Download as pdf or txt
Download as pdf or txt
You are on page 1of 28

• Lecture 10.

7: Composite Slabs
OBJECTIVE/SCOPE

To describe the design of one-way spanning composite slabs, formed using profiled steel
sheeting and a concrete topping, including consideration of ultimate and serviceability
limit state design according to Eurocode 4: Part 1 [1] for building structures.

PREREQUISITES

Lecture 9.1: Thin-walled Members and Sheeting

Lecture 10.1: Composite Construction - General

Lecture 10.6.1: Shear Connection I

RELATED LECTURES

All other lectures in Group 10.

RELATED WORKED EXAMPLES

Worked Example 10.4: Design of a Composite Slab

SUMMARY

Descriptions of composite slabs, typical profiled sheeting and means of ensuring


composite behaviour are given. Design criteria are identified in terms of loads, design
resistance and serviceability limits. Analysis of continuous slabs is based on elastic or
plastic theories. The resistances of critical cross-sections are calculated considering all
possible modes of failure. The design for the ultimate limit state design consists of
checking that slab resistance is sufficient to withstand maximum predicted forces; design
for the serviceability limit state is performed to limit concrete cracking and slab
deflections, taking into account creep and shrinkage of the concrete. The above methods
are illustrated by Worked Example 10.4.

• 1. INTRODUCTION
• 1.1 Definition

A composite slab consists of a cold-formed profiled steel sheet covered with a concrete
slab containing reinforcement (Figure 1). Such slabs are generally used in frame
structures, with steel floor beams, as discussed previously in Lecture 10.1. They can also
be used in combination with other materials.
In this type of construction the profiled sheet has several functions:

• it provides a working platform for construction.


• it acts as formwork for the concrete slab.
• it constitutes bottom reinforcement for the slab.

The present lecture is mainly concerned with composite slabs when the steel-concrete
bond has been formed, i.e. after hardening of the concrete. Design for the construction
stage, when the profiled steel sheet supports the weight of wet concrete, is only
considered briefly.

• 1.2 Types of Profiled Sheet

There are many types of profiled sheet used for the construction of composite slabs
(Figure 2). These types vary in form, rib depth, rib spacing, sheet size, style of lateral
over-lapping; in the methods of stiffening the flat elements of the profile; and in the
methods of mechanical connection which ensure bond between the steel sheet and
concrete slab.
The thickness of the sheets can vary from 0,75 mm to 1,5 mm but in normal practice it
lies between 0,75 and 1,0 mm.

The height of the profiled sheets can vary from 38 mm to 80 mm.


Whatever the particular requirements for a steel framed building, it is probable that they
can be met by using a profiled sheet from this range, as the typical criteria for sound
insulation, fire protection, maximum span and maximum load can easily be met.

• 1.3 Steel-Concrete Connection

The bond between the concrete slab and the profiled sheet must be capable of
transmitting longitudinal shear at the steel-concrete interface.

This connection can be made in one or more of the following ways, as shown in Figure 3
(which has been taken from Fig. 7.1 of Eurocode 4 [1]):

• by the re-entrant shape of the ribs creating bond by friction (Figure 3a,b).
• by embossments on the flanges or ribs of the sheet (Figure 3c).
• by anchorages situated at the ends of the slab, consisting of stud connectors
welded through the sheet (Figure 3d), shot-fired shear connectors (Figure 3e), or
by deformation of the ribs (Figure 3f).
• 2. DESIGN PRINCIPLES
• 2.1 Design Situations

When designing composite slabs two distinct structural states must be checked: firstly,
the temporary state of execution, when only the sheeting resists the applied loads;
secondly, the permanent state, after the concrete is bonded to the steel giving composite
action.

Relevant limit states and load cases are considered for both design situations.

a) Profiled sheeting as shuttering

Verifications at the ultimate limit state and the serviceability limit state are required,
with respect to the safety and serviceability of the profiled sheeting acting as formwork
for the wet concrete. The effects of any temporary props used during execution, must be
taken into account in this design situation.

b) Composite slabs

Verifications at the ultimate limit state and the serviceability limit state are required,
with respect to the safety and the serviceability of the composite slab after composite
behaviour has commenced and any props have been removed.

