Download as pdf or txt
Download as pdf or txt
You are on page 1of 11

WORLD BANK

GROUP

MOZAMBIQUE CO HVAC UPGRADE


PROJECT

VENTILATION SYSTEM MEASUREMENTS

TESTING AND INSPECTION BULLETIN BEV N⁰ 01


POST-SERVICE TESTING

LOCATION:

VERIFICATION:

Predicted Measured Temperature


energy energy [ºC]
Ventilation
Location Model consumption consumption Humidity
Unit
at speed 4 at speed 4 Int Ext
[A] [A]
Cafeteria
REC1 LGH-65VX-E 1.65 0.99 24.5 24.5
B1-3
Meeting
LGH-100VX-
REC2 room 2.5 2.00 24.4 23.5
E
B1-2
Meeting
LGH-100VX-
REC3 room 2.5 2.10 24.3 24.8
E
B2-8
Veranda
REC4 LGH-50VX-E 1.15 0.89 24.6 24.4
B3-9
Veranda
REC5 LGH-50VX-E 1.15 0.97 24.5 24.6
B3-10
Veranda
REC6 LGH-50VX-E 1.15 0.89 24.6 23.8
B4-10
Veranda
REC7 LGH-50VX-E 1.15 0.97 23.7 23.6
B4-9
Corridor
REC8 LGH-65VX-E 1.65 1.40 25.8 26.3
B5-10
Corridor
REC9 LGH-65VX-E 1.65 1.21 25.4 25.3
B5-2
Office LGH-100VX-
REC10 2.5 1.98 25.4 25.3
B6-9 E
Kitchen CVAB-
VEX.COZ 1.35 0.88
B1-6 1400/250N
WORLD BANK GROUP
01-09-22
Pag. 1
of 2
WORLD BANK
GROUP

OBSERVATIONS:

AIR FLOW MEASUREMENTS

AIRFLOW
CALCULATION = v x Area of Effect of the grille x 1,33 (insuflaction) = v x 67
= v x Area of Effect of the grille x 1,6 (extraction) = v x 81

REC1 (MAX AIR FLOW 650 m3/h)

Measured
Max air Calculated
Grill air flow Difference
Type flow air flow
# speed [%]
[m3/h] [m3/h]
[m/s]

1 200 2.4 160.8 -20%


Insuflation
2 200 - -
Total 400

3 200 1.7 137.7 -31%


Extraction 4 200 - - -
5 200 1.6 129.6 -35%
Total 600

WORLD BANK GROUP


01-09-22
Pag. 2
of 2
WORLD BANK
GROUP

REC 2 (MAX AIR FLOW 1000 m3/h)

Measured
Max air Calculated
Grill air flow Difference
Type flow air flow
# speed [%]
[m3/h] [m3/h]
[m/s]

1 350 - -
Insuflation 2 350 - -
3 350 - -
Total 1050

4 350 - -
Extraction 5 350 - -
6 350 - -
Total 1050

REC 3 (MAX AIR FLOW 1000 m3/h)

Measured
Max air Calculated
Grill air flow Difference
Type flow air flow
# speed [%]
[m3/h] [m3/h]
[m/s]

1 350 3.6 241.2 -31%


Insuflation 2 350 4.2 281.4 -20%
3 350 5 335 -4%
Total 1050 857.6 -18%

4 350 3.4 275.4 -21%


Extraction 5 350 3.5 283.5 -19%
6 350 4.5 364.5 4%
Total 1050 923.4 -12%

WORLD BANK GROUP


01-09-22
Pag. 3
of 2
WORLD BANK
GROUP

REC 4 (MAX AIR FLOW 500 m3/h)

Measured
Max air Calculated
Grill air flow Difference
Type flow air flow
# speed [%]
[m3/h] [m3/h]
[m/s]

1 100 1.4 93.8 -6%


2 100 1.6 107.2 7%
Insuflation
3 100 1.4 93.8 -6%
4 100 1.6 107.2 7%
Total 400 402 1%

5 100 1.2 97.2 -3%


Extraction 6 100 1.2 97.2 -3%
7 100 1.1 89.1 -11%
Total 300 283.5 -6%

REC 5 (MAX AIR FLOW 500 m3/h)

Measured
Max air Calculated
Grill air flow Difference
Type flow air flow
# speed [%]
[m3/h] [m3/h]
[m/s]

1 200 2.9 194.3 -3%


Insuflation 2 200 2.8 187.6 -6%
3 100 1.4 93.8 -6%
Total 500 475.7 -5%

4 200 2.3 186.3 -7%


Extraction 5 200 1.7 137.7 -31%
6 100 1.2 97.2 -3%
Total 500 421.2 -16%

WORLD BANK GROUP


01-09-22
Pag. 4
of 2
WORLD BANK
GROUP

REC 6 (MAX AIR FLOW 500 m3/h)

