www.arpnjournals.com
ABSTRACT
Recognition and categorization of voltage and current distortions in an electrical network is a critical assignment
in power systems control and security. This present work introduces a novel hybrid technique for electrical network
distortions recognition and categorization. The idea of least mean square filter collectively with discrete wavelet transform
is utilized to estimate important features such as magnitude and slope from the measured voltage or current signals. The
discrete wavelet transform is utilized to enable least mean square filter to afford a decent execution; the measured voltage
or current signal is sent to the discrete wavelet transform to find the noise present in it and its variance. The noise and its
variance are then passed collectively with the measured signal to the least mean square filter. These two features are treated
as the fuzzy inputs to the expert system that employs a few standards on the fuzzy inputs to distinguish the category in
which the measured signal has a place. To demonstrate the capacity of the presented hybrid method for categorizing the
power quality distortions, a point by point computerized simulation and its outcomes including different sorts of power
quality occasions are exhibited. The simulation outcomes delineate that the presented hybrid method has the capacity to
precisely recognize and categorizing the power quality distortions.
Keywords: discrete wavelet transform, fuzzy expert system, least mean square filter, power quality, power system disturbances.
2007
VOL. 13, NO. 6, MARCH 2018 ISSN 1819-6608
ARPN Journal of Engineering and Applied Sciences
©2006-2018 Asian Research Publishing Network (ARPN). All rights reserved.
www.arpnjournals.com
are not generally convenient because of the settings that a fuzzy expert framework that uses a few standards on
depend for the most part on the designer or administrator them to recognize and order the power quality occasions in
of the frameworks for a specific arrangement of occasions. the measured waveform. A few computerized simulation
If numerous occasion types or features are examined, the outcomes utilizing MATLAB and practical information
expert framework would turn out to be more confused and outcomes are displayed to fulfil and guarantee the capacity
dangers of losing selectivity would increment. of the presented method for characterizing the distortions
In this paper, two phases system for effectively.
distinguishing the power system distortions is proposed. In
the principal phase, the measured voltage waveform is PRESENTED METHODOLOGY
gone through discrete wavelet change (DWT) to The presented approach is depicted in Figure-1.
distinguish its noise [22]. The variance of this noise The two phases are executed with every voltage signals,
together with the measured voltage waveform is sent to the (i) calculating an updated esteem of features (magnitude
LMS filter to improve and accelerate its rate of and slope) using LMS filter with the use of DWT, (ii)
convergence. In the next phase, the outputs of the LMS categorizing the distortions using fuzzy expert system with
filter; the magnitude of the measured voltage waveform the aid of estimated features.
and its rate of progress with time (slope), are gone through
Magnitude Signal
Captured Signal Classification
LMS Filter Fuzzy Expert System
Slope
−
, = (2)
√| |
Adaptive
where a and b are the time shift and scale Process
respectively, 𝑡 is the mother wavelet and other
wavelets are its shifted time and scaled version. Figure-2. Least mean square filter.
The DWT computations are made for a selected
subset of scales and time shift. This strategy is carried by Least mean square filter (LMS filter)
utilizing filters and calculating the details and The LMS method of signal feature extraction is
approximations components. The details (D) are the low depicted in Figure-2, where yt denotes the actual signal, ŷ
scale, high frequency components of the signal. The denotes the signal estimate and Xt = [x0t, x1t, …, xN-1t]T is
approximations (A) are the high scale, low frequency the input vector at the tth instant. The signal can be
components of the signal. The DWT coefficients are assessed accurately by the filter with an appropriate
calculated as follows: esteem of its coefficient Wt, which is computed by
reducing the squared of the signal error et [24]. Thus the
, = , ∑ [𝑛]𝑔 , [𝑛] (3) framework gains knowledge from its condition; this is
represented as a tuned filter where the filter coefficients
where a = 2j, b = k2j, j N, k N. The wavelet are adapted in a recursion manner towards their optimal
filter g plays the role of . esteems. At every iteration, the weight vector W t is
calculated as,
+ = + − t (4)
2008
VOL. 13, NO. 6, MARCH 2018 ISSN 1819-6608
ARPN Journal of Engineering and Applied Sciences
©2006-2018 Asian Research Publishing Network (ARPN). All rights reserved.
