Content

4 1. Driven by innovation: the 5000 Series


5 2. Introduction to the new panel
development

3. Housing types
6 3.1 For wall mounting
7 3.2 For frame installation

8 4. Modular design of the


Modular Fire Panel 5000 Series

10 5. Overview of the “ease of use“


operating concept

11 6. Modular components

16 7. Technical specifications
5
1 Driven by innovation: 2 Introduction to the
the 5000 Series new panel development

The Modular Fire Panel 5000 Series is the latest innovative product
of the successful Bosch development department. The new innovative Modular Fire Panel 5000 Series with its unique modular
design adapts perfectly to local conditions and regulations
One panel can handle up to 46 modules with maximum 32 addressable
loops. A stand alone panel can operate up to 4064 addressable devices,
networked panels up to 2048
One addressable loop can handle up to 254 LSNi elements
Max. loop length: 3000 m, max. loop current: up to 1500 mA
Allows the installation of addressable and conventional elements on the
panel
Up to 10.000 events can be stored in the history log
Each panel can be equipped with up to 4 simcards. One slot can also be
used for the integration of the OPC licence key. Available are address cards
with 512, 1024 and 2048 address points
EVAC Voice Alarm Two cabinet versions are available with extension housings for all
System from Bosch
Serial Interface conceivable applications
5000 Series – Wall mount version: Housing is directly mounted to the wall
– Frame mount version: Housings are hinged into special mounting frames
Remote Ethernet OPC Clearly structured operating menu and displays provide a quick overview
Keypad (RK)
“Ease of Use”, one of the most important user requirements is completely
CAN-Bus
fulfilled thanks to the intuitive user guidance
Building Integration Thanks to the modular housing design and the hot-plug feature the system
System (BIS)
Panel Network can be expanded easily to meet the growing needs
Click and go: Modules are automatically power supplied after being
plugged to the rail
Five good reasons to choose the Modular Fire Panel 5000 Series
Read out of diagnostic data directly on the panel possible
• You get exactly what you need Bosch Voice EVAC System (Digital Public Address and Emergency Sound
• It grows with your requirements System) can be connected via serial interface
A minimum of 16 panels can be networked through the external CAN Bus
• Modules for unbeatable flexibility
Several remote keypads can be integrated to one panel or a panel network
• Easy to install and maintain
through the CAN Bus
• Optimized storage Panel network possible via Fibre Optics
3 Housing types | 7
3 Housing types 3.2 Frame mounting

CPH 0006 A MPH 0010 A EPH 0012 A


Modular Panel Housing Modular Panel Housing Extension Housing
for 6 Modules, Frame Installation for 10 Modules, for 12 Modules, Frame Installation
Frame Installation

3.1 Wall mounting

HCP 0006 A HBC 0010 A HBE 0012 A


Modular Panel Housing Modular Panel Housing Modular Extension Housing
for up to 6 modules for 10 Modules for 12 Modules

PSF 0002 A PMF 0004 A FDT 000X A


Power Supply Small, Power Supply Big, Front door, 4 types (optional)
Frame Installation Frame Installation

FDT 000X A FRK 0019 A PSS 0002 A FSH 0000 A FMH 0000 A FBH 0000 A
Front door, 4 types (optional) 19" Rack Installation Kit Power Supply Small Mounting Frame Small Mounting Frame Medium Mounting Frame Large

PSB 0004 A FRS 0019 A FRM 0019 A FRB 0019 A


Power Supply 19" Rack Installation Kit, Small 19" Rack Installation Kit, Medium 19" Rack Installation Kit, Large
4 Modular design of the Modular Fire Panel 5000 Series | 9
4 Modular design of the
Modular Fire Panel 5000 Series

Address Cards OPC License Key

Panel Housing

Modules

Alarm
Test

A-5000
FP

93115589000024
Transmission Device
activated
x100 x10 x1
Bypassed Bypass
Diagnostics
M
P
C0000AM
ainP
anelC
ontrolerD
EE
NIT4.998.137.257
Isolate
Transmission Device
bypassed
Signals bypassed Maintenance Configuration

