Getting Started

3.3 Matching the Control Voltage for the Binary Inputs and
Inserting the Buffer Battery

Control voltage

Warning!
Only one jumper may be fitted per binary input.

When delivered, the binary inputs of the EAZ and D-CPU modules in the central unit,
and the EFE or EFE_10 modules in the bay units, are configured for 220 V rated
control voltage.
For each binary input, different switching thresholds can be selected. This is done on
the central unit by means of 3 jumpers on the EAZ module and 4 jumpers on the D-
CPU module, and in the bay units by 3 jumpers each on the EFE or EFE_10 modules.

Central unit

Warning!
Dangerous voltages may be present inside the device!
Make sure to switch the auxiliary voltage off before opening the front panel.

To change the rated control voltages of the binary inputs in the central unit:
‰ Open the front panel. The location of the EAZ and D-CPU module is shown in
Figure 2-2, page 18.
‰ Remove the front plug connectors X3, X4, X5 on the D-CPU module
(Figure 3-2, page 36).
‰ Press down the locking bolt of the modules at the bottom guide rail.
‰ Use the extraction handle (included in the delivery) to pull out the module.
‰ Change the rated control voltages for the binary inputs of the EAZ module as
desired by relocating the jumpers (shown in Figure 3-1, page 35 and Table 3-1,
page 35).
‰ Change the rated control voltages for the binary inputs of the
D-CPU module by relocating the jumpers (shown in Figure 3-2, page 36 and Table
3-2, page 36).
To insert the buffer battery into the central unit:
‰ Press the battery firmly into its snap-in holder (see Figure 3-2, page 36) on the D-
CPU module. Observe the correct battery polarity!

34 7SS52 V4 Manual
E50410-A0012-U501-A4-7691-4
Matching the Control Voltage for the Binary Inputs and Inserting the Buffer Battery

Figure 3-1 Location of the jumpers on the EAZ module (central unit)

Table 3-1 Control voltage for the binary inputs on the EAZ (central unit) in relation to the
fitted jumper

Control voltage setting

Name 24 V 60 V 110 V 220 V

BI1 to BI5 (on the D-CPU module, Table 3-2, page 36)

BI6 X31 X21 X11 -

BI7 X32 X22 X12 -

BI8 X33 X23 X13 -

BI9 X34 X24 X14 -

BI10 X35 X25 X15 -

BI1 X36 X26 X16 -

BI12 X37 X27 X17 -

7SS52 V4 Manual 35
E50410-A0012-U501-A4-7691-4
Getting Started

Figure 3-2 Location of the jumpers and the buffer battery on the D-CPU module (central unit)

Table 3-2 Control voltage for the binary inputs on the D-CPU module (central unit) in
relation to the fitted jumper

Connector Binary Jumper


inputs
24 V 60 V 110 V 220V
X20, X21 BI1 1, 1 2, 2 3, 3 4, 4
X22, X23 BI2 1, 1 2, 2 3, 3 4, 4
X24, X25 BI3 1, 1 2, 2 3, 3 4, 4
X26, X27 BI4 1, 1 2, 2 3, 3 4, 4
X28, X29 BI5 1, 1 2, 2 3, 3 4, 4
BI6 to BI12 (on the EAZ module, Table 3-1, page 35)

36 7SS52 V4 Manual
E50410-A0012-U501-A4-7691-4
Matching the Control Voltage for the Binary Inputs and Inserting the Buffer Battery

Bay unit 7SS523

Warning!
Dangerous voltages may be present inside the device!
Make sure to switch the auxiliary voltage off before opening the front panel.

To change the rated control voltages of the binary inputs in a bay unit:
‰ Open the front panel. The location of the EFE module is shown in Figure 2-4, page
21.
‰ Remove the plug connector X1 to the front plate on the EFE module (Figure 3-3,
page 37) and pull out the module.
‰ Change the rated control voltages of the binary inputs to the desired settings, see
Figure 3-3, page 37 and Table 3-3, page 38.
To insert the buffer battery into the bay unit:
‰ Press the battery firmly into its snap-in holder (see Figure 2-4, page 21) on the PFE
module. Observe the correct battery polarity! The polarity is marked on the back
of the board.

EFE

Unit bus plug connector


Figure 3-3 Location of the jumpers on the EFE module (bay unit 7SS523)

7SS52 V4 Manual 37
E50410-A0012-U501-A4-7691-4
Getting Started

Table 3-3 Control voltage for the binary inputs on the EFE (bay unit) in relation to the fitted
jumper

Control voltage setting


Name 24 V 60 V 110 V 220 V

BI 1 X37 X36 X35 -


BI 2 X40 X39 X38 -
BI 3 X43 X42 X41 -
BI 4 X46 X45 X44 -
BI 5 X49 X48 X47 -
BI 6 X52 X51 X50 -
BI 7 X55 X54 X53 -
BI 8 X58 X57 X56 -
BI 9 X61 X60 X59 -
BI 10 X64 X63 X62 -
BI 11 X67 X66 X65 -
BI 12 X70 X69 X68 -
BI 13 X73 X72 X71 -
BI 14 X76 X75 X74 -
BI 15 X79 X78 X77 -
BI 16 X82 X81 X80 -
BI 17 X85 X84 X83 -
BI 18 X88 X87 X86 -
BI 19 X91 X90 X89 -
BI 20 X94 X93 X92 -

38 7SS52 V4 Manual
E50410-A0012-U501-A4-7691-4
Matching the Control Voltage for the Binary Inputs and Inserting the Buffer Battery

Bay unit 7SS525

Warning!
Dangerous voltages may be present inside the device!
Make sure to switch the auxiliary voltage off before opening the front panel.

To change the rated control voltages of the binary inputs in a bay unit:
‰ Open the front panel. The location of the EFE_10 module is shown in Figure 2-5,
page 22.
‰ Remove the plug connector X1 to the front plate on the EFE_10 module (Figure 3-
4, page 39) and pull out the module.
‰ Change the rated control voltages of the binary inputs to the desired settings, see
Figure 3-4, page 39 and Table 3-4, page 40.
To insert the buffer battery into the bay unit:
‰ Press the battery firmly into its snap-in holder (see Figure 2-5, page 22) on the PFE/
SVW module. Observe the correct battery polarity! The polarity is marked on the
back of the board.

Figure 3-4 Location of the jumpers on the EFE_10 module (bay unit 7SS525)

7SS52 V4 Manual 39
E50410-A0012-U501-A4-7691-4
Getting Started

Table 3-4 Control voltage for the binary inputs on the EFE_10 (bay unit) in relation to the
fitted jumper

Control voltage setting


Name 24 V 60 V 110 V 220 V

BI 1 X37 X36 X35 -


BI 2 X40 X39 X38 -
BI 3 X43 X42 X41 -
BI 4 X46 X45 X44 -
BI 5 X49 X48 X47 -
BI 6 X52 X51 X50 -
BI 7 X55 X54 X53 -
BI 8 X58 X57 X56 -
BI 9 X76 X75 X74 -
BI 10 X79 X78 X77 -

40 7SS52 V4 Manual
E50410-A0012-U501-A4-7691-4