r2b p3 206 02 P HD 00200 - Datasheets For Control Valve, Globe, U 21000 - Rev.1

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 377

PHASE II OF REFINERY IN DOS

BOCAS (FCC)

DATASHEETS FOR CONTROL Page 1 / 377


Doc. TITLE
VALVE, GLOBE, U-21000 Rev. 1

Contract Doc. No. R2B-P3-206-02-P-HD-00200 Contract No. PTI-ID-O-004-2-2020


Contractor
Contractor Doc. No. SO6625-EK0E-TDS-P3210200 Job. No.
SO6625

DATASHEETS FOR
CONTROL VALVE, GLOBE
U-21000

BETWEEN

PTI-Infraestructura de Desarrollo, S.A. de C.V.

AND

Samsung Ingeniería Manzanillo, S.A. de C.V. /


Asociados Constructores DBNR, S.A. de C.V.

“COMPLEMENTARY ENGINEERING, PROCUREMENT, CONSTRUCTION AND SUPPORT


DURING TESTS AND STARTUP OF THE CATALYTIC CRACKING FCC PLANT FOR THE
REFINERY IN DOS BOCAS, PARAÍSO, TABASCO” (PHASE II)

Contract No. PTI-ID-O-004-2-2020

1 05/09/2022 ISSUED FOR CONSTRUCTION DHA SBP KHL

0 08/11/2021 ISSUED FOR CONSTRUCTION DHA JHP KHL

C 04/12/2021 ISSUED FOR REVIEW DHA JHP KHL

B 05/28/2020 ISSUED FOR REVIEW DHK JHP KHL

A 12/19/2019 ISSUED FOR REVIEW HHL JHP KHL

Rev. Date Description Prepared by Reviewed by Approved by

This document, including any patented or patentable features, embodies confidential information of Samsung Ingeniería Manzanillo, S.A. de
C.V. and its use is conditioned upon the user’s agreement not to reproduce the document in whole or in part. Nor the material described
thereon nor to use the document for any purpose other than specifically permitted in writing by Samsung Ingeniería Manzanillo, S.A. de. C.V.
PHASE II OF REFINERY IN DOS
BOCAS (FCC)

DATASHEETS FOR CONTROL Page 2 / 377


Doc. TITLE
VALVE, GLOBE, U-21000 Rev. 1

Contract Doc. No. R2B-P3-206-02-P-HD-00200 Contract No. PTI-ID-O-004-2-2020


Contractor
Contractor Doc. No. SO6625-EK0E-TDS-P3210200 Job. No.
SO6625

REVISION HISTORY
Rev DATE DESCRIPTION

A 12/19/2019 Initial Issued For Review

B 05/28/2020 Updated according to PTI-ID comments and TBE

C 04/12/2021 Issued For Review

0 08/11/2021 Issued For Construction

1 05/09/2022 Issued For Construction

* Notes:

This page records all revisions on the procedures


Requisition number: R2B-P3-206-02-P-MR-00200 P. O. number:

Rev. No. Item Number Tag Number Instrument Type Page No.
1 1 FV -21001 CONTROL VALVE - FF S1
1 2 FV -21002 CONTROL VALVE - FF S2
1 3 FV -21007 CONTROL VALVE - FF S3
1 4 FV -21008 CONTROL VALVE - FF S4
1 5 FV -21009 CONTROL VALVE - FF S5
1 6 FV -21010 CONTROL VALVE - FF S6
1 7 FV -21011 CONTROL VALVE - FF S7
1 8 FV -21012 CONTROL VALVE - FF S8
1 9 FV -21027 CONTROL VALVE - FF S9
1 10 FV -21028 CONTROL VALVE - FF S10
1 11 FV -21029 CONTROL VALVE - FF S11
1 12 FV -21030 CONTROL VALVE - FF S12
1 13 FV -21031 CONTROL VALVE - FF S13
1 14 FV -21032 CONTROL VALVE - FF S14
1 15 FV -21033 CONTROL VALVE - FF S15
1 16 FV -21034 CONTROL VALVE - FF S16
1 17 FV -21035 CONTROL VALVE - FF S17
1 18 FV -21039 CONTROL VALVE - FF S18
1 19 FV -21040 CONTROL VALVE - FF S19
1 20 FV -21041 CONTROL VALVE - FF S20
1 21 FV -21042 CONTROL VALVE - FF S21
1 22 FV -21043 CONTROL VALVE - FF S22
1 23 FV -21044 CONTROL VALVE - FF S23
1 24 FV -21045 CONTROL VALVE - FF S24
1 25 FV -21046 CONTROL VALVE - FF S25
1 26 FV -21047 CONTROL VALVE - FF S26
1 27 FV -21052 CONTROL VALVE - FF S27
1 28 FV -21053 CONTROL VALVE - FF S28
1 29 FV -21055 CONTROL VALVE - FF S29
1 30 FV -21056 CONTROL VALVE - FF S30
1 31 FV -21057 CONTROL VALVE - FF S31
1 32 FV -21063 CONTROL VALVE - FF S32
1 33 FV -21064 CONTROL VALVE - FF S33
1 34 FV -21065 CONTROL VALVE - FF S34
1 35 FV -21066 CONTROL VALVE - FF S35
1 36 FV -21067 CONTROL VALVE - FF S36
1 37 FV -21068 CONTROL VALVE - FF S37
1 38 FV -21070 CONTROL VALVE - FF S38
1 39 FV -21071 CONTROL VALVE - FF S39
1 40 FV -21072 CONTROL VALVE - FF S40
1 41 FV -21073A CONTROL VALVE - FF S41
1 42 FV -21074 CONTROL VALVE - FF S42
1 43 FV -21081 CONTROL VALVE - FF S43
1 44 FV -21087 CONTROL VALVE - FF S44
1 45 FV -21088 CONTROL VALVE - FF S45
1 46 FV -21101 CONTROL VALVE - FF S46
1 47 FV -21102 CONTROL VALVE - FF S47
1 48 FV -21103 CONTROL VALVE - FF S48
1 49 FV -21108 CONTROL VALVE - FF S49
1 50 FV -21111B CONTROL VALVE - FF S50
1 51 FV -21115 CONTROL VALVE - FF S51
1 52 FV -21116 CONTROL VALVE - FF S52
1 53 FV -21120 CONTROL VALVE - FF S53
1 54 FV -21124 CONTROL VALVE - FF S54
1 55 FV -21125 CONTROL VALVE - FF S55
1 56 FV -21133 CONTROL VALVE - FF S56

Domain: DBNRPK3 Plant: R2B_P3


Area: 21000 Unit: 21000
1 DHA 4/22/2022 ISSUED FOR CONSTRUCTION Binder Package
0 DHA 8/11/2021 ISSUED FOR CONSTRUCTION Formal issue Date: 4/22/2022
C DHA 4/12/2021 ISSUED FOR REVIEW Instrument Specification List
B DHK 5/28/2020 ISSUED FOR REVIEW FCC CV Globe
A HHL 12/19/2019 ISSUED FOR REVIEW Page I-1 of 3
No. By Date Description Doc. No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Requisition number: R2B-P3-206-02-P-MR-00200 P. O. number:

Rev. No. Item Number Tag Number Instrument Type Page No.
1 57 FV -21134 CONTROL VALVE - FF S57
1 58 FV -21139 CONTROL VALVE - FF S58
1 59 FV -21142 CONTROL VALVE - FF S59
1 60 FV -21143 CONTROL VALVE - FF S60
1 61 FV -21201 CONTROL VALVE - FF S61
1 62 FV -21208 CONTROL VALVE - FF S62
1 63 FV -21213 CONTROL VALVE - FF S63
1 64 FV -21214 CONTROL VALVE - FF S64
1 65 FV -21218 CONTROL VALVE - FF S65
1 66 FV -21229 CONTROL VALVE - FF S66
1 67 FV -21234 CONTROL VALVE - FF S67
1 68 FV -21235 CONTROL VALVE - FF S68
1 69 FV -21236 CONTROL VALVE - FF S69
1 70 FV -21237 CONTROL VALVE - FF S70
1 71 FV -21402 CONTROL VALVE - FF S71
1 72 FV -21403 CONTROL VALVE - FF S72
1 73 FV -21408 CONTROL VALVE - FF S73
1 74 FV -21409 CONTROL VALVE - FF S74
1 75 FV -21410 CONTROL VALVE - FF S75
1 76 FV -21411 CONTROL VALVE - FF S76
1 77 FV -21414 CONTROL VALVE - FF S77
1 78 FV -21415 CONTROL VALVE - FF S78
1 79 FV -21417 CONTROL VALVE - FF S79
1 80 FV -21420 CONTROL VALVE - FF S80
1 81 FV -21422 CONTROL VALVE - FF S81
1 82 FV -21424 CONTROL VALVE - FF S82
1 83 FV -21503 CONTROL VALVE - FF S83
1 84 FV -21607 CONTROL VALVE - FF S84
1 85 HV -21026 CONTROL VALVE - FF S85
1 86 HV -21109 CONTROL VALVE - FF S86
1 87 FV -21076 CONTROL VALVE - FF S87
1 88 LV -21126 CONTROL VALVE - FF S88
1 89 LV -21200 CONTROL VALVE - FF S89
1 90 LV -21205 CONTROL VALVE - FF S90
1 91 LV -21214 CONTROL VALVE - FF S91
1 92 LV -21218 CONTROL VALVE - FF S92
1 93 FV -21243 CONTROL VALVE - FF S93
1 94 LV -21404 CONTROL VALVE - FF S94
1 95 LV -21410 CONTROL VALVE - FF S95
1 96 LV -21502 CONTROL VALVE - FF S96
1 97 LV -21503 CONTROL VALVE - FF S97
1 98 LV -21504 CONTROL VALVE - FF S98
1 99 LV -21505 CONTROL VALVE - FF S99
1 100 LV -21601 CONTROL VALVE - FF S100
1 101 LV -21602 CONTROL VALVE - FF S101
1 102 LV -21603 CONTROL VALVE - FF S102
1 103 PDV -21010 CONTROL VALVE - FF S103
1 104 PDV -21011 CONTROL VALVE - FF S104
1 105 PDV -21065 CONTROL VALVE - FF S105
1 106 PDV -21404 CONTROL VALVE - FF S106
1 107 PV -21003 CONTROL VALVE - FF S107
1 108 PV -21043 CONTROL VALVE - FF S108
1 109 PV -21044 CONTROL VALVE - FF S109
1 110 PV -21045 CONTROL VALVE - FF S110
1 111 PV -21046A CONTROL VALVE - FF S111
1 112 PV -21046B CONTROL VALVE - FF S112

Domain: DBNRPK3 Plant: R2B_P3


Area: 21000 Unit: 21000
1 DHA 4/22/2022 ISSUED FOR CONSTRUCTION Binder Package
0 DHA 8/11/2021 ISSUED FOR CONSTRUCTION Formal issue Date: 4/22/2022
C DHA 4/12/2021 ISSUED FOR REVIEW Instrument Specification List
B DHK 5/28/2020 ISSUED FOR REVIEW FCC CV Globe
A HHL 12/19/2019 ISSUED FOR REVIEW Page I-2 of 3
No. By Date Description Doc. No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Requisition number: R2B-P3-206-02-P-MR-00200 P. O. number:

Rev. No. Item Number Tag Number Instrument Type Page No.
1 113 PV -21073 CONTROL VALVE - FF S113
1 114 PV -21200A CONTROL VALVE - FF S114
1 115 PV -21200B CONTROL VALVE - FF S115
1 116 PV -21408 CONTROL VALVE - FF S116
1 117 PV -21416 CONTROL VALVE - FF S117
1 118 PV -21520 CONTROL VALVE - FF S118
1 119 PV -21522B CONTROL VALVE - FF S119
1 120 PV -21636 CONTROL VALVE - FF S120
1 121 PV -21719 CONTROL VALVE - FF S121
1 122 TDV -21507A CONTROL VALVE - FF S122
1 123 TV -21612 CONTROL VALVE - FF S123
1 124 PV -21522A CONTROL VALVE - FF S124
1 125 FV -21204 - Added CONTROL VALVE - FF S125

Domain: DBNRPK3 Plant: R2B_P3


Area: 21000 Unit: 21000
1 DHA 4/22/2022 ISSUED FOR CONSTRUCTION Binder Package
0 DHA 8/11/2021 ISSUED FOR CONSTRUCTION Formal issue Date: 4/22/2022
C DHA 4/12/2021 ISSUED FOR REVIEW Instrument Specification List
B DHK 5/28/2020 ISSUED FOR REVIEW FCC CV Globe
A HHL 12/19/2019 ISSUED FOR REVIEW Page I-3 of 3
No. By Date Description Doc. No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
1 Tag No. FV -21001
2 Service PA TO FA001
3 P&ID No. Line No. R2B-P3-206-02-A-DTI-00055 1-1/2"-P-210421-B1A2-N
4 Area Classification Ingress Protection CLASS 1 DIV 2 Gr. B ,C&D, T3 NEMA 4X
GENERAL 5 Ambient Temperature: Unit Min. Max. °C 10 48
6 Allowable Sound dBA Tightness Requirement <85 ANSI IV (standard)
7 Available Air Supply Pressure Unit Min. Max. kgf/cm²-g 4.2 8.0
8 Electric Connection Pneum. Connection 1/2” NPT (F) 1/4” NPT (F)
9 Power Failure Position FO
10 Line Size and Schedule Sch. Outlet Line Sch. 1 1/2 in 160 2" 160
PIPE
11 Line Class Rating Pipe Material B1A2 150# A106 GR.B, SMLS
LINE
12 Pipe Insulation Thickness Corrosion Allowance N N/A 3.2mm
13 Fluid State Phase Plant Air Gas/Vapor Single Phase
14 Sour Service Special Condition N/A N/A
15 Flow Rate Units Min. Nor. Max. Nm³/h 272 272 272
16 Inlet Pressure Units Min. Nor. Max. kgf/cm²-g 7.2 7.17 6.67
17 Pressure Drop Units Min. Nor. Max. kgf/cm² 4.38 4.35 3.85
18 Inlet Temperature Units Min. Nor. Max. °C 40 40 40
PROCESS 19 Density Units Min. Nor. Max. kg/m³
CONDITIONS 20 Viscosity Units Min. Nor. Max. cP 0.019 0.019 0.019
21 Molecular Weight (MW) Specific Gravity @ Oper. 28.85
22 Spec. Heat Ratio (Cp/Cv) Compressibility (Z) 1.392 0.997
23 Vapor Pressure (Liq.) Cavitation or Flashing kgf/cm²-a N/A
24 Critical Pressure (Liq) Flash (wt%) kgf/cm²-a
25 Design Pressure Min. Max. -1.033 kgf/cm²-g 10.5 kgf/cm²-g
26 Design Temperature Min. Max. 10 °C 80 °C
27 Max.Shutoff DP Solid % 10.5 kgf/cm²
28 Calculated Cv Units Min. Nor. Max. Cv 2.91 2.92 3.13
CALCULATED
29 Travel Units Min. Nor. Max. % 79 79 81
RESULTS
30 Noise dBA @1m Units Min. Nor. Max. dBA 60 60 60
31 MFR Model FISHER EZ 56 MFR Model FISHER DVC6200F/SC-AD
32 Body Type Single Seat Globe 57 Signal: Inlet Outlet FF Protocol 0-2.8 kgf/cm2
33 Body Size Trim Size 1 in 1/2 in 58 Increase Signal Valve: DIRECT
34 End Connec.Size & Rating 1" 300# RF POSITIONER 59 Cam Characteristic LINEAR
35 Rated Cv Characteristic 4.91 EQ% 60 Bypass Gauges N/A YES
36 Body Material WCC Steel 61 Signal Fail. to Valve FO
BODY 37 Bonnet Type Material Plain WCC Steel 62 Electric Enclosure Ex ia IIC T5 , NEMA 4X
AND 38 Flow Direct. Flow Act. To Up FTO 63 MFR Model N/A N/A
TRIM 39 Packing Type Material Enviro Seal PTFE Carbon 64 Type Power N/A N/A
SOLENOID
40 Lubricator Isolat. Valve N/A N/A 65 When De-Enegr.Valve: N/A
VALVE
41 Guiding No. of Ports Post 1 66 Material Latcher N/A N/A
42 Trim Type Internal Design Micro Form Unbalanced 67 Electric Enclosure N/A
43 Rated Travel Leak Class 3/4 in ANSI IV 68 MFR Model N/A N/A
44 Plug/ Ball/ Disk Material S41600 SST 69 Type Quantity N/A N/A
45 Seat Material S41600 SST SWITCHES 70 Contacts / Rating N/A
46 Cage Stem Material N/A S31600 SST 71 Switching Position N/A
47 Gasket Material S31600 SST/Graphite 72 Electric Enclosure N/A
48 MFR Model FISHER 657 73 MFR Model FISHER 67CFR
49 Type Diaphragm Spring Return AIR SET 74 Set Pressure 4.2 kgf/cm2-g
50 Size Stroke Time 30i < 5 Sec 75 Filter Gauge 5 Micron min YES
ACTUATOR 51 Air Failure Valve: FO 76 Vol. Tank Booster NO NO
52 Handwheel Location N/A 77 Diffuser Lock-up NO NO
ACCESSORY
53 Mounting Position VERTICAL 78 Fire Safe Fireproof NO NO
54 Spring Range 0.4 - 2.4 kgf/cm2-g 79 Mech. Stop Quick Exa. NO NO
55 Include Pressure (Shutoff) 80 Hydro. Pressure YES
85 Vendor EMERSON 81 Leakage YES
PURCHASE TESTS
86 Manufacturer FISHER 82 Cryogenic N/A
87 Requisition No. R2B-P3-206-02-P-MR-00200 83 NACE Requirement N/A
88 Model No. EZ 84 PWHT Requirement N/A
Notes:

INSTRUMENT SPECIFICATION - CONTROL VALVE


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S1.1 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Fieldbus Device Data Sheet
Tag No.: FV -21001
Fieldbus Tag No.:

Service : PA TO FA001

Basic Fieldbus Function Blocks Segment Information


Analog Input Block (AI) 1 Number Device:
1 22
20 Execution (msec)
Discrete Input Block (DI) 4 Number Segment #: DFJB-21012
2 23
15 Execution Time
3 Bias/Gain Station (BG) 0 Execution (msec) 24 LAS Capable: Yes No
Manual Loader (ML) 0 Number 25 Device Current Draw (mA): 19
4
0 Execution (msec) Device Minimum Voltage: 9.
26
Analog Output Block (AO) 1 Number Device Capacitance: 5 nF
5 20 Execution (msec) Polarity-sensitive: Yes No
27
Discrete Output Block (DO) 1 Number Segment Terminator Location:
6 20 Execution (msec)
28
7 Control Selector (CS)
DD Revision: 3
PID,PI,I Controller (PID) 29
8
20 Execution (msec)
CFF Revision: 1.9
Ratio Station (RA) 30
9
P,PD Controller (PD) 0 Number
10 0 Execution (msec)

* Execution time in msec.

Advanced Function Blocks Notes:

11 Device Control (DC)

12 Output Splitter (OS)

13 Signal Characterizer (SC)

14 Lead Lag (LL)

15 Deadtime (DT)

16 Integrator(Totalizer) (IT)

17 Setpoint Ramp Generator (SPG)

18 Input Selector (IS)

19 Arithmetic (AR)

20 Timer (TMR)

21 Analog Alarm (AAL)

INSTRUMENT SPECIFICATION -FOUNDATION FIELDBUS


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S1.2 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Tag Number : FV -21001

1. In-Built surge protector is provided by vendor.

1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S1.3 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
1 Tag No. FV -21002
2 Service PA TO FA001
3 P&ID No. Line No. R2B-P3-206-02-A-DTI-00055 4"-P-210466-B1A2-N
4 Area Classification Ingress Protection CLASS 1 DIV 2 Gr. B ,C&D, T3 NEMA 4X
GENERAL 5 Ambient Temperature: Unit Min. Max. °C 10 48
6 Allowable Sound dBA Tightness Requirement <85 ANSI IV (standard)
7 Available Air Supply Pressure Unit Min. Max. kgf/cm²-g 4.2 8.0
8 Electric Connection Pneum. Connection 1/2” NPT (F) 1/4” NPT (F)
9 Power Failure Position FO
10 Line Size and Schedule Sch. Outlet Line Sch. 4 in STD 6" STD
PIPE
11 Line Class Rating Pipe Material B1A2 150# A106 GR.B, SMLS
LINE
12 Pipe Insulation Thickness Corrosion Allowance N N/A 3.2mm
13 Fluid State Phase Plant Air Gas/Vapor Single Phase
14 Sour Service Special Condition N/A N/A
15 Flow Rate Units Min. Nor. Max. Nm³/h 4040 4040 4040
16 Inlet Pressure Units Min. Nor. Max. kgf/cm²-g 7.2 7.12 6.62
17 Pressure Drop Units Min. Nor. Max. kgf/cm² 4.375 4.3 3.8
18 Inlet Temperature Units Min. Nor. Max. °C 40 40 40
PROCESS 19 Density Units Min. Nor. Max. kg/m³
CONDITIONS 20 Viscosity Units Min. Nor. Max. cP 0.019 0.019 0.019
21 Molecular Weight (MW) Specific Gravity @ Oper. 28.85
22 Spec. Heat Ratio (Cp/Cv) Compressibility (Z) 1.392 0.997
23 Vapor Pressure (Liq.) Cavitation or Flashing kgf/cm²-a N/A
24 Critical Pressure (Liq) Flash (wt%) kgf/cm²-a
25 Design Pressure Min. Max. -1.033 kgf/cm²-g 10.5 kgf/cm²-g
26 Design Temperature Min. Max. 10 °C 80 °C
27 Max.Shutoff DP Solid % 10.5 kgf/cm²
28 Calculated Cv Units Min. Nor. Max. Cv 53.6 54.2 58.2
CALCULATED
29 Travel Units Min. Nor. Max. % 48 48 52
RESULTS
30 Noise dBA @1m Units Min. Nor. Max. dBA 74 74 74
31 MFR Model FISHER ES 56 MFR Model FISHER DVC6200F/SC-AD
32 Body Type Single Seat Globe 57 Signal: Inlet Outlet FF Protocol 0-2.8 kgf/cm2
33 Body Size Trim Size 3 in 2 5/16 in 58 Increase Signal Valve: DIRECT
34 End Connec.Size & Rating 3" 300# RF POSITIONER 59 Cam Characteristic LINEAR
35 Rated Cv Characteristic 102 Linear 60 Bypass Gauges N/A YES
36 Body Material WCC Steel 61 Signal Fail. to Valve FO
BODY 37 Bonnet Type Material Plain WCC Steel 62 Electric Enclosure Ex ia IIC T5 , NEMA 4X
AND 38 Flow Direct. Flow Act. To Up FTO 63 MFR Model N/A N/A
TRIM 39 Packing Type Material Enviro Seal PTFE Carbon 64 Type Power N/A N/A
SOLENOID
40 Lubricator Isolat. Valve N/A N/A 65 When De-Enegr.Valve: N/A
VALVE
41 Guiding No. of Ports Cage 1 66 Material Latcher N/A N/A
42 Trim Type Internal Design Whisper I Unbalanced 67 Electric Enclosure N/A
43 Rated Travel Leak Class 1 1/8 in ANSI IV 68 MFR Model N/A N/A
44 Plug/ Ball/ Disk Material S41600 SST 69 Type Quantity N/A N/A
45 Seat Material S41600 SST SWITCHES 70 Contacts / Rating N/A
46 Cage Stem Material CB7Cu-1 SST S31600 SST 71 Switching Position N/A
47 Gasket Material S31600 SST/Graphite 72 Electric Enclosure N/A
48 MFR Model FISHER 657 73 MFR Model FISHER 67CFR
49 Type Diaphragm Spring Return AIR SET 74 Set Pressure 4.2 kgf/cm2-g
50 Size Stroke Time 46i < 8 Sec 75 Filter Gauge 5 Micron min YES
ACTUATOR 51 Air Failure Valve: FO 76 Vol. Tank Booster NO NO
52 Handwheel Location N/A 77 Diffuser Lock-up NO NO
ACCESSORY
53 Mounting Position VERTICAL 78 Fire Safe Fireproof NO NO
54 Spring Range 0.4 - 2.0 kgf/cm2-g 79 Mech. Stop Quick Exa. NO NO
55 Include Pressure (Shutoff) 80 Hydro. Pressure YES
85 Vendor EMERSON 81 Leakage YES
PURCHASE TESTS
86 Manufacturer FISHER 82 Cryogenic N/A
87 Requisition No. R2B-P3-206-02-P-MR-00200 83 NACE Requirement N/A
88 Model No. ES 84 PWHT Requirement N/A
Notes:

INSTRUMENT SPECIFICATION - CONTROL VALVE


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S2.1 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Fieldbus Device Data Sheet
Tag No.: FV -21002
Fieldbus Tag No.:

Service : PA TO FA001

Basic Fieldbus Function Blocks Segment Information


Analog Input Block (AI) 1 Number Device:
1 22
20 Execution (msec)
Discrete Input Block (DI) 4 Number Segment #: DFJB-21012
2 23
15 Execution Time
3 Bias/Gain Station (BG) 0 Execution (msec) 24 LAS Capable: Yes No
Manual Loader (ML) 0 Number 25 Device Current Draw (mA): 19
4
0 Execution (msec) Device Minimum Voltage: 9.
26
Analog Output Block (AO) 1 Number Device Capacitance: 5 nF
5 20 Execution (msec) Polarity-sensitive: Yes No
27
Discrete Output Block (DO) 1 Number Segment Terminator Location:
6 20 Execution (msec)
28
7 Control Selector (CS)
DD Revision: 3
PID,PI,I Controller (PID) 29
8
20 Execution (msec)
CFF Revision: 1.9
Ratio Station (RA) 30
9
P,PD Controller (PD) 0 Number
10 0 Execution (msec)

* Execution time in msec.

