Earth Pits Maintenance sheet Apparel Knitting

Date 31-Dec-22

Sr.# Description Status Remarks

Done general
OK cleaning from outer
1 General Cleaning of earth pit and inner side

Satisfied. Physcial
OK
access to EP
2 Physical access to earth pit

No loosing was
OK
found
3 Nut bolt tighting

slightly rust was


OK
found. Cleaned it
4 Check Rusting condition on electrode

NO Already found wet


5 Chemical/water penetration

Remarks:- __________________________________________________________________________________

Inspected By :- Muhammad Tayyab Verified By:- Anum Saleem


APPAREL KNITTING UNIT
INTERLOOP LTD
WHAT DOES HAZARD MEAN?

HAZARD MEANS:
• ANY POTENTIAL OR ACTUAL THREAT TO THE WELLBEING OF PEOPLE,
MACHINERY OR ENVIRONMENT

ELECTRICAL HAZARD SAFETY MEANS:


• TAKING PRECAUTIONS TO IDENTIFY AND CONTROL ELECTRICAL HAZARDS
TYPES OF ELECTRICAL HAZARDS
DEFECTIVE EQUIPMENT OR TOOLS
POWER STRIPS:
• CAN BE OVER LOADED
BECAUSE OF MULTIPLE
PLUG ARRANGEMENT
• MOST HAVE OVERLOAD PROTECTION
BUT OFTEN MALFUNCTION CAUSING FIRE
• USE FIXED WIRING WHEN POSSIBLE
ELECTRIC CIRCUITS HAZARDS
• A HAZARD EXISTS WHEN A CONDUCTOR IS TOO SMALL TO SAFELY CARRY THE
CURRENT.
• TOO MANY DEVICES PLUGGED INTO CIRCUIT
THERE ARE FOUR MAIN TYPES OF ELECTRICAL INJURIES:
• ELECTROCUTION (DEATH DUE TO ELECTRICAL SHOCK)

• ELECTRICAL SHOCK

• BURNS

• FALLS
INJURY
THE MOST COMMON SHOCK RELATED NONFATAL INJURY

• OCCUR WHEN YOU TOUCH ELECTRICAL WIRING OR


EQUIPMENT THAT IS IMPROPERLY USED OR MAINTAINED
• TYPICALLY OCCURS ON THE HANDS
• VERY SERIOUS INJURY THAT NEEDS IMMEDIATE ATTENTION
PREVENTIONS
PROTECTIVE MEASURES

• PROTECTIVE MEASURES
• PROPER GROUNDING
• USING GFCI’S
• USING FUSES AND CIRCUIT BREAKERS
• PROPER USE OF FLEXIBLE CORDS
• MAINTAIN SAFE DISTANCE FROM OVERHEAD POWER LINES
ELECTRICAL PROTECTION METHODS
• MAINTAIN SAFE DISTANCE FROM OVERHEAD POWER LINES:
• STAYING AWAY
• FOLLOWING TABLE SHOWS THE SAFE POWER LINE CLEARANCE DISTANCE FOR
VARIOUS LINE VOLTAGES.
POWER SOURCE IDENTIFICATION

• MARK ALL BREAKERS ACCORDINGLY FOR THE CIRCUITS THEY PROTECT


• MARK ALL DISCONNECT MEANS ACCORDINGLY FOR THE EQUIPMENT THEY
SERVICE
• IDENTIFY ALL VOLTAGES WITH PROPER LABELING
FOLLOW LOCKOUT/TAGOUT (LOTO)
• ESSENTIAL SAFETY PROCEDURE
• PROTECTS WORKERS FROM INJURY WHILE
WORKING ON OR NEAR ELECTRICAL CIRCUITS
AND EQUIPMENT
• PREVENTS CONTACT WITH OPERATING
EQUIPMENT PARTS SUCH AS, BLADES, GEARS,
SHAFTS, ETC.
• LOTO PREVENTS THE UNEXPECTED RELEASE
OF HAZARDOUS GASES, FLUIDS, OR SOLID
MATTER IN AREAS WHERE WORKERS ARE
PRESENT.
INSTRUCTIONS
• DON’T USE IN WET/DAMP ENVIRONMENTS.
• KEEP WORKING AREAS WELL LIT.
• ENSURE THAT CORDS DO NOT CAUSE A TRIPPING HAZARD.
• REMOVE DAMAGED TOOLS FROM USE.
• USE DOUBLE-INSULATED TOOLS.
• AVOID ACCIDENTAL STARTING. DO NOT HOLD FINGERS ON THE SWITCH
BUTTON WHILE CARRYING A PLUGGED-IN TOOL.
• USE GLOVES AND APPROPRIATE FOOTWEAR.
• STORE IN DRY A PLACE WHEN NOT USING
• ENSURE THAT THE RIGHT PERSON IS CARRYING OUT ELECTRICAL WORK –
LICENSED VERSUS COMPETENT

• ELECTRICITY IS ESSENTIAL BUT, IMPROPERLY USED, IT CAN BE DEADLY!


TO STAY ALIVE, YOU HAVE TO STAY ALERT
HTL Machine DB SLD LEGENTS

MCB MCB

63A,3P Indicating Light


415V,50HZ Voltmeter
V
6mm²,4Core 4 Pole
V

MCB MCB MCB MCB MCB MCB


20A,2P 20A,2P 20A,2P 20A,2P 20A,2P 20A,2P
3Pin Industrial

4mm², 1Core
Socket_1

3Pin Industrial
Socket_2

4mm², 1Core
Flow meter LPG
3Pin Industrial Socket_4
4mm², 1Core

3Pin Industrial Socket_5


4mm², 1Core
3Pin Industrial Socket_3
4mm², 1Core

2022 NAME SIGN


TITLEE HTL Machine DB SLD
Drawn By AS
DATE SCALE REV. NO. DWG NO.
Checked By AS
DWG NO.

Approved By AB 18-Nov-22 NTS 0/1 ILA-17.


Fast Cables Limited
www.fast-cables.com UAN:111-000-343
TEST CERTIFICATE DOC NO : Q.C/3/04

CUSTOMER : INTERLOOP LIMITED ERP NO : 2107-22A-PMF-0136

ADDRESS : FSD

DESCRIPTION : 70MM SQ S/C CU/PVC/INS 450/750 V (GREEN-YELLOW)

ORDER NO : 2107-14B-SOR-0126 ORDER DATE : 28-JUL-21

DLV NO : 2108-14B-DLV-0002 DLV DATE : 02-AUG-21

LOTNO : A58240.21 TEST DATE : 12-JUL-21

STATUS : Verified QTY PRODUCED : 2007 UOM: MTR

PRINT ON DATE : 25-NOV-22 15:34:46 QTY SUPPLIED : 300 UOM: MTR

SR# TEST NAME STANDARD OBSERVED REMARKS


REQUIREMENT VALUE

1 High Voltage Withstand Test A.C 2.5 kV AC for 5 min withstood ok

2 Thickness of insulation 1.40 1.40- 1.60 ok

3 DC resistance of conductor at 20°C (Maximum) 0.268 0.260 ok

4 Stranding formation Compacted Compacted ok

5 Insulation resistance at 20°C 05 More than Required ok

MANAGER QUALITY CONTROL MANAGER WORKS

RDF : LABTESTDLVcomp
Fast Cables Limited
www.fast-cables.com UAN:111-000-343
TEST CERTIFICATE DOC NO : Q.C/3/04

