Download as xlsx, pdf, or txt
Download as xlsx, pdf, or txt
You are on page 1of 2

CALCULATION SIZING CABLE ELECTRICAL FOR FIRE PUMP

PROJECT : PT. SOFTEX INDONESIA


LOCATION : SIDOARJO
DOC. NO. :

NYY 4C - 95 mm2 NYY 3C - 35 mm2


NYY 3C - ELECTRIC
Electric Pump Panel 35 mm2 FIRE PUMP
NYA 1C - 50 mm2 NYA 1C - 16 mm2 MOTOR

NYAF 4x(1C - 4mm2)

NYYHY 4C - 4 mm2
FRC 4C - 120 mm2 NYYHY 4C - 1.5 mm2
FIRE PUMP Diesel
DISTRIBUTION Pump Diesel Engine
MDP NYY 3C - 2.5 mm2 NYYHY 2C - 1.5 mm2
Local Panel
E = BC 1C - 50 mm2 PANEL Panel NYYHY 4C - 1.5 mm2 Battery

NYY 4C - 2.5 mm2


Jockey NYY 3C - 2.5 mm2
NYA 1C - 1.5 mm2 Pump NYA 1C - 1.5 mm2 JP Electric
Panel Motor

Required Cables :
No Cable From To Cable Size Notes
A Power Distribution
1 Main Power MDP Fire Pump Distribution Panel NYY 4C - 120 mm2
2 Earthing MDP Fire Pump Distribution Panel BC 1C - 50 mm2
B Electric Fire Pump (EFP)
1 EFP Panel Power Fire Pump Distribution Panel Electric Pump Panel NYY 4C - 95 mm2
2 Earthing Panel Fire Pump Distribution Panel Electric Pump Panel NYA 1C - 50 mm2
3 Line Motor A Electric Pump Panel EFP Motor NYY 3C - 35 mm2
4 Line Motor B Electric Pump Panel EFP Motor NYY 3C - 35 mm2
5 Earthing Motor Electric Pump Panel EFP Motor NYA 1C - 16 mm2 Warna Kuning Strip Hijau
C Diesel Fire Pump (DFP)
1 DFP Panel Power Fire Pump Distribution Panel Diesel Pump Panel NYY 3C - 2.5 mm2
2 Battery Charger Diesel Pump Panel Diesel Engine Local Panel NYYHY 4C - 4 mm2
3 Overspeed + Low Oil Protection Diesel Pump Panel Diesel Engine Local Panel NYYHY 4C - 1.5 mm2
4 High Temperature Diesel Pump Panel Diesel Engine Local Panel NYYHY 2C - 1.5 mm2
5 Starter 1 & Starter 2 (Crank) Diesel Pump Panel Diesel Engine Local Panel NYYHY 4C - 1.5 mm2
6 To Battery Diesel Engine Local Panel Battery NYAF 4x(1C- 4 mm2) 2 Core Red & 2 Core Black
D Jockey Pump (JP) DOL STARTER
1 JP Panel Power Fire Pump Distribution Panel Jockey Pump Panel NYY 4C - 2.5 mm2
2 Earthing Panel Fire Pump Distribution Panel Jockey Pump Panel NYA 1C - 1.5 mm2 Warna Kuning Strip Hijau
3 Line Motor Jockey Pump Panel JP Motor NYY 3C - 2.5 mm2
4 Earthing Motor Jockey Pump Panel JP Motor NYA 1C - 1.5 mm2 Warna Kuning Strip Hijau

ATTACHMENT :

ELECTRIC FIRE PUMP Type : EVMSG 5 -17/4


HSC Flow : 25 USGPM
Model : 150 x 125 CN2HA 5 185 (SP)(GP) Head : 120 m
Flow : 1250 USGPM = 284 m3/h Electric Motor : 4 kW/380V/50Hz/TEFC/3PH/3000 Rpm
Head : 110 m Material pump : AISI 304 SS with Cast Iron Base Pump Material
Electric Motor : Teco 185 kW/380V/50Hz/3000 rpm

FULL LOAD CALCULATION CURRENT CAPACITY CALCULATION

P
I = Icc = I x 0.577
√3 x V x Cos j

Description : Icc = Current Capacity


V= 380 V
Cos j = 0.8 Calculation ICC Vol.
P (Electrical Motor) 90 kW Electrical Motor 113.42 Ampere
P (Diesel Engine) 90 kW Jockey Motor - Ampere
P (Jockey Motor) 4 kW

Calculation (Full Load) + SF 15% I Vol. GROUNDING CABLE CALCULATION


Electric Panel 196.56 Ampere
Diesel Panel 6.00 Ampere Description Cross Sect (mm2) 30% (mm2)
Jockey Panel 8.74 Ampere Elec. Cable (Full Load) 95 35 28.5
total Load 211.30 Ampere Elec. Cable (Star Delta) 35 16 10.5
MDP Cable (Full Load) 120 50 36
Full Load capacity for jockey panel &
jockey pump is 8,74 A, so Cable From
MDP to jockey Panel and Jockey panel
to jockey Motor
use 3x2.5mm2

Current capacity for electrical pump is


113,42 A, so Cable From Electric Pump
Panel to Electric Motor use 3x35 mm2,
and Full Load capacity for Electric Pump
panel is 196,56
A, so cable from MDP to electric pump
panel use
4x95mm2

Total Load capacity for Power Source


existing is 418,79 A, so Cable From power
source to MDP use 4x240 mm2

Prepared By : Checked By : Checked By : Approved By : Approved By :

Sonny Hari Wijaya Akbar Dirgantara Yosef.S Ferdy.D .........