3767 Manual

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 56

Electropneumatic Positioner

Type 3767

Fig. 1
2 · Type 3767

Mounting and
Operating Instructions

EB 8355-2 EN
Edition March 2004
Contents

Contents Page
1 Design and principle of operation . . . . . . . . . . . . . . . . . . . 4
1.1 Versions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
1.2 Technical data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
2 Attachment to control valve . . . . . . . . . . . . . . . . . . . . . . 10
2.1 Direct attachment to Type 3277 Actuator . . . . . . . . . . . . . . . . 10
2.2 Attachment according to IEC 60534-6 . . . . . . . . . . . . . . . . . 15
2.2.1 Mounting sequence . . . . . . . . . . . . . . . . . . . . . . . . . . 16
2.2.2 Presetting the travel . . . . . . . . . . . . . . . . . . . . . . . . . . 16
2.3 Atttachment to rotary actuators . . . . . . . . . . . . . . . . . . . . 19
2.3.1 Mounting the cam follower lever . . . . . . . . . . . . . . . . . . . . 20
2.3.2 Mounting the intermediate piece . . . . . . . . . . . . . . . . . . . . 20
2.3.3 Default setting of the cam disk . . . . . . . . . . . . . . . . . . . . . 22
2.3.4 Reversing amplifier for double-acting actuators . . . . . . . . . . . . . 26
3 Connections. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
3.1 Pneumatic connections . . . . . . . . . . . . . . . . . . . . . . . . 28
3.1.1 Pressure gauge . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
3.1.2 Supply pressure . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
3.2 Electrical connections . . . . . . . . . . . . . . . . . . . . . . . . . 30
3.2.1 Switching amplifiers . . . . . . . . . . . . . . . . . . . . . . . . . . 31
4 Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
4.1 Adjusting the positioner at the valve . . . . . . . . . . . . . . . . . . 32
4.1.1 Adjusting the proportional band Xp and air delivery Q . . . . . . . . . 33
4.1.2 Adjusting the actuator: "Actuator stem extends" . . . . . . . . . . . . 33
4.1.3 Adjusting the actuator: "Actuator stem retracts". . . . . . . . . . . . . 34
4.2 Changing the operating direction . . . . . . . . . . . . . . . . . . . 35
4.3 Adjusting the limit switches . . . . . . . . . . . . . . . . . . . . . . 36
4.4 Adjusting the position transmitter. . . . . . . . . . . . . . . . . . . . 38
5 Converting and retrofitting the positioner . . . . . . . . . . . . . . . 40
5.1 Converting from electropneumatic to pneumatic . . . . . . . . . . . . 40
5.2 Fitting limit switches . . . . . . . . . . . . . . . . . . . . . . . . . . 41
5.3 Fitting a solenoid valve . . . . . . . . . . . . . . . . . . . . . . . . 41
5.4 Removing the solenoid valve . . . . . . . . . . . . . . . . . . . . . . 42
6 Servicing explosion-protected versions . . . . . . . . . . . . . . . . 42
7 Dimensions in mm . . . . . . . . . . . . . . . . . . . . . . . . . . 43

2 EB 8355-2 EN
Safety instructions

4 The positioner may only be assembled, started up or operated by trained


and experienced personnel familiar with the product.
According to these mounting and operating instructions, trained personnel is
referred to as individuals who are able to judge the work they are assigned
to and recognize possible dangers due to their specialized training, their
knowledge and experience as well as their knowledge of the relevant stan-
dards.
4 Explosion-protected versions of this positioner may only be operated by per-
sonnel who have undergone special training or instructions or who are au-
thorized to work on explosion-protected devices in hazardous areas. Refer
to section 6 on Servicing explosion-protected versions.
4 Any hazards that could be caused by the process medium, the operating
pressure, the signal pressure or by moving parts of the control valve are to
be prevented by means of the appropriate measures. If inadmissible motions
or forces are produced in the actuator as a result of the supply pressure
level, it must be restricted by means of a suitable supply pressure reducing
station.
4 Proper shipping and appropriate storage are assumed.

4 Note! The device with a CE marking fulfils the requirements of the Directives
94/9/EC (ATEX) and 89/336/EEC (EMC).
The declaration of conformity can be viewed and downloaded on the
Internet at http://www.samson.de.

EB 8355-2 EN 3
Design and principle of operation

1 Design and principle of aphragm lever (flapper plate). Any change


operation in the reference variable or the valve stem
position cause the pressure to change up-
The positioner consists of an electro- stream or downstream of the booster. The
pneumatic converter unit (i/p converter) and air controlled by the booster (signal pressure
a pneumatic unit equipped with a lever for pst) flows through the volume restriction (11)
travel pick-up, a measuring diaphragm, and to the pneumatic actuator, causing the plug
the pneumatic control system with nozzle, stem to move to a position corresponding to
diaphragm lever (flapper plate), and the DC input signal (reference variable).
booster. The adjustable Xp restriction (8) and volume
The positioner is designed either for direct restriction (11) are used to optimize the
attachment to SAMSON Type 3277 Actua- positioner control loop. The pick-up lever (1)
tors or for attachment according to NAMUR and the range spring (4) must be selected to
(IEC 60534-6) with an adapter housing. match the rated valve travel and the nominal
The positioner can be additionally equipped span of the reference variable.
with either inductive limit switches and/or a
solenoid valve or a position transmitter. Positioner with inductive limit switches
The DC control signal, e.g. 4 to 20 mA, is- In this version, the rotary shaft of the
sued by the control unit is transmitted to the positioner carries two adjustable tags which
electropneumatic conversion unit (13) where actuate the built-in proximity switches.
it is converted into a proportional pressure
signal pe. Positioner with solenoid valve
The positioner operates according to the
force-balance principle. The valve travel, i.e. When the positioner is equipped with a so-
the valve position, is transmitted to the lenoid valve, the control valve can be moved
pick-up lever (1) over the pin (1.1) and de- to the fail-safe position regardless of the
termines the force of the measuring spring positioner's output signal. If a control signal
(4). This force is compared to the positioning corresponding to the binary signal "0" (off)
force generated by the pressure pe at the is applied to the input, the signal pressure
measuring diaphragm (5). pst is shut off and the actuator is vented. The
If either the control signal or the valve posi- actuator springs move the control valve to its
tion changes, the diaphragm lever (3) fail-safe position. If a control signal corre-
moves, altering the distance to the nozzle sponding to the binary signal "1" (on) is ap-
(2.1 or 2.2), depending on the set operating plied to the input, the signal pressure pst is
direction of the positioner. supplied to the actuator. The control valve is
The air is supplied to the booster (10) and in control operation.
the pressure regulator (9). The controlled
supply air is fed to the i/p module, then
flows through the Xp restriction (8) and the
nozzle (2.1, 2.2) to finally stream on the di-

4 EB 8355-2 EN
Design and principle of operation

2.1
3

2.2
Travel
5
1 1.2

Pe 1.1
6.1 4 6.2
p 13
mA
i
Supply
91 Pick-up lever 6.1 Span adjuster
1.1 Pin 6.2 Zero adjuster
V 1.2 Clamp 7 Turnboard
Xp Q 2.1 Nozzle >> 8 Xp restriction
Pst 2.2 Nozzle <> 9 Pressure regulator
3 Diaphragm lever 10 Booster
4 Range 11 Volume restriction
7 8 9 10 11 12 spring 12 Solenoid valve
5 Measuring (optional)
diaphragm 13 i/p converter
4 3 7 8 9 11

13 6.1 6.2
Fig. 2 · Functional diagram and inside view

EB 8355-2 EN 5
Design and principle of operation

Positioner with position transmitter


A positioner containing a position transmit-
ter cannot be equipped with integrated limit
switches or an integrated solenoid valve
since the position transmitter requires most
of the space inside. The position transmitter
is used to establish a certain relationship be-
tween the valve position, i.e. the valve
travel, and a controller output signal of 4 to
20 mA. The position transmitter setting en-
sures that both end positions "valve
CLOSED" or "valve OPEN" as well as all in-
termediate positions can be signalized.
Since the valve position is signalized inde-
pendently of the input signal to the
positioner, the position transmitter is a suit-
able option for checking the current valve
position.

6 EB 8355-2 EN
Versions

1.1 Versions
Positioner Type 3767- x x x 0 1 x x 0 x x
Explosion-protection
None 0
II 2 G EEx ia IIC T6 acc. to ATEX 1
Ex ia CSA/FM 3
II 3 G EEx nA II T6 acc. to ATEX 8
Accessories
Inductive limit switches
None 0
With two Type SJ 2-SN 2
Solenoid valve
None 0
6 V DC 2
12 V DC 3
24 V DC 4
Analog position transmitter 6 0
Pneumatic connection
¼ NPT 1
ISO 288/1-G ¼ 2
Electrical connection
M 20 x 1.5 blue 1
M 20 x 1.5 black 2
Connector HAN 7D (not with CSA/FM) 4
Special version
None 0
CrNiMo steel housing 2
Reference variable
4 to 20 mA 1
0 to 20 mA 2
1 to 5 mA 3

EB 8355-2 EN 7
Technical data

1.2 Technical data


Positioner

Travel range, adjustable Direct attachment: 7.5 to 30 mm


Attachment acc. to IEC 60534-6: 7.5 to 120 mm or
Opening angle Depending on the cam disk: 30 to 120°

Reference variable
Signal range 4 (0) to 20 mA 1 to 5 mA
Span 8 to 20 mA 2 to 4 mA
Coil reference Ri at 20 °C 200 Ω 880 Ω

Supply air 1.4 to 6 bar (20 to 90 psi)


Air quality acc. to ISO 8573-1: Max. particle size and density: Class 4,
Oil content: Class 3, pressure dew point: Class 3

Signal pressure pst (output) Can be limited between approx. 2.5 to 6.0 bar (38 to 90 psi)

Characteristic Linear characteristic, deviation from terminal-based conformity ≤ 1 %

Hysteresis ≤ 0.3 %

Sensitivity ≤ 0.1 %

Operating direction Reversible

Proportional band Xp < 1 to 2.5 % (proportional-action coefficient Kp > 100 to 40)

With supply air = 6 bar: ≤ 280 ln/h with


Air consumption With supply air = 1.4 bar: ≤ 280 ln/h
min. adjusted pressure regulator
3
Actuator pressurized: 3.0 mn /h 8.5 mn3/h
Air delivery 3 3
Actuator vented: 4.5 mn /h 14.0 mn /h
–20 to 80 °C with plastic cable gland
Permissible –40 to 80 °C with metal cable gland (special version down to –45 °C)
ambient temperature –20 to 70 °C for positioners with position transmitter
See attached certificate for explosion-protected devices

Influences Temperature: ≤ 0.3 %/10 K


Supply air: ≤ 1 % between 1.4 and 6 bar
Vibration: None between 10 and 150 Hz and 4 g