Advanced Function Blocks Notes:

11 Device Control (DC)

12 Output Splitter (OS)

13 Signal Characterizer (SC)

14 Lead Lag (LL)

15 Deadtime (DT)

16 Integrator(Totalizer) (IT)

17 Setpoint Ramp Generator (SPG)

18 Input Selector (IS)

19 Arithmetic (AR)

20 Timer (TMR)

21 Analog Alarm (AAL)

INSTRUMENT SPECIFICATION -FOUNDATION FIELDBUS


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S2.2 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Tag Number : FV -21002

1. In-Built surge protector is provided by vendor.

1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S2.3 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
1 Tag No. FV -21007
2 Service FA008 PA TO DC002
3 P&ID No. Line No. R2B-P3-206-02-A-DTI-00063 3"-AP-210070-T-A06T1-PP
4 Area Classification Ingress Protection CLASS 1 DIV 2 Gr. B ,C&D, T3 NEMA 4X
GENERAL 5 Ambient Temperature: Unit Min. Max. °C 10 48
6 Allowable Sound dBA Tightness Requirement <85 ANSI IV (standard)
7 Available Air Supply Pressure Unit Min. Max. kgf/cm²-g 4.2 8.0
8 Electric Connection Pneum. Connection 1/2” NPT (F) 1/4” NPT (F)
9 Power Failure Position FO
10 Line Size and Schedule Sch. Outlet Line Sch. 3 in STD 4" STD
PIPE
11 Line Class Rating Pipe Material T-A06T1 150# A106 GR.B, SMLS
LINE
12 Pipe Insulation Thickness Corrosion Allowance PP 50mm 1.6mm
13 Fluid State Phase Plant Air Gas/Vapor Single Phase
14 Sour Service Special Condition N/A N/A
15 Flow Rate Units Min. Nor. Max. Nm³/h 2014 2014 2215
16 Inlet Pressure Units Min. Nor. Max. kgf/cm²-g 7.63 6.781 6.185
17 Pressure Drop Units Min. Nor. Max. kgf/cm² 5.484 4.75 3.612
18 Inlet Temperature Units Min. Nor. Max. °C 40 157 157
PROCESS 19 Density Units Min. Nor. Max. kg/m³
CONDITIONS 20 Viscosity Units Min. Nor. Max. cP 0.019 0.019 0.019
21 Molecular Weight (MW) Specific Gravity @ Oper. 28.85
22 Spec. Heat Ratio (Cp/Cv) Compressibility (Z) 1.4 1.001
23 Vapor Pressure (Liq.) Cavitation or Flashing kgf/cm²-a N/A
24 Critical Pressure (Liq) Flash (wt%) kgf/cm²-a
25 Design Pressure Min. Max. -1.033 kgf/cm²-g 10.5 kgf/cm²-g
26 Design Temperature Min. Max. 10 °C 185 °C
27 Max.Shutoff DP Solid % 10.5 kgf/cm²
28 Calculated Cv Units Min. Nor. Max. Cv 24.4 31.1 35.
CALCULATED
29 Travel Units Min. Nor. Max. % 44 59 79
RESULTS
30 Noise dBA @1m Units Min. Nor. Max. dBA 76 82 81
31 MFR Model FISHER ES 56 MFR Model FISHER DVC6200F/SC-AD
32 Body Type Single Seat Globe 57 Signal: Inlet Outlet FF Protocol 0-2.8 kgf/cm2
33 Body Size Trim Size 1.5 in 1 7/8 in 58 Increase Signal Valve: DIRECT
34 End Connec.Size & Rating 1.5" 300# RF POSITIONER 59 Cam Characteristic LINEAR
35 Rated Cv Characteristic 37.2 Linear 60 Bypass Gauges N/A YES
36 Body Material WCC Steel 61 Signal Fail. to Valve FO
BODY 37 Bonnet Type Material Plain WCC Steel 62 Electric Enclosure Ex ia IIC T5 , NEMA 4X
AND 38 Flow Direct. Flow Act. To Up FTO 63 MFR Model N/A N/A
TRIM 39 Packing Type Material Enviro Seal PTFE Carbon 64 Type Power N/A N/A
SOLENOID
40 Lubricator Isolat. Valve N/A N/A 65 When De-Enegr.Valve: N/A
VALVE
41 Guiding No. of Ports Cage 1 66 Material Latcher N/A N/A
42 Trim Type Internal Design Whisper I Unbalanced 67 Electric Enclosure N/A
43 Rated Travel Leak Class 3/4 in ANSI IV 68 MFR Model N/A N/A
44 Plug/ Ball/ Disk Material S41600 SST 69 Type Quantity N/A N/A
45 Seat Material S41600 SST SWITCHES 70 Contacts / Rating N/A
46 Cage Stem Material CB7Cu-1 SST S31600 SST 71 Switching Position N/A
47 Gasket Material S31600 SST/Graphite 72 Electric Enclosure N/A
48 MFR Model FISHER 657 73 MFR Model FISHER 67CFR
49 Type Diaphragm Spring Return AIR SET 74 Set Pressure 4.2 kgf/cm2-g
50 Size Stroke Time 45i < 6 Sec 75 Filter Gauge 5 Micron min YES
ACTUATOR 51 Air Failure Valve: FO 76 Vol. Tank Booster NO NO
52 Handwheel Location N/A 77 Diffuser Lock-up NO NO
ACCESSORY
53 Mounting Position VERTICAL 78 Fire Safe Fireproof NO NO
54 Spring Range 0.4 - 2.0 kgf/cm2-g 79 Mech. Stop Quick Exa. NO NO
55 Include Pressure (Shutoff) 80 Hydro. Pressure YES
85 Vendor EMERSON 81 Leakage YES
PURCHASE TESTS
86 Manufacturer FISHER 82 Cryogenic N/A
87 Requisition No. R2B-P3-206-02-P-MR-00200 83 NACE Requirement N/A
88 Model No. ES 84 PWHT Requirement N/A
Notes:

INSTRUMENT SPECIFICATION - CONTROL VALVE


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S3.1 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Fieldbus Device Data Sheet
Tag No.: FV -21007
Fieldbus Tag No.:

Service : FA008 PA TO DC002

Basic Fieldbus Function Blocks Segment Information


Analog Input Block (AI) 1 Number Device:
1 22
20 Execution (msec)
Discrete Input Block (DI) 4 Number Segment #: DFJB-21044
2 23
15 Execution Time
3 Bias/Gain Station (BG) 0 Execution (msec) 24 LAS Capable: Yes No
Manual Loader (ML) 0 Number 25 Device Current Draw (mA): 0
4
0 Execution (msec) Device Minimum Voltage: .
26
Analog Output Block (AO) 1 Number Device Capacitance: 0
5 20 Execution (msec) Polarity-sensitive: Yes No
27
Discrete Output Block (DO) 1 Number Segment Terminator Location:
6 20 Execution (msec)
28
7 Control Selector (CS)
DD Revision: 3
PID,PI,I Controller (PID) 29
8
20 Execution (msec)
CFF Revision: 1.9
Ratio Station (RA) 30
9
P,PD Controller (PD) 0 Number
10 0 Execution (msec)

* Execution time in msec.

Advanced Function Blocks Notes:

11 Device Control (DC)

12 Output Splitter (OS)

13 Signal Characterizer (SC)

14 Lead Lag (LL)

15 Deadtime (DT)

16 Integrator(Totalizer) (IT)

17 Setpoint Ramp Generator (SPG)

18 Input Selector (IS)

19 Arithmetic (AR)

20 Timer (TMR)

21 Analog Alarm (AAL)

INSTRUMENT SPECIFICATION -FOUNDATION FIELDBUS


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S3.2 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Tag Number : FV -21007

1. In-Built surge protector is provided by vendor.

1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S3.3 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
1 Tag No. FV -21008
2 Service FA008 PA TO DC002
3 P&ID No. Line No. R2B-P3-206-02-A-DTI-00063 3"-AP-210164-T-A06T1-PP
4 Area Classification Ingress Protection CLASS 1 DIV 2 Gr. B ,C&D, T3 NEMA 4X
GENERAL 5 Ambient Temperature: Unit Min. Max. °C 10 48
6 Allowable Sound dBA Tightness Requirement <85 ANSI IV (standard)
7 Available Air Supply Pressure Unit Min. Max. kgf/cm²-g 4.2 8.0
8 Electric Connection Pneum. Connection 1/2” NPT (F) 1/4” NPT (F)
9 Power Failure Position FO
10 Line Size and Schedule Sch. Outlet Line Sch. 3 in STD 4" STD
PIPE
11 Line Class Rating Pipe Material T-A06T1 150# A106 GR.B, SMLS
LINE
12 Pipe Insulation Thickness Corrosion Allowance PP 50mm 1.6mm
13 Fluid State Phase Plant Air Gas/Vapor Single Phase
14 Sour Service Special Condition N/A N/A
15 Flow Rate Units Min. Nor. Max. Nm³/h 2014 2014 2215
16 Inlet Pressure Units Min. Nor. Max. kgf/cm²-g 7.63 6.781 6.185
17 Pressure Drop Units Min. Nor. Max. kgf/cm² 5.484 4.75 3.612
18 Inlet Temperature Units Min. Nor. Max. °C 40 157 157
PROCESS 19 Density Units Min. Nor. Max. kg/m³
CONDITIONS 20 Viscosity Units Min. Nor. Max. cP 0.019 0.019 0.019
21 Molecular Weight (MW) Specific Gravity @ Oper. 28.85
22 Spec. Heat Ratio (Cp/Cv) Compressibility (Z) 1.4 1.001
23 Vapor Pressure (Liq.) Cavitation or Flashing kgf/cm²-a N/A
24 Critical Pressure (Liq) Flash (wt%) kgf/cm²-a
25 Design Pressure Min. Max. -1.033 kgf/cm²-g 10.5 kgf/cm²-g
26 Design Temperature Min. Max. 10 °C 185 °C
27 Max.Shutoff DP Solid % 10.5 kgf/cm²
28 Calculated Cv Units Min. Nor. Max. Cv 24.4 31.1 35.
CALCULATED
29 Travel Units Min. Nor. Max. % 44 59 79
RESULTS
30 Noise dBA @1m Units Min. Nor. Max. dBA 76 82 81
31 MFR Model FISHER ES 56 MFR Model FISHER DVC6200F/SC-AD
32 Body Type Single Seat Globe 57 Signal: Inlet Outlet FF Protocol 0-2.8 kgf/cm2
33 Body Size Trim Size 1.5 in 1 7/8 in 58 Increase Signal Valve: DIRECT
34 End Connec.Size & Rating 1.5" 300# RF POSITIONER 59 Cam Characteristic LINEAR
35 Rated Cv Characteristic 37.2 Linear 60 Bypass Gauges N/A YES
36 Body Material WCC Steel 61 Signal Fail. to Valve FO
BODY 37 Bonnet Type Material Plain WCC Steel 62 Electric Enclosure Ex ia IIC T5 , NEMA 4X
AND 38 Flow Direct. Flow Act. To Up FTO 63 MFR Model N/A N/A
TRIM 39 Packing Type Material Enviro Seal PTFE Carbon 64 Type Power N/A N/A
SOLENOID
40 Lubricator Isolat. Valve N/A N/A 65 When De-Enegr.Valve: N/A
VALVE
41 Guiding No. of Ports Cage 1 66 Material Latcher N/A N/A
42 Trim Type Internal Design Whisper I Unbalanced 67 Electric Enclosure N/A
43 Rated Travel Leak Class 3/4 in ANSI IV 68 MFR Model N/A N/A
44 Plug/ Ball/ Disk Material S41600 SST 69 Type Quantity N/A N/A
45 Seat Material S41600 SST SWITCHES 70 Contacts / Rating N/A
46 Cage Stem Material CB7Cu-1 SST S31600 SST 71 Switching Position N/A
47 Gasket Material S31600 SST/Graphite 72 Electric Enclosure N/A
48 MFR Model FISHER 657 73 MFR Model FISHER 67CFR
49 Type Diaphragm Spring Return AIR SET 74 Set Pressure 4.2 kgf/cm2-g
50 Size Stroke Time 45i < 6 Sec 75 Filter Gauge 5 Micron min YES
ACTUATOR 51 Air Failure Valve: FO 76 Vol. Tank Booster NO NO
52 Handwheel Location N/A 77 Diffuser Lock-up NO NO
ACCESSORY
53 Mounting Position VERTICAL 78 Fire Safe Fireproof NO NO
54 Spring Range 0.4 - 2.0 kgf/cm2-g 79 Mech. Stop Quick Exa. NO NO
55 Include Pressure (Shutoff) 80 Hydro. Pressure YES
85 Vendor EMERSON 81 Leakage YES
PURCHASE TESTS
86 Manufacturer FISHER 82 Cryogenic N/A
87 Requisition No. R2B-P3-206-02-P-MR-00200 83 NACE Requirement N/A
88 Model No. ES 84 PWHT Requirement N/A
Notes:

INSTRUMENT SPECIFICATION - CONTROL VALVE


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S4.1 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Fieldbus Device Data Sheet
Tag No.: FV -21008
Fieldbus Tag No.:

Service : FA008 PA TO DC002

Basic Fieldbus Function Blocks Segment Information


Analog Input Block (AI) 1 Number Device:
1 22
20 Execution (msec)
Discrete Input Block (DI) 4 Number Segment #: DFJB-21044
2 23
15 Execution Time
3 Bias/Gain Station (BG) 0 Execution (msec) 24 LAS Capable: Yes No
Manual Loader (ML) 0 Number 25 Device Current Draw (mA): 19
4
0 Execution (msec) Device Minimum Voltage: 9.
26
Analog Output Block (AO) 1 Number Device Capacitance: 5 nF
5 20 Execution (msec) Polarity-sensitive: Yes No
27
Discrete Output Block (DO) 1 Number Segment Terminator Location:
6 20 Execution (msec)
28
7 Control Selector (CS)
DD Revision: 3
PID,PI,I Controller (PID) 29
8
20 Execution (msec)
CFF Revision: 1.9
Ratio Station (RA) 30
9
P,PD Controller (PD) 0 Number
10 0 Execution (msec)

* Execution time in msec.

Advanced Function Blocks Notes:

11 Device Control (DC)

12 Output Splitter (OS)

13 Signal Characterizer (SC)

14 Lead Lag (LL)

15 Deadtime (DT)

16 Integrator(Totalizer) (IT)

17 Setpoint Ramp Generator (SPG)

18 Input Selector (IS)

19 Arithmetic (AR)

20 Timer (TMR)

21 Analog Alarm (AAL)

INSTRUMENT SPECIFICATION -FOUNDATION FIELDBUS


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S4.2 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Tag Number : FV -21008

1. In-Built surge protector is provided by vendor.

1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S4.3 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
1 Tag No. FV -21009
2 Service FA008 PA TO DC002
3 P&ID No. Line No. R2B-P3-206-02-A-DTI-00063 3"-AP-210166-T-A06T1-PP
4 Area Classification Ingress Protection CLASS 1 DIV 2 Gr. B ,C&D, T3 NEMA 4X
GENERAL 5 Ambient Temperature: Unit Min. Max. °C 10 48
6 Allowable Sound dBA Tightness Requirement <85 ANSI IV (standard)
7 Available Air Supply Pressure Unit Min. Max. kgf/cm²-g 4.2 8.0
8 Electric Connection Pneum. Connection 1/2” NPT (F) 1/4” NPT (F)
9 Power Failure Position FO
10 Line Size and Schedule Sch. Outlet Line Sch. 3 in STD 4" STD
PIPE
11 Line Class Rating Pipe Material T-A06T1 150# A106 GR.B, SMLS
LINE
12 Pipe Insulation Thickness Corrosion Allowance PP 50mm 1.6mm
13 Fluid State Phase Plant Air Gas/Vapor Single Phase
14 Sour Service Special Condition N/A N/A
15 Flow Rate Units Min. Nor. Max. Nm³/h 2014 2014 2215
16 Inlet Pressure Units Min. Nor. Max. kgf/cm²-g 7.63 6.781 6.185
17 Pressure Drop Units Min. Nor. Max. kgf/cm² 5.484 4.75 3.612
18 Inlet Temperature Units Min. Nor. Max. °C 40 157 157
PROCESS 19 Density Units Min. Nor. Max. kg/m³
CONDITIONS 20 Viscosity Units Min. Nor. Max. cP 0.019 0.019 0.019
21 Molecular Weight (MW) Specific Gravity @ Oper. 28.85
22 Spec. Heat Ratio (Cp/Cv) Compressibility (Z) 1.4 1.001
23 Vapor Pressure (Liq.) Cavitation or Flashing kgf/cm²-a N/A
24 Critical Pressure (Liq) Flash (wt%) kgf/cm²-a
25 Design Pressure Min. Max. -1.033 kgf/cm²-g 10.5 kgf/cm²-g
26 Design Temperature Min. Max. 10 °C 185 °C
27 Max.Shutoff DP Solid % 10.5 kgf/cm²
28 Calculated Cv Units Min. Nor. Max. Cv 24.4 31.1 35.
CALCULATED
29 Travel Units Min. Nor. Max. % 44 59 79
RESULTS
30 Noise dBA @1m Units Min. Nor. Max. dBA 76 82 81
31 MFR Model FISHER ES 56 MFR Model FISHER DVC6200F/SC-AD
32 Body Type Single Seat Globe 57 Signal: Inlet Outlet FF Protocol 0-2.8 kgf/cm2
33 Body Size Trim Size 1.5 in 1 7/8 in 58 Increase Signal Valve: DIRECT
34 End Connec.Size & Rating 1.5" 300# RF POSITIONER 59 Cam Characteristic LINEAR
35 Rated Cv Characteristic 37.2 Linear 60 Bypass Gauges N/A YES
36 Body Material WCC Steel 61 Signal Fail. to Valve FO
BODY 37 Bonnet Type Material Plain WCC Steel 62 Electric Enclosure Ex ia IIC T5 , NEMA 4X
AND 38 Flow Direct. Flow Act. To Up FTO 63 MFR Model N/A N/A
TRIM 39 Packing Type Material Enviro Seal PTFE Carbon 64 Type Power N/A N/A
SOLENOID
40 Lubricator Isolat. Valve N/A N/A 65 When De-Enegr.Valve: N/A
VALVE
41 Guiding No. of Ports Cage 1 66 Material Latcher N/A N/A
42 Trim Type Internal Design Whisper I Unbalanced 67 Electric Enclosure N/A
43 Rated Travel Leak Class 3/4 in ANSI IV 68 MFR Model N/A N/A
44 Plug/ Ball/ Disk Material S41600 SST 69 Type Quantity N/A N/A
45 Seat Material S41600 SST SWITCHES 70 Contacts / Rating N/A
46 Cage Stem Material CB7Cu-1 SST S31600 SST 71 Switching Position N/A
47 Gasket Material S31600 SST/Graphite 72 Electric Enclosure N/A
48 MFR Model FISHER 657 73 MFR Model FISHER 67CFR
49 Type Diaphragm Spring Return AIR SET 74 Set Pressure 4.2 kgf/cm2-g
50 Size Stroke Time 45i < 6 Sec 75 Filter Gauge 5 Micron min YES
ACTUATOR 51 Air Failure Valve: FO 76 Vol. Tank Booster NO NO
52 Handwheel Location N/A 77 Diffuser Lock-up NO NO
ACCESSORY
53 Mounting Position VERTICAL 78 Fire Safe Fireproof NO NO
54 Spring Range 0.4 - 2.0 kgf/cm2-g 79 Mech. Stop Quick Exa. NO NO
55 Include Pressure (Shutoff) 80 Hydro. Pressure YES
85 Vendor EMERSON 81 Leakage YES
PURCHASE TESTS
86 Manufacturer FISHER 82 Cryogenic N/A
87 Requisition No. R2B-P3-206-02-P-MR-00200 83 NACE Requirement N/A
88 Model No. ES 84 PWHT Requirement N/A
Notes:

INSTRUMENT SPECIFICATION - CONTROL VALVE


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S5.1 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Fieldbus Device Data Sheet
Tag No.: FV -21009
Fieldbus Tag No.:

Service : FA008 PA TO DC002

Basic Fieldbus Function Blocks Segment Information


Analog Input Block (AI) 1 Number Device:
1 22
20 Execution (msec)
Discrete Input Block (DI) 4 Number Segment #: DFJB-21041
2 23
15 Execution Time
3 Bias/Gain Station (BG) 0 Execution (msec) 24 LAS Capable: Yes No
Manual Loader (ML) 0 Number 25 Device Current Draw (mA): 19
4
0 Execution (msec) Device Minimum Voltage: 9.
26
Analog Output Block (AO) 1 Number Device Capacitance: 5 nF
5 20 Execution (msec) Polarity-sensitive: Yes No
27
Discrete Output Block (DO) 1 Number Segment Terminator Location:
6 20 Execution (msec)
28
7 Control Selector (CS)
DD Revision: 3
PID,PI,I Controller (PID) 29
8
20 Execution (msec)
CFF Revision: 1.9
Ratio Station (RA) 30
9
P,PD Controller (PD) 0 Number
10 0 Execution (msec)

* Execution time in msec.

