Professional Documents
Culture Documents
1994 Detection of Arc in SWGR
1994 Detection of Arc in SWGR
Systems
930
sult of the frequency domain analysis of the fault cur-
rent is that there is a significant dynamic increase in
the magnitude of even harmonics. The unsymmetri-
cal waveform of the fault current causes this increase
in magnitude of the even harmonics. A second im-
portant result of the frequency analysis is that the
magnitudes of the 3rd and non-triplen odd harmon-
ics, introduced by the controller, were reduced by the
arcing fault event. The * 3 harmonic was reduced to
'
almost 12 per-cent, also the 5'" to around 15 per-cent
and 7"'to 11 per-cent of the fundamental component.
This reduction can be best explained as follows: The
electric arc, staged between two sample wires. has a
significant non-linear impedance. When the arc oc- I
06 061 O Q 063 084 065 o s 067 0- 089 07
curs, the arc impedance connected in parallel with bn(-I
the load causes additional current with random, non- Figure 3: Arcing fault current under full load
linear intervals. Arc impedance is resistive in nature.
The current drawn by the load bank has both real and tortion of the current is due t o the non-linear nature
imaginary components. The real part of the current of the arcing fault impedance. As the fault strikes
is due to the resistive part of the load. The imaginary with random intervals, additional resistive load is be-
component of the current is due to the inductive part ing added into the system load. This increases the
of the entire load bank. Therefore the additional cur- magnitude of the current for an unpredictable dura-
rent drawn by the arc impedance combines with the tion. Frequency analysis results of this fault current
current of the resistive load present in the system. is given in Figure 6.
This increases the magnitude of the total complex Frequency domain analysis. in this case. demon-
strated ele\ation of magnitudes of both even and odd
order harmonics. The staged fault given in Figure 5
has a considerably long duration. The second method
employed to start the arcing faults in this study w a s
!
'O'I ozr F-?--WW
contamination with saline solution. None of the pa-
rameters of the experimental system were modified, to
obtain consistency with the method discussed previ-
ously. The only difference was, instead of placing fine
iron wire across the sample wires, they were contam-
inated with several drops of saline solution and the
fault path was created through this contamination.
The faults, in this case also, were staged under differ-
ent system loads. Under the full load and inductive
load conditions, the changes of the harmonic compo-
sition of the system current during arcing fault events
started with saline solution and iron wire were in good
Figure 2: Harmonic composition of system current approximation. The last method employed t o start
with full load staged arcing faults was contamination with graphite
current in the system. The increased combination of dust. The arcing faults initiated in this way caused
inductive and resistive loading becomes more domi- the worst damage t o the sample wires. The distorted
nant in the characteristics of the current waveform waveform of the fault current under full load condi-
during the random arcing strikes and reduces the ef- 1
93 1
monics showed an increase in magnitude during the
arcing events under the inductive loading, under the
full load condition odd order harmonics showed a sig-
nificant reduction in relative magnitude. This clearly
suggests that odd harmonics are strongly depended
upon the status of the load in the system. Figure
10 exhibits the mean and the standard deviation of
per-unit reduction of odd harmonics, with respect to
normalized pre-event magnitude, during ardng events
under the full load.
-1 5
08 081. OQ OQ OM om o s 087 o s om os
a(-)
932
DETECTOR ARCHITECTURE The -Ith harmonic of the system current 14,
933
Table 2: '
Magnltude varialioma o? odd harmonics
81" n c a started wlth km w h COMBINATIONS OF THE STATES DESCRIBING
M1h-k-
THE OPERATION OF THE SYSTEM
1.1
I
VE h 4 Vhiph Operation
1 0 0 0 Inductive load operation
1 0 0 1 N.A.
1 0 1 0 Arcing Fault
1 0 1 1 Switchinginductiveload
1 1 0 0 Motor controller operation
1 1 0 1 N.A
1 1 1 0 N A.
1 1 1 1 Motor controller switched-on
References
Figure 10 Magnitude variations of odd harmonics
under full load [l] Aucoin, B. M. and B. Don Russell, "Distribution
High Impedance Fault Detection Utilizing High
Frequency Current Components", IEEE l h n s
actions on Power Appamtus and Systems, Vol.
PAS-101,No. 6 June 1982.
[2]Russell, B. Don., Ketan Mehta and Ram P. Chin-
ch&, "An Arcing Fault Detection Technique Us-
ing Low Frequency Current Components Perfor-
mance Evaluation Using Recorded Field Data",
IEEE l h n s a c t w n s on Power Delivery, Vol. 3,
No. 4, October 1988.