Explosion protection Type of protection EEx ia IIC T6, see attached certificate

Degree of protection IP 54 (upgradable to IP 65 using a filter check valve, see Accessories table)

Electromagnetic Complying with requirements specified in EN 61000-6-2, EN 61000-6-3 and


compatibility NAMUR Recommendation NE 21

Weight Approx. 1 kg

8 EB 8355-2 EN
Technical data

Inductive limit switches


2 proximity switches Type SJ 2-SN
Control circuit Ratings according to downstream transistor relay
Hysteresis at rated travel ≤1 %
Solenoid valve
Input Binary direct current signal
Nominal signal 6 V DC 12 V DC 24 V DC
Signal 0 (no pick-up),
≤ 1.2 V ≤ 2.4 V ≤ 4.7 V
DC signal at –25 °C
Signal 1 (safe pick-up),
≥ 5.4 V ≥ 9.6 V ≥ 18 V
DC signal at 80 °C
Maximum permissible signal 28 V 25 V 32 V
Coil resistance Ri at 20 °C 2909 Ω 5832 Ω 11714 Ω
Air consumption in steady state In addition to that of the positioner: "Off" ≤ 60 ln/h · "On"≤ 10 ln/h

Closing time with Type 3277


120 cm² 240 cm² 350 cm² 700 cm²
Actuator
Rated travel and 0.2 to 1 bar ≤1 s ≤ 1.5 s ≤4 s
signal pressure
range 0.4 to 2 bar ≤ 0.5 s ≤2 s ≤ 2.5 s ≤8 s
(KVS = 0.14)
0.6 to 3 bar ≤1s ≤ 1.5 s ≤5 s
Position transmitter* – Intrinsically safe output current circuit
Output signal Two-wire circuit 4 to 20 mA, reversible operating direction
Min. terminal voltage 12 V DC, max.
Power supply Only with intrinsically safe circuit
45 V DC
Performance Characteristic: output linear to input, deviation from characteristic ≤ 1 %
Hysteresis ≤ 0.6 %
Response ≤ 0.1 %
Influence of power supply ≤ 1 % when voltage changes occur within the specified limits
HF influence ≤ 0.1 %, f = 150 MHz, 1 W power output at a distance of 0.5 m
Load influence ≤ 0.1 %
Permissible ambient temperature –20 to 70 °C –20 to … Refer to certificate
Ambient temperature influence ≤ 0.4 % on lower measuring range value, ≤ 0.2 % on measuring span
Ripple of output signal ≤ 0.3 %

* Data refer to standard spring (15 mm travel with Type 3277 Actuator) and gain of 100.

EB 8355-2 EN 9
Attachment to control valve

2 Attachment to control valve want to change the operating direction, re-


move the fastening screw at the turnboard,
The positioner is attached either directly to turn the board by 180°, and refasten the
SAMSON Type 3277 Actuator or to valves turnboard with the screw. Make sure the
with cast yokes or with rod-type yokes in ac- three rubber gaskets inserted in the housing
cordance with IEC 60534-6 (NAMUR). remain in position.
When combined with an intermediate piece,
the device can also be attached to rotary ac- Note!
tuators as a rotary positioner. As the When any subsequent changes are made,
positioner is also available as a basic unit e.g. reversing the operating direction of the
without accessory equipment, refer to the ta- positioner control loop or changing the actu-
bles on the following pages for both the re- ator from “Actuator stem extends” to “Actu-
quired mounting parts and their associated ator stem retracts” or vice versa, the
order numbers. positioner's mounting position must be
Do not remove the protective cover on the changed accordingly.
back of the positioner before actually start-
ing to attach the positioner.

Mounting position and operating direction

The operating direction of the positioner


also determines its mounting position on the 2.1 Direct attachment to Type
actuator as illustrated in Figs. 3, 4 and 6. 3277 Actuator
The turnboard (7, Fig. 2) at the positioner
must be mounted correspondingly. For an
increasing input signal (reference variable), Required accessories are listed in Tables 1
the signal pressure pst can either be increas- to 4 on page 14.
ing (direct action >>) or decreasing (reverse
action <>). This also applies when the refer-
The attachment of the positioner either on
ence variable decreases: direct action >>
the left or right side of the actuator (always
causes the signal pressure to decrease, re-
looking at the signal pressure connection or
verse action <> causes the signal pressure to
switchover plate) is determined by the re-
increase.
quired operating direction of the positioner,
On the turnboard (7), the operating direc- i.e. >> or <>.
tion is indicated by symbols (direct >>, re-
verse <>). Depending on the position of the
turnboard, the adjusted operating direction
and the associated symbol become visible.
If the required operating direction does not
correspond to the visible symbol, or if you

10 EB 8355-2 EN
Attachment to control valve

Actuator stem extends

Internal signal pressure


Op. direction >> connection
Attachment left Operating
direction <>
Connection block
Attachment right
Tip of gasket (16)
Actuator stem retracts

Signal pressure connection


over piping

Op. direction <> Operating


Attachment left direction>>
Attachment right

Side view of connection block


With gasket (new) With switch plate (old)
Cover plate
SUPPLY

Actuator stem extends

Marking Switch plate (13)

Actuator stem retracts


Gasket (16)
Signal pressure input
Switchover plate for attachment right

Signal pressure Actuator stem extends


input for attach- >> Operating direction <>
ment left Attachment left Attachment right

Actuator stem retracts


Seal <> Operating direction >>
with filter Attachment left Attachment right
Symbol
Marking
Fig. 3 · Mounting position and connections of Type 3277 (top) and Type 3277-5 120 cm2 (bottom) Actuators

EB 8355-2 EN 11
Attachment to control valve

1. Screw the clamp (1.2) to the actuator 8. Place the connection block with its seals
stem. Make sure that the fastening screw on the positioner and the actuator yoke
is located in the groove of the actuator and screw tight using the fastening
stem. screw.
Actuators with "Actuator stem retracts"
2. Screw the associated lever D1 or D2 (for
require the ready-made signal pressure
700 cm² actuator) to the pick-up lever of
line to be installed.
the positioner.
3. Fasten the distance plate (15) with the 2
Actuators with 120 cm diaphragm area
seal pointing towards the actuator yoke.
The signal pressure is transmitted to the dia-
4. Attach the positioner such that the lever phragm chamber over the switchover plate
D1 or D2 slides centrically over the pin (Figs. 3 and 4, bottom).
(1.1) of the clamp (1.2). Screw the
positioner to the distance plate (15). 7. Remove the screw in the rear cover of the
positioner (Fig. 5) and seal the lateral
5. Mount the cover (16). signal pressure output "output" with the
6. Check whether the correct measuring plug contained in the accessories kit.
spring has been installed as listed in Ta- 8. Mount the positioner such that the bore
ble 4. in the distance plate (15) mates with the
Range spring 1 is installed as standard. seal in the bore of the actuator yoke.
If necessary, replace it with range spring
2 included in the accessories and fix it at 9. Align the switchover plate with the corre-
the outer slot. sponding symbol and fasten it to the ac-
tuator yoke.
Actuators with 240, 350 and 700 cm² dia-
phragm area Note!
When a solenoid valve or a similar device is
7. Make sure that the tip of the gasket (16)
attached to the 120 cm² actuator in addition
projecting from the side of the connec-
to the positioner, do not remove the rear M3
tion block (Fig. 3, middle) is positioned
screw plug. In this case, the signal pressure
to match the actuator symbol that corre-
must be transmitted from the signal pressure
sponds to the actuator's fail-safe action
output to the actuator over an additional
"Actuator stem extends" or "Actuator
connecting plate (Table 2). The switchover
stem retracts."
plate is not used.
If necessary, remove the three fixing
screws and the cover. Reposition the
gasket (16) turned by 180°.
The old connection block version re-
quires the switch plate (13) to be turned
such that the corresponding actuator
symbol points to the marking.

12 EB 8355-2 EN
Attachment to control valve

Filling the actuator with air aphragm area of 120 cm², an internal bore
hole ensures that the spring chamber is filled
If the spring chamber of the actuator must with air.
be filled with the positioner's exhaust air,
use piping (Table 3) to connect the spring
chamber (with version "Actuator stem ex- Note!
tends") to the connection block. To do so, When the valve is installed, the side cover of
remove the plug from the connection block. the actuator must be mounted such that the
vent plug points downward.
For version "Actuator stem retracts" and
Type 3277-5 Actuators with an effective di-

Type 3277 15
Vent plug
240 cm²
350 cm²
700 cm²

1.2
D2

D1
Cover

Attachment left Attachment right


Looking onto the signal pressure connection
Type 3277-5
120 cm² Vent plug must point
downward when valve is
Distance plate (15) installed

Clamp (1.2)

Signal pressure bore

Switchover plate
Fig. 4 · Mounting the clamp

EB 8355-2 EN 13
Attachment to control valve

Table 1 Mounting kit


Required lever with associated clamp and distance plate Actuator size [cm²] Order no.

D1 with vent plug for output (38) G¼ 1400-6790


120
Connecting thread ¼ NPT 1400-6791
D1 (33 mm long with 17-mm-high clamp) 240 and 350 1400-6370
D2 (44 mm long with 13-mm-high clamp) 700 1400-6371
Table 2 Order no.
Swichover plate for actuators 120 cm² Actuator 3277-5xxxxxx.00 (old) 1400-6819
Swichover plate new Actuator 3277-5xxxxxx.01 or higher (new) 1400-6822
1
Connecting plate for additional attachment of, Actuator 3277-5xxxxxx.00 (old), G 8 1400-6820
1
e.g. a solenoid valve Actuator 3277-5xxxxxx.00 (old), 8 NPT 1400-6821
Connecting plate new Actuator 3277-5xxxxxx.01 or higher (new) 1400-6823
Note! Only the new switchover and connecting plates can be used for new actuators (model index 01). Old and new
plates cannot be interchanged.

Connection block required for actuators with 240, 350, 700 cm2 diaphragm G¼ 1400-8811
area (including seals and fastening screw) ¼ NPT 1400-8812
Table 3 Material Actuator size [cm²] Order no.
Piping required Steel 240 1400-6444
including screw fitting
Stainless steel 240 1400-6445
For actuator: Steel 350 1400-6446
“Actuator stem retracts“
or Stainless steel 350 1400-6447
when the top diaphragm case is filled with ex- Steel 700 1400-6448
haust air from the positioner
Stainless steel 700 1400-6449

Table 4 · Range spring required Travel [mm] Actuator size [cm²] Order no.
2 (4.5 coils) 7.5 120, 240 1400-6443
1 (9.5 coils, installed as standard) 10 to 15 120, 240 and 350 1400-6442
2 15 700 1400-6443
1 30 700 1400-6442
Accessories Order no.
G¼ 1400-7458
Pressure gauge build-on block (only for 120 cm2)
¼ NPT 1400-7459
Stainl. steel/Brass 1400-6950
Pressure gauge kit for supply pressure and signal pressure
Stainl. steel/St. steel 1400-6951
Filter check valve, replaces the vent plug and increases the degree of protection to IP 65 1790-7408

14 EB 8355-2 EN
Attachment to control valve

2.2 Attachment according to IEC


60534-6

Required mounting parts are listed in Table


5. The rated travel of the valve determines
which lever and range spring (Table 6) are
required.

Spring Plug screw


An adapter housing (Fig. 7) is required for
NAMUR attachment. The valve travel is Fig. 5 · Installing the spring on the back of the
housing
transmitted over the lever (18) and shaft
(25) to the bracket (28) of the adapter hous-
The positioner can be attached either to the
ing and then passed on to the pin (27a) lo-
left or the right of the control valve (Figs. 6
cated on the positioner lever. Fix the spring
and 7). Turn the positioner at the adapter
included in the accessories at the back of the
housing by 180° to set or change the oper-
positioner housing as illustrated in Fig. 5 to
ating direction of the positioner/control
ensure that the pin (27a) is properly located
valve unit.
in the bracket (28).

