Reults Dog

You might also like

Download as xls, pdf, or txt
Download as xls, pdf, or txt
You are on page 1of 13

Study ID Untitled

Study Case ID LF

Data Revision Base


Configuration Normal

Loading Cat Normal


Generation Cat Normal
Diversity Factor Normal Loading

Buses 64
Branches 66
Generators 0
Power Grids 1
Loads 19

Load-MW 2.365
Load-Mvar 1.466
Generation-MW 2.459
Generation-Mvar 1.581
Loss-MW 0.0934
Loss-Mvar 0.115

Mismatch-MW 0
Mismatch-Mvar 0
Bus ID Nominal kV Amp Rating Type
Bus15 11 0 Load
Bus16 11 0 Load
Bus25 132 0 Load
Bus26 11 0 Load
Bus27 11 0 Load
Bus28 132 0 Load
Bus29 11 0 Load
Bus30 11 0 Load
Bus31 11 0 Load
Bus32 11 0 Load
Bus33 132 0 Load
Bus34 132 0 SWNG
Bus35 0.44 0 Load
Bus36 11 0 Load
Bus39 11 0 Load
Bus40 0.44 0 Load
Bus42 11 0 Load
Bus43 11 0 Load
Bus45 11 0 Load
Bus46 11 0 Load
Bus51 11 0 Load
Bus52 0.44 0 Load
Bus55 11 0 Load
Bus56 0.44 0 Load
Bus57 11 0 Load
Bus58 0.44 0 Load
Bus59 11 0 Load
Bus60 0.44 0 Load
Bus61 11 0 Load
Bus62 11 0 Load
Bus63 11 0 Load
Bus64 11 0 Load
Bus67 11 0 Load
Bus68 0.44 0 Load
Bus69 11 0 Load
Bus70 0.44 0 Load
Bus71 11 0 Load
Bus72 0.44 0 Load
Bus73 11 0 Load
Bus74 0.44 0 Load
Bus75 11 0 Load
Bus76 0.44 0 Load
Bus77 11 0 Load
Bus80 11 0 Load
Bus81 0.44 0 Load
Bus82 11 0 Load
Bus85 11 0 Load
Bus86 0.44 0 Load
Bus89 11 0 Load
Bus90 0.44 0 Load
Bus91 11 0 Load
Bus92 11 0 Load
Bus95 11 0 Load
Bus96 0.44 0 Load
Bus97 11 0 Load
Bus100 11 0 Load
Bus101 0.44 0 Load
Bus102 11 0 Load
Bus103 0.44 0 Load
Bus106 11 0 Load
Bus107 0.44 0 Load
Bus108 11 0 Load
Bus111 11 0 Load
Bus112 0.44 0 Load
Voltage kW Loading kvar Loading Amp Loading
10832.6 2426.9 1548.5 153.4
10981 2458.3 1572.2 153.4
132000 819.5 527 4.262
10981.3 819.4 524.1 51.14
10981.2 819.4 524.1 51.14
132000 819.5 527 4.262
10981.3 819.4 524.1 51.14
10981.2 2458.3 1572.2 153.4
10981.2 819.4 524.1 51.14
10981.3 819.4 524.1 51.14
132000 819.5 527 4.262
132000 2458.5 1581.1 12.79
424.7 84.22 52.19 134.7
10830.7 85.42 54 5.387
10808.5 77.52 48.92 4.896
424.6 76.53 47.43 122.4
10798.2 921.8 599.9 58.8
10795.9 833.5 544.1 53.23
10799.4 1009.9 655.7 64.37
10793 748.3 490.3 47.86
10799.4 88.07 55.71 5.571
423.2 86.78 53.78 139.3
10798.2 88.05 55.7 5.571
423.2 86.76 53.77 139.3
10795.9 84.99 53.73 5.377
423.4 83.79 51.93 134.4
10793 748.3 490.3 47.86
407.7 718.2 445.1 1196
10799.9 425 246.8 26.27
10800.5 930.6 568.3 58.29
10801.7 992.9 607.4 62.21
10808.5 1071.1 656.7 67.11
10799.9 77.42 48.86 4.894
424.3 76.43 47.37 122.4
10801.7 62.15 39.08 3.924
425.9 61.51 38.12 98.1
10800.5 63.15 40.31 4.005
419.4 61.82 38.31 100.1
10800.5 316.2 200.6 20.02
422 310.9 192.7 500.4
10800.5 126.3 80.61 8.009
419.4 123.6 76.62 200.2
10824 124.1 78.47 7.833
10824 92.95 58.86 5.868
423.7 91.52 56.72 146.7
10823.9 31.18 19.6 1.964
10823.9 31.18 19.6 1.964
426.8 30.86 19.12 49.11
10826.9 76.43 48.04 4.814
427 75.66 46.89 120.4
10826.9 76.43 48.04 4.814
10770 400.6 251.8 25.37
