Professional Documents
Culture Documents
AGASTAT CB-1029D-30-Tyco-Electronics
AGASTAT CB-1029D-30-Tyco-Electronics
Alphanumeric Index
Series Type Page
R0 = R1
( T0 – TS
T1 – TS ) Factory-set
Time Delay.
Approximate
Resistance* Short Circuit
T0 = Desired Time No Resistor to Reduce Time Delay
TS = Short Time (see relay type) (seconds) Delay by 1/2 (seconds)
T1 = Long Time (see relay type) 1.0 33K ohms 0.1
R1 = Extrernal Resistor Value required to obtain T1
R0 = External Resistor Value required to obtain T0 5.0 200K ohms 0.1
10.0 400K ohms 0.1
Example: Given a CUH-41-30060, find an external resistor value that will
give a 30 second delay. * Resistor values shown correspond to a 1.0 multiplying factor. Use the graph below to
determine other resistor values required to obtain time periods between the limits stated in
the chart.
Known: T1 = 60 seconds
TS = 1 second
R1 = 1 meg
R0 = 1 x 106 (29)
59
Dimensions are shown for Dimensions are in inches over Specifications and availability www.tycoelectronics.com
reference purposes only. (millimeters) unless otherwise subject to change. Technical support: 1203
specified. Refer to inside back cover.
Catalog 1308242
Issued 3-03 AGASTAT
Dimensions are shown for Dimensions are in inches over Specifications and availability www.tycoelectronics.com
1204 reference purposes only. (millimeters) unless otherwise subject to change. Technical support:
specified. Refer to inside back cover.
Catalog 1308242
Issued 3-03 AGASTAT
ON Repeat Cycle: Application of the operating voltage starts time delay 1. Upon
OPERATING expiration of this delay, the output contacts energize. Time delay 2 begins
VOLTAGE
OFF simultaneously. At the end of time delay 2, the output contacts de-energize,
and a new cycle begins. The cycles continue until power is removed. To reset
CLOSED the timer, input voltage must be removed. The state of the output contacts
CONTROL
SWITCH may be reversed on the 11-pin 48K by closing the control switch. Note: For the
OPEN 48K series, the time delays are identical.
ENERGIZED
OUTPUT ON
CONTACTS DELAY
OPERATING
DE-ENER. VOLTAGE
OFF
CLOSED
On / Interval : Time delay 1 is initiated upon application of a control signal (i.e., CONTROL
SWITCH
operating voltage or closure of the control switch on 11-pin models). The OPEN
output contacts energize at the end of time delay 1 and de-energize at the end
of time delay 2. Output contacts and the time delay circuit reset upon removal ENERGIZED
OUTPUT
of the control signal regardless of state. Note: For the 48K series, delay 2 is CONTACTS
fixed at 0.5 seconds. DE-ENER.
DELAY ACCUMULATION
ON / CLOSED
OPERATING VOLTAGE/ One Shot (Latching Interval): Operating voltage must be applied continu-
CONTROL SWITCH
OFF / OPEN ously. Output contacts energize and time delay is initiated upon closure of the
control switch. Once closed, state of control switch has no further influence
ENERGIZED until time delay has expired. Upon expiration of time delay, output contacts de-
OUTPUT
CONTACTS DELAY 1
energize and timer is reset by opening the control switch.
DELAY 2
DE-ENER.
ON
OPERATING
VOLTAGE
OFF
CLOSED
CONTROL OFF AT
SWITCH ANY TIME
Dimensions are shown for Dimensions are in inches over Specifications and availability www.tycoelectronics.com
reference purposes only. (millimeters) unless otherwise subject to change. Technical support: 1205
specified. Refer to inside back cover.
Catalog 1308242
Issued 3-03 AGASTAT
BDS08SS Socket
• 8-pin octal socket
• DIN rail or panel mount
• Rated 10A @ 300VAC
• #6-32 screws w/captive clamp plates
• File E140494
• File LR29523M37
BDS11SS Socket
• 11-pin octal-type socket
• DIN rail or panel mount
• Rated 10A @ 300VAC
• #6-32 screws w/captive clamp plates
• File E140494
• File LR29523M37
BCSF11SC Socket
• Use with SCF series timer
• 11-pin octal-type socket
• DIN rail or panel mount
• Rated 10A @ 380VAC
• M3 screws w/captive clamp plates
• File E140494
• File LR29523M37
BDT11SS Socket
• 11-pin tab socket
• DIN rail or panel mount
• Rated 10A @ 300VAC
• #6-32 screws w/captive clamp plates
• File E140494
• File LR29523M37
3RP1 series
Multifunction Solid State DIN Mount
Time Delay Relay
• Available as SPDT or DPDT
• 15 time setting ranges
• .05s - 100hr programmable timing range
• Universal 24-240 VAC/VDC or fixed input types.
• 3A switching current rating
• Fits 35mm DIN track
• Single function, Delay-On available
VDE
Users should thoroughly review the technical data before selecting a product part
number. It is recommended that user also seek out the pertinent approvals files of
the agencies/laboratories and review them to ensure the product meets the
requirements for a given application.
Configuring
• Changing the timer range and their functions will only be effective when L1 L1
they are carried out in a voltage-free state.
• Trigger input B1 or B3 must only be started when the supply voltage is S1 S1 S1
applied.
• The same potential must be applied to A1 and B1, or A3 and B3. With the A1 B1 A1 B1
two-voltage design, only one voltage range must be connected. K2 K1 K2 K1
A2
• The triggering of the load paralleled to the start input is not permissible N N
when using AC (see adjacent diagrams).
Ordering Information – Authorized distributors are more likely to stock boldface items listed below.
Input Voltage Input Contact Wiring Functions Part
DC AC Type Arrang. Diagram Number
3RP1505 Multifunction
24 24, 100-127 Fixed SPDT 1 to 8 1 to 8 3RP15 05-1AQ30
24 24, 200-240 Fixed SPDT 1 to 8 1 to 8 3RP15 05-1AP30
24 24, 100-127 Fixed DPDT 9 to 24 9 to 24 3RP15 05-1BQ30
24-240 24-240 Universal DPDT 9 to 24 9 to 24 3RP15 05-1BW30
3RP1525 Delay On
24 24, 100-127 Fixed SPDT 1 1 3RP15 25-1AQ30
24 24, 200-240 Fixed SPDT 1 1 3RP15 25-1AP30
24 24, 100-127 Fixed DPDT 9 9 3RP15 25-1BQ30
24 24, 200-240 Fixed DPDT 9 9 3RP15 25-1BP30
Dimensions are shown for Dimensions are in inches over Specifications and availability www.tycoelectronics.com
reference purposes only. (millimeters) unless otherwise subject to change. Technical support: 1207
specified. Refer to inside back cover.
Catalog 1308242
Issued 3-03 P&B
Outline Dimensions
3.39
3RP1505-1A, 3RP1525-1A 3RP1505-1B, 3RP1525-1B (86.0)
3.39 .19
(86.0) .31
.19 (5.0) 2.36 (8.0)
(5.0) .31
(8.0) (60.0)
2.36 1.18
(60.0) (30.0)
4.33
(110.0)
3.54
(90.0) 3.23
3.23
(82.0) (82.0)
2.99
(76.0) 4.33 2.44 4.72
(110.0) 4.02 (62.0) (120.0)
(102.0)
2.44
(62.0)
4.72
(120.0)
.59 .59
(15.0) .23 (15.0) .23
.886 (6.0) .886
(22.5) (6.0)
(22.5)
Wiring Diagram
1. On-Delay 2. Off-Delay 3. On and Off Delay 4. Flashing
With Auxiliary Voltage With Auxiliary Voltage
3RP1505-1A 3RP1505-1A 3RP1505-1A 3RP1505-1A
3RP1525-1A
AC/DC 24V AC/DC 24V AC/DC 24V AC/DC 24V
AC100/127V AC100/127V AC100/127V AC100/127V
AC200/240V AC200/240V AC200/240V AC200/240V
A1 A3 15 A1 B1 A3 B3 15 A1 B1 A3 B3 15 A1 A3 15
A2 16 18 A2 16 18 A2 16 18 A2 16 18
5. Making-Pulse Contact 6. Breaking-Pulse Contact 7. Pulse Forming 8. Additive On-Delay With Auxiliary
With Auxiliary Voltage With Auxiliary Voltage Voltage and Instantaneous Contact
3RP1505-1A 3RP1505-1A 3RP1505-1A 3RP1505-1A
3RP1525-1A
AC/DC 24V AC/DC 24V AC/DC 24V AC/DC 24V
A1 A3 15 A1 B1A3 B3 15 A1 B1A3 B3 15 A1 B1 A3 B3 15
Σ
➝ ➝ ➝
A2 16 18 A2 16 18 A2 16 18 A2 16 18
A1 A3 15 25 A1 B1 A3 B3 15 25 A1 B1 A3 B3 15 25 A1 B1 A3 B3 15 25
A2 16 18 26 28 A2 16 18 26 28 A2 16 18 26 28 A2 16 18 26 28
13. Making-Pulse Contact 14. Breaking-Pulse Contact 15. Pulse Forming 16. Additive On-Delay With Auxiliary
With Auxiliary Voltage With Auxiliary Voltage Voltage and Instantaneous Contact
3RP1505-1B 3RP1505-1B 3RP1505-1B 3RP1505-1B
A1 A3 15 25 A1 B1 A3 B3 15 25 A1 B1 A3 B3 15 25 A1 B1 A3 B3 15 21
Σ
➝
➝ ➝
➝ ➝ ➝
A2 16 18 26 28 A2 16 18 26 28 A2 16 18 26 28 A2 16 18 22 24
Dimensions are shown for Dimensions are in inches over Specifications and availability www.tycoelectronics.com
1208 reference purposes only. (millimeters) unless otherwise subject to change. Technical support:
specified. Refer to inside back cover.
Catalog 1308242
Issued 3-03 P&B
Wiring Diagrams (continued)
17. On-Delay and 18. Off-Delay 19. On and Off Delay 20. Flashing and
Instantaneous Contact With Auxiliary Voltage and With Auxiliary Voltage and Instantaneous Contact
Instantaneous Contact Instantaneous Contact
3RP1505-1B 3RP1505-1B 3RP1505-1B 3RP1505-1B
A1 A3 15 21 A1 B1 A3 B3 15 21 A1 B1 A3 B3 15 21 A1 A3 15 21
A2 16 18 22 24 A2 16 18 22 24 A2 16 18 22 24 A2 16 18 22 24
21. Making-Pulse Contact and 22. Breaking-Pulse Contact 23. Pulse Forming With 24. Star-Delta Function
Instantaneous Contact With Auxiliary Voltage and Auxiliary Voltage and
Instantaneous Contact Instantaneous Contact
3RP1505-1B 3RP1505-1B 3RP1505-1B 3RP1505-1B
A1 A3 15 21 A1 B1 A3 B3 15 21 A1 B1 A3 B3 15 21 A1 A3 17 27
➝ ➝
➝
∇
A2 16 18 22 24 A2 16 18 22 24 A2 16 18 22 24 A2 Y18 28
2. Off Delay 6. Impulse Off 10. Off Delay 14. Impulse Off 18. Off Delay 22. Impulse Off
A./A2 A./A2 A./A2 A./A2 A./A2 A./A2
>
_ 35ms >
_ 35ms >
_ 35ms >
_ 35ms >
_ 35ms >
_ 35ms
B./A2 B./A2 B./A2 B./A2 B./A2 B./A2
15/18 15/18 15/18 15/18 15/18 15/18
15/16 15/16 15/16 15/16 15/16 15/16
t t t t t t
25/28 25/28 21/24 21/24
25/26 25/26 21/22 21/22
3. On/Off Delay 7. Pulse Shaping 11. On/Off Delay 15. Pulse Shaping 19. On/Off Delay 23. Pulse Shaping
A./A2 A./A2 A./A2 A./A2 A./A2 A./A2
>
_ 35ms >
_ 35ms >
_ 35ms
B./A2 B./A2 B./A2 B./A2 B./A2 B./A2
15/18 15/18 15/18 15/18 15/18 15/18
15/16 15/16 15/16 15/16 15/16 15/16
t t t t t t t t t
25/28 25/28 21/24 21/24
25/26 25/26 21/22 21/22
4. Flasher 8. Cumulative On Delay 12. Flasher 16. Cumulative On Delay 20. Flasher 24. Star/Delta
A./A2 A./A2 A./A2 A./A2 A./A2 A./A2
t1 t3 t2 t1 t2
15/18 15/18 t3 15/18 17/18
15/16 B./A2 15/16 B./A2 15/16 27/28
t t 15/18 t t 15/18 t t t
15/16 25/28 15/16 21/24 50ms
Σt 25/26 Σt 21/22
22/24
21/22
Dimensions are shown for Dimensions are in inches over Specifications and availability www.tycoelectronics.com
reference purposes only. (millimeters) unless otherwise subject to change. Technical support: 1209
specified. Refer to inside back cover.