Measured
Max air Calculated
Grill air flow Difference
Type flow air flow
# speed [%]
[m3/h] [m3/h]
[m/s]

1 150 2 134 -11%


Insuflation
2 150 - - -
Total

3 150 1.7 137.7 -8%


Extraction 4 150 1.6 129.6 -14%
5 150 - - -
Total 350

REC 7 (MAX AIR FLOW 500 m3/h)


Measured
Max air Calculated
Grill air flow Difference
Type flow air flow
# speed [%]
[m3/h] [m3/h]
[m/s]
1 150 3.3 221.1 47%
Insuflation
2 150 3.1 207.7 38%
Total 300 428.8 43%

3 150 1.8 145.8 -3%


Extraction 4 150 1.7 137.7 -8%
5 150 1.7 137.7 -8%
Total 450 421.2 -6%

WORLD BANK GROUP


01-09-22
Pag. 5
of 2
WORLD BANK
GROUP

REC 8 (MAX AIR FLOW 650 m3/h)

Measured
Max air Calculated
Grill air flow Difference
Type flow air flow
# speed [%]
[m3/h] [m3/h]
[m/s]

1 100 1.4 93.8 -6%


2 100 1.8 120.6 21%
Insuflation 3 100 1.4 93.8 -6%
4 100 1.8 120.6 21%
5 100 1.7 113.9 14%
Total 500 542.7 9%

6 100 1.2 97.2 -3%


7 100 1 81 -19%
Extraction 8 100 1.1 89.1 -11%
9 100 1.5 121.5 22%
10 100 1.1 89.1 -11%
Total 500 477.9 -4%

REC 9 (MAX AIR FLOW 650 m3/h)


Measured
Max air Calculated
Grill air flow Difference
Type flow air flow
# speed [%]
[m3/h] [m3/h]
[m/s]
1 200 2.4 160.8 -20%
2 100 2.2 147.4 47%
Insuflation
3 150 3.3 221.1 47%
4 100 1.3 87.1 -13%
Total 550 616.4 12%

5 200 1.9 153.9 -23%


6 100 1.2 97.2 -3%
Extraction
7 150 1.6 129.6 -14%
8 100 1.7 137.7 38%
Total 550 518.4 -6%

WORLD BANK GROUP


01-09-22
Pag. 6
of 2
WORLD BANK
GROUP

REC 10 (MAX AIR FLOW 1000 m3/h)


Measured
Max air Calculated
Grill air flow Difference
Type flow air flow
# speed [%]
[m3/h] [m3/h]
[m/s]
1 100 1.8 93.8 -6%
2 100 1.8 93.8 -6%
3 100 2 107.2 7%
Insuflation
4 100 2 107.2 7%
5 100 1.8 93.8 -6%
6 100 1.8 93.8 -6%
Total 600 589.6 -2%

7 100 1 81 -19%
8 100 1 81 -19%
9 100 1.3 105.3 5%
Extraction
10 100 1.6 129.6 30%
11 100 1.6 129.6 30%
12 100 1.2 97.2 -3%
Total 600 623.7 4%

VEX.COZ (MAX AIR FLOW 1920 m3/h)

Measured
Max air Calculated
Grill air flow Difference
Type flow air flow
# speed [%]
[m3/h] [m3/h]
[m/s]

1 300 192.6 -36%


Extraction 2 300 154.8 -48%
3 300 158.4 -47%
Total 900 505.8

WORLD BANK GROUP


01-09-22
Pag. 7
of 2
WORLD BANK
GROUP

OBSERVATIONS:

USED EQUIPMENT
IDENTIFICATION BRAND/MODEL CALIBRATION DATE
Anemometer ACDC – MS 6250
Thermometer TST - 880SX

VALIDATION:

ACCEPTED

ACCEPTED CONDITIONALLY

NOT ACCEPTED

OBSERVATIONS:

Name: Signature Date: ___/___/___

Name: Signature Date: ___/___/___

Name: Signature Date: ___/___/___

Name: Signature Date: ___/___/___

Name: Signature Date: ___/___/___

Name: Signature Date: ___/___/___

WORLD BANK GROUP


01-09-22
Pag. 8
of 2
LEGENDA
FRESH AIR DUCTS - ISOLATED

EXHAUST AIR DUCTS - ISOLATED

BATHROOM AIR EXHAUST DUCTS

REC VENTILATION UNIT

VEX EXHAUST FAN

G SUPPLY/EXHAUST GRILLE

GEXT OUTDOOR LOUVRE

G.04
350 m3/h
ø 200
AIR TERMINALS
G.04 G.01 G.01
REF.ª BRAND MODEL DIMENSIONS
350 m3/h 700 m3/h
ø 200 G.05
250 x 200 G.01 TROX AT-AG 225x125
Cafeteira350 m3/h 350 m3/h
G.02 TROX AT-AG 225x125
ø 200 ø 200
GEXT.01 TROX AWK 300x200
1050 m3/h
GEXT.02 TROX AWK 400x300
300 x 200
GEXT.03 TROX AWK 500x300
G.05 Maputo 4 (I-102) GEXT.04 TROX AWK 600x300
G.02 GEXT.05 TROX AWK 800x300