Power
Switch to day mode Further functions
Fault

Fault system Search Function/ Reset


Fault Transmission Element
Device

OPEN
Fault Signals 0 0 0 0 Status
Fire Control Fault Bypass

Short Rail
Main Panel Controller with Touch Screen

Power Supply Bracket


Long Rail

Der Temperatursensor
wird zwischen den
Baterien befestigt!
Modules Battery Battery Power Supply Unit
11
5 Overview of the “ease of use” 6 Modular components
operating concept

Status LEDs Fixed membrane key, opens a Fixed membrane


menu for networking of fire panels keys for The panel controller is the central operating unit of
MPC XX00 B
alphanumeric Operating and Display Unit with Panel the fire panel. All messages are indicated on the
inputs Controller X-XX display and all operating keys are located on the
Touch-sensitive operating operating surface. A LCD touch display is used as
area with virtual keys to display and keypad.
Fixed membrane key,
indicate operating menus 22 fixed membrane keys are used for standard
opens a window with service
and message windows operating steps. The current status of the system is
information
Alarm
displayed by 11 LEDs.
- CAN-Bus interface (for panel networking)
A-5000
FP

93115589000024
x100 x10 x1
M
P
C0000AM
ainP
anelC
ontrolerD
EE
NIT4.998.137.257

OPEN
- USB interface
Alarm
Test
- RS 232 interface,
Transmission Device
activated - Ethernet interface (for integration to BIS)
Bypassed Bypass
Diagnostics
Isolate
Transmission Device
bypassed
Signals bypassed Maintenance Configuration

Power
Switch to day mode Further functions
Fault

The universal power supply unit in plug-in design with


UPS 2416 A
Fault system Search Function/ Reset
Element
rack and panel connectors is a 24 V DC single output
Fault Transmission

Universal Power Supply


Device
Fault Signals 0 0 0 0 Status
Fire Control Fault Bypass
power supply with 6 A output current.
The power supply unit is protected against overvoltage
and reverse polarity.
The output voltage is monitored and regulated
externally.

Optional key switch, Info bar Fixed membrane key, Fixed membrane key,
e.g. for manual to go back to used for confirmation
day-night mode the previous menu of inputs
changeover
Slide-in and connection carrier for the power supply
FPO 5000 PSB CH /
Fixed membrane key, opens Fixed membrane key, Fixed membrane key, unit “UPS 2416 A”.
FPO 5000 PSB1 / FPO 5000 PSB2
the main operation menu opens a menu for operator to switch off the internal Power Supply Bracket The carrier consists of glass fibre reinforced plastic
code input buzzer and includes the pre-wired rack and panel connectors
for the power supply units.
The FPO 5000 PSB CH Power Supply Bracket provides
The basic functions are assigned to fixed membrane keys. The new operating an additional fuse at the mains supply terminal.

concept makes it possible to change the language simply by pressing a special


key sequence. Diagnostic data can be read out directly at the panel.
12 | 6 Modular components 6 Modular components | 13

The short plug-in and connection carrier for up to 2 The analog addressable line module enables the
PRS 0002 A LSN 1500 A
Panel Rail Short modules consists of glass fibre reinforced plastic and LSN improved Module 1500 mA installation of a loop or two stubs with up to 254
includes rack and panel connectors. addressable detectors and devices and provides 1500
The two modules on the rail are power supplied mA line current. It occupies the position of two
(+5 V / GND) directly from the Main Panel Controller standard modules.
(MPC).

The long plug-in and connection carrier for up to 4 It enables the installation of up to 4 supervised
PRD 0004 A CZM 0004 A
Panel Rail Long modules consists of glass fibre reinforced plastic and 4 Zone Conventional Module conventional zones for conventional 2-wire detectors
includes rack and panel connectors. and dry contact type devices.
The long panel rails are equipped with a DC/DC
converter to generate the +5 V operating voltage for
the modules and are power supplied (+24 V / GND) via
the “BCM 0000 A” battery controller module.