CUSTOMER : INTERLOOP LIMITED ERP NO : 2105-51A-PMF-0147

ADDRESS : FSD

DESCRIPTION : 35MM SQ 4/C CU/PVC/PVC 600/1000 V (BLACK)

ORDER NO : 2107-14B-SOR-0126 ORDER DATE : 28-JUL-21

DLV NO : 2108-14B-DLV-0002 DLV DATE : 02-AUG-21

LOTNO : B20329.21 TEST DATE : 24-MAY-21

STATUS : Verified QTY PRODUCED : 1005 UOM: MTR

PRINT ON DATE : 25-NOV-22 15:34:46 QTY SUPPLIED : 650 UOM: MTR

SR# TEST NAME STANDARD OBSERVED REMARKS


REQUIREMENT VALUE

1 High Voltage Withstand Test A.C 3.5 kV AC for 5 min withstood ok

2 Thickness of sheath 1.80 1.80- 2.00 ok

3 Thickness of insulation 1.20 1.20- 1.40 ok

4 DC resistance of conductor at 20°C (Maximum) 0.524 0.518 ok

5 Stranding formation Shaped Shaped ok

6 Insulation resistance at 20°C 36.7 More than Required ok

MANAGER QUALITY CONTROL MANAGER WORKS

RDF : LABTESTDLVcomp
Fast Cables Limited
www.fast-cables.com UAN:111-000-343
TEST CERTIFICATE DOC NO : Q.C/3/04

CUSTOMER : INTERLOOP LIMITED ERP NO : 2107-22A-PMF-0302

ADDRESS : FSD

DESCRIPTION : 1.5MM SQ 3/C CU/PVC/PVC FLEX 300/500 V (GRAY)

ORDER NO : 2107-14B-SOR-0124 ORDER DATE : 28-JUL-21

DLV NO : 2108-14B-DLV-0003 DLV DATE : 02-AUG-21

LOTNO : A4484.21 TEST DATE : 26-JUL-21

STATUS : Verified QTY PRODUCED : 49 UOM: COIL

PRINT ON DATE : 25-NOV-22 15:37:07 QTY SUPPLIED : 5 UOM: COIL

SR# TEST NAME STANDARD OBSERVED REMARKS


REQUIREMENT VALUE

1 DC resistance of conductor at 20°C (Maximum) 13.30 13.20 ok

2 Stranding formation 0.26 (Max) 0.25- 0.26 ok

3 Thickness of insulation 0.70 0.70- 0.90 ok

4 Thickness of sheath 1.20 1.20- 1.40 ok

5 High Voltage Withstand Test A.C 2 kV AC for 5 min withstood ok

6 Insulation resistance at 20°C 10 More than Required ok

MANAGER QUALITY CONTROL MANAGER WORKS

RDF : LABTESTDLVcomp
Fast Cables Limited
www.fast-cables.com UAN:111-000-343
TEST CERTIFICATE DOC NO : Q.C/3/04

CUSTOMER : INTERLOOP LIMITED ERP NO : 2106-22A-PMF-0522

ADDRESS : FSD

DESCRIPTION : 16MM SQ S/C CU/PVC/INS 450/750 V (GREEN-YELLOW)

ORDER NO : 2107-14B-SOR-0124 ORDER DATE : 28-JUL-21

DLV NO : 2108-14B-DLV-0003 DLV DATE : 02-AUG-21

LOTNO : A57935.21 TEST DATE : 29-JUN-21

STATUS : Verified QTY PRODUCED : 2000 UOM: MTR

PRINT ON DATE : 25-NOV-22 15:37:07 QTY SUPPLIED : 1050 UOM: MTR

SR# TEST NAME STANDARD OBSERVED REMARKS


REQUIREMENT VALUE

1 DC resistance of conductor at 20°C (Maximum) 1.15 1.05 ok

2 Stranding formation Compacted Compacted ok

3 Thickness of insulation 1.00 1.00- 1.20 ok

4 Insulation resistance at 20°C 06 More than Required ok

5 High Voltage Withstand Test A.C 2.5 kV AC for 5 min withstood ok

MANAGER QUALITY CONTROL MANAGER WORKS

RDF : LABTESTDLVcomp
Fast Cables Limited
www.fast-cables.com UAN:111-000-343
TEST CERTIFICATE DOC NO : Q.C/3/04

CUSTOMER : INTERLOOP LIMITED ERP NO : 2107-22A-PMF-0048

ADDRESS : FSD

DESCRIPTION : 2.5MM SQ 4/C CU/PVC/PVC FLEX 300/500 V (GRAY)

ORDER NO : 2107-14B-SOR-0124 ORDER DATE : 28-JUL-21

DLV NO : 2108-14B-DLV-0003 DLV DATE : 02-AUG-21

LOTNO : A58092.21 TEST DATE : 06-JUL-21

STATUS : Verified QTY PRODUCED : 971 UOM: MTR

PRINT ON DATE : 25-NOV-22 15:37:07 QTY SUPPLIED : 500 UOM: MTR

SR# TEST NAME STANDARD OBSERVED REMARKS


REQUIREMENT VALUE

1 Stranding formation 0.26 (Max) 0.25- 0.26 ok

2 DC resistance of conductor at 20°C (Maximum) 7.98 7.88 ok

3 Thickness of insulation 0.80 0.80- 1.00 ok

4 High Voltage Withstand Test A.C 2 kV AC for 5 min withstood ok

5 Thickness of sheath 1.20 1.20- 1.40 ok

6 Insulation resistance at 20°C 09 More than Required ok

MANAGER QUALITY CONTROL MANAGER WORKS

RDF : LABTESTDLVcomp
Fast Cables Limited
www.fast-cables.com UAN:111-000-343
TEST CERTIFICATE DOC NO : Q.C/3/04

CUSTOMER : INTERLOOP LIMITED ERP NO : 2108-22A-PMF-0150

ADDRESS : FSD

DESCRIPTION : 10MM SQ S/C CU/PVC/INS 450/750 V (GREEN)

ORDER NO : 2107-14B-SOR-0126 ORDER DATE : 28-JUL-21

DLV NO : 2108-14B-DLV-0137 DLV DATE : 26-AUG-21

LOTNO : A58861.21 TEST DATE : 11-AUG-21

STATUS : Verified QTY PRODUCED : 870 UOM: MTR

PRINT ON DATE : 25-NOV-22 15:35:32 QTY SUPPLIED : 870 UOM: MTR

SR# TEST NAME STANDARD OBSERVED REMARKS


REQUIREMENT VALUE

1 Stranding formation Compacted Compacted ok

2 DC resistance of conductor at 20°C (Maximum) 1.83 1.73 ok

3 Thickness of insulation 1.00 1.00- 1.20 ok

4 High Voltage Withstand Test A.C 2.5 kV AC for 5 min withstood ok

5 Insulation resistance at 20°C 07 More than Required ok

MANAGER QUALITY CONTROL MANAGER WORKS

RDF : LABTESTDLVcomp
Fast Cables Limited
www.fast-cables.com UAN:111-000-343
TEST CERTIFICATE DOC NO : Q.C/3/04

CUSTOMER : INTERLOOP LIMITED ERP NO : 2108-22A-PMF-0182

ADDRESS : FSD

DESCRIPTION : 4.0MM SQ 4/C CU/PVC/PVC FLEX 600/1000 V (GRAY)

