnect as required.
Transformer W015
1
2 Actuators and controller must have separate transformers.
Line Consult controller instruction data1 for
Common, Blk
more detailed
WARNING Live Electrical Components! 3
Volts installation information. 2 + Hot, Red 3
During installation, testing, servicing and troubleshooting of this product, it may
4 To reverse control rotation, use the reversing switch.
be necessary to work with live electrical components. Have a qualified licensed electrician 2
4
or other individual who has been properly trained in handling live electrical components W 3 W, Wht
perform these tasks. Failure to follow all electrical safety precautions when exposed to live Series 90 R 4 R, Wht
electrical components could result in death or serious injury. Controller R W B 5 B, Wht
B
6 ‘U5’ Output 2-10 VDC
Series 90 high limit control - 280
AFRX24-MFT95
W016
103
W017
AFRX24-MFT95 Actuator, Proportional Potentiometric Control AFRX24-MFT95
W018_AFRX
W020_AFRX
AFRX24-MFT95
AFRX24-MFT95
AFRX24-MFT95
AFRX24-MFT95
AFRX24-MFT95
AFRX24-MFT95
AFRX24-MFT95
104
AFRB24 N4, AFRB24 N4H, AFRB24-S N4, AFRB24-S N4H,
AFRX24 N4, AFRX24 N4H, AFRX24-S N4, AFRX24-S N4H
NEMA 4, On/Off, Spring Return, 24 V
D1363
D C
E F B
Models A
AFRB24 N4 Basic Version ARB N4, ARX N4, NRB N4, NRX N4
AFRB24 N4H Basic Version w/built in heater Valve Nominal Size Dimensions (Inches [mm])
AFRB24-S N4 Basic Version w/built-in aux. switch Valve Body Inches DN [mm] A B
AFRB24-S N4H Basic Version w/built-in aux. switch & heater B231-B232 1¼” 32 3.72” [94.6] 1.84” [47.4]
AFRX24 N4 Flexible Version B238-B240 1½” 40 3.88” [98.5] 2.04” [51.9]
AFRX24-S N4 Flexible Version w/built-in aux. switch B248-B254 2” 50 4.93” [125.2] 2.73” [69.5]
AFRX24 N4H Flexible Version w/built in heater B277-B280 3” 80 5.82” [147.9] 2.73” [69.5]
AFRX24-S N4H Flexible Version aux. switch & heater
Technical Data
Dimensions with 3-Way Valve1363
Power supply 24 VAC ± 20% 50/60 Hz
D1364
24 VDC +20% / -10%
Power consumption running 5 W / heater 25 W
holding 2.5 W
Transformer sizing 7.5 VA (class 2 power source) / heater 25 VA
Electrical connection 3 ft [1m], 10 ft [3m] or 16 ft [5m] 18 GA appliance
AFR... N4 cable, with or without 1/2” conduit connector
D C
-S models: Two 3 ft [1m], 10 ft [3m] or
16 ft [5m] appliance cables with or without 1/2” conduit
connectors
105
AFRB24 N4, AFRB24 N4H, AFRB24-S N4, AFRB24-S N4H,
AFRX24 N4, AFRX24 N4H, AFRX24-S N4, AFRX24-S N4H
NEMA 4, On/Off, Spring Return, 24 V
W063_AFRBX24_N4
1 24 VAC Transformer
Line 1 Common
Volts 3
2 + Hot
AFRB24 N4
AFRB24 N4H 2
AFRB24-S N4
AFRB24-S N4H
AFRX24 N4
AFRX24-S N4
W064_AFRBX24_S_N4
1 Provide overload protection and disconnect as required.
Actuators may be connected in parallel. Power consumption
2 must be observed.