www.arpnjournals.com
where is the adaptation parameter, Wt = [w0t, where A is the magnitude of the complex signal
w1t, …, wN-1t]T is the filter coefficient and t is the Vt, and 𝜉 is its noise component and ̂ = 𝐴 𝜔 ∆𝑇+𝜑 .
gradient of the error performance surface with respect to The voltage can be formulated as,
filter coefficient, this can be calculated as,
̂ = ̂− 𝜔∆𝑇
(11)
̂= − (5)
This formula is used in the proposed feature
The recursion (4) is known as the LMS technique extraction method and the strategy that explains the
and it is initialized by assuming all filter coefficients as extraction procedure is depicted in Figure-3. The error
zero. First the technique continues by calculating the error signal et for this situation is calculated as,
signal et, then it is employed to calculate the adapted
coefficients. This process is executed till the stable = −̂ (12)
conditions are achieved. The stableness of the closed loop
network is administered by the parameter and it ought to where ̂ is the evaluated esteem of voltage at the
fulfil the following criteria, th
t time. Then
where the total input power pertains to the sum of where the weight = 𝜔̂𝑡− ∆𝑇 , ̂ is the
the mean squared value of the input data. When the calculated angular frequency. The essentialness of the
adaptation parameter is little, the LMS technique model is that the input data consists of only one
consumes huge time to gain knowledge about its input component and the weight vector. The complex LMS
with least mean square error and vice versa. Accordingly, method as introduced in [11] is utilised to calculate the
a time changing step sized ordering of is desirable for state. The method reduces the square of the signal error by
optimal convergence [25]. recursively changing the complex weight vector at
every sampling time as,
LMS BASED FEATURE EXTRACTION
The voltage signal of a three phase electrical = − + ̂∗ (14)
network can be presented in discrete mode as,
where * denotes the complex conjugate of the
V t = Vm cos ωt∆T + φ + ϵ value and is the convergence parameter ensuring the
t
π stability and convergence rate of the technique.
V t = Vm cos ωt∆T + φ − +ϵ t The step size is changed as in [24] for good
π
V t = Vm cos ωt∆T + φ + +ϵ (7) convergence of the LMS technique in the presence of
t
noise. For complex states, the equations can be updated as,
where Vm is the maximum magnitude of the
fundamental component, ϵt is the noise present in the + = + 𝛾𝑝 𝑝∗ (15)
voltage signal, t is the sampling time, φ is the phase of
where 𝑝 denotes the autocorrelation of and
fundamental component, and ω is the angular frequency of
is calculated as
the voltage signal (ω = πf, with f being the system −
2009
VOL. 13, NO. 6, MARCH 2018 ISSN 1819-6608
ARPN Journal of Engineering and Applied Sciences
©2006-2018 Asian Research Publishing Network (ARPN). All rights reserved.
www.arpnjournals.com
The fuzzy output of the proposed FIS is power following section. The slope and fuzzy output membership
quality of the voltage signal which has five membership functions are estimated by training approach.
functions and is projected as normal, sag, swell, outage The set of fuzzy rule are given as follows:
and surge. In this work, a number between 0 and 3 is If (the magnitude is SM) and (the slope is PS) then
assigned for the crisp output of the mamdani type FIS, (the output is Sag).
where Outage = 0, Sag = 0.5, Normal = 1, Swell = 1.5 and If (the magnitude is VSM) and (the slope is PS) then
Surge = 2. The membership function plot of the fuzzy (the output is Outage).
output is shown in Figure-6. The ranges of magnitude If (the magnitude is LM) and (the slope is PS) then
membership function are estimated based on the definition (the output is Swell).
of each power quality occasion as described in the If (the magnitude is VLM) and (the slope is PS) then
(the output is Surge).
2010
VOL. 13, NO. 6, MARCH 2018 ISSN 1819-6608
ARPN Journal of Engineering and Applied Sciences
©2006-2018 Asian Research Publishing Network (ARPN). All rights reserved.
www.arpnjournals.com
If (the magnitude is NM) and (the slope is ZS) then If (the magnitude is VLM) and (the slope is NS) then
(the output is Normal). (the output is Surge).