ORDER NO : 2107-14B-SOR-0126 ORDER DATE : 28-JUL-21

DLV NO : 2108-14B-DLV-0137 DLV DATE : 26-AUG-21

LOTNO : A58946.21 TEST DATE : 13-AUG-21

STATUS : Verified QTY PRODUCED : 1300 UOM: MTR

PRINT ON DATE : 25-NOV-22 15:35:32 QTY SUPPLIED : 1300 UOM: MTR

SR# TEST NAME STANDARD OBSERVED REMARKS


REQUIREMENT VALUE

1 Stranding formation 0.31 (Max) 0.30- 0.31 ok

2 DC resistance of conductor at 20°C (Maximum) 4.95 4.85 ok

3 Insulation resistance at 20°C 36.7 More than Required ok

4 High Voltage Withstand Test A.C 3.5 kV AC for 5 min withstood ok

5 Thickness of insulation 1.00 1.00- 1.20 ok

6 Thickness of sheath 1.80 1.80- 2.00 ok

MANAGER QUALITY CONTROL MANAGER WORKS

RDF : LABTESTDLVcomp
Fast Cables Limited
www.fast-cables.com UAN:111-000-343
TEST CERTIFICATE DOC NO : Q.C/3/04

CUSTOMER : INTERLOOP LIMITED ERP NO : 2108-22A-PMF-0199

ADDRESS : FSD

DESCRIPTION : 70MM SQ BARE COPPER CONDUCTOR

ORDER NO : 2107-14B-SOR-0126 ORDER DATE : 28-JUL-21

DLV NO : 2108-14B-DLV-0137 DLV DATE : 26-AUG-21

LOTNO : A58976.21 TEST DATE : 16-AUG-21

STATUS : Verified QTY PRODUCED : 300 UOM: MTR

PRINT ON DATE : 25-NOV-22 15:35:32 QTY SUPPLIED : 300 UOM: MTR

SR# TEST NAME STANDARD OBSERVED REMARKS


REQUIREMENT VALUE

1 DC resistance of conductor at 20°C (Maximum) 0.268 0.260 ok

2 Stranding formation Compacted Compacted ok

3 Outer Diameter Of Conductor 9.30- 10.20 10.10 ok

MANAGER QUALITY CONTROL MANAGER WORKS

RDF : LABTESTDLVcomp
Fast Cables Limited
www.fast-cables.com UAN:111-000-343
TEST CERTIFICATE DOC NO : Q.C/3/04

CUSTOMER : INTERLOOP LIMITED ERP NO : 2108-22A-PMF-0067

ADDRESS : FSD

DESCRIPTION : 4.0MM SQ S/C CU/PVC/INS 450/750 V (GREEN)

ORDER NO : 2107-14B-SOR-0124 ORDER DATE : 28-JUL-21

DLV NO : 2108-14B-DLV-0138 DLV DATE : 26-AUG-21

LOTNO : A58757.21 TEST DATE : 06-AUG-21

STATUS : Verified QTY PRODUCED : 1300 UOM: MTR

PRINT ON DATE : 25-NOV-22 15:36:30 QTY SUPPLIED : 1300 UOM: MTR

SR# TEST NAME STANDARD OBSERVED REMARKS


REQUIREMENT VALUE

1 Stranding formation Compacted Compacted ok

2 DC resistance of conductor at 20°C (Maximum) 4.61 4.55 ok

3 Insulation resistance at 20°C 08 More than Required ok

4 High Voltage Withstand Test A.C 2.5 kV AC for 5 min withstood ok

5 Thickness of insulation 0.80 0.80- 1.00 ok

MANAGER QUALITY CONTROL MANAGER WORKS

RDF : LABTESTDLVcomp
Fast Cables Limited
www.fast-cables.com UAN:111-000-343
TEST CERTIFICATE
Customer : INTERLOOP LIMITED Doc No : Q.C/3/04

Description : 1.5MM SQ 3/C CU/PVC/PVC FLEX 300/500 V (GRAY) ERP No. : 2107-22A-ISR-0182

Specification : BS EN 60228, BS 6500 Date : 15-JUL-21

Lot No. : G01017.21 Qty.Produced : 100

Status : Length : 07 COILS

Report on Date : 26-NOV-22 12:06:59

Sr.# Test Name UOM Standard Observed Remarks


Requirement Value
1 Stranding formation 0.26 (Max) 0.25- 0.26 ok

2 Thickness of insulation mm 0.70 0.70- 0.90 ok

3 Thickness of sheath mm 0.90 0.90- 1.10 ok

4 DC resistance of conductor at 20°C (Maximum) Ohm/KM(Max) 13.30 13.18 ok

5 High Voltage Withstand Test A.C K.V 2 kV AC for 5 min withstood ok

6 Insulation resistance at 20°C M.ohm.km(min) 10 More than Required ok

Quality Control Department

Note : This is a system generated report that does not require signature.
Head Office: 192-Y Block, Commercial Area, DHA, Lahore UAN: 111-000-343
Regional Offices: Lahore, Karachi, Islamabad, Sahiwal, Multan, Rahim Yar Khan, Peshawar, Sialkot, Faisalabad, Gujranwala, Sargodha, Swat, Bannu

RDF :
Fast Cables Limited
www.fast-cables.com UAN:111-000-343
TEST CERTIFICATE
Customer : INTERLOOP LIMITED Doc No : Q.C/3/04

Description : 2.5MM SQ S/C CU/PVC/INS FLEX 450/750 V (GREEN) ERP No. : 2109-22A-ISR-0116

Specification : BS EN 60228, BS 6004 Date : 09-SEP-21

Lot No. : G01219.21 Qty.Produced : 500

Status : Length : 500 MTR

Report on Date : 26-NOV-22 12:10:23

Sr.# Test Name UOM Standard Observed Remarks


Requirement Value
1 Stranding formation 0.26 (Max) 0.25- 0.26 ok

2 Thickness of insulation mm 0.80 0.80- 1.00 ok

3 DC resistance of conductor at 20°C (Maximum) Ohm/KM(Max) 7.98 7.87 ok

4 High Voltage Withstand Test A.C K.V 2.5 kV AC for 5 min withstood ok

5 Insulation resistance at 20°C M.ohm.km(min) 9 More than Required ok

Quality Control Department

Note : This is a system generated report that does not require signature.
Head Office: 192-Y Block, Commercial Area, DHA, Lahore UAN: 111-000-343
Regional Offices: Lahore, Karachi, Islamabad, Sahiwal, Multan, Rahim Yar Khan, Peshawar, Sialkot, Faisalabad, Gujranwala, Sargodha, Swat, Bannu

RDF :
Fast Cables Limited
www.fast-cables.com UAN:111-000-343
TEST CERTIFICATE DOC NO : Q.C/3/04

CUSTOMER : INTERLOOP LIMITED ERP NO : 2109-22A-PMF-0157

ADDRESS : FSD

DESCRIPTION : 95MM SQ 3.5/C CU/PVC/PVC 600/1000 V (BLACK)