Attachment left Attachment right


Mounting position on the plate looking onto the travel pick-up (20), actuator facing upward (see also Fig. 7)
Actuator with fail-safe action “Actuator stem extends” (FA)
Direct op. direction >> Reverse op. direction <> Direct op. direction >> Reverse op. direction <>

20

Electrical connection Pneumatic connections Electrical connection

Actuator with fail-safe action “Actuator stem retracts” (FE)


Direct op. direction >> Reverse op. direction <> Direct op. direction >> Reverse op. direction <>

20

Pneumatic connection Electrical connections Pneumatic connection

Fig. 6 · Attachment to the left or right of the valve when NAMUR attachment is used

EB 8355-2 EN 15
Attachment to control valve

2.2.1 Mounting sequence clip must be clamped onto the lever (18)
with the open side pointing downward.
Choose the required mounting parts and
6. Plug the lever (18) together with the
range spring from Table 4 or 5 and install
clamping plate (22) on the shaft (25).
them as illustrated in Fig. 7.
The clip must clasp the pin (19).
Control valve with cast yoke
2.2.2 Presetting the travel
1. Screw the plate (20) to the stem connec-
tor connecting the actuator and plug 1. Move the valve to 50 % travel.
stems using countersunk screws. For 2. Adjust the shaft (25) in the adapter hous-
2100 and 2800 cm2 actuators, use an ing such that the black pointer (24)
additional mounting bracket (32). matches the cast mark on the adapter
2. Remove the rubber plug from inside the housing.
adapter housing. Fasten the housing to 3. Fasten the clamp (22) tightly in this posi-
the left or right side of the NAMUR rib tion using the screw (23).
(as shown in Fig. 6) using a hexagon
screw. 4. Screw in the pin (27a) at the positioner
lever on the side of the insert nut and se-
Control valve with rod-type yoke cure it with a hex nut (27b) on the oppo-
site side. Observe the mounting position
1. Screw the plate (20) to the follower A or B according to Table 6 and Fig. 7.
clamp of the plug stem.
5. Place the positioner on the adapter hous-
2. Screw the studs (29) into the adapter ing, observing the operating direction.
housing. Make sure that the pin (27a) rests
3. Place the housing with the mounting against the bracket (28) and screw it
plate (30) on either the right or left side tight.
(Fig. 6) of the plug stem and fasten it Caution! The pin must not slip out of the
with the nuts (31). Make sure that the le- bracket once it has been installed.
ver (18) to be mounted subsequently is in 6. Check whether the correct range spring
horizontal position when the valve is at has been installed as listed in Tables
mid-travel. 5/6.
4. Screw the pin (19) into the center row of Range spring 1 is installed as standard.
holes in the plate (20) and lock it in a If necessary, replace it with range spring
position approximately above the correct 2 included in the accessories and fix it at
lever marking (1 to 2) as in Table 6. the outer slot.

5. Clamp the clip (21) onto the lever (18). If 7. Adjust the positioner as described in sec-
the actuator is attached with its air con- tion 4.1.
nection pointing to the front (Fig. 6), the

16 EB 8355-2 EN
Attachment to control valve

Mounting position

27b
A B

Attachment to
NAMUR rib
26 27a 28

1,5 2
1

24 25 22 23 19 21 20 18

32
18 Lever N1, N2
Attachement to
19 Pin
rod-type yoke
20 Plate
21 Clip
22 Clamping plate
23 Screw
31
24 Pointer 29
25 Shaft 30
26 Lever of the positioner
27a Pin
27b Lock nut
28 Bracket
29 Studs
30 Plate
31 Nuts
32 Mounting bracket 20 19

Fig. 7 · Attachment according to IEC 60534-6 (NAMUR)

EB 8355-2 EN 17
Attachment to control valve

Table 5 Control valve Travel [mm] With lever Order no.


7.5 to 60 N1 (125 mm) 1400-6787
NAMUR mounting kit, Valve with cast yoke
22.5 to 120 N2 (212 mm) 1400-6789
Refer to Fig. 7 20 to 25 N1 1400-6436
concerning parts
20 to 25 N2 1400-6437
Valve with
rod-type yoke, 25 to 30 N1 1400-6438
rod diameter 25 to 30 N2 1400-6439
[mm]
30 to 35 N1 1400-6440
30 to 35 N2 1400-6441
1400-6771
Attachment to Fisher and Masoneilan linear actuators
and
(one each of both mounting kits is required per actuator)
1400-6787
Additional range spring acc. to Table 6 Range spring 1 (9.5 coils, installed as standard) 1400-6442
Range spring 2 (4.5 coils) 1400-6443
Accessories Order no.
G¼ 1400-7458
Pressure gauge build-on block
¼ NPT 1400-7459
Stainless steel/Brass 1400-6950
Pressure gauge kit
Stainless steel/Stainless steel 1400-6951
Filter check valve, replaces the vent plug and increases the degree of protection to IP 65 1790-7408

Table 6
Travel [mm]* 7,5 15 15 30 30 60 30 60 60 120
Pin on marking* 1 2 1 2 1 2 1 2 1 2
Distance pin/fulcrum of the lever 42 to 84 mm 84 to 168 mm
With lever N1 (125 mm long) N2 (212 mm long)
Pin (27a) on position A A B A B
Range spring required (see Table 5) 2 1 1 1 1

* Intermediate values must be interpolated

18 EB 8355-2 EN
Attachment to control valve

2.3 Atttachment to rotary actuators


The positioner can also be attached to ro- when the mounting kits and accessories
tary actuators according to VDI/VDE 3845 listed in Table 7 are used.

Table 7 · Complete mounting parts, including range spring 2, but excluding the cam disk Order no.
160 cm² 1400-7103
SAMSON Type 3278 Actuator 320 cm² 1400-7104
Actuator acc. to VDI/VDE 3845 1400-8815
Camflex I, DN 25 to 100 1400-7118
Attachment to Masoneilan actuators Camflex I, DN 125 to 250 1400-7119
Camflex II 1400-7120
Range spring required Order no.
Standard operation of reference variable, range spring 2 (4.5 coils) 1400-6443
Split-range operation, range spring 1 (9.5 coils, installed as standard) 1400-6442
Reversing amplifier Order no.

Reversing amplifier for double-acting Threaded connection G 1079-1118


springless actuators Threaded connection NPT 1079-1119
Cam disk with accessories Order no.
1)
~, linear (0050-0080), opening angle 0 to 70°, for butterfly valves 1400-6774
~, equal percentage 2) (0050-0081), opening angle 0 to 70°, for butterfly valves 1400-6775
~, linear basic characteristic 3) (0050-0072), opening angle 0 to 90° 1400-6664
~, equal percentage basic characteristic 3) (0050-0073), opening angle 0 to 90° 1400-6665
~, linear 1) (0050-0074, Vetec), opening angle 0 to 56° and 0 to 75° 1400-6666
2)
~, equal percentage (0050-0075, Vetec), opening angle 0 to 44° and 0 to 75° 1400-6667
1)
~, linear (0050-0122), opening angle 0 to 90° for Type 3310 1400-7580
~, equal percentage 2) (0050-0123), opening angle 0 to 90° for Type 3310 1400-7581
~, equal percentage 2) (0050-0124), opening angle 0 to 55° for Type 3310 1400-7582
~, linear1) (0050-0125), opening angle 0 to 55° for Type 3310 1400-7583
1)
~, linear (0059-0007, Camflex) set to between 0 and 55° 1400-6637
2)
~, equal percentage (0059-0008, Camflex) set to between 0 and 55° 1400-6638
1) 2) 3)
Linearizes the flow characteristic Creates an equal percentage flow characteristic Based on opening angle
Accessories Order no.
G¼ 1400-7458
Pressure gauge build-on block
¼ NPT 1400-7459
St. steel/Brass 1400-6950
Pressure gauge kit
St. steel/St. steel 1400-6951
Filter check valve, replaces the vent plug and increases the degree of protection to IP 65 1790-7408

EB 8355-2 EN 19
Attachment to control valve

The rotary motion of these actuators is con- (37) opposite the insert nuts. Fasten with
verted into a linear motion required by the the supplied screws (38) and washers.
pneumatic control unit of the positioner us-
ing the cam disk of the actuator shaft and a Note!
cam follower roll on the positioner lever. To ensure a close physical contact between
the cam follower roll and the cam disk, fix
Note! Use Table 7 to check whether the the spring contained in the accessories kit
proper range spring (1 or 2) has been in- (order no. 1400-6660) at the rear of the
stalled. Range spring 1 is installed as stan- positioner housing (see Fig. 5).
dard. If necessary, replace it with range
spring 2 included in the accessories and at-
tach it at the outer slot. 2.3.2 Mounting the intermediate
piece
Double-acting springless rotary actuators re- SAMSON Type 3278 Actuator
quire the use of a reversing amplifier on the
connection side of the positioner housing 1. Screw the adapter (36) to the free end of
(see section 2.3.4). the actuator shaft.
When using a reversing amplifier, the pres-
2. Attach the intermediate piece (34) to the
sure regulator (9, Fig. 2) must be turned
actuator housing using two screws. Align
clockwise as far as it will go (also see sec-
the intermediate piece to ensure that the
tion 3.1.2).
air connections of the positioner point to-
When attaching the positioner to the
wards the diaphragm housing.
SAMSON Type 3278 Rotary Actuator (Fig.
8, left), the actuator's inside and the unused 3. Align the cam disk (40) and scale (39)
reverse side of the diaphragm are filled with as described in section 2.3.3 and fasten
the positioner's exhaust air. Additional pip- with screws.
ing is not required. When attaching the
positioner to actuators from other manufac- Actuators according to VDI/VDE 3845
turers (Fig. 8, right), the reverse side of the (fixing level 1)
diaphragm can be filled with air over a pipe
1. Place the complete intermediate piece
connection installed between the actuator
(34, 44, 45, and 42) onto the mounting
and the intermediate piece.
bracket that came with the actuator and
fasten with screws.
2.3.1 Mounting the cam follower
lever 2. Align the cam disk (40) and scale (39)
as described in section 2.3.3 and fasten
1. Place the lever with the cam follower roll with screws.
(35) on the side of the feedback lever