Catalog 1308242
Issued 3-03 (PDF Rev. 4-04) AGASTAT
Ordering Information – Authorized distributors are likely to stock boldface part numbers listed below.
Part Number Timing Modes Operating Voltage Termination Pins
48K01AS One - On-Delay 120VAC 50/60 Hz. 8
48K90US Four - On-Delay, Interval, On/Interval, Repeat Cycle Universal (24-240VAC, 50/60 Hz. or 24-125VDC) 8
48K91US Eight - On-Delay, Off-Delay, Interval, On/Interval, One Shot, Universal (24-240VAC, 50/60 Hz. or 24-125VDC) 11
Repeat Cycle, On-Delay/Off-Delay, Accumulating On
Ordering Note: The part numbers listed above are standard products with knobs for adjustment of mode, range and timing. On a special order basis other models are
available with recessed dials requiring a screwdriver for adjustment. On the special order versions, the "S" part number suffix is replaced by an "R" suffix. Consult factory
for availability of special order models.
1.89
(48.0) Max.
Dimensions are shown for Dimensions are in inches over Specifications and availability www.tycoelectronics.com
1210 reference purposes only. (millimeters) unless otherwise subject to change. Technical support:
specified. Refer to inside back cover.
Catalog 1308242
Issued 3-03 P&B
CNT series
Multifunction, Digital
Time Delay Relay/Counter
• 10 programmable timing modes + 2 counting modes
• 0.1 sec. to 9,990 hr. programmable timing range
• 1 to 99,900 counting range
• LCD digital display
• Universal (24-240VAC/VDC) and fixed input types
• 10A output relay with DPDT contacts
• Thumbwheel switches for programming
File E22575
File LR15734
Users should thoroughly review the technical data before selecting a product part
number. It is recommended that user also seek out the pertinent approvals files of
the agencies/laboratories and review them to ensure the product meets the
requirements for a given application.
.591
(15.0)
1.654
Section "A-A" (42.0)
“A
1.890
”
(48.0)
With this setting, the relay would operate after a delay period of 214 seconds. A 2 1 4 S
Function Select:
Timer Mode: A = Delay On Operate E = Recycle I = Pulse
B = Delay On Release F = Single Cycle J = Cumulative Delay On Operate
C = Interval On G = Control On-Off Interval On
D = Control-Off Interval On H = Control On-Off Delay
Counter Mode: B = Divide by 10 C = Divide by 100 A & D-J = Normal Count
Time/Counter Setting: 001 to 999
Time Base/Counter Mode Select:
Time Base: .1S = 0.1 to 99.9 Sec. .1M = 0.1 to 99.9 Min. .1H = 0.1 to 99.9 Hrs. 10H =10 to 9990 Hrs.
S = 1 to 999 Sec. M = 1 to 999 Min. H = 1 to 999 Hrs.
Counter Mode: CO = Operate at Preset Count CR = Release at Preset Count
CO or CR – Divide-by-100 Mode
Operation is as described previously, except count is incremented for every
100 on/off input signals for a maximum presettable count of 99,900.
Dimensions are shown for Dimensions are in inches over Specifications and availability www.tycoelectronics.com
1212 reference purposes only. (millimeters) unless otherwise subject to change. Technical support:
specified. Refer to inside back cover.
Catalog 1308242
Issued 3-03 P&B
CNS series
Multifunction Time Delay Relay
• 8 programmable timing modes (4 on 8-pin models)
• 0.1 sec. to 100 min. programmable timing range
• Universal (24-240VAC/VDC) and fixed input types
• 10A output relay with DPDT contacts
• DIP switch selection of timing mode and range
• Knob and dial scale for setting actual delay time
File E22575
File LR15734
Users should thoroughly review the technical data before selecting a product part
number. It is recommended that user also seek out the pertinent approvals files of
the agencies/laboratories and review them to ensure the product meets the
requirements for a given application.
1 8 1 11
Dimensions are shown for Dimensions are in inches over Specifications and availability www.tycoelectronics.com
reference purposes only. (millimeters) unless otherwise subject to change. Technical support: 1213
specified. Refer to inside back cover.
Catalog 1308242
Issued 3-03 P&B
Mounting Clip Dimensions
SSA-24C667
Mouting Clip
2.283 1.970
(58.0) (50.0)
2.047
(52.0)
.591
(15.0)
1.654
(42.0)
1.890
(48.0)
1 2 3 4 1 2 3 4
72 & 92 - Output relay is energized at the completion of the time interval which is initiated 76 & 96 - Output relay is energized by the closing of the control switch with the input applied
by the application of input voltage. or the application of input voltage with the control switch already closed. The time interval will
76 & 96 - Same as the above except, closing the control switch after time out will de- be initiated by the opening of the control switch with the relay de-energizing at the completion
energize the relay and reset the timer. Opening the switch will initiate another time interval. of the time interval. Closing the control switch after time out will energize the relay in
Closing the control switch during timing will reset the time to zero and inhibit timing until preparation for another time interval. Closing the control switch during timing will reset the
opened again. time to zero and inhibit timing until opened again.
Interval Off
Recycler (Initially On)
1 2 3 4
76 & 96 - Output relay will initially be energized with the application of the input voltage when
1 2 3 4
the control switch is open. Control switch closing will de-energize the relay and start a time
72 & 92 - Output relay will begin cycling at a 50% duty cycle with the application of input interval. At the completion of the time interval, the relay will energize. With the control switch
power. The initial state of the relay will be energized. closed upon application of input voltage, a time interval will be initiated after which the relay will
76 & 96 - Same as the above except, closing the control switch will energize the relay and energize. Closing of the control switch during timing will have no effect on timing or the state
inhibit timing until it is once again opened, at which time it will start from zero time. of the relay.
Dimensions are shown for Dimensions are in inches over Specifications and availability www.tycoelectronics.com
1214 reference purposes only. (millimeters) unless otherwise subject to change. Technical support:
specified. Refer to inside back cover.
Catalog 1308242
Issued 3-03 P&B
CNM5 series
Multifunction Time Delay Relay For
Plug-In or Panel Mounting
• Five timing functions selectable via rotary switch
• 0.1 sec. to 9,990 hr. timing range
• Fixed input type (120VAC ± 15%)
• 10A output relay with DPDT contacts
• 1/16 DIN style enclosure with 11-pin plug-in base
• Thumbwheel switches for programming delay time
File E22575
File LR15734
Users should thoroughly review the technical data before selecting a product part
number. It is recommended that user also seek out the pertinent approvals files of
the agencies/laboratories and review them to ensure the product meets the
requirements for a given application.
Ordering Information – Authorized distributors are more likely to stock boldface items listed below.
Time Delay Relay Accessory
Input Voltage Part Number Part Number Name Description
120VAC CNM5 SSA-24C667 Mounting Clip Ratchet-fit clip slides onto CNM5 from behind
to secure CNM5 in panel mount applications.
.64 .591
(16.3) (15.0)
.560 3.15
(14.2) (80.0) 1.654
Fits 1.77 x 1.77 (45 x 45) panel cutout. (42.0)
1.890
Wiring Diagrams (Bottom Views) (48.0)
1 11 1 11
INPUT INPUT
**Important: A dry circuit switch is recommended. A "dry circuit" switch is one rated to
reliably switch currents of less than 50mA. Use of a switch rated for other than dry circuit
may result in failure of the time delay relay to function properly.
Dimensions are shown for Dimensions are in inches over Specifications and availability www.tycoelectronics.com
reference purposes only. (millimeters) unless otherwise subject to change. Technical support: 1215
specified. Refer to inside back cover.
Catalog 1308242
Issued 3-03 P&B
Timer Function Descriptions
Off Delay: Output relay is turned on by applying CONTROL input with input
voltage present or application of input voltage with the CONTROL input on. The
time interval will be started by removing the CONTROL input with the output relay
3 1 2 S turning off at completion of the time interval. Reapplying the CONTROL during
timing will reset the time to zero and inhibit timing until removed. LED is off when
CONTROL input is on, flashing during timing and on continuously when the output
TIME SET TIME relay is off.
000 TO 999 BASE
Interval: Output relay is turned on for a programmed time interval by applying
input voltage. LED flashes when output relay is on and is on continuously when
the output relay is off. Applying CONTROL input will have no effect on timing or
Time Base: the state of the relay.
.1 S = 1/10 Seconds Timing Range 0.1 to 99.9 Seconds
S = Seconds Timing Range 1 to 999 Seconds On Delay: Output relay is off for a programmed time interval which is started by
.1 M = 1/10 Minutes Timing Range 0.1 to 99.9 Minutes applying input voltage. LED flashes when output relay is off and is on continuously
M = Minutes Timing Range 1 to 999 Minutes when the output relay is on. Applying CONTROL input will have no effect on timing
.1 H = 1/10 Hours Timing Range 0.1 to 99.9 Hours or the state of the relay.
H = Hours Timing Range 1 to 999 Hours
10 H = 10 Hours Timing Range 10 to 9990 Hours
Dimensions are shown for Dimensions are in inches over Specifications and availability www.tycoelectronics.com
1216 reference purposes only. (millimeters) unless otherwise subject to change. Technical support:
specified. Refer to inside back cover.
Catalog 1308242
Issued 3-03 AGASTAT
SSF series
Programmable
Time Delay Relay
• 4 user-programmable timing modes
• 0.1 sec. to 10 hr. programmable timing range
• Parameters set with recessed screwdriver dials
• Universal voltage (plug-in relay dependent)
• 10A DPDT replaceable output relay minimizes downtime
• Front screw terminals
• DIN-rail, panel or machine tool track mount
File E15631
File LR29186
Users should thoroughly review the technical data before selecting a product part
number. It is recommended that user also seek out the pertinent approvals files of
the agencies/laboratories and review them to ensure the product meets the
requirements for a given application.
Outline Dimensions 0.188 (5) WIDE SLOT FOR #8 OR M4 MACHINE SCREW Ordering Information
2.19
2.67
(68) 1.095
(56) SSF R 90 A
(28)
0.342 (9) | | | |
Series SSF R = UL Operating Mode 90 Operating Voltage
Universal Recognized Multiple modes - (+10%, –15%)
3.125 2 3 4 5 Timer Component On-Delay A = 120VAC, 50/60 Hz.
(79) 1 6 Off-Delay B = 240VAC, 50/60 Hz.
DIN HOLE
3.81
Interval E = 24VAC, 50/60 Hz.
TRACK PATTERN
MOUNT FOR (97) Latching Interval F = 48VAC, 50/60 Hz.