ORDER NO : 2107-14B-SOR-0126 ORDER DATE : 28-JUL-21

DLV NO : 2109-14B-DLV-0137 DLV DATE : 20-SEP-21

LOTNO : A59583.21 TEST DATE : 10-SEP-21

STATUS : Verified QTY PRODUCED : 670 UOM: MTR

PRINT ON DATE : 25-NOV-22 15:33:57 QTY SUPPLIED : 670 UOM: MTR

SR# TEST NAME STANDARD OBSERVED REMARKS


REQUIREMENT VALUE

1 Stranding formation P=shaped,N=compactedP=shaped,N=compacteok

2 DC resistance of conductor at 20°C (Maximum) P=0.193,N=0.387 P=0.187,N=0.380 ok

3 Thickness of insulation P=1.60,N=1.40 P=1.60-1.80,N=1.40-1.6ok

4 High Voltage Withstand Test A.C 3.5 kV AC for 5 min withstood ok

5 Insulation resistance at 20°C 36.7 More than Required ok

6 Thickness of sheath 2.20 2.20- 2.40 ok

MANAGER QUALITY CONTROL MANAGER WORKS

RDF : LABTESTDLVcomp
Fast Cables Limited
www.fast-cables.com UAN:111-000-343
TEST CERTIFICATE DOC NO : Q.C/3/04

CUSTOMER : INTERLOOP LIMITED ERP NO : 2109-22A-PMF-0276

ADDRESS : FSD

DESCRIPTION : 10MM SQ 4/C CU/PVC/PVC FLEX 600/1000 V (GRAY)

ORDER NO : 2107-14B-SOR-0126 ORDER DATE : 28-JUL-21

DLV NO : 2109-14B-DLV-0172 DLV DATE : 25-SEP-21

LOTNO : A59837.21 TEST DATE : 19-SEP-21

STATUS : Verified QTY PRODUCED : 700 UOM: MTR

PRINT ON DATE : 26-NOV-22 11:03:17 QTY SUPPLIED : 700 UOM: MTR

SR# TEST NAME STANDARD OBSERVED REMARKS


REQUIREMENT VALUE

1 Stranding formation 0.41 (Max) 0.40- 0.41 ok

2 DC resistance of conductor at 20°C (Maximum) 1.91 1.83 ok

3 Thickness of insulation 1.00 1.00- 1.20 ok

4 Thickness of sheath 1.80 1.80- 2.00 ok

5 High Voltage Withstand Test A.C 3.5 kV AC for 5 min withstood ok

6 Insulation resistance at 20°C 36.7 More than Required ok

MANAGER QUALITY CONTROL MANAGER WORKS

RDF : LABTESTDLVcomp
Fast Cables Limited
www.fast-cables.com UAN:111-000-343
TEST CERTIFICATE DOC NO : Q.C/3/04

CUSTOMER : INTERLOOP LIMITED ERP NO : 2109-22A-PMF-0389

ADDRESS : FSD

DESCRIPTION : 35MM SQ 4/C CU/PVC/PVC FLEX 600/1000 V (GRAY)

ORDER NO : 2107-14B-SOR-0126 ORDER DATE : 28-JUL-21

DLV NO : 2109-14B-DLV-0172 DLV DATE : 25-SEP-21

LOTNO : A60084.21 TEST DATE : 24-SEP-21

STATUS : Verified QTY PRODUCED : 400 UOM: MTR

PRINT ON DATE : 26-NOV-22 11:03:17 QTY SUPPLIED : 400 UOM: MTR

SR# TEST NAME STANDARD OBSERVED REMARKS


REQUIREMENT VALUE

1 Thickness of sheath 1.80 1.80- 2.00 ok

2 Stranding formation 0.41 (Max) 0.40- 0.41 ok

3 DC resistance of conductor at 20°C (Maximum) 0.554 0.540 ok

4 Thickness of insulation 1.20 1.20- 1.40 ok

5 High Voltage Withstand Test A.C 3.5 kV AC for 5 min withstood ok

6 Insulation resistance at 20°C 36.7 More than Required ok

MANAGER QUALITY CONTROL MANAGER WORKS

RDF : LABTESTDLVcomp
Fast Cables Limited
www.fast-cables.com UAN:111-000-343
TEST CERTIFICATE DOC NO : Q.C/3/04

CUSTOMER : INTERLOOP LIMITED ERP NO : 2107-22A-PMF-0287

ADDRESS : FSD

DESCRIPTION : 1.5MM SQ 3/C CU/PVC/PVC FLEX 300/500 V (GRAY)

ORDER NO : 2107-14B-SOR-0124 ORDER DATE : 28-JUL-21

DLV NO : 2109-14B-DLV-0190 DLV DATE : 29-SEP-21

LOTNO : A58427.21 TEST DATE : 19-JUL-21

STATUS : Verified QTY PRODUCED : 972 UOM: MTR

PRINT ON DATE : 25-NOV-22 15:37:42 QTY SUPPLIED : 920 UOM: MTR

SR# TEST NAME STANDARD OBSERVED REMARKS


REQUIREMENT VALUE

1 Stranding formation 0.26 (Max) 0.25- 0.26 ok

2 DC resistance of conductor at 20°C (Maximum) 13.30 13.19 ok

3 Insulation resistance at 20°C 10 More than Required ok

4 Thickness of sheath 1.20 1.20- 1.40 ok

5 High Voltage Withstand Test A.C 2 kV AC for 5 min withstood ok

6 Thickness of insulation 0.80 0.80- 1.00 ok

MANAGER QUALITY CONTROL MANAGER WORKS

RDF : LABTESTDLVcomp
Fast Cables Limited
www.fast-cables.com UAN:111-000-343
TEST CERTIFICATE DOC NO : Q.C/3/04

CUSTOMER : INTERLOOP LIMITED ERP NO : 2109-22A-PMF-0512

ADDRESS : FSD

DESCRIPTION : 16MM SQ 4/C CU/PVC/PVC FLEX 600/1000 V (GRAY)

ORDER NO : 2107-14B-SOR-0126 ORDER DATE : 28-JUL-21

DLV NO : 2110-14B-DLV-0054 DLV DATE : 13-OCT-21

LOTNO : A60421.21 TEST DATE : 30-SEP-21

STATUS : Verified QTY PRODUCED : 170 UOM: MTR

PRINT ON DATE : 26-NOV-22 11:02:20 QTY SUPPLIED : 170 UOM: MTR

SR# TEST NAME STANDARD OBSERVED REMARKS


REQUIREMENT VALUE

1 Stranding formation 0.41 (Max) 0.40- 0.41 ok

2 DC resistance of conductor at 20°C (Maximum) 1.21 1.11 ok

3 Insulation resistance at 20°C 36.7 More than Required ok

4 Thickness of sheath 1.80 1.80- 2.00 ok

5 High Voltage Withstand Test A.C 3.5 kV AC for 5 min withstood ok

6 Thickness of insulation 1.00 1.00- 1.20 ok

MANAGER QUALITY CONTROL MANAGER WORKS

RDF : LABTESTDLVcomp
Fast Cables Limited
www.fast-cables.com UAN:111-000-343
TEST CERTIFICATE DOC NO : Q.C/3/04

CUSTOMER : INTERLOOP LIMITED ERP NO : 2202-22A-PMF-0143

ADDRESS : FSD

DESCRIPTION : 95MM SQ 3.5/C CU/PVC/PVC 600/1000 V (BLACK)