AFRB24-S N4
AFRB24-S N4H
AFRX24-S N4
AFRX24-S N4H
Auxiliary Switches
GK-AF-NF N4H 24V heater
106
AFRBUP N4, AFRBUP-S N4, AFRBUP N4H, AFRBUP-S N4H,
AFRXUP N4, AFRXUP-S N4, AFRXUP N4H, AFRXUP-S N4H
NEMA 4, On/Off, Spring Return, 24 to 240 VAC
D1363
D C
E F B
Models A
AFRBUP N4 Basic Version
AFRBUP-S N4 Basic Version w/built-in aux. switch ARB N4, ARX N4, NRB N4, NRX N4
AFRBUP N4H Basic Version w/built in heater Valve Nominal Size Dimensions (Inches [mm])
AFRBUP-S N4H Basic Version w/built-in aux. switch & heater Valve Body Inches DN [mm] A B
AFRXUP N4 Flexible Version B231-B232 1¼” 32 3.72” [94.6] 1.84” [47.4]
AFRXUP-S N4 Flexible Version w/built-in aux. switch B238-B240 1½” 40 3.88” [98.5] 2.04” [51.9]
AFRXUP N4H Flexible Version w/built in heater B248-B254 2” 50 4.93” [125.2] 2.73” [69.5]
AFRXUP-S N4H Flexible Version w/built-in aux. switch & heater B261-B265 2½” 65 5.55” [140.9] 2.73” [69.5]
B277-B280 3” 80 5.82” [147.9] 2.73” [69.5]
Technical Data
Power supply 24...240 VAC -20% / +10%, 50/60 Hz
24...125 VDC ±10%
Dimensions with 3-Way Valve1363
Power consumption running 7 W / heater 25 W
D1364
holding 3.5 W
Transformer sizing 7 VA @ 24 VAC (class 2 power source)
8.5 VA @ 120 VAC / heater 25 VA @120 VAC
18 VA @ 240 VAC
Electrical connection
AFRBUP... N4 3 ft [1m], 10 ft [3m] or 16 ft [5m] 18 GA appliance
AFRXUP... N4 cable, with or without 1/2” conduit connector D C
-S models: Two 3 ft [1m], 10 ft [3m] or
16 ft [5m] appliance cables with or without 1/2” conduit
connectors
heater (N4H) terminal block, 18-16 GA
Overload protection electronic throughout 0 to 95° rotation
E F B
Control on/off
P10419 - 09/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
A
Torque 180 in-lb [20 Nm] minimum
Direction of rotation spring reversible with CW/CCW mounting inside housing NRB N4, NRX N4
Mechanical angle of rotation 95° (adjustable with mechanical end stop, Valve Nominal Size Dimensions (Inches [mm])
35° to 95°) Valve Body Inches DN [mm] A B C
Running time motor < 75 sec B329-B331 1¼” 32 3.96” [100.6] 2.27” [57.7] 2.14” [54.3]
spring 20 sec @ -4°F to 122°F [-20°C to 50°C]; B338-B341 1½” 40 4.39” [111.6] 2.51” [63.7] 2.40” [61.1]
< 60 sec @ -22°F [-30°C]
B347-B352 2” 50 4.90” [124.5] 2.73” [69.5] 2.74” [69.7]
spring (with heater) 20 sec @ -4°F to 122°F [-20°C to 50°C];
< 60 sec @ -49°F [-45°C]
Position indication visual indicator, 0° to 95°
(0° is full spring return position)
Manual override 5 mm hex crank (³⁄₁₆" Allen), supplied
Humidity max. 95% RH non-condensing
Ambient temperature -22°F to 122°F [-30°C to 50°C]
with heater -49°F to 122°F [-45°C to 50°C]
Storage temperature -40°F to 176°F [-40°C to 80°C]
Housing UL Type 4, NEMA 4, IP66
Housing material polycarbonate
Agency listings † cULus acc. to UL60730-1A/-2-14,
CAN/CSA E60730-1:02, CE acc. to
2004/108/EC & 2006/95/EC
Noise level <50dB(A) motor @ 75 seconds
≤62dB(A) spring return
Servicing maintenance free
Quality standard ISO 9001
Weight 9.7 lbs (4.4 kg), 10 lbs (4.5 kg) with switches
10.5 lbs (4.8 kg) with heater
† Rated Impulse Voltage 4kV, Type of action 1.AA (1.AA.B for -S version), Control Pollution Degree 4.
107
AFRBUP N4, AFRBUP-S N4, AFRBUP N4H, AFRBUP-S N4H,
AFRXUP N4, AFRXUP-S N4, AFRXUP N4H, AFRXUP-S N4H
NEMA 4, On/Off, Spring Return, 24 to 240 VAC A
Accessories
W066_AFRBUP_N4
Tool-06 8mm and 10 mm wrench
43442-00001 Gland (needed for additional wires)
11097-00001 Gasket for Gland (needed for additional wires)
NOTE: When using AFRBUP N4, AFRBUP-S N4, AFRBUP N4H, AFRBUP-S N4H, AFRXUP N4,
AFRXUP-S N4, AFRXUP N4H, AFRXUP-S N4H actuators, only use accessories listed on this page.
For actuator wiring information and diagrams, refer to Belimo Wiring Guide.