SCREW N = 48VDC
MOUNT O =24VDC
7 8 9 10 P = 125VDC
X = No factory-
0.343 (9) installed relay.†
6-32 CAPTIVE 0.322
CLAMP SCREWS (8)
† Voltage determined by customer-supplied relay. Only relays that operate
Wiring Diagram (Top View) on the above-listed voltages should be used. Timer operation using
other relay voltages is not recommended.
Dimensions are shown for Dimensions are in inches over Specifications and availability www.tycoelectronics.com
reference purposes only. (millimeters) unless otherwise subject to change. Technical support: 1217
specified. Refer to inside back cover.
Catalog 1308242
Issued 3-03 AGASTAT
SCF series
Programmable
Time Delay Relay
• 4 user-programmable timing modes
• 0.1 sec. to 10 hr. programmable timing range
• Parameters set with recessed dials
• Narrow width saves panel space
• 10A DPDT output relay
• Socket can be DIN-rail or back panel mounted
File E15631(relay) and E140494 (socket)
File LR29186 (relay) and LR29513M7 (socket)
Users should thoroughly review the technical data before selecting a product part
number. It is recommended that user also seek out the pertinent approvals files of
the agencies/laboratories and review them to ensure the product meets the
requirements for a given application.
Dimensions are shown for Dimensions are in inches over Specifications and availability www.tycoelectronics.com
1218 reference purposes only. (millimeters) unless otherwise subject to change. Technical support:
specified. Refer to inside back cover.
Catalog 1308242
Issued 3-03 P&B
CN1 series
On Delay, Time Delay Relay For
Plug-In or Panel Mounting
• 0.1 sec. to 9,990 hr. timing range
• Fixed input type (120VAC ± 15%)
• 10A output relay with DPDT contacts
• 1/16 DIN style enclosure with 8-pin plug-in base
• Thumbwheel switches for programming delay time
File E22575
File LR15734
Users should thoroughly review the technical data before selecting a product part
number. It is recommended that user also seek out the pertinent approvals files of
the agencies/laboratories and review them to ensure the product meets the
requirements for a given application.
Ordering Information – Authorized distributors are more likely to stock boldface items listed below.
Time Delay Relay Accessory
Input Voltage Part Number Part Number Name Description
120VAC CN1 SSA-24C667 Mounting Clip Ratchet-fit clip slides onto CN1 from behind
to secure CN1 in panel mount applications.
2.283 1.970
(58.0) (50.0)
1.88 1.76 2.047
(47.8) (44.7)
3 1 2 S (52.0)
.64 .591
(16.3) (15.0)
Fits 1.77 x 1.77 (45 x 45) panel cutout. 3.15 1.654
(80.0) (42.0)
1.890
Wiring Diagram (Bottom View) (48.0)
CG series
CMOS IC Time Delay Relay
• Repeatability to .05%
• Choice of timing modes
– Delay on operate
– Delay on release
– Interval on
• Knob adjustable
• 10A output relay with DPDT contacts
• Various models time from 0.5 sec. to 100 min.
File E22575
File LR15734
Users should thoroughly review the technical data before selecting a product part
number. It is recommended that user also seek out the pertinent approvals files of
the agencies/laboratories and review them to ensure the product meets the
requirements for a given application.
N.O. RELAY ON ➛
CONTACTS OFF
TIME ➛
CONTROL ON
SWITCH OFF Input Data @ 25°C
N.O. RELAY ON Voltage: 120VAC and 24VDC.
➛
➛
CONTACTS OFF TIME
Power Requirement: AC Types: Typically less than 3 VA.
DC Types: Typically less than 3 W.
Transient Protection: Yes.
Reverse Voltage Protection: Yes.
Interval on – The relay energizes and timing begins when input voltage is Input Voltages & Limits @25°C
applied. At the end of the time delay period the relay will de-energize.
Voltage Nominal Minimum Maximum
Reset is accomplished by removing, then reapplying, the input voltage. Type Voltage Voltage Voltage
AC 120 105 130
INPUT ON DC 24 20 32
VOLTAGE OFF
Note: DC voltage must be filtered (5% p-p ripple max. at nom. voltage).
AC models will operate on 50 or 60 Hz.
N.O. RELAY ON ➛
CONTACTS OFF
TIME ➛
Environmental Data
Temperature Range: Storage: -40°C to +85°C.
Timing Specifications Operating: -10°C to +55°C.
Timing Ranges: From 0.5 to 5.0 sec. through 10 to 100 min.
Timing Adjustment: Knob adjustable.
Tolerance (for AC units add ±1/2 cycle 60 Hz.):
Knob Adj. Types:–0, +10% of max. specified at high end of timing range;
+0, –10% of min. specified at low end. Mechanical Data
Delta Time (for AC units add ±1 cycle 60 Hz.): ± 2%, typ.; ± 5%, max. Termination: 8- or 11-pin octal style plug.
Repeatability (including first cycle of operation): Enclosure: Yellow plastic case. Knob adjustable types have dial scale for
AC: ± 0.1%, typ.; ± 0.5%, max.; but not less than ± 16 ms. reference only.
DC: ± 0.05% typ.; ± 0.1% max.; but not less than ± 3 ms. Sockets: Models with 8-pin base fit either 27E122 or 27E891 (snap-on)
Release Time: 30 ms, typ.; 45 ms, max. screw terminal sockets. 11-pin types fit either 27E123 or
Recycle Time: AC: 40 ms, typ.; 60 ms, max. 27E892 (snap-on) screw terminal sockets.
DC: 30 ms, typ.; 45 ms, max. Weight: 8 oz. (227g) approximately.
Dimensions are shown for Dimensions are in inches over Specifications and availability www.tycoelectronics.com
1220 reference purposes only. (millimeters) unless otherwise subject to change. Technical support:
specified. Refer to inside back cover.
Catalog 1308242
Issued 3-03 P&B
Ordering Information – Authorized distributors are more likely to stock boldface items listed below.
Outline Dimensions
2.406 MAX.
(61.1)
➛
➛
➛
➛
➛
➛
➛
EXT.
CONT.
+ INPUT _ + INPUT
_
SW*
(DC POLARITY INDICATED) (DC POLARITY INDICATED)
Fig.1 Fig.2
8 Pin 11 Pin
* If control switch is closed when power is applied, relay will immediately energize. A 50 millisecond minimum switch closure is required. IMPORTANT: a dry circuit switch is recommemded. A
“dry circuit” switch is one rated to reliably switch currents of less than 50mA. Use of a switch rated for other than dry circuit may result in failure of the time delay relay to function properly.
** Note: input polarity for DC operation. For most reliable operation on AC, connect high side to “+” and low side to “–”.
Dimensions are shown for Dimensions are in inches over Specifications and availability www.tycoelectronics.com
reference purposes only. (millimeters) unless otherwise subject to change. Technical support: 1221
specified. Refer to inside back cover.
Catalog 1308242
Issued 3-03 P&B
CD series
CMOS IC Time Delay Relay
• 1% Repeatability
• Operates from -40°C to +55°C
• Delay on operate or delay on release timing modes
• Fixed, knob or resistor adjustable types
– Calibrated dial on knob adjustable types
• 10A output relay with SPDT or DPDT contacts
• Various models time from 0.1 to 180 sec.
File E22575
File LR15734
Users should thoroughly review the technical data before selecting a product part
number. It is recommended that user also seek out the pertinent approvals files of
the agencies/laboratories and review them to ensure the product meets the
requirements for a given application.
INPUT ON
VOLTAGE OFF
N.O. RELAY ON
➛
TIME ➛
CONTACTS OFF
Input Data @ 25°C
Voltage: 24 & 120VAC and 12 through 110VDC.
Delay on release – Input voltage must be applied continuously to operate Power Requirement: AC Types: Typically less than 3 VA.
the internal relay. When control Input is applied, the relay energizes. DC Types: Typically less than 3 W.
When control input is removed, timing begins. When timing is complete, Transient Protection: Yes.
the relay will de-energize. Time may be reset to zero during timing by Reverse Voltage Protection: Yes.
reapplying control input.
Input Voltages & Limits @ 25°C
Voltage Nominal Minimum Maximum
CONTROL ON
INPUT OFF
Type Voltage Voltage Voltage
N.O. RELAY ON
TIME AC 24 20 28
➛
CONTACTS OFF ➛
120 105 130
12 11 13
DC 24 20 32
48 41 55
110 95 125
Note: DC voltage must be filtered (5% p-p ripple max. at nom. voltage).
AC models will operate on 50 or 60 Hz.
Timing Specifications
Timing Ranges: From 0.1 to 180 sec.
Timing Adjustment: Fixed, external resistor and knob adjustable.
Tolerance (for AC units add ±1/2 cycle 60 Hz.):
Knob Adj. Types: ± 5% of max. specified at high end of timing range; min.
specified, or less, at low end; ± 10% full scale.
Fixed Types: ± 5%.
Res. Adj. Types: ± 5% at high end of timing range; min. specified, or less,
Environmental Data
at low end.
Delta Time (for AC units add ±1 cycle 60 Hz.): ± 5%. Temperature Range: Storage: -55°C to +85°C.
Repeatability (for AC units add ±1 cycle 60 Hz.): ± 1%. Operating: -40°C to +55°C.
Release Time: 45 ms, typ.; 60 ms, max.
Recycle Time: 45 ms, typ.; 60 ms, max.
Mechanical Data
Contact Data @ 25°C Termination: 8- or 11-pin octal style plug.
Arrangements: 2 Form C (DPDT). Enclosure: Yellow plastic case. Knob adjustable types have dial scale
Material: Silver-cadmium oxide alloy. calibrated in seconds ± 5%.
Rating: 10A @ 30VDC or 277VAC, resistive; 1/2 HP @ 250VAC; 1/3 HP @ Sockets: Models with 8-pin base fit either 27E122 or 27E891 (snap-on)
120VAC. screw terminal sockets. 11-pin types fit either 27E123 or
Expected Mechanical Life: 10 million operations. 27E892 (snap-on) screw terminal sockets.
Expected Electrical Life: 100,000 operations, min., at rated load. Weight: 8 oz. (227g) approximately.
Dimensions are shown for Dimensions are in inches over Specifications and availability www.tycoelectronics.com
1222 reference purposes only. (millimeters) unless otherwise subject to change. Technical support:
specified. Refer to inside back cover.
Catalog 1308242
Issued 3-03 P&B
Ordering Information – Authorized distributors are more likely to stock boldface items listed below.
Delay on Operate Models Delay on Release Models
Voltage Time Adjustment Wiring Dia. Part Number Voltage Time Adjustment Wiring Dia. Part Number
0.1 to 1 Sec. CDB-38-70001 0.1 to 1 Sec. CDB-38-70016
0.1 to 5 Sec. CDB-38-70002 0.1 to 5 Sec. CDB-38-70091
120VAC 0.1 to 10 Sec. Knob 1 CDB-38-70003 120VAC 0.1 to 10 Sec. Knob 3 CDB-38-70014
0.3 to 30 Sec. CDB-38-70006 0.3 to 30 Sec. CDB-38-70092
0.6 to 60 Sec. CDB-38-70004 0.6 to 60 Sec. CDB-38-70012
1.8 to 180 Sec. CDB-38-70005 1.8 to 180 Sec. CDB-38-70015
120VAC 1 Sec. Fixed CDA-38-70012 120VAC 1 Sec. Fixed 3 CDA-38-70025
0.1 to 1 Sec. CDF-38-70001 12VDC 180 Sec. Fixed 3 CDC-38-20026
120VAC 0.1 to 5 Sec. Resistor 2 CDF-38-70002 0.1 to 10 Sec. CDD-38-30014
0.1 to 10 Sec. CDF-38-70003 24VDC 0.6 to 60 Sec. Knob 3 CDD-38-30012
0.1 to 10 Sec. CDD-38-30003 1.8 to 180 Sec. CDD-38-30008
24VDC 0.6 to 60 Sec. Knob 1 CDD-38-30004
1.8 to 180 Sec. CDD-38-30005
48VDC 0.6 to 60 Sec. Knob 1 CDD-38-40002
0.1 to 1 Sec. CDD-38-60004
110VDC 0.1 to 10 Sec. Knob 1 CDD-38-60001
0.6 to 60 Sec. CDD-38-60002
1.8 to 180 Sec. CDD-38-60003
Outline Dimensions ➛
2.406 MAX.
(61.1)
➛
CONTROL
INPUT* _
EXTERNAL RESISTOR +
➛
➛
➛
➛
➛
➛
➛
➛
➛
➛
+ _
+ _ _ SUPPLY
+
INPUT INPUT INPUT
(DC POLARITY INDICATED)** (DC POLARITY INDICATED)** (DC POLARITY INDICATED)**
Fig. 1 Fig. 2 Fig. 3
8 Pin 11 Pin 11 Pin
* If control input is applied when supply input is applied, relay will immediately energize. A 50 millisecond minimum control pulse is required.