20 EB 8355-2 EN
Attachment to control valve

33

Attachment to SAMSON
Type 3278

37 35 38

Attachment acc. to
39 VDI/VDE 3845

40
39
40
Vent plug or
filter check valve

34
34

36
44

45
33 Positioner
34 Intermediate piece 42
35 Lever with cam follower roll
36 Adapter 43
37 Feedback lever
38 Screws
39 Scale
40 Cam disk
41 Actuator shaft
42 Plate
43 Mounting bracket
44 Coupling

Fig. 8 · Attachment to rotary actuators

EB 8355-2 EN 21
Attachment to control valve

2.3.3 Default setting of the cam Use the turnboard (7) to adjust the operat-
disk ing direction of the positioner, i.e. whether
the valve opens or closes when the reference
The valve model used determines the default variable increases (direct >> or reverse <>).
setting of the cam disk. Each cam disk carries two cam sections
whose starting points are indicated by small
bores. Depending on the operating direction
Note!
of the rotary actuator – signal pressure
Cam disks tailored to the special character-
opens or closes the valve – the starting point
istic of a valve cause the valve to open in a
of the cam, either marked N (standard char-
non-linear or non-equal percentage way.
acteristic) or I (reverse characteristic), must
The visible difference between the set point
point towards the cam follower roll. When
(4 to 20 mA) and the actual value (opening
the starting point is located on the back of
angle) does not constitute a system deviation
the cam disk, turn over the cam disk.
of the positioner.

Note!
Figs. 9 and 10 show linear cam disks. The starting point (bore) of the selected cam
Fig. 9 illustrates a control valve assembly section must be aligned with the fulcrum of
with a spring-loaded rotary actuator that the cam disk, the 0° position of the scale,
opens counterclockwise. The arrangement of and the arrow symbol on the inspection
the springs in the actuator determines the glass.
fail-safe position of the valve.
Fig. 10 shows how to adjust the cam disk When aligning the cam disk, the dou-
when a double-acting springless rotary actu- ble-sided scale disk must be clipped on the
ator is used. The direction of rotation, either cam disk such that the value on the scale
counterclockwise or clockwise, depends on corresponds to the control valve's direction
the actuator and valve model used. The cam of rotation.
disk must be set when the valve is closed.
Note!
Make sure the 0° position of the scale al-
ways corresponds to CLOSED position.
For actuators with fail-safe position "Valve
OPEN" and for springless actuators, it is
therefore necessary to apply the maximum
supply pressure to the actuator before align-
ing the cam disk.

22 EB 8355-2 EN
Attachment to control valve

Single-acting spring-loaded rotary actuator


Linear cam disk (equal percentage cam disk is represented by a broken and dotted line)
Valve opens counterclockwise
For valves that open clockwise, the cam disk must be turned over so that the cam follower roll moves
over the same disk segments as shown in the figures below, but with the cam disk turning clockwise.
Fail-safe position: Valve CLOSED without supply air
Direct operating direction >> Reversible operating direction <>
Reference Signal Charact- Reference Signal Charact-
Valve Valve
variable pressure eristic variable pressure eristic
increases increases opens N decreases increases opens I

Cam follower roll Starting point I


Starting point N
Boreholes to secure
the cam disk

Insert clip and


press tongues outwards

Fail-safe position: Valve OPEN without supply air


Direct operating direction >> Reversible operating direction <>
Reference Signal Charact- Reference Signal Charact-
Valve Valve
variable pressure eristic variable pressure eristic
decreases decreases opens I increases decreases opens N

Cam follower roll


Starting point I
Starting point N

Position at max. signal pressure

Fig. 9 · Setting the cam disk

EB 8355-2 EN 23
Attachment to control valve

Double-acting springless rotary actuator with reversing amplifier


Linear cam disk (equal percentage cam disk is represented by a broken and dotted line)
View from the positioner onto the actuator shaft
Valve opens counterclockwise – Starting position: valve CLOSED
Direct operating direction >> Reversible operating direction <>
Reference Signal Charact- Reference Signal Charact-
Valve Valve
variable pressure eristic variable pressure eristic
A1 increases, A2 A1 incresese, A2
increases opens N decreases opens I
decreases decreases

Cam follower roll Starting point I


Starting point N
Boreholes to secure
the cam disk

Insert clip and


press tongues outwards

View from the positioner onto the actuator shaft


Valve opens clockwise – Starting position: valve CLOSED
Direct operating direction >> Reversible operating direction <>
Reference Signal Charact- Reference Signal Charact-
Valve Valve
variable pressure eristic variable pressure eristic
A1 increases, A2 A1 increases, A2
increases opens N decreases opens I
decreases decreases

Cam follower roll


Starting point I
Starting point N

Fig. 10 · Setting the cam disk

24 EB 8355-2 EN
Attachment to control valve

Securing the aligned cam disk


To additionally prevent the cam disk from
being turned, drill a bore into the adapter
(36) or the coupling (44) and install a 2 mm
dowel pin.
Four bore holes are located centrically
around the center bore hole on the cam
disk. Select a suitable bore to install the pin.

EB 8355-2 EN 25
Attachment to control valve

2.3.4 Reversing amplifier for Signal pressure connections


double-acting actuators A1: Connect output A1 to the signal pressure
connection on the actuator that opens the
When used with double-acting actuators,
valve when the pressure increases.
the positioner must be equipped with a re-
versing amplifier. The reversing amplifier is A2: Connect output A2 to the signal pressure
listed as an accessory in Table 7 on page connection on the actuator that closes the
19. valve when the pressure increases.
The output signal pressure of the positioner
is supplied at output A1 of the reversing am-
plifier. An opposing pressure, which equals
the required supply pressure when added to
the pressure at A1, is supplied at output A2.
A1 + A2 = Z applies.

Assembly

Note!
Remove the sealing plug (1.5) before install-
ing the reversing amplifier. The rubber seal
(1.4) must remain installed.

1. Screw the special nuts (1.3) included in


the accessories of the reversing amplifier
into the threaded connections of the
positioner.
2. Insert the gasket (1.2) into the recess of
the reversing amplifier and push the two
hollowed special screws (1.1) into the
connecting bore holes A1 and Z.
3. Place the reversing amplifier onto the
positioner and screw tight using the two
special screws (1.1).
4. Screw the supplied filter (1.6) using a
screwdriver (8 mm wide) into the con-
necting bore holes A1 and Z.

26 EB 8355-2 EN
Attachment to control valve

From the positioner

Control signals to the actuator

1 Reversing amplifier
1.1 Special screws
1.2 Gasket
1.3 Special nuts
1.4 Rubber seal
1.5 Sealing plug
1.6 Filter

Fig. 11 · Mounting a reversing amplifier

EB 8355-2 EN 27
Connections

3 Connections can be found on the intermediate piece or


the reversing amplifier.
3.1 Pneumatic connections
Note!
The pneumatic connections are designed as When using older models with index
tapped holes with ¼ NPT or G ¼ thread. 3767-x...x. 02 or lower, mounting parts will
The conventional male connections for metal have to be replaced as well.
and copper pipes (or plastic hoses) can be
used.

Note!
The supply air must be dry and free of any 3.1.1 Pressure gauge
oil and dust.
To monitor the positioner, we recommend to
Always observe the maintenance instructions
install pressure gauges for the supply air
applicable to the connected pressure reduc-
and the signal pressure.
ing stations. Blow out air lines thoroughly
The required parts are listed as accessories
before connecting them.
in Tables 4, 5 or 7.

When attaching the Type 3277 Actuator di- 3.1.2 Supply pressure
rectly, the signal pressure connection is
fixed. When using NAMUR attachment, the The required supply pressure is determined
signal pressure line is connected to either by the bench range and the operating direc-
the upper or lower diaphragm chamber of tion (fail-safe action) of the actuator.
the actuator depending on the actuator's The bench range is written on the nameplate
fail-safe action, i.e. "Actuator stem retracts" as spring range or signal pressure range
or "Actuator stem extends". depending on the type of actuator. FA (actu-
ator stem extends) or FE (actuator stem re-
Exhaust air tracts) or a symbol indicates the operating
direction.
Positioners with model index 3767-x...x.03
or higher are equipped with a hinged cover Actuator stem extends (FA):
without a vent connection. The required ex- Fail-safe position "Valve CLOSED"
haust air connection for these models are (for globe and angle valves)
now included in the mounting accessories.
For direct positioner attachment, the vent Required supply pressure =
plug is located on the plastic cover of the Upper bench range value + 0.2 bar,
actuator; for NAMUR attachment, it is lo- minimum 1.4 bar.
cated on the adapter housing, and for at-
tachment to rotary actuators the vent plug

28 EB 8355-2 EN
Connections

Actuator stem retracts (FE):


Fail-safe position "Valve OPEN"
(for globe and angle valves)
The required supply pressure for a
tight-closing valve is roughly estimated from
the maximum signal pressure pstmax:
2
pstmax = F + d ⋅π ⋅ Δp [bar]
4⋅ A

d = Seat diameter [cm]


Δp = Differential pressure at the valve [bar]
A = Actuator diaphragm area [cm2]
F = Upper range value of the actuator

In the absence of such specifications, pro-


ceed as follows:
Required supply pressure =
Upper bench range value + 1 bar

Pressure regulator
After tilting the cover plate back, the pres-
sure regulator (9) can be continuously ad-
justed. When the adjuster is turned counter-
clockwise as far as it will go, signal pres-
sures for spring ranges up to 2.5 bar are
controlled. When the adjuster is turned
clockwise all the way, signal pressures for
spring ranges up to 6.0 bar are controlled.
If the signal pressure must not exceed a cer-
tain value, this limit can be adjusted using a
pressure gauge (accessories).

EB 8355-2 EN 29
Connections

3.2 Electrical connections Caution!


The terminal assignment specified in the cer-
For electrical installation, you are re- tificate must be adhered to. Reversing the
quired to observe the relevant assignment of the electrical terminals may
electrotechnical regulations and the cause the explosion protection to become in-
accident prevention regulations that effective!
apply in the country of use. In Ger- Do not tamper with enameled screws inside
many, these are the VDE regulations or on the housing..
and the accident prevention regula-
tions of the employers' liability insur- Note on the selection of cables and wires:
ance association. To install intrinsically safe circuits, observe
The following standards apply for in- section 12 of the standard EN 60079-14:
stallation in hazardous areas: 2003 (VDE 0165 Part 1). To run multi-core
EN 60079-14: 2003 (VDE 0165 cables or lines with more than one intrinsi-
Part 1) "Electrical apparatus for ex- cally safe circuit, section 12.2.2.7 of this
plosive gas atmospheres" and standard applies.
EN 50281-1-2: 1999 (VDE 0165 An additional cable gland can be installed
Part 2) "Electrical apparatus for use when connecting the device over two sepa-
in the presence of combustible rate cables. Cable entries left unused must
dust". be sealed with blanking plugs. Devices used
For the interconnection of intrinsically at ambient temperatures down to –40 °C
safe electrical equipment, the permis- must have metal cable entries.
sible maximum values specified in
the EC type examination certificate
apply (Ui or U0; Ii or I0; Pi or P0; Ci or
C0, and Li or L0).
For EEx nA equipment (non-sparking
apparatus), the standard EN 50021:
1999 specifies that connecting, inter-
rupting, or switching circuits while
energized is only allowed during in-
stallation, maintenance or repair
work.
For EEx nL equipment (energy-limited
apparatus), the standard EN 50021:
1999 allows this type of equipment
to be switched under normal operat-
ing conditions.