Typical Specification
AFRBUP N4
On/Off spring return damper actuators shall be direct coupled type which require
AFRBUP N4H
no crank arm and linkage and be capable of direct mounting to a jackshaft up to a AFRBUP-S N4
1.05” diameter. The actuators must be designed so that they may be used for either AFRBUP-S N4H
clockwise or counterclockwise fail-safe operation. Actuators shall be protected AFRXUP N4
from overload at all angles of rotation. If required, two SPDT auxiliary switch shall AFRXUP N4H
be provided having the capability of one being adjustable. Actuators with auxiliary AFRXUP-S N4
switches must be constructed to meet the requirements for Double Insulation so AFRXUP-S N4H
an electrical ground is not required to meet agency listings. Actuators shall be A
cULus Approved and have a 5 year warranty, and be manufactured under ISO 9001
International Quality Control Standards. Actuators shall be as manufactured by Belimo.
On/Off Wiring
W067_AFRBUP-S_N4
Wiring Diagrams
Wht
Blk
1 Provide overload protection and disconnect as required.
NEMA 4A Heater
108
AFRB24-MFT N4, AFRB24-MFT-S N4, AFRB24-MFT N4H, AFRB24-MFT-S N4H
AFRX24-MFT N4, AFRX24-MFT-S N4, AFRX24-MFT N4H, AFRX24-MFT-S N4H
NEMA 4, Proportional, Spring Return, Direct Coupled, 24V, Multi-Function Technology®
D1363
Models
AFRB24-MFT N4 Basic Version
AFRB24-MFT-S N4 Basic Version w/built-in aux. switch D C
AFRB24-MFT N4H Basic Version w/built in heater
AFRB24-MFT-S N4H Basic Version w/built-in aux. switch & heater
AFRX24-MFT N4 Flexible Version
AFRX24-MFT-S N4 Flexible Version w/built-in aux. switch
AFRX24-MFT N4H Flexible Version w/built in heater E F B
AFRX24-MFT-S N4H Flexible Version w/built in aux. switch & heater A
Technical Data ARB N4, ARX N4, NRB N4, NRX N4
Power supply 24 VAC, +/- 20%, 50/60 Hz Valve Nominal Size Dimensions (Inches [mm])
24 VDC, +20% / -10%
Valve Body Inches DN [mm] A B
Power running 7.5 W / heater 25 W
B231-B232 1¼” 32 3.72” [94.6] 1.84” [47.4]
consumption holding 3W
B238-B240 1½” 40 3.88” [98.5] 2.04” [51.9]
Transformer sizing 10 VA (Class 2 power source) / heater 25 VA
Electrical connection 3 ft [1m], 10 ft [3m] or 16 ft [5m] 18 GA appliance cables, with
B248-B254 2” 50 4.93” [125.2] 2.73” [69.5]
AFRB... N4 1/2” conduit connector B261-B265 2½” 65 5.55” [140.9] 2.73” [69.5]
AFRX... N4 -S models: two 3 ft [1m], 10 ft [3m] or B277-B280 3” 80 5.82” [147.9] 2.73” [69.5]
16 ft [5m] appliance cables with 1/2” conduit connectors
heater (N4H) terminal block, 26-16 GA
Overload protection electronic throughout 0 to 95° rotation Dimensions with 3-Way Valve1363
Operating range Y* 2 to 10 VDC, 4 to 20 mA (default)
D1364
variable (VDC, PWM, floating point, on/off)
Input impedance 100 kΩ for 2 to 10 VDC (0.1 mA)
500 Ω for 4 to 20 mA
1500 Ω for PWM, floating point and on/off control
Feedback output U* 2 to 10 VDC, 0.5 mA max
Torque minimum 180 in-lb (20 Nm)
D C
Direction of spring reversible with cw/ccw mounting inside housing
rotation* motor reversible with built-in switch
Mechanical 95° (adjustable with mechanical end stop, 35° to 95°)
angle of rotation*
Running time motor* 150 seconds (default), variable (70 to 220 seconds)
spring <20 sec @ -4°F to 122°F [-20°C to 50°C]; E F B
<60 sec @ -22°F [-30°C] A
P10419 - 09/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
spring (with heater) <20 sec @ -4°F to 122°F [-20°C to 50°C]; NRB N4, NRX N4
<60 sec @ -49°F [-45°C]
Valve Nominal Size Dimensions (Inches [mm])
Angle of Rotation off (default)
adaptation Valve Body Inches DN [mm] A B C
Override control* min position = 0% B329-B331 1¼” 32 3.96” [100.6] 2.27” [57.7] 2.14” [54.3]
mid. position = 50% B338-B341 1½” 40 4.39” [111.6] 2.51” [63.7] 2.40” [61.1]
max. position = 100% B347-B352 2” 50 4.90” [124.5] 2.73” [69.5] 2.74” [69.7]
Position indication visual indicator, 0° to 95°
(0° is spring return position)
Manual override 5 mm hex crank (³⁄₁₆" Allen), supplied
Humidity max. 95% RH non-condensing
Ambient temperature -22°F to 122°F (-30°C to 50°C)
with heater -49°F to 122°F (-45°C to 50°C)
Storage temperature -40°F to 176°F (-40°C to 80°C)
Housing UL Type 4, NEMA 4, IP66
Housing material polycarbonate
Noise level ≤40dB(A) motor @ 150 seconds, run time dependent
≤62dB(A) spring return
Agency listings † cULus acc. to UL60730-1A/-2-14, CAN/CSA E60730-
1:02, CE acc. to 2004/108/EC & 2006/95/EC
Quality standard ISO 9001
Servicing maintenance free
Weight 9.7 lbs. (4.4 kg), 10 lbs. (4.5 kg) with switches
10.5 lbs (4.8 kg) with heater
* Variable when configured with MFT options
† Rated Impulse Voltage 800V, Type of action 1.AA (1.AA.B for -S version), Control Pollution Degree 4.
