Download as pdf or txt
Download as pdf or txt
You are on page 1of 79

SUMMARY OF BILL OF QUANTITIES

PROJECT : SAUDI FOOD AND DRUGS AUTHORITY, DAMMAM

FACILITY : MAIN LABORATORY BUILDING

S.No. Description Total Amount

1. STRUCTURAL WORK
Page 2 to 4

2. ARCHITECTURAL WORK
Page 5 to 26

3. PLUMBING WORK
Page 27 to 35

4. HVAC WORK
Page 36 to 50

5. ELECTRICAL WORK
Page51 to 79

TOTAL AMOUNT
In Words :

SFDA, Dammam Page 1


BILL OF QUANTITIES

PROJECT : SAUDI FOOD AND DRUGS AUTHORITY, DAMMAM

FACILITY : MAIN LABORATORY BUILDING

SECTION : STRUCTURAL WORK

S.No. Description Unit Qty Unit Rate Total Amount

NOTES :
The Contractor should consider while quoting
the necessary protection works to the existing
building structures in coordination with the
Engineer in-charge.

1.0 DEMOLITION WORKS:

1.1 Demolition of existing RC walls at Ground floor M2 39


existing Store (GF - 1C) as shown in as built
drawing and to give way to the proposed new
design and construction.

1.2 Cutting and demolishing of the existing grade Job 1


slab at Ground floor up to required limit to give
way for the proposed new electro / mechanical
pipings and conduitings as per the drawing.

1.0 EARTH WORK :


The size of excavation trench is assumed as the
size of the raft foundation with an allowance of
1000mm around the raft foundation.

3
1.1 Excavation for foundation in any type of soil M 742
including dewatering.

3
1.2 Backfilling for foundation and below grade slab M 500
by suitable materials including compaction in
layers.

1.3 Filling and compaction in layers below grade M3 24


slab up to required level as per drawing.

1.4 Filling and compaction of 150mm thick M3 24


capillary water barrier below grade slab.

2.0 ANTI-TERMITE TREATMENT :

2.1 Anti - termite treatment below grade slab. M2 190

Page Sub-total

SFDA, Dammam Page 2


FACILITY : MAIN LABORATORY BUILDING

SECTION : STRUCTURAL WORK (Contd. . .)

S.No. Description Unit Qty Unit Rate Total Amount

2.2 Anti - termite treatment around the building M2 39


300mm wide.

3.0 CONCRETE :
Including formwork, reinforcement, sundries,
embedded items not included elsewhere,
waterstopper, other concreting materials and
accessories.

3.1 100mm thick plain concrete below Raft M3 32


Foundation.

3.2 50mm thick plain concrete below grade beams M3 1


and entrance steps toe beams.

3.3 Reinforced concrete for Raft foundation. M3 161

3.4 Reinforced concrete for column neck. M3 8.5

3.5 Reinforced concrete for columns above grade M3 74


slab.

3.6 Reinforced concrete for grade beams and M3 5


entrance steps toe beams.

3.7 Reinforced concrete for grade slab with 4mm M3 28


thick control joint including steps and ramp.

3.8 Reinforced concrete for drop beams, solid M3 231


slabs, staircase waist & landing slab and and
parapet coping.

3
3.9 Reinforced concrete for Elevator shaft up to M 6
grade slab.

3.10 Reinforced concrete for Elevator shaft above M3 52


grade slab.

3.11 Reinforced concrete for Planted Walls (PW). M3 48

3.12 Reinforced concrete for solid slab including M3 15


metal decking (for existing duct chase).

Page Sub-total

SFDA, Dammam Page 3


FACILITY : MAIN LABORATORY BUILDING

SECTION : STRUCTURAL WORK (Contd. . .)

S.No. Description Unit Qty Unit Rate Total Amount

4.0 MOISTURE PROTECTION :

4.1 200microns polyethelene sheet. M2 190

4.2 Bituminous paint, 2coats for raft foundation, M2 710


column necks, walls and grade beams.

4.3 4mm thick waterproofing membrane (2 layers) M2 43


below raft foundation of elevator pit.

4.4 4mm thick waterproofing membrane (2 layers) M2 23


for side walls of elevator pit.

4.5 50mm thick protection screed for waterproofing M2 43


below raft foundation of elevator pit.

4.6 10mm thick protection board of approved M2 23


quality for side walls of elevator pit.

5.0 ISOLATION JOINT :

5.1 10mm thick isolation joint with flexible filler and Lm 192
sealant.

5.2 20mm thick horizontal expansion joint with filler Lm 253


and sealant for concrete beams / slab.

5.3 20mm thick vertical expansion joint with filler Lm 151


and sealant for concrete columns / CMU walls.

Page Sub-total

TOTAL STRUCTURAL WORK - Main Laboratory Building

SFDA, Dammam Page 4


PROJECT : SAUDI FOOD AND DRUGS AUTHORITY, DAMMAM

FACILITY : MAIN LABORATORY BUILDING

SECTION : ARCHITECTURAL WORK

S.No. Description Unit Qty Unit Rate Total Amount

1.0 DEMOLITION WORKS:

Notes :

a.) All materials and finishes to be retained


but damaged during demolition or during
the execution of works shall be repaired
and restored to its original state to match
existing at Contractor's expense.

b.) All dismantled items / materials with value


and which are required to be re-used
shall be removed with care, protect from
damage and store in a place as instructed
by the Engineer.

c.) All demolished materials without value or


which are not required to be re-used shall
be disposed-off properly together with the
construction debris to designated
dumping area.

d.) Disposal of Construction debris and all


other trashes shall be properly scheduled
and done in a manner which will not cause
inconvenience to adjacent property in
operation nor with it pollute the
surrounding environment.

e.) Contractor shall investigate the site


prior to pricing.

1.1 Demolition of existing 300mm thick Perimeter M2 130


CMU walls up to required limit at Ground floor,
First floor, Second floor and Roof deck to give
way for the proposed construction.

1.2 Demolition of existing 200mm, 150mm and M2 4,140


100mm thick internal CMU walls up to
slab/beam soffit at Ground floor, First floor and
Second floor to give way for the proposed
construction.

Page Sub-total

SFDA, Dammam Page 5


FACILITY : MAIN LABORATORY BUILDING

SECTION : ARCHITECTURAL WORK (Contd. . .)

S.No. Description Unit Qty Unit Rate Total Amount

1.3 Removing the existing floor finishes, likes M2 3,289


Marble tiles, Unglazed ceramic tiles, Porcelain
tiles, etc., including skirting and all related works
to give way for the proposed new design and
construction.

1.4 Removing the existing floor finishes, likes M2 321


Broadloam carpet including skirting and
chipping the existing underlay to give way for
the proposed new design and construction.

1.5 Removing the existing suspended ceiling likes, M2 3,231


600 x 600mm Acoustic tiles, Perforated metal
ceiling tiles and Gypsum board ceiling with
Gypsum cornice including suspension system
and all related electro/mechanical works to give
way for the proposed new design and
construction.

1.6 Removing of existing external glass doors, Ea 7


type D-01, type D-8, type D-09 and type D-10
fixed on masonry walls including side and top
panels and all related accessories to give way
for the proposed new design and construction.

1.7 Removing of existing internal glass doors, Ea 9


type D-12, type D-13, type D-14, type D-15 and
type D-17 fixed on masonry walls including side
and top panels and all related accessories to
give way for the proposed new design and
construction.

1.8 Removing of existing internal wooden doors, Ea 138


type D-02, type D-03, type D-03A, type D-05,
type D-06, type D-07, type D-11 and type D-16
fixed on masonry walls including all related
accessories to give way for the proposed new
design and construction.

1.9 Removing of existing external and internal glass Ea 93


windows on powder coated aluminum frame,
type W-01 to type W-05, fixed on masonry walls
including all related accessories to give way for
the proposed new design and construction.

Page Sub-total

SFDA, Dammam Page 6


FACILITY : MAIN LABORATORY BUILDING

SECTION : ARCHITECTURAL WORK (Contd. . .)

S.No. Description Unit Qty Unit Rate Total Amount

1.10 Removing of existing Laboratory caseworks, Job 1


Fume hood cupboards and related works, etc.,
in all Laboratory rooms at Ground floor, First
floor and Second floor to give way for the
proposed new design and construction.

1.11 Removing of existing Kitchen cabinets at First Lm 7


floor and Second floor Kitchen area including
all related works to give way for the proposed
new design and construction.

1.12 Removing of existing receiving counter, Lm 26


follow-up section counter and business service
counter at Ground and Second floor respectively
including all related works to give way for the
proposed new design and construction.

1.13 Removing of existing Glass partition at existing M2 30


Milk testing room including all related works to
give way for the proposed new design and
construction.

1.14 Removing of existing Cold store (Refrigerator)


wall, floor and ceiling panels including doors
and all related works to give way for the
proposed new design and construction.

1.14.1 Dimension - 5.10 / 3.20 x 5.10 / 3.70m (GF-08) Ea 1

1.14.2 Dimension - 5.00 x 5.10m (GF-09) Ea 1

1.15 Removing of existing Staircase finishes for


landing, step treads and risers including
skirting and all related works to give way for the
proposed new finishes.

1.15.1 Broadloam carpet for landing including underlay M2 9

1.15.2 Broadloam carpet for step treads and risers Lm 89


including underlay.

1.15.3 Marble tiles and unglazed ceramic tiles M2 9


including underlay (mortar) for landing.

Page Sub-total

SFDA, Dammam Page 7


FACILITY : MAIN LABORATORY BUILDING

SECTION : ARCHITECTURAL WORK (Contd. . .)

S.No. Description Unit Qty Unit Rate Total Amount

1.15.4 Marble tiles and unglazed ceramic tiles Lm 147


including underlay (mortar) for step treads and
risers.

1.16 Demolition of existing main entrance steps, M2 48


side entrance steps and ramps including all
related works to give way for the proposed new
design and construction.

1.17 Removing of existing Sunscreen at external M2 1,475


elevation including all related works to give way
for the proposed new design and construction.

1.18 Removing of existing Staircase railings with Lm 220


vertical supports including all related works to
give way for the proposed new design and
construction.

1.19 Removing of existing Internal and External Job 1


signages including all related works to give way
for the proposed new design and construction.

1.20 Demolition of existing HVAC equipments pad Job 1


including related works to give way for the
proposed new design and construction.

1.21 Removing of existing Precast panel along grid Ea 5


line 2 / J, K, L&M and grid line B&U / 3&4,
including related works to give way for the
proposed new design and construction.

1.22 Removing of existing precast panel along grid Lm 100


line 1&6 / A to V (top of existing Sunscreen)
incliding all related works to give way for the
proposed new design and construction,
approximate height = 1.50m(as per elevation).

1.23 Removing of existing precast panel on top of Ea 1


main entrance door including related works to
give way for the proposed new design and
construction ( Approx. size = 5.0 x 0.80m).

Page Sub-total

SFDA, Dammam Page 8


FACILITY : MAIN LABORATORY BUILDING

SECTION : ARCHITECTURAL WORK (Contd. . .)

S.No. Description Unit Qty Unit Rate Total Amount

1.24 Cutting and demolishing of existing precast Ea 2


panel along grid line 5 / A&V (Corner) up to
required limit as shown in drawing including
related works to give way for the proposed new
design and construction.

1.25 Removing of existing wall tiles along existing Job 1


perimeter walls up to required limit to received
new cement plaster or new wall finishes as per
the proposed new design and construction.

1.26 Removing of existing paint on existing CMU Job 1


walls to be retained, to received new cement
plaster and finishes as per the proposed new
design and construction.

2.0 BLOCK WORK :


Including joint reinforcement, lintels,
miscellaneous concrete wall elements,
other masonry materials and
accessories.

2.1 300mm thick insulated CMU (150mm thk CMU M2 720


+ 50mm thk insulation + 100mm thk CMU)

2.2 200mm thick insulated CMU. M2 395

2.3 200mm thick CMU. M2 1,684

2.4 150mm thick CMU. M2 2,611

2.5 100mm thick CMU. M2 354

3.0 METAL WORK :


Including jointing materials, paint, hardware and
accessories.

3.1 Supply and install aluminum trellis with extruded


airfoils (Demi-fins) factory paint baked enamels
or powder coated horizontal sunscreen (typical)
including all necessary materials and fixing
accessories required to complete the work as
per the drawing.

Page Sub-total

SFDA, Dammam Page 9


FACILITY : MAIN LABORATORY BUILDING

SECTION : ARCHITECTURAL WORK (Contd. . .)

S.No. Description Unit Qty Unit Rate Total Amount

3.1.1 Size, 2.20 x 3.10m Ea 74

3.1.2 Size, 2.20 x 3.31m Ea 6

3.1.3 Size, 1.10 x 2.90m Ea 2

3.1.4 Size, 1.60 x 7.20m Ea 1

3.2 Suply and install Horizontal Aluminum profile


factory paint baked enamels (or powder coated)
finish as shown in drawing including fixing
accessories and all necessary materials to
complete the works.

3.2.1 Size, 350mm thick x 600mm wide Lm 117

3.2.2 Size, 350mm thick x 400mm wide Lm 8

3.2.3 Size, 350mm thick x 300mm wide Lm 13

3.3 Suply and install decorative aluminum cladded Lm 320


horizontal strips in powder coated finish as per
profile as shown in drawing including fixing
accessories and all necessary materials to
complete the works.

3.4 Supply and install Aluminum Header Entrance M2 29


Canopy in powder coated finish as shown in
drawing including fixing accessories and all
necessary materials to complete the works.

3.5 Supply and install 60mm dia. Stainless steel Lm 13


handrailing with vertical support at on top of
Planter box in chromed finish as shown in
drawing including fixing accessorie and all
necessary materials to complete the works.

3.6 Supply and install 75 mm diameter x 2mm


handrail, 50mm x 30mm vertical post and
30mm x 2mm horizontal railings all in stainless
steel including fixing accessories and all
necessary materials to complete the works.

3.6.1 At Staircase 1 to 4 as shown in the drawings, Lm 255


(typical).

Page Sub-total

SFDA, Dammam Page 10


FACILITY : MAIN LABORATORY BUILDING

SECTION : ARCHITECTURAL WORK (Contd. . .)

S.No. Description Unit Qty Unit Rate Total Amount

3.7 Supply and install Stainless steel Tripod Ea 1


Turnstile gate barrier ( 0.8 m High ) w/ swing
Gate barrier

3.8 Supply and install Stainless steel swing Ea 1


Gate barrier ( 0.8 m High )

4.0 THERMAL AND MOISTURE PROTECTION :

4.1 ROOF FINISHES AND PROTECTION :

4.1.1 50mm thick washed gravel topping M2 242

4.1.2 Felt Layer (2mm thick non-woven polypropylene M2 278


protective fabric).

4.1.3 4mm thick water proofing membrane with M2 278


primer.

4.1.4 Light Weight Concrete to Slope. M2 242

4.1.5 200 Microns Polyethelene Sheet. M2 278

4.1.6 Aluminum Flashing including sealant. Lm 119

4.2 WET AREA WATER PROOFING

4.2.1 2layers, 4mm thk waterproofing membrane with M2 195


bituminous asphalt primer to wet areas like
toilets, janitor room etc. including skirting

5.0 INSULATION

5.1 50mm thick extruded polysterene insulation for M2 242


roof.

6.0 DOORS AND FRAMES


Including glazing, painting, hardware, louver,
attachment materials and accessories
complete as per drawing and schedule. Actual
clear dimensions should be checked on site
prior to final fabrication and installation.

Page Sub-total

SFDA, Dammam Page 11


FACILITY : MAIN LABORATORY BUILDING

SECTION : ARCHITECTURAL WORK (Contd. . .)

S.No. Description Unit Qty Unit Rate Total Amount

6.1 Door type D-1, double leaves, swing type door Ea 2


with 12mm thick frameless single glazed
tempered clear glass with fixed side lite on both
sides and top portion, with top and bottom
stainless steel frames, handles, push plates and
fixing accessories. Provide SFDA logo, nylon
brush weatherstripping, door closer, stainless
steel threshold and all necessary accessories.
(6.0 x 4.01m)

6.2 Door type D-1A, single leaf, swing type door Ea 1


with 12mm thick frameless single glazed
tempered clear glass with fixed side lite on both
sides and top portion, with top and bottom
stainless steel frames, handles, push plates and
fixing accessories. Provide nylon brush
weatherstripping, door closer, stainless steel
threshold and all necessary accessories.
(2.92 x 2.90m)

6.3 Door type D-1B, double leaves, swing type Ea 1


door with 12mm thick frameless single glazed
tempered clear glass with fixed side lite on both
sides and top portion, with top and bottom
stainless steel frames, handles, push plates and
fixing accessories. Provide , nylon brush
weatherstripping, door closer, stainless
steel threshold and all necessary accessories.
(3.1 x 4.01m)

6.4 Door type D-2, double leaves, swing type fire Ea 6


rated hollow metal door on metal frame and
door jamb with semi-gloss enamel paint finish
and tight sealed with metal paint finish. Provide
door closer and all necessary accessories.
(1.70 x 2.20m)

6.5 Door type D-3, single leaf, swing type fire rated Ea 2
hollow metal door on metal frame and door jamb
with semi-gloss enamel paint finish, with 8mm
thick single glazed tempered clear glass
transom and tight sealed with metal paint finish.
Provide door closer and all necessary
accessories. (0.90 x 2.7m)

Page Sub-total

SFDA, Dammam Page 12


FACILITY : MAIN LABORATORY BUILDING

SECTION : ARCHITECTURAL WORK (Contd. . .)