If (the magnitude is VSM) and (the slope is ZS) then
(the output is Outage). In the past rules, the categorization of few power
If (the magnitude is SM) and (the slope is NS) then quality occasions such as a voltage sag and swell can be
(the output is Sag). just in view of the magnitude input, but the second input
If (the magnitude is VLM) and (the slope is ZS) then slope in the rules 1 and 7 for a voltage sag; and in the rules
(the output is Surge). 3 and 9 for a voltage swell is utilized to recognize the
If (the magnitude is LM) and (the slope is NS) then starting and the end of these occasions, thus these rules are
(the output is Swell). more valuable for both classifying and distinguishing the
power quality distortions.
SIMULATION RESULTS the power to the distribution system that contains a short
In this work, power quality distortions signals are transmission line section and three loads such as normal,
five voltage signal distortions admitting sag, swell, outage, heavy, and nonlinear loads at the point of common
surge and harmonic distortions [27]. These voltage coupling (PCC). Each generated signal comprises of 25
distortions are produced by using MATLAB software as cycles of a voltage waveform sampled at a rate of 6.4 kHz,
per the simulation test network shown in Figure-7. The which is equal to 128 samples per cycle. The following
simulation test network comprises of a generator providing simulation analyses are proposed to outline the
2011
VOL. 13, NO. 6, MARCH 2018 ISSN 1819-6608
ARPN Journal of Engineering and Applied Sciences
©2006-2018 Asian Research Publishing Network (ARPN). All rights reserved.
www.arpnjournals.com
performance and efficiency of the presented method. The network through a circuit.
heavy and nonlinear loads are interconnected to the
Figure-8. Voltage sag: (a) waveform, (b) magnitude, (c) slope and (d) fuzzy output.
Voltage swell LMS filter are depicted in Figure-9b and c. The crisp
On account of voltage swell, there is an ascent of output of the fuzzy logic controller is depicted in Figure.
10-90% in the voltage magnitude for 0.5 cycles to 1 min. 9d. It is clearly discovered that the presented method
The swell is produced by detaching the substantial load for clearly detects and characterizes the swell disturbance.
10 cycles. The exponential decaying voltage swell from The tracking error of fuzzy output for the swell signal is
0.2 sec to 0.4 sec at power transmission line is depicted in under 0.2%.
Figure-9a. The magnitude and the slope outputs from the
2012
VOL. 13, NO. 6, MARCH 2018 ISSN 1819-6608
ARPN Journal of Engineering and Applied Sciences
©2006-2018 Asian Research Publishing Network (ARPN). All rights reserved.
www.arpnjournals.com
Figure-9. Voltage swell: (a) waveform, (b) magnitude, (c) slope and (d) fuzzy output.
Voltage outage magnitude and the slope outputs from the LMS filter are
An outage might be viewed as lost of voltage on depicted in Figure-10b and c. The crisp output of the fuzzy
the network. Such distortion depicts a drop of 90–100% of logic controller is depicted in Figure-10d. It is clearly
the rated bus voltage for duration of 0.5 cycles to 1 min. A discovered that the presented hybrid method can exactly
waveform of the exponential decaying voltage outage identify the outage in the disturbance waveform. The
produced by a 10 cycle three phase short circuit fault from tracking error of fuzzy output for the voltage outage is
0.2 sec to 0.4 sec at PCC is depicted in Figure-10a. The under 0.1%.
Figure-10. Voltage outage: (a) waveform, (b) magnitude, (c) slope and (d) fuzzy output.
Voltage surge magnitude and the slope outputs from the LMS filter are
The surge happens on unplugging the substantial depicted in Figure-11b and c. The crisp output of the fuzzy
load for one quarter cycle as depicted in Figure-11a and b, logic controller is depicted in Figure-4d. It is clearly
where the magnitude is all of a sudden raised from 1 to 3 discovered that the presented method clearly detects and
p.u. The sudden change in voltage waveform from 0.2 sec characterizes the swell disturbance. The tracking error of
to 0.21 sec at PCC is depicted in Figure-11a. The the magnitude is under 0.4%.