• 2.2 Actions

The loads and other actions to be considered, for the ultimate and serviceability limit
state, are given in the relevant Eurocodes.

For the situation where the profiled sheeting acts as formwork, the following loads
should be considered in the calculations, taking into account any propping effects:

• self-weight of the profiled sheeting.


• weight of the wet concrete.
• execution loads.
• temporary storage load, if applicable.

The execution loads represent the weight of the operatives, any loads due to placing the
concrete, and also take into account any impact or vibration likely to occur during
execution. In accordance with Eurocode 4 [1], a representative value of execution loads
(including any excess of concrete) can be taken to be 1,5kN/m2, distributed on an area
3m x 3m (or the span of the sheeting, if less) and 0,75kN/m2 on the remaining formwork
surface.

For the situation where the steel and the concrete act compositely, the loads acting on the
slab should comply with Eurocode 1 [2].
• self-weight of the slab (profiled sheeting and concrete)
• weight of floor finishes
• imposed loads

For the serviceability limit state, long duration values of the loads are required for the
calculation of deformations taking into account creep and shrinkage of the concrete.

• 2.3 Material Properties

Profiled sheeting

Steel used for the fabrication of profiled sheeting has a minimum nominal yield strength
of 220N/mm2. In general, however, composite slabs are fabricated from profiled steel
sheeting manufactured from galvanised steel of grades 280 to 350, according to
European Standard pr EN 10147 [3]. The respective nominal values of yield strength for
these steels are:

Steel grade 280 : fyb = 280 N/mm2

Steel grade 350 : fyb = 350 N/mm2

The characteristic yield strength fyap, is equal to the nominal yield strength of the basic
material fyb quoted above for calculating ultimate resistance.

Concrete

Concrete used for composite slabs can be made with normal or lightweight aggregate.

The most commonly used grades of concrete (grading according to Eurocode 2 [4]) are
given in Table 1, which also gives the following properties: characteristic cylinder 28
days compressive strength, fck; mean tensile strength, fctm, which is associated with the
shear strength Rd; and the secant modulus of elasticity, Ecm.

Reinforcement

All reinforcing steels used in composite slabs should conform to the requirements of
Eurocode 2 [4]. The types concerned are essentially ribbed bars and ribbed wires,
including welded mesh, fabricated from steels of classes of ductility A or B. Class A is
recommended for negative moment reinforcement and fire resistance reinforcement.

Characteristic values for the most commonly used reinforcing steels are given in Table
2.

• 2.4 Deflection Limits

a) Deflection during execution (construction stage)


During execution, deflection of the profiled sheeting under loads due to self-weight and
wet concrete, must not exceed a limiting value.

For example, Eurocode 4 [1], sets this limit at l/180 or 20 mm, where l is the span of the
sheeting between supports. In the case of propped profiled sheeting, props are
considered as supports. In situations where greater deflection can be tolerated,
calculation for the ultimate limit state should take into account the weight of additional
concrete due to the deflection (the "ponding" effect).

b) Deflection in the composite state (permanent state)

Deflections in the composite state must be limited, in order that the slab may fulfil its
intended function and that any other elements in contact with it (false ceilings, pipework,
screens, partitions) will not be damaged. Deflection limits should, therefore, be
considered relative to the use of the slab, the execution procedure and architectural
aspects (aesthetics).

The values recommended by Eurocode 3 [5], for floors and roofs in buildings, are as
follows:

max  l/250

(l is the span of the composite slab)

2  l/300

where

max is the total deflection of the floor or roof, including any pre-camber and any
variation of the deflection due to the permanent loads immediately after loading, and
including 2.

2 is the variation of the deflection due to variable loading acting on the slab plus any
time-dependent deformations due to the permanent loads.

If the composite slab supports brittle elements (cement floor finishes, non-flexible
partitions, etc), 2 must be limited to l/350.

• 2.5 Verification Conditions

Two verifications are necessary to ensure that safety and serviceability requirements are
met:

• verification at the ultimate limit states


• verification at the serviceability limit states

a) Verification conditions for the ultimate limit states


The resistance of the profiled sheeting (execution stage) or the composite slab
(permanent state) must be sufficient to resist the exterior loads. Each section or member
must be capable of resisting the internal forces determined by the analysis of the
structure.