30 EB 8355-2 EN
Connections

The wiring for the reference variable is led Accessories:


to the terminals 11 and 12.
Positioner index 3767-x...x. 03 or lower
The positioner does not have to be con- Cable gland PG 13.5
nected to a bonding conductor. If need be, Plastic, black Order no. 1400-6781
the bonding conductor can be connected ei- Plastic, blue Order no. 1400-6782
ther inside or outside of the housing. Brass, nickel-plated Order no. 1400-6979
Depending on the version used, the Adapter PG 13.5 to ½ NPT:
positioner is equipped with inductive limit Metallic Order no. 1400-7109
switches and/or a solenoid valve. Versions Painted blue Order no. 1400-7110
with position transmitter do not permit the
connection of these accessories. Positioner index 3767-x...x. 04 or higher
Cable gland M 20 x 1.5
The position transmitter is operated on a Plastic, black Order no. 1400-6985
two-wire circuit. The usual supply voltage is Plastic, blue Order no. 1400-6986
24 V DC. Considering the resistance of the Brass, nickel-plated Order no. 1400-4875
supply leads, the voltage at the position
transmitter terminals can be between 12 Adapter M 20 x 1.5 to ½ NPT:
and 45 V DC. Aluminum, powder-coated
Order no. 0310-2149
For terminal assignment, refer to Fig. 12 or
the label on the terminal strip. 3.2.1 Switching amplifiers
To operate the inductive limit switches,
switching amplifiers complying with EN
60947-5-6 must be connected in the output
circuit. Observe the relevant regulations
when installing the positioner in hazardous
areas.

On the rear Version with position transmitter

mA Switching amplifier mA
control signal 6 to 24 V DC control signal
acc. to EN 60947-5-6 solenoid valve
Voltage supply for transmitter,
only for position transmitter
Fig. 12 · Electrical connections

EB 8355-2 EN 31
Operation

4 Operation variable. The reference variable range and


thus the upper range value determine the
4.1 Adjusting the positioner at the travel of the valve.
valve In split-range operation (Fig. 13, right), the
control valves operate on smaller reference
Starting point and reference variable variables. The controller output signal is
used to control two control valves, dividing it
When adjusting the positioner directly at the such that the valves pass through their entire
control valve, the travel (opening angle) travel range at half the input signal range
must be adapted to the reference variable. each (e.g. first valve set to 4 to 12 mA, sec-
With a reference variable, for example, 4 to ond valve set to 12 to 20 mA). To avoid
20 mA, the valve must pass through its en- overlapping, allow for a dead band of
tire travel range from 0 to 100 % (Fig. 13, ±0.5 mA as shown in Fig. 13.
left).
The starting point (zero) is adjusted at the
For rotary positioners, an opening angle, zero adjuster screw (6.2); the span, i.e. the
for example, 0 to 70° must be assigned to upper range value, is adjusted at the span
the reference variable. adjuster screw (6.1).
The starting point refers to CLOSED position When adjusting, connect a suitable amme-
of the valve. ter to the signal input and apply a supply
Depending on the actuator version ("Actua- pressure to the supply air input.
tor stem extends" or "Actuator stem re-
tracts") and the operating direction of the
positioner (>> or <>), this starting point can
be represented by either the lower or upper
range value (4 or 20 mA) of the reference

Open Open

Travel Travel

Closed Closed Valve 2 Valve 1

Reference variable Dead band


Input signal

Fig. 13 · Standard and split-range operation

32 EB 8355-2 EN
Operation

Note! Note!
When the positioner is controlled by a com- Always adjust the Xp restriction before set-
puter whose signal is limited, e.g. between 4 ting the starting point.
to 20 mA, set the positioner to the range Later modifications shift the zero point!
from 4.5 to 20 mA.
This is the only way to ensure that the actua-
tor is completely vented and the valve com- 4.1.2 Adjusting the actuator:
pletely closed when the controller issues a "Actuator stem extends"
4 mA signal.
For operating direction <>, set the range to Starting point (e.g. 4 mA)
4 to 19.5 mA.
1. Set the input signal to 4 mA using an
ammeter.
4.1.1 Adjusting the proportional 2. Turn the zero adjuster (6.2) until the con-
band Xp and air delivery Q trol valve just starts to move from its ini-
tial position.
1. Close the volume restriction (11) as far
as the required positioning speed per- 3. Switch off the input signal and slowly in-
mits. crease it again. Check whether the valve
To check, push the diaphragm lever (3) starts to move at exactly 4.5 mA. Correct
as far it will go. any deviation on the zero adjuster (6.2).

2. Adjust the reference variable at the input Upper range value (e.g. 20 mA)
to approx. 50 % of its range.
1. Once the starting point has been set, in-
3. Turn the zero adjuster (6.2) until the
crease the input signal to 20 mA using
valve has reached approx. mid-travel.
the ammeter.
4. Use the adjuster (8) to set the propor-
At exactly 20 mA, the plug stem must stand
tional band Xp to a medium value (½
still, having passed through 100 % travel
turn).
(watch the travel indicator at the valve).
5. Check the valve's tendency to hunt and If the upper range value is incorrect, turn the
the positioning speed by briefly tapping span adjuster (travel). Four turns corre-
the diaphragm lever (3). spond to a travel change of 10 % in stan-
The Xp value is to be adjusted to be as dard operation. In split-range operation,
small as possible, without considerable this value is reduced by half. Turn the ad-
overshooting occurring. juster clockwise to reduce the travel and
counterclockwise to increase it.

EB 8355-2 EN 33
Operation

2. After correction has been completed, Starting point (e.g. 20 mA)


switch off the control signal and increase
it again. Check the starting point and the 1. Set the input signal to 20 mA using an
upper range value. Repeat the correction ammeter.
procedure until both values are correct. 2. Turn the zero adjuster (6.2) until the
valve just starts to move from its initial
Note! position.
When setting the zero adjuster (6.2), check 3. Increase the input signal and slowly re-
whether the actuator is relieved of pressure. duce it to 20 mA again. Check whether
When the input signal is 4 mA and the op- the valve starts to move at exactly
erating direction >>, or the input signal is 20 mA.
20 mA and the operating direction <>, the
pressure gauge must indicate 0 bar. Correct 4. Correct any deviations on the zero ad-
zero accordingly! juster (6.2). Turning the adjuster counter-
clockwise causes the valve to move from
its end position earlier; turning it clock-
4.1.3 Adjusting the actuator: wise causes the valve to move from its
end position later.
"Actuator stem retracts"
Upper range value (e.g. 4 mA)
Note!
When using an actuator with fail-safe action 1. Once the starting point has been set, ad-
"Actuator stem retracts", the diaphragm just the input signal to 4 mA using the
chamber must be pressurized with a signal ammeter. At exactly 4 mA, the plug stem
pressure sufficient to close the valve tightly must stand still, having passed through
even when an upstream pressure is applied 100 % travel (watch travel indicator at
in the plant. This applies to an upper range the valve).
value of the reference variable of 20 mA 2. If the upper range value is incorrect, turn
and operating direction >>, and a lower in- the span adjuster (travel). Four turns cor-
put range value of 4 mA and operating di- respond to a travel change of 10 % in
rection <>. standard operation. In split-range opera-
tion, this value is reduced by half. Turn
the adjuster clockwise to reduce the travel
The required signal pressure is either indi-
and counterclockwise to increase it.
cated on the positioner label or can be
roughly calculated as described in section 3. After correction has been completed, re-
3.1.2. set the control signal to 20 mA.
4. Turn the zero adjuster (6.2) again until
the pressure gauge indicates the re-
quired signal pressure (see section
3.1.2).

34 EB 8355-2 EN
Operation

Note!
Having attached and calibrated the
positioner, make sure that the vent plug on
the housing cover points downward when
the valve is installed in the plant.

4.2 Changing the operating


direction
If you want to change the operating direc-
tion of directly attached positioners (Fig. 3)
after they have been installed, turn the
turnboard (7) and change the position of the
connection block, the positioner, and the
clamp (1.2).
For attachment according to IEC 60534-6
(NAMUR), turn the turnboard (7) and the
positioner on the adapter housing (Fig. 6).
For rotary positioners, reassign the cam
disk as shown in Fig. 9 and 10.
For details on changing the turnboard (7),
refer to section 2 ("Mounting position and
operating direction").

EB 8355-2 EN 35
Operation

4.3 Adjusting the limit switches ing the associated nameplate on the termi-
nal block (also see Fig. 12).
The positioner version with inductive limit
switches has two adjustable tags mounted Note!
on a rotary axis which operate the associ- As the tags of the limit switches cannot be
ated proximity switches (50). turned by 360°, make sure that the switches
To operate the inductive limit switches, con- A and B are correctly assigned to the end
nect the corresponding switching amplifiers positions "valve OPEN" and "valve
in the output circuit (see section 3.2.1). CLOSED", especially when the limit switches
are to be used for fail-safe circuits.
When the tag (51) is inside the inductive
field of the switch, the switch assumes a high
resistance. When the tag is outside the field, The desired switching function, i.e. whether
the switch assumes a low resistance. The the output relay must be picked up or re-
limit switches are usually adjusted to issue a leased when the tag has entered the field,
signal for both end positions. Nevertheless, must be determined by means of jumpers for
they can also be set to signalize intermedi- either working current or closed circuit cur-
ate positions. The switches A and B must be rent at the switching amplifier.
assigned to the end positions of the control
valve (valve OPEN or CLOSED) depending
on the operating direction and the mounting
position according to Tables 8 and 9. The
terminals 41/42 and 51/52 can optionally
be assigned to the switches A and B by turn-

Fig. 14 · Limit switch

36 EB 8355-2 EN
Operation

Setting the switching point


Move the valve to the switching position and
adjust the tag by turning the adjustment
screw (53) so that the switching point is
reached and indicated by the LED on the
switching amplifier. To ensure safe switching
under any condition, the switching point is
to be adjusted to stop approx. 2 % before
the mechanical stop (OPEN – CLOSED) is
reached.

Note!
Having calibrated the positioner, make sure
that the vent plug on the housing cover
points downward when the valve is installed
in the plant.