The “BCM 0000 B” module is the control unit for the


BCM 0000 B
Battery Controller Module power supply of the complete panel. It monitors and
distributes the complete power and controls the
The annunciator module with 16 red and 16 yellow
charging of up to 4 batteries (12 V / 28 Ah resp. 40 Ah). ANI 0016 A
Annunciator Module LEDs enables the indication of alarms or messages
at 16 different points. These points can be
programmed freely.

The analog addressable line module enables the


LSN 0300 A
LSN improved Module 300 mA installation of a loop or two stubs with up to 254 It enables the installation of 2 supervised conventional
addressable detectors and devices. It provides a NZM 0002 A
Notification Appliance Zone Module notification appliance zones.
max. of 300mA line current. The module operates style Y (stub) and Z (loop):
• Sounders
• Strobes
• Horns
• Synchronisation of the outputs is possible
14 | 6 Modular components 6 Modular components | 15

2 circuit form-C relay module with feedback. Each This communication module provides two S20
RMH 0002 A FPE 5000 UGM
Relay Module output (not supervised) is equipped with normally Interface Module interfaces and the MTS/4A communication protocol to
opened (NO) and normally closed (NC) contact. the UGM. The two S20 interfaces of the module are
Can also be used as releasing interface (VdS). connected to the SGK or the SGK2 card at the UGM.

The low voltage relay module provides 8 form C This communication module provides two independent
RML 0008 A IOS 0232 A
Relay Module relay outputs to switch external loads. RS232 Communication Module RS232 interfaces to connect e. g. a printer or a laptop.
Each output is equipped with normally opened (NO)
and normally closed (NC) contact.

The “IOP 0008 A” input/output module provides This module enables the connection of fire service
IOP 0008 A ENO 0000 B
Input/Output Module 8 independent digital inputs for handling signals Fire Service Interface Module devices as per DIN 14675:
with TTL-level and 8 open-collector outputs for • Transmission device to the fire brigade
individual indication use. • Key deposit
• Pilot lamp for the key deposit
• Monitoring of a release unit
• 4 relays

The 20 mA communication module provides a S1 All messages are indicated on the display and all
IOS 0020 A FMR 5000
20 mA Communication Module interface used for dialer (AT2000), a RS232 interface Remote Keypad operating keys are located on the operating surface.
used for serial printers and a S20 interface to connect A LCD touch display is used as display and keypad.
the DR2020 log printer. 22 fixed membrane keys are used for standard
Alarm
operating steps. The current status of the system is
displayed by 11 LEDs.
• CAN-Bus interface for connection to the panel
• Wall and Flash mount
7 Technical specifications | 17
7 Technical specifications

MPC XX00 B Operating and Display Unit with Panel Controller X-XX FPO 5000 PSB CH Power Supply Bracket