ORDER NO : 2202-14B-SOR-0048 ORDER DATE : 12-FEB-22

DLV NO : 2202-14B-DLV-0061 DLV DATE : 16-FEB-22

LOTNO : A64711.22 TEST DATE : 12-FEB-22

STATUS : Verified QTY PRODUCED : 504 UOM: MTR

PRINT ON DATE : 26-NOV-22 11:09:41 QTY SUPPLIED : 250 UOM: MTR

SR# TEST NAME STANDARD OBSERVED REMARKS


REQUIREMENT VALUE

1 High Voltage Withstand Test A.C 3.5 kV AC for 5 min withstood ok

2 Thickness of sheath 2.20 2.20- 2.40 ok

3 Thickness of insulation P=1.60,N=1.40 P=1.60-1.80,N=1.40-1.6ok

4 DC resistance of conductor at 20°C (Maximum) P=0.193,N=0.387 P=0.189,N=0.381 ok

5 Stranding formation P=shaped,N=compactedP=shaped,N=compacteok

6 High Voltage Withstand Test A.C 36.7 More than Required ok

MANAGER QUALITY CONTROL MANAGER WORKS

RDF : LABTESTDLVcomp
Fast Cables Limited
www.fast-cables.com UAN:111-000-343
TEST CERTIFICATE DOC NO : Q.C/3/04

CUSTOMER : INTERLOOP LIMITED ERP NO : 2202-22A-PMF-0143

ADDRESS : FSD

DESCRIPTION : 95MM SQ 3.5/C CU/PVC/PVC 600/1000 V (BLACK)

ORDER NO : 2202-14B-SOR-0048 ORDER DATE : 12-FEB-22

DLV NO : 2202-14B-DLV-0061 DLV DATE : 16-FEB-22

LOTNO : A64712.22 TEST DATE : 12-FEB-22

STATUS : Verified QTY PRODUCED : 498 UOM: MTR

PRINT ON DATE : 26-NOV-22 11:09:41 QTY SUPPLIED : 498 UOM: MTR

SR# TEST NAME STANDARD OBSERVED REMARKS


REQUIREMENT VALUE

1 Insulation resistance at 20°C 36.7 More than Required ok

2 High Voltage Withstand Test A.C 3.5 kV AC for 5 min withstood ok

3 Thickness of sheath 2.20 2.20- 2.40 ok

4 Thickness of insulation P=1.60,N=1.40 P=1.60-1.80,N=1.40-1.6ok

5 Stranding formation P=shaped,N=compactedP=shaped,N=compacteok

6 DC resistance of conductor at 20°C (Maximum) P=0.193,N=0.387 P=0.187,N=0.380 ok

MANAGER QUALITY CONTROL MANAGER WORKS

RDF : LABTESTDLVcomp
Fast Cables Limited
www.fast-cables.com UAN:111-000-343
TEST CERTIFICATE DOC NO : Q.C/3/04

CUSTOMER : INTERLOOP LIMITED ERP NO : 2201-51A-PMF-0055

ADDRESS : FSD

DESCRIPTION : 70MM SQ 3.5/C CU/PVC/PVC 600/1000 V (BLACK)

ORDER NO : 2202-14B-SOR-0048 ORDER DATE : 12-FEB-22

DLV NO : 2202-14B-DLV-0061 DLV DATE : 16-FEB-22

LOTNO : B32641.22 TEST DATE : 10-JAN-22

STATUS : Verified QTY PRODUCED : 501 UOM: MTR

PRINT ON DATE : 26-NOV-22 11:09:41 QTY SUPPLIED : 250 UOM: MTR

SR# TEST NAME STANDARD OBSERVED REMARKS


REQUIREMENT VALUE

1 High Voltage Withstand Test A.C 3.5 kV AC for 5 min withstood ok

2 Thickness of sheath 2.00 2.00- 2.20 ok

3 Thickness of insulation P=1.40,N=1.20 P=1.40-1.60, N=1.20-1.ok

4 DC resistance of conductor at 20°C (Maximum) P=0.268,N=0.524 P=0.260,N=0.519 ok

5 Stranding formation P=shaped,N=compactedP=shaped,N=compacteok

6 Insulation resistance at 20°C 36.7 More than Required ok

MANAGER QUALITY CONTROL MANAGER WORKS

RDF : LABTESTDLVcomp
Fast Cables Limited
www.fast-cables.com UAN:111-000-343
TEST CERTIFICATE DOC NO : Q.C/3/04

CUSTOMER : INTERLOOP LIMITED ERP NO : 2201-51A-PMF-0060

ADDRESS : FSD

DESCRIPTION : 70MM SQ 3.5/C CU/PVC/PVC 600/1000 V (BLACK)

ORDER NO : 2202-14B-SOR-0048 ORDER DATE : 12-FEB-22

DLV NO : 2202-14B-DLV-0061 DLV DATE : 16-FEB-22

LOTNO : B32656.22 TEST DATE : 10-JAN-22

STATUS : Verified QTY PRODUCED : 500 UOM: MTR

PRINT ON DATE : 26-NOV-22 11:09:41 QTY SUPPLIED : 500 UOM: MTR

SR# TEST NAME STANDARD OBSERVED REMARKS


REQUIREMENT VALUE

1 High Voltage Withstand Test A.C 3.5 kV AC for 5 min withstood ok

2 Thickness of sheath 2.00 2.00- 2.20 ok

3 Thickness of insulation P=1.40,N=1.20 P=1.40-1.60, N=1.20-1.ok

4 DC resistance of conductor at 20°C (Maximum) P=0.268,N=0.524 P=0.261,N=0.518 ok

5 Stranding formation P=shaped,N=compactedP=shaped,N=compacteok

6 Insulation resistance at 20°C 36.7 More than Required ok

MANAGER QUALITY CONTROL MANAGER WORKS

RDF : LABTESTDLVcomp
Fast Cables Limited
www.fast-cables.com UAN:111-000-343
TEST CERTIFICATE
Customer : INTERLOOP LIMITED Doc No : Q.C/3/04

Description : 1.5MM SQ 3/C CU/PVC/PVC FLEX 300/500 V (GRAY) ERP No. : 2107-22A-ISR-0182

Specification : BS EN 60228, BS 6500 Date : 15-JUL-21

Lot No. : G01017.21 Qty.Produced : 100

Status : Length : 07 COILS

Report on Date : 26-NOV-22 12:06:59

Sr.# Test Name UOM Standard Observed Remarks


Requirement Value
1 Stranding formation 0.26 (Max) 0.25- 0.26 ok

2 Thickness of insulation mm 0.70 0.70- 0.90 ok

3 Thickness of sheath mm 0.90 0.90- 1.10 ok

4 DC resistance of conductor at 20°C (Maximum) Ohm/KM(Max) 13.30 13.18 ok

5 High Voltage Withstand Test A.C K.V 2 kV AC for 5 min withstood ok

6 Insulation resistance at 20°C M.ohm.km(min) 10 More than Required ok

Quality Control Department

Note : This is a system generated report that does not require signature.
Head Office: 192-Y Block, Commercial Area, DHA, Lahore UAN: 111-000-343
Regional Offices: Lahore, Karachi, Islamabad, Sahiwal, Multan, Rahim Yar Khan, Peshawar, Sialkot, Faisalabad, Gujranwala, Sargodha, Swat, Bannu

RDF :
MV/LV SWITCHGEAR SLD MV SWITCHGEAR

B VCB
G
630 A
25KA,11KV
ACB
EA
OC 2500 A,3P
A E/F
400/200/5/5
OP2

Step Down Transformer


Y EA 3000/5*3
ACB
3200 A,3P
EA NP1
415V,50HZ
3200/5*3
BusBar 3200A 3P+N+E 415V, 50HZ, 100KA for 1sec
NP6 NP5 NP4 NP3 NP2 OP7 OP6