** Note Input polarity for DC operation. For most reliable operation on AC, connect high side to “+” and low side to “–”.
Dimensions are shown for Dimensions are in inches over Specifications and availability www.tycoelectronics.com
reference purposes only. (millimeters) unless otherwise subject to change. Technical support: 1223
specified. Refer to inside back cover.
Catalog 1308242
Issued 3-03 P&B
CK series
Mid-Priced CMOS IC Time Delay Relay
• Choice of timing modes
– Delay on operate
– Delay on release
– Delay on dropout (no input required during timing)
– Interval on
• Knob or resistor adjustable types
• 10A output relay with DPDT contacts
• Various models time from 0.1 to 180 sec.
File E22575
File LR15734
Users should thoroughly review the technical data before selecting a product part
number. It is recommended that user also seek out the pertinent approvals files of
the agencies/laboratories and review them to ensure the product meets the
requirements for a given application.
Delay on release – Input voltage must be applied continuously to operate Initial Dielectric Strength
the internal relay. When the control switch is closed, the relay energizes. Between Open Contacts: 500V rms, 60 Hz.
When the control switch is opened, timing begins. When timing is Between All Other Conductors: 500V rms, 60 Hz.
complete, the relay will de-energize. Time may be reset to zero during
timing by closing the control switch.
CONTROL ON
SWITCH OFF
N.O. RELAY
CONTACTS
ON ➛
TIME ➛ Input Data @ 25°C
OFF
Voltage: 24 & 120VAC and 12 & 24VDC.
Power Requirement: AC Types: Typically less than 3 VA.
DC Types: Typically less than 3 W.
Delay on dropout – The relay operates immediately upon application of Initiate Time: Delay on dropout timers must have input voltage applied for
input voltage. Timing begins when input voltage is removed. When timing a minimum of three seconds for dropout function to be
is complete, the relay will de-energize. Reset occurs when input voltage is guaranteed.
reapplied. Transient Protection: Yes.
INPUT ON Reverse Voltage Protection: Yes.
VOLTAGE OFF
N.O. RELAY ON ➛ Input Voltages & Limits @ 25°C
CONTACTS OFF
TIME ➛ Voltage Nominal Minimum Maximum
Type Voltage Voltage Voltage
Environmental Data
Timing Specifications
Temperature Range: Storage: -55°C to +85°C.
Timing Ranges: From 0.1 to 180 sec.
Operating: -10°C to +55°C.
Timing Adjustment: External resistor and knob adjustable.
Tolerance (for AC units add ±1/2 cycle 60 Hz.):
Knob Adj. Types:–0, +20% of max. specified at high end of timing range;
min. specified, or less, at low end. Mechanical Data
Fixed Types: ± 5%. Termination: 8- or 11-pin octal style plug.
Res. Adj. Types: ± 5% at high end of timing range; min. specified, or less, Enclosure: White plastic case. Knob adjustable types have dial scale for
at low end. reference only.
Delta Time (for AC units add ±1 cycle 60 Hz.): ± 10%. Sockets: Models with 8-pin base fit either 27E122 or 27E891 (snap-on)
Repeatability (for AC units add ±1 cycle 60 Hz.): ± 2%. screw terminal sockets. 11-pin types fit either 27E123 or
Release Time: 60 ms, typ.; 100 ms, max. 27E892 (snap-on) screw terminal sockets.
Recycle Time: 60 ms, typ.; 100 ms, max. Weight: 6 oz. (170g) approximately.
Dimensions are shown for Dimensions are in inches over Specifications and availability www.tycoelectronics.com
1224 reference purposes only. (millimeters) unless otherwise subject to change. Technical support:
specified. Refer to inside back cover.
Catalog 1308242
Issued 3-03 P&B
Ordering Information – Authorized distributors are more likely to stock boldface items listed below.
Interval On Models
Voltage Time Adjustment Wiring Dia. Part Number
120VAC 0.1 to 10 Sec. Knob 3 CKB-38-79010
Outline Dimensions
➛
2.406 MAX.
(61.1)
➛
.60
➛ 2.937 MAX. ➛ .56 ➛ 1.781 MAX.
➛ (74.6) ➛ (14.2) (45.2) ➛
(15.2)
EXTERNAL
➛
EXTERNAL
➛
CONTROL
➛
CONTROL
➛
➛
SWITCH*
➛
➛
➛
➛
_ SWITCH*
➛
+ + _
➛
➛
_ CONTINUOUS CONTINUOUS
_ +
+ SUPPLY SUPPLY
INPUT INPUT INPUT INPUT
(DC POLARITY INDICATED)** (DC POLARITY INDICATED)** (DC POLARITY INDICATED)** (DC POLARITY INDICATED)**
Fig.1 Fig. 2 Fig. 3 Fig. 4
8 Pin 11 Pin 11 Pin 11 Pin
* If control switch is closed when power is applied, relay will immediately energize. A 50 millisecond minimum switch closure is required. IMPORTANT: A dry circuit switch is recommended. A “dry
circuit” switch is one rated to reliably switch currents of less than 50mA. Use of a switch rated for other than dry circuit may result in failure of the time delay relay to function properly.
** Note: Input polarity for DC operation. For most reliable operation on AC, connect high side to “+” and low side to “–”.
Dimensions are shown for Dimensions are in inches over Specifications and availability www.tycoelectronics.com
reference purposes only. (millimeters) unless otherwise subject to change. Technical support: 1225
specified. Refer to inside back cover.
Catalog 1308242
Issued 3-03 P&B
CH series
Mid- To Low-Priced
CMOS IC Time Delay Relay
• Choice of timing modes
– Delay on operate
– Delay on release
– Interval on
• Fixed or knob adjustable types
• 10A output relay with DPDT contacts
• Various models time from 1 to 180 sec.
File E22575
File LR15734
Users should thoroughly review the technical data before selecting a product part
number. It is recommended that user also seek out the pertinent approvals files of
the agencies/laboratories and review them to ensure the product meets the
requirements for a given application.
Note: DC voltage must be filtered (5% p-p ripple max. at nom. voltage).
N.O. RELAY ON AC models will operate on 50 or 60 Hz.
CONTACTS OFF TIME
Environmental Data
Timing Specifications Temperature Range: Storage: -55°C to +85°C.
Timing Ranges: From 1 to 180 sec. Operating: -10°C to +55°C.
Timing Adjustment: Fixed and knob adjustable.
Tolerance (for AC units add ±1/2 cycle 60 Hz.):
Knob Adj. Types:–0, +20% of max. specified at high end of timing range;
min. specified, or less, at low end. Mechanical Data
Fixed Types: ± 5%. Termination: 8- or 11-pin octal style plug.
Res. Adj. Types: ± 5% at high end of timing range; min. specified, or less, Enclosure: White plastic case. Knob adjustable types have dial scale for
at low end. reference only.
Delta Time (for AC units add ±1 cycle 60 Hz.): ± 10%. Sockets: Models with 8-pin base fit either 27E122 or 27E891 (snap-on)
Repeatability (for AC units add ±1 cycle 60 Hz.): ± 2%. screw terminal sockets. 11-pin types fit either 27E123 or
Release Time: 125 ms, typ.; 200 ms, max. 27E892 (snap-on) screw terminal sockets.
Recycle Time: 125 ms, typ.; 200 ms, max. Weight: 6 oz. (170g) approximately.
Dimensions are shown for Dimensions are in inches over Specifications and availability www.tycoelectronics.com
1226 reference purposes only. (millimeters) unless otherwise subject to change. Technical support:
specified. Refer to inside back cover.
Catalog 1308242
Issued 3-03 P&B
Ordering Information – Authorized distributors are more likely to stock boldface items listed below.
Outline Dimensions
➛
2.406 MAX.
(61.1)
➛
.60
➛ 2.937 MAX. ➛ .56 ➛ 1.781 MAX.
(15.2)
➛ (74.6) ➛ (14.2) (45.2) ➛
EXTERNAL RESISTOR
EXT SWITCH*
➛
➛
➛
➛
➛
➛
➛
➛
+ INPUT _ +
INPUT
_ + -
(DC POLARITY INDICATED) (DC POLARITY INDICATED) AC INPUT
Fig. 1 Fig. 2 Fig. 3
8 Pin 11 Pin 11 Pin
* If control switch is closed when power is applied, relay will immediately energize. A 50 millisecond minimum switch closure is required. IMPORTANT: A dry circuit switch is recommended. A
“dry circuit” switch is one rated to reliably switch currents of less than 50mA. Use of a switch rated for other than dry circuit may result in failure of the time delay relay to function properly.
** Note: Input polarity for DC operation. For most reliable operation on AC, connect high side to “+” and low side to “–”.
Dimensions are shown for Dimensions are in inches over Specifications and availability www.tycoelectronics.com
reference purposes only. (millimeters) unless otherwise subject to change. Technical support: 1227
specified. Refer to inside back cover.
Catalog 1308242
Issued 3-03 P&B
CB series
CMOS IC Time Delay Relay
• Choice of timing modes
– Delay on operate
– Delay on release
– Interval on with or without control switch
• Knob adjustable
• 10A output relay with SPDT or DPDT contacts
• Various models time from 0.1 sec. to 100 min.
File E22575
File LR15734
Users should thoroughly review the technical data before selecting a product part
number. It is recommended that user also seek out the pertinent approvals files of
the agencies/laboratories and review them to ensure the product meets the
requirements for a given application.
Interval on (without control switch) – The relay energizes and timing Input Data @ 25°C
begins when input voltage is applied. At the end of the time delay period Voltage: 24 and 120VAC, and 12 and 24VDC.
the relay will de-energize. Reset is accomplished by removing, then Power Requirement: AC Types: Typically less than 3 VA.
reapplying, the input voltage. DC Types: Typically less than 3 W.
INPUT ON
Transient Protection: Yes.
VOLTAGE OFF Reverse Voltage Protection: Yes.
Dimensions are shown for Dimensions are in inches over Specifications and availability www.tycoelectronics.com
1228 reference purposes only. (millimeters) unless otherwise subject to change. Technical support:
specified. Refer to inside back cover.
Catalog 1308242
Issued 3-03 P&B
Ordering Information – Authorized distributors are more likely to stock boldface items listed below.