Advanced Function Blocks Notes:

11 Device Control (DC)

12 Output Splitter (OS)

13 Signal Characterizer (SC)

14 Lead Lag (LL)

15 Deadtime (DT)

16 Integrator(Totalizer) (IT)

17 Setpoint Ramp Generator (SPG)

18 Input Selector (IS)

19 Arithmetic (AR)

20 Timer (TMR)

21 Analog Alarm (AAL)

INSTRUMENT SPECIFICATION -FOUNDATION FIELDBUS


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S5.2 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Tag Number : FV -21009

1. In-Built surge protector is provided by vendor.

1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S5.3 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
1 Tag No. FV -21010
2 Service MP STM TO DC001 RX
3 P&ID No. Line No. R2B-P3-206-02-A-DTI-00064 12"-VM-210423-T-B04T1-EC
4 Area Classification Ingress Protection CLASS 1 DIV 2 Gr. B ,C&D, T3 NEMA 4X
GENERAL 5 Ambient Temperature: Unit Min. Max. °C 10 48
6 Allowable Sound dBA Tightness Requirement <85 ANSI IV (standard)
7 Available Air Supply Pressure Unit Min. Max. kgf/cm²-g 4.2 8.0
8 Electric Connection Pneum. Connection 1/2” NPT (F) 1/2” NPT (F)
9 Power Failure Position FC
10 Line Size and Schedule Sch. Outlet Line Sch. 12 in STD 14" STD
PIPE
11 Line Class Rating Pipe Material T-B04T1 300# A106 GR.B, SMLS
LINE
12 Pipe Insulation Thickness Corrosion Allowance EC 115mm 1.6mm
13 Fluid State Phase Steam Gas/Vapor Single Phase
14 Sour Service Special Condition N/A N/A
15 Flow Rate Units Min. Nor. Max. kg/h 44174 44174 44174
16 Inlet Pressure Units Min. Nor. Max. kgf/cm²-g 13.19 10.14 9.53
17 Pressure Drop Units Min. Nor. Max. kgf/cm² 11.47 7.805 7.128
18 Inlet Temperature Units Min. Nor. Max. °C 220 220 220
PROCESS 19 Density Units Min. Nor. Max. kg/m³
CONDITIONS 20 Viscosity Units Min. Nor. Max. cP 0.017 0.017 0.017
21 Molecular Weight (MW) Specific Gravity @ Oper. 18.02
22 Spec. Heat Ratio (Cp/Cv) Compressibility (Z) 1.24 0.949
23 Vapor Pressure (Liq.) Cavitation or Flashing kgf/cm²-a N/A
24 Critical Pressure (Liq) Flash (wt%) kgf/cm²-a
25 Design Pressure Min. Max. -1.033 kgf/cm²-g 15.5 kgf/cm²-g
26 Design Temperature Min. Max. 10 °C 260 °C
27 Max.Shutoff DP Solid % 15.5 kgf/cm²
28 Calculated Cv Units Min. Nor. Max. Cv 319 406 430
CALCULATED
29 Travel Units Min. Nor. Max. % 36 47 50
RESULTS
30 Noise dBA @1m Units Min. Nor. Max. dBA 85 85 85
31 MFR Model FISHER EWT 56 MFR Model FISHER DVC6200F/SC-AD
32 Body Type Single Seat Globe 57 Signal: Inlet Outlet FF Protocol 4.2 kgf/cm2
33 Body Size Trim Size 10 in 8 in 58 Increase Signal Valve: DIRECT
34 End Connec.Size & Rating 10" 300# RF POSITIONER 59 Cam Characteristic LINEAR
35 Rated Cv Characteristic 771.7 Linear 60 Bypass Gauges N/A YES
36 Body Material WCC Steel 61 Signal Fail. to Valve FC
BODY 37 Bonnet Type Material Plain WCC Steel 62 Electric Enclosure Ex ia IIC T5 , NEMA 4X
AND 38 Flow Direct. Flow Act. To Up FTC 63 MFR Model N/A N/A
TRIM 39 Packing Type Material Enviro Seal Graphite ULF 64 Type Power N/A N/A
SOLENOID
40 Lubricator Isolat. Valve N/A N/A 65 When De-Enegr.Valve: N/A
VALVE
41 Guiding No. of Ports Cage 1 66 Material Latcher N/A N/A
42 Trim Type Internal Design Whisper III Balanced 67 Electric Enclosure N/A
43 Rated Travel Leak Class 4 in ANSI IV 68 MFR Model N/A N/A
44 Plug/ Ball/ Disk Material S41600 SST 69 Type Quantity N/A N/A
45 Seat Material S41600 SST SWITCHES 70 Contacts / Rating N/A
46 Cage Stem Material CB7Cu-1 SST S31600 SST 71 Switching Position N/A
47 Gasket Material S31600 SST/Graphite 72 Electric Enclosure N/A
48 MFR Model FISHER 785C 73 MFR Model FISHER 67DFR
49 Type Piston Spring Return AIR SET 74 Set Pressure 4.2 kgf/cm2-g
50 Size Stroke Time 335 < 25 Sec 75 Filter Gauge 5 Micron min YES
ACTUATOR 51 Air Failure Valve: FC 76 Vol. Tank Booster NO NO
52 Handwheel Location N/A 77 Diffuser Lock-up NO NO
ACCESSORY
53 Mounting Position VERTICAL 78 Fire Safe Fireproof NO NO
54 Spring Range 2.0 - 3.2 kgf/cm2-g 79 Mech. Stop Quick Exa. NO NO
55 Include Pressure (Shutoff) 80 Hydro. Pressure YES
85 Vendor EMERSON 81 Leakage YES
PURCHASE TESTS
86 Manufacturer FISHER 82 Cryogenic N/A
87 Requisition No. R2B-P3-206-02-P-MR-00200 83 NACE Requirement N/A
88 Model No. EWT 84 PWHT Requirement N/A
Notes:

INSTRUMENT SPECIFICATION - CONTROL VALVE


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S6.1 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Fieldbus Device Data Sheet
Tag No.: FV -21010
Fieldbus Tag No.:

Service : MP STM TO DC001 RX

Basic Fieldbus Function Blocks Segment Information


Analog Input Block (AI) 1 Number Device:
1 22
20 Execution (msec)
Discrete Input Block (DI) 4 Number Segment #: DFJB-21049
2 23
15 Execution Time
3 Bias/Gain Station (BG) 0 Execution (msec) 24 LAS Capable: Yes No
Manual Loader (ML) 0 Number 25 Device Current Draw (mA): 19
4
0 Execution (msec) Device Minimum Voltage: 9.
26
Analog Output Block (AO) 1 Number Device Capacitance: 5 nF
5 20 Execution (msec) Polarity-sensitive: Yes No
27
Discrete Output Block (DO) 1 Number Segment Terminator Location:
6 20 Execution (msec)
28
7 Control Selector (CS)
DD Revision: 3
PID,PI,I Controller (PID) 29
8
20 Execution (msec)
CFF Revision: 1.9
Ratio Station (RA) 30
9
P,PD Controller (PD) 0 Number
10 0 Execution (msec)

* Execution time in msec.

Advanced Function Blocks Notes:

11 Device Control (DC)

12 Output Splitter (OS)

13 Signal Characterizer (SC)

14 Lead Lag (LL)

15 Deadtime (DT)

16 Integrator(Totalizer) (IT)

17 Setpoint Ramp Generator (SPG)

18 Input Selector (IS)

19 Arithmetic (AR)

20 Timer (TMR)

21 Analog Alarm (AAL)

INSTRUMENT SPECIFICATION -FOUNDATION FIELDBUS


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S6.2 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Tag Number : FV -21010

1. Valve will normally be in the closed position. Valve opening will be intermittent and generally short-term.
2. In-Built surge protector is provided by vendor.

1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S6.3 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
1 Tag No. FV -21011
2 Service GA110 STUP NPTHA TO DC001 RX
3 P&ID No. Line No. R2B-P3-206-02-A-DTI-00064 4"-P-211107-B2A2-NACE-N
4 Area Classification Ingress Protection CLASS 1 DIV 2 Gr. B ,C&D, T3 NEMA 4X
GENERAL 5 Ambient Temperature: Unit Min. Max. °C 10 48
6 Allowable Sound dBA Tightness Requirement <85 ANSI IV (standard)
7 Available Air Supply Pressure Unit Min. Max. kgf/cm²-g 4.2 8.0
8 Electric Connection Pneum. Connection 1/2” NPT (F) 1/4” NPT (F)
9 Power Failure Position FC
10 Line Size and Schedule Sch. Outlet Line Sch. 4 in XS 4" XS
PIPE
11 Line Class Rating Pipe Material B2A2-NACE 300# A106 GR.B, SMLS
LINE
12 Pipe Insulation Thickness Corrosion Allowance N N/A 3.2mm
13 Fluid State Phase Hydrocarbon Liquid Single Phase
14 Sour Service Special Condition YES N/A
15 Flow Rate Units Min. Nor. Max. m³/h 29 58 63.7
16 Inlet Pressure Units Min. Nor. Max. kgf/cm²-g 23.69 19.8 18.52
17 Pressure Drop Units Min. Nor. Max. kgf/cm² 17.59 13.59 12.28
18 Inlet Temperature Units Min. Nor. Max. °C 40 40 40
PROCESS 19 Density Units Min. Nor. Max. kg/m³ 734 734 734
CONDITIONS 20 Viscosity Units Min. Nor. Max. cP 0.528 0.528 0.528
21 Molecular Weight (MW) Specific Gravity @ Oper.
22 Spec. Heat Ratio (Cp/Cv) Compressibility (Z)
23 Vapor Pressure (Liq.) Cavitation or Flashing 1.92 kgf/cm²-a NO
24 Critical Pressure (Liq) Flash (wt%) 36.22 kgf/cm²-a
25 Design Pressure Min. Max. -1.033 kgf/cm²-g 25.5 kgf/cm²-g
26 Design Temperature Min. Max. 10 °C 120 °C
27 Max.Shutoff DP Solid % 25.5 kgf/cm²
28 Calculated Cv Units Min. Nor. Max. Cv 6.92 15.8 18.4
CALCULATED
29 Travel Units Min. Nor. Max. % 22 48 56
RESULTS
30 Noise dBA @1m Units Min. Nor. Max. dBA 72 74 74
31 MFR Model FISHER ET 56 MFR Model FISHER DVC6200F/SC-AD
32 Body Type Single Seat Globe 57 Signal: Inlet Outlet FF Protocol 0-3.5 kgf/cm2
33 Body Size Trim Size 2 in 1 5/16 in 58 Increase Signal Valve: DIRECT
34 End Connec.Size & Rating 2" 300# RF POSITIONER 59 Cam Characteristic LINEAR
35 Rated Cv Characteristic 33.3 Linear 60 Bypass Gauges N/A YES
36 Body Material WCC Steel 61 Signal Fail. to Valve FC
BODY 37 Bonnet Type Material Plain WCC Steel 62 Electric Enclosure Ex ia IIC T5 , NEMA 4X
AND 38 Flow Direct. Flow Act. To Down FTO 63 MFR Model N/A N/A
TRIM 39 Packing Type Material ISO Seal PTFE 64 Type Power N/A N/A
SOLENOID
40 Lubricator Isolat. Valve N/A N/A 65 When De-Enegr.Valve: N/A
VALVE
41 Guiding No. of Ports Cage 1 66 Material Latcher N/A N/A
42 Trim Type Internal Design Standard Balanced 67 Electric Enclosure N/A
43 Rated Travel Leak Class 3/4 in ANSI IV 68 MFR Model N/A N/A
44 Plug/ Ball/ Disk Material S31600 SST/CoCr-A Seat 69 Type Quantity N/A N/A
45 Seat Material R30006 Cobalt Alloy SWITCHES 70 Contacts / Rating N/A
46 Cage Stem Material S31600 SST/ ENCS20910 SST 71 Switching Position N/A
47 Gasket Material S31600 SST/Graphite 72 Electric Enclosure N/A
48 MFR Model FISHER 667 73 MFR Model FISHER 67CFR
49 Type Diaphragm Spring Return AIR SET 74 Set Pressure 4.2 kgf/cm2-g
50 Size Stroke Time 40i < 8 Sec 75 Filter Gauge 5 Micron min YES
ACTUATOR 51 Air Failure Valve: FC 76 Vol. Tank Booster NO NO
52 Handwheel Location N/A 77 Diffuser Lock-up NO NO
ACCESSORY
53 Mounting Position VERTICAL 78 Fire Safe Fireproof NO NO
54 Spring Range 0.7 - 2.7 kgf/cm2-g 79 Mech. Stop Quick Exa. NO NO
55 Include Pressure (Shutoff) 80 Hydro. Pressure YES
85 Vendor EMERSON 81 Leakage YES
PURCHASE TESTS
86 Manufacturer FISHER 82 Cryogenic N/A
87 Requisition No. R2B-P3-206-02-P-MR-00200 83 NACE Requirement NACE-0103
88 Model No. ET 84 PWHT Requirement YES
Notes:

INSTRUMENT SPECIFICATION - CONTROL VALVE


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S7.1 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Fieldbus Device Data Sheet
Tag No.: FV -21011
Fieldbus Tag No.:

Service : GA110 STUP NPTHA TO DC001 RX

Basic Fieldbus Function Blocks Segment Information


Analog Input Block (AI) 1 Number Device:
1 22
20 Execution (msec)
Discrete Input Block (DI) 4 Number Segment #: DFJB-21049
2 23
15 Execution Time
3 Bias/Gain Station (BG) 0 Execution (msec) 24 LAS Capable: Yes No
Manual Loader (ML) 0 Number 25 Device Current Draw (mA): 19
4
0 Execution (msec) Device Minimum Voltage: 9.
26
Analog Output Block (AO) 1 Number Device Capacitance: 5 nF
5 20 Execution (msec) Polarity-sensitive: Yes No
27
Discrete Output Block (DO) 1 Number Segment Terminator Location:
6 20 Execution (msec)
28
7 Control Selector (CS)
DD Revision: 3
PID,PI,I Controller (PID) 29
8
20 Execution (msec)
CFF Revision: 1.9
Ratio Station (RA) 30
9
P,PD Controller (PD) 0 Number
10 0 Execution (msec)

* Execution time in msec.

Advanced Function Blocks Notes:

11 Device Control (DC)

12 Output Splitter (OS)

13 Signal Characterizer (SC)

14 Lead Lag (LL)

15 Deadtime (DT)

16 Integrator(Totalizer) (IT)

17 Setpoint Ramp Generator (SPG)

18 Input Selector (IS)

19 Arithmetic (AR)

20 Timer (TMR)

21 Analog Alarm (AAL)

INSTRUMENT SPECIFICATION -FOUNDATION FIELDBUS


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S7.2 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Tag Number : FV -21011

1. Valve will normally be in the closed position. Valve opening will be intermittent and generally short-term.
2. Special PWHT Required.
3. In-Built surge protector is provided by vendor.

1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S7.3 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
1 Tag No. FV -21012
2 Service FA004 MP STM TO DC001 RX
3 P&ID No. Line No. R2B-P3-206-02-A-DTI-00065 2"-VM-210477-T-B04T1-EC
4 Area Classification Ingress Protection CLASS 1 DIV 2 Gr. B ,C&D, T3 NEMA 4X
GENERAL 5 Ambient Temperature: Unit Min. Max. °C 10 48
6 Allowable Sound dBA Tightness Requirement <85 ANSI IV (standard)
7 Available Air Supply Pressure Unit Min. Max. kgf/cm²-g 4.2 8.0
8 Electric Connection Pneum. Connection 1/2” NPT (F) 1/4” NPT (F)
9 Power Failure Position FO
10 Line Size and Schedule Sch. Outlet Line Sch. 2 in XS 3" STD
PIPE
11 Line Class Rating Pipe Material T-B04T1 300# A106 GR.B, SMLS
LINE
12 Pipe Insulation Thickness Corrosion Allowance EC 90mm 1.6mm
13 Fluid State Phase Steam Gas/Vapor Single Phase
14 Sour Service Special Condition N/A N/A
15 Flow Rate Units Min. Nor. Max. kg/h 179 205 358
16 Inlet Pressure Units Min. Nor. Max. kgf/cm²-g 13.36 10.28 9.34
17 Pressure Drop Units Min. Nor. Max. kgf/cm² 11.48 7.54 6.01
18 Inlet Temperature Units Min. Nor. Max. °C 220 220 220
PROCESS 19 Density Units Min. Nor. Max. kg/m³
CONDITIONS 20 Viscosity Units Min. Nor. Max. cP 0.017 0.017 0.017
21 Molecular Weight (MW) Specific Gravity @ Oper. 18.02
22 Spec. Heat Ratio (Cp/Cv) Compressibility (Z) 1.238 0.947
23 Vapor Pressure (Liq.) Cavitation or Flashing kgf/cm²-a N/A
24 Critical Pressure (Liq) Flash (wt%) kgf/cm²-a
25 Design Pressure Min. Max. -1.033 kgf/cm²-g 15.5 kgf/cm²-g
26 Design Temperature Min. Max. 10 °C 260 °C
27 Max.Shutoff DP Solid % 15.5 kgf/cm²
28 Calculated Cv Units Min. Nor. Max. Cv 1.43 2.05 3.81
CALCULATED
29 Travel Units Min. Nor. Max. % 58 69 87
RESULTS
30 Noise dBA @1m Units Min. Nor. Max. dBA 73 73 78
31 MFR Model FISHER EZ 56 MFR Model FISHER DVC6200F/SC-AD
32 Body Type Single Seat Globe 57 Signal: Inlet Outlet FF Protocol 0-2.8 kgf/cm2
33 Body Size Trim Size 1 in 1/2 in 58 Increase Signal Valve: DIRECT
34 End Connec.Size & Rating 1" 300# RF POSITIONER 59 Cam Characteristic LINEAR
35 Rated Cv Characteristic 4.91 EQ% 60 Bypass Gauges N/A YES
36 Body Material WCC Steel 61 Signal Fail. to Valve FO
BODY 37 Bonnet Type Material Style 1 Extension WCC Steel 62 Electric Enclosure Ex ia IIC T5 , NEMA 4X
AND 38 Flow Direct. Flow Act. To Up FTO 63 MFR Model N/A N/A
TRIM 39 Packing Type Material Enviro Seal Graphite ULF 64 Type Power N/A N/A
SOLENOID
40 Lubricator Isolat. Valve N/A N/A 65 When De-Enegr.Valve: N/A
VALVE
41 Guiding No. of Ports Post 1 66 Material Latcher N/A N/A
42 Trim Type Internal Design Micro Form Unbalanced 67 Electric Enclosure N/A
43 Rated Travel Leak Class 3/4 in ANSI IV 68 MFR Model N/A N/A
44 Plug/ Ball/ Disk Material S41600 SST 69 Type Quantity N/A N/A
45 Seat Material S41600 SST SWITCHES 70 Contacts / Rating N/A
46 Cage Stem Material N/A S31600 SST 71 Switching Position N/A
47 Gasket Material S31600 SST/Graphite 72 Electric Enclosure N/A
48 MFR Model FISHER 657 73 MFR Model FISHER 67CFR
49 Type Diaphragm Spring Return AIR SET 74 Set Pressure 4.2 kgf/cm2-g
50 Size Stroke Time 30i < 5 Sec 75 Filter Gauge 5 Micron min YES
ACTUATOR 51 Air Failure Valve: FO 76 Vol. Tank Booster NO NO
52 Handwheel Location N/A 77 Diffuser Lock-up NO NO
ACCESSORY
53 Mounting Position VERTICAL 78 Fire Safe Fireproof NO NO
54 Spring Range 0.6 - 2.2 kgf/cm2-g 79 Mech. Stop Quick Exa. YES (DOWN STOP) NO
55 Include Pressure (Shutoff) 80 Hydro. Pressure YES
85 Vendor EMERSON 81 Leakage YES
PURCHASE TESTS
86 Manufacturer FISHER 82 Cryogenic N/A
87 Requisition No. R2B-P3-206-02-P-MR-00200 83 NACE Requirement N/A
88 Model No. EZ 84 PWHT Requirement N/A
Notes:

INSTRUMENT SPECIFICATION - CONTROL VALVE


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S8.1 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Fieldbus Device Data Sheet
Tag No.: FV -21012
Fieldbus Tag No.:

Service : FA004 MP STM TO DC001 RX

Basic Fieldbus Function Blocks Segment Information


Analog Input Block (AI) 1 Number Device:
1 22
20 Execution (msec)
Discrete Input Block (DI) 4 Number Segment #: DFJB-21029
2 23
15 Execution Time
3 Bias/Gain Station (BG) 0 Execution (msec) 24 LAS Capable: Yes No
Manual Loader (ML) 0 Number 25 Device Current Draw (mA): 19
4
0 Execution (msec) Device Minimum Voltage: 9.
26
Analog Output Block (AO) 1 Number Device Capacitance: 5 nF
5 20 Execution (msec) Polarity-sensitive: Yes No
27
Discrete Output Block (DO) 1 Number Segment Terminator Location:
6 20 Execution (msec)
28
7 Control Selector (CS)
DD Revision: 3
PID,PI,I Controller (PID) 29
8
20 Execution (msec)
CFF Revision: 1.9
Ratio Station (RA) 30
9
P,PD Controller (PD) 0 Number
10 0 Execution (msec)

* Execution time in msec.

Advanced Function Blocks Notes:

11 Device Control (DC)

12 Output Splitter (OS)

13 Signal Characterizer (SC)

14 Lead Lag (LL)

15 Deadtime (DT)

16 Integrator(Totalizer) (IT)

17 Setpoint Ramp Generator (SPG)

18 Input Selector (IS)

19 Arithmetic (AR)

20 Timer (TMR)

21 Analog Alarm (AAL)

INSTRUMENT SPECIFICATION -FOUNDATION FIELDBUS


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S8.2 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Tag Number : FV -21012

1. Provide an adjustable limit stop with locking feature, per vendor design practice, to limit travel in the closed position.
Field set limit stop to maintain the minimum flow requirement for associated equipment or service.