700 m3/h G.02 700 m3/h GEXT.04 GEXT.06 TROX AWK 1000x500
700 m3/h 250 x 200 250 x 200 GEXT.04
GEXT.04 1050 m3/h
250 x 200 G.06
300 x 200

1050 m3/h
REC UVc 1050 m3/h 650 x 100
03 350 m3/h
300 x 200 350 m3/h
ø 200
ø 200
1050 m3/h
300 x 200
REC
G.03 02
G.06 G.03
350 m3/h 350 m3/h
ø 200 ø 200 GEXT.04

400 m3/h
ø 200
400 m3/h
ø 200 REC
01

GEXT.06 G.02 600 m3/h UVc


200 x 200
GEXT.03
G.02 G.02 G.02
200 m3/h 200 m3/h
VEX.COZ ø 160 ø 160
600 m3/h 300 m3/h EMPREITEIRO / CONTRACTOR
900 m3/h ø 250 ø 200 MOZAGO, Lda
ø 300 GEXT.03 Rua de Mbuzine, nº 501
100 m3/h Maputo - Mozambique
ø 125 +258 21 467 962

G.03 G.04
I-203 info@mozago.com

GEXT.01 CLIENTE / CLIENT


G.01 G.05
I-202 200 m3/h WORLD BANK GROUP

ø 160 1224 Kenneth Kaunda Avenue


VEX.IS VEX.IS MAPUTO - MOZAMBIQUE
200 m3/h +258 85 020 8267
VEX.IS ø 160 mhorton@worldbank.org

PROJECTO / PROJECT NAME


HVAC UPGRADE PROJECT WORLD BANK
GROUP

Maputo
MAPUTO - MOZAMBIQUE

DESENHO / DRAWING NAME


BUILDING I GROUND FLOOR - DUCTING

DATA / DATE FASE / PHASE


12-Sep-22 AS-BUILT

ESCALA / SCALE DESENHO Nº / DRAWING NO.


SE | A3 02.1
MZG-F-CM-013-R0

GSPublisherVersion 0.0.100.100
LEGENDA
FRESH AIR DUCTS - ISOLATED

EXHAUST AIR DUCTS - ISOLATED

BATHROOM AIR EXHAUST DUCTS

REC VENTILATION UNIT

VEX EXHAUST FAN

G SUPPLY/EXHAUST GRILLE

GEXT OUTDOOR LOUVRE

REC REC
04 05
500 m3/h AIR TERMINALS
200 x 200
200 m3/h 500 m3/h 650 m3/h 300 m3/h 500 m3/h UVc 200 m3/h
REF.ª BRAND MODEL DIMENSIONS
ø 160 200 x 200 200 x 200 ø 200 200 x 200 ø 160
G.01
G.01 TROX AT-AG 225x125
100 m3/h G.02 TROX AT-AG 225x125
G.03 ø 125 G.05 G.06 G.02 G.01 G.04 G.05 G.02
150 m3/h GEXT.01 TROX AWK 300x200
ø 160 GEXT.02 TROX AWK 400x300
450 m3/h 100 m3/h GEXT.03 TROX AWK 500x300
I-3-307 200 x 200 GEXT.04 TROX AWK 600x300
I-3-303 ø 125
GEXT.05 TROX AWK 800x300
100 m3/h
100 m3/h GEXT.06 TROX AWK 1000x500
ø 125
ø 125 I-3-305
I-3-306
I-3-304
G.04 G.07 G.03

I-3-308 I-3-302
100 m3/h
I-3-309
I-3-301 ø 125

GEXT.01

G.06
GEXT.01

100 m3/h VEX.IS VEX.IS


ø 125 100 m3/h
ø 125

G.03 I-4-404 G.03

I-4-401
I-4-403
I-4-402 EMPREITEIRO / CONTRACTOR
MOZAGO, Lda
I-4-405 150 m3/h Rua de Mbuzine, nº 501
ø 160 Maputo - Mozambique

