1000V DC-DC Conveter Datasheet Modified

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 7

SuryaLog SLHVXXXX/XXWX-L

DC-DC Converter

High voltage DC-DC Converter with maximum efficiency and wide input-output voltage range (100 / 200
VDC to 1000 VDC).

FEATURES:-
 Specifically designed for renewable energy applications.
 Wide Input voltage range: 100 / 200 VDC to 1000VDC
 Industrial grade operating temperature: - 10ºC to +80ºC
 Higher isolation voltage up to 4.5KVAC
 Highest efficiency in its class up to 90%.
 Low ripple, Low noise.
 Inbuilt protections like Reverse input voltage protection, Output short circuit, Over–voltage protection.
 High reliability and long life.
 RoHS, CE Approvals.
 Mounting: PCB Mounting, Din-Rail mounting.
 Add on features (Advance mode)-
1. Selectable input voltage range
2. Current limiting
3. Flicker free (during low radiation)
4. Starting Delay Adjustment

Website: - www.suryalog.com Email: info@suryalog.com/sales@suryalog.com office: - +91-9527818443 Support: +91-9022928497

Page 1 of 7
SuryaLog SLHVXXXX/XXWX-L
DC-DC Converter

SLHV series of DC-DC regulated converters is specifically designed for PV and Renewable applications to cater the
most variable input voltage range of 100 / 200 -1000VDC with highest efficiency in its class and are most reliable
under variable environmental conditions. It can be used in variety of application like SCB (String Combiner Box),
Solar Water Pump, Solar Tracker, High Voltage Inverter and many more to achieve stable and reliable output
voltage.

Selection Guide: 15W


Nominal Output Efficiency (%), Max.
Output
Model Voltage and 500VDC,Typical, Resistive Certifications
Power
Current(Vo/Io) with Load Load(Ω)
SLHV0124/15WX-L 24V/0.625A 80.71 38.4
SLHV0115/15WX-L 15V/1A 76.57 15
15W CE,ROHS
SLHV0112/15WX-L 12V/1.25A 73.05 9.6

Model wise efficiency : 15W


Model Input voltage Load(A) Efficiency (%)
200VDC 0.625 79.85
SLHV0124/15WX-L 600VDC 0.625 79.1
1000VDC 0.625 77.33
200VDC 0.99 73.27
SLHV0115/15WX-L 600VDC 0.99 75.27
1000VDC 0.99 68.54
164VDC 1.27 68.38
SLHV0112/15WX-L 600VDC 1.27 72.56
1000VDC 1.27 65.62
External Input Fuse SLHV01XX/15WX-L Necessary 1A

Physical Specifications: 15W


Casing Material Black flame-retardant and heat-resistant plastic.

Dimensions PCB Mounting 8mmx52mmx25mm


(L X W X H)

Din-Rail Mounting 93mmx60mmx37mm

Weight PCB Mounting 150g (Typ.)

Din-Rail Mounting 190g (Typ.)

Cooling Method Free Air Convection

Website: - www.suryalog.com Email: info@suryalog.com/sales@suryalog.com office: - +91-9527818443 Support: +91-9022928497

Page 2 of 7
SuryaLog SLHVXXXX/XXWX-L
DC-DC Converter

Selection Guide: 30W


Nominal Output Efficiency(%) Max.
Output
Model Voltage and 500VDC,Typical, Resistive Certifications
Power
Current(Vo/Io) with Load Load(Ω)

SLHV0124/30WX-L 24V/1.25A 30W 87.65 19 CE,ROHS

Model wise efficiency : 30W


Model Input voltage Load(A) Efficiency (%)
200VDC 1.25 86.89
SLHV0124/30WX-L 600VDC 1.25 86.00
1000VDC 1.25 78.34
External Input Fuse SLHV01XX/30WX-L Necessary 1A

Physical Specifications: 30W


Casing Material Black flame-retardant and heat-resistant plastic.