2. In-Built surge protector is provided by vendor.

1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S8.3 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
1 Tag No. FV -21027
2 Service FA004 MP STM TO DC001 RX
3 P&ID No. Line No. R2B-P3-206-02-A-DTI-00065 2"-VM-210429-T-B04T1-EA
4 Area Classification Ingress Protection CLASS 1 DIV 2 Gr. B ,C&D, T3 NEMA 4X
GENERAL 5 Ambient Temperature: Unit Min. Max. °C 10 48
6 Allowable Sound dBA Tightness Requirement <85 ANSI IV (standard)
7 Available Air Supply Pressure Unit Min. Max. kgf/cm²-g 4.2 8.0
8 Electric Connection Pneum. Connection 1/2” NPT (F) 1/4” NPT (F)
9 Power Failure Position FO
10 Line Size and Schedule Sch. Outlet Line Sch. 2 in XS 3" STD
PIPE
11 Line Class Rating Pipe Material T-B04T1 300# A106 GR.B
LINE
12 Pipe Insulation Thickness Corrosion Allowance EC 90mm 1.6mm
13 Fluid State Phase Steam Gas/Vapor Single Phase
14 Sour Service Special Condition N/A N/A
15 Flow Rate Units Min. Nor. Max. kg/h 179 358 394
16 Inlet Pressure Units Min. Nor. Max. kgf/cm²-g 13.36 10.27 9.674
17 Pressure Drop Units Min. Nor. Max. kgf/cm² 9.36 6.23 5.655
18 Inlet Temperature Units Min. Nor. Max. °C 220 220 220
PROCESS 19 Density Units Min. Nor. Max. kg/m³
CONDITIONS 20 Viscosity Units Min. Nor. Max. cP 0.017 0.017 0.017
21 Molecular Weight (MW) Specific Gravity @ Oper. 18.02
22 Spec. Heat Ratio (Cp/Cv) Compressibility (Z) 1.238 0.947
23 Vapor Pressure (Liq.) Cavitation or Flashing kgf/cm²-a N/A
24 Critical Pressure (Liq) Flash (wt%) kgf/cm²-a
25 Design Pressure Min. Max. -1.033 kgf/cm²-g 15.5 kgf/cm²-g
26 Design Temperature Min. Max. 10 °C 260 °C
27 Max.Shutoff DP Solid % 15.5 kgf/cm²
28 Calculated Cv Units Min. Nor. Max. Cv 1.45 3.6 4.18
CALCULATED
29 Travel Units Min. Nor. Max. % 40 63 67
RESULTS
30 Noise dBA @1m Units Min. Nor. Max. dBA 68 74 75
31 MFR Model FISHER EZ 56 MFR Model FISHER DVC6200F/SC-AD
32 Body Type Single Seat Globe 57 Signal: Inlet Outlet FF Protocol 0-2.8 kgf/cm2
33 Body Size Trim Size 1 in 3/4 in 58 Increase Signal Valve: DIRECT
34 End Connec.Size & Rating 1" 300# RF POSITIONER 59 Cam Characteristic LINEAR
35 Rated Cv Characteristic 8.84 EQ% 60 Bypass Gauges N/A YES
36 Body Material WCC Steel 61 Signal Fail. to Valve FO
BODY 37 Bonnet Type Material Style 1 Extension WCC Steel 62 Electric Enclosure Ex ia IIC T5 , NEMA 4X
AND 38 Flow Direct. Flow Act. To Up FTO 63 MFR Model N/A N/A
TRIM 39 Packing Type Material Enviro Seal Graphite ULF 64 Type Power N/A N/A
SOLENOID
40 Lubricator Isolat. Valve N/A N/A 65 When De-Enegr.Valve: N/A
VALVE
41 Guiding No. of Ports Post 1 66 Material Latcher N/A N/A
42 Trim Type Internal Design Micro Form Unbalanced 67 Electric Enclosure N/A
43 Rated Travel Leak Class 3/4 in ANSI IV 68 MFR Model N/A N/A
44 Plug/ Ball/ Disk Material S41600 SST 69 Type Quantity N/A N/A
45 Seat Material S41600 SST SWITCHES 70 Contacts / Rating N/A
46 Cage Stem Material N/A S31600 SST 71 Switching Position N/A
47 Gasket Material S31600 SST/Graphite 72 Electric Enclosure N/A
48 MFR Model FISHER 657 73 MFR Model FISHER 67CFR
49 Type Diaphragm Spring Return AIR SET 74 Set Pressure 4.2 kgf/cm2-g
50 Size Stroke Time 30i < 5 Sec 75 Filter Gauge 5 Micron min YES
ACTUATOR 51 Air Failure Valve: FO 76 Vol. Tank Booster NO NO
52 Handwheel Location N/A 77 Diffuser Lock-up NO NO
ACCESSORY
53 Mounting Position VERTICAL 78 Fire Safe Fireproof NO NO
54 Spring Range 0.6 - 2.2 kgf/cm2-g 79 Mech. Stop Quick Exa. NO NO
55 Include Pressure (Shutoff) 80 Hydro. Pressure YES
85 Vendor EMERSON 81 Leakage YES
PURCHASE TESTS
86 Manufacturer FISHER 82 Cryogenic N/A
87 Requisition No. R2B-P3-206-02-P-MR-00200 83 NACE Requirement N/A
88 Model No. EZ 84 PWHT Requirement N/A
Notes:

INSTRUMENT SPECIFICATION - CONTROL VALVE


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S9.1 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Fieldbus Device Data Sheet
Tag No.: FV -21027
Fieldbus Tag No.:

Service : FA004 MP STM TO DC001 RX

Basic Fieldbus Function Blocks Segment Information


Analog Input Block (AI) 1 Number Device:
1 22
20 Execution (msec)
Discrete Input Block (DI) 4 Number Segment #: DFJB-21026
2 23
15 Execution Time
3 Bias/Gain Station (BG) 0 Execution (msec) 24 LAS Capable: Yes No
Manual Loader (ML) 0 Number 25 Device Current Draw (mA): 19
4
0 Execution (msec) Device Minimum Voltage: 9.
26
Analog Output Block (AO) 1 Number Device Capacitance: 5 nF
5 20 Execution (msec) Polarity-sensitive: Yes No
27
Discrete Output Block (DO) 1 Number Segment Terminator Location:
6 20 Execution (msec)
28
7 Control Selector (CS)
DD Revision: 3
PID,PI,I Controller (PID) 29
8
20 Execution (msec)
CFF Revision: 1.9
Ratio Station (RA) 30
9
P,PD Controller (PD) 0 Number
10 0 Execution (msec)

* Execution time in msec.

Advanced Function Blocks Notes:

11 Device Control (DC)

12 Output Splitter (OS)

13 Signal Characterizer (SC)

14 Lead Lag (LL)

15 Deadtime (DT)

16 Integrator(Totalizer) (IT)

17 Setpoint Ramp Generator (SPG)

18 Input Selector (IS)

19 Arithmetic (AR)

20 Timer (TMR)

21 Analog Alarm (AAL)

INSTRUMENT SPECIFICATION -FOUNDATION FIELDBUS


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S9.2 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Tag Number : FV -21027

1. In-Built surge protector is provided by vendor.

1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S9.3 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
1 Tag No. FV -21028
2 Service FA004 MP STM TO DC001 RX
3 P&ID No. Line No. R2B-P3-206-02-A-DTI-00065 2"-VM-210455-T-B04T1-EA
4 Area Classification Ingress Protection CLASS 1 DIV 2 Gr. B ,C&D, T3 NEMA 4X
GENERAL 5 Ambient Temperature: Unit Min. Max. °C 10 48
6 Allowable Sound dBA Tightness Requirement <85 ANSI IV (standard)
7 Available Air Supply Pressure Unit Min. Max. kgf/cm²-g 4.2 8.0
8 Electric Connection Pneum. Connection 1/2” NPT (F) 1/4” NPT (F)
9 Power Failure Position FO
10 Line Size and Schedule Sch. Outlet Line Sch. 2 in XS 3" STD
PIPE
11 Line Class Rating Pipe Material T-B04T1 300# A106 GR.B
LINE
12 Pipe Insulation Thickness Corrosion Allowance EC 90mm 1.6mm
13 Fluid State Phase Steam Gas/Vapor Single Phase
14 Sour Service Special Condition N/A N/A
15 Flow Rate Units Min. Nor. Max. kg/h 179 358 394
16 Inlet Pressure Units Min. Nor. Max. kgf/cm²-g 13.36 10.27 9.674
17 Pressure Drop Units Min. Nor. Max. kgf/cm² 9.36 6.23 5.655
18 Inlet Temperature Units Min. Nor. Max. °C 220 220 220
PROCESS 19 Density Units Min. Nor. Max. kg/m³
CONDITIONS 20 Viscosity Units Min. Nor. Max. cP 0.017 0.017 0.017
21 Molecular Weight (MW) Specific Gravity @ Oper. 18.02
22 Spec. Heat Ratio (Cp/Cv) Compressibility (Z) 1.238 0.947
23 Vapor Pressure (Liq.) Cavitation or Flashing kgf/cm²-a N/A
24 Critical Pressure (Liq) Flash (wt%) kgf/cm²-a
25 Design Pressure Min. Max. -1.033 kgf/cm²-g 15.5 kgf/cm²-g
26 Design Temperature Min. Max. 10 °C 260 °C
27 Max.Shutoff DP Solid % 15.5 kgf/cm²
28 Calculated Cv Units Min. Nor. Max. Cv 1.45 3.6 4.18
CALCULATED
29 Travel Units Min. Nor. Max. % 40 63 67
RESULTS
30 Noise dBA @1m Units Min. Nor. Max. dBA 68 74 75
31 MFR Model FISHER EZ 56 MFR Model FISHER DVC6200F/SC-AD
32 Body Type Single Seat Globe 57 Signal: Inlet Outlet FF Protocol 0-2.8 kgf/cm2
33 Body Size Trim Size 1 in 3/4 in 58 Increase Signal Valve: DIRECT
34 End Connec.Size & Rating 1" 300# RF POSITIONER 59 Cam Characteristic LINEAR
35 Rated Cv Characteristic 8.84 EQ% 60 Bypass Gauges N/A YES
36 Body Material WCC Steel 61 Signal Fail. to Valve FO
BODY 37 Bonnet Type Material Style 1 Extension WCC Steel 62 Electric Enclosure Ex ia IIC T5 , NEMA 4X
AND 38 Flow Direct. Flow Act. To Up FTO 63 MFR Model N/A N/A
TRIM 39 Packing Type Material Enviro Seal Graphite ULF 64 Type Power N/A N/A
SOLENOID
40 Lubricator Isolat. Valve N/A N/A 65 When De-Enegr.Valve: N/A
VALVE
41 Guiding No. of Ports Post 1 66 Material Latcher N/A N/A
42 Trim Type Internal Design Micro Form Unbalanced 67 Electric Enclosure N/A
43 Rated Travel Leak Class 3/4 in ANSI IV 68 MFR Model N/A N/A
44 Plug/ Ball/ Disk Material S41600 SST 69 Type Quantity N/A N/A
45 Seat Material S41600 SST SWITCHES 70 Contacts / Rating N/A
46 Cage Stem Material N/A S31600 SST 71 Switching Position N/A
47 Gasket Material S31600 SST/Graphite 72 Electric Enclosure N/A
48 MFR Model FISHER 657 73 MFR Model FISHER 67CFR
49 Type Diaphragm Spring Return AIR SET 74 Set Pressure 4.2 kgf/cm2-g
50 Size Stroke Time 30i < 5 Sec 75 Filter Gauge 5 Micron min YES
ACTUATOR 51 Air Failure Valve: FO 76 Vol. Tank Booster NO NO
52 Handwheel Location N/A 77 Diffuser Lock-up NO NO
ACCESSORY
53 Mounting Position VERTICAL 78 Fire Safe Fireproof NO NO
54 Spring Range 0.4 - 2.0 kgf/cm2-g 79 Mech. Stop Quick Exa. NO NO
55 Include Pressure (Shutoff) 80 Hydro. Pressure YES
85 Vendor EMERSON 81 Leakage YES
PURCHASE TESTS
86 Manufacturer FISHER 82 Cryogenic N/A
87 Requisition No. R2B-P3-206-02-P-MR-00200 83 NACE Requirement N/A
88 Model No. EZ 84 PWHT Requirement N/A
Notes:

INSTRUMENT SPECIFICATION - CONTROL VALVE


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S10.1 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Fieldbus Device Data Sheet
Tag No.: FV -21028
Fieldbus Tag No.:

Service : FA004 MP STM TO DC001 RX

Basic Fieldbus Function Blocks Segment Information


Analog Input Block (AI) 1 Number Device:
1 22
20 Execution (msec)
Discrete Input Block (DI) 4 Number Segment #: DFJB-21026
2 23
15 Execution Time
3 Bias/Gain Station (BG) 0 Execution (msec) 24 LAS Capable: Yes No
Manual Loader (ML) 0 Number 25 Device Current Draw (mA): 19
4
0 Execution (msec) Device Minimum Voltage: 9.
26
Analog Output Block (AO) 1 Number Device Capacitance: 5 nF
5 20 Execution (msec) Polarity-sensitive: Yes No
27
Discrete Output Block (DO) 1 Number Segment Terminator Location:
6 20 Execution (msec)
28
7 Control Selector (CS)
DD Revision: 3
PID,PI,I Controller (PID) 29
8
20 Execution (msec)
CFF Revision: 1.9
Ratio Station (RA) 30
9
P,PD Controller (PD) 0 Number
10 0 Execution (msec)

* Execution time in msec.

Advanced Function Blocks Notes:

11 Device Control (DC)

12 Output Splitter (OS)

13 Signal Characterizer (SC)

14 Lead Lag (LL)

15 Deadtime (DT)

16 Integrator(Totalizer) (IT)

17 Setpoint Ramp Generator (SPG)

18 Input Selector (IS)

19 Arithmetic (AR)

20 Timer (TMR)

21 Analog Alarm (AAL)

INSTRUMENT SPECIFICATION -FOUNDATION FIELDBUS


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S10.2 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Tag Number : FV -21028

1. In-Built surge protector is provided by vendor.

1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S10.3 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
1 Tag No. FV -21029
2 Service FA004 MP STM TO DC001 RX
3 P&ID No. Line No. R2B-P3-206-02-A-DTI-00065 2"-VM-210457-T-B04T1-EA
4 Area Classification Ingress Protection CLASS 1 DIV 2 Gr. B ,C&D, T3 NEMA 4X
GENERAL 5 Ambient Temperature: Unit Min. Max. °C 10 48
6 Allowable Sound dBA Tightness Requirement <85 ANSI IV (standard)
7 Available Air Supply Pressure Unit Min. Max. kgf/cm²-g 4.2 8.0
8 Electric Connection Pneum. Connection 1/2” NPT (F) 1/4” NPT (F)
9 Power Failure Position FO
10 Line Size and Schedule Sch. Outlet Line Sch. 2 in XS 3" STD
PIPE
11 Line Class Rating Pipe Material T-B04T1 300# A106 GR.B
LINE
12 Pipe Insulation Thickness Corrosion Allowance EC 90mm 1.6mm
13 Fluid State Phase Steam Gas/Vapor Single Phase
14 Sour Service Special Condition N/A N/A
15 Flow Rate Units Min. Nor. Max. kg/h 179 358 394
16 Inlet Pressure Units Min. Nor. Max. kgf/cm²-g 13.36 10.27 9.674
17 Pressure Drop Units Min. Nor. Max. kgf/cm² 9.36 6.23 5.655
18 Inlet Temperature Units Min. Nor. Max. °C 220 220 220
PROCESS 19 Density Units Min. Nor. Max. kg/m³
CONDITIONS 20 Viscosity Units Min. Nor. Max. cP 0.017 0.017 0.017
21 Molecular Weight (MW) Specific Gravity @ Oper. 18.02
22 Spec. Heat Ratio (Cp/Cv) Compressibility (Z) 1.238 0.947
23 Vapor Pressure (Liq.) Cavitation or Flashing kgf/cm²-a N/A
24 Critical Pressure (Liq) Flash (wt%) kgf/cm²-a
25 Design Pressure Min. Max. -1.033 kgf/cm²-g 15.5 kgf/cm²-g
26 Design Temperature Min. Max. 10 °C 260 °C
27 Max.Shutoff DP Solid % 15.5 kgf/cm²
28 Calculated Cv Units Min. Nor. Max. Cv 1.45 3.6 4.18
CALCULATED
29 Travel Units Min. Nor. Max. % 40 63 67
RESULTS
30 Noise dBA @1m Units Min. Nor. Max. dBA 68 74 75
31 MFR Model FISHER EZ 56 MFR Model FISHER DVC6200F/SC-AD
32 Body Type Single Seat Globe 57 Signal: Inlet Outlet FF Protocol 0-2.8 kgf/cm2
33 Body Size Trim Size 1 in 3/4 in 58 Increase Signal Valve: DIRECT
34 End Connec.Size & Rating 1" 300# RF POSITIONER 59 Cam Characteristic LINEAR
35 Rated Cv Characteristic 8.84 EQ% 60 Bypass Gauges N/A YES
36 Body Material WCC Steel 61 Signal Fail. to Valve FO
BODY 37 Bonnet Type Material Style 1 Extension WCC Steel 62 Electric Enclosure Ex ia IIC T5 , NEMA 4X
AND 38 Flow Direct. Flow Act. To Up FTO 63 MFR Model N/A N/A
TRIM 39 Packing Type Material Enviro Seal Graphite ULF 64 Type Power N/A N/A
SOLENOID
40 Lubricator Isolat. Valve N/A N/A 65 When De-Enegr.Valve: N/A
VALVE
41 Guiding No. of Ports Post 1 66 Material Latcher N/A N/A
42 Trim Type Internal Design Micro Form Unbalanced 67 Electric Enclosure N/A
43 Rated Travel Leak Class 3/4 in ANSI IV 68 MFR Model N/A N/A
44 Plug/ Ball/ Disk Material S41600 SST 69 Type Quantity N/A N/A
45 Seat Material S41600 SST SWITCHES 70 Contacts / Rating N/A
46 Cage Stem Material N/A S31600 SST 71 Switching Position N/A
47 Gasket Material S31600 SST/Graphite 72 Electric Enclosure N/A
48 MFR Model FISHER 657 73 MFR Model FISHER 67CFR
49 Type Diaphragm Spring Return AIR SET 74 Set Pressure 4.2 kgf/cm2-g
50 Size Stroke Time 30i < 5 Sec 75 Filter Gauge 5 Micron min YES
ACTUATOR 51 Air Failure Valve: FO 76 Vol. Tank Booster NO NO
52 Handwheel Location N/A 77 Diffuser Lock-up NO NO
ACCESSORY
53 Mounting Position VERTICAL 78 Fire Safe Fireproof NO NO
54 Spring Range 0.4 - 2.0 kgf/cm2-g 79 Mech. Stop Quick Exa. NO NO
55 Include Pressure (Shutoff) 80 Hydro. Pressure YES
85 Vendor EMERSON 81 Leakage YES
PURCHASE TESTS
86 Manufacturer FISHER 82 Cryogenic N/A
87 Requisition No. R2B-P3-206-02-P-MR-00200 83 NACE Requirement N/A
88 Model No. EZ 84 PWHT Requirement N/A
Notes:

INSTRUMENT SPECIFICATION - CONTROL VALVE


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S11.1 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Fieldbus Device Data Sheet
Tag No.: FV -21029
Fieldbus Tag No.:

Service : FA004 MP STM TO DC001 RX

Basic Fieldbus Function Blocks Segment Information


Analog Input Block (AI) 1 Number Device:
1 22
20 Execution (msec)
Discrete Input Block (DI) 4 Number Segment #: DFJB-21024
2 23
15 Execution Time
3 Bias/Gain Station (BG) 0 Execution (msec) 24 LAS Capable: Yes No
Manual Loader (ML) 0 Number 25 Device Current Draw (mA): 19
4
0 Execution (msec) Device Minimum Voltage: 9.
26
Analog Output Block (AO) 1 Number Device Capacitance: 5 nF
5 20 Execution (msec) Polarity-sensitive: Yes No
27
Discrete Output Block (DO) 1 Number Segment Terminator Location:
6 20 Execution (msec)
28
7 Control Selector (CS)
DD Revision: 3
PID,PI,I Controller (PID) 29
8
20 Execution (msec)
CFF Revision: 1.9
Ratio Station (RA) 30
9
P,PD Controller (PD) 0 Number
10 0 Execution (msec)

* Execution time in msec.

Advanced Function Blocks Notes:

11 Device Control (DC)

12 Output Splitter (OS)

13 Signal Characterizer (SC)

14 Lead Lag (LL)

15 Deadtime (DT)

16 Integrator(Totalizer) (IT)

17 Setpoint Ramp Generator (SPG)

18 Input Selector (IS)

19 Arithmetic (AR)

20 Timer (TMR)

21 Analog Alarm (AAL)

INSTRUMENT SPECIFICATION -FOUNDATION FIELDBUS


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S11.2 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Tag Number : FV -21029

1. In-Built surge protector is provided by vendor.

1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S11.3 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
1 Tag No. FV -21030
2 Service FA004 MP STM TO DC001 RX
3 P&ID No. Line No. R2B-P3-206-02-A-DTI-00065 2"-VM-210459-T-B04T1-EA
4 Area Classification Ingress Protection CLASS 1 DIV 2 Gr. B ,C&D, T3 NEMA 4X
GENERAL 5 Ambient Temperature: Unit Min. Max. °C 10 48
6 Allowable Sound dBA Tightness Requirement <85 ANSI IV (standard)
7 Available Air Supply Pressure Unit Min. Max. kgf/cm²-g 4.2 8.0
8 Electric Connection Pneum. Connection 1/2” NPT (F) 1/4” NPT (F)
9 Power Failure Position FO
10 Line Size and Schedule Sch. Outlet Line Sch. 2 in XS 3" STD
PIPE
11 Line Class Rating Pipe Material T-B04T1 300# A106 GR.B
LINE
12 Pipe Insulation Thickness Corrosion Allowance EC 90mm 1.6mm
13 Fluid State Phase Steam Gas/Vapor Single Phase
14 Sour Service Special Condition N/A N/A
15 Flow Rate Units Min. Nor. Max. kg/h 179 358 394
16 Inlet Pressure Units Min. Nor. Max. kgf/cm²-g 13.36 10.27 9.674
17 Pressure Drop Units Min. Nor. Max. kgf/cm² 9.36 6.23 5.655
18 Inlet Temperature Units Min. Nor. Max. °C 220 220 220
PROCESS 19 Density Units Min. Nor. Max. kg/m³
CONDITIONS 20 Viscosity Units Min. Nor. Max. cP 0.017 0.017 0.017
21 Molecular Weight (MW) Specific Gravity @ Oper. 18.02
22 Spec. Heat Ratio (Cp/Cv) Compressibility (Z) 1.238 0.947
23 Vapor Pressure (Liq.) Cavitation or Flashing kgf/cm²-a N/A
24 Critical Pressure (Liq) Flash (wt%) kgf/cm²-a
25 Design Pressure Min. Max. -1.033 kgf/cm²-g 15.5 kgf/cm²-g
26 Design Temperature Min. Max. 10 °C 260 °C
27 Max.Shutoff DP Solid % 15.5 kgf/cm²
28 Calculated Cv Units Min. Nor. Max. Cv 1.45 3.6 4.18
CALCULATED
29 Travel Units Min. Nor. Max. % 40 63 67
RESULTS
30 Noise dBA @1m Units Min. Nor. Max. dBA 68 74 75
31 MFR Model FISHER EZ 56 MFR Model FISHER DVC6200F/SC-AD
32 Body Type Single Seat Globe 57 Signal: Inlet Outlet FF Protocol 0-2.8 kgf/cm2
33 Body Size Trim Size 1 in 3/4 in 58 Increase Signal Valve: DIRECT
34 End Connec.Size & Rating 1" 300# RF POSITIONER 59 Cam Characteristic LINEAR
35 Rated Cv Characteristic 8.84 EQ% 60 Bypass Gauges N/A YES
36 Body Material WCC Steel 61 Signal Fail. to Valve FO
BODY 37 Bonnet Type Material Style 1 Extension WCC Steel 62 Electric Enclosure Ex ia IIC T5 , NEMA 4X
AND 38 Flow Direct. Flow Act. To Up FTO 63 MFR Model N/A N/A
TRIM 39 Packing Type Material Enviro Seal Graphite ULF 64 Type Power N/A N/A
SOLENOID
40 Lubricator Isolat. Valve N/A N/A 65 When De-Enegr.Valve: N/A
VALVE
41 Guiding No. of Ports Post 1 66 Material Latcher N/A N/A
42 Trim Type Internal Design Micro Form Unbalanced 67 Electric Enclosure N/A
43 Rated Travel Leak Class 3/4 in ANSI IV 68 MFR Model N/A N/A
44 Plug/ Ball/ Disk Material S41600 SST 69 Type Quantity N/A N/A
45 Seat Material S41600 SST SWITCHES 70 Contacts / Rating N/A
46 Cage Stem Material N/A S31600 SST 71 Switching Position N/A
47 Gasket Material S31600 SST/Graphite 72 Electric Enclosure N/A
48 MFR Model FISHER 657 73 MFR Model FISHER 67CFR
49 Type Diaphragm Spring Return AIR SET 74 Set Pressure 4.2 kgf/cm2-g
50 Size Stroke Time 30i < 5 Sec 75 Filter Gauge 5 Micron min YES
ACTUATOR 51 Air Failure Valve: FO 76 Vol. Tank Booster NO NO
52 Handwheel Location N/A 77 Diffuser Lock-up NO NO
ACCESSORY
53 Mounting Position VERTICAL 78 Fire Safe Fireproof NO NO
54 Spring Range 0.4 - 2.0 kgf/cm2-g 79 Mech. Stop Quick Exa. NO NO
55 Include Pressure (Shutoff) 80 Hydro. Pressure YES
85 Vendor EMERSON 81 Leakage YES
PURCHASE TESTS
86 Manufacturer FISHER 82 Cryogenic N/A
87 Requisition No. R2B-P3-206-02-P-MR-00200 83 NACE Requirement N/A
88 Model No. EZ 84 PWHT Requirement N/A
Notes:

INSTRUMENT SPECIFICATION - CONTROL VALVE


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S12.1 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Fieldbus Device Data Sheet
Tag No.: FV -21030
Fieldbus Tag No.:

Service : FA004 MP STM TO DC001 RX

Basic Fieldbus Function Blocks Segment Information


Analog Input Block (AI) 1 Number Device:
1 22
20 Execution (msec)
Discrete Input Block (DI) 4 Number Segment #: DFJB-21024
2 23
15 Execution Time
3 Bias/Gain Station (BG) 0 Execution (msec) 24 LAS Capable: Yes No
Manual Loader (ML) 0 Number 25 Device Current Draw (mA): 19
4
0 Execution (msec) Device Minimum Voltage: 9.
26
Analog Output Block (AO) 1 Number Device Capacitance: 5 nF
5 20 Execution (msec) Polarity-sensitive: Yes No
27
Discrete Output Block (DO) 1 Number Segment Terminator Location:
6 20 Execution (msec)
28
7 Control Selector (CS)
DD Revision: 3
PID,PI,I Controller (PID) 29
8
20 Execution (msec)
CFF Revision: 1.9
Ratio Station (RA) 30
9
P,PD Controller (PD) 0 Number
10 0 Execution (msec)

* Execution time in msec.

