Professional Documents
Culture Documents
9181-34widc - Yidc Univ 8 28 13
9181-34widc - Yidc Univ 8 28 13
9181-34widc - Yidc Univ 8 28 13
9181-34WIDC/115
9181-34WIDCE/115
9181-34WIDC/24DC
9181-34WIDCE/24DC
9181-34YIDC/115
9181-34YIDCE/115
9181-34YIDC/24DC
9181-34YIDCE/24DC
9181-34IIDCE/115
9181-34IIDCE/24DC
Unitrol Electronics, Inc.
702 Landwehr Road
Northbrook, IL 60062
847-480-0115
techsupport@unitrol-electronics.com
www-unitrol-electronics.com
DIR/9181-34WIDC-YIDC UNIV.
Thank you for purchasing this Unitrol SOFT TOUCH system to be
mounted to your existing MFDC welding control. Please carefully
follow the directions to ensure that your welder operator will be
protected against pinch-point injury.
MODEL NUMBER: 9181-34
SERIAL NUMBER:
DATE OF MANUFACTURE:
SOLENOID VALVE VOLTAGE:
TESTED BY:
PACKED BY:
*When air is removed from the lower port of the welder cylinder
1
9181-34WIDC, 9181-34WIDCE, 9181-34YIDC, 9181-34YIDCE
PURPOSE: To prevent fingers (or other body parts) sustaining permanent injury between moving
resistance welder electrodes. This is especially important with welder operations that require small
parts to be hand loaded between electrodes that have a clearance of are more than ¼”.
2
9181-34WIDC, 9181-34WIDCE, 9181-34YIDC, 9181-34YIDCE
INSTALL pneumatic kit per drawing #1964D-1 on page 13 and color print provided in this kit.
This SOFT TOUCH kit replaces the original welder solenoid valve and flow regulators. The
only component that will remain is the original main pressure regulator.
Be sure that only the components shown on this drawing are installed. Remove any other
components such as flow control valves, etc. that may have been originally installed.
ROCKER ARM WELDERS: There are special considerations for ROCKER ARM welders:
1. If the moving upper welder arm is very long (over 24”), leave the
flow control valve in the upper port of the cylinder as shown on
page 13. This will prevent the arm from slamming down at the
start of each weld sequence.
2. The back of the air cylinder piston typically has only a small area
exposed to incoming air to start moving the cylinder until it
breaks away from the bottom position. This means that the very
low SOFT TOUCH air psi introduced into the bottom port of the
cylinder acting on this small area will not be enough to start
moving the cylinder. Install Linoleum or other material washer as
shown on page 13 to provide a larger area at the start of each
stroke.
ACTION: When 5-way solenoid valve SVL is energized, air is exhausted from the back side of the
cylinder, and low-pressure air is sent to the top of the cylinder to close the electrodes under low
force. If the SOFT TOUCH sensor board detects continuity, relay contacts connected to the
welder’s pressure switch or level 2 terminals will close, and SVH valve will be energized (SVL
remains energized). This will shift the quick exhaust valve and put full weld force on the
electrodes.
4
9181-34WIDC, 9181-34WIDCE, 9181-34YIDC, 9181-34YIDCE
5
9181-34WIDC, 9181-34WIDCE, 9181-34YIDC, 9181-34YIDCE
a. Wire the low-pressure solenoid SVL to terminals #10 and #11 on TS1.
b. Wire the high-pressure solenoid SV0 (5 WAY) to terminals SV0 and TS3 (12) on the power
chassis.
c. Wire the TIP DRESS switch to terminals 15 and 16.
2. CONNECTING SENSOR WIRES: Connect wires from the welder transformer
secondary (any point), as shown on page 7 or 8, to the SOFT TOUCH terminal marked TO
WELDER SECONDARY. The order of connection is not important. Ideally this connection should
be done on copper parts that do not move. Two blue wires have been provided in this kit. Cut any
excess wire off for a clean installation.
3. CONNECTING POWER WIRES:
a. For 115V kits (with /115 at the end of the model number), see page 7 for
connection terminals of incoming 115VAC power and solenoid control wire
from your welder control transformer.
i. Be sure that the common wire from your existing control’s transformer is connected
to the terminal marked N.
ii. Be sure that the “hot” wire (voltage that is sent through switches to turn on solenoid
valves) is connected to the terminal marked L.
iii. Be sure that the wire connected to terminal 9 is the high (not neutral) wire that was
originally connected to the welder solenoid valve.
b. For 24DC kits (with /24DC at the end of the model number), see page 8 for
connection terminals of incoming 24VDC and 115VAC power from your
welder control.
i. Be sure that the + voltage is on the + terminal and the – voltage is on the – terminal.
ii. Be sure that the wire connected to terminal 9 is the + (not -) wire that was originally
connected to the welder solenoid valve.
iii. The order of connection of the 115V power to the terminal is not important.