Programmed for 70 sec motor run time. At 150 sec motor run time, transformer sizing
is 8.5 VA and power consumption is 6 W running / 3 W holding.
109
AFRB24-MFT N4, AFRB24-MFT-S N4, AFRB24-MFT N4H, AFRB24-MFT-S N4H
AFRX24-MFT N4, AFRX24-MFT-S N4, AFRX24-MFT N4H, AFRX24-MFT-S N4H
NEMA 4, Proportional, Spring Return, Direct Coupled, 24V, Multi-Function Technology®
Accessories
W399_08
Tool-06 8mm and 10 mm wrench
43442-00001 Gland (needed for additional wires)
11097-00001 Gasket for Gland (needed for additional wires)
NOTE: When using AFRB24-MFT N4, AFRB24-MFT-S N4, AFRB24-MFT N4H, AFRB24-MFT-S N4H
AFRX24-MFT N4, AFRX24-MFT-S N4, AFRX24-MFT N4H, AFRX24-MFT-S N4H actuators, only use
accessories listed on this page. For actuator wiring information and diagrams, refer to Belimo
Wiring Guide.
Typical Specification
The actuator must provide proportional damper control in response to a 2 to 10 VDC or, with the
addition of a 500Ω resistor, a 4 to 20 mA control input from an electronic controller or positioner.
The actuators must be designed so that they may be used for either clockwise or counterclockwise
fail-safe operation. Actuators shall use a brushless DC motor controlled by a microprocessor and
be protected from overload at all angles of rotation. Run time shall be constant, and independent of VDC/4-20 mA
torque. A 2 to 10 VDC feedback signal shall be provided for position feedback. Actuators shall be
cULus Approved and have a 5 year warranty, and be manufactured under ISO 9001 International
W399_08
Quality Control Standards. Actuators shall be as manufactured by Belimo.
Wiring Diagrams
W399_08
4 The actuator internal common reference is not compatible.
Control signal may be pulsed from either the Hot (source) or the Common
5 (sink) 24 VAC line.
Contact closures A & B also can be triacs.
8 A & B should both be closed for triac source and open for triac sink.
For triac sink the common connection from the actuator must be connected
9 to the hot connection of the controller.
NEMA 4 Heater
AFB24-MFT-S N4
AFRB24-MFT-S N4H
AFR$X24-MFT-S N4
AFRX24-MFT-S N4H
Auxiliary Switches
110
AFRB24-5-14, AFRB24-S-5-14 Actuators, On/Off
Dimensions
D1378
D
I
C
B
E F A
Control on/off
Direction of rotation spring reversible with CW/CCW mounting
Angle of rotation 95°
Running time motor < 75 seconds
spring 20 seconds @ -4°F to 122°F [-20°C to 50°C];
< 60 seconds @ -22°F [-30°C]
Position indication visual indicator, 0° to 95°
(0° is full spring return position)
Manual override 5 mm hex crank (3/16" Allen), supplied
Ambient temperature -22°F to 122°F [-30°C to 50°C]
Storage temperature -40°F to 176°F [-40°C to 80°C]
Housing NEMA 2, IP54, Enclosure Type2
Agency listings † cULus according. to UL60730-1A/-2-14,
CAN/CSA E60730-1:02, CE according. to
2004/108/EC & 2006/95/EC
Noise level <50dB(A) motor @ 75 seconds
<62dB(A) spring return
Quality standard ISO 9001
† Rated Impulse Voltage 800V, Type of action 1.AA (1.AA.B for -S version), Control Pollution Degree 3.
