0231216
Application
Monitoring of industrial plants and buildings
Indication
S5 S6 It must be observed, that the fault inputs are not seperated from the
supply voltage (common terminal A2/N). In case of DC-signals the minus-
A1 11 S1 S2 X3 X1 X2 pole always to be connected to A2.
By removing the bridges X1/X3 - X1/X2 on the backside, the function of
A1 S1...S6 11
the fault signal can be changed, so that the faults 5 and 6 will only be
indicated optically and the output relay will not be influenced.
EH 9997.11 EH 9997.11 AC 220 ... 240 V 50/60 Hz AC/DC 160 ... 300 V
Article number: 0013214 stock item
· Output: 1 changeover contact
· Nominal voltage UN: AC 220 ... 240 V
· Inputs: AC/DC 160 ... 300 V
Variants
EH 9997/013: During function test, common signal will
not be operated
EH 9997/074: Open circuit operation
EH 9997/075: 8 signals; all stored, indicated and
switching common output
Technical data
Input
All technical data in this list relate to the state at the moment of edition. We reserve the right
for technical improvements and changes at any time. 1 EH 9997 / 31.10.01 d
Technical data Connection example
Contacts A1 S1...S6 11
EH 9997.11: 1 changeover contact undelayed
Thermal current I th: 6A EH9997
Switching capacity
to AC 15 A2 N 12 14
NO contact: 10 A / 230 V EN 60 947-5-1
NC contact: 5 A / 230 V EN 60 947-5-1 12 14 S3 S4 S5 S6 A2/N
Electrical life EN 60 947-5-1 S
to AC 15 at 3 A, AC 230 V: 0,1 x 106 switching cycles
Short circuit strength
e.g.
max. fuse rating: 6 AgL EN 60 947-5-1
motor contactor
Mechanical life: > 30 x 10 6 switching cycles N (L-)
M7609
General data
Ordering example
EH 9997 .11 /_ _ _ AC 230 ... 240 V AC/DC 160 ... 300 V 50/60 Hz
Nominal frequency
Inputs
Nominal voltage
Variant, if required
Contacts
Type
Dimensions