S.No. Description Unit Qty Unit Rate Total Amount

6.6 Door type D-4, double leaves, swing type hollow Ea 24


core wooden flush door with oak veneer on both
sides on hardwood door jamb, with 8mm thick
clear safety pyrex glass panel. Provide door
closer and all necessary accessories.
(1.50 x 2.20m)

6.7 Door type D-5, double leaves, swing type hollow Ea 6


core wooden flush door with oak veneer on both
sides on hardwood door jamb, with 8mm thick
clear safety wired glass panel. Provide door
closer and all necessary accessories.
(2.050 x 2.20m)

6.8 Door type D-6, double leaves, swing type hollow Ea 3


core wooden flush door with oak veneer on both
sides on hardwood door jamb. Provide door
closer and all necessary accessories.
(1.70 x 2.20m)

6.9 Door type D-7, double leaves, swing type fire Ea 6


rated hollow metal door with metal louver at
lower portion on metal frame and door jamb
with semi-gloss enamel paint finish and tight
sealed with metal paint finish. Provide door
closer and all necessary accessories.
(1.50 x 2.20m)

6.10 Door type D-8, single leaf, swing type fire Ea 4


rated hollow metal door on metal frame and
door jamb with semi-gloss enamel paint finish
and tight sealed with metal paint finish. Provide
door closer and all necessary accessories.
(0.9 x 2.20m)

6.11 Door type D-8A, single leaf, swing type fire Ea 4


rated hollow metal door on metal frame and
door jamb with semi-gloss enamel paint finish
and tight sealed with metal paint finish. Provide
door closer and all necessary accessories.
(0.8 x 2.20m)

Page Sub-total

SFDA, Dammam Page 13


FACILITY : MAIN LABORATORY BUILDING

SECTION : ARCHITECTURAL WORK (Contd. . .)

S.No. Description Unit Qty Unit Rate Total Amount

6.12 Door type D-9, single leaf, swing type hollow Ea 17


core wooden flush door with oak veneer on both
sides on hardwood door jamb. Provide door
closer and all necessary accessories.
(0.90 x 2.20m)

6.13 Door type D-9A, single leaf, swing type hollow Ea 11


core wooden flush door with oak veneer on both
sides on hardwood door jamb and with 8mm
thick clear safety wired glass panel. Provide
door closer and all necessary accessories.
(0.90 x 2.20m)

6.14 Door type D-10, double leaves, swing type Ea 7


hollow core wooden flush door with oak veneer
on both sides on hardwood door jamb. Provide
door closer and all necessary accessories.
(1.25 x 2.20m)

6.15 Door type D-10A, single leaf, swing type Ea 2


hollow core wooden flush door with oak veneer
on both sides on hardwood door jamb. Provide
door closer and all necessary accessories.
(1 x 2.20m)

6.16 Door type D-11, double leaves, swing type Ea 54


hollow core wooden flush door with oak veneer
on both sides on hardwood door jamb and with
8mm thick clear safety wired glass panel.
Provide door closer and all necessary
accessories. (1.25 x 2.20m)

6.17 Door type D-12, double leaves, swing type Ea 2


hollow core wooden flush door with oak veneer
on both sides on hardwood door jamb and with
8mm thick clear safety wired glass panel.
Provide door closer and all necessary
accessories. (1.25 x 2.20m)

6.18 Same as above, but Door type D-12A, Ea 8


(1.50 x 2.20m)

Page Sub-total

SFDA, Dammam Page 14


FACILITY : MAIN LABORATORY BUILDING

SECTION : ARCHITECTURAL WORK (Contd. . .)

S.No. Description Unit Qty Unit Rate Total Amount

6.19 Door type D-13, single leaf, swing type hollow Ea 15


core wooden flush door with plastic laminated
facing on both sides on hardwood door jamb.
Provide lockset openable only from inside and
lock/unlock indicator. Also provide door closer
and all necessary accessories.
(0.70 x 2.20m)

6.20 Door type D-14, single leaf, swing type hollow Ea 5


core wooden flush door with plastic laminated
facing on both sides on hardwood door jamb.
Provide door closer and all necessary
accessories. (0.90 x 2.20m)

6.21 Door type D-15, single leaf, swing type hollow Ea 2


core wooden flush door with oak veneer on both
sides on hardwood door jamb. Provide door
closer and all necessary accessories.
(0.80 x 2.20m)

6.22 Door type D-16, double leaves, swing type Ea 1


hollow core wooden flush door with oak veneer
on both sides on hardwood door jamb and with
8mm thick clear safety wired glass panel.
Provide door closer and all necessary
accessories. (1.60 x 2.20m)

6.23 Door type D-16A, double leaves, swing type Ea 1


hollow core wooden flush door with oak veneer
on both sides on hardwood door jamb
Provide door closer and all necessary
accessories. (1.25 x 2.20m)

6.24 Door type D-17, single leaf, swing type hollow Ea 1


core wooden flush door with oak veneer on both
sides on hardwood door jamb. Provide door
closer and all necessary accessories.
(0.60 x 2.20m)

6.25 Door type D-18, double leaves, swing type Ea 2


hollow core wooden flush door with oak veneer
on both sides on hardwood door jamb and with
8mm thick clear safety wired glass panel.
Provide door closer and all necessary
accessories. (1.40 x 2.20m)

Page Sub-total

SFDA, Dammam Page 15


FACILITY : MAIN LABORATORY BUILDING

SECTION : ARCHITECTURAL WORK (Contd. . .)

S.No. Description Unit Qty Unit Rate Total Amount

6.26 Door type D-19, double leaves, swing type Ea 1


hollow core wooden flush door with oak veneer
on both sides on hardwood door jamb. Provide
door closer and all necessary accessories.
(1.70 x 2.20m)

6.27 Door type D-20, double leaves, swing type fire Ea 2


rated hollow metal door on metal frame and
door jamb with semi-gloss enamel paint finish
and tight sealed with metal paint finish. Provide
door closer and all necessary accessories.
(1.60 x 2.20m)

6.28 Door type FD-1 , wooden panel partitions Ea 2


folding door flush with oak veneer facing on
steel hanger Provide all necessary accessories
(0.9 x 2.10m)

6.29 Repaint existing Door type ED-4 to matched Ea 7


new Doors finish as shown in the drawing.

7.0 WINDOWS
Including glazing, painting, hardware,
attachment materials and accessories,
complete as per drawing and schedule.
Checked actual clear dimension on site prior
to final fabrication and installation.

7.1 Window type W-1, fixed type window with 8mm Ea 16


thick single glazed tempered clear glass on
aluminum powder coated frames. Provide all
necessary accessories. (3.00 x 1.60m)

7.2 Window type W-2, fixed type window with 8mm Ea 25


thick single glazed tempered clear glass on
aluminum powder coated frames. Provide all
necessary accessories. (1.80 x 1.60m)

7.3 Window type W-3, fixed type window with 8mm Ea 5


thick single glazed tempered clear glass on
aluminum powder coated frames. Provide all
necessary accessories. (0.90 x 1.60m)

Page Sub-total

SFDA, Dammam Page 16


FACILITY : MAIN LABORATORY BUILDING

SECTION : ARCHITECTURAL WORK (Contd. . .)

S.No. Description Unit Qty Unit Rate Total Amount

7.4 Window type W-4, fixed type window with Ea 1


6mm thick double glazed tempered reflective
glass on aluminum powder coated frames.
with sliding panels @ lower portion
Provide all necessary accessories.
(1.9 x 1.20m)

7.5 Window type W-5, fixed type window with 6mm Ea 66


thick single glazed tempered clear glass on
aluminum powder coated frames with swing
panels @ upper and lower portions. Provide all
necessary accessories. (3.10 x 1.60m)

7.6 Same as above, but Window type W-6, Ea 6


(3.31 x 1.60m)

7.7 Roll-up blinds in fiberglass coated fabric in


powder coated aluminum alloy rollbox and
thermoplastic accessories. (Manually and
Electrically operated).

7.7.1 Size, 3.10 x 1.60m Ea 66

7.7.2 Size, 3.31 x 1.60m Ea 6

7.8 Clean and Repaint existing Window type EW-6 Ea 4


as shown in the drawing.

8.0 CURTAIN WALL SYSTEM


Supply and install structural curtain wall system
including glazing, sealants, fixing accessories
and all other necessary materials to complete
the installation as per the drawing and
specifications.

8.1 Curtain wall type CW-1, with 6mm thick Ea 17


double glazed reflective tempered glass
(Structural glazing curtain wall system). Provide
all necessary accessories.
(3.10 x 17.330m)

8.2 Curtain wall type CW-2, with 6mm thick Ea 2


double glazed reflective tempered glass
(Structural glazing curtain wall system). Provide
all necessary accessories.
(3.10 x 8.320m)

Page Sub-total

SFDA, Dammam Page 17


FACILITY : MAIN LABORATORY BUILDING

SECTION : ARCHITECTURAL WORK (Contd. . .)

S.No. Description Unit Qty Unit Rate Total Amount

8.3 Curtain wall type CW-2A, with 6mm thick Ea 3


double glazed reflective tempered glass
(Structural glazing curtain wall system). Provide
all necessary accessories.
(3.10 x 7.26m)

8.4 Curtain wall type CW-2B, with 6mm thick Ea 1


double glazed reflective tempered glass
(Structural glazing curtain wall system), with
SFDA LOGO Etched in 12mm thick frameless
glass. Provide all necessary accessories.
(3.10 x 4.010m)

8.5 Curtain wall type CW-3, with 6mm thick Ea 4


double glazed reflective tempered glass
(Structural glazing curtain wall system). Provide
all necessary accessories.
(3.10 x 14.530m)

8.6 Curtain wall type CW-4, with 6mm thick Ea 2


double glazed reflective tempered glass
(Structural glazing curtain wall system). Provide
all necessary accessories.
(3.10 x 4.105m)

8.7 Curtain wall type CW-4A, with 6mm thick Ea 2


double glazed reflective tempered glass
(Structural glazing curtain wall system). Provide
all necessary accessories.
(3.10 x 11.52m)

8.8 Curtain wall type CW-5, with 6mm thick Ea 2


double glazed reflective tempered glass
(Structural glazing curtain wall system). Provide
all necessary accessories.
(3.310 x 17.33m)

8.9 Curtain wall type CW-6, with 6mm thick Ea 2


double glazed reflective tempered glass
(Structural glazing curtain wall system). Provide
all necessary accessories.
(2.90 x 10.220m)

Page Sub-total

SFDA, Dammam Page 18


FACILITY : MAIN LABORATORY BUILDING

SECTION : ARCHITECTURAL WORK (Contd. . .)

S.No. Description Unit Qty Unit Rate Total Amount

9.0 PLASTERING

9.1 WALL PLASTERING : Including expanded


metal lath and plastering accessories.

9.1.1 Cement Plaster for internal walls including M2 7,163


columns and parapet inner face.

9.1.2 Cement Plaster for external walls with grooves M2 1,389


as per drawing.

9.2 CEILING_PLASTERING : Including expanded


metal lath if required and plastering
accessories.

9.2.1 Cement plaster on internal slab soffit ceiling. M2 596

10.0 FINISHES :

10.1 FLOOR FINISHES : Including mortar, grout,


sand bed and finishing treatment.

10.1.1 500 x 500 x 8mm thick Porcelain tiles M2 1,473

10.1.2 600 x 300 x 20mm thick Marble tiles for Stair M2 110
and Entrances landing.

10.1.3 Vinyl sheet flooring (3mm thick min.), anti static, M2 2,032
chemical resistant.

10.1.4 200 x 200 x 8mm thick Unglazed ceramic floor 2 319


M
tiles.

10.1.5 Concrete screed with floor hardener and epoxy M2 1,338


coating.

10.1.6 Concrete screed with floor hardener and epoxy M2 92


coating with high chemical resistant.

10.1.7 30mm thick Marble treads with 2nos non-slip Lm 83


carborandum strips for Entrances steps as
shown on the drawing.

10.1.8 20mm thick Marble risers for Entrances steps. Lm 83

Page Sub-total

SFDA, Dammam Page 19


FACILITY : MAIN LABORATORY BUILDING

SECTION : ARCHITECTURAL WORK (Contd. . .)

S.No. Description Unit Qty Unit Rate Total Amount

10.1.9 30mm thick Marble treads with 2nos. non-slip Lm 321


carborandum strips for Staircase steps as
shown on the drawing.

10.1.10 20mm thick Marble riser for Staircase steps. Lm 321

10.1.11 30mm thick bush hammered finish Marble tiles M2 34


for Ramp.

10.2 BASE :

10.2.1 100mm high Porcelain skirting. Lm 1,152

10.2.2 100mm high Marble tile skirting. Lm 68

10.2.3 150mm high Vinyl skirting Lm 1,107

10.2.4 100mm high Cove ceramic tiles skirting Lm 349

10.2.5 12mm thick Marble tiles baseboard along Lm 101


staircase.

10.3 FLOORING ACCESSORIES :

10.3.1 Stainless Steel Threshold Lm 15

10.3.2 Stainless Steel Strip Separator Lm 106

10.3.3 50mm thick Marble threshold. Lm 13

10.4 WALL FINISHES : Including Mortar, water


proofing, grouting Compound, finishing
treatment, and fixing accessories.

10.4.1 200 x 200 x 6mm thk. Glazed ceramic wall tiles. M2 1,272

10.4.2 300 x 300 x 8mm thk. Porcelain tiles. M2 1,344

10.4.3 500 x 500 x 8mm thick Porcelain tiles with M2 914


DADO on top as per drawing.

10.4.4 200 x 200 x 6mm thk. Glazed ceramic accent Lm 292


strips tiles

Page Sub-total

SFDA, Dammam Page 20


FACILITY : MAIN LABORATORY BUILDING

SECTION : ARCHITECTURAL WORK (Contd. . .)

S.No. Description Unit Qty Unit Rate Total Amount

11.0 SUSPENDED CEILING :


Including Heavy Duty Suspension System,
fixing materials, painting and accessories
complete as per drawing and specifications

11.1 600 x 600 x 15mm thick Acoustical ceiling tiles M2 2,165


with mylar facing or approved equivalent.

11.2 600 x 600 x 10mm thick Gypsum perforated M2 170


ceiling tiles (pre-painted) including 15mm
thick plain gypsum board edging with paint
finish.

11.3 600 x2200 mm Aluminum tiles , at zero point M2 584


anti bacteria with 20 mm thick. pre-painted
plain gypsum board edging with paint finish.

11.4 100 x 0.7mm thick Pre-painted Aluminum M2 245


ceiling liner strips

11.5 15mm thick Decorative Gypsum board ceiling M2 785


with paint finish on heavy duty metal furing
support including cove light and Gypsum
moulding

12.0 PAINTING :

12.1 WALL_PAINTING :

12.1.1 Epoxy paint coats finish, washable type for M2 1,529


internal cement plastered walls.

12.1.2 Paint finish, washable type semi-gloss for M2 581


internal plastered walls at Corridors and
Lobbies.

12.1.3 Paint finish, washable type , with anti-bacteria M2 1,914


for internal cement plastered walls

12.1.4 Stoneshield coating finish for external plastered M2 1,389


walls with grooves as shown in drawing.

12.1.5 Stoneshield coating finish with grooves on 2 2,344


M
existing precast panel as shown in drawing.

Page Sub-total

SFDA, Dammam Page 21


FACILITY : MAIN LABORATORY BUILDING

SECTION : ARCHITECTURAL WORK (Contd. . .)

S.No. Description Unit Qty Unit Rate Total Amount

12.1.6 Paint finish on internal cement plastered walls M2 2,680


and parapet inner face.

12.1.7 Repaint existing parapet inner face. M2 244

12.1.8 Repaint existing internal plaster walls with M2 153


washable type semi-gloss paint.

12.1.9 Repaint existing internal and external walls at M2 1,780


existing Electrical room , Machine room and
Staircase 1, 2 and 3 area.

12.2 CEILING PAINTING

12.2.1 Repaint textured paint finish on slab soffit M2 998


complete with surface preparation (Fair-faced)
at existing Electrical and Machine room area.

12.2.2 Textured paint finish on internal plaster ceiling M2 596


slab soffit.

13.0 TOILET ACCESSORIES :

13.1 6mm thick Facial mirror (frosted float glass) Lm 24


with 6mm thick plywood backing (900mm high)

13.2 6mm thick Vanity mirror on stainless steel Ea 7


frame with ceramic shelf. (700 x 800mm)

13.3 Toilet Paper Holder Ea 18

13.4 Paper Towel Holder Ea 3

13.5 Stainless Steel Grab Bar, L type Ea 4

13.6 Soap Dispenser Ea 34

13.7 Robe Hook Ea 35

13.8 Towel bar Ea 6

13.9 Electric Hand Dryer. Ea 6

13.10 20mm thick plywood cove auto finish with Lm 24


prismatic diffuser as shown in drawing.

Page Sub-total

SFDA, Dammam Page 22


FACILITY : MAIN LABORATORY BUILDING

SECTION : ARCHITECTURAL WORK (Contd. . .)

S.No. Description Unit Qty Unit Rate Total Amount

14.0 Supply material and Consturct dressing room Ea 10


made of formica laminated (veneer) on wooden
framings including doors, hardwares, other
accessories and materials required to complete
the work as per drawing no. A-21 to A-24.