Advanced Function Blocks Notes:

11 Device Control (DC)

12 Output Splitter (OS)

13 Signal Characterizer (SC)

14 Lead Lag (LL)

15 Deadtime (DT)

16 Integrator(Totalizer) (IT)

17 Setpoint Ramp Generator (SPG)

18 Input Selector (IS)

19 Arithmetic (AR)

20 Timer (TMR)

21 Analog Alarm (AAL)

INSTRUMENT SPECIFICATION -FOUNDATION FIELDBUS


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S12.2 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Tag Number : FV -21030

1. In-Built surge protector is provided by vendor.

1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S12.3 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
1 Tag No. FV -21031
2 Service FA004 MP STM TO DC001 RX
3 P&ID No. Line No. R2B-P3-206-02-A-DTI-00065 2"-VM-210461-T-B04T1-EA
4 Area Classification Ingress Protection CLASS 1 DIV 2 Gr. B ,C&D, T3 NEMA 4X
GENERAL 5 Ambient Temperature: Unit Min. Max. °C 10 48
6 Allowable Sound dBA Tightness Requirement <85 ANSI IV (standard)
7 Available Air Supply Pressure Unit Min. Max. kgf/cm²-g 4.2 8.0
8 Electric Connection Pneum. Connection 1/2” NPT (F) 1/4” NPT (F)
9 Power Failure Position FO
10 Line Size and Schedule Sch. Outlet Line Sch. 2 in XS 3" STD
PIPE
11 Line Class Rating Pipe Material T-B04T1 300# A106 GR.B
LINE
12 Pipe Insulation Thickness Corrosion Allowance EC 90mm 1.6mm
13 Fluid State Phase Steam Gas/Vapor Single Phase
14 Sour Service Special Condition N/A N/A
15 Flow Rate Units Min. Nor. Max. kg/h 179 358 394
16 Inlet Pressure Units Min. Nor. Max. kgf/cm²-g 13.36 10.27 9.674
17 Pressure Drop Units Min. Nor. Max. kgf/cm² 9.36 6.23 5.655
18 Inlet Temperature Units Min. Nor. Max. °C 220 220 220
PROCESS 19 Density Units Min. Nor. Max. kg/m³
CONDITIONS 20 Viscosity Units Min. Nor. Max. cP 0.017 0.017 0.017
21 Molecular Weight (MW) Specific Gravity @ Oper. 18.02
22 Spec. Heat Ratio (Cp/Cv) Compressibility (Z) 1.238 0.947
23 Vapor Pressure (Liq.) Cavitation or Flashing kgf/cm²-a N/A
24 Critical Pressure (Liq) Flash (wt%) kgf/cm²-a
25 Design Pressure Min. Max. -1.033 kgf/cm²-g 15.5 kgf/cm²-g
26 Design Temperature Min. Max. 10 °C 260 °C
27 Max.Shutoff DP Solid % 15.5 kgf/cm²
28 Calculated Cv Units Min. Nor. Max. Cv 1.45 3.6 4.18
CALCULATED
29 Travel Units Min. Nor. Max. % 40 63 67
RESULTS
30 Noise dBA @1m Units Min. Nor. Max. dBA 68 74 75
31 MFR Model FISHER EZ 56 MFR Model FISHER DVC6200F/SC-AD
32 Body Type Single Seat Globe 57 Signal: Inlet Outlet FF Protocol 0-2.8 kgf/cm2
33 Body Size Trim Size 1 in 3/4 in 58 Increase Signal Valve: DIRECT
34 End Connec.Size & Rating 1" 300# RF POSITIONER 59 Cam Characteristic LINEAR
35 Rated Cv Characteristic 8.84 EQ% 60 Bypass Gauges N/A YES
36 Body Material WCC Steel 61 Signal Fail. to Valve FO
BODY 37 Bonnet Type Material Style 1 Extension WCC Steel 62 Electric Enclosure Ex ia IIC T5 , NEMA 4X
AND 38 Flow Direct. Flow Act. To Up FTO 63 MFR Model N/A N/A
TRIM 39 Packing Type Material Enviro Seal Graphite ULF 64 Type Power N/A N/A
SOLENOID
40 Lubricator Isolat. Valve N/A N/A 65 When De-Enegr.Valve: N/A
VALVE
41 Guiding No. of Ports Post 1 66 Material Latcher N/A N/A
42 Trim Type Internal Design Micro Form Unbalanced 67 Electric Enclosure N/A
43 Rated Travel Leak Class 3/4 in ANSI IV 68 MFR Model N/A N/A
44 Plug/ Ball/ Disk Material S41600 SST 69 Type Quantity N/A N/A
45 Seat Material S41600 SST SWITCHES 70 Contacts / Rating N/A
46 Cage Stem Material N/A S31600 SST 71 Switching Position N/A
47 Gasket Material S31600 SST/Graphite 72 Electric Enclosure N/A
48 MFR Model FISHER 657 73 MFR Model FISHER 67CFR
49 Type Diaphragm Spring Return AIR SET 74 Set Pressure 4.2 kgf/cm2-g
50 Size Stroke Time 30i < 5 Sec 75 Filter Gauge 5 Micron min YES
ACTUATOR 51 Air Failure Valve: FO 76 Vol. Tank Booster NO NO
52 Handwheel Location N/A 77 Diffuser Lock-up NO NO
ACCESSORY
53 Mounting Position VERTICAL 78 Fire Safe Fireproof NO NO
54 Spring Range 0.4 - 2.0 kgf/cm2-g 79 Mech. Stop Quick Exa. NO NO
55 Include Pressure (Shutoff) 80 Hydro. Pressure YES
85 Vendor EMERSON 81 Leakage YES
PURCHASE TESTS
86 Manufacturer FISHER 82 Cryogenic N/A
87 Requisition No. R2B-P3-206-02-P-MR-00200 83 NACE Requirement N/A
88 Model No. EZ 84 PWHT Requirement N/A
Notes:

INSTRUMENT SPECIFICATION - CONTROL VALVE


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S13.1 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Fieldbus Device Data Sheet
Tag No.: FV -21031
Fieldbus Tag No.:

Service : FA004 MP STM TO DC001 RX

Basic Fieldbus Function Blocks Segment Information


Analog Input Block (AI) 1 Number Device:
1 22
20 Execution (msec)
Discrete Input Block (DI) 4 Number Segment #: DFJB-21022
2 23
15 Execution Time
3 Bias/Gain Station (BG) 0 Execution (msec) 24 LAS Capable: Yes No
Manual Loader (ML) 0 Number 25 Device Current Draw (mA): 19
4
0 Execution (msec) Device Minimum Voltage: 9.
26
Analog Output Block (AO) 1 Number Device Capacitance: 5 nF
5 20 Execution (msec) Polarity-sensitive: Yes No
27
Discrete Output Block (DO) 1 Number Segment Terminator Location:
6 20 Execution (msec)
28
7 Control Selector (CS)
DD Revision: 3
PID,PI,I Controller (PID) 29
8
20 Execution (msec)
CFF Revision: 1.9
Ratio Station (RA) 30
9
P,PD Controller (PD) 0 Number
10 0 Execution (msec)

* Execution time in msec.

Advanced Function Blocks Notes:

11 Device Control (DC)

12 Output Splitter (OS)

13 Signal Characterizer (SC)

14 Lead Lag (LL)

15 Deadtime (DT)

16 Integrator(Totalizer) (IT)

17 Setpoint Ramp Generator (SPG)

18 Input Selector (IS)

19 Arithmetic (AR)

20 Timer (TMR)

21 Analog Alarm (AAL)

INSTRUMENT SPECIFICATION -FOUNDATION FIELDBUS


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S13.2 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Tag Number : FV -21031

1. In-Built surge protector is provided by vendor.

1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S13.3 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
1 Tag No. FV -21032
2 Service FA004 MP STM TO DC001 RX
3 P&ID No. Line No. R2B-P3-206-02-A-DTI-00065 2"-VM-210463-T-B04T1-EA
4 Area Classification Ingress Protection CLASS 1 DIV 2 Gr. B ,C&D, T3 NEMA 4X
GENERAL 5 Ambient Temperature: Unit Min. Max. °C 10 48
6 Allowable Sound dBA Tightness Requirement <85 ANSI IV (standard)
7 Available Air Supply Pressure Unit Min. Max. kgf/cm²-g 4.2 8.0
8 Electric Connection Pneum. Connection 1/2” NPT (F) 1/4” NPT (F)
9 Power Failure Position FO
10 Line Size and Schedule Sch. Outlet Line Sch. 2 in XS 3" STD
PIPE
11 Line Class Rating Pipe Material T-B04T1 300# A106 GR.B
LINE
12 Pipe Insulation Thickness Corrosion Allowance EC 90mm 1.6mm
13 Fluid State Phase Steam Gas/Vapor Single Phase
14 Sour Service Special Condition N/A N/A
15 Flow Rate Units Min. Nor. Max. kg/h 179 358 394
16 Inlet Pressure Units Min. Nor. Max. kgf/cm²-g 13.36 10.27 9.674
17 Pressure Drop Units Min. Nor. Max. kgf/cm² 9.36 6.23 5.655
18 Inlet Temperature Units Min. Nor. Max. °C 220 220 220
PROCESS 19 Density Units Min. Nor. Max. kg/m³
CONDITIONS 20 Viscosity Units Min. Nor. Max. cP 0.017 0.017 0.017
21 Molecular Weight (MW) Specific Gravity @ Oper. 18.02
22 Spec. Heat Ratio (Cp/Cv) Compressibility (Z) 1.238 0.947
23 Vapor Pressure (Liq.) Cavitation or Flashing kgf/cm²-a N/A
24 Critical Pressure (Liq) Flash (wt%) kgf/cm²-a
25 Design Pressure Min. Max. -1.033 kgf/cm²-g 15.5 kgf/cm²-g
26 Design Temperature Min. Max. 10 °C 260 °C
27 Max.Shutoff DP Solid % 15.5 kgf/cm²
28 Calculated Cv Units Min. Nor. Max. Cv 1.45 3.6 4.18
CALCULATED
29 Travel Units Min. Nor. Max. % 40 63 67
RESULTS
30 Noise dBA @1m Units Min. Nor. Max. dBA 68 74 75
31 MFR Model FISHER EZ 56 MFR Model FISHER DVC6200F/SC-AD
32 Body Type Single Seat Globe 57 Signal: Inlet Outlet FF Protocol 0-2.8 kgf/cm2
33 Body Size Trim Size 1 in 3/4 in 58 Increase Signal Valve: DIRECT
34 End Connec.Size & Rating 1" 300# RF POSITIONER 59 Cam Characteristic LINEAR
35 Rated Cv Characteristic 8.84 EQ% 60 Bypass Gauges N/A YES
36 Body Material WCC Steel 61 Signal Fail. to Valve FO
BODY 37 Bonnet Type Material Style 1 Extension WCC Steel 62 Electric Enclosure Ex ia IIC T5 , NEMA 4X
AND 38 Flow Direct. Flow Act. To Up FTO 63 MFR Model N/A N/A
TRIM 39 Packing Type Material Enviro Seal Graphite ULF 64 Type Power N/A N/A
SOLENOID
40 Lubricator Isolat. Valve N/A N/A 65 When De-Enegr.Valve: N/A
VALVE
41 Guiding No. of Ports Post 1 66 Material Latcher N/A N/A
42 Trim Type Internal Design Micro Form Unbalanced 67 Electric Enclosure N/A
43 Rated Travel Leak Class 3/4 in ANSI IV 68 MFR Model N/A N/A
44 Plug/ Ball/ Disk Material S41600 SST 69 Type Quantity N/A N/A
45 Seat Material S41600 SST SWITCHES 70 Contacts / Rating N/A
46 Cage Stem Material N/A S31600 SST 71 Switching Position N/A
47 Gasket Material S31600 SST/Graphite 72 Electric Enclosure N/A
48 MFR Model FISHER 657 73 MFR Model FISHER 67CFR
49 Type Diaphragm Spring Return AIR SET 74 Set Pressure 4.2 kgf/cm2-g
50 Size Stroke Time 30i < 5 Sec 75 Filter Gauge 5 Micron min YES
ACTUATOR 51 Air Failure Valve: FO 76 Vol. Tank Booster NO NO
52 Handwheel Location N/A 77 Diffuser Lock-up NO NO
ACCESSORY
53 Mounting Position VERTICAL 78 Fire Safe Fireproof NO NO
54 Spring Range 0.4 - 2.0 kgf/cm2-g 79 Mech. Stop Quick Exa. NO NO
55 Include Pressure (Shutoff) 80 Hydro. Pressure YES
85 Vendor EMERSON 81 Leakage YES
PURCHASE TESTS
86 Manufacturer FISHER 82 Cryogenic N/A
87 Requisition No. R2B-P3-206-02-P-MR-00200 83 NACE Requirement N/A
88 Model No. EZ 84 PWHT Requirement N/A
Notes:

INSTRUMENT SPECIFICATION - CONTROL VALVE


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S14.1 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Fieldbus Device Data Sheet
Tag No.: FV -21032
Fieldbus Tag No.:

Service : FA004 MP STM TO DC001 RX

Basic Fieldbus Function Blocks Segment Information


Analog Input Block (AI) 1 Number Device:
1 22
20 Execution (msec)
Discrete Input Block (DI) 4 Number Segment #: DFJB-21020
2 23
15 Execution Time
3 Bias/Gain Station (BG) 0 Execution (msec) 24 LAS Capable: Yes No
Manual Loader (ML) 0 Number 25 Device Current Draw (mA): 19
4
0 Execution (msec) Device Minimum Voltage: 9.
26
Analog Output Block (AO) 1 Number Device Capacitance: 5 nF
5 20 Execution (msec) Polarity-sensitive: Yes No
27
Discrete Output Block (DO) 1 Number Segment Terminator Location:
6 20 Execution (msec)
28
7 Control Selector (CS)
DD Revision: 3
PID,PI,I Controller (PID) 29
8
20 Execution (msec)
CFF Revision: 1.9
Ratio Station (RA) 30
9
P,PD Controller (PD) 0 Number
10 0 Execution (msec)

* Execution time in msec.

Advanced Function Blocks Notes:

11 Device Control (DC)

12 Output Splitter (OS)

13 Signal Characterizer (SC)

14 Lead Lag (LL)

15 Deadtime (DT)

16 Integrator(Totalizer) (IT)

17 Setpoint Ramp Generator (SPG)

18 Input Selector (IS)

19 Arithmetic (AR)

20 Timer (TMR)

21 Analog Alarm (AAL)

INSTRUMENT SPECIFICATION -FOUNDATION FIELDBUS


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S14.2 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Tag Number : FV -21032

1. In-Built surge protector is provided by vendor.

1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S14.3 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
1 Tag No. FV -21033
2 Service FA004 MP STM TO DC001 RX
3 P&ID No. Line No. R2B-P3-206-02-A-DTI-00065 2"-VM-210469-T-B04T1-EA
4 Area Classification Ingress Protection CLASS 1 DIV 2 Gr. B ,C&D, T3 NEMA 4X
GENERAL 5 Ambient Temperature: Unit Min. Max. °C 10 48
6 Allowable Sound dBA Tightness Requirement <85 ANSI IV (standard)
7 Available Air Supply Pressure Unit Min. Max. kgf/cm²-g 4.2 8.0
8 Electric Connection Pneum. Connection 1/2” NPT (F) 1/4” NPT (F)
9 Power Failure Position FO
10 Line Size and Schedule Sch. Outlet Line Sch. 2 in XS 3" STD
PIPE
11 Line Class Rating Pipe Material T-B04T1 300# A106 GR.B
LINE
12 Pipe Insulation Thickness Corrosion Allowance EC 90mm 1.6mm
13 Fluid State Phase Steam Gas/Vapor Single Phase
14 Sour Service Special Condition N/A N/A
15 Flow Rate Units Min. Nor. Max. kg/h 179 358 394
16 Inlet Pressure Units Min. Nor. Max. kgf/cm²-g 13.36 10.27 9.674
17 Pressure Drop Units Min. Nor. Max. kgf/cm² 9.36 6.23 5.655
18 Inlet Temperature Units Min. Nor. Max. °C 220 220 220
PROCESS 19 Density Units Min. Nor. Max. kg/m³
CONDITIONS 20 Viscosity Units Min. Nor. Max. cP 0.017 0.017 0.017
21 Molecular Weight (MW) Specific Gravity @ Oper. 18.02
22 Spec. Heat Ratio (Cp/Cv) Compressibility (Z) 1.238 0.947
23 Vapor Pressure (Liq.) Cavitation or Flashing kgf/cm²-a N/A
24 Critical Pressure (Liq) Flash (wt%) kgf/cm²-a
25 Design Pressure Min. Max. -1.033 kgf/cm²-g 15.5 kgf/cm²-g
26 Design Temperature Min. Max. 10 °C 260 °C
27 Max.Shutoff DP Solid % 15.5 kgf/cm²
28 Calculated Cv Units Min. Nor. Max. Cv 1.45 3.6 4.18
CALCULATED
29 Travel Units Min. Nor. Max. % 40 63 67
RESULTS
30 Noise dBA @1m Units Min. Nor. Max. dBA 68 74 75
31 MFR Model FISHER EZ 56 MFR Model FISHER DVC6200F/SC-AD
32 Body Type Single Seat Globe 57 Signal: Inlet Outlet FF Protocol 0-2.8 kgf/cm2
33 Body Size Trim Size 1 in 3/4 in 58 Increase Signal Valve: DIRECT
34 End Connec.Size & Rating 1" 300# RF POSITIONER 59 Cam Characteristic LINEAR
35 Rated Cv Characteristic 8.84 EQ% 60 Bypass Gauges N/A YES
36 Body Material WCC Steel 61 Signal Fail. to Valve FO
BODY 37 Bonnet Type Material Style 1 Extension WCC Steel 62 Electric Enclosure Ex ia IIC T5 , NEMA 4X
AND 38 Flow Direct. Flow Act. To Up FTO 63 MFR Model N/A N/A
TRIM 39 Packing Type Material Enviro Seal Graphite ULF 64 Type Power N/A N/A
SOLENOID
40 Lubricator Isolat. Valve N/A N/A 65 When De-Enegr.Valve: N/A
VALVE
41 Guiding No. of Ports Post 1 66 Material Latcher N/A N/A
42 Trim Type Internal Design Micro Form Unbalanced 67 Electric Enclosure N/A
43 Rated Travel Leak Class 3/4 in ANSI IV 68 MFR Model N/A N/A
44 Plug/ Ball/ Disk Material S41600 SST 69 Type Quantity N/A N/A
45 Seat Material S41600 SST SWITCHES 70 Contacts / Rating N/A
46 Cage Stem Material N/A S31600 SST 71 Switching Position N/A
47 Gasket Material S31600 SST/Graphite 72 Electric Enclosure N/A
48 MFR Model FISHER 657 73 MFR Model FISHER 67CFR
49 Type Diaphragm Spring Return AIR SET 74 Set Pressure 4.2 kgf/cm2-g
50 Size Stroke Time 30i < 5 Sec 75 Filter Gauge 5 Micron min YES
ACTUATOR 51 Air Failure Valve: FO 76 Vol. Tank Booster NO NO
52 Handwheel Location N/A 77 Diffuser Lock-up NO NO
ACCESSORY
53 Mounting Position VERTICAL 78 Fire Safe Fireproof NO NO
54 Spring Range 0.4 - 2.0 kgf/cm2-g 79 Mech. Stop Quick Exa. NO NO
55 Include Pressure (Shutoff) 80 Hydro. Pressure YES
85 Vendor EMERSON 81 Leakage YES
PURCHASE TESTS
86 Manufacturer FISHER 82 Cryogenic N/A
87 Requisition No. R2B-P3-206-02-P-MR-00200 83 NACE Requirement N/A
88 Model No. EZ 84 PWHT Requirement N/A
Notes:

INSTRUMENT SPECIFICATION - CONTROL VALVE


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S15.1 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Fieldbus Device Data Sheet
Tag No.: FV -21033
Fieldbus Tag No.:

Service : FA004 MP STM TO DC001 RX

Basic Fieldbus Function Blocks Segment Information


Analog Input Block (AI) 1 Number Device:
1 22
20 Execution (msec)
Discrete Input Block (DI) 4 Number Segment #: DFJB-21027
2 23
15 Execution Time
3 Bias/Gain Station (BG) 0 Execution (msec) 24 LAS Capable: Yes No
Manual Loader (ML) 0 Number 25 Device Current Draw (mA): 19
4
0 Execution (msec) Device Minimum Voltage: 9.
26
Analog Output Block (AO) 1 Number Device Capacitance: 5 nF
5 20 Execution (msec) Polarity-sensitive: Yes No
27
Discrete Output Block (DO) 1 Number Segment Terminator Location:
6 20 Execution (msec)
28
7 Control Selector (CS)
DD Revision: 3
PID,PI,I Controller (PID) 29
8
20 Execution (msec)
CFF Revision: 1.9
Ratio Station (RA) 30
9
P,PD Controller (PD) 0 Number
10 0 Execution (msec)

* Execution time in msec.