2013
VOL. 13, NO. 6, MARCH 2018 ISSN 1819-6608
ARPN Journal of Engineering and Applied Sciences
©2006-2018 Asian Research Publishing Network (ARPN). All rights reserved.
www.arpnjournals.com
Figure-11. Voltage surge: (a) waveform, (b) magnitude, (c) slope and (d) fuzzy output.
Figure-12. Voltage harmonic: (a) waveform, (b) magnitude, (c) slope and (d) fuzzy output.
2014
VOL. 13, NO. 6, MARCH 2018 ISSN 1819-6608
ARPN Journal of Engineering and Applied Sciences
©2006-2018 Asian Research Publishing Network (ARPN). All rights reserved.
www.arpnjournals.com
The tracking error of LMS filter is observed to be that the presented method has the capability to discover
under 0.5%. The tracking error depicts the measured and categorize the power system distortions with good
voltage magnitude using LMS filter. If the magnitude is exactness, precise and very less computational time when
assessed with high precision and minimum tracking error, compared with other existing strategies.
the slope is precisely assessed. Subsequently, the fuzzy
inputs (magnitude and slope) are exact. This implies that REFERENCES
the fuzzy classifier will give accurate outcomes. For every
sort of power system distortions, another 100 case studies [1] Bollen MHJ. 2000. Understanding power quality
were set up by altering the values of all loads (normal, problems: voltage sags and interruptions. New York:
heavy, nonlinear) and altering the starting and the end time IEEE Press.
instant of every disturbance. The generated signals are
mixed with random white noise of zero mean and [2] Baggini Angelo. 2008. Handbook of power quality.
distinctive ranges of the signal to noise ratio (SNR) (20 db,
New York: John Wiley & Sons.
30 db and 40 db). In [28], a hybrid strategy utilizing a
DWT, kalman filter and fuzzy expert system for the
[3] R. Thilepa, S. Devakumar and D. J. Yogaraj. 2015.
categorization of power quality disturbance was proposed.
The simulation outcomes demonstrate that the normal Power quality improvement by voltage control using
classification accuracies of the proposed hybrid technique dstatcom in MATLAB. ARPN Journal of Engineering
are 95.57%, 97.85% and 99% with SNR 20 dB, 30 dB and and Applied Sciences. 10(6).
40 dB correspondingly, whereas classification accuracies
of the existing strategy [28] are 92.3%, 97% and 98.71% [4] Arrillaga J, Bradley DA, Bodge PS. 1985. Power
with SNR 20 dB, 30 dB and 40 dB respectively. These system harmonics. Wiley.
analyses show that the presented technique for feature
extraction and decision making are effective for the [5] Heydt GT, Fjeld PS, Liu CC, Pierce D, Tu L, Hensley
classification. Moreover, the LMS method in the presented G. 1999. Applications of the windowed FFT to
classifier gives more precise outcomes than the existing
electric power quality assessment. IEEE Trans Power
method.
Deliv. 14(4): 1411-6.
CONCLUSIONS
A novel hybrid classification technique using [6] Cheong, L. C., Sudirman, R., & Hussin, S. S. 2015.
DWT, LMS filter and fuzzy expert system is presented in Feature extraction of EEG signal using wavelet
this work for recognizing and classifying the power transform for autism classification. ARPN Journal of
system distortions. The DWT is utilized to separate the Engineering and Applied Sciences. 10(19).
noise of the measured voltage signal. The variance of the
noise is given along with the measured voltage signal to [7] Poisson O, Rioual P, Meunier M. 2000. Detection
the LMS filter to enhance its efficiency and performance. and measurement of power quality disturbances using
LMS filter is then employed to calculate the magnitude wavelet transform. IEEE Trans Power Deliv. 15(3):
and the slope of the voltage signal that turn into the inputs
1039-44.
to the fuzzy logic for categorization of the different
voltage distortions. A few case studies have been carried
out to evaluate the efficiency and performance of the
presented method. The simulation outcomes demonstrate
2015
VOL. 13, NO. 6, MARCH 2018 ISSN 1819-6608
ARPN Journal of Engineering and Applied Sciences
©2006-2018 Asian Research Publishing Network (ARPN). All rights reserved.
www.arpnjournals.com
[8] Gaing ZL. 2004. Wavelet-based neural network for [19] Dash PK, Mishra S, Salama MMA, Liew AC. 2000.
power disturbance recognition and classification. Classification of power system disturbances using a
IEEE Trans Power Deliv. 19(4): 1560-8. fuzzy expert system and a Fourier linear combiner.