15.0 Supply material and install commercially Lm 26


available metal locker or approved equal as
shown in drawing no. A-21 to A-24.

16.0 Supply materials and install commercially Lm 27


available bench with 25mm x 50mm hardwood
on 25 x 25mm tubular steel framings and
supports as shown in drawing no. A-21 to A-24.

17.0 PLANTER BOX :


Supply and construct planter boxes as indicated
in the drawing, including CMU walls, plastering,
painting, waterproofing, agricultural soil, plants,
shrubs and all necessary civil works as per
drawing to complete the job.

17.1 At Main Entrance Ea 2

17.2 At Main Lobby Ea 1

18.0 COUNTERS:
Supply and install the following Counters as
indicated in the drawings.

18.1 Reception Counter Lm 16

18.2 Receiving Counter Lm 5

18.3 20mm thick , Granite counter top on 19 mm Lm 2


plywood backing for security in ground floor

19.0 Supply and install façade signage (SFDA Ls 1


standard logo) with English/Arabic text including
Electrical conduit, wiring,junction box and fixing
accessories,etc. to complete the work.

Page Sub-total

SFDA, Dammam Page 23


FACILITY : MAIN LABORATORY BUILDING

SECTION : ARCHITECTURAL WORK (Contd. . .)

S.No. Description Unit Qty Unit Rate Total Amount

20.0 FREEZER & COLD STORAGE :

20.1 Supply & install Freezers & Cold storage wall Job 1 By Others
covering, floor covering and ceiling covering
insulated panels with doors as shown in the
drawing and as per manufacturer's standard
and approved by the client's representatives
including all other necessary materials and
accessories to complete the job.

21.0 LABORATORY CASE WORK :


Supply and install the following Laboratory
caseworks including fixing and other necessary
accessories required to complete the
installation as per the drawings.

21.1 Typical Island Bench - Plan A, refer to drawing Lm 19


ML-A-35 ( misc.Det.5 )

21.2 Same as the above but with no Over Bench Lm 61


Shelvings

21.3 Perimeter Sink Unit, refer to drawing Lm 109


ML-A-33 ( misc.Det.3 )

21.4 Island Split Service Bench, refer to drawing Lm 188


ML-A-35 ( misc.Det.5 )

21.5 Perimeter Bench with Workstations, refer to Lm 246


drawing ML-A-33 & 34 ( misc.Det.3 &4 )

21.6 Perimeter Bench with no Wall Units, refer to Lm 36


drawing ML-A-33 & 34 ( misc.Det.3 &4 )

21.7 Free Zone for Under Bench Mobile Storage Lm 227


Units or Loose Equipment.

21.8 Fume Cupboard, refer to drawing Lm 118


ML-A-32 ( misc.Det.2 ) for types and sizes.

21.9 Bench with Shelvings refer to drawing Lm 19


ML-A-35 ( misc.Det.5 )

21.10 Safety Station - Type 2, refer to drawing Set 34


ML-A-31 ( misc.Det.1 )

Page Sub-total

SFDA, Dammam Page 24


FACILITY : MAIN LABORATORY BUILDING

SECTION : ARCHITECTURAL WORK (Contd. . .)

S.No. Description Unit Qty Unit Rate Total Amount

22.0 Supply material and install commercially Lm 171


available metal shelvings or approved equal as
shown in drawing for all Stores.

23.0 CONVEYING SYSTEM :


Supply & install elevators including elevator
car, all electro-mechanical parts, equipments,
controls and all other necessary accessories
required to complete the system.

23.1 Passenger Elevator from Ground floor to Ea 2


Second floor, capacity 1000 Kgs. (13 persons)
with speed of 1.0m / sec, Machine room type.

24.0 PRECAST WORK :


Supply and installation of precast elements,
including fixing, finishing, joints and all materials
and accessories, needs to complete the system
as per drawing.

24.1 Supply and install 120mm thick U shape precast M2 467


concrete wall panel with stoneshield coating
finish and grooves wherever necessary as
shown in the drawing including fixing
accessories and other necessary materials to
complete the work.

24.2 Supply and install Glass Reinforced Concrete


(GRC) wall panel with stoneshields coating
finish with grooves as shown in the drawing
including fixing accessories and other
necessary materials to complete the work.

24.2.1 200mm thick x 1.10 x 18.40m GRC panel Ea 2

24.2.2 100mm thick x 1.10 x 18.40m GRC panel Ea 56

25.0 Preventive maintenance to all existing Passeger Job 1


and Freight Elevator units. The Contractor shall
replace all defective parts if any during testing
and commissioning.

Page Sub-total

SFDA, Dammam Page 25


FACILITY : MAIN LABORATORY BUILDING

SECTION : ARCHITECTURAL WORK (Contd. . .)

S.No. Description Unit Qty Unit Rate Total Amount

26.0 Removed and replaced all damaged existing Job 1


450 x 450 x 50mm thick precast concrete
pavers at lower roof and provide loose gravel
all around perimeter of parapet and chiller pads
as shown in the drawing.

27.0 Supply and install 50 x 6mm thick steel grating Optional


with wider spacings (to avoid bird from nesting)
with epoxy coatings suitable for galvanized
steel with 4mm thick composite aluminum
header ( to serve as Catwalk ).

27.1 Size, 3.10 x 2.20m Ea 43 Optional

27.2 Size, 3.31 x 2.20m Ea 4 Optional

27.3 Size, 3.10 x 2.80m Ea 23 Optional

27.4 Size, 3.31 x 2.80m Ea 2 Optional

27.5 Size, 2.20 x 0.90m Ea 90 Optional

27.6 Size, 3.80 x 0.90m Ea 3 Optional

Page Sub-total

TOTAL ARCHITECTURAL WORK - Main Laboratory Building

SFDA, Dammam Page 26


PROJECT : SAUDI FOOD AND DRUGS AUTHORITY, DAMMAM

FACILITY : MAIN LABORATORY BUILDING

SECTION : PLUMBING WORK

S.No. Description Unit Qty Unit Rate Total Amount

1.0 DEMOLITION WORKS:

1.1 Demolishing and Dismantling of the existing Job 1


Plumbing equipments, Laboratory equipments,
plumbing fixtures and related works, Fire hose
cabinets, fire extinguishers, Gas cylinder tanks
and related works, all exposed pipings for
water, drainage, gas, fire fighting, chemical
waste, sanitary, vent, rain water, compressed
air and vacuum air, all floor drains, clean-outs,
etc., and all related works to give way to the
proposed new design and construction. The
valuable and re-usable materials shall be
handed over to the Supervising Engineer. The
demolished debris shall be removed and
disposed to a location approved by the
Supervising Engineer.

2.0 FIRE FIGHTING SYSTEM :

2.1 WATER SUPPLY PIPING : Complete with


jointings, supports, fittings, and other
specials needed for a complete installation
including testing, commissioning, sterilizing,
civil works and other related works.

2.1.1 100mm dia., Black steel pipe, Schedule-40. Lm 30

2.1.2 50mm dia., Black steel pipe, Schedule-40. Lm 154

2.2 Fire hose cabinet including 50mm dia. Ea 9


collapsible hose 30m long, landing valve,
nozzle and one portable fire extinguisher.

2.3 Portable CO2, fire extinguisher, 6kg capacity Ea 51


complete with steel wall bracket.

2.4 FM-200 SYSTEM :

2.4.1 PIPES AND FITTINGS : Supply, install,


testing and commissioning of black steel pipe
Schedule 40 including fittings, valves and other
accessories required to complete the system
ready for operation.

Page Sub-total

SFDA, Dammam Page 27


FACILITY : MAIN LABORATORY BUILDING

SECTION : PLUMBING WORK (Contd. . .)

S.No. Description Unit Qty Unit Rate Total Amount

2.4.1.1 38mm dia., Black steel pipe, Schedule-40. Lm 474

2.4.1.2 25mm dia., Black steel pipe, Schedule-40. Lm 175

2.4.2 Spray nozzles Ea 48

2.4.3 Manual Pull Station Ea 11

2.4.4 Solenoid Valve Station, 25mm dia. Ea 48

2.4.5 Supply, installation, testing and commissioning Ea 2


of FM-200 cylinders, 235 lbs capacity with
control panel and all other accessories, ready
for operation.

2.4.6 Same as above, but 210 lbs capacity Ea 4

2.4.7 Same as above, but 200 lbs capacity Ea 4

2.4.8 Same as above, but 190 lbs capacity Ea 4

2.4.9 Same as above, but 180 lbs capacity Ea 2

2.4.10 Same as above, but 160 lbs capacity Ea 2

2.4.11 Same as above, but 145 lbs capacity Ea 2

2.4.12 Same as above, but 135 lbs capacity Ea 2

3.0 DOMESTIC WATER SUPPLY AND


DRAINAGE SYSTEM :

3.1 POTABLE WATER SUPPLY : Complete


with jointings, fittings, supports, hangers, other
specials required for a complete installation
including testing, commissioning, sterilizing
and all civil works related thereto.

3.1.1 75mm dia. CPVC pipe, Schedule - 80. Lm 8

3.1.2 50mm dia. CPVC pipe, Schedule - 80. Lm 51

3.1.3 38mm dia. CPVC pipe, Schedule - 80. Lm 92

3.1.4 32mm dia. CPVC pipe, Schedule - 80. Lm 60

Page Sub-total

SFDA, Dammam Page 28


FACILITY : MAIN LABORATORY BUILDING

SECTION : PLUMBING WORK (Contd. . .)

S.No. Description Unit Qty Unit Rate Total Amount

3.1.5 25mm dia. CPVC pipe, Schedule - 80. Lm 18

3.1.6 20mm dia. CPVC pipe, Schedule - 80. Lm 100

3.1.7 15mm dia. CPVC pipe, Schedule - 80. Lm 81

3.2 HOT WATER LINE : Complete with


rubber insulation, jointings, fittings, supports and
hangers, other special required for a complete
installation including testing, sterilizing and civil
works related thereto.

3.2.1 32mm dia. CPVC pipe, Schedule - 80. Lm 4

3.2.2 25mm dia. CPVC pipe, Schedule - 80. Lm 15

3.2.3 20mm dia. CPVC pipe, Schedule - 80. Lm 13

3.2.4 15mm dia. CPVC pipe, Schedule - 80. Lm 55

3.3 TREATED COLD WATER SUPPLY :


Complete with installation, jointings, supports
and hangers, hose bibs, other specials required
for a complete installation including testing,
sterilizing and other related civil works.

3.3.1 63mm dia. CPVC pipe, Schedule - 80. Lm 20

3.3.2 50mm dia. CPVC pipe, Schedule - 80. Lm 170

3.3.3 38mm dia. CPVC pipe, Schedule - 80. Lm 155

3.3.4 32mm dia. CPVC pipe, Schedule - 80. Lm 105

3.3.5 25mm dia. CPVC pipe, Schedule - 80. Lm 178

3.3.6 20mm dia. CPVC pipe, Schedule - 80. Lm 15

3.3.7 15mm dia. CPVC pipe, Schedule - 80. Lm 311

3.4 TREATED HOT WATER SUPPLY :


Complete with installation, jointings, supports
and hangers, hose bibs, other specials required
for a complete installation including testing,
sterilizing and other related civil works

Page Sub-total

SFDA, Dammam Page 29


FACILITY : MAIN LABORATORY BUILDING

SECTION : PLUMBING WORK (Contd. . .)

S.No. Description Unit Qty Unit Rate Total Amount

3.4.1 25mm dia. CPVC pipe, Schedule - 80. Lm 266

3.4.2 20mm dia. CPVC pipe, Schedule - 80. Lm 289

3.4.3 15mm dia. CPVC pipe, Schedule - 80. Lm 130

3.5 VALVES :

3.5.1 Gate valve, 63mm dia. Ea 2

3.5.2 Gate valve, 50mm dia. Ea 12

3.5.3 Gate valve, 25mm dia. Ea 11

3.5.4 Gate valve, 20mm dia. Ea 35

3.5.5 Gate valve, 15mm dia. Ea 33

3.5.6 Drain valve, 32mm dia with end cap Ea 3

3.5.7 Check valve, 50mm dia. Ea 4

3.5.8 Check valve, 25mm dia. Ea 2

3.5.9 Pressure Regulating valve, 38mm dia. Ea 6

3.5.10 Control valve, 20mm dia. Ea 2

3.5.11 Regulating valve, 38mm dia. Ea 8

3.5.12 Float valve assembly, 50mm dia. Ea 3

3.5.13 Automatic Air Vent Ea 2

3.6 WATER HAMMER ARRESTOR :

3.6.1 20mm dia. Ea 7

3.6.2 15mm dia. Ea 1

3.7 SANITARY DRAINAGE PIPING :


Including jointings, trenching, fittings and all civil
works related thereto.

3.7.1 110mm dia. UPVC pipe, Class-4. Lm 162

Page Sub-total

SFDA, Dammam Page 30


FACILITY : MAIN LABORATORY BUILDING

SECTION : PLUMBING WORK (Contd. . .)

S.No. Description Unit Qty Unit Rate Total Amount

3.7.2 75mm dia. UPVC pipe, Class-4. Lm 30

3.7.3 50mm dia. UPVC pipe, Class-4. Lm 35

3.8 DRAINS AND CLEANOUTS :

3.8.1 Floor drain, 50mm dia. connection with PVC Ea 10


body and cover.

3.8.2 Floor cleanout 110mm dia, PVC body and Ea 5


cover.

3.8.3 Cleanout 110mm dia, PVC body and cover. Ea 7

3.8.4 Cleanout 75mm dia, PVC body and cover. Ea 1

3.8.5 Floor Gulley ,75 mm dia, Ea 5

3.8.6 Floor Gulley ,50 mm dia, Ea 2

3.9 CHEMICAL WASTE PIPING:

3.9.1 110mm diameter polyolefin pipe Lm 765

3.9.2 50mm diameter polyolefin pipe Lm 130

3.10 CHEMICAL WASTE DRAINS & CLEANOUT :

3.10.1 Floor Gully, 50mm dia. PVC body and cover. Ea 24

3.10.2 Floor Gully, 100mm dia. PVC body and cover. Ea 6

3.10.3 Floor drain 110mm dia connection with PVC Ea 111


body and cover.

3.10.4 Floor cleanout 110mm dia connection with PVC Ea 8


body and cover.

3.10.5 Cleanout 110mm dia connection with PVC Ea 26


body and cover.

3.11 SANITARY VENT SYSTEM :

3.11.1 PIPES AND FITTINGS : Including joints,


fittings, supports, and all accessories.

3.11.1.1 75mm dia. UPVC pipe, Class-4. Lm 170

Page Sub-total

SFDA, Dammam Page 31


FACILITY : MAIN LABORATORY BUILDING

SECTION : PLUMBING WORK (Contd. . .)

S.No. Description Unit Qty Unit Rate Total Amount

3.11.1.2 50mm dia. UPVC pipe, Class-4. Lm 724

3.11.2 Roof vent cowl, 75mm dia. Ea 5

3.11.3 Roof vent cowl, 50mm dia. Ea 1

3.12 RAIN WATER SYSTEM :

3.12.1 PIPES AND FITTINGS : Including


jointings, fittings, supports, materials and all
accessories complete in all aspects.

3.12.1.1 110mm dia. UPVC pipe, Class-4. Lm 271

3.13 ROOF DRAINS :

3.13.1 Roof drains, 110mm dia connection with Ea 15


cast iron body and strainer.

4.0 PLUMBING FIXTURES:


Including fittings, trims, mounting
accessories and materials complete
in all aspects.

4.1 Lavatory, vitreous china, counter type including Ea 15


counters as per drawing.

4.2 Lavatory vitreous china, wall mounted type. Ea 1

4.3 Handspray, reinforced plastic body, flexible Ea 16


metal hose with aerator, mounting bracket,
vacuum breaker and self-closing push button
valve.

4.4 Electric water heater EWH, 50 liters capacity Ea 2


with pressure relief valve, check valve, isolation
valve and heating element 1.2 kW.

4.5 Electric water heater EWH, 80 liters capacity Ea 7


with pressure relief valve, check valve, isolation
valve and heating element 1.5 kW.

4.6 Water closet, Western wall mounted type, Ea 8


vitreous china with flush tank complete.

Page Sub-total

SFDA, Dammam Page 32


FACILITY : MAIN LABORATORY BUILDING

SECTION : PLUMBING WORK (Contd. . .)

S.No. Description Unit Qty Unit Rate Total Amount

4.7 Water closet, Eastern type, vitreous china Ea 8


with flush tank complete.

5.0 PUMPS AND EQUIPMENTS

5.1 Treated water booster pump (TWBP1 & 2), Ea 2


45GPM capacity @ 90ft Head, Centrifugal type
with 2 HP motor 220 volts complete with control
panel and accessories.
(1-duty and 1-standby)

5.2 Domestic water booster pump (DWBP1 & 2), Ea 2


45GPM capacity @ 75ft Head, Centrifugal type
with 1.5 HP motor 220 volts complete with
control panel and accessories.
(1-duty and 1-standby)

5.3 100 liters pressure tank diaphragm type Ea 2


stainless steel type.