When considering a limit state of rupture or excessive deformation, it shall be verified


that

Sd  Rd

where

Sd is the design value of load effects

Rd is the design value of the resistance

The load combinations required for design, and the calculation of their effects (moments,
shears, etc.) are not discussed in this lecture; for further information reference should be
made to the relevant Eurocodes or to National Codes.

Calculation of the resistance of critical sections of composite slabs is given in Section 4.

b) Verification conditions for the serviceability limit states

The behaviour of the profiled sheeting, under its self-weight and the weight of the wet
concrete, must fall within accepted limits.

The following verifications should be made:

• deflection within the permissible limit (appearance, ponding effect).


• marks on the sheet due to the temporary construction props should not be visible.

The behaviour of the composite slab under permanent loads and variable service loads
must fall within accepted limits.

The following states should be verified:

• Concrete cracking restricted to a limited width (corrosion of reinforcement,


appearance).
• Deflection, or variation of deflection, within the permissible limit (use of slab,
damage of non-structural elements, appearance, etc).
• Vibrations not exceeding a limiting value (this limit state is not treated in this
lecture).

• 3. BEHAVIOUR AND ANALYSIS


• 3.1 Behaviour of Profiled Sheeting
During execution when the concrete is wet, the profiled sheeting alone resists the
exterior loads. Its behaviour is then comparable to the behaviour of profiles used for roof
decking.

The profiled sheeting is subjected mainly to bending and shear; compression due to
bending may arise in either the flanges or the web; shear occurs essentially near the
supports. The thin-plate elements, which make up the profiled sheeting, may buckle
prior to yield under these compressive and shear stresses, thereby reducing the resistance
and stiffness of the sheeting.

Current design procedures rely on the concept of effective width, as described in Lecture
9.1, to provide a method for the calculation for this type of thin-walled member. Clearly,
the effective width of the compression flange depends upon the maximum stress
imposed on the flange, which in turn depends on the location of the neutral axis of the
cross-section. As the ineffective area of the flange increases under increasing bending
moment, the neutral axis of the profile is lowered and the extreme fibre stresses change
accordingly. Iterative design calculations, therefore, become necessary both for
resistance and deflection.

• 3.2 Behaviour of Composite Slabs

The behaviour of composite slabs is somewhat different from that of other similar forms
of composite construction, such as reinforced concrete slabs or composite beams of steel
and concrete. Composite action is achieved in reinforced concrete by the bond of the
concrete to the reinforcement due to the special profile of the bars used. This bond,
verified by tests, is the same as the ultimate resistance of the reinforcement in tension
assuming always that the slab can develop full resistance to bending. In composite
beams, composite action is achieved by connectors fixed to the top flange of the steel
beam. The design of these connectors may be based on the assumption that the beam
attains ultimate bending resistance (full connection). If the number of connectors is
smaller than that required for full connection then the connection is partial. In this case
the ultimate resistance to bending depends essentially on the number of connectors, the
slope of the load-slip diagram for the connectors, the span of the beam, and the method
of construction, i.e. execution.

The composite slab with profiled sheeting is half-way between these two systems. On
the one hand sheeting with embossments or anchorages is comparable to reinforcement,
whereas, on the other hand, sheeting is an element with bending rigidity similar to steel
beams. The difference results from the fact that profiled sheeting, and similarly the
embossments, can be deformed under load. Also, unlike reinforcement, profiled sheeting
does not benefit from being totally embedded in concrete. The numerous parameters
involved, therefore, make the analysis of the actual behaviour of composite slabs very
complicated.

Recent theoretical and experimental studies have identified different parameters and
revealed two behaviour modes. These modes are based on the analysis of load-deflection
curves which can be obtained, for example, when bending tests are performed on
composite slabs on two supports subjected to two concentrated loads (Figure 4).