Advanced Function Blocks Notes:

11 Device Control (DC)

12 Output Splitter (OS)

13 Signal Characterizer (SC)

14 Lead Lag (LL)

15 Deadtime (DT)

16 Integrator(Totalizer) (IT)

17 Setpoint Ramp Generator (SPG)

18 Input Selector (IS)

19 Arithmetic (AR)

20 Timer (TMR)

21 Analog Alarm (AAL)

INSTRUMENT SPECIFICATION -FOUNDATION FIELDBUS


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S15.2 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Tag Number : FV -21033

1. In-Built surge protector is provided by vendor.

1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S15.3 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
1 Tag No. FV -21034
2 Service FA004 MP STM TO DC001 RX
3 P&ID No. Line No. R2B-P3-206-02-A-DTI-00065 2"-VM-210471-T-B04T1-EA
4 Area Classification Ingress Protection CLASS 1 DIV 2 Gr. B ,C&D, T3 NEMA 4X
GENERAL 5 Ambient Temperature: Unit Min. Max. °C 10 48
6 Allowable Sound dBA Tightness Requirement <85 ANSI IV (standard)
7 Available Air Supply Pressure Unit Min. Max. kgf/cm²-g 4.2 8.0
8 Electric Connection Pneum. Connection 1/2” NPT (F) 1/4” NPT (F)
9 Power Failure Position FO
10 Line Size and Schedule Sch. Outlet Line Sch. 2 in XS 3" STD
PIPE
11 Line Class Rating Pipe Material T-B04T1 300# A106 GR.B
LINE
12 Pipe Insulation Thickness Corrosion Allowance EC 90mm 1.6mm
13 Fluid State Phase Steam Gas/Vapor Single Phase
14 Sour Service Special Condition N/A N/A
15 Flow Rate Units Min. Nor. Max. kg/h 454 358 394
16 Inlet Pressure Units Min. Nor. Max. kgf/cm²-g 13.36 10.27 9.674
17 Pressure Drop Units Min. Nor. Max. kgf/cm² 9.36 6.23 5.655
18 Inlet Temperature Units Min. Nor. Max. °C 220 220 220
PROCESS 19 Density Units Min. Nor. Max. kg/m³
CONDITIONS 20 Viscosity Units Min. Nor. Max. cP 0.017 0.017 0.017
21 Molecular Weight (MW) Specific Gravity @ Oper. 18.02
22 Spec. Heat Ratio (Cp/Cv) Compressibility (Z) 1.238 0.947
23 Vapor Pressure (Liq.) Cavitation or Flashing kgf/cm²-a N/A
24 Critical Pressure (Liq) Flash (wt%) kgf/cm²-a
25 Design Pressure Min. Max. -1.033 kgf/cm²-g 15.5 kgf/cm²-g
26 Design Temperature Min. Max. 10 °C 260 °C
27 Max.Shutoff DP Solid % 15.5 kgf/cm²
28 Calculated Cv Units Min. Nor. Max. Cv 3.59 3.6 4.18
CALCULATED
29 Travel Units Min. Nor. Max. % 63 63 67
RESULTS
30 Noise dBA @1m Units Min. Nor. Max. dBA 78 74 75
31 MFR Model FISHER EZ 56 MFR Model FISHER DVC6200F/SC-AD
32 Body Type Single Seat Globe 57 Signal: Inlet Outlet FF Protocol 0-2.8 kgf/cm2
33 Body Size Trim Size 1 in 3/4 in 58 Increase Signal Valve: DIRECT
34 End Connec.Size & Rating 1" 300# RF POSITIONER 59 Cam Characteristic LINEAR
35 Rated Cv Characteristic 8.84 EQ% 60 Bypass Gauges N/A YES
36 Body Material WCC Steel 61 Signal Fail. to Valve FO
BODY 37 Bonnet Type Material Style 1 Extension WCC Steel 62 Electric Enclosure Ex ia IIC T5 , NEMA 4X
AND 38 Flow Direct. Flow Act. To Up FTO 63 MFR Model N/A N/A
TRIM 39 Packing Type Material Enviro Seal Graphite ULF 64 Type Power N/A N/A
SOLENOID
40 Lubricator Isolat. Valve N/A N/A 65 When De-Enegr.Valve: N/A
VALVE
41 Guiding No. of Ports Post 1 66 Material Latcher N/A N/A
42 Trim Type Internal Design Micro Form Unbalanced 67 Electric Enclosure N/A
43 Rated Travel Leak Class 3/4 in ANSI IV 68 MFR Model N/A N/A
44 Plug/ Ball/ Disk Material S41600 SST 69 Type Quantity N/A N/A
45 Seat Material S41600 SST SWITCHES 70 Contacts / Rating N/A
46 Cage Stem Material N/A S31600 SST 71 Switching Position N/A
47 Gasket Material S31600 SST/Graphite 72 Electric Enclosure N/A
48 MFR Model FISHER 657 73 MFR Model FISHER 67CFR
49 Type Diaphragm Spring Return AIR SET 74 Set Pressure 4.2 kgf/cm2-g
50 Size Stroke Time 30i < 5 Sec 75 Filter Gauge 5 Micron min YES
ACTUATOR 51 Air Failure Valve: FO 76 Vol. Tank Booster NO NO
52 Handwheel Location N/A 77 Diffuser Lock-up NO NO
ACCESSORY
53 Mounting Position VERTICAL 78 Fire Safe Fireproof NO NO
54 Spring Range 0.4 - 2.0 kgf/cm2-g 79 Mech. Stop Quick Exa. NO NO
55 Include Pressure (Shutoff) 80 Hydro. Pressure YES
85 Vendor EMERSON 81 Leakage YES
PURCHASE TESTS
86 Manufacturer FISHER 82 Cryogenic N/A
87 Requisition No. R2B-P3-206-02-P-MR-00200 83 NACE Requirement N/A
88 Model No. EZ 84 PWHT Requirement N/A
Notes:

INSTRUMENT SPECIFICATION - CONTROL VALVE


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S16.1 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Fieldbus Device Data Sheet
Tag No.: FV -21034
Fieldbus Tag No.:

Service : FA004 MP STM TO DC001 RX

Basic Fieldbus Function Blocks Segment Information


Analog Input Block (AI) 1 Number Device:
1 22
20 Execution (msec)
Discrete Input Block (DI) 4 Number Segment #: DFJB-21022
2 23
15 Execution Time
3 Bias/Gain Station (BG) 0 Execution (msec) 24 LAS Capable: Yes No
Manual Loader (ML) 0 Number 25 Device Current Draw (mA): 19
4
0 Execution (msec) Device Minimum Voltage: 9.
26
Analog Output Block (AO) 1 Number Device Capacitance: 5 nF
5 20 Execution (msec) Polarity-sensitive: Yes No
27
Discrete Output Block (DO) 1 Number Segment Terminator Location:
6 20 Execution (msec)
28
7 Control Selector (CS)
DD Revision: 3
PID,PI,I Controller (PID) 29
8
20 Execution (msec)
CFF Revision: 1.9
Ratio Station (RA) 30
9
P,PD Controller (PD) 0 Number
10 0 Execution (msec)

* Execution time in msec.

Advanced Function Blocks Notes:

11 Device Control (DC)

12 Output Splitter (OS)

13 Signal Characterizer (SC)

14 Lead Lag (LL)

15 Deadtime (DT)

16 Integrator(Totalizer) (IT)

17 Setpoint Ramp Generator (SPG)

18 Input Selector (IS)

19 Arithmetic (AR)

20 Timer (TMR)

21 Analog Alarm (AAL)

INSTRUMENT SPECIFICATION -FOUNDATION FIELDBUS


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S16.2 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Tag Number : FV -21034

1. In-Built surge protector is provided by vendor.

1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S16.3 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
1 Tag No. FV -21035
2 Service FA004 MP STM TO DC001 RX
3 P&ID No. Line No. R2B-P3-206-02-A-DTI-00065 2"-VM-210473-T-B04T1-EA
4 Area Classification Ingress Protection CLASS 1 DIV 2 Gr. B ,C&D, T3 NEMA 4X
GENERAL 5 Ambient Temperature: Unit Min. Max. °C 10 48
6 Allowable Sound dBA Tightness Requirement <85 ANSI IV (standard)
7 Available Air Supply Pressure Unit Min. Max. kgf/cm²-g 4.2 8.0
8 Electric Connection Pneum. Connection 1/2” NPT (F) 1/4” NPT (F)
9 Power Failure Position FO
10 Line Size and Schedule Sch. Outlet Line Sch. 2 in XS 3" STD
PIPE
11 Line Class Rating Pipe Material T-B04T1 300# A106 GR.B
LINE
12 Pipe Insulation Thickness Corrosion Allowance EC 90mm 1.6mm
13 Fluid State Phase Steam Gas/Vapor Single Phase
14 Sour Service Special Condition N/A N/A
15 Flow Rate Units Min. Nor. Max. kg/h 454 358 394
16 Inlet Pressure Units Min. Nor. Max. kgf/cm²-g 13.36 10.27 9.674
17 Pressure Drop Units Min. Nor. Max. kgf/cm² 9.36 6.23 5.655
18 Inlet Temperature Units Min. Nor. Max. °C 220 220 220
PROCESS 19 Density Units Min. Nor. Max. kg/m³
CONDITIONS 20 Viscosity Units Min. Nor. Max. cP 0.017 0.017 0.017
21 Molecular Weight (MW) Specific Gravity @ Oper. 18.02
22 Spec. Heat Ratio (Cp/Cv) Compressibility (Z) 1.238 0.947
23 Vapor Pressure (Liq.) Cavitation or Flashing kgf/cm²-a N/A
24 Critical Pressure (Liq) Flash (wt%) kgf/cm²-a
25 Design Pressure Min. Max. -1.033 kgf/cm²-g 15.5 kgf/cm²-g
26 Design Temperature Min. Max. 10 °C 260 °C
27 Max.Shutoff DP Solid % 15.5 kgf/cm²
28 Calculated Cv Units Min. Nor. Max. Cv 3.59 3.6 4.18
CALCULATED
29 Travel Units Min. Nor. Max. % 63 63 67
RESULTS
30 Noise dBA @1m Units Min. Nor. Max. dBA 78 74 75
31 MFR Model FISHER EZ 56 MFR Model FISHER DVC6200F/SC-AD
32 Body Type Single Seat Globe 57 Signal: Inlet Outlet FF Protocol 0-2.8 kgf/cm2
33 Body Size Trim Size 1 in 3/4 in 58 Increase Signal Valve: DIRECT
34 End Connec.Size & Rating 1" 300# RF POSITIONER 59 Cam Characteristic LINEAR
35 Rated Cv Characteristic 8.84 EQ% 60 Bypass Gauges N/A YES
36 Body Material WCC Steel 61 Signal Fail. to Valve FO
BODY 37 Bonnet Type Material Style 1 Extension WCC Steel 62 Electric Enclosure Ex ia IIC T5 , NEMA 4X
AND 38 Flow Direct. Flow Act. To Up FTO 63 MFR Model N/A N/A
TRIM 39 Packing Type Material Enviro Seal Graphite ULF 64 Type Power N/A N/A
SOLENOID
40 Lubricator Isolat. Valve N/A N/A 65 When De-Enegr.Valve: N/A
VALVE
41 Guiding No. of Ports Post 1 66 Material Latcher N/A N/A
42 Trim Type Internal Design Micro Form Unbalanced 67 Electric Enclosure N/A
43 Rated Travel Leak Class 3/4 in ANSI IV 68 MFR Model N/A N/A
44 Plug/ Ball/ Disk Material S41600 SST 69 Type Quantity N/A N/A
45 Seat Material S41600 SST SWITCHES 70 Contacts / Rating N/A
46 Cage Stem Material N/A S31600 SST 71 Switching Position N/A
47 Gasket Material S31600 SST/Graphite 72 Electric Enclosure N/A
48 MFR Model FISHER 657 73 MFR Model FISHER 67CFR
49 Type Diaphragm Spring Return AIR SET 74 Set Pressure 4.2 kgf/cm2-g
50 Size Stroke Time 30i < 5 Sec 75 Filter Gauge 5 Micron min YES
ACTUATOR 51 Air Failure Valve: FO 76 Vol. Tank Booster NO NO
52 Handwheel Location N/A 77 Diffuser Lock-up NO NO
ACCESSORY
53 Mounting Position VERTICAL 78 Fire Safe Fireproof NO NO
54 Spring Range 0.4 - 2.0 kgf/cm2-g 79 Mech. Stop Quick Exa. NO NO
55 Include Pressure (Shutoff) 80 Hydro. Pressure YES
85 Vendor EMERSON 81 Leakage YES
PURCHASE TESTS
86 Manufacturer FISHER 82 Cryogenic N/A
87 Requisition No. R2B-P3-206-02-P-MR-00200 83 NACE Requirement N/A
88 Model No. EZ 84 PWHT Requirement N/A
Notes:

INSTRUMENT SPECIFICATION - CONTROL VALVE


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S17.1 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Fieldbus Device Data Sheet
Tag No.: FV -21035
Fieldbus Tag No.:

Service : FA004 MP STM TO DC001 RX

Basic Fieldbus Function Blocks Segment Information


Analog Input Block (AI) 1 Number Device:
1 22
20 Execution (msec)
Discrete Input Block (DI) 4 Number Segment #: DFJB-21020
2 23
15 Execution Time
3 Bias/Gain Station (BG) 0 Execution (msec) 24 LAS Capable: Yes No
Manual Loader (ML) 0 Number 25 Device Current Draw (mA): 19
4
0 Execution (msec) Device Minimum Voltage: 9.
26
Analog Output Block (AO) 1 Number Device Capacitance: 5 nF
5 20 Execution (msec) Polarity-sensitive: Yes No
27
Discrete Output Block (DO) 1 Number Segment Terminator Location:
6 20 Execution (msec)
28
7 Control Selector (CS)
DD Revision: 3
PID,PI,I Controller (PID) 29
8
20 Execution (msec)
CFF Revision: 1.9
Ratio Station (RA) 30
9
P,PD Controller (PD) 0 Number
10 0 Execution (msec)

* Execution time in msec.

Advanced Function Blocks Notes:

11 Device Control (DC)

12 Output Splitter (OS)

13 Signal Characterizer (SC)

14 Lead Lag (LL)

15 Deadtime (DT)

16 Integrator(Totalizer) (IT)

17 Setpoint Ramp Generator (SPG)

18 Input Selector (IS)

19 Arithmetic (AR)

20 Timer (TMR)

21 Analog Alarm (AAL)

INSTRUMENT SPECIFICATION -FOUNDATION FIELDBUS


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S17.2 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Tag Number : FV -21035

1. In-Built surge protector is provided by vendor.

1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S17.3 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
1 Tag No. FV -21039
2 Service FA004 MP STM TO DC001 RX
3 P&ID No. Line No. R2B-P3-206-02-A-DTI-00065 3"-VM-210426-T-B04T1-EC
4 Area Classification Ingress Protection CLASS 1 DIV 2 Gr. B ,C&D, T3 NEMA 4X
GENERAL 5 Ambient Temperature: Unit Min. Max. °C 10 48
6 Allowable Sound dBA Tightness Requirement <85 ANSI IV (standard)
7 Available Air Supply Pressure Unit Min. Max. kgf/cm²-g 4.2 8.0
8 Electric Connection Pneum. Connection 1/2” NPT (F) 1/4” NPT (F)
9 Power Failure Position FO
10 Line Size and Schedule Sch. Outlet Line Sch. 3 in STD 3" STD
PIPE
11 Line Class Rating Pipe Material T-B04T1 300# A106 GR.B, SMLS
LINE
12 Pipe Insulation Thickness Corrosion Allowance EC 90mm 1.6mm
13 Fluid State Phase Steam Gas/Vapor Single Phase
14 Sour Service Special Condition N/A N/A
15 Flow Rate Units Min. Nor. Max. kg/h 454 623 1021
16 Inlet Pressure Units Min. Nor. Max. kgf/cm²-g 13.34 10.3 9.45
17 Pressure Drop Units Min. Nor. Max. kgf/cm² 10.61 6.49 4.668
18 Inlet Temperature Units Min. Nor. Max. °C 220 220 220
PROCESS 19 Density Units Min. Nor. Max. kg/m³
CONDITIONS 20 Viscosity Units Min. Nor. Max. cP 0.017 0.017 0.017
21 Molecular Weight (MW) Specific Gravity @ Oper. 18.02
22 Spec. Heat Ratio (Cp/Cv) Compressibility (Z) 1.238 0.947
23 Vapor Pressure (Liq.) Cavitation or Flashing kgf/cm²-a N/A
24 Critical Pressure (Liq) Flash (wt%) kgf/cm²-a
25 Design Pressure Min. Max. -1.033 kgf/cm²-g 15.5 kgf/cm²-g
26 Design Temperature Min. Max. 10 °C 260 °C
27 Max.Shutoff DP Solid % 15.5 kgf/cm²
28 Calculated Cv Units Min. Nor. Max. Cv 3.63 5.9 11.
CALCULATED
29 Travel Units Min. Nor. Max. % 21 38 70
RESULTS
30 Noise dBA @1m Units Min. Nor. Max. dBA 78 79 82
31 MFR Model FISHER EZ 56 MFR Model FISHER DVC6200F/SC-AD
32 Body Type Single Seat Globe 57 Signal: Inlet Outlet FF Protocol 0-2.8 kgf/cm2
33 Body Size Trim Size 1.5 in 1 in 58 Increase Signal Valve: DIRECT
34 End Connec.Size & Rating 1.5" 300# RF POSITIONER 59 Cam Characteristic LINEAR
35 Rated Cv Characteristic 16.7 Linear 60 Bypass Gauges N/A YES
36 Body Material WCC Steel 61 Signal Fail. to Valve FO
BODY 37 Bonnet Type Material Style 1 Extension WCC Steel 62 Electric Enclosure Ex ia IIC T5 , NEMA 4X
AND 38 Flow Direct. Flow Act. To Up FTO 63 MFR Model N/A N/A
TRIM 39 Packing Type Material Enviro Seal Graphite ULF 64 Type Power N/A N/A
SOLENOID
40 Lubricator Isolat. Valve N/A N/A 65 When De-Enegr.Valve: N/A
VALVE
41 Guiding No. of Ports Post 1 66 Material Latcher N/A N/A
42 Trim Type Internal Design Standard Unbalanced 67 Electric Enclosure N/A
43 Rated Travel Leak Class 3/4 in ANSI IV 68 MFR Model N/A N/A
44 Plug/ Ball/ Disk Material S41600 SST 69 Type Quantity N/A N/A
45 Seat Material S41600 SST SWITCHES 70 Contacts / Rating N/A
46 Cage Stem Material N/A S31600 SST 71 Switching Position N/A
47 Gasket Material S31600 SST/Graphite 72 Electric Enclosure N/A
48 MFR Model FISHER 657 73 MFR Model FISHER 67CFR
49 Type Diaphragm Spring Return AIR SET 74 Set Pressure 4.2 kgf/cm2-g
50 Size Stroke Time 34i < 5 Sec 75 Filter Gauge 5 Micron min YES
ACTUATOR 51 Air Failure Valve: FO 76 Vol. Tank Booster NO NO
52 Handwheel Location N/A 77 Diffuser Lock-up NO NO
ACCESSORY
53 Mounting Position VERTICAL 78 Fire Safe Fireproof NO NO
54 Spring Range 0.4 - 2.0 kgf/cm2-g 79 Mech. Stop Quick Exa. YES (DOWN STOP) NO
55 Include Pressure (Shutoff) 80 Hydro. Pressure YES
85 Vendor EMERSON 81 Leakage YES
PURCHASE TESTS
86 Manufacturer FISHER 82 Cryogenic N/A
87 Requisition No. R2B-P3-206-02-P-MR-00200 83 NACE Requirement N/A
88 Model No. EZ 84 PWHT Requirement N/A
Notes:

INSTRUMENT SPECIFICATION - CONTROL VALVE


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S18.1 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Fieldbus Device Data Sheet
Tag No.: FV -21039
Fieldbus Tag No.:

Service : FA004 MP STM TO DC001 RX

Basic Fieldbus Function Blocks Segment Information


Analog Input Block (AI) 1 Number Device:
1 22
20 Execution (msec)
Discrete Input Block (DI) 4 Number Segment #: DFJB-21036
2 23
15 Execution Time
3 Bias/Gain Station (BG) 0 Execution (msec) 24 LAS Capable: Yes No
Manual Loader (ML) 0 Number 25 Device Current Draw (mA): 19
4
0 Execution (msec) Device Minimum Voltage: 9.
26
Analog Output Block (AO) 1 Number Device Capacitance: 5 nF
5 20 Execution (msec) Polarity-sensitive: Yes No
27
Discrete Output Block (DO) 1 Number Segment Terminator Location:
6 20 Execution (msec)
28
7 Control Selector (CS)
DD Revision: 3
PID,PI,I Controller (PID) 29
8
20 Execution (msec)
CFF Revision: 1.9
Ratio Station (RA) 30
9
P,PD Controller (PD) 0 Number
10 0 Execution (msec)

* Execution time in msec.

Advanced Function Blocks Notes:

11 Device Control (DC)

12 Output Splitter (OS)

13 Signal Characterizer (SC)

14 Lead Lag (LL)

15 Deadtime (DT)

16 Integrator(Totalizer) (IT)

17 Setpoint Ramp Generator (SPG)

18 Input Selector (IS)

19 Arithmetic (AR)

20 Timer (TMR)

21 Analog Alarm (AAL)

INSTRUMENT SPECIFICATION -FOUNDATION FIELDBUS


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S18.2 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Tag Number : FV -21039

1. Provide an adjustable limit stop with locking feature, per vendor design practice, to limit travel in the closed position.Field set limit stop to maintain the
minimum flow requirement for associated equipment or service.

2. In-Built surge protector is provided by vendor.

1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S18.3 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
1 Tag No. FV -21040
2 Service FA004 MP STM TO DC001 RX
3 P&ID No. Line No. R2B-P3-206-02-A-DTI-00065 3"-VM-210431-T-B04T1-EC
4 Area Classification Ingress Protection CLASS 1 DIV 2 Gr. B ,C&D, T3 NEMA 4X
GENERAL 5 Ambient Temperature: Unit Min. Max. °C 10 48
6 Allowable Sound dBA Tightness Requirement <85 ANSI IV (standard)
7 Available Air Supply Pressure Unit Min. Max. kgf/cm²-g 4.2 8.0
8 Electric Connection Pneum. Connection 1/2” NPT (F) 1/4” NPT (F)
9 Power Failure Position FO
10 Line Size and Schedule Sch. Outlet Line Sch. 3 in STD 3" STD
PIPE
11 Line Class Rating Pipe Material T-B04T1 300# A106 GR.B, SMLS
LINE
12 Pipe Insulation Thickness Corrosion Allowance EC 90mm 1.6mm
13 Fluid State Phase Steam Gas/Vapor Single Phase
14 Sour Service Special Condition N/A N/A
15 Flow Rate Units Min. Nor. Max. kg/h 454 623 1021
16 Inlet Pressure Units Min. Nor. Max. kgf/cm²-g 13.34 10.3 9.45
17 Pressure Drop Units Min. Nor. Max. kgf/cm² 10.61 6.49 4.668
18 Inlet Temperature Units Min. Nor. Max. °C 220 220 220
PROCESS 19 Density Units Min. Nor. Max. kg/m³
CONDITIONS 20 Viscosity Units Min. Nor. Max. cP 0.017 0.017 0.017
21 Molecular Weight (MW) Specific Gravity @ Oper. 18.02
22 Spec. Heat Ratio (Cp/Cv) Compressibility (Z) 1.238 0.947
23 Vapor Pressure (Liq.) Cavitation or Flashing kgf/cm²-a N/A
24 Critical Pressure (Liq) Flash (wt%) kgf/cm²-a
25 Design Pressure Min. Max. -1.033 kgf/cm²-g 15.5 kgf/cm²-g
26 Design Temperature Min. Max. 10 °C 260 °C
27 Max.Shutoff DP Solid % 15.5 kgf/cm²
28 Calculated Cv Units Min. Nor. Max. Cv 3.63 5.9 11.
CALCULATED
29 Travel Units Min. Nor. Max. % 21 38 70
RESULTS
30 Noise dBA @1m Units Min. Nor. Max. dBA 78 79 82
31 MFR Model FISHER EZ 56 MFR Model FISHER DVC6200F/SC-AD
32 Body Type Single Seat Globe 57 Signal: Inlet Outlet FF Protocol 0-2.8 kgf/cm2
33 Body Size Trim Size 1.5 in 1 in 58 Increase Signal Valve: DIRECT
34 End Connec.Size & Rating 1.5" 300# RF POSITIONER 59 Cam Characteristic LINEAR
35 Rated Cv Characteristic 16.7 Linear 60 Bypass Gauges N/A YES
36 Body Material WCC Steel 61 Signal Fail. to Valve FO
BODY 37 Bonnet Type Material Style 1 Extension WCC Steel 62 Electric Enclosure Ex ia IIC T5 , NEMA 4X
AND 38 Flow Direct. Flow Act. To Up FTO 63 MFR Model N/A N/A
TRIM 39 Packing Type Material Enviro Seal Graphite ULF 64 Type Power N/A N/A
SOLENOID
40 Lubricator Isolat. Valve N/A N/A 65 When De-Enegr.Valve: N/A
VALVE
41 Guiding No. of Ports Post 1 66 Material Latcher N/A N/A
42 Trim Type Internal Design Standard Unbalanced 67 Electric Enclosure N/A
43 Rated Travel Leak Class 3/4 in ANSI IV 68 MFR Model N/A N/A
44 Plug/ Ball/ Disk Material S41600 SST 69 Type Quantity N/A N/A
45 Seat Material S41600 SST SWITCHES 70 Contacts / Rating N/A
46 Cage Stem Material N/A S31600 SST 71 Switching Position N/A
47 Gasket Material S31600 SST/Graphite 72 Electric Enclosure N/A
48 MFR Model FISHER 657 73 MFR Model FISHER 67CFR
49 Type Diaphragm Spring Return AIR SET 74 Set Pressure 4.2 kgf/cm2-g
50 Size Stroke Time 34i < 5 Sec 75 Filter Gauge 5 Micron min YES
ACTUATOR 51 Air Failure Valve: FO 76 Vol. Tank Booster NO NO
52 Handwheel Location N/A 77 Diffuser Lock-up NO NO
ACCESSORY
53 Mounting Position VERTICAL 78 Fire Safe Fireproof NO NO
54 Spring Range 0.4 - 2.0 kgf/cm2-g 79 Mech. Stop Quick Exa. YES (DOWN STOP) NO
55 Include Pressure (Shutoff) 80 Hydro. Pressure YES
85 Vendor EMERSON 81 Leakage YES
PURCHASE TESTS
86 Manufacturer FISHER 82 Cryogenic N/A
87 Requisition No. R2B-P3-206-02-P-MR-00200 83 NACE Requirement N/A
88 Model No. EZ 84 PWHT Requirement N/A
Notes:

INSTRUMENT SPECIFICATION - CONTROL VALVE


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S19.1 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Fieldbus Device Data Sheet
Tag No.: FV -21040
Fieldbus Tag No.:

Service : FA004 MP STM TO DC001 RX

Basic Fieldbus Function Blocks Segment Information


Analog Input Block (AI) 1 Number Device:
1 22
20 Execution (msec)
Discrete Input Block (DI) 4 Number Segment #: DFJB-21035
2 23
15 Execution Time
3 Bias/Gain Station (BG) 0 Execution (msec) 24 LAS Capable: Yes No
Manual Loader (ML) 0 Number 25 Device Current Draw (mA): 19
4
0 Execution (msec) Device Minimum Voltage: 9.
26
Analog Output Block (AO) 1 Number Device Capacitance: 5 nF
5 20 Execution (msec) Polarity-sensitive: Yes No
27
Discrete Output Block (DO) 1 Number Segment Terminator Location:
6 20 Execution (msec)
28
7 Control Selector (CS)
DD Revision: 3
PID,PI,I Controller (PID) 29
8
20 Execution (msec)
CFF Revision: 1.9
Ratio Station (RA) 30
9
P,PD Controller (PD) 0 Number
10 0 Execution (msec)

* Execution time in msec.