Touch panel type Resistive type, analog, 4 wires, film on glass Operating Temperature -5 °C ... 50 °C (23 °F ... 122 °F)
Display element 320 x 240 dots LCD Touch panel Storage Temperature -20 °C ... 60 °C ( -4 °F ... 140 °F)
with flexible keys and displays Material PA6 plastic Grilon BS V0 (UL94 V-0)
Active touch area (H x W) 127.5 mm x 170 mm Color Satin finish anthrazit, RAL 7016
Fix operating elements 22 membrane keys Dimensions (H x W x D) approx. 240 x 305 x 65 mm (9.4 x 12.0 x 2.6 inches)
Status displays 11 LEDs
Interfaces CAN1, CAN2, Ethernet (RJ45), USB, RS232
Maximum length of CAN cable Lmax = 1000 m, depending FPO 5000 PSB1 Power Supply Bracket
on configuration and cable type at panel networking
Input voltage range 20 V DC ... 30 V DC Operating Temperature -5 °C ... 50 °C (23 °F ... 122 °F)
Output voltage to PRS 0002 A +5 V DC 4,5 % / max. 500 mA output current Storage Temperature -20 °C ... 60 °C ( -4 °F ... 140 °F)
Maximum current consumption Material PA6 plastic Grilon BS V0 (UL94 V-0)
- standby mode 120 mA Color Satin finish anthrazit, RAL 7016
- alarm mode 205 mA Dimensions (H x W x D) approx. 240 x 205 x 125 mm (9.4 x 8.0 x 4.9 inches)
Operating temperature -5 °C ... 50 °C (23 °F ... 122 °F)
Storage temperature -20 °C ... 70 °C (-4 °F ... 158 °F)
FPO 5000 PSB2 Power Supply Bracket
Dimensions (H x W x D) approx. 190 x 404 x 60 mm
Weight approx. 2000 g
Operating Temperature -5 °C ... 50 °C (23 °F ... 122 °F)
Storage Temperature -20 °C ... 60 °C ( -4 °F ... 140 °F)
UPS 2416 A Universal Power Supply Material PA6 plastic Grilon BS V0 (UL94 V-0)
Color Satin finish anthrazit, RAL 7016
Input voltage (min - max) 100 - 240 V AC Dimensions (H x W x D) approx. 220 x 175 x 115 mm (8.6 x 6.8 x 4.5 inches)
Input frequency range 47 - 63 Hz
Efficiency 85 %
PRS 0002 A Panel Rail Short
Hold up time > 60 ms at 230 V AC
> 16 ms at 115 V AC
Input voltage +5 V DC via MPC / +24 V DC via BCM
Output voltage 26 V DC … 29 V DC
Output voltage +24 V DC
Maximum load 6A
Operating Temperature -5 °C ... 50 °C (23 °F ... 122 °F)
Continuous output power 160 W
Storage Temperature -20 °C ... 60 °C (-4 °F ... 140 °F)
Safety standards EN 60950
Material ABS plastic Polylac PA-766 (UL94 V-0)
Operating Temperature -5 °C ... 50 °C (23 °F ... 122 °F)
Color Satin finish anthrazit, RAL 7016
Storage Temperature -20 °C ... 60 °C (-4 °F ... 140 °F)
Dimensions (H x W x D) approx. 146 x 216 x 35 mm (5.7 x 8.5 x 1.4 inches)
Cooling Convection without fan
Weight approx. 135 g (4.8 ounces)
Housing material Steel /Aluminium, anodized
Housing color Matt black
Dimensions (H x W x D) approx. 200 x 100 x 40 mm (7.9 x 3.9 x 1.6 inches)
Weight approx. 780 g (27.5 ounces)
18 | 7 Technical specifications 7 Technical specifications | 19