5.4 Circulating Hot Water Pump (CWP1 & 2 ) Ea 2


3 GPM capacity @ 17 ft Head, Centrifugal type
120 watts , 220 volts complete with
control panel and accessories.
(1-duty and 1-standby)

5.5 Vertical electric water heater ( EWH-1 , EWH2 ) Ea 2


500 Capacity , with complete controls and
accessories with heating element 30 kW
(1-duty and 1-standby)

5.6 Supply and installation of pre-fabricated fiber Ea 3


glass Overhead Water tank with insulation
including service manhole, vent pipe with insect
screen and all necessary fixing accessories to
complete the job. Capacity 5,000 liters.

6.0 INDUSTRIAL PLUMBING :

6.1 COMPRESSED / VACUUM AIR PIPINGS:


Complete with jointings, fittings, supports,
hangers, other specials required for a complete
installation including testing, commissioning
and all civil works related thereto.

6.1.1 20mm dia copper pipe type-L. Lm 74

Page Sub-total

SFDA, Dammam Page 33


FACILITY : MAIN LABORATORY BUILDING

SECTION : PLUMBING WORK (Contd. . .)

S.No. Description Unit Qty Unit Rate Total Amount

6.1.2 12mm dia Copper pipe type-L. Lm 520

6.2 VALVES:

6.2.1 Isolation Valves, 20mm dia. Ea 8

6.2.2 Isolation Valves, 12mm dia. Ea 34

6.3 Connection pipes with cap for future used, Ea 12


including necessary pipes and valves as per
drawings.

6.4 GAS PIPINGS:


Complete with jointings, fittings, supports,
hangers, other specials required for a complete
installation including, testing, commissioning
and all civil works related thereto.

6.4.1 50mm dia Hot Dip Galvanized Iron Pipe. Lm 45

6.4.2 38mm dia Hot Dip Galvanized Iron Pipe. Lm 90

6.4.3 32mm dia Hot Dip Galvanized Iron Pipe. Lm 188

6.4.4 25mm dia Hot Dip Galvanized Iron Pipe. Lm 292

6.4.5 20mm dia Hot Dip Galvanized Iron Pipe. Lm 6

6.4.6 12mm dia Hot Dip Galvanized Iron Pipe. Lm 1570

6.5 VALVES:

6.5.1 Isolation Valve, 12mm dia. Ea 64

6.5.2 Isolation Valve, 25 dia. Ea 6

6.5.3 Isolation Valve, 32 dia. Ea 2

6.5.4 Isolation Valve, 38 dia. Ea 2

6.6 Connection pipes with cap for future used, Ea 36


including necessary pipes and valves as per
drawings.

Page Sub-total

SFDA, Dammam Page 34


FACILITY : MAIN LABORATORY BUILDING

SECTION : PLUMBING WORK (Contd. . .)

S.No. Description Unit Qty Unit Rate Total Amount

7.0 Nitrogen Generator including accessories, Ea 2


complete.

8.0 GAS LEAK DETECTORS


Complete with jointings, fittings, supports,
hangers, other specials required for a complete
installation including, testing, commissioning

8.1 Nitrogen leak detectors Ea 25

8.2 Helium leak detectors Ea 13

8.3 Butane leak detectors Ea 11

8.4 Hydrogen leak detectors Ea 3

8.5 Argon leak detectors Ea 1

8.6 Acetylene leak detectors Ea 1

8.7 Combination leak detectors Ea 24

9.0 Combined oxygen depletion and carbon Job 1


Enrichment monitor in a laboratory

Page Sub-total

TOTAL PLUMBING WORK - Main Laboratory Building

SFDA, Dammam Page 35


PROJECT : SAUDI FOOD AND DRUGS AUTHORITY, DAMMAM

FACILITY : MAIN LABORATORY BUILDING

SECTION : HVAC WORK

S.No. Description Unit Qty Unit Rate Total Amount

1.0 DEMOLITION WORKS:

1.1 Demolishing and Dismantling of the existing Job 1


all HVAC equipments including concrete pads
likes Chillers, Air Handling Units (AHU's), Fan
Coil Units (FCU's), ACCU's, Window type A/C's,
all types of Pumps, all HVAC duct works and
related works, all Air distribution devices, all
exposed chilled water pipings and supports, all
condensate drain pipes, all exhaust fans and
related works, etc., and all related HVAC works
to give way for the proposed new design and
construction. The valuable and re-usable
materials shall be handed over to the
Supervising Engineer. The demolished debris
shall be removed and disposed to a location
approved by the Supervising Engineer.

(Note : All equipments shall be linked with


Building Management System)

2.0 HEATING AND COOLING SYSTEM:


Supply and installation of chiller units, air
handling unit (AHU) and fan coil units (FCU)
including control package, adoptable for BMS
connections, instrumentation and testing,
commissioning and balancing of each system.

2.1 AIR HANDLING UNITS: (HRU)


Chilled water air handling unit (AHU), single
skin, cold cooling coil with variable frequency
inverter, static pressure controller/sensor, 3-way
modulating motorized valve, gauges, flexible
connectors, strainers, control package and all
related valves, instrumentations and fitting
connections required as per drawing no. M-14
and other data as per HRU/AHU schedule:

2.1.1 Type HRU - GF1, actual cooling load, 183.6kW, Ea 1


supply air - 1667 L/S, E.S.P. @ 510 pascal,
Electric heater - 24kW (2 stage), Humidifier -
23kg/hr, Power supply - 380 / 3 / 60.

Page Sub-total

SFDA, Dammam Page 36


FACILITY : MAIN LABORATORY BUILDING

SECTION : HVAC WORK (Contd. . .)

S.No. Description Unit Qty Unit Rate Total Amount

2.1.2 Type HRU - GF2, actual cooling load, 195.8kW, Ea 1


supply air - 1784 L/S, E.S.P. @ 534 pascal,
Electric heater - 24kW (2 stage), Humidifier -
23kg/hr, Power supply - 380 / 3 / 60.

2.1.3 Type AHU - GF3, actual cooling load, 57.14kW, Ea 1


supply air - 2475 L/S, E.S.P. @ 536 pascal,
Electric heater - 6kW, Humidifier - 12kg/hr,
Power supply - 380 / 3 / 60.
(Standard Airhandling unit, non heat
recovery with constant speed motor).

2.1.4 Type HRU - GF4, actual cooling load, 195.8kW, Ea 1


supply air - 1797 L/S, E.S.P. @ 512 pascal,
Electric heater - 24kW (2 stage), Humidifier -
23kg/hr, Power supply - 380 / 3 / 60.

2.1.5 Type HRU - F1, actual cooling load, 262kW, Ea 1


supply air - 2749 L/S, E.S.P. @ 365 pascal,
Electric heater - 30kW (3 stage), Humidifier -
28kg/hr, Power supply - 380 / 3 / 60.

2.1.6 Type HRU - F2, actual cooling load, 263.9kW, Ea 1


supply air - 2860 L/S, E.S.P. @ 386 pascal,
Electric heater - 30kW (3 stage), Humidifier -
30kg/hr, Power supply - 380 / 3 / 60.

2.1.7 Type HRU - F3, actual cooling load, 240.8kW, Ea 1


supply air - 2486 L/S, E.S.P. @ 380 pascal,
Electric heater - 30kW (3 stage), Humidifier -
28kg/hr, Power supply - 380 / 3 / 60.

2.1.8 Type HRU - F4, actual cooling load, 293kW, Ea 1


supply air - 3643 L/S, E.S.P. @ 340 pascal,
Electric heater - 42kW (3 stage), Humidifier -
48kg/hr, Power supply - 380 / 3 / 60.

2.1.9 Type HRU - SF1, actual cooling load, 263.9kW, Ea 1


supply air - 2836 L/S, E.S.P. @ 276 pascal,
Electric heater - 33kW (3 stage), Humidifier -
30kg/hr, Power supply - 380 / 3 / 60.

2.1.10 Type HRU - SF2, actual cooling load, 263.9kW, Ea 1


supply air - 2846 L/S, E.S.P. @ 280 pascal,
Electric heater - 33kW (3 stage), Humidifier -
30kg/hr, Power supply - 380 / 3 / 60.

Page Sub-total

SFDA, Dammam Page 37


FACILITY : MAIN LABORATORY BUILDING

SECTION : HVAC WORK (Contd. . .)

S.No. Description Unit Qty Unit Rate Total Amount

2.1.11 Type HRU - SF3, actual cooling load, 240.8kW, Ea 1


supply air - 2349 L/S, E.S.P. @ 278 pascal,
Electric heater - 30kW (3 stage), Humidifier -
36kg/hr, Power supply - 380 / 3 / 60.

2.1.12 Type HRU - SF4, actual cooling load, 263.9kW, Ea 1


supply air - 2842 L/S, E.S.P. @ 268 pascal,
Electric heater - 33kW (3 stage), Humidifier -
30kg/hr, Power supply - 380 / 3 / 60.

2.1.13 Type AHU - SF5, actual cooling load, 77kW, Ea 1


supply air - 680 L/S, E.S.P. @ 210 pascal,
Electric heater - 8kW ( 2 stage ) , Humidifier
8kg/hr,Power supply - 380 / 3 / 60.
(Standard Airhandling unit, non heat
recovery with constant speed motor).

2.2 CHILLED WATER FAN COIL UNIT (FCU)


Concealed ducted with 3-way modulating
motorized valve, electric heater, control
package and all related valves, gauges, flexible
connectors, strainers, instrumentations and
fitting connections as per drawing no. M-14 and
other datas as per FCU schedule, unit shall be
3-speed.

2.2.1 Type FCU - GF1, actual cooling load - 12 kW, Ea 1


supply air - 614 L/S, ESP @ 150 Pascal,
Electric heater - 0.80 kW, 220-1-60

2.2.2 Type FCU - GF2, actual cooling load - 5.5 kW, Ea 1


supply air - 285 L/S, ESP @ 125 Pascal,
Electric heater - 0.50 kW, 220-1-60

2.2.3 Type FCU - GF3, actual cooling load - 8.5 kW, Ea 1


supply air - 460 L/S, ESP @ 125 Pascal,
No heater, 220-1-60

2.2.4 Type FCU - F1, actual cooling load - 8 kW, Ea 1


supply air - 420 L/S, ESP @ 150 Pascal,
Electric heater - 0.50 kW, 220-1-60

2.2.5 Type FCU - F2, actual cooling load - 8.5 kW, Ea 2


supply air - 460 L/S, ESP @ 165 Pascal,
Electric heater - 0.50 kW, 220-1-60

Page Sub-total

SFDA, Dammam Page 38


FACILITY : MAIN LABORATORY BUILDING

SECTION : HVAC WORK (Contd. . .)

S.No. Description Unit Qty Unit Rate Total Amount

2.2.6 Type FCU - F3, actual cooling load - 5.5 kW, Ea 1


supply air - 285 L/S, ESP @ 125 Pascal,
Electric heater - 0.50 kW, 220-1-60

2.2.7 Type FCU - SF1, actual cooling load - 8.5 kW, Ea 2


supply air - 460 L/S, ESP @ 165 Pascal,
Electric heater - 0.50 kW, 220-1-60

2.2.8 Type FCU - SF2, actual cooling load - 5.5 kW, Ea 1


supply air - 285 L/S, ESP @ 125 Pascal,
Electric heater - 0.50 kW, 220-1-60

2.2.9 Type FCU - SF3, actual cooling load - 8 kW, Ea 1


supply air - 420 L/S, ESP @ 150 Pascal,
Electric heater - 0.50 kW, 220-1-60

2.2.10 Type FCU - R1, actual cooling load - 15.2 kW, Ea 1


supply air - 1108 L/S, ESP @ 75 Pascal,
No heater, 220-1-60

2.2.11 Type FCU - R2, actual cooling load - 13.7 kW, Ea 1


supply air - 830 L/S, ESP @ 75 Pascal,
No heater, 220-1-60

2.3 DX-Split type A/C Units, with fan coil unit


matched with air-cooled condensing unit,
including insulated refrigerant pipings, with
pipe supports, concrete pads, controls
cables (ACCU's to FCU's) and all other
appurtenances, testing and commissioning
for a complete installation as per drawing
and specifications.

2.3.1 FCU - 1 / ACCU - 1, cooling load - 10.5 kW @ Set 2


75 Pa, Cooling only, Power input - 4.5 kW and
Ducted type.

2.3.2 FCU - R3 / ACCU - R3, cooling load - 7 kW @ Set 1


75 Pa, with heat pump, Power input 2.6 kW and
power supply 220/1/60 .

Page Sub-total

SFDA, Dammam Page 39


FACILITY : MAIN LABORATORY BUILDING

SECTION : HVAC WORK (Contd. . .)

S.No. Description Unit Qty Unit Rate Total Amount

3.0 VARIABLE AIR VOLUME (VAV) UNIT:


Modulating motorized damper, Modulating
shut-off type complete control package with
space thermostat and accessories, including
testing and commissioning.

3.1 VAV Units, duct mounted

GROUND FLOOR LEVEL :

3.1.1 VAV - GF1, 412 L/S Ea 1

3.1.2 VAV - GF2, 246 L/S Ea 1

3.1.3 VAV - GF3, 200 L/S Ea 2

3.1.4 VAV - GF4, 620 L/S Ea 2

FIRST FLOOR LEVEL :

3.1.5 VAV - F1, 1200 L/S Ea 2

3.1.6 VAV - F2, 430 L/S Ea 1

3.1.7 VAV - F3, 750 L/S Ea 2

3.1.8 VAV - F4, 440 L/S Ea 1

3.1.9 VAV - F5, 770 L/S Ea 1

3.1.10 VAV - F6, 1200 L/S Ea 1

3.1.11 VAV - F7, 880 L/S Ea 1

3.1.12 VAV - F8, 1400 L/S Ea 1

3.1.13 VAV - F9, 300 L/S Ea 1

3.1.14 VAV - F10, 500 L/S Ea 1

SECOND FLOOR LEVEL :

3.1.15 VAV - SF1, 340 L/S Ea 2

3.1.16 VAV - SF2, 1600 L/S Ea 1

Page Sub-total

SFDA, Dammam Page 40


FACILITY : MAIN LABORATORY BUILDING

SECTION : HVAC WORK (Contd. . .)

S.No. Description Unit Qty Unit Rate Total Amount

3.1.17 VAV - SF3, 800 L/S Ea 1

3.1.18 VAV - SF4, 1060 L/S Ea 1

3.1.19 VAV - SF5, 512 L/S Ea 1

3.1.20 VAV - SF6, 700 L/S Ea 1

3.1.21 VAV - SF7, 700 L/S Ea 1

3.1.22 VAV - SF8, 700 L/S Ea 1

4.0 VENTILATION AND EXHAUST SYSTEM:


Unit mounting with complete controls, related
accessories including testing and
commissioning.

4.1 Exhaust Fan Unit with spun aluminum


construction with accessories, complete in
all aspects.

Ground Floor Level :

4.1.1 Type, EF-GF1, air flow - 300 L/S @ 75 Pa, Ea 1


Wall mounted with shutter, Power Supply -
220-1-60

4.1.2 Type, EF-GF2, air flow - 350 L/S @ 75 Pa, Ea 1


Wall mounted with shutter, Power Supply -
220-1-60

4.1.3 Type, EF-GF3, air flow - 600 L/S @ 450 Pa, Ea 1


Upblast centrifugal with backdraft damper,
Power Supply - 220-1-60.

4.1.4 Type, EF-GF4, air flow - 1200 L/S @ 470 Pa, Ea 1


Ducted In-Line, Centrifugal, Power Supply -
220-1-60

4.1.5 Type, EF-GF5, air flow - 400 L/S @ 180 Pa, Ea 1


Ducted In-Line, Centrifugal, Power Supply -
220-1-60

4.1.6 Type, EF-GF6, air flow - 420 L/S @ 220 Pa, Ea 1


Ducted In-Line, Centrifugal, Power Supply -
220-1-60

Page Sub-total

SFDA, Dammam Page 41


FACILITY : MAIN LABORATORY BUILDING

SECTION : HVAC WORK (Contd. . .)

S.No. Description Unit Qty Unit Rate Total Amount

4.1.7 Type, EF-GF7, air flow - 300 L/S @ 75 Pa, Ea 1


Wall mounted with shutter, Power Supply -
220-1-60

4.1.8 Type, EF-GF8, air flow - 120 L/S @ 85 Pa, Ea 1


Ducted In-Line, Centrifugal, Power Supply -
220-1-60

4.1.9 Type, EF-GF9, air flow - 1200 L/S @ 480 Pa, Ea 1


Upblast centrifugal with backdraft damper,
Power Supply - 220-1-60.

4.1.10 Type, EF-GF10, air flow - 120 L/S @ 85 Pa, Ea 1


Ducted In-Line, Centrifugal, Power Supply -
220-1-60

4.1.11 Type, EF-GF11, air flow - 300 L/S @ 75 Pa, Ea 1


Wall mounted with shutter, Power Supply -
220-1-60

4.1.12 Type, TF-GF1, air flow - 350 L/S @ 85 Pa, Ea 1


Wall mounted with shutter, Power Supply -
220-1-60

First Floor Level :

4.1.13 Type, EF-F1, air flow - 80 L/S @ 85 Pa, Ea 1


Wall mounted with shutter, Power Supply -
220-1-60

4.1.14 Type, EF-F2, air flow - 300 L/S @ 85 Pa, Ea 1


Wall mounted with shutter, Power Supply -
220-1-60

4.1.15 Type, EF-F3, air flow - 1300 L/S @ 330 Pa, Ea 1


Upblast centrifugal with backdraft damper,
Power Supply - 220-1-60.