Advanced Function Blocks Notes:

11 Device Control (DC)

12 Output Splitter (OS)

13 Signal Characterizer (SC)

14 Lead Lag (LL)

15 Deadtime (DT)

16 Integrator(Totalizer) (IT)

17 Setpoint Ramp Generator (SPG)

18 Input Selector (IS)

19 Arithmetic (AR)

20 Timer (TMR)

21 Analog Alarm (AAL)

INSTRUMENT SPECIFICATION -FOUNDATION FIELDBUS


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S19.2 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Tag Number : FV -21040

1. Provide an adjustable limit stop with locking feature, per vendor design practice, to limit travel in the closed position.Field set limit stop to maintain the
minimum flow requirement for associated equipment or service.

2. In-Built surge protector is provided by vendor.

1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S19.3 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
1 Tag No. FV -21041
2 Service FA004 MP STM TO DC001 RX
3 P&ID No. Line No. R2B-P3-206-02-A-DTI-00065 3"-VM-210433-T-B04T1-EC
4 Area Classification Ingress Protection CLASS 1 DIV 2 Gr. B ,C&D, T3 NEMA 4X
GENERAL 5 Ambient Temperature: Unit Min. Max. °C 10 48
6 Allowable Sound dBA Tightness Requirement <85 ANSI IV (standard)
7 Available Air Supply Pressure Unit Min. Max. kgf/cm²-g 4.2 8.0
8 Electric Connection Pneum. Connection 1/2” NPT (F) 1/4” NPT (F)
9 Power Failure Position FO
10 Line Size and Schedule Sch. Outlet Line Sch. 3 in STD 3" STD
PIPE
11 Line Class Rating Pipe Material T-B04T1 300# A106 GR.B, SMLS
LINE
12 Pipe Insulation Thickness Corrosion Allowance EC 90mm 1.6mm
13 Fluid State Phase Steam Gas/Vapor Single Phase
14 Sour Service Special Condition N/A N/A
15 Flow Rate Units Min. Nor. Max. kg/h 454 623 1021
16 Inlet Pressure Units Min. Nor. Max. kgf/cm²-g 13.34 10.3 9.45
17 Pressure Drop Units Min. Nor. Max. kgf/cm² 10.61 6.49 4.668
18 Inlet Temperature Units Min. Nor. Max. °C 220 220 220
PROCESS 19 Density Units Min. Nor. Max. kg/m³
CONDITIONS 20 Viscosity Units Min. Nor. Max. cP 0.017 0.017 0.017
21 Molecular Weight (MW) Specific Gravity @ Oper. 18.02
22 Spec. Heat Ratio (Cp/Cv) Compressibility (Z) 1.238 0.947
23 Vapor Pressure (Liq.) Cavitation or Flashing kgf/cm²-a N/A
24 Critical Pressure (Liq) Flash (wt%) kgf/cm²-a
25 Design Pressure Min. Max. -1.033 kgf/cm²-g 15.5 kgf/cm²-g
26 Design Temperature Min. Max. 10 °C 260 °C
27 Max.Shutoff DP Solid % 15.5 kgf/cm²
28 Calculated Cv Units Min. Nor. Max. Cv 3.63 5.9 11.
CALCULATED
29 Travel Units Min. Nor. Max. % 21 38 70
RESULTS
30 Noise dBA @1m Units Min. Nor. Max. dBA 78 79 82
31 MFR Model FISHER EZ 56 MFR Model FISHER DVC6200F/SC-AD
32 Body Type Single Seat Globe 57 Signal: Inlet Outlet FF Protocol 0-2.8 kgf/cm2
33 Body Size Trim Size 1.5 in 1 in 58 Increase Signal Valve: DIRECT
34 End Connec.Size & Rating 1.5" 300# RF POSITIONER 59 Cam Characteristic LINEAR
35 Rated Cv Characteristic 16.7 Linear 60 Bypass Gauges N/A YES
36 Body Material WCC Steel 61 Signal Fail. to Valve FO
BODY 37 Bonnet Type Material Style 1 Extension WCC Steel 62 Electric Enclosure Ex ia IIC T5 , NEMA 4X
AND 38 Flow Direct. Flow Act. To Up FTO 63 MFR Model N/A N/A
TRIM 39 Packing Type Material Enviro Seal Graphite ULF 64 Type Power N/A N/A
SOLENOID
40 Lubricator Isolat. Valve N/A N/A 65 When De-Enegr.Valve: N/A
VALVE
41 Guiding No. of Ports Post 1 66 Material Latcher N/A N/A
42 Trim Type Internal Design Standard Unbalanced 67 Electric Enclosure N/A
43 Rated Travel Leak Class 3/4 in ANSI IV 68 MFR Model N/A N/A
44 Plug/ Ball/ Disk Material S41600 SST 69 Type Quantity N/A N/A
45 Seat Material S41600 SST SWITCHES 70 Contacts / Rating N/A
46 Cage Stem Material N/A S31600 SST 71 Switching Position N/A
47 Gasket Material S31600 SST/Graphite 72 Electric Enclosure N/A
48 MFR Model FISHER 657 73 MFR Model FISHER 67CFR
49 Type Diaphragm Spring Return AIR SET 74 Set Pressure 4.2 kgf/cm2-g
50 Size Stroke Time 34i < 5 Sec 75 Filter Gauge 5 Micron min YES
ACTUATOR 51 Air Failure Valve: FO 76 Vol. Tank Booster NO NO
52 Handwheel Location N/A 77 Diffuser Lock-up NO NO
ACCESSORY
53 Mounting Position VERTICAL 78 Fire Safe Fireproof NO NO
54 Spring Range 0.4 - 2.0 kgf/cm2-g 79 Mech. Stop Quick Exa. YES (DOWN STOP) NO
55 Include Pressure (Shutoff) 80 Hydro. Pressure YES
85 Vendor EMERSON 81 Leakage YES
PURCHASE TESTS
86 Manufacturer FISHER 82 Cryogenic N/A
87 Requisition No. R2B-P3-206-02-P-MR-00200 83 NACE Requirement N/A
88 Model No. EZ 84 PWHT Requirement N/A
Notes:

INSTRUMENT SPECIFICATION - CONTROL VALVE


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S20.1 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Fieldbus Device Data Sheet
Tag No.: FV -21041
Fieldbus Tag No.:

Service : FA004 MP STM TO DC001 RX

Basic Fieldbus Function Blocks Segment Information


Analog Input Block (AI) 1 Number Device:
1 22
20 Execution (msec)
Discrete Input Block (DI) 4 Number Segment #: DFJB-21029
2 23
15 Execution Time
3 Bias/Gain Station (BG) 0 Execution (msec) 24 LAS Capable: Yes No
Manual Loader (ML) 0 Number 25 Device Current Draw (mA): 19
4
0 Execution (msec) Device Minimum Voltage: 9.
26
Analog Output Block (AO) 1 Number Device Capacitance: 5 nF
5 20 Execution (msec) Polarity-sensitive: Yes No
27
Discrete Output Block (DO) 1 Number Segment Terminator Location:
6 20 Execution (msec)
28
7 Control Selector (CS)
DD Revision: 3
PID,PI,I Controller (PID) 29
8
20 Execution (msec)
CFF Revision: 1.9
Ratio Station (RA) 30
9
P,PD Controller (PD) 0 Number
10 0 Execution (msec)

* Execution time in msec.

Advanced Function Blocks Notes:

11 Device Control (DC)

12 Output Splitter (OS)

13 Signal Characterizer (SC)

14 Lead Lag (LL)

15 Deadtime (DT)

16 Integrator(Totalizer) (IT)

17 Setpoint Ramp Generator (SPG)

18 Input Selector (IS)

19 Arithmetic (AR)

20 Timer (TMR)

21 Analog Alarm (AAL)

INSTRUMENT SPECIFICATION -FOUNDATION FIELDBUS


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S20.2 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Tag Number : FV -21041

1. Provide an adjustable limit stop with locking feature, per vendor design practice, to limit travel in the closed position.Field set limit stop to maintain the
minimum flow requirement for associated equipment or service.

2. In-Built surge protector is provided by vendor.

1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S20.3 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
1 Tag No. FV -21042
2 Service FA004 MP STM TO DC001 RX
3 P&ID No. Line No. R2B-P3-206-02-A-DTI-00065 3"-VM-210435-T-B04T1-EC
4 Area Classification Ingress Protection CLASS 1 DIV 2 Gr. B ,C&D, T3 NEMA 4X
GENERAL 5 Ambient Temperature: Unit Min. Max. °C 10 48
6 Allowable Sound dBA Tightness Requirement <85 ANSI IV (standard)
7 Available Air Supply Pressure Unit Min. Max. kgf/cm²-g 4.2 8.0
8 Electric Connection Pneum. Connection 1/2” NPT (F) 1/4” NPT (F)
9 Power Failure Position FO
10 Line Size and Schedule Sch. Outlet Line Sch. 3 in STD 3" STD
PIPE
11 Line Class Rating Pipe Material T-B04T1 300# A106 GR.B, SMLS
LINE
12 Pipe Insulation Thickness Corrosion Allowance EC 90mm 1.6mm
13 Fluid State Phase Steam Gas/Vapor Single Phase
14 Sour Service Special Condition N/A N/A
15 Flow Rate Units Min. Nor. Max. kg/h 454 623 1021
16 Inlet Pressure Units Min. Nor. Max. kgf/cm²-g 13.34 10.3 9.45
17 Pressure Drop Units Min. Nor. Max. kgf/cm² 10.61 6.49 4.668
18 Inlet Temperature Units Min. Nor. Max. °C 220 220 220
PROCESS 19 Density Units Min. Nor. Max. kg/m³
CONDITIONS 20 Viscosity Units Min. Nor. Max. cP 0.017 0.017 0.017
21 Molecular Weight (MW) Specific Gravity @ Oper. 18.02
22 Spec. Heat Ratio (Cp/Cv) Compressibility (Z) 1.238 0.947
23 Vapor Pressure (Liq.) Cavitation or Flashing kgf/cm²-a N/A
24 Critical Pressure (Liq) Flash (wt%) kgf/cm²-a
25 Design Pressure Min. Max. -1.033 kgf/cm²-g 15.5 kgf/cm²-g
26 Design Temperature Min. Max. 10 °C 260 °C
27 Max.Shutoff DP Solid % 15.5 kgf/cm²
28 Calculated Cv Units Min. Nor. Max. Cv 3.63 5.9 11.
CALCULATED
29 Travel Units Min. Nor. Max. % 21 38 70
RESULTS
30 Noise dBA @1m Units Min. Nor. Max. dBA 78 79 82
31 MFR Model FISHER EZ 56 MFR Model FISHER DVC6200F/SC-AD
32 Body Type Single Seat Globe 57 Signal: Inlet Outlet FF Protocol 0-2.8 kgf/cm2
33 Body Size Trim Size 1.5 in 1 in 58 Increase Signal Valve: DIRECT
34 End Connec.Size & Rating 1.5" 300# RF POSITIONER 59 Cam Characteristic LINEAR
35 Rated Cv Characteristic 16.7 Linear 60 Bypass Gauges N/A YES
36 Body Material WCC Steel 61 Signal Fail. to Valve FO
BODY 37 Bonnet Type Material Style 1 Extension WCC Steel 62 Electric Enclosure Ex ia IIC T5 , NEMA 4X
AND 38 Flow Direct. Flow Act. To Up FTO 63 MFR Model N/A N/A
TRIM 39 Packing Type Material Enviro Seal Graphite ULF 64 Type Power N/A N/A
SOLENOID
40 Lubricator Isolat. Valve N/A N/A 65 When De-Enegr.Valve: N/A
VALVE
41 Guiding No. of Ports Post 1 66 Material Latcher N/A N/A
42 Trim Type Internal Design Standard Unbalanced 67 Electric Enclosure N/A
43 Rated Travel Leak Class 3/4 in ANSI IV 68 MFR Model N/A N/A
44 Plug/ Ball/ Disk Material S41600 SST 69 Type Quantity N/A N/A
45 Seat Material S41600 SST SWITCHES 70 Contacts / Rating N/A
46 Cage Stem Material N/A S31600 SST 71 Switching Position N/A
47 Gasket Material S31600 SST/Graphite 72 Electric Enclosure N/A
48 MFR Model FISHER 657 73 MFR Model FISHER 67CFR
49 Type Diaphragm Spring Return AIR SET 74 Set Pressure 4.2 kgf/cm2-g
50 Size Stroke Time 34i < 5 Sec 75 Filter Gauge 5 Micron min YES
ACTUATOR 51 Air Failure Valve: FO 76 Vol. Tank Booster NO NO
52 Handwheel Location N/A 77 Diffuser Lock-up NO NO
ACCESSORY
53 Mounting Position VERTICAL 78 Fire Safe Fireproof NO NO
54 Spring Range 0.4 - 2.0 kgf/cm2-g 79 Mech. Stop Quick Exa. YES (DOWN STOP) NO
55 Include Pressure (Shutoff) 80 Hydro. Pressure YES
85 Vendor EMERSON 81 Leakage YES
PURCHASE TESTS
86 Manufacturer FISHER 82 Cryogenic N/A
87 Requisition No. R2B-P3-206-02-P-MR-00200 83 NACE Requirement N/A
88 Model No. EZ 84 PWHT Requirement N/A
Notes:

INSTRUMENT SPECIFICATION - CONTROL VALVE


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S21.1 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Fieldbus Device Data Sheet
Tag No.: FV -21042
Fieldbus Tag No.:

Service : FA004 MP STM TO DC001 RX

Basic Fieldbus Function Blocks Segment Information


Analog Input Block (AI) 1 Number Device:
1 22
20 Execution (msec)
Discrete Input Block (DI) 4 Number Segment #: DFJB-21028
2 23
15 Execution Time
3 Bias/Gain Station (BG) 0 Execution (msec) 24 LAS Capable: Yes No
Manual Loader (ML) 0 Number 25 Device Current Draw (mA): 19
4
0 Execution (msec) Device Minimum Voltage: 9.
26
Analog Output Block (AO) 1 Number Device Capacitance: 5 nF
5 20 Execution (msec) Polarity-sensitive: Yes No
27
Discrete Output Block (DO) 1 Number Segment Terminator Location:
6 20 Execution (msec)
28
7 Control Selector (CS)
DD Revision: 3
PID,PI,I Controller (PID) 29
8
20 Execution (msec)
CFF Revision: 1.9
Ratio Station (RA) 30
9
P,PD Controller (PD) 0 Number
10 0 Execution (msec)

* Execution time in msec.

Advanced Function Blocks Notes:

11 Device Control (DC)

12 Output Splitter (OS)

13 Signal Characterizer (SC)

14 Lead Lag (LL)

15 Deadtime (DT)

16 Integrator(Totalizer) (IT)

17 Setpoint Ramp Generator (SPG)

18 Input Selector (IS)

19 Arithmetic (AR)

20 Timer (TMR)

21 Analog Alarm (AAL)

INSTRUMENT SPECIFICATION -FOUNDATION FIELDBUS


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S21.2 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Tag Number : FV -21042

1. Provide an adjustable limit stop with locking feature, per vendor design practice, to limit travel in the closed position.Field set limit stop to maintain the
minimum flow requirement for associated equipment or service.

2. In-Built surge protector is provided by vendor.

1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S21.3 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
1 Tag No. FV -21043
2 Service FA004 MP STM TO DC001 RX
3 P&ID No. Line No. R2B-P3-206-02-A-DTI-00065 3"-VM-210437-T-B04T1-EC
4 Area Classification Ingress Protection CLASS 1 DIV 2 Gr. B ,C&D, T3 NEMA 4X
GENERAL 5 Ambient Temperature: Unit Min. Max. °C 10 48
6 Allowable Sound dBA Tightness Requirement <85 ANSI IV (standard)
7 Available Air Supply Pressure Unit Min. Max. kgf/cm²-g 4.2 8.0
8 Electric Connection Pneum. Connection 1/2” NPT (F) 1/4” NPT (F)
9 Power Failure Position FO
10 Line Size and Schedule Sch. Outlet Line Sch. 3 in STD 3" STD
PIPE
11 Line Class Rating Pipe Material T-B04T1 300# A106 GR.B, SMLS
LINE
12 Pipe Insulation Thickness Corrosion Allowance EC 90mm 1.6mm
13 Fluid State Phase Steam Gas/Vapor Single Phase
14 Sour Service Special Condition N/A N/A
15 Flow Rate Units Min. Nor. Max. kg/h 454 623 1021
16 Inlet Pressure Units Min. Nor. Max. kgf/cm²-g 13.34 10.3 9.45
17 Pressure Drop Units Min. Nor. Max. kgf/cm² 10.61 6.49 4.668
18 Inlet Temperature Units Min. Nor. Max. °C 220 220 220
PROCESS 19 Density Units Min. Nor. Max. kg/m³
CONDITIONS 20 Viscosity Units Min. Nor. Max. cP 0.017 0.017 0.017
21 Molecular Weight (MW) Specific Gravity @ Oper. 18.02
22 Spec. Heat Ratio (Cp/Cv) Compressibility (Z) 1.238 0.947
23 Vapor Pressure (Liq.) Cavitation or Flashing kgf/cm²-a N/A
24 Critical Pressure (Liq) Flash (wt%) kgf/cm²-a
25 Design Pressure Min. Max. -1.033 kgf/cm²-g 15.5 kgf/cm²-g
26 Design Temperature Min. Max. 10 °C 260 °C
27 Max.Shutoff DP Solid % 15.5 kgf/cm²
28 Calculated Cv Units Min. Nor. Max. Cv 3.63 5.9 11.
CALCULATED
29 Travel Units Min. Nor. Max. % 21 38 70
RESULTS
30 Noise dBA @1m Units Min. Nor. Max. dBA 78 79 82
31 MFR Model FISHER EZ 56 MFR Model FISHER DVC6200F/SC-AD
32 Body Type Single Seat Globe 57 Signal: Inlet Outlet FF Protocol 0-2.8 kgf/cm2
33 Body Size Trim Size 1.5 in 1 in 58 Increase Signal Valve: DIRECT
34 End Connec.Size & Rating 1.5" 300# RF POSITIONER 59 Cam Characteristic LINEAR
35 Rated Cv Characteristic 16.7 Linear 60 Bypass Gauges N/A YES
36 Body Material WCC Steel 61 Signal Fail. to Valve FO
BODY 37 Bonnet Type Material Style 1 Extension WCC Steel 62 Electric Enclosure Ex ia IIC T5 , NEMA 4X
AND 38 Flow Direct. Flow Act. To Up FTO 63 MFR Model N/A N/A
TRIM 39 Packing Type Material Enviro Seal Graphite ULF 64 Type Power N/A N/A
SOLENOID
40 Lubricator Isolat. Valve N/A N/A 65 When De-Enegr.Valve: N/A
VALVE
41 Guiding No. of Ports Post 1 66 Material Latcher N/A N/A
42 Trim Type Internal Design Standard Unbalanced 67 Electric Enclosure N/A
43 Rated Travel Leak Class 3/4 in ANSI IV 68 MFR Model N/A N/A
44 Plug/ Ball/ Disk Material S41600 SST 69 Type Quantity N/A N/A
45 Seat Material S41600 SST SWITCHES 70 Contacts / Rating N/A
46 Cage Stem Material N/A S31600 SST 71 Switching Position N/A
47 Gasket Material S31600 SST/Graphite 72 Electric Enclosure N/A
48 MFR Model FISHER 657 73 MFR Model FISHER 67CFR
49 Type Diaphragm Spring Return AIR SET 74 Set Pressure 4.2 kgf/cm2-g
50 Size Stroke Time 34i < 5 Sec 75 Filter Gauge 5 Micron min YES
ACTUATOR 51 Air Failure Valve: FO 76 Vol. Tank Booster NO NO
52 Handwheel Location N/A 77 Diffuser Lock-up NO NO
ACCESSORY
53 Mounting Position VERTICAL 78 Fire Safe Fireproof NO NO
54 Spring Range 0.4 - 2.0 kgf/cm2-g 79 Mech. Stop Quick Exa. YES (DOWN STOP) NO
55 Include Pressure (Shutoff) 80 Hydro. Pressure YES
85 Vendor EMERSON 81 Leakage YES
PURCHASE TESTS
86 Manufacturer FISHER 82 Cryogenic N/A
87 Requisition No. R2B-P3-206-02-P-MR-00200 83 NACE Requirement N/A
88 Model No. EZ 84 PWHT Requirement N/A
Notes:

INSTRUMENT SPECIFICATION - CONTROL VALVE


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S22.1 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Fieldbus Device Data Sheet
Tag No.: FV -21043
Fieldbus Tag No.:

Service : FA004 MP STM TO DC001 RX

Basic Fieldbus Function Blocks Segment Information


Analog Input Block (AI) 1 Number Device:
1 22
20 Execution (msec)
Discrete Input Block (DI) 4 Number Segment #: DFJB-21032
2 23
15 Execution Time
3 Bias/Gain Station (BG) 0 Execution (msec) 24 LAS Capable: Yes No
Manual Loader (ML) 0 Number 25 Device Current Draw (mA): 19
4
0 Execution (msec) Device Minimum Voltage: 9.
26
Analog Output Block (AO) 1 Number Device Capacitance: 5 nF
5 20 Execution (msec) Polarity-sensitive: Yes No
27
Discrete Output Block (DO) 1 Number Segment Terminator Location:
6 20 Execution (msec)
28
7 Control Selector (CS)
DD Revision: 3
PID,PI,I Controller (PID) 29
8
20 Execution (msec)
CFF Revision: 1.9
Ratio Station (RA) 30
9
P,PD Controller (PD) 0 Number
10 0 Execution (msec)

* Execution time in msec.

Advanced Function Blocks Notes:

11 Device Control (DC)

12 Output Splitter (OS)

13 Signal Characterizer (SC)

14 Lead Lag (LL)

15 Deadtime (DT)

16 Integrator(Totalizer) (IT)

17 Setpoint Ramp Generator (SPG)

18 Input Selector (IS)

19 Arithmetic (AR)

20 Timer (TMR)

21 Analog Alarm (AAL)

INSTRUMENT SPECIFICATION -FOUNDATION FIELDBUS


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S22.2 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Tag Number : FV -21043

1. Provide an adjustable limit stop with locking feature, per vendor design practice, to limit travel in the closed position.Field set limit stop to maintain the
minimum flow requirement for associated equipment or service.