AFRB24-S, AFRX24-S
Auxiliary switches 2 x SPDT 3A (0.5A) @ 250 VAC, UL approved
one set at +10°, one adjustable 10° to 90°
111
AFRB24-5-14, AFRB24-S-5-14 Actuators, On/Off
Wiring Diagrams
W063_AFB(X)
1 24 VAC Transformer
W064_AFB(X)_-S
+10°, one is adjustable 10° to 90°. 1 Provide overload protection and disconnect as required.
Actuators may be connected in parallel. Power consumption
2 must be observed.
Meets cULus requirements without the need of an electrical ground
connection. 3 Actuator may also be powered by 24VDC.
AFB24-S
AFX24-S
112
AFRBUP-5-14, AFRBUP-S-5-14 Actuators, On/Off
Dimensions
D1378
D
I
C
B
E F A
AFRBUP-S, AFRXUP-S
Auxiliary switches 2 x SPDT 3A (0.5A) @ 250 VAC, UL approved
one set at +10°, one adjustable 10° to 90°
113
AFRBUP-5-14, AFRBUP-S-5-14 Actuators, On/Off
A
Wiring Diagrams
W066_AFB(X)UP
1 Provide overload protection and disconnect as required.
W067_AFB(X)UP-S
Meets cULus requirements without the need of an electrical ground
connection. Wht
Blk
WARNING Live Electrical Components!
During installation, testing, servicing and troubleshooting of this product, it may
be necessary to work with live electrical components. Have a qualified licensed electrician
or other individual who has been properly trained in handling live electrical components
perform these tasks. Failure to follow all electrical safety precautions when exposed to live
electrical components could result in death or serious injury.
AFBUP-S
AFXUP-S
114
GKRB24-3-5-14 Actuators, On/Off, Floating Point, Fail-Safe
Dimensions
D1379
D
I C
B
E F A
GKRB, GKRX
Nominal Top
Valve Flange Face-to-Face
Pipe Flange Height
Models Body
Size Design
Diameter Length
GKRB24-3-5-14
A B C
B6400 4” [100] 9.00" [228.6] 8.30” [210.8] 9.30” [235.9]
Technical Data B6500 5" [125] 10.00" [254] 10.30" [261.6] 10.50" [266.4]
F05
Control on/off, floating point B6600 6" [150] 11.00" [279.4] 12.50" [317.5] 11.70" [296.9]
Power supply 24 VAC ± 20% 50/60 Hz
24 VDC ± 10%
Power consumption running 12 W
holding 3 W
Transformer sizing 18 VA (Class 2 power source)
Electrical connection 3 ft,18 GA plenum rated cable
½” conduit connector
Overload protection electronic throughout 0° to 95° rotation
Input impedance 100 kΩ (0.1mA), 500 Ω, 1500 Ω (floating
point, on/off)
Angle of rotation max. 95°, adjustable with mechanical stop
P10419 - 09/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
115
GKRB24-3-5-14 Actuators, On/Off, Floating Point, Fail-Safe
W399_10
C = Control unit 2.50 mm2 <100 m <20 m 1 m (L 1) + 19 m (L 2)
L1 = Belimo connecting cable, 1 m (4 x 0.75 mm2)
L2 = Customer cable A = Actuator
Ltot = Maximum cable length C = Control unit
L1 = Belimo connecting cable, 1 m (4 x 0.75 mm2)
W399_10
116
GKRX24-MFT-5-14 Actuators, Multi-Function Technology, Fail-Safe
Dimensions
D1379
D
I C
B
E F A
GKRB, GKRX
Nominal Top
Valve Flange Face-to-Face
Pipe Flange Height
Body Diameter Length
Size Design
Models A B C
GKRX24-MFT-5-14 B6400 4” [100] 9.00” [228.6] 8.30” [210.8] 9.30” [235.9]
B6500 5" [125] 10.00" [254] 10.30" [261.6] 10.50" [266.4]
Technical Data F05
B6600 6" [150] 11.00" [279.4] 12.50" [317.5] 11.70" [296.9]
Control 2 to 10 VDC, 4 to 40 mA (default)
variable (VDC, PWM, floating point, on/off)
Power supply 24 VAC ± 20% 50/60 Hz
24 VDC ± 10%
Power consumption running 12 W
holding 3 W
Transformer sizing 21 VA (Class 2 power source)
Electrical connection 3 ft,18 GA plenum rated cable
½” conduit connector
10 ft. [3m], 16 ft. [5m]
Overload protection electronic throughout 0° to 95° rotation
P10419 - 09/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
117
GKRX24-MFT-5-14 Actuators, Multi-Function Technology, Fail-Safe
Wiring Diagrams
W399_08
1 Provide overload protection and disconnect as required.
W399_08
Contact closures A & B also can be triacs.
