SCHEDULE FOR SUMP PUMP

SL:NO FLOW RATE (l/s) HEAD (Bar) QTY Remarks PURPOSE


1 5 2.5 1 set (1 Duty+1 Standby) SUMP PUMP
SUMP PIT CAPACITY
SUMP PUMP(UG TO GF LOW LEVEL) - B-CREST, JVC Under Ground Domestic water tank capacity= 38,050.00 Imp.Gal
Under Ground Fire water capacity= 50,000.00 Imp.Gal
Flow rate & Pipe Sizing Under Ground water tank volume(Domestic+Fire)= 88,050.00 Imp.Gal
TOTAL VOLUME (CU.M) 400 Cu.m
= Sump pump@UG,Assume Half of the tank will drain within 12 hrs 16.68 Cu.m/hr
Total tank capacity 4.05 M³
Sump pump@UG,Assume Half of the tank will drain within 12 hrs 277.97 l/m
Required flow rate = 4.63 l/s Sump pump@B2,Assume Half of the tank will drain within 12 hrs 4.63 l/s
Required flow rate = 73 Us.gpm As per approved structural & mep -Sumpit size(1.5m(w)*1.5m(l)*1.9m(h)+0.2(f.b)
volume of water sump pit can hold 4.27 Cu.m
Pump head calculation volume of water sump pit can hold 4,270.00 l
Pressure loss in the pipe & fittings = 1.4 m H₂0 The Sump pit can hold the drain water for 10 min approximately 15 min
Pressure considered at discharge valve 5.0 m H₂0
Total head = 6.4 m H₂0
Safety factor 15.0 % = 1.0 m H₂0
Static head = 1.2 m H₂0
Total pressure loss with safety = 8.5 m H₂0
0.8 bar SUMP PIT CAPACITY 4.05 Cu.m

Selected Pump 1.15 Mtrs


STATIC HEAD UG (LVL=-0.70) TO GF(LVL=+0.85)
1 set of Sump pump (1 Duty + 1 Standby) @ 5 l/s, 2.5 bar
1.15 Mtrs
Pipe pressure drop calculation

Pipe selected
Ø 75 mm SCH 80 PIPE(3")
Flow rate = 4.63 l/sec
Velocity = 3.56 ft/sec
1.1 m/sec
Pipe friction loss = 0.71 psi/100ft
Pipe friction loss = 1.64 ft/100ft
Pipe length No. of fittings
(M) ELBOW90 TEE GV STR. NRV
Suction (A)
Discharge (B)+Riser
(C )+B/L Break
41.0 9 1 1 0 1
pressure manhole
(D)
Total 41.0 9 1 1 0 1
Total equivalent length
Total Length
Qnty. Eq. Length (ft)
(ft)
Pipe 41.0 134.5 134.48
Fittings
E90 9 11.0 99.00
TEE 1 12.0 12.00
GV 1 1.9 1.90
STR. 0 0.0 0.00
NRV 1 27.0 27.00
Total 274.38 ft

Total length of pipe = 274.4 ft


Pressure loss = 0.7 psi/100ft
Total pressure loss in pipe & fitting = 1.9 psi
= 1.4 m H₂0