Table 8 Direct attachment to Type 3277 Actuator (Fig. 3)


Attachment left Attachment right
Switch
Valve position Tag OUT Tag IN Tag OUT Tag IN
CLOSED B A A B
OPEN A B B A

Table 9 NAMUR attachment right or left (Fig. 6) and attachment to rotary actuators (Fig. 8)
Actuator stem extends FA Actuator stem retracts FE
Operating Valve Switch Switch
direction position Tag Tag
OUT IN OUT IN
CLOSED B A A B
>>
OPEN A B B A
CLOSED A B B A
<>
OPEN B A A B

EB 8355-2 EN 37
Operation

4.4 Adjusting the position Zero point (ZERO)


transmitter Use the switches 1 and 2 to preset the zero
point and the ZERO potentiometer for
Note! fine-tuning. The adjusted value always refers
The starting point (zero) and upper range to 4 mA.
value (span) must be set before calibrating
the position transmitter. Span (SPAN)
Use the switches 3 and 4 to preset the span,
Depending on the position of the 4-pin plug i.e. the upper range value, and the SPAN
(symbol on plug: >> or <>), the feedback potentiometer for fine-tuning. The adjusted
signal can be set to either a range of 4 to value always refers to 20 mA.
20 mA or 20 to 4 mA for 0 to 100 % travel.

Example:
Move the valve to open position while ob-
serving the position transmitter signal. If the
signal does not move in the desired direc-
tion, switch over the multi-pin plug. Adjust
the zero point (4 mA) and span (20 mA) for
the valve positions according to Table 10.

Fig. 15 · Position transmitter

Table 10 Position transmitter


Valve movement Observed transmitter signal Direction of signal Adjust zero/span to
20 mA Valve OPEN
OK
4 mA Valve CLOSED
Current increases ↑
Not OK 4 mA Valve OPEN
OPEN →Reconnect plug 20 mA Valve CLOSED

4 mA Valve OPEN
CLOSED OK
20 mA Valve CLOSED
Current decreases ↓
Not OK 20 mA Valve OPEN
→Reconnect plug 4 mA Valve CLOSED

38 EB 8355-2 EN
Operation

Adjusting the zero point


Note on adjusting the position transmitter
1. Use the input signal of the positioner to for positioners with NAMUR adapter
move the valve to closed position (valve housing
CLOSED – travel 0 %). When the positioner and the position
transmitter signal have different operating
2. The ammeter must now indicate approx.
directions (<< and <>), the zero point of the
4 mA.
transmitter signal could be unadjustable due
3. Correct smaller deviations on the ZERO to the additional deflection caused by the
potentiometer until the meter shows ex- bracket (28, Fig. 7) of the adapter housing.
actly 4 mA. If deviations are too high If so, readjust the black pointer (section
and cannot be corrected using the poten- 2.2.2 on page 16) so that the sensor of the
tiometer (adjustment range of approx. position transmitter reaches the control
20 turns), set the switches 1 and 2 to in- range.
dicate an mA value which is within the Unscrew the clamp. For “Actuator stem
adjustment range of the ZERO potenti- extends” (FA), shift the pointer upward
ometer. towards the actuator; for "Actuator stem
retracts" (FE), shift the pointer downward
4. Set the zero point to exactly 4 mA using
towards the valve. For valves with rod-type
the ZERO potentiometer.
yoke, slightly shift the positioner on the rod
in downward (FE) or upward (FA) direction.
Adjusting the span
1. Use the input signal of the positioner to
move the valve to open position (valve
OPEN – travel 100 %).
2. The ammeter must now indicate approx. Note!
20 mA. Every time you make a change as described
above, the zero point and span of the
3. Correct smaller deviations on the SPAN positioner must be readjusted before cali-
potentiometer until the meter shows ex- brating the position transmitter.
actly 20 mA. If deviations are too high,
set the switches 3 and 4 to indicate an
mA value which is within the adjustment
range of the SPAN potentiometer.
4. Turn the SPAN potentiometer until the
meter shows exactly 20 mA. Since zero
and span have a mutual influence on
each other, repeat the correction proce-
dure at both potentiometers until both
values are correct.

EB 8355-2 EN 39
Converting and retrofitting the positioner

5 Converting and retrofitting 3. Place the connecting plate (3) with the
the positioner seal on the housing bores and screw
tight. The restriction must be seated in
the seal above the right internal bore.
Read instructions in section 6 for explo-
sion-protected versions! 4. Replace the cable gland (5) with the
pneumatic screw gland (1).
5. Connect the silicone hose (2) and insert
5.1 Converting from electropneu- the guard plate (4) into the housing.
matic to pneumatic
6. Reattach the support with terminal base.
The electropneumatic positioner can be con- 7. Change the type designation (model no.)
verted into a Type 3766 Pneumatic on the nameplate to Type 3766.
Positioner with the following conversion kit:
M20 x 1.5, order no. 1400-7575
The Mounting and Operating Instructions
1. Remove the support including the termi- EB 8355-1 EN apply for the Type 3766
nal base and disconnect the cable to the Positioner.
i/p module.
2. Unscrew the fastening screws and re-
move the i/p module (6) including the
seals (7, 8).

Fig. 16 · Converting the positioner

40 EB 8355-2 EN
Converting and retrofitting the positioner

5.2 Fitting limit switches 5. Refasten the bracket with plate (1) and
stick the adhesive label for the limit
switches on the housing cover.
Accessories: Limit switch retrofit kit depend-
ing on model index 3767-xxxxxxxxxx.04 6. Screw additional cable gland on the
Order no. 1400-8810 for index .06 or housing.
higher
Order no.1400-7573 for index .04/.05 5.3 Fitting a solenoid valve
Order no.1400-6389 for index .03
Accessories: Solenoid valve retrofit kit
1. Unscrew the bracket with plate (1). Order no. 1400-7122

2. Remove the screws (2) and replace the


entire input unit (3) with a unit including 1. Push the plate (5) to one side.
limit switches. Make sure the O-ring is
2. Unscrew the four screws (7). Lift off the
inserted in the housing.
black cover with the rubber gasket and
3. Attach the terminal block for the limit sig- insert the solenoid valve (6). The rubber
nals 41/42 and 51/52 in the terminal gasket with the restriction is located in
base. the rear of the solenoid valve.
4. Guide the connecting cable to the termi- 3. Unscrew the plate (1).
nals and fasten, (brown = +, blue = −).
4. Attach the terminal block (10) for the so-
lenoid valve in the terminal base.

1 2 3 2 5

10

9 8 7 6
Fig. 17 · Retrofitting limit switches and solenoid valve

EB 8355-2 EN 41
Servicing explosion-protected versions

5. Insert the panel (9) at the rear of the 6 Servicing explosion-protected


positioner and attach it to the input unit versions
using two screws.
6. Guide the connecting cable down behind If a part of the positioner on which the ex-
the mounted panel of the input unit and plosion protection is based needs to be ser-
up again to terminals 81/82 and fasten viced, the positioner must not be put back
(brown = +, blue = –). into operation until an expert has inspected
the device according to explosion protection
7. Screw the bracket with plate (1) back on. requirements, has issued a certificate stating
8. Screw additional cable gland on the this or given the device a mark of confor-
housing. mity.
Inspection by an expert is not required if the
5.4 Removing the solenoid valve manufacturer performs a routine check on
the device prior to putting it back into oper-
Accessories: Cover retrofit kit for solenoid ation. The passing of the routine check must
valve opening, order no. 1400-6949 be documented by attaching a mark of con-
formity to the device.
Explosion-protected components may only
1. Unscrew bracket with plate (1). Remove
be replaced by original, checked compo-
the connecting cable of the solenoid
nents from the manufacturer.
valve from terminals 81/82.
Devices that have already been used outside
2. Unscrew the two screws (7) that are not
of hazardous areas and are intended for
sealed with paint and remove the sole-
use in hazardous areas in future must com-
noid valve with its connecting cable.
ply with the safety demands placed on re-
3. Place the rubber gasket on the spigot of paired devices. Prior to operation, they must
the cover and screw it into the housing be tested according to the specifications
stipulated for "Repairing explosion-pro-
4. Screw on the bracket with plate (1).
tected devices".

42 EB 8355-2 EN
Dimensions in mm

7 Dimensions in mm

Pneumatic connections
G ¼ or ¼ NPT
185

M20 x 1.5
68

19.5
164 29 14 Output (38)
76
37

28
Input signal 150 Supply (9)
Reversing amplifier
(optional)
68
35
39

36
44

50
19.5

N1=113
N2=200
Ø110
56 58

Attachment with intermediate


Attachment IEC 60534-6
piece for rotary actuators
(NAMUR) with adapter housing
Pneum. connection
50 82 of reversing amplifier
Fulcrum of
actuator shaft Output 1 (A1)
28.5
46

56

28.5
76
50

66

164 Output 2 (A2)


Supply (Z)
44 EB 8355-2 EN
EB 8355-2 EN 45
46 EB 8355-2 EN
EB 8355-2 EN 47
48 EB 8355-2 EN
EB 8355-2 EN 49
50
$GGHQGXP3DJH $GGHQGXP3DJH
,QVWDOODWLRQ0DQXDOIRUDSSDUDWXVFHUWLILHGE\&6$IRUXVHLQKD]DUGRXVORFDWLRQV 
 7DEOH7KHFRUUHODWLRQEHWZHHQWHPSHUDWXUHFODVVLILFDWLRQDQGSHUPLVVLEOHDPELHQW
(OHFWULFDOUDWLQJRILQWULQVLFDOO\VDIHDSSDUDWXVDQGDSSDUDWXVIRULQVWDOODWLRQLQKD]DUGRXV
ORFDWLRQV  WHPSHUDWXUHUDQJHVLVVKRZQLQWKHWDEOHEHORZ 

EB 8355-2 EN

7DEOH0D[LPXPYDOXHV 7HPSHUDWXUHFODVV 3HUPLVVEOHDPELHQW
WHPSHUDWXUHUDQJH
 LSFLUFXLW 3RVLWLRQ /LPLWVZLWFKHV 6ROHQRLGYDOYH
LQGLFDWRU LQGXFWLYH  7 ƒ&ƒ&

&LUFXLW 7 ƒ&ƒ&


  DQG 
1R 7 ƒ&ƒ&

7HUPLQDO 
  DQG 
1R  7DEOH)RUWKH0RGHO²3RVLWLRQHUWKHFRUUHODWLRQEHWZHHQWHPSHUDWXUH
 FODVVLILFDWLRQSHUPLVVLEOHDPELHQWWHPSHUDWXUHUDQJHVDQGPD[LPXP
L PD[ 9 9 9 9  VKRUWFLUFXLWFXUUHQWLVVKRZQLQWKHWDEOHEHORZ