Mode 1

The characteristic of this mode is an initial linear curve, as in Figure 5, which


corresponds to the behaviour of a homogeneous material held together by surface effects
(chemical bond and friction) and mechanical effects (embossments and anchorages). No
significant relative slip between the steel and the concrete takes place; as the load
increases, the rigidity decreases because of the cracks which form in the concrete in
tension. Shear stresses between the steel and concrete increase in the zone between the
concentrated load and the support. At a certain point the relative slip is such that the
bond is broken and the load suddenly decreases. All the shear force must therefore be
taken up by friction and by any embossments; the amount of load decrease is therefore
dependent on the quality of the mechanical bond. With further deformation of the slab
the load increases again slightly without ever reaching the level of the initial phase. This
means that the mechanical bond is incapable of achieving a composite effect superior to
that of simple surface bond. It should be noted that the decrease in the load is not due to
the sudden opening of tension cracks in the concrete, because this is prevented by the
sheeting, but by relative slip between the concrete and the sheeting.

Mode 2

This mode is characterised by an initial phase similar to that of mode 1. However, the
second phase is different: after a decrease in load, corresponding to failure of the steel-
concrete bond in the sheared zone, the load increases again up to a higher level. This
increase shows that the mechanical connection is capable of transferring the shear force
until failure occurs by bending, corresponding to full shear connection, or by
longitudinal shear, corresponding to partial shear connection.

The two modes described above represent brittle (or non-ductile) behaviour (mode1),
and ductile behaviour (mode 2), see Figure 5.

• 3.3 Analysis of Composite Slabs

The analysis of a composite slab may be made in accordance with one of the following
methods:

• linear elastic.
• linear elastic with moment redistribution.
• plastic according to the theory of plastic hinges.
• a higher order analysis which takes into account non-linear material behaviour
and slip between the profiled sheeting and the concrete slab.

a) Analysis for the ultimate limit states

In most cases analysis of composite slabs, continuous over several spans, is performed
according to the elastic method, for a slab of unit width (1m), comparable to a beam of
constant inertia (Figure 6, line (1)). The assumed inertia is that of the uncracked section.

It is possible to take concrete cracking into account in several ways:


• Arbitrarily reduce the moment at the supports (maximum reduction 30%) and
consequently increase the span moments (Figure 6, line (2)).
• Totally neglect reinforcement over the supports and consider the slab as a series
of simply supported beams (Figure 6, line (3)). Minimum reinforcement must
always be placed over intermediate supports for serviceability reasons.
• Consider that the slab is a beam with variable inertia, depending on the
reinforcement. The assumed inertia is that of the cracked section.

The analysis will use one of the above statical models in conjunction with the design
loads determined, as discussed earlier in Section 2.2.

Worked Example 10.4 illustrates how the actual stresses and strains are determined and
how the internal forces and moments (M, N, V) are calculated for the structural system
chosen.

b) Analysis for the serviceability limit states

An analysis of the composite slab, for calculating deflection, may be made with the
following assumptions:

• The slab is comparable to a continuous beam of constant inertia, equal in value to


the average inertia of the cracked and uncracked section.
• Long-term loading effects on the concrete are taken into account using a variation
in the modular ratio Ea/Ec. For simplification, Eurocode 4 recommends an average
value of Ea/Ec for both long and short term effects.

Possible slip between the profiled sheeting and concrete slab must be taken into account
at the serviceability limit states. Slip may occur in the span and greatly influence
deflection. It is necessary, therefore, to fully understand the behaviour of composite
slabs through approved testing.

To eliminate excessive slip it is possible to place anchorages, for example welded studs
or shot-fired connectors, at the ends of the spans (see Figure 3d and e).

• 4. RESISTANCES OF SECTIONS
According to Section 3, the critical sections which should be verified, are as follows
(Figure 7):

• Section I : ultimate moment of resistance failure for positive bending.


• Section II : ultimate moment of resistance failure for negative bending.
• Section III-IV : ultimate resistance to vertical shear failure.
• Section V : ultimate resistance to longitudinal shear failure.

• 4.1 Positive Bending Resistance

The ultimate moment of resistance of a section, Mpc, may be determined by assuming a


plastic distribution of stresses (Figure 8). For an under-reinforced* section, the position
of the plastic neutral axis is given by:

x = [Aap.fyap/ap]/[b.0,85fck/c] (1)

where:

Aap is the area of the profiled sheet section.

fyap is the characteristic yield strength of the sheet steel.

ap is the partial safety factor for steel sheeting.

b is the width of the slab (b = 1000 mm).

fck is the characteristic compressive strength of the concrete.

c is the partial safety factor for concrete.