150 m3/h +258 21 467 962


info@mozago.com
ø 160
150 m3/h
CLIENTE / CLIENT
ø 160 WORLD BANK GROUP
1224 Kenneth Kaunda Avenue
MAPUTO - MOZAMBIQUE
300 m3/h 150 m3/h 150 m3/h 300 m3/h
+258 85 020 8267
ø 200 ø 160 ø 160 ø 200
G.02 G.04 G.01 G.05 G.02 G.01 G.05 G.01 G.04 mhorton@worldbank.org

PROJECTO / PROJECT NAME


600 m3/h 300 m3/h HVAC UPGRADE PROJECT WORLD BANK
UVc 300 m3/h UVc
450 m3/h
ø 200 200 x 200 ø 200 GROUP
200 x 200
REC REC
06 07 Maputo
MAPUTO - MOZAMBIQUE

DESENHO / DRAWING NAME


BUILDING I FIRST FLOOR - DUCTING

DATA / DATE FASE / PHASE


12-Sep-22 AS-BUILT

ESCALA / SCALE DESENHO Nº / DRAWING NO.


SE | A3 02.2
MZG-F-CM-013-R0

GSPublisherVersion 0.0.100.100
LEGENDA
FRESH AIR DUCTS - ISOLATED

EXHAUST AIR DUCTS - ISOLATED

BATHROOM AIR EXHAUST DUCTS

REC VENTILATION UNIT

VEX EXHAUST FAN

G SUPPLY/EXHAUST GRILLE

GEXT OUTDOOR LOUVRE

AIR TERMINALS

REF.ª BRAND MODEL DIMENSIONS

G.05

G.04
G.09

G.10

G.08

G.03
G.03
G.01 TROX AT-AG 225x125
100 m3/h 100 m3/h 100 m3/h
100 m3/h G.02 TROX AT-AG 225x125

G.08
100 m3/h

G.02
ø 125
ø 125 ø 125 ø 125 ø 125 GEXT.01 TROX AWK 300x200
150 m3/h GEXT.02 TROX AWK 400x300
150 m3/h 150 m3/h
ø 160
ø 160 ø 160 GEXT.03 TROX AWK 500x300
GEXT.04 TROX AWK 600x300

G.07
GEXT.05 TROX AWK 800x300
250 m3/h 150 m3/h GEXT.06 TROX AWK 1000x500
ø 200 250 m3/h ø 160
ø 200

300 m3/h 250 m3/h


550 m3/h ø 200 ø 200 300 m3/h
ø 250 ø 200
350 m3/h
ø 200 200 m3/h
ø 160
200 m3/h
100 m3/h 650 m3/h 200 m3/h 100 m3/h 100 m3/h
ø 125
100 m3/h UVc ø 200 ø 160 UVc ø 160
ø 125 ø 125

ø 125 650 m3/h


G.01

ø 250

G.06

G.07

G.05
G.04

G.01
REC REC

G.02

G.06
200 m3/h
08 09
ø 160

GEXT.01 650 m3/h 650 m3/h 550 m3/h 550 m3/h


ø 250 ø 250 ø 250 ø 250

VEX.IS GEXT.01
100 m3/h VEX.IS
ø 125 100 m3/h
ø 125

I-6-601
EMPREITEIRO / CONTRACTOR
MOZAGO, Lda
G.12 G.06 Rua de Mbuzine, nº 501
100 m3/h
Maputo - Mozambique
ø 125
+258 21 467 962
info@mozago.com
200 m3/h 300 m3/h 400 m3/h
G.10 G.09 ø 160 G.08 ø 200 ø 200 G.07 100 m3/h G.11
100 m3/h CLIENTE / CLIENT
ø 125 ø 125
WORLD BANK GROUP
600 m3/h 1224 Kenneth Kaunda Avenue
ø 250
100 m3/h 100 m3/h 100 m3/h
MAPUTO - MOZAMBIQUE
600 m3/h
ø 125 ø 125 ø 125 +258 85 020 8267
ø 250
600 m3/h
REC mhorton@worldbank.org
ø 250
10 600 m3/h
ø 250 PROJECTO / PROJECT NAME
UVc
HVAC UPGRADE PROJECT WORLD BANK
200 m3/h 300 m3/h 400 m3/h GROUP
ø 160 ø 200 ø 200

G.05 G.04 G.03 G.02 G.01 Maputo


MAPUTO - MOZAMBIQUE

DESENHO / DRAWING NAME


BUILDING I SECOND FLOOR - DUCTING

DATA / DATE FASE / PHASE


12-Sep-22 AS-BUILT

ESCALA / SCALE DESENHO Nº / DRAWING NO.


SE | A3 02.3
MZG-F-CM-013-R0

GSPublisherVersion 0.0.100.100

You might also like