IEEE Trans Power Deliv. 15(2): 472-7.
[9] Dwivedi UD, Singh SN. 2010. Enhanced detection of
power-quality events using intra and interscale [20] Reaz M, Choong F, Sulaiman M, Yasin F, Kamada
dependencies of wavelet coefficients. IEEE Trans M. 2007. Expert system for power quality disturbance
Power Deliv. 25(1): 358-66. classifier. IEEE Trans Power Deliv. 22(3): 1979-88.
[10] Lobos T, Rezmer J, Janik P, Amarís H, Alonso M, [21] Styvaktatis E, Bollen MHJ, Gu IYH. 2002. Expert
Álvarez C. 2009. Application of wavelets and Prony system for classification and analysis of power system
method for disturbance detection in fixed speed wind events. IEEE Trans Power Deliv. 17(2): 423-8.
farms. Int. J Electr Power Energy Syst. 31(9): 429-36.
[22] Babatunde S. 2012. Emmanuel, Discrete wavelet
[11] Gencer Ö, Öztürk S, Erfidan T. 2010. A new mathematical transformation method for non-
approach to voltage sag detection based on wavelet stationary heart sounds signal analysis. ARPN Journal
transform. Int. J. Electr. Power Energy Syst. 32(2): of Engineering and Applied Sciences. 7(8).
133-40.
[23] Mallat Stephane. 1999. A wavelet tour of signal
[12] Manoj Arun S. and M. K. Elango. 2015. Effectiveness processing. USA: Academic Press.
of wavelet families for power quality event
quantization, ARPN Journal of Engineering and [24] R. H. Kwong and E.W. Johnston. 1992. A variable
Applied Sciences. 10(8). step size LMS algorithm. IEEE Trans. Signal
Processing. 40(7): 1633-1642.
[13] Xiao X, Xu F, Yang H. 2009. Short duration
disturbance classifying based on S-transform [25] T. Aboulnasr and K. Mayyas. 1997. A robust variable
maximum similarity. Int. J. Electr. Power Energy step-size LMS-type algorithm: analysis and
Syst. 31(7, 8): 374-8. simulations. IEEE Trans. Signal Processing. 45(3):
631-639.
[14] Chilukuri MV, Dash PK. 2004. Multiresolution S-
transform-based fuzzy recognition system for power [26] F. Pasila, R. Alimin and H. Natalius. 2014. Neuro-
quality events. IEEE Trans Power Deliv. 19(1): 323- fuzzy architecture of the 3d model of massive parallel
30. actuators. ARPN Journal of Engineering and Applied
Sciences. 9(12).
[15] Suja S, Suja Jovitha. 2010. Pattern recognition of
power signal disturbances using S Transform and TT [27] T. Devaraju, V. C. Veera Reddy and M. Vijaya
Transform. Int. J Electr Power Energy Syst. 32(1): 37- Kumar. 2010. Performance of DVR under different
53. voltage sag and swell conditions. ARPN Journal of
Engineering and Applied Sciences. 5(10).
[16] A. K. Pradhan, A. Routray and Abir Basak. 2005.
Power System Frequency Estimation Using Least [28] Abdelsalam A. A., Eldesouky A. A. & Sallam, A. A.
Mean Square Technique. IEEE transactions on power 2012. Classification of power system disturbances
delivery. 20(3). using linear Kalman filter and fuzzy-expert system.
International Journal of Electrical Power & Energy
[17] Feuer and E. Weinstein. 1985. Convergence analysis Systems. 43(1): 688-695.
of LMS filters with uncorrelated Gaussian data. IEEE
Trans. Acoust., Speech, Signal Processing. 33(1):
222-229.
2016