If the neutral axis is situated above the profiles of the sheeting (x  hc) the design
positive bending resistance has the value:

M+p,Rd = Aap.fyap[dc - x/2]/ap (2)

All commonly used profiled sheeting (ha  60 mm), in conjunction with a concrete slab
of minimum thickness hc = 50 mm, have a plastic neutral axis situated above the
profiles. For deeper sheets, the neutral axis may be situated within the height of the
profiled sheeting.

In this case, the positive bending resistance of a section may be calculated as follows, by
neglecting the concrete in the troughs (Figure 9):

M+p,Rd = Mcz + Mpa,r


+ (3)

z = ht - dc/2 - ep + (ep - e)Nc/[Aap.fyap/ap]


+ (4)

Nc = hc.0,85fck/c (5)

Mpa,r = 1,25Mpa [1 - Nc/(Aap.fyap/ap)]  Mpa (6)

where

e is the distance from the centroid of the effective area of the sheeting to its underside.

ep is the distance from the plastic neutral axis of the effective area of sheeting to its
underside.
Mpa is the plastic moment resistance of the effective cross-section of the sheeting.


• 4.2 Negative Bending Resistance

The section of a continuous composite slab at a support can be compared to a reinforced


concrete section. As a simplification, the contribution of the profiled sheet is neglected.
The design section and the distribution of stresses at the ultimate limit state are shown in
Figure 10.

The design negative bending resistance is given by yielding of the reinforcement at the
support (under-reinforced slab):

M+p,Rd = As.fysz-/s (7)

where
As is the area of reinforcement

fys is the yield strength of the reinforcement

s is the partial safety factor for the reinforcement

z- is the lever-arm of the internal forces Nc and Nt.

The condition of equilibrium between these forces allows the determination of z-:

Nc- = bcx0,85fck/c= As.fys/s= Nt- (8)

x = [As.fys/s][bc0,85fck/c] (9)

= ds - x/2 (10)

where

bc is the width of the concrete in compression, taken as the width of the troughs over 1m
for simplicity (bc = bo).

ds is the effective depth

• 4.3 Vertical and Punching Shear Resistance

In general the vertical and the punching shear resistances are assumed to be given by the
concrete section since the contribution of the steel sheeting is neglected.

The vertical shear design resistance, over a width equal to the distance between centres
of ribs has the value:

Vv,Rd = bo ds c (11)

where

c is the limiting shear stress appropriate for composite slabs (c included).

c = Rd k1 k2

where

k1 = 1,6 - ds  1,0 (ds in m)

k2 = 1,2 + 40 po

o = As/bo ds < 0,02


As is the area of reinforcement in tension provided in order to distribute cracking. In
positive bending regions, As is to be replaced by Aap.

Rd is the basic shear strength (see Table 1).

The punching shear resistance Vp,Rd of a composite slab at a concentrated load should be
determined from:

Vp,Rd = Cp hc c (12)

where

Cp is the critical perimeter determined as shown in Figure 11.

hc is the thickness of the concrete slab (above the ribs).

c is the limiting shear stress given above.

• 4.4 Longitudinal Shear Resistance


Resistance to longitudinal shear in composite slabs is due to the steel-concrete bond at
the interface of these two materials, established by friction, embossments or connectors
placed at the ends of the spans (see Section 3). The ultimate resistance of these
connections can only be determined by testing, as described in Section 10.3 of Eurocode
4 [1].

a) Empirical "m-k" method

The most commonly used method for calculating ultimate longitudinal shear was
developed in the United States [6]. This method is used in many codes of practice,
including Eurocode 4. It is based on at least six tests of simply supported composite
slabs, which determine two coefficients m and k (see Figure 12), for the test profile.

The longitudinal shear resistance of a composite slab, consisting of the same type of
profiled sheet as that tested, is then given by the following maximum design vertical
shear:

Vl,Rd = bds[(mAsp/bls) + k]/vs (13)

where

ls is the shear span.

vs is the appropriate partial safety factor for longitudinal shear only.