10770 77.68 48.59 4.912
426.9 77.18 47.83 122.8
10769.2 238.2 149.7 15.09
10769.2 77.31 48.62 4.896
424.6 76.52 47.42 122.4
10768.1 85.36 53.44 5.4
426.5 84.76 52.53 135
10768.1 75.55 47.66 4.789
423.2 74.59 46.23 119.7
10768.1 160.9 101.1 10.19
10769.8 84.66 53.52 5.369
422.3 83.47 51.73 134.2
% Loading
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
ID Type kW Flow kvar Flow
500mcm cable Cable 2458.3 1572.2
1000mcm T/F to feeder2 Cable 819.4 524.1
1000mcm T/F2 to feeder1 Cable 819.4 524.1
1000mcm T/F3 to feeder1 Cable 819.4 524.1
Cable13 Cable 921.9 600
Cable15 Cable 833.7 544.2
Cable16 Cable 748.5 490.4
Cable18 Cable 347.5 197.9
Cable20 Cable 425 246.8
Cable22 Cable 930.7 568.4
Cable24 Cable 993.5 607.8
Cable26 Cable 31.18 19.6
Cable29 Cable 238.3 149.7
Cable31 Cable 160.9 101.1
Cable33 Cable 84.66 53.52
Line1 Line 2426.9 1548.5
Line11 Line 1071.1 656.7
Line12 Line 662.4 457.8
Line13 Line 124.1 78.47
Line14 Line 76.43 48.04
Line15 Line 400.6 251.8
Line16 Line 85.42 54
T1 I-8 Grid1 Transf. 2W 819.5 527
T2 I-8 Grid1 Transf. 2W 819.5 527
T3 I-8 Grid1 Transf. 2W 819.5 527
T7 Transf. 2W 85.42 54
T11 Transf. 2W 77.52 48.92
T20 Transf. 2W 88.07 55.71
T24 Transf. 2W 88.05 55.7
T25 Transf. 2W 84.99 53.73
T26 Transf. 2W 748.3 490.3
T33 Transf. 2W 77.42 48.86
T34 Transf. 2W 62.15 39.08
T35 Transf. 2W 63.15 40.31
T36 Transf. 2W 316.2 200.6
T37 Transf. 2W 126.3 80.61
T39 Transf. 2W 92.95 58.86
T41 Transf. 2W 31.18 19.6
T43 Transf. 2W 76.43 48.04
T45 Transf. 2W 77.68 48.59
T47 Transf. 2W 77.31 48.62
T48 Transf. 2W 85.36 53.44
T50 Transf. 2W 75.55 47.66
T52 Transf. 2W 84.66 53.52
Amp Flow % Loading
153.4 37.1
51.14 11.2
51.14 11.2
51.14 11.2
58.8
53.23
47.86
21.38
26.27
58.29
62.21
1.964
15.09
10.19
5.369
153.4
67.11
43.05
7.833
4.814
25.37
5.387
4.262 2.4
4.262 2.4
4.262 2.4
5.387 50.5
4.896 45.8
5.571 52.1
5.571 52.1
5.377 50.3
47.86 142
4.894 45.8
3.924 36.7
4.005 74.9
20.02 59.4
8.009 74.9
5.868 55
1.964 36.8
4.814 36.1
4.912 22.9
4.896 36.5
5.4 25.2
4.789 44.7
5.369 50.1
ID Rating/Limit Rated kV kW
Lump9 190.5 kVA 0.44 76.43
Lump22 209.6 kVA 0.44 84.22
Lump23 190.5 kVA 0.44 76.53
Lump24 152.4 kVA 0.44 61.51
Lump25 76.21 kVA 0.44 61.82
Lump26 762.1 kVA 0.44 310.9
Lump27 152.4 kVA 0.44 123.6
Lump28 217.2 kVA 0.44 86.78
Lump29 1905.3 kVA 0.44 718.2
Lump30 209.6 kVA 0.44 83.79
Lump31 217.2 kVA 0.44 86.76
Lump32 76.21 kVA 0.44 30.86
Lump33 228.6 kVA 0.44 91.52
Lump34 186.7 kVA 0.44 75.66
Lump35 209.6 kVA 0.44 84.76
Lump36 186.7 kVA 0.44 74.59
Lump37 190.5 kVA 0.44 76.52
Lump38 190.5 kVA 0.44 77.18
Lump39 209.6 kVA 0.44 83.47
% Loading Vterminal
48.9 96.43
49 96.53
49 96.51
49 96.79
100.1 95.32
50 95.91
100.1 95.32
48.9 96.18
47.9 92.66
48.9 96.22
48.9 96.17
49.1 96.99
48.9 96.3
49.1 97.05
49.1 96.93
48.9 96.18
49 96.5
49.1 97.03
48.8 95.99
ID Rating/Limit Rated kV MW
I-8 Grid Station 1250 MVA 132 2.459
Amp % Generation
12.79

You might also like