8 RU9
L
, RU, PD[

P$ P$ P$ P$ 7HPSHUDWXUHFODVV 3HUPLVVLEOHDPELHQW 0D[LPXPVKRUW
WHPSHUDWXUHUDQJH FLUFXLWFXUUHQW
L PD[ : : P: P:  

3 RU3 7 ƒ&ƒ&
L Q) Q) Q) Q)

& 7 ƒ&ƒ& P$
L —+ —+ —+ —+

/ 7 ƒ&ƒ&

7 ƒ&ƒ&
1RWHV(QWLW\SDUDPHWHUVPXVWPHHWWKHIROORZLQJUHTXLUHPHQWV
  6ROHQRLGYDOYH9DQG9YHUVLRQ3 LRU3PD[QROLPLWHG 7 ƒ&ƒ& P$

 & L PD[  & L PD[  L PD[ D L D  L 7 ƒ&ƒ&
  
8 RU9 ”8 RU9 , RU, ”, RU, 3 ”3 RU3  & •& DQG/ •/

7DEOH&6$²FHUWLILHGEDUULHUSDUDPHWHUVRIFLUFXLWDQG  ,QWULQVLFDOO\VDIHLILQVWDOOHGDVVSHFLILHGLQPDQXIDFWXUHU·VLQVWDOODWLRQPDQXDO
6XSSO\EDUULHU (YDOXDWLRQEDUULHU &6$FHUWLILHGIRUKD]DUGRXVORFDWLRQV
%DUULHU
9 PD[  5  PLQ 9 PD[   ([LD,,&7&ODVV,=RQH  7\SH(QFORVXUH
&ODVV,*URXSV$%&'
FLUFXLW ”9 •  ”9 'LRGH5HWXUQ &ODVV,,*URXSV()*&ODVV,,,

FLUFXLW ”9 •  ”9 'LRGH5HWXUQ 1RWHV
  0D[WZRFDEOHHQWULHVSHUSRVLWLRQHU
FLUFXLW   ”9 •  ”9 'LRGH5HWXUQ 
  (DFKSDLURI,6ZLUHVPXVWEHSURWHFWHGE\DVKLHOGWKDWLVJURXQGHGDWWKH
FLUFXLW   ”9 •  ”9 'LRGH5HWXUQ
 ,6*URXQG7KHVKLHOGVKDOOH[WHQGDVFORVHWRWKHWHUPLQDODVSRVVLEOH
FLUFXLW   9DQG9YHUVLRQ   9YHUVLRQ 
   7KHLQVWDOODWLRQVKDOOEHLQDFFRUGDQFHZLWKWKH&DQDGLDQ(OHFWULFDO&RGH3DUW

 


 
 


 
 

5HYLVLRQV&RQWURO1XPEHU0D\  $GGHQGXPWR(%(1  5HYLVLRQV&RQWURO1XPEHU0D\  $GGHQGXPWR(%(1 


$GGHQGXP3DJH $GGHQGXP3DJH


+$=$5'286  
6$)( &6$FHUWLILHGIRUKD]DUGRXVORFDWLRQV
 
/2&$7,21   /2&$7,21 


&ODVV,'LY*URXSV$%&'  7\SH(QFORVXUH

&ODVV,,'LY*URXSV()*&ODVV,,,
( 
  FRQWUROVLJQDO  FRQWUROOHUVXSSO\ ,33RVLWLRQHUZLWK SRVLWLRQLQGLFDWRUVROHQRLGYDOYHDQGOLPLWVZLWFKHV

  
FLUFXLW
(
 SRVLWLRQLQGLFDWRU

 
+$=$5'286  6$)(

  FLUFXLW
 /2&$7,21 'LY=RQH  /2&$7,21
  OLPLWVZLWFK
 UHQ
 RWL
  FLUFXLW 7HUPLQDO1R
UHOD\RU
OH LV
 R  OLPLWVZLWFK WUDQVLVWRU
 RXWSXW  FRQWUROVLJQDO
 FLUFXLW 
RG 3S
0 L
 VROHQRLGYDOYH
  FLUFXLW
6 WHUW

L
 SRVLWLRQLQGLFDWRU
  FLUFXLW
78$ P V
 FLUFXLW

5$ QUDW
OLPLWVZLWFK
 HUQ
  OLPLWVZLWFK
33 \
 FLUFXLW
 WLRL
7HUPLQDO1R
OH V  FLUFXLW $' DHOU
  OLPLWVZLWFK
VXSSO\EDUULHU

GR R3 (, UWR
 FLUFXLW
), LV
 HYDOXDWLRQEDUULHU
0 3, &( V
 VROHQRLGYDOYH
Q
 VXSSO\EDUULHU
  FLUFXLW
631 UDW
HYDOXDWLRQ 8 J

,6*URXQG H
 , transmitter *URXQG
9HUVLRQ  0RGHOZLWKLSFRQYHUWHUVROHQRLGYDOYHDQGLQGXFWLYHOLPLWVZLWFKHV  1RWHV
   0RGHOZLWKLSFRQYHUWHUDQGSRVLWLRQLQGLFDWRU 
 
&LUFXLW&RQWUROOHU&6$FHUWLILHGRU&6$²FHUWLILHGEDUULHUV   7KHLQVWDOODWLRQVKDOOEHLQDFFRUGDQFHZLWKWKH&DQDGLDQ(OHFWULFDO&RGH3DUW
 
5HOD\RUWUDQVLVWRURXWSXWRUFKDQQHO V UHVS&6$FHUWLILHG   )RUWKHPD[LPXPYDOXHVIRUWKHLQGLYLGXDOFLUFXLWVVHH7DEOHDQG


6XSSO\DQGHYDOXDWLRQEDUULHU&6$FHUWLILHG   7KHFDEOHVVKDOOEHSURWHFWHGE\FRQGXLWV
3RVLWLRQLQGLFDWRUFKDQQHORQO\YHUVLRQ 

  &DEOHHQWU\RQO\ULJLGPHWDOFRQGXLWDFFRUGLQJWRGUDZLQJ

 1R7DQG7
)RUWKHSHUPLVVLEOHPD[LPXPYDOXHVIRUWKHLQWULQVLFDOO\VDIHFLUFXLWVVHH7DEOH
)RUWKHSHUPLVVLEOHEDUULHUSDUDPHWHUVIRUWKHFLUFXLWVDQGVHH7DEOH
 
&DEOHHQWU\0[RUPHWDOFRQGXLWDFFRUGLQJWRGUDZLQJ1R²7 
RU²7 

2QLQWHUFRQQHFWLRQWRIRUPJURXQGIUHHVLJQDOFLUFXLWVRQO\HYDOXDWLRQEDUULHUVVKDOOEH 
LQVWDOOHGLQWKHUHWXUQOLQH&RUUHFWSRODULW\VKDOOEHHQVXUHG 











EB 8355-2 EN
5HYLVLRQV&RQWURO1XPEHU0D\  $GGHQGXPWR(%(1  5HYLVLRQV&RQWURO1XPEHU0D\  $GGHQGXPWR(%(1 

51
52
$GGHQGXP3DJH $GGHQGXP3DJH   

 ,QVWDOODWLRQ0DQXDOIRUDSSDUDWXVDSSURYHGE\)0IRUXVHLQKD]DUGRXVORFDWLRQV
,QVWDOODWLRQGUDZLQJ&RQWURO5HOD\.+$²27,([.+$²27,([RU 
.+$²27,([ZLWK0RGHO6-E13UR[LPLW\6HQVRUV (OHFWULFDOUDWLQJRILQWULQVLFDOO\VDIHDSSDUDWXVDQGDSSDUDWXVIRULQVWDOODWLRQLQKD]DUGRXV
ORFDWLRQV

EB 8355-2 EN
 
 7DEOH0D[LPXPYDOXHV
 +$=$5'286 6$)(
 /2&$7,21 /2&$7,21  LSFLUFXLW 3RVLWLRQ /LPLWVZLWFKHV 6ROHQRLGYDOYH
0RGHOGHVLJQDWLRQFRGH7\SH.+DE²F([G
LQGLFDWRU LQGXFWLYH
([LD,,&&ODVV,=RQH
&ODVV,*URXSV$%&' 7HUPLQDOV
&ODVV,,*URXSV()*&ODVV,,,  &LUFXLW1R   DQG 
D 6XSSO\9ROWDJHW\SH$RU'
D $&G '&
 E 6XSSO\/HYHO 
W
F  9'&“ 9$& 7HUPLQDO1R   DQG 
WD WRLQWULQVLFDOO\  9$& 
 Q VDIHRXWSXW F 2XWSXWW\SH277$RU7$
R
F G 1XPEHURIFKDQQHOVRU
L
8 RU9PD[ 
9 9 9 9


,L RU,PD[ 
P$ P$ P$ P$
 
 W
X : : P: P:  
LQWULQVLFDOO\VDIH S
W  3LRU3PD[ 
    X OV
R D
U 
7HUPLQDO1R RXWSXW G LQ
  Q Q) Q) Q) Q)
HQ
P
U
&L 
 D

WRVHQVRURUFRQWDFW \ H
W
RLW LW
 O
S
LV XF
SUR[LPLW\VHQVRU FKDQQHO S /L 
—+ —+ —+ —+
  X
V
3R UFL

3, KF   
  LW LQWULQVLFDOO\VDIH
 ZV    1RWHV(QWLW\SDUDPHWHUVPXVWPHHWWKHIROORZLQJUHTXLUHPHQWV
 
 WL SUR[LPLW\VHQVRU RXWSXW   6ROHQRLGYDOYH9DQG9YHUVLRQ3L RU3PD[QROLPLWHG 
 
WRVHQVRURUFRQWDFW   6ROHQRLGYDOYH9YHUVLRQ3LRU3PD[P:
O LP
 
HG / 
R FKDQQHO 
 6ZLWFK,VRODWRUV
0       
8 RU9&RU9W ”8LRU9PD[  , RU,&RU,W ”,L RU,PD[3 RU3PD[”3LRU3PD[  
7\SH.+$²27,([
RU.+$²27,([    
 &D •&L &FDEOHDQG/D •/L/FDEOH
RU.+$²27,([ 
WRRQHFRPPRQ
 OLQHSRVVLEOH 7DEOH)0&6$²DSSURYHGEDUULHUSDUDPHWHUVRIFLUFXLWDQG 

      &6$&HUWLILHG 6XSSO\EDUULHU (YDOXDWLRQEDUULHU
%DUULHU
 9& 5PLQ ,& 3PD[ 9& 5PLQ ,6&
 FLUFXLW ”9 •  ”P$ ”: ”9  P$
7KHWRWDOVHULHVLQGXFWDQFHDQGVKXQWFDSDFLWDQFHRIVKLHOG
 PD[LPXPFDSDFLWDQFHRIHDFKLQGXFWLYHVHQVRUQ)
ZLULQJVKDOOEHUHVWULFWHGWRWKHIROORZLQJPD[LPXPYDOXHV PD[LPXPLQGXFWDQFHRIHDFKLQGXFWLYHVHQVRU—+ ”9 •  ”P$ ”: ”9  P$
 FLUFXLW
6\VWHPSDUDPHWHUV FLUFXLW   ”9 •  ”P$   ”9  P$