Dimensions Din-Rail Mounting 128mmx67mmx40mm


(L x W x H)
Weight Din-Rail Mounting 150g (Typ.)
Cooling Method Free Air Convection

Model wise efficiency : 40W


Nominal Output Efficiency(%) Max.
Output
Model Voltage and 500VDC,Typical, Resistive Certifications
Power
Current(Vo/Io) with Load Load(Ω)
SLHV0124/40WX-L 24V/1.66 A 40W 89.71 14 CE,ROHS

Input Specifications: 40W


Model Input voltage Load(A) Efficiency (%)
300VDC 1.76 81.99
SLHV0124/40WX-L 600VDC 1.76 89.19
1000VDC 1.76 81.36
External Input Fuse SLHV01XX/40WX-L Necessary 1A

Physical Specifications: 40W


Casing Material Black flame-retardant and heat-resistant plastic.
Dimensions Din-Rail Mounting 128mmx67mmx40mm
(L x W x H)
Weight Din-Rail Mounting 150g (Typ.)
Cooling Method Free Air Convection
Website: - www.suryalog.com Email: info@suryalog.com/sales@suryalog.com office: - +91-9527818443 Support: +91-9022928497

Page 3 of 7
SuryaLog SLHVXXXX/XXWX-L
DC-DC Converter

General Specifications: For Complete range


Parameter Operating Conditions Min. Max. Unit
Operating -10 80 °C
Temperature
°C
Storage Temperature -10 85 °C
Storage Humidity -- 95* %RH
Wave-Soldering 260°C, ±5°C ; time:5~10s
Soldering
Temperature Manual- Soldering 360°C , ±10°C ; time:3~5s

Switching Frequency 63 70 kHz


Power Derating 50 °C to SLHVXXXX/XXWX-L 1.5 % / °C
+60°C --

Specifications: For Complete Range

Parameter Operating Conditions Min Typical Max Unit


Input Voltage Accuracy ±1.3 ±.0.5 ±1.4 %
Output Voltage Accuracy ±1 ±.0.5 ±1 %
Line Regulation ±1 ±0.4 ±1 %
Load Regulation ±1 ±0.4 ±1 %
20MHz Bandwidth (peak-
Ripple & Noise* 50 100 200 mV
peak value)
Temperature Drift Coefficient
±0.01 % / °C

Short Circuit Protection Continuous, self-recovery


Over-Current Protection ≥110%
SLHV0124/XXWX-L ≤27VDC
Over-Voltage Protection SLHV0115/XXWX-L ≤18VDC
SLHV0112/XXWX-L ≤15VDC
Min. Load 60 70 80 mA
Delay Time 100V-1000V 1 2 3 Sec
Overload recovery time 4 5 10 Sec
Short circuit recovery time 4 5 10 Sec

Website: - www.suryalog.com Email: info@suryalog.com/sales@suryalog.com office: - +91-9527818443 Support: +91-9022928497

Page 4 of 7
SuryaLog SLHVXXXX/XXWX-L
DC-DC Converter

Product Characteristic Curve: For Complete range

.
Fig.1
NOTE:-
SLHVXXXX/XXWX-L Series, derating curve is line.
This product is suitable for use in natural air cooling environments, if in a closed environment; please contact our company’s FAE.

Fig. 2
Note: The actual output power = Nominal output power × Temperature derating × Input voltage derating.

Note: - Above all graph valid for typical range.

Fig. 3 Fig.4

Website: - www.suryalog.com Email: info@suryalog.com/sales@suryalog.com office: - +91-9527818443 Support: +91-9022928497

Page 5 of 7
SuryaLog SLHVXXXX/XXWX-L
DC-DC Converter

Mounting Dimensions:

Fig. 5

Fig.6

Fig. 7

Website: - www.suryalog.com Email: info@suryalog.com/sales@suryalog.com office: - +91-9527818443 Support: +91-9022928497

Page 6 of 7
SuryaLog SLHVXXXX/XXWX-L
DC-DC Converter

*Additional feature of advance*version:

1. Flexible starting voltage (i.e. 100V, 200V etc.).


2. Starting delay adjustment possible (50 sec to 300 sec).
3. Flicker free- Load/Health monitoring of I/P string, which avoids repeated switching ‘ON’ & ‘OFF’ during low radiation
(define the load power at the time of ordering) S/W ‘ON’ load only if I/P string health is ‘ok’.
4. Cc/cv mode for battery charging (on demand).

Note:
 Unless otherwise specified, parameters in this datasheet were measured under the conditions of Ta=25 ℃, humidity<75% with
nominal Input voltage and rated output load.
 All index testing methods in this datasheet are based on our Company’s corporate standards.
 We can provide product customization service, please contact our technicians directly for specific information.
 Any specifications mentioned and or not mentioned in the documents and datasheets are subject to change without prior notice.

Website: - www.suryalog.com Email: info@suryalog.com/sales@suryalog.com office: - +91-9527818443 Support: +91-9022928497

Page 7 of 7