[3] Russell, B. Don. and Ram P. Chinchali, "A dig-
ital Signal Processing Algorithm For Detecting
Arcing Faults On Power Distribution Feeders",
Figure 11: Decision making stage of the detector IEEE lhnsactions on Power Delivery, Vol. 4,
No. 1, January 1989.
fundamental component of current can easily achieve
protection against bolted short circuits. In fact, con- [4]Russell, B. Don, Ram P. Chinchali. and C.
ventional overcurrent protection devices are able to J. Kim, "Behaviour Of Low Requency Spec-
clear short circuits dectively. Thus total protection tra During Arcing Fault And Switching Events",
should be accomplished by combining an arcing fault IEEE lhnsactions on Power Delivery, Vol. 3,
detector with a conventional overcurrent protective No. 4, October 1988.
device. Table 2 gives all of the possible combinations 151 Kwon, Hynn Wook, Gi Won Lee. Young Moon
of the states and the corresponding operation of the Park, Man Chull Yoon, and Myeong Ho Yoo,
system. "High Impedance Fault Detection Utilizing In-
'
Some of the combinations of the states do not cor- cremental Variance Of Normalized Even Order
respond t o any one of the operation characteristics of Harmonic Power", IEEE Tmnsactions on Power
the system and they were marked as N.A (Not Appli- Delivery, Vol. 6 , No. 2, April 1991.
cable).
[6] Huang, Ching-Lien, Hui-Yung Chui and Ming-
CON CL USlONS Tong Chen, "Algorithm Comparison For High
Impedance h u l t Detection Based On Staged
The effects of electrical arcing faults in the low volt-
age electrical distribution system were discussed. A Fault Test", IEEE ~ n a a c t w n son P e r De-
method t o clear such faults was suggested. The sim- livery, Vol. 3, No. 4, October 1988.
ilarity of the waveform properties of the system cur- [PI Emanuel, A. E. and E. M. Gullachensld, "High
rent under switching operations and arcing faults was Impedance Fault Arcing On Sandy Soil in 15kV
emphasized. The method of monitoring the system Distribution Feeders: Contributions To The
voltage to prevent nuisance circuit clearing during E d u a t i o n Of The Low Frequency Spectrum",
switching events was described. The results of this ZEEE lhnsactwns on Power Delivery, Vol. 5,
study showed that the undesirable conclusion of arc- No. 2, April 1990.
ing faults, complete bumdown, can be prevented.
The aerospace industry has also suffered from the [8]Howell, E. Keith, "How Switches Produce Elec-
disastrous effects of arcing faults. The detector ar- trical Noise", IEEE Tmnsaetions on Electnnnag-
chitecture presented here should apply t o aerospace netic Compotibilify,Vol. EMC-21, No. 3, August
applications with some modifications. 1979.
934
[9] Jeerings, D. I. and J. R. Linders, "Unique Xs-
pects Of Distribution System Harmonics Due To [21] Linden, John R., "Electric Wave Distortions:
High Impedance Ground Faults", IEEE Tons- Their Hidden Cost nd Containment", IEEE
actions on Power Delivery, Vol. 5. So. 2, April Tmnsactions On Industry .4pplications, Vol. Li-
1990. 15, So. 5, September-October 1979.
['22] Dunk-Jacobs, J. R., "The Effects Of Arcing
[lo] Jeerings. D. I. and J. R. Linders. --IPractical
Ground Faults On Low-Voltage System Design",
Protective Relay For Doan-Conductor Faults",
IEEE Transactions On Industry .4pplications,
IEEE Tmnsactions on Power Delivery, Vol. 6,
Vol. L4-8, No. 3, May-June 1972.
No. 2, April 1991.
[23] Frequency Devices, IKC., 25 Locust St.. Haver-
[ l l ] Gopal, S., Rao, Y. K., "Flashover Phenomena Of hill, MA 01830.
Polluted Insulators'. IEE Proceedings, Vol. 131,
Pt. C, No 4. July 1984. [24] Ece, Dogan Gokhan, "The Effects Of Electrical
Faults On Physical Properties Of Polyimide In-
[12] Low, S .S. and Boehne, E. W.,-Flashovers sulated Electrical Wire", Vanderbilt University
Across Porcelain Clad Circuit Breakers Due To Thesis, 1990.
Atmospheric Contamination', IEEE Tmnsac-
tzons On Power Appamtus -4nd Systems, Vol.
Psis-98, No. 3 MayJune 1979.
935