PRD 0004 A Panel Rail Long LSN 0300 A LSN improved Module 300 mA

Input voltage (min - max) 24 V DC via BCM Indication / operation elements 2 LEDs (1x red, 1x yellow) / 1 Key
Output voltage + 5 V DC 4.5% / +24 V DC via BCM 0000A Input voltage (min - max) 20 V DC - 30 V DC, 5V DC ±5%
Maximum input current 8 A at 24 V DC Max. current consumption
Maximum output current 1 A at 5 V DC - standby mode 36 mA plus 1.7 x current of elements
Operating Temperature -5 °C ... 50 °C (23 °F ... 122 °F) - alarm mode 39 mA plus 1.7 x current of elements
Storage Temperature -20 °C ... 60 °C (-4 °F ... 140 °F) Line length max. 1000 m (3280 ft.)
Material ABS plastic Polylac PA-766 (UL94 V-0) Number of elements max. 254 LSNi Elements
Color Satin finish anthrazit, RAL 7016 Loop current max. 300 mA
Dimensions (H x W x D) approx. 146 x 396 x 35 mm (5.7 x 15.6 x 1.4 inches) Max. auxilliary power supply 500 mA
Weight approx. 320 g Safety standards IEC 60950 / EN 60950
Operating Temperature -5 °C ... 50 °C (23 °F ... 122 °F)
Storage Temperature -20 °C ... 60 °C (-4 °F ... 140 °F)
BCM 0000 B Battery Controller Module Housing material and color ABS plastic Polylac PA-766 (UL94 V-0),
Satin finish anthrazit, RAL 7016
Indication / operation elements 1 LED green (Main Power On) Permissible relative humidity max. 95 % non condensing
3 LEDs yellow (Main power fault, Battery 1/2 fault) Dimensions (H x W x D) approx. 127 x 96 x 60 mm (5.0 x 3.8 x 2.4 inches)
Start key (to charge batteries with U < 22 V
Weight approx. 225 g (7.9 ounces)
and to start-up the fire panel only with battery power)
Input voltage (min - max) 20 V DC - 30 V DC
Current consumption at 24 V DC 31 mA (standby) / 40 mA (battery fault) LSN 1500 A LSN improved Module 1500 mA
Safety standards IEC 60950 / EN 60950
Outputs 2 outputs Indication / operation elements 2 LEDs (1x red, 1x yellow) / 1 Key
2.8 A each Input voltage (min - max) 20 V DC - 30 V DC
Operating Temperature -5 °C ... 50 °C (23 °F ... 122 °F) Max. current consumption
Storage Temperature -20 °C ... 60 °C (-4 °F ... 140 °F) - standby mode 165 mA plus 1.1 x current of elements
Permissible relative humidity max. 95 % non condensing - alarm mode 170 mA plus 1.1 x current of elements
Housing material and color ABS plastic Polylac PA-766 (UL94 V-0), Line length max. 3000 m (3281 yards)
Satin finish anthrazit, RAL 7016 Number of elements max. 254 LSNi Elements
Dimensions (H x W x D) approx.127 x 96 x 60 mm (5.0 x 3.8 x 2.4 inches) Loop current max. 1500 mA
Weight approx. 185 g (6.5 ounces) Max. auxilliary power supply 500 mA
Safety standards IEC 60950 / EN 60950
Operating Temperature -5 °C ... 50 °C (23 °F ... 122 °F)
Storage Temperature -20 °C ... 60 °C (-4 °F ... 140 °F)
Housing material and color ABS plastic Polylac PA-766 (UL94 V-0),
Satin finish anthrazit, RAL 7016
Permissible relative humidity max. 95 % non condensing
Dimensions (H x W x D) approx. 127 x 200 x 60 mm (5.0 x 7.6 x 2.4 inches)
Weight approx. 450 g
20 | 7 Technical specifications 7 Technical specifications | 21

CZM 0004 A 4 Zone Conventional Module NZM 0002 A Notification Appliance Zone Module

Indication / operation elements 8 LEDs (4x red, 4x yellow) / 4 keys Indication / operation elements 4 LEDs (2x red, 2x yellow) / 2 Keys
Input voltage (min - max) 20 V DC - 30 V DC / 5 V DC ±5 % Input voltage (min - max) 20 V DC - 30 V DC / 5 V DC ±5 %
Maximum current consumption Current consumption
- standby mode (4 zones) 65 mA (at 24 V DC) - standby mode (2 zones) 40 mA (at 24 V DC)
- alarm mode (4 zones) 65 mA + 100 mA per zone (at 24 V DC) - alarm mode (2 zones) 65 mA (at 24 V DC)
Maximum output voltage 20 V DC ± 10 % Maximum output voltage 29.5 V DC
Maximum output current 100 mA Maximum output current 500 mA per NAC output (in Alarm mode)
Safety standards IEC 60950 / EN 60950 Safety standards IEC 60950 / EN 60950
Operating Temperature -5 °C ... 50 °C (23 °F ... 122 °F) Operating Temperature -5 °C ... 50 °C (23 °F ... 122 °F)
Storage Temperature -20 °C ... 60 °C (-4 °F ... 140 °F) Storage Temperature -20 °C ... 60 °C (-4 °F ... 140 °F)
Permissible relative humidity max. 95 % non condensing Permissible relative humidity max. 95 % non condensing
Housing material and color ABS plastic Polylac PA-766 (UL94 V-0), Housing material and color ABS plastic Polylac PA-766 (UL94 V-0),
Satin finish anthrazit, RAL 7016 Satin finish anthrazit, RAL 7016
Dimensions (H x W x D) approx. 127 x 96 x 60 mm (5.0 x 3.8 x 2.4 inches) Dimensions (H x W x D) approx. 127 x 96 x 60 mm (5.0 x 3.8 x 2.4 inches)
Weight approx. 270 g (9.5 ounces) Weight approx. 135 g (4.8 ounces)