4.1.16 Type, EF-F4, air flow - 1100 L/S @ 380 Pa, Ea 1


Ducted In-Line, Centrifugal, Power Supply -
220-1-60

4.1.17 Type, EF-F5, air flow - 620 L/S @ 175 Pa, Ea 1


Ducted In-Line, Centrifugal, Power Supply -
220-1-60

Page Sub-total

SFDA, Dammam Page 42


FACILITY : MAIN LABORATORY BUILDING

SECTION : HVAC WORK (Contd. . .)

S.No. Description Unit Qty Unit Rate Total Amount

4.1.18 Type, EF-F6, air flow - 1000 L/S @ 386 Pa, Ea 1


Ducted In-Line, Centrifugal, Power Supply -
220-1-60

4.1.19 Type, EF-F7, air flow - 750 L/S @ 350 Pa, Ea 1


Upblast centrifugal with backdraft damper,
Power Supply - 220-1-60.

4.1.20 Type, TF-F1, air flow - 300 L/S @ 85 Pa, Ea 1


Wall mounted with shutter, Power Supply -
220-1-60

Second Floor Level :

4.1.21 Type, EF-SF1, air flow - 1250 L/S @ 343 Pa, Ea 1


Upblast centrifugal with backdraft damper,
Power Supply - 220-1-60.

4.1.22 Type, EF-SF2, air flow - 600 L/S @ 365 Pa, Ea 1


Ducted In-Line, Centrifugal, Power Supply -
220-1-60

4.1.23 Type, EF-SF3, air flow - 100 L/S @ 75 Pa, Ea 1


Wall mounted with shutter, Power Supply -
220-1-60

4.1.24 Type, EF-SF4, air flow - 300 L/S @ 85 Pa, Ea 1


Wall mounted with shutter, Power Supply -
220-1-60

4.1.25 Type, EF-SF5, air flow - 170 L/S @ 125 Pa, Ea 1


Ducted In-Line, Centrifugal, Power Supply -
220-1-60

4.1.26 Type, EF-SF6, air flow - 950 L/S @ 354 Pa, Ea 1


Ducted In-Line, Centrifugal, Power Supply -
220-1-60

4.1.27 Type, EF-SF7, air flow - 600 L/S @ 320 Pa, Ea 1


Upblast centrifugal with backdraft damper,
Power Supply - 220-1-60.

4.1.28 Type, TF-SF1, air flow - 350 L/S @ 85 Pa, Ea 1


Wall mounted with shutter, Power Supply -
220-1-60

Page Sub-total

SFDA, Dammam Page 43


FACILITY : MAIN LABORATORY BUILDING

SECTION : HVAC WORK (Contd. . .)

S.No. Description Unit Qty Unit Rate Total Amount

4.1.29 Type, TF-SF2, air flow - 300 L/S @ 85 Pa, Ea 1


Wall mounted with shutter, Power Supply -
220-1-60

4.1.30 Type, EF-R1, air flow - 130 L/S @ 100 Pa, Ea 1


Roof mounted centrifugal with backdraft
damper,Power Supply -220-1-60

4.1.31 Type, EF-R2, air flow - 140 L/S @ 75 Pa, Ea 1


Wall mounted with shutter, Power Supply -
220-1-60

5.0 PRESSURIZATION FAN SYSTEM :


Unit mounting, with complete controls, and
accessories including testing and
commissioning.

5.1 Pressurization supply fan, aluminum spun


construction with complete aspects.

5.1.1 Type PF, air flow - 1800 L/S @ 375 Pa, Ea 3


Centrifugal - Louvered with aluminum filters
Power Supply - 380 / 3 / 60.

6.0 DUCT WORKS :


Including all fittings, hangers, volume/fire
dampers, other tuming/accessories for
complete installation in all aspects including
liners, insulations as per drawings and
specifications.

2
6.1 Insulated duct. M 2,857

6.2 Uninsulated duct. M2 2,035

6.3 Weatherproof duct. M2 1,490

6.4 Duct Liners with perforated sheet layer as M2 188


per drawing.

6.5 Flexible duct, 150mm dia. Lm 24

6.6 Flexible duct, 200mm dia. Lm 68

6.7 Flexible duct, 250mm dia. Lm 56

Page Sub-total

SFDA, Dammam Page 44


FACILITY : MAIN LABORATORY BUILDING

SECTION : HVAC WORK (Contd. . .)

S.No. Description Unit Qty Unit Rate Total Amount

6.8 Flexible duct, 300mm dia. Lm 60

6.9 Flexible duct, 350mm dia. Lm 62

6.10 Flexible duct, 400mm dia. Lm 10

6.11 Flexible duct, 450mm dia. Lm 3

7.0 AIR DISTRIBUTION DEVICES :


Including all fittings, lintel plenum and
accessories for complete installations

7.1 DIFFUSERS :

7.1.1 Supply ceiling diffusers, 600 x 600mm. Ea 1

7.1.2 Supply ceiling diffusers, 530 x 530mm. Ea 11

7.1.3 Supply ceiling diffusers, 450 x 450mm. Ea 40

7.1.4 Supply ceiling diffusers, 380 x 380mm. Ea 27

7.1.5 Supply ceiling diffusers, 300 x 300mm. Ea 39

7.1.6 Supply ceiling diffusers, 250 x 250mm. Ea 16

7.1.7 Supply ceiling diffusers, 230 x 230mm. Ea 7

7.1.8 Return ceiling diffusers, 600 x 600mm. Ea 1

7.1.9 Return ceiling diffusers, 530 x 530mm. Ea 11

7.1.10 Return ceiling diffusers, 450 x 450mm. Ea 41

7.1.11 Return ceiling diffusers, 380 x 380mm. Ea 29

7.1.12 Return ceiling diffusers, 300 x 300mm. Ea 35

7.1.13 Return ceiling diffusers, 250 x 250mm. Ea 15

7.1.14 Return ceiling diffusers, 230 x 230mm. Ea 2

7.1.15 Supply Liner Diffiser , 2 slot x 3 m Ea 23

7.1.16 Return Liner Diffiser , 2 slot x 3 m Ea 23

Page Sub-total

SFDA, Dammam Page 45


FACILITY : MAIN LABORATORY BUILDING

SECTION : HVAC WORK (Contd. . .)

S.No. Description Unit Qty Unit Rate Total Amount

7.1.17 Supply plenum Box, 6000 x 1500mm Ea 2

7.1.18 Supply plenum Box , 1400 x 850mm Ea 2

7.2 GRILLES :

7.2.1 Exhaust Grille, 200 x 200mm. Ea 3

7.2.2 Exhaust Grille, 230 x 230mm. Ea 7

7.2.3 Exhaust Grille, 250 x 250mm. Ea 4

7.2.4 Exhaust Grille, 300 x 300mm. Ea 5

7.2.5 Exhaust Grille, 400 x 200mm. Ea 1

7.2.6 Exhaust Grille, 400 x 250mm. Ea 1

7.2.7 Exhaust Eggcrate, 600 x 600mm. Ea 9

7.2.8 Exhaust Eggcrate, 530 x 530mm. Ea 2

7.2.9 Exhaust Eggcrate, 450 x 450mm. Ea 12

7.2.10 Exhaust Eggcrate, 380 x 380mm. Ea 14

7.2.11 Exhaust Eggcrate, 300 x 300mm. Ea 14

7.2.12 Exhaust Air Valve, 230mm dia Ea 18

7.2.13 Door Grilles, 250 x 200mm. Ea 1

7.2.14 Door Grilles, 500 x 300mm. Ea 7

7.2.15 Door Grilles, 300 x 200mm. Ea 1

7.3 FRESH AIR SAND TRAP LOUVERS:


Including 25mm thick aluminum filters, plenum
and accessories.

7.3.1 Sand Trap Louvers, 2000 x 1500mm. Ea 6

7.4 DUCT BELL MOUTHS : Including screen


etc. complete.

Page Sub-total

SFDA, Dammam Page 46


FACILITY : MAIN LABORATORY BUILDING

SECTION : HVAC WORK (Contd. . .)

S.No. Description Unit Qty Unit Rate Total Amount

7.4.1 Size 500 x 250mm. Ea 3

7.4.2 Size 550 x 300mm. Ea 1

7.4.3 Size 600 x 300mm. Ea 1

7.4.4 Size 1050 x 480mm. Ea 1

7.5 Exhaust Duct End - Bend with screen as shown Ea 12


in drawing (varies in sizes).

8.0 CHILLED WATER PIPING SYSTEM:


Complete with insulation, jointings, fittings
supports, hangers, sleeves, drain cool sensors,
flexible connections, back flow preventers,
reducers and all other materials/ accessories
required to complete the work as per drawing,
specifications and civil works related thereto
including testing & commissioning with
capability of building management system.

8.1 CHILLED WATER PIPING:

8.1.1 38mm dia. Seamless black steel pipe Lm 15


Schedule 40- ASTM-53

8.1.2 32mm dia. Seamless black steel pipe Lm 52


Schedule 40- ASTM-53

8.1.3 25mm dia. Seamless black steel pipe Lm 128


Schedule 40- ASTM-53

8.1.4 20mm dia. Seamless black steel pipe Lm 50


Schedule 40- ASTM-53

8.2 CHILLED WATER PIPING:


Complete with pre-formred fiber glass
aluminum with corrugated aluminum sheet
jacketing inside the Mechanical room and
exposed at roof

8.2.1 200mm dia. Seamless black steel pipe Lm 55


Schedule 40- ASTM-53

8.2.2 150mm dia. Seamless black steel pipe Lm 74


Schedule 40- ASTM-53

Page Sub-total

SFDA, Dammam Page 47


FACILITY : MAIN LABORATORY BUILDING

SECTION : HVAC WORK (Contd. . .)

S.No. Description Unit Qty Unit Rate Total Amount

8.2.3 125mm dia. Seamless black steel pipe Lm 77


Schedule 40- ASTM-53

8.2.4 100mm dia. Seamless black steel pipe Lm 115


Schedule 40- ASTM-53

8.2.5 75mm dia. Seamless black steel pipe Lm 135


Schedule 40- ASTM-53

8.2.6 50mm dia. Seamless black steel pipe Lm 64


Schedule 40- ASTM-53

8.2.7 38mm dia. Seamless black steel pipe Lm 5


Schedule 40- ASTM-53

8.3 CONDENSATE DRAIN PIPES (CD)


Including supports hangers and other fixing
accessories

8.3.1 38mm dia. UPVC pipe, Class-5 Lm 113

8.3.2 20mm dia. UPVC pipe, Class-5 Lm 52

8.3.3 32mm dia. UPVC pipe, Class-5 Lm 14

8.4 VALVE WITH MATING FLANGE AND


RELATED ACCESSORIES:

8.4.1 Motorized 2-way butteryfly valve, 150mm dia. Ea 4


flanged connection.

8.4.2 Gate Valve, 200mm dia, flanged connection. Ea 7

8.4.3 Check Valve, 200mm dia, flanged connection. Ea 2

8.4.4 Gate Valve, 150mm dia, flanged connection. Ea 8

8.4.5 Check Valve, 150mm dia, flanged connection. Ea 4

8.4.6 Double Regulating Valve, 150mm dia, flanged Ea 4


connection.

8.4.7 Regulating Valve, 125mm dia, flanged Ea 4


connection.

Page Sub-total

SFDA, Dammam Page 48


FACILITY : MAIN LABORATORY BUILDING

SECTION : HVAC WORK (Contd. . .)

S.No. Description Unit Qty Unit Rate Total Amount

8.4.8 Gate Valve, 125mm dia., flanged connection. Ea 8

8.4.9 Flexible Connector, 200mm dia., flanged Ea 4


connection.

8.4.10 Wye Strainer with drain valve, 200mm dia., Ea 2


flanged connection.

8.4.11 Flexible Connector, 150mm dia., flanged Ea 8


connection.

8.4.12 Wye Strainer with drain valve, 150mm dia., Ea 4


flanged connection.

9.0 CHILLED WATER PUMP:


Complete with local control panel and
accessories adoptable for BMS connection.

9.1 Chilled Water Pump (CWP1 to CWP4), 34 L/S, Ea 4


Pump Head - 16 meter, motor rating - 15 kW
End Suction type / Constant speed, 380-3-60.
(2-duty and 2-standby).

10.0 AUXILLARIES OF CHILLED WATER


SYSTEM:

10.1 TANKS AND ACCESSORIES

10.1.1 Expansion tank, 500 liters, diaphragm type, Ea 2


vertical mounted including valves and
accessories.

10.1.2 Flow Switch Ea 4

10.1.3 Chemical Dosing Tanks 30 liters capacity Ea 1


including valves and accessories.

10.1.4 Pressurization Unit, with pump, 1/2 HP, PRV, Set 1


valves and accessories.

10.1.5 Temperature gauges, (as per unit and piping Ea 8


system layout and detail ref. drawing no. M-14)

10.1.6 Pressure Gauges, (as per unit and piping Ea 12


system layout, ref. drawing. no. M-14).

Page Sub-total

SFDA, Dammam Page 49


FACILITY : MAIN LABORATORY BUILDING

SECTION : HVAC WORK (Contd. . .)

S.No. Description Unit Qty Unit Rate Total Amount

10.1.7 Automatic Air Vent, 20mm dia. connection. Ea 8

11.0 AIR COOLED WATER CHILLER UNIT:

11.1 Supply and installed Air Cooled Water Chiller Ea 4


including all valves, connections, insulations,
sealants, supports and complete in all aspects.
The work also include Micro Computer Control
Center and must contain at least two circular for
cooling as shown in the drawing:

- Cooling capacity = 605 kW


- External temperature = 115deg.Fdb
- Entering water temperature = 52.8deg.F
- Leaving water temperature = 43deg.F
- Height = 39 feet above sea level.

12.0 BUILDING MANAGEMENT SYSTEM AND


CONTROL SYSTEM :

12.1 Supply, installation, testing and commissioning Job 1


of all mechanical / electrical controls including
direct digital control system, Network Interface
unit, personal computer with B.M.S. software
(Central Control Station) and all other necessary
controls, and for monitoring of equipment as per
drawing and specifications.

Page Sub-total

TOTAL HVAC WORK - Main Laboratory Building

SFDA, Dammam Page 50


PROJECT : SAUDI FOOD AND DRUGS AUTHORITY, DAMMAM

FACILITY : MAIN LABORATORY BUILDING

SECTION : ELECTRICAL WORK

S.No. Description Unit Qty Unit Rate Total Amount

1.0 DEMOLITION WORKS:

1.1 Demolishing and Dismantling of the existing Job 1


all Electrical equipments including Lighting ,
small power ( Socket outlets , Panel boards ,
Disturbution panels , Sub Panel boards ,
Dis connect switches, etc ) , Cables
( Power , Telephone , Low current,etc )
All Conduits and trunking ,etc and related
works, etc., and all related Electrical works
to give way for the proposed new design and
construction. The valuable and re-usable
materials shall be handed over to the
Supervising Engineer. The demolished debris
shall be removed and disposed to a location
approved by the Supervising Engineer.

2.0 MAIN DISTRIBUTION PANELBOARDS :


Supply, installation, testing and commissioning
with main and branch circuit breakers, including
bus bars, enclosures, supports, grounding,
internal wirings and other accessories required
to complete the work as per drawings and
specifications.

2.1 MAIN DISTRIBUTION_PANELBOARDS:


Including indicator lamps volt meter, ammeter,
selector switches and all accessories,
incoming and outgoing breakers shall be
molded case circuit breakers (MCCB)
industrial type, heavy duty.

2.1.1 Main Distribution Panel "MDP-L" Ea 1


380/220V, 3Phase, 4W, 60Hz with full neutral
bus and ground terminals, IP20 Enclosure.
Main:
1000 AT / 1250 AF, 3P, ACB

Branches:
1 - 500 AT / 630 AF, 3P, MCCB
2 - 300 AT / 400 AF, 3P, MCCB
7 - 100 AT / 100 AF, 3P, MCCB
2 - 70 AT / 100 AF, 3P, MCCB

Page Sub-total

SFDA, Dammam Page 51


FACILITY : MAIN LABORATORY BUILDING

SECTION : ELECTRICAL WORK (Contd. . .)

S.No. Description Unit Qty Unit Rate Total Amount

2.1.2 Emergency Main Distribution Panel "EMDP-L" Ea 1


380/220V, 3Phase, 4W, 60Hz with full neutral
bus and ground terminals, IP20 Enclosure.
Main:
1400 AT / 1600 AF, 3P, ACB

Branches:
1 - 500 AT / 630 AF, 3P, MCCB
2 - 300 AT / 400 AF, 3P, MCCB
3 - 250 AT / 300 AF, 3P, MCCB
4 - 100 AT / 100 AF, 3P, MCCB
2 - 70 AT / 100 AF, 3P, MCCB
2 - 60 AT / 100 AF, 3P, MCCB

2.1.3 Panel Board type MCC-RN1 Ea 1


380/220V, 3Phase, 4W, 60Hz with full neutral bus
bus and ground terminals, IP20 Enclosure.
Main:
3000AT / 3200AF, 3P, ACB
Branches:
2 - 1200AT / 1400AF, 3P, ACB
3 - 200AT / 250AF, 3P, MCCB
2 - 100AT / 100AF, 3P, MCCB

2.1.4 Panel Board type MCC-RN2 Ea 1


380/220V, 3Phase, 4W, 60Hz with full neutral bus
bus and ground terminals, IP20 Enclosure.
Main:
3000AT / 3200AF, 3P, ACB
Branches:
2 - 1200AT / 1400AF, 3P, ACB
2 - 200AT / 250AF, 3P, MCCB
2 - 100AT / 100AF, 3P, MCCB
1 - 60 AT / 100 AF, 3P, MCCB

2.1.5 Panel Board type MCC-RN3 Ea 1


380/220V, 3Phase, 4W, 60Hz with full neutral bus
bus and ground terminals, IP20 Enclosure.
Main:
1000AT / 1250AF, 3P, ACB
Branches:
4 - 150AT / 250AF, 3P, MCCB
6 - 100AT / 100AF, 3P, MCCB

Page Sub-total

SFDA, Dammam Page 52


FACILITY : MAIN LABORATORY BUILDING

SECTION : ELECTRICAL WORK (Contd. . .)