MCCB MCCB MCCB


MCCB MCCB MCCB MCCB MCCB
MCCB MCCB MCCB MCB MCCB MCCB ACB
1000A,3P 400A,3P 400~800A,3P
800A,3P 250A,3P 50A,3P 100A,3P 100A,3P
600A,3P 400A,3P 175A,3P 175A,3P 600A,3P 600A,3P 2500 A,3P
415V,50Hz 415V,50Hz 415V, 50Hz
415V,50Hz 415V,50Hz 415V,50Hz 415V,50Hz 415V,50Hz
415V,50Hz 415V,50Hz 415V,50Hz 415V,50Hz 415V,50Hz 415V,50Hz 415V,50HZ

EA EA
EA

2500/5*1 400/5*3 800/5*3 100/5*3

Spare

3×95mm², 3.5Core
Knitting DB

1×6mm², 4Core
Compressor Dryer # 02
Spare
Spare
Spare
Spare

1×25mm², 4Core
LT Lightning DB
Spare
Spare
Spare

1×10mm², 4Core
LOT Making Area DB
1×150mm², 3.5Core
Compressor # 02

Spare
Automatic PFI Automatic PFI
Plant 600 KVAR Plant 512.5KVAR
LEGENTS

VCB
MV SWITCHGEAR
Indication Lights
VCB Voltmeter
630 A V

25KA,11KV
Am-meter
A
EA
A OC ACB
400/200/5/5 E/F
Current Transformer

Step Down Transformer


2000KVA 11000V/415V
Power Transformer

ACB
Power Factor Improvement Panel
3200 A,3P OP1
EA
415V,50HZ
Single Phase
3000/5*3
Three Phase
OP5 OP4 OP3 EA Energy Analyzer

Moulded Case Circuit


Breaker
MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB ACB
800A,3P 50A,3P 100A,3P 250A,3P 300A,3P 400A,3P 600A,3P 1600A,3P
100A,3P 400A,3P 50A,3P 100A,3P
415V,50Hz 415V,50Hz 415V,50Hz 415V,50Hz 415V,50Hz
G Generator
415V,50Hz 415V,50Hz 415V,50Hz 415V,50Hz 415V,50Hz 415V,50Hz 415V,50Hz

OP Operational panel
NP Not-Operational panel

EA EA EA EA

400/5*3 100/5*3 100/5*3 300/5*3 1600/5*1

Spare

3×95mm², 3.5Core
Printing Hall DB
1×35mm², 4Core

Chiller DB
2×35mm², 4Core

Fire Hydrant
Oval Printing M/C DB

Spare
3×95mm², 4Core
Compressor Dryer # 01
1×6mm², 4Core
1×150mm², 3.5Core
Compressor # 01

Spare

2×25mm², 4Core
2×16mm², 4Core
Embroidery+Table Printing
Section DB
Spare

2022 NAME SIGN TITLEE


LT ROOM SLD
Drawn By AS
Checked By MA DATE SCALE REV. NO. DEPT. DWG NO.

Approved By MA 10-Nov-22 NTS 0/0 ENGG


DWG NO.
ILA-22
Chiller DB Oval Printing M/C DB

95mm², 3.5Core 35mm², 4Core

95mm², 3.5Core 35mm², 4Core

95mm², 3.5Core Printing Hall DB

Embroidery+Table Printing DB 35mm², 4Core

25mm², 4Core Compressor Dryer # 01

25mm², 4Core 6mm², 4Core

16mm², 4Core Compressor # 01

16mm², 4Core 150mm², 3.5Core

LOT Making Area DB LT Lightning DB

10mm², 4Core 25mm², 4Core

Compressor Dryer # 02 Knitting DB

6mm², 4Core 95mm², 3.5Core

Compressor # 02 150mm², 3.5Core


Earth Pit# 4
Transformer earthing
Earth Pit# 2
LT Panels
Earth Pit# 3
HT Panels
Earth Pit# 5
Generator
Earth Pit# 4
Transformer earthing
Scanned with CamScanner
Scanned with CamScanner
Scanned with CamScanner
Scanned with CamScanner
Scanned with CamScanner
Scanned with CamScanner
Scanned with CamScanner
Scanned with CamScanner
Scanned with CamScanner
Scanned with CamScanner
Scanned with CamScanner
Capacity Information Sheet
Location CTS DB. INTERLOOP Knitting Unit Apparel
Total Capacity 63A
Total no. of breakers 12
Total no. of operational 11
breakers
Total no. of spare 1
breakers
Measured Load Current (A)
R-Y 419
INCOMING
3Ø (400-415)
Incoming Y-B 422 IRed 20
Supply R-B 420 IYellow 20
Voltage
(v) R-N 237 IBlue 19
P-N (220-240) Y-N 238 INeutral 2
B-N 240 IEarth 0
Measured

Pole
Sr # CB Rating Current (A) Size Cable Description of Equipment
R Y B

1. 32A 13.6 13.5 13.2 1x10mm2,3 Core 3 Gurring Machine

2. 16A 2.5 0 0 1x2.5 mm2,1 Core 1


CTS

3. 16A 0 0 0 1x2.5 mm2,1 Core 1


Washing Tub-1 (stand by)
1x2.5 mm2,1 Core
4. 16A 0.5 0 0 1
Auto coating

5. 16A 0.3 0 0 1x2.5 mm2,1 Core 1


Washing Tub-2
1x2.5 mm2,1 Core
6. 16A 1.4 0 0 1
Exposing area lights +power

7. 32A 0 0 0 1x1.5 mm2,3 Core 1


Mixing Machine

8. 20A 0 0 0 1x1.5 mm2,3 Core 1


Mixing Machine-1 (Stand By)

9. 16A 8 8 7 1x4mm2,3 Core 3


Oven_1

10. 16A 0 0 0 1x4mm2,3 Core 3


Oven_2 (Stand By)

Waseem Anum saleem


Measured By Checked B
CTS DB
Capacity Information Sheet

Location Fabric Hall#1 DB. INTERLOOP Knitting Unit Apparel

Total Capacity 63A


Total no. of breakers 25
Total no. of operational 18
breakers
Total no. of spare 7
breakers
Measured Load Current (A)
R-Y 405
INCOMING
3Ø (400-415)
Incoming Y-B 400 IRed 27.9
Supply R-B 400 IYellow 36.7
Voltage
(v) R-N 232 IBlue 30.7
P-N (220-240) Y-N 232 INeutral 1.9
B-N 230 IEarth 0
Measured