4. Connecting control wires: Connect wires from terminals #6 and #7 (order is not
important) to the welding control. These wires are connected to a relay on the TS3 board that will
CLOSE when continuity has been detected. They can be connected in two ways:
a. On welders that have a PRESSURE SWITCH input terminal, connect these two wires and
remove any factory jumper on these terminals. This is the preferred method of hookup.
b. On welders that have a dual level initiation terminal (ie. closing first level brings electrodes
together; closing of second level starts the welder through the welding sequence), connect
these wires to close the second level of initiation.
Use the TIP DRESS switch to turn the valves on and off for this adjustment.
7
9181-34WIDC, 9181-34WIDCE, 9181-34YIDC, 9181-34YIDCE
8
9181-34WIDC, 9181-34WIDCE, 9181-34YIDC, 9181-34YIDCE
9
9181-34WIDC, 9181-34WIDCE, 9181-34YIDC, 9181-34YIDCE
10
9181-34WIDC, 9181-34WIDCE, 9181-34YIDC, 9181-34YIDCE
INITIAL TUNING OF
SOFT TOUCH SENSOR BOARD
Before starting this procedure, locate the welder’s tap switch (if one is on your welder) and
move the selection handle from lowest to highest number 10 times to clean the contacts on
this switch. Then leave it on the HIGHEST tap switch position that will be used in your
production.
Also be sure that the 2 or 3 plug-in relays on the TS3 SOFT TOUCH sensor board are fully
pushed into their sockets.
1. Turn the welding control ON and be sure that the green indicator is glowing on the new SOFT
TOUCH board.
2. SETTING THE SOFT TOUCH SENSOR BOARD WITH OPEN ELECTRODES:
a. Connect the positive lead of a digital voltmeter to terminal #TP4 and the negative lead on
#TP1 (GND) on the TS3 TOUCH SENSOR board. It is important that you observe the +
and – connection to your meter. You will be reading DC volts under 5V.
b. If the welder has a tap switch, set it to the highest number and be sure the electrodes are
not touching (electrodes open).
c. Locate the multi-turn blue potentiometer marked mounted just above the transformer on
this board.
d. Turn this potentiometer until the meter shows approximately 4.0 V. The potentiometer is a
20-turn style. Turn clockwise to increase, and counterclockwise to decrease. When it
reaches the maximum value, turning any further will not result in voltage changes and a
soft click will be heard every turn.
i. Note that it if you are lowering the voltage it may take many turns before you see
any drop in the reading. This is normal.
ii. Drifting of this reading is normal and reflects changes in incoming line voltage. On
some welders with very low open electrode input voltages you will not be able to go
any higher than 3.50 volts. This is OK for operation. See the trouble shooting chart
on page 13 if you cannot get this voltage to rise anywhere near this voltage.
e. Move the negative lead of the digital voltmeter from TP1 to TP5. Leave the positive lead on
TP4.
11
9181-34WIDC, 9181-34WIDCE, 9181-34YIDC, 9181-34YIDCE
f. Locate the other blue multi-turn potentiometer marked R7 on the right side of the board.
Turn this pot until the value shown on the meter is approximately +1.0 V. Note that this
reading can be positive (+) or negative (-). If it is negative, continue to turn the
potentiometer to lower the negative reading until you cross over 0 volts. The reading will
now start climbing positive to the required approximate +1.0 V reading.
g. At this time the YELLOW LD1 on the outside of the cabinet (back of this board) should be
flashing slowly.
If you do not read voltage of at least +0.8V (800mv) at these test points, see TROUBLE
SHOOTING procedure on page 13. The system will not operate correctly without this
reading.
h. This setting should now work for all transformer tap positions.
IMPORTANT: After the welder has been making welds for about 15 minutes, check the
voltage at test points #4 and #5 as shown in step f above. If the voltage being read has
drifted lower than 0.700V (700 mv), readjust potentiometer R7 to bring it back up to
about +1,0V. Some drifting is normal and follows the change in the welder transformer
as the windings heat up and also as line voltage changes.
i.
DRIFTING VALUES: If the voltage readings with open electrodes at these test points
changes more than 0.5V (500 mv), rotate the welder’s transformer switch from low to high
number setting about 10 times to clean the contacts in this switch. Dirty tap switches can
cause drifting of values in system.
This reading will change if the welder transformer tap switch is moved to a new location.