Delay on Operate Models Delay on Release Models
Voltage Time Adjustment Wiring Dia. Part Number Voltage Time Adjustment Wiring Dia. Part Number
24VAC 0.1 to 10 Sec. Knob 1 CB-1041B-30 24VAC 0.1 to 10 Sec. Knob 3 CB-1045B-38
1.8 to 180 Sec CB-1042B-30 1.8 to 180 Sec CB-1046B-38
0.1 to 1 Sec. CB-1001B-70 0.1 to 10 Sec. 3 CB-1021B-78
0.1 to 5 Sec. CB-1002B-70 120VAC 0.1 to 10 Sec. Knob 5 CB-1022B-78
0.1 to 10 Sec. CB-1003B-70 0.6 to 60 Sec. 3 CB-1023B-78
120VAC 0.6 to 60 Sec. Knob 1 CB-1004B-70 1.8 to 180 Sec. 3 CB-1024B-78
1.8 to 180 Sec. CB-1005B-70 24VDC 0.1 to 10 Sec. Knob 3 CB-1038D-38
1 to 10 Min. CB-1006B-70 1.8 to 180 Sec. CB-1039D-38
10 to 100 Min. CB-1007B-70
12VDC 0.1 to 10 Sec. Knob 1 CB-1047D-20 Interval on Models
0.1 to 1 Sec. CB-1026D-30 Voltage Time Adjustment Wiring Dia. Part Number
24VDC 0.1 to 10 Sec. Knob 1 CB-1028D-30 24VAC 0.1 to 10 Sec. Knob 1 CB-1043B-39
0.6 to 60 Sec. CB-1029D-30 0.1 to 5 Sec. 1 CB-1011B-79
1.8 to 180 Sec. CB-1030D-30 120VAC 0.1 to 10 Sec. Knob 1 CB-1014B-79
1 to 10 Min. 1 CB-1018B-79
24VDC 0.1 to 5 Sec. Knob 1 CB-1034D-39
1.8 to 180 Sec. CB-1036D-39
Outline Dimensions
➛
2.406 MAX.
(61.1)
➛
➛
➛
➛
➛
➛
➛
➛
+ _ + _
+ _ CONTINUOUS CONTINUOUS
SUPPLY SUPPLY
INPUT (DC POLARITY INPUT INPUT
INDICATED)** (DC POLARITY INDICATED)** (DC POLARITY INDICATED)**
Fig. 1 Fig. 3 Fig. 5
8 Pin 11 Pin 8 Pin
* If control switch is closed when power is applied, relay will immediately energize. A 50 millisecond minimum switch closure is required. IMPORTANT: A dry circuit switch is recommended. A
“dry circuit” switch is one rated to reliably switch currents of less than 50mA. Use of a switch rated for other than dry circuit may result in failure of the time delay relay to function properly.
** Note: Input polarity for DC operation. For most reliable operation on AC, connect high side to “+” and low side to “–”.
Dimensions are shown for Dimensions are in inches over Specifications and availability www.tycoelectronics.com
reference purposes only. (millimeters) unless otherwise subject to change. Technical support: 1229
specified. Refer to inside back cover.
Catalog 1308242
Issued 3-03 P&B
CR series
Recycle Time Delay Relay
• Individual ON and OFF time adjustment knobs
• 10A output relay with DPDT contacts
• Various models time from 0.1 to 180 sec.
File E22575
File LR15734
Users should thoroughly review the technical data before selecting a product part
number. It is recommended that user also seek out the pertinent approvals files of
the agencies/laboratories and review them to ensure the product meets the
requirements for a given application.
Ordering Information – Authorized distributors are more likely to stock boldface items listed below.
Voltage Time Part Number DC Voltage Time Part Number
AC 0.1 to 10 Sec. CRB-48-70010 Type 24VDC 1.8 to 180 Sec. CRD-48-30180
Types 120VAC 0.3 to 30 Sec. CRB-48-70030
0.6 to 60 Sec. CRB-48-70060
1.8 to 180 Sec. CRB-48-70180
.875
➛ (22.23)
➛
➛
➛
➛
➛
1 8
1.25 + INPUT _
(31.75)
(DC POLARITY INDICATED)
Fig.1
➛
8 Pin
** Note: Input polarity for DC operation. For most reliable operation on AC, connect high side
to “+” and low side to “–”.
➛
2.406 MAX.
(61.1)
Dimensions are shown for Dimensions are in inches over Specifications and availability www.tycoelectronics.com
1230 reference purposes only. (millimeters) unless otherwise subject to change. Technical support:
specified. Refer to inside back cover.
Catalog 1308242
Issued 3-03 P&B
CL -CU series
Compact Time Delay Relay
• Delay on operate timing mode
• Fixed, knob or resistor adjustable types
• 10A output relay with DPDT contacts
• Variety of mounting options
• Various models time from 0.1 to 120 sec.
• No timing cycle interrupt transfer (CL only)
File E22575
File LR15734
Users should thoroughly review the technical data before selecting a product part
number. It is recommended that user also seek out the pertinent approvals files of
the agencies/laboratories and review them to ensure the product meets the
requirements for a given application.
CL Ordering Information – Authorized distributors are more likely to stock boldface items listed below.
Voltage Time Adjustment Wiring Dia. Part Number Voltage Time Adjustment Wiring Dia. Part Number
24VAC 0.1 to 10 Sec. Knob 1 CLB-51-30010 12VDC 0.1 to 10 Sec. Knob 1 CLD-51-20010
24VAC 0.1 to 10 Sec. Resistor 2 CLF-42-30010 12VDC 10 Sec. Fixed 1 CLC-41-20010
0.1 to 10 Sec. CLB-51-70010 12VDC 1.2 to 120 Sec. Resistor 2 CLH-41-20120
120VAC 0.3 to 30 Sec. Knob 1 CLB-51-70030 24VDC 5 Sec. Fixed 1 CLC-41-30005
1.2 to 120 Sec. CLB-51-70120
0.1 to 10 Sec. CLH-41-30010
120VAC 3 Sec. Fixed 1 CLA-41-70003 24VDC 0.3 to 30 Sec. Resistor 2 CLH-41-30030
30 Sec. CLA-41-70030 0.1 to 10 Sec. CLH-45-30010
0.1 to 10 Sec. CLF-41-70010
41 style models (e.g. CLA-41-70010) have plain case.
120VAC 0.1 to 10 Sec. Resistor 2 CLF-42-70010
42 style models (e.g. CLF-42-70010) have bracket mount case.
1.2 to 120 Sec. CLF-41-70120
45 style models (e.g. CLH-45-30010) have bracket mount case with test button.
51 style models (e.g. CLB-51-30010) have plain case with knob.
Dimensions are shown for Dimensions are in inches over Specifications and availability www.tycoelectronics.com
reference purposes only. (millimeters) unless otherwise subject to change. Technical support: 1231
specified. Refer to inside back cover.
Catalog 1308242
Issued 3-03 P&B
CU Ordering Information – Authorized distributors are more likely to stock boldface items listed below.
Voltage Time Adjustment Wiring Dia. Part Number Voltage Time Adjustment Wiring Dia. Part Number
24VAC 10 Sec. Fixed 1 CUA-41-30010 1 to 10 Sec. CUF-41-70010
1 to 10 Sec. CUF-41-30010 1 to 10 Sec. CUF-42-70010
24VAC 1 to 10 Sec. Resistor 2 CUF-42-30010 120VAC 1 to 30 Sec. Resistor 2 CUF-41-70030
1 to 120 Sec. CUF-41-70120
1 to 10 Sec. CUB-51-70010 1 to 120 Sec. CUF-42-70120
120VAC 1 to 30 Sec. Knob 1 CUB-51-70030
1 to 60 Sec. CUB-51-70060 1 to 10 Sec. CUH-41-30010
1 to 120 Sec. CUB-51-70120 1 to 10 Sec. CUH-42-30010
24VDC 1 to 120 Sec. Resistor 2 CUH-41-30120
1 Sec. CUA-41-70001 1 to 120 Sec. CUH-42-30120
3 Sec. CUA-41-70003
3 Sec. CUA-42-70003 41 style models (e.g. CUA-41-70010) have plain case.
120VAC 5 Sec. Fixed 1 CUA-41-70005 42 style models (e.g. CUA-42-70010) have bracket mount case.
10 Sec. CUA-41-70010 51 style models (e.g. CUB-51-70010) have plain case with knob.
10 Sec. CUA-42-70010
30 Sec. CUA-42-70030
120 Sec. CUA-41-70120
Outline Dimensions
41 Style 42 & 45 Style 51 Style
1.531 MAX.
➛ (38.89) ➛
1.406 MAX.
.645 TYP. .375 ➛ (35.71) ➛
➛ (15.88) ➛ (9.53) .07
.312 TYP.
(7.92) ➛ ➛ (1.78) ➛ ➛
➛
➛
.625 MAX.
➛ (15.88)
➛
1.906 MAX.
(48.41) 1.906 MAX.
2.500 (48.41)
(63.50) 2.156 MAX.
(15.46)
2.90 MAX.
(73.66)
➛
.281 REF.
➛
(7.14)
.437
➛
➛
1.531 MAX. ➛
➛ ➛ (7.14)
➛
(38.89)
➛
➛
➛ ➛
➛
➛
➛ ➛
➛
.250 ➛
(6.35)
HEADER➛ .281 REF. ➛
(7.14)
THICKNESS 0.20
(.51)
➛
➛
4 6 4 5 6
➛
➛
➛
7 9 7 9
A B A B
+ INPUT - + INPUT -
(DC DC POLARITY INDICATED) ** (DC POLARITY INDICATED) **
Fig. 1 Fig. 2
** Note: Input polarity for DC operation. For most reliable operation on AC, connect high side to “+” and low side to “–”.
Dimensions are shown for Dimensions are in inches over Specifications and availability www.tycoelectronics.com
1232 reference purposes only. (millimeters) unless otherwise subject to change. Technical support:
specified. Refer to inside back cover.
Catalog 1308242
Issued 3-03 AGASTAT
MD0 series
Subminiature, On-Delay
Time Delay Relay
• On-delay timing mode
• Seven user-selectable timing ranges (0.1 sec. to 10 hr.)
• High accuracy and reliability
• Exceptional transient protection (ANSI C37.90)
• 5A DPDT or 4PDT output contacts
• Universal voltage
File E60363
File LR51332
Users should thoroughly review the technical data before selecting a product part
number. It is recommended that user also seek out the pertinent approvals files of
the agencies/laboratories and review them to ensure the product meets the
requirements for a given application.
Environmental Data
Temperature Range: Storage: -25°C to +85°C.
Timing Specifications Operating: -25°C to +60°C.
Timing Ranges: Instantaneous; 0.1 to 1 / 1 to 10 / 10 to 100 sec.;
1 to 10 / 10 to 100 min.; 1 to 10 hr.
Timing Range Selection: Screwdriver select via recessed dial on side.
Timing Adjustment: Screwdriver adjust via recessed dial with reference
calibrations on top. Mechanical Data
Accuracy: Repeat Accuracy: ± 0.5% Mounting/Termination: MD0 series time delay relays can be socket
Overall Accuracy: ± 1% ± 0.02 sec. mounted horizontally or vertically and will
Reset Time: 25 ms. operate within repeat accuracy of ± 0.5%.
Sockets: Fits either 27E166 or 27E894 (snap-on) screw terminal sockets.
Status Indication: Power On LED and Output Contacts LED.
Contact Data @ 25°C Weight: 4 oz. (96g) approximately.
Arrangements: 2 Form C (DPDT) or 4 Form C (4PDT).
Rating: 5A @ 30VDC or 240VAC, resistive.
Expected Electrical Life: 100,000 operations, min., at rated resistive load.
Dimensions are shown for Dimensions are in inches over Specifications and availability www.tycoelectronics.com
reference purposes only. (millimeters) unless otherwise subject to change. Technical support: 1233
specified. Refer to inside back cover.
Catalog 1308242
Issued 3-03 (PDF Rev. 4-04) AGASTAT
SSC series
Specification Grade Discrete Plug-in
Time Delay Relay
• On-Delay, Off-Delay and Interval timing modes
• 13 timing ranges from 0.1 sec. to 60 min.