8 A & B should both be closed for triac source and open for triac sink.
For triac sink the common connection from the actuator
9 must be connected to the hot connection of the controller.
PWM
WARNING Live Electrical Components!
W399_08
During installation, testing, servicing and troubleshooting of this product, it
may be necessary to work with live electrical components. Have a qualified
licensed electrician or other individual who has been properly trained in
handling live electrical components perform these tasks. Failure to follow all
electrical safety precautions when exposed to live electrical components could
result in death or serious injury.
W399_08
118
Accessories
CCV-EXT-KIT, CCV and PICCV Valve Neck Extension Kit
Application
The CCV-EXT-KIT can be used with most CCV’s* and PICCV in order
to achieve a large clearance over the pipe. The Extension Kit will
D165
provide an additional 2” of space between the top of the valve and the
base of the actuator. bracket is made from aluminum and is not
intended as a thermal block.
– Extension kit will be automatically assembled with any
Flanged CCV assembly.
Technical Data
Extension Height 2"
Total Weight 0.7 lb
Material
Extension Housing Aluminum - Anodized
Shaft Stainless Steel
Threaded Hardware Stainless Steel
Bearing Oilite® Bearing
Retaining Clip Stainless Steel
Available for Spring TR LRB (X) ARB (X) TF LF AF
and Non-Spring
Extension Bracket
Actuators
CCV-EXT-Kit
• • • • • •
* Cannot be used with N4 actuators.
* Available for previous NF assemblies.
* CCV-EXT-KIT cannot be used with any valve smaller than the
B212(B) and B312(B).
* For use with B2 and B3 series only. Cannot be used with B6 series.
P10419 - 09/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
2"
1.65" 1.65"
119
Accessories
ZS-CCV... New Characterized Control Valve Weather Shield
Application
The ZS-CCV... weather shield provides moderate protection for valves
which are mounted outdoors. This product is designed as a water tight
enclosure. The housing allows easy mounting over the actuator, while
allowing easy viewing of the actuator in operation. Weather shield for
PICCV/CCV to provide protection for actuators in outdoor applications.
Specifications
Cover PETG with UV resistant smoke tint
Perimeter Gasket Silicon Rubber
Rubber Gasket Silicon Rubber
Spring Clips Stainless Steel
Temperature limitations: -22˚F to 122˚F (-30˚C to 50˚C)
Plate (ZS-CCV-100) Aluminum
Plate Galvaneal w/black powder coat
L W H
16.25” [413] 8.75” [222] 4.5” [114]
Parts List
Cover including Rubber Perimeter Gasket, Rubber Gasket
Back Plate
120
Accessories
Auxiliary Switches S1A, S2A
For non-spring return direct-coupled actuators
Application
The S1A and S2A auxiliary switches are used to indicate when a
desired position of a valve is reached or to interface additional
controls for a specific control sequence.
Operation
The S1A and S2A auxiliary switches are mounted onto the direct coupled
actuator. The switches are modular units that mount directly onto LR and
AR type actuators and are locked into place by guiding grooves on the
sides of the actuator.
A driver disk is attached to the actuator handle and offers direct
transmission of the actuator position to the micro switch cams. The
switching points can be set over the full scale of 0 to 1 simply by
adjusting the slotted discs.
Types
S1A 1 SPDT 3 ft, 18 GA Appliance Cable
S1A/300 1 SPDT 6 ft, 18 GA Appliance Cable
S1A/500 1 SPDT 10 ft, 18 GA Appliance Cable
Wiring Diagram
Mounting Instructions
1. Press down the manual override button and rotate the actuator
fully counter clockwise.
2. Place the switch/potentiometer adaptor onto the hex shaft of the
handle which is in the center of the valve/actuator coupling.
3. Slide switch onto the actuator using the actuator guiding grooves
on the sides of the actuator.
4. Check for correct mating of the adaptor to the switch.
5. Adjust switch dials as necessary.
121
Accessories
Feedback Potentiometer P...A
For the non-spring return direct-coupled actuators
Application
The P…A feedback potentiometers are used with LR and AR actuators
to provide a resistive signal which varies with valve position.
The P…A units are applied with commercial proportional temperature
controllers to provide feedback of the valve position, or with electric or
electronic meters to provide position indication. The signal can also be
used as a positioner for parallel operation of multiple actuators.
Operation
The P…A feedback potentiometers are mounted onto the direct coupled
actuator. The switches are modular units that mount directly onto LR and
AR type actuators and are locked into place by guiding grooves on the
sides of the actuator.
A driver disk is attached to the actuator handle and offers direct
transmission of the actuator position to the micro switch cams.