Pole
Sr # CB Rating Current (A) Size Cable Description of Equipment
R Y B

1. 28~40A 7 9 7 1x 6mm2,4 Core 4 Main Sub breaker

2. 32A 0 0 8 1x2.5 mm2,2 Core 2


IM AC

3. 32A 0 0 8 1x2.5 mm2,2 Core 2


Dispensary AC
1x2.5 mm2,2 Core
4. 32A 0 0 8 2
Lycra AC

5. 32A - - - - 2
Spare
-
6. 32A - - - 2
Spare

7. 32A - - - - 2
Spare

8. 25A 0.9 0 0 1x6 mm2,4 Core 4


ELCB Sub-breaker

9. 20A 1 0 0 1x1.5mm2,1 Core 1


Lycra Lights
10. 10A 1 0 0 1x2.5mm2,1 Core 1
Exit sign +weighing scale

11 10A 1 1 0 1x2.5mm2,1 Core 1


3 pin septical

12 10A - - - - 1
Spare

13 10A - - - - 1
Spare

14 10A - - - - 1
Spare

15 20A 7 5 5 1x6mm2,4 Core 4


MCB Sub-breaker

16 16A 0 17 0 1x2.5mm2,1 Core 1


Kitchen socket

17 16A 1 0 0 1x2.5mm2,1 Core 1


Kitchen socket

18 16A 0 1 0 1x2.5mm2,1 Core 1


IM Office socket

19 16A 0 1 0 1x2.5mm2,1 Core 1


IM Office socket

20 16A 0 1 0 1x2.5mm2,1 Core 1


Dispensary socket

21 16A 0 1 0 1x2.5mm2,1 Core 1


Dispensary Light

22 16A 0 0 0 1x2.5mm2,1 Core 1


IM office light

23 16A 0 0 0 1x1.5mm2,1 Core 1


Weighing Scale

24 40A 0 0 0 1x2.5mm2,4 Core 1


Lifter charger

25 32A - - - -
MCB Sub-breaker (Spare)

Measured By Checked By
Waseem Anum Saleem
(Electrical Technician) Sr. Engineer Electrical
Pictorial Evidence
Fabric Hall#1 DB
Load Management system Knitting Unit Apparel

OTHER FACILITIES
1 Main Source WAPDA -
2 TRANSFORMER 2000KVA (Operational) 1
3 TRANSFORMER 2500kVA (Not-Operational) 1
4 Diesel Engine 500KVA 1

UNIT LOAD
LOAD INSTALLED UNIT LOAD RUNNING RUNNING
SR. NO. MACHINE DETAILS QUNATITY INSTALLED
CURRENT (A) LOAD (KW) (KW) LOAD (KW)
(KW)
Embellishment
1 Oval Printing Machine 1 140 95.00 95 86.22 86.22
2 Curring Machine 1 10.4 8.0 8 6.41 6.41
3 Heat Transfer Machine 1 10.31 0.5 0.5 2.11 2.110
TOTAL 3.0 160.7 103.5 103.5 94.7 94.7
Total Running Load 94.7

Knitting
1 Pleece Knit Dia 34" PL-KF38-LB 8 4.5 4.62 36.96 2.77 22.17
2 Pleece Knit Dia 34" PL-KF38-LB 12 5.61 5.77 69.24 3.46 41.46
3 Single knit open Fukhuara Dia 34" OD7-M2XC-A3 2RE 15 7.3 7.5 112.5 4.50 67.44
4 Tubular knit Fukuhara Dia 30" M2XC-A3-2SRE 6 7.30 7.5 45 4.50 26.98
5 Tubular knit Fukuhara Dia 30" M2XC-2SRE 5 7.23 7.5 37.5 4.45 22.26
6 Jersey knit Dia 14" Pailung KS3B/A 1 4.50 4.62 4.62 2.77 2.77
7 Jersey knit Dia 16" Pailung KS3B/A 1 4.51 4.62 4.62 2.78 2.78
8 Jersey knit Dia 18" Pailung KS3B/A 2 4.48 4.62 9.24 2.76 5.52
9 Jersey knit Dia 20" Pailung KS3B/A 2 4.37 4.62 9.24 2.69 5.38
10 Jersey knit Dia 22" Pailung KS3B/A 1 4.26 4.62 4.62 2.62 2.62
11 Jersey knit Dia 24" Pailung KS3B/A 1 4.22 4.62 4.62 2.60 2.60
12 Jersey knit Dia 26" Pailung KS3B/A 1 4.22 4.62 4.62 2.60 2.60
13 Jersey knit Dia 34" Pailung KS3B/A 4 5.50 5.5 22 3.39 13.55
14 Jersey knit Dia 30" Pailung KS3B/A 4 5.46 5.5 22 3.36 13.45
15 Semi-jacquard Flat knitting machine Matsuya M-172SJT 4 1.10 0.23 0.92 0.23 0.90
16 Semi-jacquard Flat knitting machine Matsuya M-172SJT 1 1.00 0.23 0.23 0.20 0.20
TOTAL 68.0 75.6 76.7 387.9 45.7 158.0
Total Running Load 47.5

LOT Making
1 Roll lapping (local machine) 1 1.55 3.00 3 0.95 0.95
2 Roll unwinding (local machine) 1 1.42 1.5 1.5 0.87 0.87
3 Roll reversing (local machine) 1 15.10 7 7 9.30 9.300
4 Edge sewing (local machine) 1 2.50 3 3 1.54 1.540
TOTAL 4.0 20.6 14.5 14.5 12.7 12.7
Total Running Load 12.7

COMPRESSOR SECTION
1 Air Compressor 1 145.00 132 132 89.30 89.30
2 Air Compressor( (Stand by) 1 135.00 132 132 83.14 83.14
4 Compressor Dryer 1 9.90 9.24 9.24 6.10 6.10
5 Compressor Dryer (Stand by) 1 10.60 9.24 9.24 6.53 6.53
TOTAL 4.0 300.5 282.5 282.5 185.1 95.4
Total Running Load 95.4

AHU
1 AHU 1 133.00 85 85 81.91 81.91
2 Showring pump motor 1 37.80 22.4 22.4 23.28 23.28
3 Supply fan motor 2 45.30 15 15 27.90 55.80
4 Return fan 2 46.50 15 15 28.64 57.28
5 Rotary Motor 2 2.50 1.75 1.75 1.54 3.08
6 Blower motor 1 2.80 2.2 2.2 1.72 1.72
TOTAL 8.0 134.9 56.4 85.0 83.1 81.9
Total Running Load 81.9

Fabric Hall
1 Desert Coolar 2 6.00 7.5 15 3.695 7.39
2 Exhaust Fan 6 2.00 1.5 9 1.232 7.39
3 Battery charger stacker 1 5.60 6.1 6.1 3.449 3.45
4 Battery charger fork lifter 1 6.50 6.48 6.48 4.003 4.00
5 Jeany Charger 1 3.80 3.3 3.3 2.340 2.34
6 LED Lights 21 0.60 0.015 0.315 0.123 0.32
32.0 24.5 23.4 31.2 14.8 24.9
Total Running Load 24.9

CHILLER
1 Electric Chillers 1 200.00 164.8 164.8 123.176 123.18
2 Cooling Pump Motor (Stand by) 1 17.30 30 30 10.655 10.65
3 Cooling Water Pump Motor 1 38.20 30 30 23.527 23.53
4 Chilled Water Pump Motor (Stand by) 1 9.50 30 11 5.851 5.85
5 Chilled Pump motor 1 45.00 30 30 27.715 27.71
6 Cooling Tower 1 18.50 12 12 11.394 11.39
TOTAL 6.0 328.5 296.8 277.8 202.3 202.3
Total Running Load 202.3

Other

Miscellaneous Load (Lights+Beam emergency lights+Computers+Think Clients floor 1 35 15 15 7.165 7.16


1 mixing machine etc)
Total 1.0 35.0 15.0 15.0 7.2 7.2
Total Running Load 7.2

SUMMARY LOAD
OVERALL INSTALLED LOAD (KW) 809.5
OVERALL RUNNING LOAD (KW) 519.1
70mm²
Earth Pit# 3
HT Earthing

95mm²,1Core

LT Earthing
Earth Pit# 2
Bare Conductor

Bare Conductor
Knitting DB
95mm², 1Core
Insolated Cable

Earth Pit# 4
Transformer Earthing
MV SWITCHGEAR

Bare Conductor 70mm²


Compressor # 02
50mm², 1Core
VCB
630 A

Insolated Cable
25KA,11KV

LT Lightning DB
25mm², 1Core
(Not-Operational)

Insolated Cable
2500KVA 11000V/415V
Step Down Transformer

LOT Making Area DB


10mm², 1Core
70mm²
Earth Pit# 5

Insolated Cable
Bare Conductor
Generator Earthing
G

ACB

Compressor # 01
2500 A,3P

150mm², 1Core
Insolated Cable

Compressor Dryer #
01
4mm², 1Core
Insolated Cable

Printing Hall DB
MV SWITCHGEAR

DWG NO.

