BERITA ACARA SERAH TERIMA

Pada hari ini Jum'at, Tanggal 04, Bulan November Tahun 2022 Telah dilakukan penyerahan atas pekerjaan Pemasangan / Penggantian Battery
di lokasi berikut :

Nama Site : CISELAM - CIBENING

Site ID : 602965

Area : PURWAKARTA CITY

Adapun penyerahan Installation dan Rektifikasi dengan rincian sebagai berikut :

No Item Material Brand Battery Type Battery Capacity Serial Number


1 Battery 4 Block RITAR FT12-100 100 AH BMG-H3i-S/N 22HO1132
BMG-H3i-S/N 22HO1057
BMG-H3i-S/N 22HO1114
BMG-H3i-S/N 22HO0983
2 Cage Baterry ( Cor)

Pekerjaan tersebut telah selesai, dapat diterima dengan baik dan dapat dioperasionalkan.
Demikian Berita Acara Serah Terima ini dibuat untuk dipergunakan sebagaimana mestinya, atas perhatian dan kerjasamanya kami ucapkan

banyak terima kasih.

PT Bach Multi Global PT Indosat Tbk


Indosat Ooredoo Hutchison

( Noer Muhammad Ramlan ) ( Andi Karmana )


PT.BACH MULTI GLOBAL
Jl.Cideng Barat No.72
Jakarta Pusat 10150 – Indonesia
Tel. (021) 386 2351 / 386 2352Fax.
(021) 386 2350 / 386 2360

DELIVERY NOTE
Site ID : 602965 Date : 4-Nov-22

Site Name : CISELAM - CIBENING

NO QTY UOM ITEM DESCRIPTION S/N REMAKS


1 1 Bank Ritar FT 12 – 100 BMG-H3i-S/N 22HO1132
BMG-H3i-S/N 22HO1057
BMG-H3i-S/N 22HO1114
BMG-H3i-S/N 22HO0983
1 1 Lot Material Cage Battery (COR)

PT Bach Multi Global PT Indosat Tbk


Indosat Ooredoo Hutchison

( Herman S ) ( )
ACCEPTANCE TEST PROCEDURE (ATP)

Customer : PT.H3I Battery Brand / Type : RITAR FT 12-100


Site ID : 602965 Total Battery : 4 Blocks / 1 Bank
Site Name : CISELAM - CIBENING Capacity : 100 Ah
Region : West Java Outer Temp. Cabinet/Room : 21 °C
Load : 10.2 Ampere
MEASUREMENT & TEST
** (This battery back up simulation only perform and make sure if the battery working after installed. Simulation test will do by turning off the PLN
)

Test Hours (minutes) Battery Back Up Test


Bank Serial Nummber Battery
0 15 45 60 Capacity (Ah) OK NOK

BMG-H3i-S/N 22HO1132 12.93 12.63 12.02 12.02 100 √

BMG-H3i-S/N 22HO1057 13.81 13.11 12.53 12.43 100 √

1
BMG-H3i-S/N 22HO1114 13.32 12.45 12.45 12.45 100 √

BMG-H3i-S/N 22HO0983 13.46 13.32 12.46 12.30 100 √

Voltage (Volt) 53.52 51.51 49.46 49.20

Test Hours (minutes) Battery Back Up Test


Bank Serial Nummber Battery
0 10 20 30 Capacity (Ah) OK Defect

Voltage (Volt)

Test Hours (menutes) Battery Back Up Test


Bank Serial Nummber Battery
0 10 20 30 Capacity (Ah) OK Defect

Voltage (Volt)

Test Hours (menutes) Battery Back Up Test


Bank Serial Nummber Battery
0 10 20 30 Capacity (Ah) OK Defect

Voltage (Volt)
** Make sure setting floating voltage, battery capacity and battery current limit correct

[Supplier Name] : Manage Service : Approved by :

( Marak Ramdani ) ( Noer Mohammad Ramlan ) ( Indosat Ooredoo Hutchison )

Page 1 of 3
ACCEPTANCE TEST PROCEDURE (ATP)

DOCUMENTATION
EXISTING CONDITION ON SITE ( BEFORE BATTERY INSTALATION )

PHOTO NAME PLATE OF SITE ID PHOTO BATTERY & CAGE BATTERY ON SITE

PHOTO EXISTING BATTERY & RECTIFIER PHOTO EXISTING CABLE & MCB BATTERY

N/A

PHOTO CABINET RECTIFIER / BATTERY DC Load Meassurement (Rect. Off)

N/A

PHOTO BATTERY EX Replacement PHOTO BATTERY TERPASANG

Page 2 of 3
ACCEPTANCE TEST PROCEDURE (ATP)

DOCUMENTATION
CONDITION ON SITE ( AFTER BATTERY INSTALATION )

PHOTO NEW BATTERY INSTALL IN RECTIFIER PHOTO CABINET WITH NEW BATTERY IN RECTIFIER

N/A N/A

Volt Battery Meassurement 15 Minutes Volt Battery Meassurement 45 Minutes

N/A

Volt Battery Meassurement 60 Minutes PHOTO SAFETY BATTERY ( CAGE BATTERY )

PHOTO Progress PHOTO LOCATION EXSISTING BATTERY OLD