Types
P140A Feedback Potentiometer 140 Ω
P200A Feedback Potentiometer 200 Ω
P500A Feedback Potentiometer 500 Ω
P1000A Feedback Potentiometer 1000 Ω
P2800A Feedback Potentiometer 2800 Ω
P5000A Feedback Potentiometer 5000 Ω
P10000A Feedback Potentiometer 10000 Ω
122
Wiring Accessories
Protective Terminal Cover
For the non-spring return direct-coupled actuators
Application
Belimo non-spring return actuators with terminal strips are can be
converted from NEMA 1/IP20 to NEMA 2/IP54 using the protective
terminal cover ZS-T.
Terminal
Cover Conduit
Fitting
Rubber
Seals
123
MFT Standard Configuration
P-10013 A13 0.0 to 10.0 VDC 2.0 to 10.0 VDC 150 100 Manual
P-10015 A15 2.0 to 5.0 VDC 2.0 to 10.0 VDC 150 100 Manual
P-10016 A16 2.0 to 6.0 VDC 2.0 to 10.0 VDC 150 100 Manual
P-10017 A17 6.0 to 10.0 VDC 2.0 to 10.0 VDC 150 100 Manual
P-10018 A18 14.0 to 17.0 VDC 2.0 to 10.0 VDC 150 100 Manual
P-10020 A20 9.0 to 12.0 VDC 2.0 to 10.0 VDC 150 100 Manual
P-10028 A28 0.0 to 10.0 VDC 0.0 to 10.0 VDC 100 100 Manual
P-10031 A31 0.0 to 4.0 VDC 2.0 to 10.0 VDC 150 100 Manual
P-10063 A63 0.5 to 4.5 VDC 0.5 to 4.5 VDC 150 100 Manual
P-10064 A64 5.5 to 10.0 VDC 5.5 to 10.0 VDC 150 100 Manual
P-20001 W01 0.59 to 2.93 sec. 2.0 to 10.0 VDC 150 100 Manual
P-20002 W02 0.02 to 5.00 sec. 2.0 to 10.0 VDC 150 100 Manual
PWM
P-20003 W03 0.10 to 25.50 sec. 2.0 to 10.0 VDC 150 100 Manual
P-20004 W04 0.10 to 25.60 sec. 2.0 to 10.0 VDC 150 100 Manual
P-20005 W05 0.10 to 5.20 sec. 0.0 to 5.0 VDC 150 100 Manual
P-30001 F01 Floating point 2.0 to 10.0 VDC 150 100 Manual
Floating Point
P-30002 F02 Floating point 0.0 to 10.0 VDC 150 100 Manual
P-30003 F03 Floating point 2.0 to 10.0 VDC 100 100 Manual
P-30004 F04 Floating point 0.0 to 5.0 VDC 100 100 Manual
P-30005 F05 Floating point 0.0 to 10.0 VDC 100 100 Manual
P-30006 F06 Floating point 0.0 to 5.0 VDC 150 100 Manual
P-40001 J01 On/Off 2.0 to 10.0 VDC 75 100 Manual
P-40002 J02 On/Off 2.0 to 10.0 VDC 150 100 Manual
On/Off
Example: AF24-MFT US is the basic model. Add the P… pre-set MFT configuration number and list price to the actuator when ordering, as needed.
Note: V-codes used for NV…Series actuator. All other MFT actuators use P-codes.
Note: Most popular configurations available at no additional cost.
Note: If the configuration needed is not listed, please fill in pg. 112 or call Belimo Customer Service at 800-543-9038.
Note: For Non-Spring Return Actuators the 3-digit code can be used in place of the P… pre-set MFT configuration number.