S.No. Description Unit Qty Unit Rate Total Amount

2.2 SUB DISTRIBUTION_PANELBOARDS:


Including indicator lamps volt meter, ammeter,
selector switches and all accessories,
incoming and outgoing breakers shall be
molded case circuit breakers (MCCB)
industrial type, heavy duty.

2.2.1 Panel Board type SDP-1F Ea 1


380/220V, 3Phase, 4W, 60Hz with full neutral bus
bus and ground terminals, IP20 Enclosure.
Main:
500AT / 630AF, 3P, MCCB
Branches:
1 - 200AT / 250AF, 3P, MCCB
6 - 100AT / 100AF, 3P, MCCB
3 - 60AT / 100AF, 3P, MCCB

2.2.2 Panel Board type ESDP-1F Ea 1


380/220V, 3Phase, 4W, 60Hz with full neutral bus
bus and ground terminals, IP20 Enclosure.
Main:
300AT / 400AF, 3P, MCCB
Branches:
5 - 100AT / 100AF, 3P, MCCB
3 - 60AT / 100AF, 3P, MCCB

2.2.3 Panel Board type SDP-2F Ea 1


380/220V, 3Phase, 4W, 60Hz with full neutral bus
bus and ground terminals, IP20 Enclosure.
Main:
300AT / 400AF, 3P, MCCB
Branches:
5 - 100AT / 100AF, 3P, MCCB
2 - 70AT / 100AF, 3P, MCCB
3 - 60AT / 100AF, 3P, MCCB

2.2.4 Panel Board type ESDP-2F Ea 1


380/220V, 3Phase, 4W, 60Hz with full neutral bus
bus and ground terminals, IP20 Enclosure.
Main:
300AT / 400AF, 3P, MCCB
Branches:
5 - 100AT / 100AF, 3P, MCCB
2 - 60AT / 100AF, 3P, MCCB
1 - 30AT / 100AF, 3P, MCCB

Page Sub-total

SFDA, Dammam Page 53


FACILITY : MAIN LABORATORY BUILDING

SECTION : ELECTRICAL WORK (Contd. . .)

S.No. Description Unit Qty Unit Rate Total Amount

2.2.5 Panel Board type ESDP-RF Ea 1


380/220V, 3Phase, 4W, 60Hz with full neutral bus
bus and ground terminals, IP20 Enclosure.
Main:
500AT / 630AF, 3P, MCCB
Branches:
12 - 100AT / 100AF, 3P, MCCB

2.2.6 Panel Board type SDP-UPS Ea 1


380/220V, 3Phase, 4W, 60Hz with full neutral bus
bus and ground terminals, IP20 Enclosure.
Main:
250AT / 300AF, 3P, MCCB

Branches:
4 - 100AT / 100AF, 3P, MCCB
4 - 60AT / 100AF, 3P, MCCB

2.2.7 Panel Board type MBCP Ea 1


380/220V, 3Phase, 4W, 60Hz with full neutral bus
bus and ground terminals, IP20 Enclosure.

Main:
2 - 250AT / 300AF, 3P, MCCB
with External By-pass Isolator Switch (EBIS),
250A, 3P.

2.3 PANEL BOARDS:

2.3.1 Panel Board type PBL-GN1 Ea 1


380/220V, 3Phase, 4W, 60Hz with full neutral bus
bus and ground terminals, IP20 Enclosure.
Main:
70AT / 100AF, 3P, MCCB
Branches:
30 - 20AT / 100AF, 1P

2.3.2 Panel Board type PBL-GN2 Ea 1


380/220V, 3Phase, 4W, 60Hz with full neutral bus
bus and ground terminals, IP20 Enclosure.
Main:
70AT / 100AF, 3P, MCCB
Branches:
30 - 20AT / 100AF, 1P

Page Sub-total

SFDA, Dammam Page 54


FACILITY : MAIN LABORATORY BUILDING

SECTION : ELECTRICAL WORK (Contd. . .)

S.No. Description Unit Qty Unit Rate Total Amount

2.3.3 Panel Board type PBL-GN3 Ea 1


380/220V, 3Phase, 4W, 60Hz with full neutral bus
bus and ground terminals, IP20 Enclosure.
Main:
100AT / 100AF, 3P, MCCB
Branches:
36 - 20AT / 100AF, 1P

2.3.4 Panel Board type PBL-GM1 Ea 1


380/220V, 3Phase, 4W, 60Hz with full neutral bus
bus and ground terminals, IP20 Enclosure.
Main:
100AT / 100AF, 3P, MCCB
Branches:
4 - 20AT / 100AF, 1P
14 - 30AT / 100AF, 1P
4 - 40AT / 100AF, 3P

2.3.5 Panel Board type PBL-GM2 Ea 1


380/220V, 3Phase, 4W, 60Hz with full neutral bus
bus and ground terminals, IP20 Enclosure.
Main:
100AT / 100AF, 3P, MCCB
Branches:
8 - 20AT / 100AF, 1P
10 - 30AT / 100AF, 1P
6 - 40AT / 100AF, 1P
4 - 40AT / 100AF, 3P

2.3.6 Panel Board type PBL-GE1 Ea 1


380/220V, 3Phase, 4W, 60Hz with full neutral bus
bus and ground terminals, IP20 Enclosure.
Main:
70AT / 100AF, 3P, MCCB
Branches:
34 - 10AT / 100AF, 1P
2 - 30AT / 100AF, 1P
1 - 20AT / 100AF, 1P

2.3.7 Panel Board type PBL-GE2 Ea 1


380/220V, 3Phase, 4W, 60Hz with full neutral bus
bus and ground terminals, IP20 Enclosure.
Main:
70AT / 100AF, 3P, MCCB
Branches:
24 - 20AT / 100AF, 1P

Page Sub-total

SFDA, Dammam Page 55


FACILITY : MAIN LABORATORY BUILDING

SECTION : ELECTRICAL WORK (Contd. . .)

S.No. Description Unit Qty Unit Rate Total Amount

2.3.8 Panel Board type PBL-GE3 Ea 1


380/220V, 3Phase, 4W, 60Hz with full neutral bus
bus and ground terminals, IP20 Enclosure.
Main:
100AT / 100AF, 3P, MCCB
Branches:
42 - 10AT / 100AF, 1P

2.3.9 Panel Board type PBL-GE4 Ea 1


380/220V, 3Phase, 4W, 60Hz with full neutral bus
bus and ground terminals, IP20 Enclosure.
Main:
60AT / 100AF, 3P, MCCB
Branches:
24 - 20AT / 100AF, 1P

2.3.10 Panel Board type PBL-GU Ea 1


380/220V, 3Phase, 4W, 60Hz with full neutral bus
bus and ground terminals, IP20 Enclosure.
Main:
60AT / 100AF, 3P, MCCB
Branches:
24 - 20AT / 100AF, 1P

2.3.11 Panel Board type PBL-GCS Ea 1


380/220V, 3Phase, 4W, 60Hz with full neutral bus
bus and ground terminals, IP20 Enclosure.
Main:
250AT / 300AF, 3P, MCCB
Branches:
16 - 30AT / 100AF, 3P

2.3.12 Panel Board type PBL-1N1 Ea 1


380/220V, 3Phase, 4W, 60Hz with full neutral bus
bus and ground terminals, IP20 Enclosure.
Main:
60AT / 100AF, 3P, MCCB
Branches:
24 - 20AT / 100AF, 1P

2.3.13 Panel Board type PBL-1N2 Ea 1


380/220V, 3Phase, 4W, 60Hz with full neutral bus
bus and ground terminals, IP20 Enclosure.
Main:
60AT / 100AF, 3P, MCCB

Page Sub-total

SFDA, Dammam Page 56


FACILITY : MAIN LABORATORY BUILDING

SECTION : ELECTRICAL WORK (Contd. . .)

S.No. Description Unit Qty Unit Rate Total Amount

Branches:
24 - 20AT / 100AF, 1P

2.3.14 Panel Board type PBL-1N3 Ea 1


380/220V, 3Phase, 4W, 60Hz with full neutral bus
bus and ground terminals, IP20 Enclosure.
Main:
100AT / 100AF, 3P, MCCB
Branches:
36 - 20AT / 100AF, 1P

2.3.15 Panel Board type PBL-1N4 Ea 1


380/220V, 3Phase, 4W, 60Hz with full neutral bus
bus and ground terminals, IP20 Enclosure.
Main:
100AT / 100AF, 3P, MCCB
Branches:
36 - 20AT / 100AF, 1P

2.3.16 Panel Board type PBL-1E1 Ea 1


380/220V, 3Phase, 4W, 60Hz with full neutral bus
bus and ground terminals, IP20 Enclosure.
Main:
100AT / 100AF, 3P, MCCB
Branches:
33 - 10AT / 100AF, 1P
1 - 30AT / 100AF, 3P

2.3.17 Panel Board type PBL-1E2 Ea 1


380/220V, 3Phase, 4W, 60Hz with full neutral bus
bus and ground terminals, IP20 Enclosure.
Main:
60AT / 100AF, 3P, MCCB
Branches:
24 - 20AT / 100AF, 1P

2.3.18 Panel Board type PBL-1E3 Ea 1


380/220V, 3Phase, 4W, 60Hz with full neutral bus
bus and ground terminals, IP20 Enclosure.
Main:
100AT / 100AF, 3P, MCCB
Branches:
36 - 10AT / 100AF, 1P

Page Sub-total

SFDA, Dammam Page 57


FACILITY : MAIN LABORATORY BUILDING

SECTION : ELECTRICAL WORK (Contd. . .)

S.No. Description Unit Qty Unit Rate Total Amount

2.3.19 Panel Board type PBL-1E4 Ea 1


380/220V, 3Phase, 4W, 60Hz with full neutral bus
bus and ground terminals, IP20 Enclosure.
Main:
60AT / 100AF, 3P, MCCB
Branches:
24 - 20AT / 100AF, 1P

2.3.20 Panel Board type PBL-1U1 Ea 1


380/220V, 3Phase, 4W, 60Hz with full neutral bus
bus and ground terminals, IP20 Enclosure.
Main:
100AT / 100AF, 3P, MCCB
Branches:
42 - 20AT / 100AF, 1P

2.3.21 Panel Board type PBL-1U2 Ea 1


380/220V, 3Phase, 4W, 60Hz with full neutral bus
bus and ground terminals, IP20 Enclosure.
Main:
100AT / 100AF, 3P, MCCB
Branches:
42 - 20AT / 100AF, 1P

2.3.22 Panel Board type PBL-1M1 Ea 1


380/220V, 3Phase, 4W, 60Hz with full neutral bus
bus and ground terminals, IP20 Enclosure.
Main:
100AT / 100AF, 3P, MCCB
Branches:
4 - 20AT / 100AF, 1P
14 - 30AT / 100AF, 1P
4 - 40AT / 100AF, 3P

2.3.23 Panel Board type PBL-1M2 Ea 1


380/220V, 3Phase, 4W, 60Hz with full neutral bus
bus and ground terminals, IP20 Enclosure.
Main:
100AT / 100AF, 3P, MCCB
Branches:
8 - 20AT / 100AF, 1P
10 - 30AT / 100AF, 1P
3 - 40AT / 100AF, 1P
7 - 40AT / 100AF, 3P

Page Sub-total

SFDA, Dammam Page 58


FACILITY : MAIN LABORATORY BUILDING

SECTION : ELECTRICAL WORK (Contd. . .)

S.No. Description Unit Qty Unit Rate Total Amount

2.3.24 Panel Board type PBL-2N1 Ea 1


380/220V, 3Phase, 4W, 60Hz with full neutral bus
bus and ground terminals, IP20 Enclosure.
Main:
60AT / 100AF, 3P, MCCB
Branches:
24 - 20AT / 100AF, 1P

2.3.25 Panel Board type PBL-2N2 Ea 1


380/220V, 3Phase, 4W, 60Hz with full neutral bus
bus and ground terminals, IP20 Enclosure.
Main:
60AT / 100AF, 3P, MCCB

Branches:
24 - 20AT / 100AF, 1P

2.3.26 Panel Board type PBL-2N3 Ea 1


380/220V, 3Phase, 4W, 60Hz with full neutral bus
bus and ground terminals, IP20 Enclosure.
Main:
100AT / 100AF, 3P, MCCB

Branches:
36 - 20AT / 100AF, 1P

2.3.27 Panel Board type PBL-2N4 Ea 1


380/220V, 3Phase, 4W, 60Hz with full neutral bus
bus and ground terminals, IP20 Enclosure.
Main:
100AT / 100AF, 3P, MCCB
Branches:
36 - 20AT / 100AF, 1P

2.3.28 Panel Board type PBL-2E1 Ea 1


380/220V, 3Phase, 4W, 60Hz with full neutral bus
bus and ground terminals, IP20 Enclosure.
Main:
100AT / 100AF, 3P, MCCB
Branches:
31 - 10AT / 100AF, 1P
5- 30AT / 100AF, 1P

2.3.29 Panel Board type PBL-2E2 Ea 1


380/220V, 3Phase, 4W, 60Hz with full neutral bus
bus and ground terminals, IP20 Enclosure.

Page Sub-total

SFDA, Dammam Page 59


FACILITY : MAIN LABORATORY BUILDING

SECTION : ELECTRICAL WORK (Contd. . .)

S.No. Description Unit Qty Unit Rate Total Amount

Main:
60AT / 100AF, 3P, MCCB
Branches:
24 - 20AT / 100AF, 1P

2.3.30 Panel Board type PBL-2E3 Ea 1


380/220V, 3Phase, 4W, 60Hz with full neutral bus
bus and ground terminals, IP20 Enclosure.
Main:
100AT / 100AF, 3P, MCCB
Branches:
31 - 10AT / 100AF, 1P
5- 30AT / 100AF, 1P

2.3.31 Panel Board type PBL-2E4 Ea 1


380/220V, 3Phase, 4W, 60Hz with full neutral bus
bus and ground terminals, IP20 Enclosure.
Main:
60AT / 100AF, 3P, MCCB
Branches:
24 - 20AT / 100AF, 1P

2.3.32 Panel Board type PBL-2U1 Ea 1


380/220V, 3Phase, 4W, 60Hz with full neutral bus
bus and ground terminals, IP20 Enclosure.
Main:
60AT / 100AF, 3P, MCCB
Branches:
30 - 20AT / 100AF, 1P

2.3.33 Panel Board type PBL-2U2 Ea 1


380/220V, 3Phase, 4W, 60Hz with full neutral bus
bus and ground terminals, IP20 Enclosure.
Main:
100AT / 100AF, 3P, MCCB
Branches:
42 - 20AT / 100AF, 1P

2.3.34 Panel Board type PBL-2M1 Ea 1


380/220V, 3Phase, 4W, 60Hz with full neutral bus
bus and ground terminals, IP20 Enclosure.
Main:
70AT / 100AF, 3P, MCCB
Branches:
6 - 20AT / 100AF, 1P
12 - 30AT / 100AF, 1P
4 - 40AT / 100AF, 3P

Page Sub-total

SFDA, Dammam Page 60


FACILITY : MAIN LABORATORY BUILDING

SECTION : ELECTRICAL WORK (Contd. . .)

S.No. Description Unit Qty Unit Rate Total Amount

2.3.35 Panel Board type PBL-2M2 Ea 1


380/220V, 3Phase, 4W, 60Hz with full neutral bus
bus and ground terminals, IP20 Enclosure.
Main:
70AT / 100AF, 3P, MCCB
Branches:
6 - 20AT / 100AF, 1P
12 - 30AT / 100AF, 1P
4 - 40AT / 100AF, 3P

2.3.36 Panel Board type PBL-RE1 Ea 1


380/220V, 3Phase, 4W, 60Hz with full neutral bus
bus and ground terminals, IP20 Enclosure.
Main:
100AT / 100AF, 3P, MCCB
Branches:
6 - 10AT / 100AF, 1P
11 - 20AT / 100AF, 1P
13 - 30AT / 100AF, 1P
2 - 30AT / 100AF, 3P

2.3.37 Panel Board type PBL-RE2 Ea 1


380/220V, 3Phase, 4W, 60Hz with full neutral bus
bus and ground terminals, IP20 Enclosure.
Main:
100AT / 100AF, 3P, MCCB
Branches:
4 - 10AT / 100AF, 1P
9 - 20AT / 100AF, 1P
11 - 30AT / 100AF, 1P
2 - 30AT / 100AF, 1P

2.4 Uninterrupted Power Supply (UPS1), 120KVA, Ea 1


380V - 380/220V, 3PH, 4W, 60 Hz, complete
with Battery, 20 minutes duration.