• 10A DPDT output contacts
• Escellent repeatability of ± 1% or better.
• Exceptional immunity to transients and noise.
• Wide operating temperature range.
File LR29186
Users should thoroughly review the technical data before selecting a product part
number. It is recommended that user also seek out the pertinent approvals files of
the agencies/laboratories and review them to ensure the product meets the
requirements for a given application.
SCB/SCC series
Specification Grade Discrete Plug-in
Time Delay Relay
• On-Delay, Off-Delay and Interval timing modes
• 13 timing ranges from 0.1 sec. to 60 min.
• 10A DPDT output contacts
• Knob, fixed or external timing adjustment.
• Rated for pilot duty
• Premium components
®
File E60363
File LR51332 ® File E60363 (SCC only)
Users should thoroughly review the technical data before selecting a product part
number. It is recommended that user also seek out the pertinent approvals files of
the agencies/laboratories and review them to ensure the product meets the
requirements for a given application.
STA series
Specification Grade Discrete Plug-in
Time Delay Relay With QC Terminals
• On-Delay, Off-Delay, Interval and Accumulating On-Delay
timing modes
• 13 timing ranges from 0.1 sec. to 48 hr.
• 10A DPDT output contacts
• Knob, fixed or external timing adjustment.
• QC plug-in terminals save space, two LEDs show status
®
File E60363
File LR51332
Users should thoroughly review the technical data before selecting a product part
number. It is recommended that user also seek out the pertinent approvals files of
the agencies/laboratories and review them to ensure the product meets the
requirements for a given application.
Contact Data @ 25°C Ordering Information (All "X's" must be included to complete part number)
Arrangements: 2 Form C (DPDT). STA RX 01 2X S A A XA
Rating: 10A @ 28VDC or 120VAC, resistive; 1/3 HP @ 120/240VAC; 345VA.
Same polarity. | | | | | | | |
Expected Mechanical Life: 10 million operations. Series STA | Operating Mode | Status | Timing Range |
Expected Electrical Life: 500,000 operations, min., at rated resistive load. Discrete | 01 = On-Delay | Indication | A =0 .1 to 3 sec. |
Industrial | 02 = Off-Delay | SX == No
LEDs
| B = 0.5 to 15 sec. |
Initial Dielectric Strength Timer 03 = Interval LEDs C = 1 to 30 sec.
With | 09 = Accumulating | | D = 2 to 60 sec. |
Between Terminals and Case: 1,000VAC plus twice the nominal voltage
for one minute. Tab-type | On-Delay | | E = 4 to 120 sec. |
Terms. | | F = 6 to 180 sec. |
Output
Outline Dimensions G = 10 to 300 sec.
| 2X = DPDT | I = 2 to 60 min. |
Relay | |
Mounting Series J = 1 to 6 hr.
1.500 MAX.
RX = 11-pin tab-type | K = 3 to 180 cycles |
header (order L = 0.33 to 10 min.
(38)
socket
| M = 0.5 to 15 min.
|
separately) | N = 1 to 30 min. |
.281 REF.
1.390 MAX. .660 MAX.
(17)
3.045
(77) (7)
| R = 2 to 48 hr. |
(35)
Operating Voltage Timing Adjustment
(+10%, –15%) XA = Knob Adjust
Wiring Diagrams (Bottom Views) A = 120VAC, 50/60 XB = External
Hz. / 120VDC Potentiometer or
Insulated, shielded two-conductor
cable similar to Belden 8719, 8720 E = 24VAC, 50/60 resistor (Operating
or 8769 required for leads longer Hz. / 24VDC modes 1 and 3
than 6 inches. Maximum F = 48VAC, 50/60 only).
permissble length is 50 feet.
Hz. / 48VDC XF =Fixed Times –
Q = 12VDC Specify time delay
in seconds per the
following examples:
XF9.000 = 9 sec.
XF99.00 = 99 sec.
XF999.0 = 9999 sec.
XF1000 = 1000 sec.
Off-Delay & On-Delay On-Delay
Accumulating & &
On-Delay Interval Interval Authorized distributors are likely to stock the following:
Fixed or Knob Fixed or Knob External Potentiomer None at present.
Adjust Adjust or Resistor Adjust
Dimensions are shown for Dimensions are in inches over Specifications and availability www.tycoelectronics.com
1236 reference purposes only. (millimeters) unless otherwise subject to change. Technical support:
specified. Refer to inside back cover.
Catalog 1308242
Issued 3-03 AGASTAT
SRC series
Specification Grade Repeat Cycle
Plug-in Time Delay Relay
• Repeat Cycle timing mode
• Dual knobs for user adjustment of on and off times.
• 13 timing ranges from 0.1 sec. to 60 min.
• 10A DPDT output contacts
• Exceptional immunity to line transients and noise
• Premium components enhance reliability
• Superior reset time of 24 msec.
Users should thoroughly review the technical data before selecting a product part
number. It is recommended that user also seek out the pertinent approvals files of
the agencies/laboratories and review them to ensure the product meets the
requirements for a given application.
Dimensions are shown for Dimensions are in inches over Specifications and availability www.tycoelectronics.com
reference purposes only. (millimeters) unless otherwise subject to change. Technical support: 1237
specified. Refer to inside back cover.
Catalog 1308242
Issued 3-03 AGASTAT
SST series
Industrial Grade Discrete Plug-in
Time Delay Relay
• On-Delay, Off-Delay, Interval, One Shot & Repeat modes
• Time delays to 120 min.
• Fast setting with time calibrated knobs.
• Superior transient protection.
• Rugged construction with 8- or 11-pin plug.
• Flame retardant housing.
File E15631
File LR33434
Users should thoroughly review the technical data before selecting a product part
number. It is recommended that user also seek out the pertinent approvals files of
the agencies/laboratories and review them to ensure the product meets the
requirements for a given application.
Temperature Range: Storage: -23°C to +71°C. VAC 1.8 - 180 sec. SST32EDA 24 0.1 - 10 sec. SST42EAA
VDC 1.8 - 180 sec. SST42EDA
Operating: -23°C to +54°C. 24 0.1 - 10 sec. SST32OAA
VDC 1.8 - 180 sec. SST32ODA 24 0.1 - 10 sec. SST42OAA
Outline Dimensions VDC 1.8 - 180 sec. SST42ODA
12 0.1 - 10 sec. SST32QAA
VDC 1.8 - 180 sec. SST32QDA 12 0.1 - 10 sec. SST42QAA
VDC 1.8 - 180 sec. SST42QDA
2.0 MAX.
* Also known as Latching Interval
(50.8) SST7 – Repeat Cycle Types
SQUARE
Input Time Range Part No.
.812 MAX. 3.20 MAX. 120 0.1 - 10 sec. SST72AAA
(20.6) (81.3)
4.60 MAX. VDC 1.8 - 180 sec. SST72ADA
(116.8) 3 - 300 sec. SST72AEA
18 sec. - 30 min. SST72AGA
Wiring Diagrams (Bottom Views) 36 sec. - 60 min. SST72AHA
24 0.1 - 10 sec. SST72EAA
VDC 1.8 - 180 sec. SST72EDA
24 0.1 - 10 sec. SST72OAA
VDC 1.8 - 180 sec. SST72ODA
12 0.1 - 10 sec. SST72QAA
VDC 1.8 - 180 sec. SST72QDA
SCE series
Specification Grade Discrete Plug-in
True Off-Delay Time Delay Relay
• True Off-Delay timing modes
• Six time delays from 0.1 sec. to 10 min.
• 10A SPDT or 5A DPDT output contacts.
• Excellent repeat accuracy – typically better than ± 1%.
• 8--pin octal plug.
®
File E15631
File LR51332
CAUTION: Users should thoroughly review the technical data before selecting a product part
If unit has not been energized for several months, apply operating number. It is recommended that user also seek out the pertinent approvals files of
voltage for 20 minutes prior to initial time delay. the agencies/laboratories and review them to ensure the product meets the
requirements for a given application.
Dimensions are shown for Dimensions are in inches over Specifications and availability www.tycoelectronics.com
reference purposes only. (millimeters) unless otherwise subject to change. Technical support: 1239
specified. Refer to inside back cover.
Catalog 1308242
Issued 3-03 AGASTAT
VTM-1 series
Specification Grade, On-Delay
Timing Module
• On-delay timing mode
• Timing from 1 to 1000 sec.
• 1A solid state SPST-NO output
• 0.25" (6.35) quick connect terminals
• Universal voltage: 24 to 240VAC/VDC
• Rated to 10 million operations
File E60363
File LR51332
Users should thoroughly review the technical data before selecting a product part
number. It is recommended that user also seek out the pertinent approvals files of
the agencies/laboratories and review them to ensure the product meets the
requirements for a given application.
Wiring Diagram
Notes:
1. Do not operate timer
without connecting load
in series with line voltage.
2. For a time delay of 1
second, connect a jumper
across the center two
terminals.
Dimensions are shown for Dimensions are in inches over Specifications and availability www.tycoelectronics.com
1240 reference purposes only. (millimeters) unless otherwise subject to change. Technical support:
specified. Refer to inside back cover.
Catalog 1308242
Issued 3-03 (PDF Rev. 4-04) AGASTAT
VTM1 series
On-Delay
Timing Module
• On-delay timing mode
• Reliable solid state timing circuitry.
• Excellent transient protection.
• Compact design.
• Flame retardant, solvent resistant housing.
File E60363
File LR33434
Users should thoroughly review the technical data before selecting a product part
number. It is recommended that user also seek out the pertinent approvals files of
the agencies/laboratories and review them to ensure the product meets the
requirements for a given application.
(T )
Treq - Tmin
Rt = x 1,000,000 ohms
max - Tmin
Accuracy: Repeat Accuracy: ± 1% Environmental Data
Overall Accuracy: ± 2% at R = 1 megohm. Temperature Range: Storage: -40°C to +85°C.
Reset Time: 100 ms, max., before time-out; 10 ms, max., after time-out. Operating: -40°C to +65°C.
Output Switch Data
Arrangement: Solid state 1 Form A (SPST-NO).
Rating: 1A, inductive, at nominal operating voltage.
Expected Electrical Life: 10,000,000 operations at rated load.
Mechanical Data
Mounting: Panel mount with one #8 screw.
Termination: 0.250 in (6.35) quick connect terminals.
Initial Dielectric Strength Weight: 3 oz. (84g) approximately.
Between Terminals and Mounting: 3,000VAC rms.
Between Input and Output: 1,500VAC rms.
2.00
1.25 VTM1 A CD
(31.8)
(50.8) .885 | | |
(22.5)
Series VTM1 Input Voltage Time Range
On-Delay A = 120VAC/VDC CD = 0.5 - 10 sec.
2.00 Timing Module E = 24VAC/VDC DD = 3 - 60 sec.
(50.8) Q = 12VAC/VDC FD = 0.5 - 10 min.
GD = 3 - 60 min.
Wiring Diagram
Rt =
( Treq - Tmin
Tmax - Tmin ) x 1,000,000 ohms
Dimensions are shown for Dimensions are in inches over Specifications and availability www.tycoelectronics.com
reference purposes only. (millimeters) unless otherwise subject to change. Technical support: 1241
specified. Refer to inside back cover.
Catalog 1308242
Issued 3-03 AGASTAT
VTMA1 series
On-Delay Timing Module
With Internal Potentiometer
• On-delay timing mode
• Discrete voltage or universal type.
• Internal potentiometer for timing adjustment.
• Reliable solid state timing circuitry.
• Excellent transient protection.
• Flame retardant, solvent resistant housing.