ANI 0016 A Annunciator Module RMH 0002 A Relay Module

Indication elements 32 LEDs (16x red, 16x yellow) Indication / operation elements 4 LEDs (2x red, 2x yellow) / 2 Keys
Input voltage (min - max) 20 V DC - 30 V DC / 5 V DC ±5 % Fuses F1 = T 6.3 A F2 = T 6.3 A
Maximum current consumption Input voltage (min - max) 20 V DC - 30 V DC / 5 V DC ±5 %
- standby mode (all LEDs OFF) 6 mA (at 24 V DC) Feedback current Maximum 4.5 mA per relay
- alarm mode (all LEDs ON) 26 mA (at 24 V DC) Feedback output voltage max. 30 V DC
Safety standards IEC 60950 / EN 60950 Maximum current consumption
Operating Temperature -5 °C ... 50 °C (23 °F ... 122 °F) - standby mode 10 mA (at 24 V DC)
Storage Temperature -20 °C ... 60 °C (-4 °F ... 140 °F) - with both relays actuated 50 mA (at 24 V DC)
Permissible relative humidity max. 95 % non condensing Max. relay contact rating 5 A at 120 V / 230 V AC or 5 A at 30 V DC
Housing material and color ABS plastic Polylac PA-766 (UL94 V-0), Safety standards IEC 60950 / EN 60950
Satin finish anthrazit, RAL 7016 Operating Temperature -5 °C ... 50 °C (23 °F ... 122 °F)
Dimensions (H x W x D) approx. 127 x 96 x 60 mm (5.0 x 3.8 x 2.4 inches) Storage Temperature -20 °C ... 60 °C (-4 °F ... 140 °F)
Weight approx. 206 g (7.3 ounces) Permissible relative humidity max. 95 %
Housing material and color ABS plastic Cycolac VW300 (UL94 5 VA),
Satin finish anthrazit, RAL 7016
Dimensions (H x W x D) approx. 127 x 96 x 60 mm (5.0 x 3.8 x 2.4 inches)
Weight approx. 135 g (4.8 ounces)
22 | 7 Technical specifications 7 Technical specifications | 23

RML 0008 A Relay Module IOS 0020 A 20 mA Communication Module

Input voltage (min - max) 20 V DC - 30 V DC / 5 V DC ± 5 % Input voltage (min - max) 20 V DC - 30 V DC / 5 V DC ± 5 %


Max. current consumption Max. current consumption 15 mA (at 24 V DC)
- standby mode 4 mA (at 24 V DC) Auxiliary Voltage Output 1.3 A at 24 V DC (at the 20 mA interface)
- all relays actuated 68 mA (at 24 V DC) Maximum length of line 20 mA : 1000 m (3280 ft.), RS 232 : 3 m (10 ft.)
Max. relay contact rating at 30 V DC / 1 A Safety class II as per IEC 60950 / EN 60950
Safety class II as per IEC 60950 / EN 60950 Protection class IP 30 as per IEC 60529
Protection class IP 30 as per IEC 60529 Operating Temperature -5 °C ... 50 °C (23 °F ... 122 °F)
Over voltage protection 2 kV as per EN 54 / UL864 Storage Temperature -20 °C ... 60 °C (-4 °F ... 140 °F)
Operating Temperature -5 °C ... 50 °C (23 °F ... 122 °F) Permissible relative humidity max. 95 % non condensing
Storage Temperature -20 °C ... 60 °C (-4 °F ... 140 °F) Housing material and color ABS plastic Polylac PA-766 (UL94 V-0),
Permissible relative humidity max. 95 % non condensing Satin finish anthrazit, RAL 7016
Housing material and color ABS plastic Polylac PA-766 (UL94 V-0), Dimensions (H x W x D) approx. 127 x 96 x 60 mm (5.0 x 3.8 x 2.4 inches)
Satin finish anthrazit, RAL 7016 Weight approx. 175 g (6.2 ounces)
Dimensions (H x W x D) approx. 127 x 96 x 60 mm (5.0 x 3.8 x 2.4 inches)
Weight approx. 150 g (5.3 ounces)
FPE-5000-UGM Interface Module

