Netsure DC Distribution Panels
Distribution Panels
• 80A up to 600A
Product Overview Application
y Flexible output options DC distribution panels for Vertiv™ NetSure™ distribution panels are ideal for
NetSure™ systems are designed to installations where overcurrent protection
• Single load or A & B provide overcurrent protection for multiple or separation of load circuits is required
output options small loads. Panels accept either fuses on the output of a rectifier or converter.
y Compact panels from 1A to 20A or load breakers up to Panels can be pre-installed in NetSure DC
150A. Options include up to (36) GMT power systems from Vertiv or purchased
• 19"W or 23"W with adapters fuses or up to (4) load breakers and (12) as a stand-alone item.
GMT fuses. The fuses plug into one of the
y Ease of installation
mounting positions on the front panel. Additional information
• Front or rear accessible
Each position has a localized return
terminals for attaching For additional specification,
load conductors
landing. An isolated Form-C alarm output
engineering or installation information,
is available on each panel as well as a
use specification number 520406,
y Isolated Form-C alarm output resistive battery alarm output. Any panel
545277, 545700, 548066, 548067,
can be mounted in a 19" or 23" relay rack,
y Ideal for stand-alone applications 562579, 563171 or 563317..
wall mounted, or flush mounted.
or adding supplemental DC
distribution to existing Vertiv™
NetSure™ solutions
562579
563171
563317
1
Vertiv™ NetSure™ DC Distribution Panels
Distribution Panels
520406 545277 24V or 48V DC 545700 48V DC GMT
Circuit Breaker Assembly Distribution Panel Assembly Distribution Fuse Panel Assembly
Accepts up to (2) separately ordered Accepts up to (20) bullet nose-type Accepts up to (20) separately ordered
GJ-type circuit breakers, as well as a circuit breakers or TPS/TLS type fuses GMT fuses. May be connected for single
third circuit breaker if an accessory in bullet nose fuse holders. Designed load distribution or dual (A and B side)
circuit breaker mounting kit is ordered for mounting on a wall or in a 23" relay load distribution. Designed for mounting
and installed. This assembly is designed rack. Maximum current rating is 600 in a 19" or 23" relay rack. Includes an
for wall mounting. Furnished brackets amperes. Panel is UL Listed for use in external fuse alarm circuit card which
permit mounting in either a 19" or 23" DC power distribution centers for provides resistive battery and Form-C
relay rack. communications equipment. relay contacts for external alarm circuits.
2
Distribution Panels (continued)
548066 48V DC 548067 48V DC 562579 48V DC
Distribution Cabinet Assembly Distribution Cabinet Assembly Distribution Panel Assembly
Accepts up to (19) TPS/TLS-type fuses Accepts up to (24) TPS/TLS-type fuses Accepts up to (12) GMT fuse load
(3 to 100A) or bullet nose type circuit (3 to 100A) or bullet nose type circuit positions and (4) bullet nose-type
breakers (1 to 250A). Designed for breakers (1 to 250A). Designed for circuit breaker load positions. Designed
mounting in a 19" relay rack. mounting in a 23" relay rack. for mounting in a 19" relay rack. UL
Recognized for use in DC power
distribution centers for communications
equipment. Includes an external fuse
alarm circuit card which provides resistive
battery and Form-C relay contacts to
external CBA/FA alarms. Relay contacts
rated for 30 VDC @ 2 A.
Accepts up to (36) GMT fuse load 19" panel accepts up to (20) fuse load
positions. Designed for mounting in a positions. 19" and 23" relay rack mounting
19" relay rack. UL Recognized for use options available. Offers dual (Side A and
in DC power distribution centers for Side B) load distribution. Includes:
communications equipment. Includes
y Local alarm/status indicators (Feed A
an external fuse alarm circuit card which
Power, Feed B Power, Feed A FA, Feed
provides resistive battery and Form-C
B FA, Major, and Minor)
relay contacts to external CBA/FA alarms.
Relay contacts rated for 30 VDC @ 2 A. y Alarm relay contacts (Major, Minor, A
Power Fail, B Power Fail, and FA) for
connection to external alarms
Fuses
Part Number Ampere Rating Fuse Color
248610301 18/100 GMT -A -
248610200 1/4 Violet
248610300 1/2 Red
248610500 3/4 Brown
248610700 1-1/3 White
248610800 2 Orange
248610900 3 Blue
248611000 5 Green
248611300 7-1/2 Black-White
248611200 10 Red-White
248611500 15 Red-Blue
248872600 Replacement Dummy Fuse Replacement Dummy Fuse
102774 Replacement Safety Fuse Cover Replacement Safety Fuse Cover
Vertiv.com | Vertiv Headquarters, 1050 Dearborn Drive, Columbus, OH, 43085, USA
© 2020 Vertiv Group Corp. All rights reserved. Vertiv™ and the Vertiv logo are trademarks or registered trademarks of Vertiv Group Corp. All other names and logos referred to are trade names, trademarks or registered trademarks of their respective owners. While every
precaution has been taken to ensure accuracy and completeness here, Vertiv Group Corp. assumes no responsibility, and disclaims all liability, for damages resulting from use of this information or for any errors or omissions. Specifications, rebates and other promotional
offers are subject to change at Vertiv’s sole discretion upon notice.
DC-00135 (R06/20) 4