File E60363
File LR33434
Users should thoroughly review the technical data before selecting a product part
number. It is recommended that user also seek out the pertinent approvals files of
the agencies/laboratories and review them to ensure the product meets the
requirements for a given application.
Mechanical Data
Initial Dielectric Strength Mounting: Panel mount with one #8 screw.
Termination: 0.250 in (6.35) quick connect terminals.
Between Terminals and Mounting: 3,000VAC rms. Weight: 4 oz. (112g) approximately.
Between Input and Output: 1,500VAC rms.
L1 L2
Dimensions are shown for Dimensions are in inches over Specifications and availability www.tycoelectronics.com
1242 reference purposes only. (millimeters) unless otherwise subject to change. Technical support:
specified. Refer to inside back cover.
Catalog 1308242
Issued 3-03 AGASTAT
VTMR1 series
On-Delay Timing Module
With Internal Potentiometer, Relay Output
• On-delay timing mode
• 8A SPDT relay output.
• Internal potentiometer for timing adjustment.
• Reliable solid state timing circuitry.
• Excellent transient protection.
• Flame retardant, solvent resistant housing.
File E60363
File LR33434
Users should thoroughly review the technical data before selecting a product part
number. It is recommended that user also seek out the pertinent approvals files of
the agencies/laboratories and review them to ensure the product meets the
requirements for a given application.
Dimensions are shown for Dimensions are in inches over Specifications and availability www.tycoelectronics.com
reference purposes only. (millimeters) unless otherwise subject to change. Technical support: 1243
specified. Refer to inside back cover.
Catalog 1308242
Issued 3-03 AGASTAT
VTM2 series
Off-Delay
Timing Module
• Off-delay timing mode
• Reliable solid state timing circuitry.
• Excellent transient protection.
• Compact design.
• Flame retardant, solvent resistant housing.
File E60363
File LR33434
Users should thoroughly review the technical data before selecting a product part
number. It is recommended that user also seek out the pertinent approvals files of
the agencies/laboratories and review them to ensure the product meets the
requirements for a given application.
2.00
1.25 VTM2 A CD
(31.8)
(50.8) .885 | | |
(22.5)
Series VTM2 Input Voltage Time Range
Off-Delay A = 120VAC/VDC CD = 0.5 - 10 sec.
2.00 Timing Module E = 24VAC/VDC DD = 3 - 60 sec.
(50.8) Q = 12VAC/VDC GD = 3 - 60 min.
Wiring Diagram
( )
VOLTAGE Treq - Tmin
3 Rt = x 1,000,000 ohms
Tmax - Tmin
Dimensions are shown for Dimensions are in inches over Specifications and availability www.tycoelectronics.com
1244 reference purposes only. (millimeters) unless otherwise subject to change. Technical support:
specified. Refer to inside back cover.
Catalog 1308242
Issued 3-03 AGASTAT
VTM3 series
Interval
Timing Module
• Interval timing mode
• Reliable solid state timing circuitry.
• Excellent transient protection.
• Compact design.
• Flame retardant, solvent resistant housing.
File E60363
File LR33434
Users should thoroughly review the technical data before selecting a product part
number. It is recommended that user also seek out the pertinent approvals files of
the agencies/laboratories and review them to ensure the product meets the
requirements for a given application.
2.00
1.25 VTM3 A CD
(31.8)
(50.8) .885 | | |
(22.5)
Series VTM3 Input Voltage Time Range
Interval A = 120VAC/VDC CD = 0.5 - 10 sec.
2.00 Timing Module E = 24VAC/VDC DD = 3 - 60 sec.
(50.8) Q = 12VAC/VDC GD = 3 - 60 min.
Wiring Diagram
( )
3
Treq - Tmin
Rt = x 1,000,000 ohms
Tmax - Tmin
Dimensions are shown for Dimensions are in inches over Specifications and availability www.tycoelectronics.com
reference purposes only. (millimeters) unless otherwise subject to change. Technical support: 1245
specified. Refer to inside back cover.
Catalog 1308242
Issued 3-03 AGASTAT
VTM4 series
One Shot (Latching Interval)
Timing Module
• One shot (latching interval) timing mode
• Reliable solid state timing circuitry.
• Excellent transient protection.
• Compact design.
• Flame retardant, solvent resistant housing.
File E60363
File LR33434
Users should thoroughly review the technical data before selecting a product part
number. It is recommended that user also seek out the pertinent approvals files of
the agencies/laboratories and review them to ensure the product meets the
requirements for a given application.
VTM4 A CD
1.25
2.00
(50.8)
(31.8) | | |
.885
(22.5) Series VTM4 Input Voltage Time Range
One Shot A = 120VAC/VDC CD = 0.5 - 10 sec.
(Latching Interval) E = 24VAC/VDC DD = 3 - 60 sec.
2.00
(50.8)
Timing Module Q = 12VAC/VDC FD = 0.5 - 10 min.
GD = 3 - 60 min.
Wiring Diagram
Dimensions are shown for Dimensions are in inches over Specifications and availability www.tycoelectronics.com
1246 reference purposes only. (millimeters) unless otherwise subject to change. Technical support:
specified. Refer to inside back cover.
Catalog 1308242
Issued 3-03 AGASTAT
VTM7 series
Repeat Cycle
Timing Module
• Repeat cycle timing mode
• Independently adjustable On and Off times.
• Reliable solid state timing circuitry.
• Excellent transient protection.
• Compact design.
• Flame retardant, solvent resistant housing.
File E60363
File LR33434
Users should thoroughly review the technical data before selecting a product part
number. It is recommended that user also seek out the pertinent approvals files of
the agencies/laboratories and review them to ensure the product meets the
requirements for a given application.
Wiring Diagram
POLARITY SHOWN Rt
FOR DC OFF An external resistance of 1 megohm is
MODELS required to obtain the maximum time Authorized distributors are likely to stock the following:
LOAD 1 7 6 5 for all ranges. To determine the actual None at present.
Rt resistance needed to obtain the
2 4 required time delay, use the following
INPUT ON formula:
VOLTAGE
3
Rt =
( Treq - Tmin
Tmax - Tmin ) x 1,000,000 ohms
Dimensions are shown for Dimensions are in inches over Specifications and availability www.tycoelectronics.com
reference purposes only. (millimeters) unless otherwise subject to change. Technical support: 1247
specified. Refer to inside back cover.
Catalog 1308242
Issued 3-03 (PDF Rev. 4-04) AGASTAT
7000 series
Industrial Electropneumatic
Timing Relay
Dimensions are shown for Dimensions are in inches over Specifications and availability www.tycoelectronics.com
1248 reference purposes only. (millimeters) unless otherwise subject to change. Technical support:
specified. Refer to inside back cover.
Catalog 1308242
Issued 3-03 AGASTAT
Auxiliary switch options
To increase the versatility of the basic timer models, auxiliary switches may 4. De-energizing coil resets both switches instantly. First delay is
be added to either on-delay or off-delay types. They switch additional circuits, independently adjustable, up to 30% of overall delay.
provide two-step timing action, or furnish electrical interlock for sustained coil (Recommended maximum 100 seconds.)
energization from a momentary impulse, depending on the type selected and Auxiliary Switch Options for Off-Delay
its adjustment. Because of their simple attachment and adjustment features, In these models the same auxiliary switch provides either two-step timing or
they can be installed at the factory or in the field, by any competent mechanic. instant transfer action, depending on the adjustment of the actuator.
All auxiliary switches are SPDT with UL listings of 10A @ 125, 250, or 480 VAC. Two-Step Timing (Auxiliary Switch Code T, maximum of 1 per relay.)
A maximum of one Code T or two Code L auxiliary switches may be added to 1. Energizing coil transfers main and auxiliary switches instantly.
each relay. The L or LL switch is available with on-delay relays only. The T 2. De-energizing coil begins time delay.
switch is available with both the on-delay and off-delay relays. 3. After first delay auxiliary switch transfers.
Auxiliary Switch Options for On-Delay 4. Main switch transfers after total preset delay. First delay is independently
Instant Transfer (Auxiliary Switch Code L, maximum of 2 per relay.) adjustable, up to 30% of overall delay. (Recommended maximum 100 sec-
1. Energizing coil begins time delay and transfers auxiliary switch. onds.)
2. Main switch transfers after total preset delay. Instant Transfer (Auxiliary Switch Code L, maximum of 1 per relay.)
3. De-energizing coil resets both switches instantly. 1. Energizing coil transfers main and auxiliary switches instantly.
Auxiliary switch is nonadjustable. 2. De-energizing coil resets auxiliary switch and begins time delay.
Two-Step Timing (Auxiliary Switch Code T, maximum of 1 per relay.) 3. Main switch transfers after total preset delay.
1. Energizing coil begins time delay. Auxiliary switch is factory adjusted to give instant transfer operation, but may
2. After first delay auxiliary switch transfers. be easily adjusted in the field to provide two-step timing.
3. Main switch transfers after total preset delay.
Dimensions are shown for Dimensions are in inches over Specifications and availability www.tycoelectronics.com
reference purposes only. (millimeters) unless otherwise subject to change. Technical support: 1249
specified. Refer to inside back cover.
Catalog 1308242
Issued 3-03 AGASTAT
Timing Specifications (All values shown are at nominal voltage and 25°C unless otherwise specified).
Operating Modes: Minimum operating voltages are based on vertically mounted 7012 units.
Model 7012/7014: On-delay (delay on pick-up). 7012 horizontally mounted or 7022 vertically or horizontally mounted units
Model 7022/7024: Off-delay (delay on drop-out). will operate satisfactorily at minimum voltages approximately 5% lower than
Model 7032: On-delay, off-delay (double head). those listed.
Timing Adjustment: Timing is set by simply turning the calibrated dial to AC units drop out at approximately 50% of rated voltage. DC units drop out
the desired time value. In the zone of approximately 25° separating the at approximately 10% of rated voltage.
high and low end of timing ranges A,D,E, and K, instantaneous operation All units may be operated on intermittent duty cycles at voltages 10% above
(no time delay) will occur. All other ranges produce an infinite time delay the listed maximums (intermittent duty - maximum 50% duty cycle and 30
when the dial is set in this zone. minutes "on" time.)
Models 7014 and 7032 are available with letter-calibrated dials only. The
upper end of the time ranges in these models may be twice the values Surge/Transient Protection Option Characteristics (DC Timers Only)
shown.
Coil Voltage Max Excess Max De-energization
Linear Timing Ranges: Models 7012, Models 7014,
Nominal (DC) Energy Capacity (Joule) Transient Voltage
Code 7022, 7024 7032
A .1 to 1 Sec. .2 to 2 Sec. 12 V 0.4 J 48 V
B .5 to 5 Sec. .7 to 7 Sec. 24 V 1.8 J 93 V
C 1.5 to 15 Sec 2 to 20 Sec. 28 V 1.8 J 93 V
D 5 to 50 Sec. 10 to 100 Sec. 32 V 2.5 J 135 V
E 20 to 200 Sec. 30 to 300 Sec. 48 V 3.57 J 145 V
F 1 to 10 Min. 1.5 to 15 Min. 60 V 6J 250 V
H 3 to 30 Min. 3 to 30 Min. 96 V 10 J 340 V
I 6 to 60 Min. Not Avail. 110 V 10 J 340 V
J 3 to 120 Cyc. Not Avail. 125 V 10 J 340 V
K 1 to 300 Sec. Not Avail. 220 V 17 J 366 V
Repeat Accuracy: 250 V 17 J 366 V
For delays of 200 seconds or less: 7012*, 7022, 7024: +5%
7014*: +10% Surge Life
7032: +15% Applied 100,000 times continuously with the interval of 10 seconds at room
For delays greater than 200 seconds: 7012*, 7022, 7014*, 7024: +10% temperature. Below 68 VAC: 12A; Above 68 VAC: 35A
7032: +15% Temperature Range
* The first time delay afforded by Model 7012 with H (3 to 30 min.) and I (6 Operating: -22°F to +167°F (-30°C to + 75°C)
to 60 min.) time ranges or Model 7014 with H time range will be approx. Storage: -40°F to +167°F (-40°C to +75°C)
15% longer than subsequent delays due to coil temperature rise.
