The four-times rule, the various offset rules, and the other rules we’ve discussed so far have all been for obstructions that are comparatively small and relatively close to the sprinkler deflectors. But what about sprinkler spacing for very large obstructions that might be located further away?
Chapter 11 of NFPA 13 has—you guessed it—special rules for these
scenarios. When an obstruction is more than 4 feet wide, extended coverage sprinklers cannot be arranged to throw water around the obstacle, no matter how far down the obstruction is. Flanking the obstruction will not solve the problem either. Instead, sprinklers must be installed underneath the obstruction (11.2.5.3.2). This applies to sidewall sprinklers, as well (11.3.6.3.2).
The only exception to this mandate is when obstructions do not exceed
4 feet and are lower than 18 inches from the sprinkler deflector. In this case, an adequate spray pattern will develop without placing sprinklers beneath the obstruction (11.2.5.3.2, 11.3.6.3).
Unfortunately, it’s possible for adjacent sprinklers to wet and cool
sprinklers installed under obstructions, especially if the obstruction has open grating or is a round duct. And this spray may cool those lower sprinklers and delay activation.
To ensure the lower sprinklers operate as intended, the heads installed
under open grating or round ducts should have the same kind of water shield (baffle) typically found on intermediate-level in-rack sprinklers (11.2.5.3.4-5). Sometimes, fire sprinklers must be installed under obstructions. When these obstructions are open grating decks (such as those found in warehouses) or round ducting, you need to use fire sprinklers similar to intermediate-level in-rack sprinklers. That is, they must be equipped with a water shield, like this Viking sprinkler, to protect them from the cooling spray of nearby sprinklers.