10mm², 1Core
Insolated Cable
Earthing connection Traceability / SLD

2022
VCB

Drawn By
630 A

Checked By

Approved By
Embroidery+Table
25KA,11KV

Printing Section DB
AS

MA
MA
NAME

16mm², 1Core
(Operational)

Insolated Cable
SIGN
2000KVA 11000V/415V
Step Down Transformer

DATE

10-Nov-22

Printing Heaters M/C


DB2
25mm², 1Core
NTS
SCALE

Insolated Cable
Earth Pit # 6
0/0

Hazarous Area DB 6 mm², 1Core


REV. NO.

6mm², 1Core Bare Conductor


ENGG

Insolated Cable
DEPT.

Chiller
Earth Pit #
Earthing connection Traceability / SLD

25mm², 1Core 6 mm², 1Core


Insolated Cable Bare Conductor
DWG NO.

DWG NO. 23
I

Earth Pit #
AHU
6 mm², 1Core
25mm², 1Core
Insolated Cable Bare Conductor
Printing Hall DB SLD
R Y B MCCB
100A,3P
415V,50Hz,36KA

V A
300/5

BusBar 63A 3P+N+E 415V, 50HZ, 36KA for 1sec

MCB
MCB MCB MCB MCB
28~40A,4P
20A,3P 20A,3P 20A,3P

MCB MCB MCB MCB MCB MCB


10A ,3P 10A ,3P 10A ,3P 10A ,3P MCB MCB MCB MCB MCB
32A,2P 32A,2P 32A,2P 32A ,2P 32A,2P
32A,2P

EOCR EOCR

Dryer
EOCR

Exhaust
Main

CTS DB
Water coolar DB#2
MC MC MC MC

AC
Embalishment Office
Spare
Printing

SM Office AC
Exhaust

AC
Embalishment Office
Spare

CTS Exhaust

Printing
Spare

Printing Hall Lights

MCB MCB MCB


16A ,1P 16A ,1P 16A ,1P

E EXIT
Spare
Spare
LEGENTS
MCCB

Indicating Light

Voltmeter
V
Am-meter
A

MCB

ELCB
MCB MCB MCB MCB ELCB
20A,3P 20A,3P 20A,3P 40A,4P
,3P Current TRANSFORMER

Single Phase
Three Phase
Spare
Spare
Spare

Spare

MCB MCB MCB MCB MCB MCB MCB


16A ,1P 16A ,1P 16A ,1P 16A ,1P 16A ,1P 16A ,1P 16A ,1P
g DB
Networkin
Color

Light

Office
Exit sign

Light

Power

Power
Office

Office

2022 NAME SIGN TITLEE


Printing Hall DB SLD
Drawn By AS

Checked By AS DATE SCALE REV. NO. DWG NO.


Approved By AB 17-Nov-22 NTS 0/0 DWG ILA-015
Low Gauge Cables
Rectification+
standard color
coding
Rectification of Low gauge
cables
Standard color coding

Interloop Ltd

Knitting Apparel Unit


Apparel Knitting Unit

Low gauge cables rectification & standard


color coding

Low gauge cables were found in Quality inspection machines DB


and all cables were found no standard shrouding. We have
replaced all cables with proper standard cable size and also
insertion of standard color coding for these cables

BEFORE
Quality Inspection Machine DB
Apparel Knitting Unit

After
Quality Inspection Machine DB
70mm²
Earth Pit# 3
HT Earthing

95mm²,1Core

LT Earthing
Earth Pit# 2
Bare Conductor

Bare Conductor
Knitting DB
95mm², 1Core
Insolated Cable

Earth Pit# 4
Transformer Earthing
MV SWITCHGEAR

Bare Conductor 70mm²


Compressor # 02
50mm², 1Core
VCB
630 A

Insolated Cable
25KA,11KV

LT Lightning DB
25mm², 1Core
(Not-Operational)

Insolated Cable
2500KVA 11000V/415V
Step Down Transformer

LOT Making Area DB


10mm², 1Core
70mm²
Earth Pit# 5

Insolated Cable
Bare Conductor
Generator Earthing
G

ACB

Compressor # 01
2500 A,3P

150mm², 1Core
Insolated Cable

Compressor Dryer #
01
4mm², 1Core
Insolated Cable

Printing Hall DB
MV SWITCHGEAR

DWG NO.

10mm², 1Core
Insolated Cable
Earthing connection Traceability / SLD

2022
VCB

Drawn By
630 A

Checked By

Approved By
Embroidery+Table
25KA,11KV

Printing Section DB
AS

MA
MA
NAME

16mm², 1Core
(Operational)

Insolated Cable
SIGN
2000KVA 11000V/415V
Step Down Transformer

DATE

10-Nov-22

Printing Heaters M/C


DB2
25mm², 1Core
NTS
SCALE

Insolated Cable
Earth Pit # 6
0/0

Hazarous Area DB 6 mm², 1Core


REV. NO.

6mm², 1Core Bare Conductor


ENGG

Insolated Cable
DEPT.

Chiller
Earth Pit #
Earthing connection Traceability / SLD

25mm², 1Core 6 mm², 1Core


Insolated Cable Bare Conductor
DWG NO.

DWG NO. 23
I

Earth Pit #
AHU
6 mm², 1Core
25mm², 1Core
Insolated Cable Bare Conductor
Power Cables
Tagging
LT Panels main Cables
DBs main power cables
SDBs main power cables

Interloop Ltd

Knitting Apparel Unit


Apparel Knitting Unit

Power Cables Tagging

1) LT Panel Power cables

Generator outgoing cables


Apparel Knitting Unit

Wapda ACB outgoing cables


Apparel Knitting Unit
Apparel Knitting Unit

2) DBs / SDBs
Spare LT panel
bottom opening
rectification
Apparel Knitting Unit

Spare LT panel bottom side opening


closed
An opening was present on incoming side of spare ACB side in LT
panel (Non-Operational panel). The issue has been rectified and
picture is attached for evidence.
Neutral & Earthing
Points terminations

[Type the company name]

[Type the company address]

[Type the phone number]

[Type the fax number]

[Pick the date]


Apparel Knitting Unit

Cables Terminations

Two Neutral cables were connected on same point on neutral bus bar. The issue
has been rectified by removing double point termination. Same as earthing
cables were commonly connect to same point.

The pictorial evidences are below:-

BEFORE
Apparel Knitting Unit

AFTER