Reset Time: 50 msec. (except model 7032) Output/Life Contact Ratings: Contact Capacity in Amps (Resistive Load)
Relay Release Time: 50 msec. for on-delay models (7012/7014) Contact Min. 100,000 Min. 1,000,000
Relay Operate Time: 50 msec. for off-delay models (7022/7024) Voltage Operations Operations
30 VDC 15.0 7.0
110 VDC 1.0 0.5
Operating Voltage Coil Data (for DPDT) 120 V 60Hz 20.0 15.0
240 V 60Hz 20.0 15.0
Operating* Operating 480 V 60Hz 12.0 10.0
Coil Code Rated Voltage Rated Voltage 10 Amps Resistive, 240 VAC
Part # Letter Voltage Range Voltage Range 1/4 Horsepower, 120 VAC/240VAC (per pole)
@ 60Hz @50Hz 15 Amps 30 VDC (per pole)
7000 A 120 102-132 110 93.5-121 5 Amps, General Purpose, 600VAC (per pole)
B 240 204-264 220 187-242 Dielectric: Withstands 1500 volts RMS 60Hz between terminals and
C 480 408-528 ground. 1,000 volts RMS 60 Hz between non-connected terminals. For
D 550 468-605 dielectric specification on hermetically sealed models consult factory.
E 24 20.5-26.5 Insulation Resistance: 500 Megohms with 500VDC applied.
AC F 127 108-140 Temperature Range: Operating: -20°F to +165°F (-29°C to 74°C)
G 240 204-264 Storage: -67°F to +165°F (-55°C to 74°C)
H 12 10.2-13.2 Temperature Variation: Using a fixed time delay which was set and
I 6 5.1-6.6 measured when the ambient temperature was 77°F (25°C), the maximum
J 208 178-229 observed shift in the average of three consecutive time delays was -20% at
K Dual Voltage Coil -20°F (-29°C) and +20% at 165°F (74°C).
(Combines A&B) Mounting/Terminals: Normal mounting of the basic unit is in a vertical
L Special AC Coils position, from the back of the panel. A front mounting bracket is also
(L1, L2, etc.) supplied with each basic unit, for installation from the front of the panel.
All units are calibrated for vertical operation. Basic models (7012, 7022)
7010 M 28 22.4-30.8 may also be horizontally mounted, and will be adjusted accordingly when
N 48 38.4-52.8 Accessory Y1 is specified in your order.
O 24 19.2-26.4 Standard screw terminals (8-32 truss head screws supplied) are located
P 125 100-137.5 on the front of the unit, with permanent schematic markings. Barrier
Q 12 9.6-13.2 isolation is designed to accommodate spade or ring tongue terminals, with
R 60 48-66 spacing to meet all industrial control specifications.
DC S 250 200-275 The basic Series 7000 may also be panel mounted with the addition of a
T 550 440-605 panelmount kit that includes all necessary hardware and faceplate. This
U 16 12.8-17.6 offers the convenience of "out-front" adjustment, with large calibrated dial
V 32 25.8-35.2 skirt knob. The faceplate and knob blend with advanced equipment and
W 96 76.8-105.6 console designs, while the body of the unit and its wiring are protected
Y 6 4.8-6.6 behind the panel.
Z 220 176-242 Other mounting options include plug-in styles and special configurations
X Special DC Coils to meet unusual installation requirements. Contact factory for details.
(X1, X2, etc.) Power Consumption: Approximately 8 watts power at rated voltage .
Approximate Weights:
*Four pole Models: Operational voltage range 90% to 110% for AC units; Models 7012, 7022 . . . . . . . 2 lbs. 4 ozs.
85% to 110% for DC units. 7014, 7024 . . . . . . . 2 lbs. 10 ozs.
7032 . . . . . . . . . . . . 3 lbs. 5 ozs.
Weight may vary slightly with coil voltage.
See next column for more coil data.
Dimensions are shown for Dimensions are in inches over Specifications and availability www.tycoelectronics.com
1250 reference purposes only. (millimeters) unless otherwise subject to change. Technical support:
specified. Refer to inside back cover.
Catalog 1308242
Issued 3-03 AGASTAT
Outline Dimensions (Dimensions in inches).
Models 7012, 7022 Models 7014, 7024 Model 7032
Dimensions are shown for Dimensions are in inches over Specifications and availability www.tycoelectronics.com
reference purposes only. (millimeters) unless otherwise subject to change. Technical support: 1251
specified. Refer to inside back cover.
Catalog 1308242
Issued 3-03 AGASTAT
Ordering Information
Typical Part No. ➤ 70 1 2 A D GZ
1. Basic Series:
70 = 7000 series electropneumatic timing relay
2. Operation:
1 = On-delay 3 = On-delay, off-delay (double head)
2 = Off-delay
3. Contact Arrangement:
2 = 2PDT (2 form C) **4 = 4PDT (4 form C)
4. Coil Voltage:
AC Coils DC Coils
A = 120VAC, 60 Hz.; 110VAC, 50Hz. M = 28VDC
B = 240VAC, 60 Hz.; 220VAC, 50Hz. N = 48VDC
C = 480VAC, 60 Hz. O = 24VDC
D = 550VAC, 60 Hz. P = 125VDC
E = 24VAC, 60 Hz. Q = 12VDC
F = 127VAC, 50 Hz. R = 60VDC
G = 240VAC, 50Hz. S = 250VDC
H = 12VAC, 60 Hz. T = 550VDC
K = Dual voltage (combines A & B) U = 16VDC
L = Special AC coils (L1, L2, etc.) V = 32VDC
W = 96VDC
Y = 6VDC
Z = 220VDC
X = Special DC coils (X1, X2, etc.)
5. Timing Range:
Models 7012, 7022 & 7024 †Models 7014 & 7032
A = .15 to 3 sec. For model 7032 specify separate time
B = .5 to 5 sec. range code for each head. Example: AB.
C = 1.5 to 15 sec. Any two ranges may be selected.
D = 5 to 50 sec. A = .2 to 2 sec.
E = 20 to 200 sec. B = .7 to 7 sec.
F = 1 to 10 min. C = 2 to 20 sec.
H = 3 to 30 min. D = 10 to 100 sec.
I = 6 to 60 min. E = 30 to 300 sec.
J = 3 to 120 cyc. F = 1.5 to 15 min.
K = 1 to 300 sec. H = 3 to 30 min.
6. Options:
A1 = Single quick-connect terminals (note 4). K = Explosion-proof Enclosure (note 1).
A2 = Double quick-connect terminals (note 4). L = Auxiliary Switch, instant transfer. 7012 only (notes 2 & 6).
B = Plug-in connectors (note 4). LL = Two Aux. Switches, instant transfer. On Model 7014 Factory Installed Only. (notes 2 & 6)
GZ = Enclosure with bottom knockouts (note 1). M = Dust-tight Gasketing (notes 4 & 5).
H2 = Hermetically sealed enclosure, 8 pin solder (notes 1 & 4). P = Octal Plug Adapter. Can be combined only with options l1,l2. M, S, X, or Y1. (note 4).
H3 = Hermetically sealed enclosure, 8 pin octal (notes 1 & 4). S = Dial Stops.
H4 = Hermetically sealed enclosure, 8 screw terminal block (notes 1 & 4). T = Auxiliary Switch, two-step timing (notes 2 & 6).
*H6 = Hermetically sealed enclosure, 11 pin solder (notes 1 & 4). V = Transient/Surge Protection (for DC coil voltage only).
*H7 = Hermetically sealed enclosure, 11 pin octal (notes 1 & 4). W = Watertight Enclosure (note 1).
*H8 = Hermetically sealed enclosure, 11 screw terminal block (notes 1 & 4). X = Panelmount includes hardware and adjustment for horizontal operation (note 4)
l1 = Tamper-proof Cap, opaque black (Cannot be combined with Option X). Y1 = Horizontal calibration, for horizontal operation without panelmounting (note 4).
l2 = Tamper-proof Cap, transparent (Cannot be combined with Option X). Y2 = Horizontal calibration, with Compensating Spring for vertical operation (note 4).
Notes:
1. Cannot be combined with B, P or X Options
2. Cannot be combined with B, P or Y2 Options
3. Cannot be combined with GZ, H, l1, l2, K, W or Y1 Options
4. Not Avail. on 4-Pole Models
5. Not Available with L, T or LL options.
6. Not Available on hermetically sealed units.
* Sized to accommodate one L or T Auxiliary Switch
** Not available on On-Delay, Off-Delay (Double Head) model.
† Available with letter calibrated dials only. Upper end of time range may be twice the value shown
†† 120 cycles = 2 sec.
Our authorized distributors are more likely to maintain the following items in stock for immediate delivery..
Dimensions are shown for Dimensions are in inches over Specifications and availability www.tycoelectronics.com
1252 reference purposes only. (millimeters) unless otherwise subject to change. Technical support:
specified. Refer to inside back cover.
Catalog 1308242
Issued 3-03 AGASTAT
Ordering options – can only be orderd as factory installed options (Dimensions, where shown, are in inches.)
Gasket
Gasket
Transient
Protection
X – Panelmount Kit
Mounting hardware
included.
Dimensions are shown for Dimensions are in inches over Specifications and availability www.tycoelectronics.com
reference purposes only. (millimeters) unless otherwise subject to change. Technical support: 1253
specified. Refer to inside back cover.
Catalog 1308242
Issued 3-03 AGASTAT
2100 series
Miniature Electropneumatic
Timing Relay
Users should thoroughly review the technical data before selecting a product
part number. It is recommended that users also seek out the pertinent
approvals files of the agencies/laboratories and review them to ensure the
product meets the requirements for a given application.
Dimensions are shown for Dimensions are in inches over Specifications and availability www.tycoelectronics.com
1254 reference purposes only. (millimeters) unless otherwise subject to change. Technical support:
specified. Refer to inside back cover.
Catalog 1308242
Issued 3-03 AGASTAT
Outline Dimensions for Industrial Models (Dimensions in inches. Multiply by 25.4 to obtain millimeters.)
Our authorized distributors are more likely to maintain the following items in stock for immediate delivery..
None at present.
Dimensions are shown for Dimensions are in inches over Specifications and availability www.tycoelectronics.com
reference purposes only. (millimeters) unless otherwise subject to change. Technical support: 1255
specified. Refer to inside back cover.
Catalog 1308242
Issued 3-03 AGASTAT
Specifications for MIL-Spec and Hermetically Sealed Models
Dielectric: In accordance with specification MIL-R-
6106E (ASG). Also withstands 1,000 Volts RMS at
60 Hz between non-connected terminals. Agastat
timing relays
Other: Agastat Miniature Timing Relays also perform to
conform to applicable Mil-Spec. requirements military
covering: specifications
Moisture Ozone in Patriot
Humidity Sunshine missiles.
Sand/Dust Acoustic Noise
Salt Spray Prolonged Storage
Outline Dimensions for MIL-Spec and Hermetically Sealed Models (In inches. Multiply by 25.4 for millimeters).
8 pin solder
8 pin solder hook or MS/AN
hook or MS/AN Connector
Connector
Our authorized distributors are more likely to maintain the following items in stock for immediate delivery..
None at present.
Dimensions are shown for Dimensions are in inches over Specifications and availability www.tycoelectronics.com
1256 reference purposes only. (millimeters) unless otherwise subject to change. Technical support:
specified. Refer to inside back cover.