2.5 ENCLOSED CIRCUIT BREAKER:


Including fixing and all accessories.

2.5.1 Enclosed Circuit Breaker type ECB1, 250 AT, Ea 1


3P, MCCB, NEMA 1/IP20 for UPS.

2.5.2 Enclosed Circuit Breaker type ECB's, Ea 4


1600 AT, 3P, ACB, NEMA 3R/IP54 Enclosure
for Chiller 1 to 4.

Page Sub-total

SFDA, Dammam Page 61


FACILITY : MAIN LABORATORY BUILDING

SECTION : ELECTRICAL WORK (Contd. . .)

S.No. Description Unit Qty Unit Rate Total Amount

2.5.3 Enclosed Circuit Breaker type ECB's, Ea 29


30A, 2P, 220V for Fume Hood.

3.0 CABLING :
Supply, installation, testing and commissioning
of cables on wall, roof or ground with suitable
G.S. clamps, spacers, supports, conduits, cable
trays, grounding, trenching, end connections,
concreting etc. from their corresponding panel
boards. All are in accordance with the drawing
and specifications.

3.1 4c x 300sq.mm + 1c x 120sq.mm (E) XLPE / Lm 12


PVC copper cable in cable tray from MDP-L to
SDP-1F.

3.2 4c x 120sq.mm + 1c x 70sq.mm (E) XLPE / Lm 15


PVC copper cable in cable tray from MDP-L to
SDP-2F.

3.3 4c x 120sq.mm + 1c x 70sq.mm (E) XLPE / Lm 12


PVC copper cable in cable tray from EMDP-L
to ESDP-1F.

3.4 4c x 120sq.mm + 1c x 70sq.mm (E) XLPE / Lm 15


PVC copper cable in cable tray from EMDP-L
to ESDP-2F.

3.5 2 sets-4c x 300sq.mm + 1c x 120 sq.mm (E) Lm 50


XLPE / PVC copper cable in cable tray from
EMDP-L to ESDP-RF.

3.6 4c x 35sq.mm + 1c x 16sq.mm (E) XLPE / Lm 144


PVC copper cable in cable tray from MDP-L to
PBL-GN1, PBL-GN2, PBL-GN3, PBL-GM1
and PBL-GM2.

3.7 4c x 35sq.mm + 1c x 16sq.mm (E) XLPE / Lm 76


PVC copper cable in cable tray from EMDP-L
to PBL-GE1, PBL-GE2 and PBL-GE3.

3.8 4c x 25sq.mm + 1c x 10sq.mm (E) XLPE / PVC Lm 50


copper cable in cable tray from EMDP-L to
PBL-GE4.

Page Sub-total

SFDA, Dammam Page 62


FACILITY : MAIN LABORATORY BUILDING

SECTION : ELECTRICAL WORK (Contd. . .)

S.No. Description Unit Qty Unit Rate Total Amount

3.9 4c x 120sq.mm + 1c x 70sq.mm (E) XLPE / Lm 10


PVC copper cable in cable tray from MBCP to
SDP-UPS.

3.10 4c x 120sq.mm + 1c x 70sq.mm (E) XLPE / Lm 20


PVC copper cable in cable tray from EMDP-L
to ECB thru UPS and EBIS via MBCP.

3.11 4c x 25sq.mm + 1c x 10 sq.mm (E) XLPE / Lm 10


PVC copper cable in cable tray from SDP-UPS
to PBL-GU.

3.12 4c x 35sq.mm + 1c x 16sq.mm (E) XLPE / PVC Lm 81


copper cable in cable tray from SDP-UPS to
PBL-1U1, PBL-1U2 and PBL-2U2.

3.13 4c x 35sq.mm + 1c x 16sq.mm (E) XLPE / PVC Lm 121


copper cable in cable tray from SDP-1F to
PBL-1N3, PBL-1N4 and PBL-1M1.

3.14 4c x 25sq.mm + 1c x 10sq.mm (E) XLPE / PVC Lm 37


copper cable in cable tray from SDP-1F to
PBL-1N1 and PBL-1N2.

3.15 4c x 70sq.mm + 1c x 35 sq.mm (E) XLPE / PVC Lm 52


copper cable in cable tray from SDP-1F to
PBL-1M2.

3.16 4c x 35sq.mm + 1c x 16sq.mm (E) XLPE / Lm 70


PVC copper cable in cable tray from ESDP-1F
to PBL-1E1 and PBL-1E3.

3.17 4c x 25sq.mm + 1c x 10sq.mm (E) XLPE / Lm 67


PVC copper cable in cable tray from ESDP-1F
to PBL-1E2 and PBL-1E4.

3.18 4c x 35sq.mm + 1c x 16sq.mm (E) XLPE / Lm 173


PVC copper cable in cable tray from SDP-2F
to PBL-2N3, PBL-2N4 and PBL-2M1.

3.19 4c x 25sq.mm + 1c x 10sq.mm (E) XLPE / Lm 37


PVC copper cable in cable tray from SDP-2F
to PBL-2N1 and PBL-2N2.

3.20 4c x 25sq.mm + 1c x 10sq.mm (E) XLPE / Lm 64


PVC copper cable in cable tray from SDP-UPS
to PBL-2U1.

Page Sub-total

SFDA, Dammam Page 63


FACILITY : MAIN LABORATORY BUILDING

SECTION : ELECTRICAL WORK (Contd. . .)

S.No. Description Unit Qty Unit Rate Total Amount

3.21 4c x 35sq.mm + 1c x 16sq.mm (E) XLPE / Lm 70


PVC copper cable in cable tray from ESDP-2F
to PBL-2E1 and PBL-2E3.

3.22 4c x 25sq.mm + 1c x 10sq.mm (E) XLPE / Lm 67


PVC copper cable in cable tray from ESDP-2F
to PBL-2E2 and PBL-2E4.

3.23 3 sets-4c x 300sq.mm + 1c x 120 sq.mm (E) Lm 100


XLPE / PVC copper cable in cable tray from
MCC-RN1 to Chiller 1 & 2 ECB's.

3.24 3 sets-4c x 300sq.mm + 1c x 120 sq.mm (E) Lm 61


XLPE / PVC copper cable in cable tray from
MCC-RN2 to Chiller 3 & 4 ECB's.

3.25 4c x 50sq.mm + 1c x 25sq.mm (E) XLPE / Lm 18


PVC copper cable in cable tray from MCC-RN1
to HRU - GF4 disconnect switch.

3.26 4c x 70sq.mm + 1c x 35sq.mm (E) XLPE / Lm 30


PVC copper cable in cable tray from MCC-RN1
to HRU - F3 disconnect switch.

3.27 4c x 95sq.mm + 1c x 50sq.mm (E) XLPE / Lm 26


PVC copper cable in cable tray from MCC-RN1
to HRU - F4 disconnect switch.

3.28 4c x 35sq.mm + 1c x 16sq.mm (E) XLPE / Lm 37


PVC copper cable in cable tray from MCC-RN2
to AHU - GF3 disconnect switch.

3.29 4c x 95sq.mm + 1c x 50sq.mm (E) XLPE / Lm 63


PVC copper cable in cable tray from MCC-RN2
to HRU - SF3 and SF4 disconnect switches.

3.30 4c x 50sq.mm + 1c x 25sq.mm (E) XLPE / Lm 38


PVC copper cable in cable tray from MCC-RN3
to HRU - GF1 and GF2 disconnect switches.

3.31 4c x 70sq.mm + 1c x 35sq.mm (E) XLPE / Lm 15


PVC copper cable in cable tray from MCC-RN3
to HRU - F1 disconnect switch.

3.32 4c x 95sq.mm + 1c x 50sq.mm (E) XLPE / Lm 62


PVC copper cable in cable tray from MCC-RN3
to HRU - F2, SF1 and SF2 disconnect switches.

Page Sub-total

SFDA, Dammam Page 64


FACILITY : MAIN LABORATORY BUILDING

SECTION : ELECTRICAL WORK (Contd. . .)

S.No. Description Unit Qty Unit Rate Total Amount

3.33 3c x 35sq.mm + 1c x 16sq.mm (E) XLPE / Lm 51


PVC copper cable in cable tray from MCC-RN1
to CWP-1 and 2 disconnect switches.

3.34 3c x 50sq.mm + 1c x 25sq.mm (E) XLPE / Lm 114


PVC copper cable in cable tray from MCC-RN2
to CWP-3 and 4 disconnect switches.

3.35 4c x 35sq.mm + 1c x 16sq.mm (E) XLPE / Lm 206


PVC copper cable in cable tray from ESDP-RF
to Elevators disconnect switches.

3.36 4c x 35sq.mm + 1c x 16sq.mm (E) XLPE / Lm 112


PVC copper cable in cable tray from ESDP-RF
to PBL-RE1 and PBL-RE2.

3.37 3 sets - 4C x 400sq.mm + 1c x 240 sq.mm (E) Lm 91


XLPE / PVC copper cable in cable tray and
PVC conduit from MSB-SB to MDP-L.

3.38 4 sets - 4C x 400sq.mm + 1c x 240 sq.mm (E) Lm 94


XLPE / PVC copper cable in cable tray and
PVC conduit from EMSB-SB to EMDP-L.

3.39 3 sets - 4C x 400sq.mm + 1c x 240 sq.mm (E) Lm 96


XLPE / PVC copper cable in cable tray and
PVC conduit from MSB-SB to MCC-RN3.

3.40 8 sets - 4C x 400sq.mm + 1c x 240 sq.mm (E) Lm 41


XLPE / PVC copper cable in cable tray and
PVC conduit from MCC-ECB1 to MCC-RN1.

3.41 8 sets - 4C x 400sq.mm + 1c x 240 sq.mm (E) Lm 46


XLPE / PVC copper cable in cable tray and
PVC conduit from MCC-ECB2 to MCC-RN2.

3.42 4c x 120sq.mm + 1c x 70sq.mm (E) XLPE / Lm 12


PVC copper cable in cable tray from EMDP-L
to PBL-GCS.

3.43 4c x 50sq.mm + 1c x 25sq.mm (E) XLPE / Lm 76


PVC copper cable in cable tray from ESDP-RF
to Elevators disconnect switches.

Page Sub-total

SFDA, Dammam Page 65


FACILITY : MAIN LABORATORY BUILDING

SECTION : ELECTRICAL WORK (Contd. . .)

S.No. Description Unit Qty Unit Rate Total Amount

3.44 4c x 25sq.mm + 1c x 10sq.mm (E) XLPE / Lm 101


PVC copper cable in cable tray from PBL-GCS
to Nitrogen Generator disconnect switch.

3.45 4c x 16sq.mm + 1c x 10sq.mm (E) XLPE / Lm 14


PVC copper cable in cable tray from PBL-GCS
to Nitrogen Generator disconnect switch.

4.0 SOCKET OUTLET/SWITCHES :


Supply, installation, testing and commissioning
of socket outlet (British type) and switches
including wirings, cables, cable trays, supports,
conduiting, grounding, metal boxes, plate cover
and other required accessories in accordance
with the drawings and specifications.

4.1 13A, 250V, 3 pin Single earthed switch socket Ea 137


outlet (mounted at 300mm AFFL), British type.

4.2 13A, 250V, 3 pin duplex earthed switch socket Ea 87


outlet (mounted at 300mm AFFL), British type.

4.3 13A, 250V, 3 pin Single earthed switch socket Ea 7


outlet (mounted at 300mm AFFL), British type,
weatherproof type.

4.4 13A, 250V, 3 pin single earthed switch socket Ea 5


outlet UPS supplied (mounted at 300mm AFFL)
British type.

4.5 13A, 250V, 3 pin duplex earthed switch socket Ea 39


outlet UPS supplied (mounted at 300mm AFFL)
British type.

4.6 13A, 250V, 3 pin duplex earthed switch socket Ea 884


outlet (mounted at trunking above the table),
British type.

4.7 13A, 250V, 3 pin duplex earthed switch socket Ea 175


outlet (table mounted ), British type.

4.8 20A, 250V, D.P switch complete with Ea 7


neon light for hand dryer (British type).

4.9 20A, 250V, D.P switch complete with Ea 9


neon light for water heater (British type).

Page Sub-total

SFDA, Dammam Page 66


FACILITY : MAIN LABORATORY BUILDING

SECTION : ELECTRICAL WORK (Contd. . .)

S.No. Description Unit Qty Unit Rate Total Amount

4.10 32A, 250V, D.P switch complete with Ea 2


neon light for cooker (British type).

4.11 30A, 250V, Twist lock complete with plug to Ea 5


American Standard type.

4.12 Junction box floor mounted (weatherproof) Ea 3


socket outlet, VDE standard + data outlet RJ45.

4.13 Floor box type FB consists of : Ea 14


- 2-13A, 250V, 3P, duplex earthed switch
socket outlet British type.
- 1 IP telephone outlet RJ-45.
- 1 IP Data outlet RJ-45.

4.14 20A, 1 way, 1 gang switch. Ea 228

4.15 20A, 1 way, 1 gang switch, weatherproof type. Ea 3

4.16 20A, 1 way, 2 gang switch. Ea 11

4.17 20A, 2 way, 1 gang switch. Ea 115

4.18 20A, 2 way, 2 gang switch. Ea 20

4.19 20A, 1 way, 1 gang switch for Exhaust fans. Ea 11

4.20 20A, DP switch with neon light for Exhaust fans. Ea 7

4.21 32A, DP switch with neon light for Exhaust fans. Ea 11

4.22 15A, 250V, single earthed switch socket outlet Ea 72


for window shutter (British type).

4.23 20A, 2P, 220V, non-fusible disconnect switches Ea 27


for VAV's

4.24 20A, 2P, 220V, non-fusible disconnect switches Ea 6


for Exhaust fans.

4.25 30A, 3P, 380V, non-fusible disconnect switches Ea 12


for Cold room and Freezer room.

4.26 30A, 2P, 220V, non-fusible disconnect switches Ea 7


for PF's and Booster pumps, weatherproof type.

Page Sub-total

SFDA, Dammam Page 67


FACILITY : MAIN LABORATORY BUILDING

SECTION : ELECTRICAL WORK (Contd. . .)

S.No. Description Unit Qty Unit Rate Total Amount

4.27 30A, 2P, 220V, non-fusible disconnect switches Ea 24


for FCU's and Exhaust fans.

4.28 60A, 2P, 220V, non-fusible disconnect switches Ea 2


for ACCU-1, weatherproof type.

4.29 60A, 3P, 380V, non-fusible disconnect switches Ea 11


for Dish washer.

4.30 Junction box complete with data outlet RJ 45 + Ea 25


1-13A, 250V, 2P+E socket outlet British type
for IP cam.

4.31 Junction box complete with data outlet RJ 45 + Ea 18


1-13A, 250V, 2P+E socket outlet British type
for IP cam, weatherproof type.

5.0 Supply, installation, testing and commissioning


of disconnect switch only including boxes,
cable trays, bracket, supports and other
accessories to complete the work. (Cables
already considered under section "CABLING").

5.1 200A, 3P, 380V, non-fusible disconnect switch Ea 11


for HRU's.

5.2 100A, 3P, 380V, non-fusible disconnect Ea 6


switches for HRU's and CWP's.

5.3 100A, 3P, 380V, non-fusible disconnect switch Ea 6


for new and existing Elevators.

5.4 60A, 3P, 380V, non-fusible disconnect switch Ea 11


for AHU-GF3 and HRU's, weatherproof type.

5.5 30A, 3P, 380V, Non-fusible disconnect switch Ea 2


for Nitrogen Generator, explosion proof type.

6.0 CABLE TRUNKING SYSTEM :


Supply and install ceiling / wall trunking system
as shown in drawing including all accessories,
junction boxes, bridges, separators, related civil
work, etc., complete.

6.1 3 compartment Galvanized steel wall trunking of Lm 970


nominal size 250mm x 50mm for power cables.

Page Sub-total

SFDA, Dammam Page 68


FACILITY : MAIN LABORATORY BUILDING

SECTION : ELECTRICAL WORK (Contd. . .)

S.No. Description Unit Qty Unit Rate Total Amount

6.2 3 compartment Galvanized steel riser trunking Lm 174


of nominal size 250mm x 50mm for power
cables.

6.3 3 compartment Galvanized steel horizontal Lm 564


trunking (above ceiling) of nominal size 300mm
x 100mm for power cables.

6.4 3 compartment Galvanized steel horizontal Lm 114


trunking (above ceiling) and riser of nominal
size 250mm x 100mm for power cables.

6.5 Galvanized steel horizontal trunking (above Lm 505


ceiling) of nominal size 250mm x 100mm for
Telephone cables.

6.6 Galvanized steel riser trunking of nominal size Lm 243


250mm x 50mm for Telephone cables.

7.0 CABLE TRAY SYSTEM:


Supply and install cable trays for power cables
above ceiling and lower roof as shown in the
drawing, including riser cable trays complete
with necessary fittings, supports (by Unistrut
channel), grounding terminals, grounding
connections, etc. and all other required
accessories to complete the installations.