&RQWURO5HOD\ FLUFXLW   ”9 •  ”P$   ”9  P$


   
7HUPLQDO1R *URXSV / & 9& ,6& 9PD[ 5PLQ
>P+@ >—)@ >9@ >P$@ >9@ > @

$%  


'LYLVLRQZLULQJPHWKRGVKDOOEHLQ FLUFXLW   9DQG9YHUVLRQ   9YHUVLRQ
DFFRUGDQFHWRWKH 
 &DQDGLDQ(OHFWULFDO&RGH3DUW 

 &'       



()*   

 
5HYLVLRQV&RQWURO1XPEHU0D\  $GGHQGXPWR(%(1  5HYLVLRQV&RQWURO1XPEHU$XJXVW $GGHQGXPWR(%(1 
$GGHQGXP3DJH    $GGHQGXP3DJH   

7DEOH7KHFRUUHODWLRQEHWZHHQWHPSHUDWXUHFODVVLILFDWLRQDQGSHUPLVVLEOHDPELHQW 

WHPSHUDWXUHUDQJHVLVVKRZQLQWKHWDEOHEHORZ +$=$5'286  


6$)(
 
/2&$7,21   /2&$7,21 

7HPSHUDWXUHFODVV 3HUPLVVEOHDPELHQW 
WHPSHUDWXUHUDQJH 
(
  FRQWUROVLJQDO  &RQWUROOHU6XSSO\
7 ƒ&   FLUFXLW 
(
 SRVLWLRQLQGLFDWRU


7 ƒ&”WD”ƒ&  FLUFXLW

 U
  OLPLWVZLWFK
 HQ
7 ƒ&
 WLR
  FLUFXLW
UHOD\RU
 OLPLWVZLWFK
OH VLR 
 WUDQVLVWRU
 RXWSXW
GR 3
7DEOH)RUWKH0RGHO²3RVLWLRQHUWKHFRUUHODWLRQEHWZHHQWHPSHUDWXUH  FLUFXLW

0 SL
 FODVVLILFDWLRQSHUPLVVLEOHDPELHQWWHPSHUDWXUHUDQJHVDQGPD[LPXP VROHQRLGYDOYH


 VKRUWFLUFXLWFXUUHQWLVVKRZQLQWKHWDEOHEHORZ 
 FLUFXLW

3HUPLVVLEOHDPELHQW 0D[LPXPVKRUW 7HUPLQDO1R
7HPSHUDWXUHFODVV 
WHPSHUDWXUHUDQJH FLUFXLWFXUUHQW 


7 ƒ& VXSSO\EDUULHU


 HYDOXDWLRQ EDUULHU
7 ƒ&”WD”ƒ& P$  VXSSO\EDUULHU

HYDOXDWLRQEDUULHU

7 ƒ& ,6*URXQG


9HUVLRQ  0RGHOZLWKLSFRQYHUWHUVROHQRLGYDOYHDQGLQGXFWLYHOLPLWVZLWFK HV  
7 ƒ&    0RGHOZLWKLSFRQYHUWHUDQGSRVLWLRQLQGLFDWRU

7 ƒ&”WD”ƒ& P$ &LUFXLW&RQWUROOHU)0&6$DSSURYHGRU)0&6$²DSSURYHGEDUULHUV

7 ƒ& 5HOD\RUWUDQVLVWRURXWSXWRUFKDQQHO V UHVS)0&6$DSSURYHG
6XSSO\DQGHYDOXDWLRQEDUULHU)0&6$DSSURYHG
3RVLWLRQLQGLFDWRUFKDQQHORQO\YHUVLRQ
)0DSSURYHGIRUKD]DUGRXVORFDWLRQV 

&ODVV,=RQH$([LD,,&7  1(0$7\SH; )RUWKHSHUPLVVLEOHPD[LPXPYDOXHVIRUWKHLQWULQVLFDOO\VDIHFLUFXLWVVHH7DEOH


&ODVV,,,,,,'LYLVLRQ*URXSV$%&'()* )RUWKHSHUPLVVLEOHEDUULHUSDUDPHWHUVIRUWKHFLUFXLWVDQGVHH7DEOH
 
1RWHV &DEOHHQWU\0[RUPHWDOFRQGXLWDFFRUGLQJWRGUDZLQJ1R²7
  7KHDSSDUDWXVPD\EHLQVWDOOHGLQLQWULQVLFDOO\VDIHFLUFXLWVRQO\ZKHQXVHGLQFRQMXQFWLRQ
RU²7
ZLWKWKH)0DSSURYHGDSSDUDWXV)RUPD[LPXPYDOXHVRI

   
8L RU9PD[,LRU,PD[3L RU3PD[&LDQG/L RIWKHYDULRXVDSSDUDWXVVHH7DEOH

  7KHDSSDUDWXVPD\EHLQVWDOOHGLQLQWULQVLFDOO\VDIHFLUFXLWVRQO\ZKHQXVHGLQ FRQMXQFWLRQ
ZLWKWKH)0DSSURYHGLQWULQVLFDOO\VDIHEDUULHU
)RUEDUULHUVHOHFWLRQVHH7DEOH

  ,QVWDOODWLRQPXVWEHLQDFFRUGDQFHZLWKWKH1DWLRQDO(OHFWULFDO&RGH$16,1)3$DQG
$16,,6$53

  8VHRQO\VXSSO\ZLUHVVXLWDEOHIRUƒ&DERYHVXUURXQGLQJWHPSHUDWXUH 


EB 8355-2 EN
5HYLVLRQV&RQWURO1XPEHU$XJXVW $GGHQGXPWR(%(1  5HYLVLRQV&RQWURO1XPEHU$XJXVW $GGHQGXPWR(%(1 

53
54

$GGHQGXP3DJH   
$GGHQGXP3DJH  

)0DSSURYHGIRUKD]DUGRXVORFDWLRQV ,QVWDOODWLRQGUDZLQJ&RQWURO5HOD\.+DEF([GHZLWK0RGHO6-E13UR[LPLW\6HQVRUV
&ODVV,'LYLVLRQ*URXSV$%&'  +$=$5'286 6$)(
&ODVV,,'LYLVLRQ*URXSV)*&ODVV,,,  /2&$7,21 /2&$7,21

EB 8355-2 EN
 &ODVV,'LYLVLRQ*URXSV$%&'
 &ODVV,,'LYLVLRQ*URXSV()DQG*
1(0$7\SH;
  &ODVV,,,'LYLVLRQ
LSSRVLWLRQHUZLWK SRVLWLRQLQGLFDWRUVROHQRLGYDOYHDQGOLPLWVZLWFKHV
 0RGHOGHVLJQDWLRQFRGH7\SH.+DE²F([G

 7HUPLQDOV
 D 6XSSO\9ROWDJHW\SH$RU'
 
+$=$5'286  6$)( D $&G '&
 W E 6XSSO\/HYHO
F  9'&“ 9$&
/2&$7,21 'LY  /2&$7,21 WRLQWULQVLFDOO\
 DQW VDIHRXWSXW  9$&
FR F 2XWSXWW\SH277$RU7$
7HUPLQDO1R
 G 1XPEHURIFKDQQHOVRU

 FRQWUROVLJQDO

LQWULQVLFDOO\RXWSXW
U
  
 FLUFXLW 68 HLWW WHPLQDO1R WRVHQVRURUFRQWDFW  
 SRVLWLRQLQGLFDWRU P 
 W
U
FKDQQHO  X
U  FLUFXLW
$75 VDQ Q
H W  WS V 
 X O
R
 D
$3 WU
 OLPLWVZLWFK G LQ
 HRQ LRLW XLF
 V U SUR[LPLW\VHQVRU Q P

 LLW 3$ \OD
 FLUFXLW D UH
RS FL
O\ W
' HU
VRIWZDUHOLPLWVZLWFK LQWULQVLFDOO\RXWSXW
OH V
R  OLPLWVZLWFK  S HK    S
S
SUR[LPLW\VHQVRU WRVHQVRURUFRQWDFW X
,() URW L FLW
6
RG 3 
0 LS  FLUFXLW ,& LV   Z  
 VRIWZDUHOLPLWVZLWFK FKDQQHO
VROHQRLGYDOYH
 VW
  L  
(3 VDQ
 O
 FLUFXLW WRRQHFRPPRQ
61 WU HG LP
8 J  RO OLQHSRVVLEOH
H 0 6ZLWFK,VRODWRUV
, transmitter  7\SH.+DE²F([G
7\SH.+DE²F([GH
*URXQG

PD[LPXPFDSDFLWDQFHRIHDFKLQGXFWLYHVHQVRUQ)

PD[LPXPLQGXFWDQFHRIHDFKLQGXFWLYHVHQVRU—+ 0RGHOGHVLJQDWLRQFRGH7\SH.+DE²F([GH
1RWHV 
  7KHLQVWDOODWLRQPXVWEHLQDFFRUGDQFHZLWKWKH1DWLRQDO(OHFWULFDO&RGH$16,1)3$
D 6XSSO\9ROWDJHW\SH$RU'
D $&G '&
  E 6XSSO\/HYHO
7KHWRWDOVHULHVLQGXFWDQFHDQGVKXQWFDSDFLWDQFHRIVKLHOG
  )RUWKHPD[LPXPYDOXHVIRUWKHLQGLYLGXDOFLUFXLWVVHH7DEOHDQG ZLULQJVKDOOEHUHVWULFWHGWRWKHIROORZLQJPD[LPXPYDOXHV  9'&“ 9$&

  9$&
F 2XWSXWW\SH57$5:666656
  7KHFDEOHVVKDOOEHSURWHFWHGE\FRQGXLWV  6567RU627
 / & 9& ,6& G 1XPEHURIFKDQQHOVRU
&RQWURO5HOD\ H 3RZHUUDLOGHVLJQDWLRQ363RU*63
  &DEOHHQWU\RQO\ULJLGPHWDOFRQGXLWDFFRUGLQJWRGUDZLQJ *URXSV
7HUPLQDO1R >P+@ >—)@ LQFOXGHV0RGHO.+'(%3%3RZHU)HHG
 1R7DQG7
>9@ >P$@ 0RGXOH RU%ODQN
$%  
 &(  
  
')*  

5HYLVLRQV&RQWURO1XPEHU$XJXVW $GGHQGXPWR(%(1  5HYLVLRQV&RQWURO1XPEHU$XJXVW $GGHQGXPWR(%(1 


EB 8355-2 EN 55
S/Z 2007-11

SAMSON AG · MESS- UND REGELTECHNIK


Weismüllerstraße 3 · 60314 Frankfurt am Main · Germany
Phone: +49 69 4009-0 · Fax: +49 69 4009-1507
Internet: http://www.samson.de EB 8355-2 EN

You might also like