For most welders, doing the original setting with the transformer tap at the HIGHEST
position that will be used in production should provide a setting that will work with the
lower transformer tap switch setting positions.
12
9181-34WIDC, 9181-34WIDCE, 9181-34YIDC, 9181-34YIDCE
13
9181-34WIDC, 9181-34WIDCE, 9181-34YIDC, 9181-34YIDCE
14
9181-34WIDC, 9181-34WIDCE, 9181-34YIDC, 9181-34YIDCE
15
9181-34WIDC, 9181-34WIDCE, 9181-34YIDC, 9181-34YIDCE
16
9181-34WIDC, 9181-34WIDCE, 9181-34YIDC, 9181-34YIDCE
See chart on the next page for trouble shooting guide for flash codes.
17
9181-34WIDC, 9181-34WIDCE, 9181-34YIDC, 9181-34YIDCE
FLASH
CODE CAUSE WHAT TO CHECK OR DO
A Normal Standby condition -
Normal condition after turn-on of
B low force SV1, waiting for sensor -
to detect metal
Normal condition if continuity
C was detected in time, and -
electrodes are still closed
1. Time set on DIP switch not 1. Increase DIPswitch time. Remember that this
long enough for cylinder time is the addition of all switches pushed
stroke down
2. Dirt on electrodes or part 2. Clean electrodes or check part being welded.
between electrodes
3. Force between electrodes 3. Increase force by:
too low and good continuity a. Raising ADVANCE PRESSURE on
cannot be established 9181-34YIDC… controls
D between electrodes.
b. Lowering ADVANCE PRESSURE on
9181-34WIDC… controls.
4. Settings on TS3 board not 4. Go through settings starting on page 9.
correct
5. TS3 board not operating 5. Faulty TS3 board. Have board repaired or
correctly replaced.
1. SOFT TOUCH not adjusted 1. Adjust SOFT TOUCH potentiometer with tips
properly open and transformer on HIGH tap, until
voltage at TP4 (+) and TP5 (-) test points
reads about +1.000 VDC
E
2. No voltage input on sensor 2. Sensor wires disconnected at transformer or
input at terminals #4 and #5 SOFT TOUCH board, transformer secondary
on SOFT TOUCH board shorted (insulation missing, etc.), or
transformer primary disconnected from SCR
or L2
18
9181-34WIDC, 9181-34WIDCE, 9181-34YIDC, 9181-34YIDCE
During normal spot welding, the high force of the electrodes is usually enough to break the oxide
surface coating and make contact through the electrodes. These materials typically have a lot of
expulsion when welded confirming that the surface must be “blown away” at the early part of each
weld.
But the low voltage and low force of the SOFT TOUCH process will not always be able to establish a
continuity path between the electrodes to let this function work.
ALTERNATIVE SENSOR INSTALLATION: Where these partially insulated materials are welded on
this machine, the only way the system will operate is with the use of a LIMIT SWITCH or PROXIMITY
SWITCH as the main sensor. The limit or prox switch will be mounted and adjusted in such a way
that it will close when the electrodes are less than ¼” apart. While this is not as elegant as the
continuity sensing of the SOFT TOUCH board, it will still provide protection in the pinch point area
between the electrodes if set up correctly. Note that if the limit or prox switch is closed before the
welding electrodes start to close, the system will not allow any movement and will display the fault.
A keylock selector switch can be installed to switch between the SOFT TOUCH sensor board on
conductive material, and limit switch operation on poor conductive material. A SOFT TOUCH
BYPASS kit is also available the will maintain the low-pressure advance but not utilize the continuity
testing when working with insulated material. Contact the Unitrol service department for more
information on these two choices.
19
9181-34WIDC, 9181-34WIDCE, 9181-34YIDC, 9181-34YIDCE
DRIFTING VALUES: If you have successfully set the SOFT TOUCH voltages, and then a
while later you have to readjust the board, it might also indicate a dirty tap switch on the
welder’s transformer. Because this system is conducting millivolts and milliamps of current
during the continuity detection sequence, bad transformer tap switch contacts can cause
large changes of voltage present at the welder secondary and cause the SOFT TOUCH
sensor board to have greatly changing values when the electrodes are open.
In this case, voltages read at test points #4 and #5 with open electrodes will change more
than 0.5V (500 mv).
To eliminate this problem, rotate the welder’s transformer switch from low to high
number setting about 10 times to clean the contacts in this switch.
20
UNITROL ELECTRONICS, INC.
702 LANDWEHR ROAD
NORTHBROOK, IL 60062
847-480-0115
techsupport@unitrol-electronics.com