For a uniformly loaded slab, ls = l/4; for simply supported beams, l is the span, whereas
for continuous beams l is the equivalent simple span between points of contraflexure; for
end spans, the full exterior span length is used in design (see Figure 13 which has been
taken from Fig. 7.10 of Eurocode 4 [1]).
If the connection provided by friction (due to the rib shape) or by embossments is not
sufficient, it is possible to place anchorages (generally steel-concrete connectors) at the
ends of the span.

The ultimate resistance of such anchorages is generally governed by the pull-out


resistance of the sheet. For a stud, this resistance is given by the following expression:

Nt,ap = k3 dw t fyap/ap (14)

k3 = 1 + a/dw  4,0

where

dw is the diameter of weld around the stud.

a is the distance between the axis of the stud and the extremity of the profiled sheet
(a  2dw).

b) Partial shear connection method

The fact that composite slabs fail by longitudinal shear in most cases, allows this
structural system to be compared to a composite steel beam and concrete slab with
partial shear connection. It is also possible to represent the resistance of such slabs by a
diagram giving MSd/MRd as a function of Nc/Ncf. This diagram is different to that given
for composite beams due to the fact that the degree of partial shear connection N c/Ncf is
not a function of the number of connectors, but of the shear length ls and of the
distribution of longitudinal shear stresses  over this length. The relative slip s between
the profiled sheeting and the concrete also plays a more important role.

The determination of such diagrams for design is therefore complicated since one of the
following is necessary:

a) non-linear analysis of the resistance and behaviour of slabs combined with shear tests
on specimens representative of the connection.

b) many tests of composite slabs, with measurements taken of the normal force N c,
transferred over the shear length.

Studies are being undertaken at present to try to establish a simplified method based on
scientific research. Eurocode 4 [1] gives such an alternative method in Appendix E,
based on research conducted recently in Germany. This alternative method will not be
described further in this lecture.

• 4.5 Elastic Properties of Cross-sections

The deflection of a composite slab is calculated using elastic theory.

a) Cracked section

The second moment of area Ibc of the cracked section can be obtained from:

Ivc = [bx3/3n] + Aap(ds - x)2 + Iap (20)

where x is the position of the elastic neutral axis:

x = [nAap/b]{[1 + (2bds/nAap)] - 1} (21)

where

Iap is the unreduced second moment of area of the sheet based upon the net sheet
thickness

b) Uncracked section

The second moment of area Ibu of the uncracked section can be obtained from:

Ibu =

(22)
where

bc is the total average rib width over a slab width of 1 m.

xu is the position of the elastic neutral axis:

xu = (23)

• 5. VERIFICATIONS
This lecture has given a brief introduction to composite slabs constructed with profiled
steel sheeting. The basic design principles have been given, which allow a schematic
structural arrangement and statical system to be determined. The procedure for analysing
the slab under the external loads to find the internal stresses and strains has then been
considered. Now, various verifications are necessary to show that structural safety
(resistance, stability) and serviceability (deflection, vibration) requirements are met.

• 5.1 Verification of the Ultimate Limit States

For composite slabs, this check generally consists of showing that the design internal
shear forces and moments at critical sections are smaller than the design resistances of
the cross-sections.

a) Positive bending (Section 4.1 and Section I of Figure 7)

This check is made at the section of maximum positive moment, generally in the
external span of a continuous slab. The condition can be expressed as:

(24)

where

is the design value of the bending moment.

is the design value of the positive bending resistance.

b) Negative bending (Section 4.2 and Section II of Figure 7)

The negative moment, at the supports, is checked (see Section 3).

The condition can be expressed as:

(25)
where

is the design value of the negative bending moment.

is the design value of the negative bending resistance.

c) Vertical shear (Section 4.3 and Sections III or IV of Figure 7)

This check is rarely critical; however, it may be critical in the case of deep slabs with
loads of relatively large magnitude. This condition may occur at end supports where the
bending moment is zero, or at intermediate supports; in the latter case, no interaction
between M and V is assumed. The condition is expressed as:

VSd  Vv,Rd (26)

where

VSd is the design value of the vertical shear.

Vv,Rd is the design value of the vertical shear resistance.

d) Longitudinal shear (Section 4.4 and Section V of Figure 7)

This check is often the determining factor for composite slabs with profiled sheeting but
no anchorage. It implies that overall failure of the slab occurs by failure of the shear
bond. The bending resistance at section I cannot then be attained.