124
MFT Programming Codes, Flexible Products
PRODUCTS
Base Actuator Angle of
MODEL Control Input Feedback Running Time Power Supply VA Rating Weight (lb)
Codes Rotation/Stroke
LRX24-3 LR000 On/Off, Floating Point — 95 (Default) 95 deg 24 VAC/DC 3 1.08
LRX24-SR LR030 2-10 VDC (4-20mA*) — 95 (Default) 95 deg 24 VAC/DC 3 1.08
45 in-lb [5 Nm]
LRX24-PC LRXX0† 0-20 V Phasecut 2-10 VDC 95 (Default) 95 deg 24 VAC/DC 3 1.08
LRX24-MFT LR100 2-10 VDC (Default) 2-10 VDC 150 (Default) 95 deg 24 VAC/DC 3 1.08
LRX24-MFT95 LRXX0† 0 to 135 Ohm 2-10 VDC 150 (Default) 95 deg 24 VAC/DC 3 1.08
LRX120-3 LR060 On/Off, Floating Point — 95 (Default) 95 deg 120-240 VAC 3 1.08
LRX120-SR LR450 2-10 VDC (4-20mA*) — 95 (Default) 95 deg 120-240 VAC 3 1.08
P-10013 A13 0.0 to 10.0 VDC 2.0 to 10.0 VDC 150 100 Manual
P-10015 A15 2.0 to 5.0 VDC 2.0 to 10.0 VDC 150 100 Manual
P-10016 A16 2.0 to 6.0 VDC 2.0 to 10.0 VDC 150 100 Manual
P-10017 A17 6.0 to 10.0 VDC 2.0 to 10.0 VDC 150 100 Manual
P-10018 A18 14.0 to 17.0 VDC 2.0 to 10.0 VDC 150 100 Manual
P10419 - 09/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
P-10020 A20 9.0 to 12.0 VDC 2.0 to 10.0 VDC 150 100 Manual
P-10028 A28 0.0 to 10.0 VDC 0.0 to 10.0 VDC 100 100 Manual
P-10031 A31 0.0 to 4.0 VDC 2.0 to 10.0 VDC 150 100 Manual
P-10063 A63 0.5 to 4.5 VDC 0.5 to 4.5 VDC 150 100 Manual
P-10064 A64 5.5 to 10.0 VDC 5.5 to 10.0 VDC 150 100 Manual
P-20001 W01 0.59 to 2.93 sec. 2.0 to 10.0 VDC 150 100 Manual
P-20002 W02 0.02 to 5.00 sec. 2.0 to 10.0 VDC 150 100 Manual
PWM
P-20003 W03 0.10 to 25.50 sec. 2.0 to 10.0 VDC 150 100 Manual
P-20004 W04 0.10 to 25.60 sec. 2.0 to 10.0 VDC 150 100 Manual
P-20005 W05 0.10 to 5.20 sec. 0.0 to 5.0 VDC 150 100 Manual
P-30001 F01 Floating point 2.0 to 10.0 VDC 150 100 Manual
Floating Point
P-30002 F02 Floating point 0.0 to 10.0 VDC 150 100 Manual
P-30003 F03 Floating point 2.0 to 10.0 VDC 100 100 Manual
P-30004 F04 Floating point 0.0 to 5.0 VDC 100 100 Manual
P-30005 F05 Floating point 0.0 to 10.0 VDC 100 100 Manual
P-30006 F06 Floating point 0.0 to 5.0 VDC 150 100 Manual
P-40001 J01 On/Off None 75 100 Manual
P-40002 J02 On/Off 2.0 to 10.0 VDC 150 100 Manual
On/Off
125
Custom MFT Configuration Order Form
FAX: USA Toll Free 1-800-228-8283
#1 Select an Actuator
(use one sheet for each unique actuator/configuration)
Name _______________________________________________________________________________
Quantity Quantity
❑ AF24-MFT US ______ ❑ AMX24-MFT ______
Company ____________________________________________________________________________
❑ AF24-MFT-S US ______ ❑ AMX24-MFTX1 ______
❑ NF24-MFT US ______ ❑ NMX24-MFT ______
Address _____________________________________________________________________________
❑ LF24-MFT US ______ ❑ NMX24-MFTX1 ______
❑ LF24-MFT-S US ______ ❑ LMX24-MFT ______
City_______________________________________ State _____________Zip _____________________
❑ AF24-MFT95 US ______ ❑ LMX24-MFTX1 ______
❑ NV24-MFT US ______ ❑ LRX24-MFT ______
Phone_____________________________________ Fax_______________________________________
❑ NVF24-MFT US ______ ❑ GMX24-MFT95 ______
❑ NVF24-MFT-E US ______ ❑ AMX24-MFT95 ______
Email _____________________________________
❑ NVFD24-MFT US ______ ❑ NMX24-MFT95 ______
❑ NVFD24-MFT-E US ______ ❑ LMX24-MFT95 ______
FIELD LABELING: LBL-MFT
❑ GMX24-MFT ______ ❑ LHX24-MFT ______
❑ GMX24-MFTX1 ______ ❑ LUX24-MFT ______ ❑ Custom configuration labels required
1-3/8” X 1-¼” orange labels preprinted to your specifications 12 label sets per sheet.
(-S=Auxiliary Switch) Includes configuration code and wiring labels.
Stop .
5 Override control and Min. (min. position) = % (0...100%) (beginning of working range) default 0
electronic angle of ZS (intermediate position) = % (0...100%) (0% = Min.; 100% = Max.) default 50
rotation limiting Max. (max. position) = % (0...100%) (end of working range) default 100