IOP 0008 A Input/Output Module Input voltage (min - max) 20 V DC - 30 V DC / 5 V DC ± 5 %


Max. current consumption 15 mA (at 24 V DC)
Input voltage (min - max) 20 V DC - 30 V DC / 5 V DC ± 5 % Maximum length of line 20 mA : 1000 m (3280 ft.), 2 S20 interfaces
Max. current consumption 10 mA (at 24 V DC) Safety class II as per IEC 60950 / EN 60950
Maximum sink current 700 mA (short protected, Imax = 1.3 A) Protection class IP 30 as per IEC 60529
Maximum length of lines 3 m (10 ft.) per input/output Operating Temperature -5 °C ... 50 °C (23 °F ... 122 °F)
Safety class II as per IEC 60950 / EN 60950 Storage Temperature -20 °C ... 60 °C (-4 °F ... 140 °F)
Protection class IP 30 as per IEC 60529 Permissible relative humidity max. 95 % non condensing
Operating Temperature -5 °C ... 50 °C (23 °F ... 122 °F) Housing material and color ABS plastic Polylac PA-766 (UL94 V-0),
Storage Temperature -20 °C ... 60 °C (-4 °F ... 140 °F) Satin finish anthrazit, RAL 7016
Permissible relative humidity max. 95 % non condensing Dimensions (H x W x D) approx. 127 x 96 x 60 mm (5.0 x 3.8 x 2.4 inches)
Housing material and color ABS plastic Polylac PA-766 (UL94 V-0), Weight approx. 175 g (6.2 ounces)
Satin finish anthrazit, RAL 7016
Dimensions (H x W x D) approx. 127 x 96 x 60 mm (5.0 x 3.8 x 2.4 inches)
Weight approx. 150 g (5.3 ounces)
24 | 7 Technical specifications | 25

IOS 0232 A RS232 Communication Module

Input voltage (min - max) 20 V DC - 30 V DC / 5 V DC ±5 %


Max. current consumption 15 mA (at 24 V DC)
Maximum length of line 3 m (10 ft.) per interface
Safety class II as per IEC 60950 / EN 60950
Protection class IP 30 as per IEC 60529
Operating Temperature -5 °C ... 50 °C (23 °F ... 122 °F)
Storage Temperature -20 °C ... 60 °C (-4 °F ... 140 °F)
Permissible relative humidity max. 95 % non condensing
Housing material and color ABS plastic Polylac PA-766 (UL94 V-0),
Satin finish anthrazit, RAL 7016
Dimensions (H x W x D) approx. 127 x 96 x 60 mm (5.0 x 3.8 x 2.4 inches)
Weight approx. 180 g (6.3 ounces)

ENO 0000 B Fire Service Interface Module

Input voltage (min - max) 20 V DC - 30 V DC / 5 V DC ± 5 %


Safety class II as per IEC 60950 / EN 60950
Protection class EN 50081-1 / FCC Part 15
Contact rating 1 A at 30 V DC
Operating Temperature -5 °C ... 50 °C (23 °F ... 122 °F)
Storage Temperature -20 °C ... 60 °C (-4 °F ... 140 °F)
Max. current consumption 25 mA (at 24 V DC)
60 mA all relay triggered
Permissible relative humidity max. 95 % non condensing
Housing material and color ABS plastic Polylac PA-766 (UL94 V-0),
Satin finish anthrazit, RAL 7016
Dimensions (H x W x D) approx. 127 x 96 x 60 mm (5.0 x 3.8 x 2.4 inches)
Weight approx. 150 g (5.3 ounces)

FMR-5000 Remote Keypad EVAC Voice Alarm


System from Bosch
Specification same as MPC XX00 B, except: Serial Interface

Input voltage (min - max) 11 V DC - 30 V DC 5000 Series

Output voltage to PRS 0002 not available


Remote Ethernet OPC
Max. current consumption 130 mA Keypad (RK)
225 mA
CAN-Bus
Dimensions (H x W x D) approx. 280 x 340 x 87 mm (11.0 x 13.4 x 3.4 inches)
Building Integration
System (BIS)
Panel Network
26 | Notes | 27