If the empirical "m-k" method is used, the condition can be expressed as:

VSd  Vl,Rd (27)

where

VSd is the design value of the vertical shear (equivalent span, see Figure 13).

VlRd Is the design value of the shear resistance.

• 5.2 Verification of the Serviceability Limit State

The following verifications should be made concerning the serviceability of the


composite slab:

a) Deformations

Vertical deflections must not exceed the limiting values (see Section 2.4b).
If the slenderness (span/effective depth) of the slab does not exceed the limiting values
given in Eurocode 2 [4], this deflection check is not essential. For one way continuous
slabs, with lightly stressed concrete, the limit is:

(28)

b) Crack width

Given that there is a profiled sheet on the lower surface of the concrete slab, only
concrete cracking at the supports must be verified. Such verifications should be made
according to the established rules for reinforced concrete, given in Eurocode 2 [4].

In normal circumstances when, for example, the slab is designed as a series of simply
supported beams, minimum reinforcement placed at the supports is sufficient. Normal
circumstances are: no exposure to aggressive physical or chemical environments; no
damage other than cracking; no requirements regarding water proofing of the slab; and
no special requirements regarding appearance.

The amount of minimum reinforcement is given by the following:

• for slabs propped at the time of concreting:

min = (29)

• for slabs unpropped at the time of concreting:

min = 0,2% (30)

• 6. CONCLUDING SUMMARY
• The design of a composite slab must consider the performance of the profiled
steel sheeting, when it acts as shuttering for the wet concrete during execution, as
well as the composite performance of the steel and hardened concrete under the
imposed floor loading.
• At the execution stage, the profiled steel sheeting acts as a thin-walled member.
Its design must take into account the possibility of local buckling.
• The design of the composite slab must consider the resistance to positive and
negative moments and also to vertical and longitudinal shear.
• The resistance to longitudinal shear at the steel/concrete interface is largely
derived from embossments in the steel sheet or from connectors placed at the ends
of the spans. Empirical methods are used to ensure adequate shear resistance.

• 7. REFERENCES
[1] Eurocode 4: "Design of Composite Steel and Concrete Structures": ENV 1994-1-1:
Part 1.1: General rules and rules form buildings, CEN (in press).

[2] Eurocode 1: "Basis of Design and Actions on Structures", CEN (in preparation).

[3] prEN 10147, "Continuous Hot Dip Zinc Coated Carbon Steel Sheet of Structural
Quality", European Standard, 1979.

[4] Eurocode 2: "Design of Concrete Structures": ENV 1992-1-1: Part 1.1: General rules
and rules form buildings, CEN, 1992.

[5] Eurocode 3: "Design of Steel Structures": ENV 1993-1-1: Part 1.1: General rules and
rules form buildings, CEN, 1992.

[6] Porter, M L and Eckberg, C E Jr, "Design Recommendations for Steel Deck Floor
Slabs", ASCE Journal of the Structural Division, New York, Vol. 102, no 11, 1976,
pp2121-2136.

• 8. ADDITIONAL READING
1. Patrick, M, "A New Partial Shear Connection Strength Model for Composite
Slabs", The Broken Hill Proprietary Company Limited, Melbourne Research
Laboratories, Report MRL/PS64/90/016, Mulgrave, Victoria, Australia, March
1990.
2. Daniels, B, "Behaviour and Load Carrying Capacity of Composite Slabs:
Mathematical Modelling and Experimental Studies", Doctoral thesis No 895,
Ecole polytechnique fédérale de Lausanne, ICOM-Construction métallique,
Lausanne, 1990.

Concrete grade C20/25 C25/30 C30/37 C35/45


fck [N/mm2] 20 25 30 35
fctm [N/mm2] 2,2 2,6 2,9 3,2
Rd [N/mm2] 0,26 0,30 0,34 0,37
Ecm [kN/mm2] 29 30,5 32 33,5

Table 1: Concrete grades and associated properties used for composite slabs

Steel grade S 500 S 550

(ribbed bars) (welded mesh)


fsk [N/mm2] 500 550
ftk [N/mm2] 550-600 580
(ft /fsk)k (minimum) 1,1 1,05
Es [kN/mm2] 210 210

Table 2 Reinforcing steel grades and associated properties

You might also like