7.1 Cable tray size 600mm x 50mm Lm 482

7.2 Cable tray size 500mm x 50mm Lm 105

7.3 Cable tray size 400mm x 50mm Lm 75

7.4 Cable tray size 300mm x 50mm Lm 85

7.5 Cable tray size 200mm x 50mm Lm 6

8.0 LIGHTING SYSTEM:


Supply, installation, testing and commissioning
of the following lighting fixtures including wiring,
conduiting grounding, metal boxes, supports,
hangers, controls, concreting, civil works and
other accessories required to complete the
work as per specification. Electronic ballast for
all fluorescent.

Page Sub-total

SFDA, Dammam Page 69


FACILITY : MAIN LABORATORY BUILDING

SECTION : ELECTRICAL WORK (Contd. . .)

S.No. Description Unit Qty Unit Rate Total Amount

8.1 Type C lighting fixture, 4 x 28W T5 fluorescent Ea 54


lamp cool white or daylight fluorescent light
fixture with clear prismatic and acrylic diffuser,
resistant to cleaning agents and disinfectants,
IP65 (Electronic ballast).

8.2 Same as above, but type EC lighting fixture Ea 91


with emergency battery back up of 3 hours for
2 lamps.

8.3 Type D lighting fixture, 4 x 28W T5 fluorescent Ea 388


lamp cool white or daylight, hygienic fluorescent
fixture with clear prismatic and acrylic diffuser,
resistant to cleaning agents and disinfectants,
IP65 (Electronic ballast).

8.4 Same as above, but type ED lighting fixture Ea 83


with emergency battery back up of 3 hours for
2 lamps.

8.5 Type F1 lighting fixture 2 x 35W, T5 fluorescent Ea 29


surface mounted luminaire with clear prismatic
acrylic diffuser moisture proof housing of
injection moulded in grey vandal resistant
polycarbonate, coil-rolled steel sheet reflector
painted with oven-dried white epoxy-polyster.

8.6 Same as above, but type F1E lighting fixture Ea 32


with emergency battery back up of 3 hours for
1 lamp.

8.7 Type F1 lighting fixture 2 x 35W, T5 fluorescent Ea 6


wall mounted luminaire with clear prismatic
acrylic diffuser moisture proof housing of
injection moulded in grey vandal resistant
polycarbonate, coil-rolled steel sheet reflector
painted with oven-dried white epoxy-polyster.

8.8 Same as above, but type F1E lighting fixture Ea 2


with emergency battery back up of 3 hours for
1 lamp.

8.9 Type F1P lighting fixture 2x35W, T5 fluorescent Ea 38


surface pendant mounted luminaire with clear
prismatic acrylic diffuser moisture proof housing
of injection moulded in grey vandal resistant

Page Sub-total

SFDA, Dammam Page 70


FACILITY : MAIN LABORATORY BUILDING

SECTION : ELECTRICAL WORK (Contd. . .)

S.No. Description Unit Qty Unit Rate Total Amount

polycarbonate, coil-rolled steel sheet reflector


painted with oven-dried white epoxy-polyster.

8.10 Same as above, but type F1PE lighting fixture Ea 16


with emergency battery back up of 3 hours for
1 lamp.

8.11 Type F3 lighting fixture 2 x 35W, T5 fluorescent Ea 2


surface mounted luminaire with clear prismatic
and acrylic diffuser moisture proof and
vaportight proof type housing of injection
moulded in grey vandal resistant polycarbonate,
coil-rolled steel sheet reflector IP65 protection
(WP), electronic ballast.

8.12 Same as above, but type F3E lighting fixture Ea 13


with emergency battery back up of 3 hours for
1 lamp, maintained.

8.13 Type DL1, recessed downlight fixture with Ea 73


1 x 26W compact fluorescent lamp and glass
diffuser, faceted reflector aluminized, highly
specular, iridescence free (IP 44).

8.14 Same as above, but type DL1E lighting fixture Ea 29


with emergency battery back-up of 3hours,
complete with control gear maintained.

8.15 Type DL2 lighting fixture, 1 x 100W, 12V, GY6.35 Ea 26


halogen lamp wide angle recessed down light,
dark light reflector aluminium, bright anozided
complete with control gear / LV transformer.

8.16 Same as above, but type DL2E lighting fixture Ea 4


with emergency battery back up of 3 hours for
duration, maintained.

8.17 Type DL3 lighting fixture, recessed downlight Ea 60


fixture with 2 x 32W compact fluorescent
TC-TEL horizontal lamp position, housing of
cast aluminium heat sink complete with glass
diffuser and control gear.

8.18 Same as above, but type DL3E lighting fixture Ea 27


with emergency battery back up of 3 hours
duration, maintained.

Page Sub-total

SFDA, Dammam Page 71


FACILITY : MAIN LABORATORY BUILDING

SECTION : ELECTRICAL WORK (Contd. . .)

S.No. Description Unit Qty Unit Rate Total Amount

8.19 Type DL4 lighting fixture, recessed downlight Ea 215


fixture with QT12ax, 50W, 12V, GY6.35 LV
Halogen lamp, darklight reflector, aluminum,
bright anodized glass, frosted complete with
LV transformer.

8.20 Type DL8 lighting fixture, 150 w , metal halide Ea 4


lamp surface mounted down light smooth
aluminum coated, highly specular ,
non- IRI descent , housing made of aluminum
(IP-64),electronic ballast.

8.21 18W fluorescent above mirror lighting fixture Ea 23


with opal sheet diffuser.

8.22 8W wall mounted exit sign lighting fixture with Ea 39


English / Arabic text and emergency battery
back up of 3 hours duration, maintained.

8.23 8W wall mounted fire exit sign lighting fixture Ea 11


with English / Arabic text and emergency battery
back up of 3 hours duration, non-maintained.

8.24 Type WL1E lighting fixture, 2 x 42W CFL wall Ea 17


mounted direct/indirect luminaire with die cast
aluminium body, IP40 and emergency battery
back up of 3 hours duration.

8.25 Type WL2 security flood light fixture, made of Ea 8


die cast aluminum pre-treated painted and
stove enameled in gray color with 250W, metal
halide lamp and control gear weatherproof type
(IP-65).

8.26 Type WL3 bulkhead light fixture made of die Ea 9


cast aluminum pre-treated painted and stove
enameled in gray colour with 250W, metal
halide lamp and control gear weatherproof type
(IP 65).

8.27 Type WL5 ,light fixture HCI-T 2×70 W Ea 8


metal halide lamp wall mounted , direct/
indirect luminaire with die cast aluminum body
(IP 65).

Page Sub-total

SFDA, Dammam Page 72


FACILITY : MAIN LABORATORY BUILDING

SECTION : ELECTRICAL WORK (Contd. . .)

S.No. Description Unit Qty Unit Rate Total Amount

8.28 8W wall mounted fire exit sign lighting fixture Ea 1


with English / Arabic text and emergency battery
back up of 3 hours duration, weatherprof type.

8.29 Concealed surface mounted light bare batten Ea 117


luminaire C/W TL'D 1 × 36 W colour 84
fluorescent lamp , control gear , etc . For
cove lighting

8.30 Concealed surface mounted light bare batten Ea 18


luminaire C/W TL'D 1 × 18 W colour 84
fluorescent lamp , control gear , etc . For
cove lighting

9.0 IP TELEPHONE / DATA SYSTEM :


Supply, installation, testing and commissioning
of IP Telephone / Data system including wiring,
conduiting, metal boxes, supports, grounding
and other materials and accessories to
complete the work as per drawings and
specifications.

9.1 IP Data outlet, duplex type Ea 206


equipped with 2-RJ45 wall mounted over
counter level with 2 data cable Cat 6A @ every
working station and with 1meter loose in every
working station and 3meter loose length @
Data cabinet.

9.2 IP-telephone and data outlet duplex type Ea 39


equipped with 2-RJ45 wall mounted @ 300mm
AFFL with 2 data cable Cat 6A @ every working
station and with 1meter loose in every working
station and 3meter loose length @ Data cabinet.

9.3 IP-telephone and data outlet duplex type Ea 53


equipped with 2-RJ45 wall mounted over
counter level with 2 data cable Cat 6A @ every
working station and with 1meter loose in every
working station and 3meter loose length @
Data cabinet.

9.4 IP telephony (IP-PABX) complete with core Set 1


switch, media gateway, signalling server etc.
as per drawing.

Page Sub-total

SFDA, Dammam Page 73


FACILITY : MAIN LABORATORY BUILDING

SECTION : ELECTRICAL WORK (Contd. . .)

S.No. Description Unit Qty Unit Rate Total Amount

9.5 Main distribution frame "SMDF" 200pairs + Set 1


protection complete with fiber optic termination
kit and patch.

9.6 Telecommunication closet "TC-GF" (42U) Ea 2


comprising of UTP patch panel data switch 1-48
port access switch 10 / 100 / 1000 panel (POE),
power over ethernet, voice patch panel
switches, fiber optic patch panel, 2-24 port RJ
45 patch panel complete with fan.

9.7 Telecommunication closet "TC-1F" (32U) Ea 1


comprising of UTP patch panel data switch 1-48
port access switch 10 / 100 / 1000 panel (POE),
power over ethernet, voice patch panel
switches, fiber optic patch panel, 2-24 port RJ
45 patch panel complete with fan.

9.8 Telecommunication closet "TC-2F" (32U) Ea 1


comprising of UTP patch panel data switch 2-48
port access switch 10 / 100 / 1000 panel (POE),
power over ethernet, voice patch panel
switches, fiber optic patch panel, 2-24 port RJ
45 patch panel complete with fan.

9.9 12 core fiber optic cable single mode. Lm 140

9.10 Telecommunication closet (42U) "Campus Ea 1


Distributor" comprising of UTP patch panel
data switch 3-48 port 10 / 100 / 1000 panel
(POE), power over ethernet, voice patch panel
switches, fiber optic patch panel, 24 port RJ45
patch panel complete with fan.

9.11 Server, as per latest technology and client Ea 1


requirements.

9.12 Wire less WIFI internet Router , complete with Ea 12


power supply , pull box , bracket & terminal
connectors

10.0 FIRE ALARM SYSTEM:


Supply, installation, testing and commissioning
of fire alarm system including wirings,
conduiting, boxes, grounding and all internal

Page Sub-total

SFDA, Dammam Page 74


FACILITY : MAIN LABORATORY BUILDING

SECTION : ELECTRICAL WORK (Contd. . .)

S.No. Description Unit Qty Unit Rate Total Amount

components as per drawings and


specification.

10.1 Intelligent Addressable Smoke Detector. Ea 107

10.2 Intelligent Addressable Heat Detector. Ea 80

10.3 Intelligent Addressable Heat Detector, wall Ea 2


mounted

10.4 Intelligent Addressable Manual call system. Ea 45

10.5 Intelligent Addressable Manual call system. Ea 1


weatherproof type

10.6 Intelligent Addressable Electronic Sounder. Ea 45

10.7 Intelligent Addressable Electronic Sounder. Ea 1


weatherproof type

10.8 Interface Unit (IFU) Ea 43

10.9 Intelligent Addressable Smoke Duct Detector. Ea 24

,10.10 Intelligent Fire Alarm Control Panel 8 Loop Ea 1


complete with battery & battery charger 48
Hours duration and suitable for IP connection.

10.11 Wiring, conduiting, termination and interfacing Lot 1


to sprinkler tamper switch and sprinkler flow
switch.

10.12 Interlock wiring from Elevator to FACP including Lot 1


conduiting.

10.13 Interlock wiring from AHU's / HRU's to FACP Lot 1


including conduiting.

10.14 Connection to Building Automation and Lot 1


Management Maintenance System

10.15 Mimic Board with Building Plans. Ea 1

11.0 AUDIO / VIDEO SYSTEM:

Page Sub-total

SFDA, Dammam Page 75


FACILITY : MAIN LABORATORY BUILDING

SECTION : ELECTRICAL WORK (Contd. . .)

S.No. Description Unit Qty Unit Rate Total Amount

Supply, installation, testing and commissioning


of Audio / Video system including wiring,
conduiting, metal boxes, supports, grounding
and other materials and accessories to
complete the work as per drawings.

11.1 Audio Video Equipment system for Meeting Set 1


Rooms complete with DVD-LD player, TV-RF
signal demodulator, matrix switcher, Audio
mixer (Character Generator), Audio processor
/ Control selector switch, digital amplifier
(200W per channel) including rack and
accessories.

11.2 Digital Video Projector motorized Lift (By Ea 1


remote control, 9000 lumens)

11.3 2500mm (H) x 4000mm (W) motorized front Ea 1


projection screen ceiling mounted complete with
mounting controls and accessories.

11.4 Front left speaker, 150W. Ea 1

11.5 Front right speaker, 150W. Ea 1

11.6 Microphone Receiver. Ea 1

11.7 Wireless Microphone. Ea 2

11.8 Stage microphone / Table microphone. Ea 2

11.9 Lavalier Microphone. Ea 1

12.0 MATV SYSTEM:


Supply, installation, testing and commissioning
of MATV system including wirings, conduiting,
boxes, grounding and all internal components
as per drawings and specifications.

12.1 TV socket twin outlet (Female). Ea 2

12.2 Distribution splitter box complete with Ea 1


accessories.

Page Sub-total

SFDA, Dammam Page 76


FACILITY : MAIN LABORATORY BUILDING

SECTION : ELECTRICAL WORK (Contd. . .)

S.No. Description Unit Qty Unit Rate Total Amount

13.0 CCTV SYSTEM:


Supply, installation, testing and commissioning
of CCTV system including wiring, conduiting,
cable tray, cable trunking and fixing of
accessories to complete the system as per
drawing and specification.

13.1 IP CCTV Dome camera (PTZ) type complete Ea 25


with coloured camera with lens.

13.2 IP CCTV coloured camera fixed type complete Ea 17


with camera with lens, weatherproof type.

13.3 IP CCTV Dome camera (PTZ) type complete Ea 1


with coloured camera with lens, weatherproof
type.

13.4 CCTV control panel complete with combined Set 1


multiplexer and digital video recorder.
1 - Matrix (48 Channel)
3 - DVR (16 Channel)
including keyboard, equipment console,
personal computer and other accessories as
per drawing.

13.5 21" CCTV colored LCD monitor Ea 3

14.0 SECURITY SYSTEM:


Supply, installation, testing and commissioning
of Security system including wiring, conduiting,
junction boxes, pull boxes, cable tray, cable
trunking and fixing of accessories to complete
the system as per drawing and specification.

14.1 Access Control Processor Control Panel Set 1


complete with personal computer, monitor &
software.

14.2 Card reader, proximity and biometric. Ea 82

14.3 Door release (DR) Ea 53

14.4 Door contact (DC) Ea 66

14.5 Electric Lock Ea 69

Page Sub-total

SFDA, Dammam Page 77


FACILITY : MAIN LABORATORY BUILDING

SECTION : ELECTRICAL WORK (Contd. . .)

S.No. Description Unit Qty Unit Rate Total Amount

14.6 Transfer Hinge Ea 67

14.7 Biometric Hand Punch Ea 2

14.8 Junction box complete with 1-13A, 250V, 2P+E Ea 67


switch socket outlet, British type + 1-Data outlet
RJ45.

15.0 CLOCK SYSTEM:


Supply, installation, testing and commissioning
of clock system including wiring, cabling,
conduiting, metal boxes, pull boxes, cable trays,
support hangers and all accessories required to
complete the works as per drawing and
specifications.

15.1 Wall mounted slave clock (min. 300mm dia.) Ea 52


single face.

15.2 Ceiling mounted slave clock (min. 300mm dia.) Ea 9


double face.

15.3 Master clock (300mm dia.) and Clock controller Set 1


with oscillator for clock system including wiring,
conduiting and all accessories.

16.0 PUBLIC ADDRESS SYSTEM :


Supply, installation, testing and commissioning
of public address system including wirings,
conduiting, boxes, grounding and all internal
components as per drawing and
specifications.

16.1 6W ceiling mounted speaker. Ea 44

16.2 Table microphone. Ea 2

16.3 Microphone Outlet Ea 1

16.4 Public Address Control panel consist of Set 1


amplifiers, mixers, control modules, tuner,
double cassette deck, DVD / CD / MP3 player
including 4 microphone inputs + 2 auxillary
inputs.

Page Sub-total

SFDA, Dammam Page 78


FACILITY : MAIN LABORATORY BUILDING

SECTION : ELECTRICAL WORK (Contd. . .)

S.No. Description Unit Qty Unit Rate Total Amount

17.0 GROUNDING AND LIGHTNING


PROTECTION SYSTEM:
Supply, installation, testing and commissioning
of grounding and lightning protection system
including copper rod, rebar jumper connections,
all accessories with the following materials as
per drawings and specification.

17.1 Copper Air Terminal 15mm dia x 500mm long. Ea 12

17.2 Ground Test Pit complete with 19mm dia x 3.0m Ea 16


copper clad steel rod.

17.3 25mm (w) x 3mm (thick) copper tape conductor Lm 275


connection from Air terminal to GTP.

17.4 25mm (w) x 3mm (thick) copper tape conductor Lm 350


complete with clip.

17.5 Loop grounding, 120sq.mm soft drawn bare Lm 270


copper

17.6 70 sq.mm Soft drawn bare copper bonded to Lm 70


structural rebars.

17.7 Ground Bar (GB), 6way with disconnect link. Ea 1

17.8 Telephone Ground Bar (TGB), 6way with Ea 1


disconnect link.

Page Sub-total

TOTAL ELECTRICAL WORK - Main Laboratory Building