2. In-Built surge protector is provided by vendor.

1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S22.3 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
1 Tag No. FV -21044
2 Service FA004 MP STM TO DC001 RX
3 P&ID No. Line No. R2B-P3-206-02-A-DTI-00065 3"-VM-210439-T-B04T1-EC
4 Area Classification Ingress Protection CLASS 1 DIV 2 Gr. B ,C&D, T3 NEMA 4X
GENERAL 5 Ambient Temperature: Unit Min. Max. °C 10 48
6 Allowable Sound dBA Tightness Requirement <85 ANSI IV (standard)
7 Available Air Supply Pressure Unit Min. Max. kgf/cm²-g 4.2 8.0
8 Electric Connection Pneum. Connection 1/2” NPT (F) 1/4” NPT (F)
9 Power Failure Position FO
10 Line Size and Schedule Sch. Outlet Line Sch. 3 in STD 3" STD
PIPE
11 Line Class Rating Pipe Material T-B04T1 300# A106 GR.B, SMLS
LINE
12 Pipe Insulation Thickness Corrosion Allowance EC 90mm 1.6mm
13 Fluid State Phase Steam Gas/Vapor Single Phase
14 Sour Service Special Condition N/A N/A
15 Flow Rate Units Min. Nor. Max. kg/h 454 623 1021
16 Inlet Pressure Units Min. Nor. Max. kgf/cm²-g 13.34 10.3 9.45
17 Pressure Drop Units Min. Nor. Max. kgf/cm² 10.61 6.49 4.668
18 Inlet Temperature Units Min. Nor. Max. °C 220 220 220
PROCESS 19 Density Units Min. Nor. Max. kg/m³
CONDITIONS 20 Viscosity Units Min. Nor. Max. cP 0.017 0.017 0.017
21 Molecular Weight (MW) Specific Gravity @ Oper. 18.02
22 Spec. Heat Ratio (Cp/Cv) Compressibility (Z) 1.238 0.947
23 Vapor Pressure (Liq.) Cavitation or Flashing kgf/cm²-a N/A
24 Critical Pressure (Liq) Flash (wt%) kgf/cm²-a
25 Design Pressure Min. Max. -1.033 kgf/cm²-g 15.5 kgf/cm²-g
26 Design Temperature Min. Max. 10 °C 260 °C
27 Max.Shutoff DP Solid % 15.5 kgf/cm²
28 Calculated Cv Units Min. Nor. Max. Cv 3.63 5.9 11.
CALCULATED
29 Travel Units Min. Nor. Max. % 21 38 70
RESULTS
30 Noise dBA @1m Units Min. Nor. Max. dBA 78 79 82
31 MFR Model FISHER EZ 56 MFR Model FISHER DVC6200F/SC-AD
32 Body Type Single Seat Globe 57 Signal: Inlet Outlet FF Protocol 0-2.8 kgf/cm2
33 Body Size Trim Size 1.5 in 1 in 58 Increase Signal Valve: DIRECT
34 End Connec.Size & Rating 1.5" 300# RF POSITIONER 59 Cam Characteristic LINEAR
35 Rated Cv Characteristic 16.7 Linear 60 Bypass Gauges N/A YES
36 Body Material WCC Steel 61 Signal Fail. to Valve FO
BODY 37 Bonnet Type Material Style 1 Extension WCC Steel 62 Electric Enclosure Ex ia IIC T5 , NEMA 4X
AND 38 Flow Direct. Flow Act. To Up FTO 63 MFR Model N/A N/A
TRIM 39 Packing Type Material Enviro Seal Graphite ULF 64 Type Power N/A N/A
SOLENOID
40 Lubricator Isolat. Valve N/A N/A 65 When De-Enegr.Valve: N/A
VALVE
41 Guiding No. of Ports Post 1 66 Material Latcher N/A N/A
42 Trim Type Internal Design Standard Unbalanced 67 Electric Enclosure N/A
43 Rated Travel Leak Class 3/4 in ANSI IV 68 MFR Model N/A N/A
44 Plug/ Ball/ Disk Material S41600 SST 69 Type Quantity N/A N/A
45 Seat Material S41600 SST SWITCHES 70 Contacts / Rating N/A
46 Cage Stem Material N/A S31600 SST 71 Switching Position N/A
47 Gasket Material S31600 SST/Graphite 72 Electric Enclosure N/A
48 MFR Model FISHER 657 73 MFR Model FISHER 67CFR
49 Type Diaphragm Spring Return AIR SET 74 Set Pressure 4.2 kgf/cm2-g
50 Size Stroke Time 34i < 5 Sec 75 Filter Gauge 5 Micron min YES
ACTUATOR 51 Air Failure Valve: FO 76 Vol. Tank Booster NO NO
52 Handwheel Location N/A 77 Diffuser Lock-up NO NO
ACCESSORY
53 Mounting Position VERTICAL 78 Fire Safe Fireproof NO NO
54 Spring Range 0.4 - 2.0 kgf/cm2-g 79 Mech. Stop Quick Exa. YES (DOWN STOP) NO
55 Include Pressure (Shutoff) 80 Hydro. Pressure YES
85 Vendor EMERSON 81 Leakage YES
PURCHASE TESTS
86 Manufacturer FISHER 82 Cryogenic N/A
87 Requisition No. R2B-P3-206-02-P-MR-00200 83 NACE Requirement N/A
88 Model No. EZ 84 PWHT Requirement N/A
Notes:

INSTRUMENT SPECIFICATION - CONTROL VALVE


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S23.1 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Fieldbus Device Data Sheet
Tag No.: FV -21044
Fieldbus Tag No.:

Service : FA004 MP STM TO DC001 RX

Basic Fieldbus Function Blocks Segment Information


Analog Input Block (AI) 1 Number Device:
1 22
20 Execution (msec)
Discrete Input Block (DI) 4 Number Segment #: DFJB-21034
2 23
15 Execution Time
3 Bias/Gain Station (BG) 0 Execution (msec) 24 LAS Capable: Yes No
Manual Loader (ML) 0 Number 25 Device Current Draw (mA): 19
4
0 Execution (msec) Device Minimum Voltage: 9.
26
Analog Output Block (AO) 1 Number Device Capacitance: 5 nF
5 20 Execution (msec) Polarity-sensitive: Yes No
27
Discrete Output Block (DO) 1 Number Segment Terminator Location:
6 20 Execution (msec)
28
7 Control Selector (CS)
DD Revision: 3
PID,PI,I Controller (PID) 29
8
20 Execution (msec)
CFF Revision: 1.9
Ratio Station (RA) 30
9
P,PD Controller (PD) 0 Number
10 0 Execution (msec)

* Execution time in msec.

Advanced Function Blocks Notes:

11 Device Control (DC)

12 Output Splitter (OS)

13 Signal Characterizer (SC)

14 Lead Lag (LL)

15 Deadtime (DT)

16 Integrator(Totalizer) (IT)

17 Setpoint Ramp Generator (SPG)

18 Input Selector (IS)

19 Arithmetic (AR)

20 Timer (TMR)

21 Analog Alarm (AAL)

INSTRUMENT SPECIFICATION -FOUNDATION FIELDBUS


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S23.2 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Tag Number : FV -21044

1. Provide an adjustable limit stop with locking feature, per vendor design practice, to limit travel in the closed position.Field set limit stop to maintain the
minimum flow requirement for associated equipment or service.

2. In-Built surge protector is provided by vendor.

1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S23.3 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
1 Tag No. FV -21045
2 Service FA004 MP STM TO DC001 RX
3 P&ID No. Line No. R2B-P3-206-02-A-DTI-00065 3"-VM-210445-T-B04T1-EC
4 Area Classification Ingress Protection CLASS 1 DIV 2 Gr. B ,C&D, T3 NEMA 4X
GENERAL 5 Ambient Temperature: Unit Min. Max. °C 10 48
6 Allowable Sound dBA Tightness Requirement <85 ANSI IV (standard)
7 Available Air Supply Pressure Unit Min. Max. kgf/cm²-g 4.2 8.0
8 Electric Connection Pneum. Connection 1/2” NPT (F) 1/4” NPT (F)
9 Power Failure Position FO
10 Line Size and Schedule Sch. Outlet Line Sch. 3 in STD 3" STD
PIPE
11 Line Class Rating Pipe Material T-B04T1 300# A106 GR.B, SMLS
LINE
12 Pipe Insulation Thickness Corrosion Allowance EC 90mm 1.6mm
13 Fluid State Phase Steam Gas/Vapor Single Phase
14 Sour Service Special Condition N/A N/A
15 Flow Rate Units Min. Nor. Max. kg/h 454 623 1021
16 Inlet Pressure Units Min. Nor. Max. kgf/cm²-g 13.34 10.3 9.45
17 Pressure Drop Units Min. Nor. Max. kgf/cm² 10.61 6.49 4.668
18 Inlet Temperature Units Min. Nor. Max. °C 220 220 220
PROCESS 19 Density Units Min. Nor. Max. kg/m³
CONDITIONS 20 Viscosity Units Min. Nor. Max. cP 0.017 0.017 0.017
21 Molecular Weight (MW) Specific Gravity @ Oper. 18.02
22 Spec. Heat Ratio (Cp/Cv) Compressibility (Z) 1.238 0.947
23 Vapor Pressure (Liq.) Cavitation or Flashing kgf/cm²-a N/A
24 Critical Pressure (Liq) Flash (wt%) kgf/cm²-a
25 Design Pressure Min. Max. -1.033 kgf/cm²-g 15.5 kgf/cm²-g
26 Design Temperature Min. Max. 10 °C 260 °C
27 Max.Shutoff DP Solid % 15.5 kgf/cm²
28 Calculated Cv Units Min. Nor. Max. Cv 3.63 5.9 11.
CALCULATED
29 Travel Units Min. Nor. Max. % 21 38 70
RESULTS
30 Noise dBA @1m Units Min. Nor. Max. dBA 78 79 82
31 MFR Model FISHER EZ 56 MFR Model FISHER DVC6200F/SC-AD
32 Body Type Single Seat Globe 57 Signal: Inlet Outlet FF Protocol 0-2.8 kgf/cm2
33 Body Size Trim Size 1.5 in 1 in 58 Increase Signal Valve: DIRECT
34 End Connec.Size & Rating 1.5" 300# RF POSITIONER 59 Cam Characteristic LINEAR
35 Rated Cv Characteristic 16.7 Linear 60 Bypass Gauges N/A YES
36 Body Material WCC Steel 61 Signal Fail. to Valve FO
BODY 37 Bonnet Type Material Style 1 Extension WCC Steel 62 Electric Enclosure Ex ia IIC T5 , NEMA 4X
AND 38 Flow Direct. Flow Act. To Up FTO 63 MFR Model N/A N/A
TRIM 39 Packing Type Material Enviro Seal Graphite ULF 64 Type Power N/A N/A
SOLENOID
40 Lubricator Isolat. Valve N/A N/A 65 When De-Enegr.Valve: N/A
VALVE
41 Guiding No. of Ports Post 1 66 Material Latcher N/A N/A
42 Trim Type Internal Design Standard Unbalanced 67 Electric Enclosure N/A
43 Rated Travel Leak Class 3/4 in ANSI IV 68 MFR Model N/A N/A
44 Plug/ Ball/ Disk Material S41600 SST 69 Type Quantity N/A N/A
45 Seat Material S41600 SST SWITCHES 70 Contacts / Rating N/A
46 Cage Stem Material N/A S31600 SST 71 Switching Position N/A
47 Gasket Material S31600 SST/Graphite 72 Electric Enclosure N/A
48 MFR Model FISHER 657 73 MFR Model FISHER 67CFR
49 Type Diaphragm Spring Return AIR SET 74 Set Pressure 4.2 kgf/cm2-g
50 Size Stroke Time 34i < 5 Sec 75 Filter Gauge 5 Micron min YES
ACTUATOR 51 Air Failure Valve: FO 76 Vol. Tank Booster NO NO
52 Handwheel Location N/A 77 Diffuser Lock-up NO NO
ACCESSORY
53 Mounting Position VERTICAL 78 Fire Safe Fireproof NO NO
54 Spring Range 0.4 - 2.0 kgf/cm2-g 79 Mech. Stop Quick Exa. YES (DOWN STOP) NO
55 Include Pressure (Shutoff) 80 Hydro. Pressure YES
85 Vendor EMERSON 81 Leakage YES
PURCHASE TESTS
86 Manufacturer FISHER 82 Cryogenic N/A
87 Requisition No. R2B-P3-206-02-P-MR-00200 83 NACE Requirement N/A
88 Model No. EZ 84 PWHT Requirement N/A
Notes:

INSTRUMENT SPECIFICATION - CONTROL VALVE


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S24.1 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Fieldbus Device Data Sheet
Tag No.: FV -21045
Fieldbus Tag No.:

Service : FA004 MP STM TO DC001 RX

Basic Fieldbus Function Blocks Segment Information


Analog Input Block (AI) 1 Number Device:
1 22
20 Execution (msec)
Discrete Input Block (DI) 4 Number Segment #: DFJB-21035
2 23
15 Execution Time
3 Bias/Gain Station (BG) 0 Execution (msec) 24 LAS Capable: Yes No
Manual Loader (ML) 0 Number 25 Device Current Draw (mA): 19
4
0 Execution (msec) Device Minimum Voltage: 9.
26
Analog Output Block (AO) 1 Number Device Capacitance: 5 nF
5 20 Execution (msec) Polarity-sensitive: Yes No
27
Discrete Output Block (DO) 1 Number Segment Terminator Location:
6 20 Execution (msec)
28
7 Control Selector (CS)
DD Revision: 3
PID,PI,I Controller (PID) 29
8
20 Execution (msec)
CFF Revision: 1.9
Ratio Station (RA) 30
9
P,PD Controller (PD) 0 Number
10 0 Execution (msec)

* Execution time in msec.

Advanced Function Blocks Notes:

11 Device Control (DC)

12 Output Splitter (OS)

13 Signal Characterizer (SC)

14 Lead Lag (LL)

15 Deadtime (DT)

16 Integrator(Totalizer) (IT)

17 Setpoint Ramp Generator (SPG)

18 Input Selector (IS)

19 Arithmetic (AR)

20 Timer (TMR)

21 Analog Alarm (AAL)

INSTRUMENT SPECIFICATION -FOUNDATION FIELDBUS


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S24.2 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Tag Number : FV -21045

1. Provide an adjustable limit stop with locking feature, per vendor design practice, to limit travel in the closed position.Field set limit stop to maintain the
minimum flow requirement for associated equipment or service.

2. In-Built surge protector is provided by vendor.

1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S24.3 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
1 Tag No. FV -21046
2 Service FA004 MP STM TO DC001 RX
3 P&ID No. Line No. R2B-P3-206-02-A-DTI-00065 3"-VM-210447-T-B04T1-EC
4 Area Classification Ingress Protection CLASS 1 DIV 2 Gr. B ,C&D, T3 NEMA 4X
GENERAL 5 Ambient Temperature: Unit Min. Max. °C 10 48
6 Allowable Sound dBA Tightness Requirement <85 ANSI IV (standard)
7 Available Air Supply Pressure Unit Min. Max. kgf/cm²-g 4.2 8.0
8 Electric Connection Pneum. Connection 1/2” NPT (F) 1/4” NPT (F)
9 Power Failure Position FO
10 Line Size and Schedule Sch. Outlet Line Sch. 3 in STD 3" STD
PIPE
11 Line Class Rating Pipe Material T-B04T1 300# A106 GR.B, SMLS
LINE
12 Pipe Insulation Thickness Corrosion Allowance EC 90mm 1.6mm
13 Fluid State Phase Steam Gas/Vapor Single Phase
14 Sour Service Special Condition N/A N/A
15 Flow Rate Units Min. Nor. Max. kg/h 454 623 1021
16 Inlet Pressure Units Min. Nor. Max. kgf/cm²-g 13.34 10.3 9.45
17 Pressure Drop Units Min. Nor. Max. kgf/cm² 10.61 6.49 4.668
18 Inlet Temperature Units Min. Nor. Max. °C 220 220 220
PROCESS 19 Density Units Min. Nor. Max. kg/m³
CONDITIONS 20 Viscosity Units Min. Nor. Max. cP 0.017 0.017 0.017
21 Molecular Weight (MW) Specific Gravity @ Oper. 18.02
22 Spec. Heat Ratio (Cp/Cv) Compressibility (Z) 1.238 0.947
23 Vapor Pressure (Liq.) Cavitation or Flashing kgf/cm²-a N/A
24 Critical Pressure (Liq) Flash (wt%) kgf/cm²-a
25 Design Pressure Min. Max. -1.033 kgf/cm²-g 15.5 kgf/cm²-g
26 Design Temperature Min. Max. 10 °C 260 °C
27 Max.Shutoff DP Solid % 15.5 kgf/cm²
28 Calculated Cv Units Min. Nor. Max. Cv 3.63 5.9 11.
CALCULATED
29 Travel Units Min. Nor. Max. % 21 38 70
RESULTS
30 Noise dBA @1m Units Min. Nor. Max. dBA 78 79 82
31 MFR Model FISHER EZ 56 MFR Model FISHER DVC6200F/SC-AD
32 Body Type Single Seat Globe 57 Signal: Inlet Outlet FF Protocol 0-2.8 kgf/cm2
33 Body Size Trim Size 1.5 in 1 in 58 Increase Signal Valve: DIRECT
34 End Connec.Size & Rating 1.5" 300# RF POSITIONER 59 Cam Characteristic LINEAR
35 Rated Cv Characteristic 16.7 Linear 60 Bypass Gauges N/A YES
36 Body Material WCC Steel 61 Signal Fail. to Valve FO
BODY 37 Bonnet Type Material Style 1 Extension WCC Steel 62 Electric Enclosure Ex ia IIC T5 , NEMA 4X
AND 38 Flow Direct. Flow Act. To Up FTO 63 MFR Model N/A N/A
TRIM 39 Packing Type Material Enviro Seal Graphite ULF 64 Type Power N/A N/A
SOLENOID
40 Lubricator Isolat. Valve N/A N/A 65 When De-Enegr.Valve: N/A
VALVE
41 Guiding No. of Ports Post 1 66 Material Latcher N/A N/A
42 Trim Type Internal Design Standard Unbalanced 67 Electric Enclosure N/A
43 Rated Travel Leak Class 3/4 in ANSI IV 68 MFR Model N/A N/A
44 Plug/ Ball/ Disk Material S41600 SST 69 Type Quantity N/A N/A
45 Seat Material S41600 SST SWITCHES 70 Contacts / Rating N/A
46 Cage Stem Material N/A S31600 SST 71 Switching Position N/A
47 Gasket Material S31600 SST/Graphite 72 Electric Enclosure N/A
48 MFR Model FISHER 657 73 MFR Model FISHER 67CFR
49 Type Diaphragm Spring Return AIR SET 74 Set Pressure 4.2 kgf/cm2-g
50 Size Stroke Time 34i < 5 Sec 75 Filter Gauge 5 Micron min YES
ACTUATOR 51 Air Failure Valve: FO 76 Vol. Tank Booster NO NO
52 Handwheel Location N/A 77 Diffuser Lock-up NO NO
ACCESSORY
53 Mounting Position VERTICAL 78 Fire Safe Fireproof NO NO
54 Spring Range 0.4 - 2.0 kgf/cm2-g 79 Mech. Stop Quick Exa. YES (DOWN STOP) NO
55 Include Pressure (Shutoff) 80 Hydro. Pressure YES
85 Vendor EMERSON 81 Leakage YES
PURCHASE TESTS
86 Manufacturer FISHER 82 Cryogenic N/A
87 Requisition No. R2B-P3-206-02-P-MR-00200 83 NACE Requirement N/A
88 Model No. EZ 84 PWHT Requirement N/A
Notes:

INSTRUMENT SPECIFICATION - CONTROL VALVE


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S25.1 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Fieldbus Device Data Sheet
Tag No.: FV -21046
Fieldbus Tag No.:

Service : FA004 MP STM TO DC001 RX

Basic Fieldbus Function Blocks Segment Information


Analog Input Block (AI) 1 Number Device:
1 22
20 Execution (msec)
Discrete Input Block (DI) 4 Number Segment #: DFJB-21028
2 23
15 Execution Time
3 Bias/Gain Station (BG) 0 Execution (msec) 24 LAS Capable: Yes No
Manual Loader (ML) 0 Number 25 Device Current Draw (mA): 19
4
0 Execution (msec) Device Minimum Voltage: 9.
26
Analog Output Block (AO) 1 Number Device Capacitance: 5 nF
5 20 Execution (msec) Polarity-sensitive: Yes No
27
Discrete Output Block (DO) 1 Number Segment Terminator Location:
6 20 Execution (msec)
28
7 Control Selector (CS)
DD Revision: 3
PID,PI,I Controller (PID) 29
8
20 Execution (msec)
CFF Revision: 1.9
Ratio Station (RA) 30
9
P,PD Controller (PD) 0 Number
10 0 Execution (msec)

* Execution time in msec.

Advanced Function Blocks Notes:

11 Device Control (DC)

12 Output Splitter (OS)

13 Signal Characterizer (SC)

14 Lead Lag (LL)

15 Deadtime (DT)

16 Integrator(Totalizer) (IT)

17 Setpoint Ramp Generator (SPG)

18 Input Selector (IS)

19 Arithmetic (AR)

20 Timer (TMR)

21 Analog Alarm (AAL)

INSTRUMENT SPECIFICATION -FOUNDATION FIELDBUS


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S25.2 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Tag Number : FV -21046

1. Provide an adjustable limit stop with locking feature, per vendor design practice, to limit travel in the closed position.Field set limit stop to maintain the
minimum flow requirement for associated equipment or service.

2. In-Built surge protector is provided by vendor.

1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S25.3 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
1 Tag No. FV -21047
2 Service FA004 MP STM TO DC001 RX
3 P&ID No. Line No. R2B-P3-206-02-A-DTI-00065 3"-VM-210449-T-B04T1-EC
4 Area Classification Ingress Protection CLASS 1 DIV 2 Gr. B ,C&D, T3 NEMA 4X
GENERAL 5 Ambient Temperature: Unit Min. Max. °C 10 48
6 Allowable Sound dBA Tightness Requirement <85 ANSI IV (standard)
7 Available Air Supply Pressure Unit Min. Max. kgf/cm²-g 4.2 8.0
8 Electric Connection Pneum. Connection 1/2” NPT (F) 1/4” NPT (F)
9 Power Failure Position FO
10 Line Size and Schedule Sch. Outlet Line Sch. 3 in STD 3" STD
PIPE
11 Line Class Rating Pipe Material T-B04T1 300# A106 GR.B, SMLS
LINE
12 Pipe Insulation Thickness Corrosion Allowance EC 90mm 1.6mm
13 Fluid State Phase Steam Gas/Vapor Single Phase
14 Sour Service Special Condition N/A N/A
15 Flow Rate Units Min. Nor. Max. kg/h 454 623 1021
16 Inlet Pressure Units Min. Nor. Max. kgf/cm²-g 13.34 10.3 9.45
17 Pressure Drop Units Min. Nor. Max. kgf/cm² 10.61 6.49 4.668
18 Inlet Temperature Units Min. Nor. Max. °C 220 220 220
PROCESS 19 Density Units Min. Nor. Max. kg/m³
CONDITIONS 20 Viscosity Units Min. Nor. Max. cP 0.017 0.017 0.017
21 Molecular Weight (MW) Specific Gravity @ Oper. 18.02
22 Spec. Heat Ratio (Cp/Cv) Compressibility (Z) 1.238 0.947
23 Vapor Pressure (Liq.) Cavitation or Flashing kgf/cm²-a N/A
24 Critical Pressure (Liq) Flash (wt%) kgf/cm²-a
25 Design Pressure Min. Max. -1.033 kgf/cm²-g 15.5 kgf/cm²-g
26 Design Temperature Min. Max. 10 °C 260 °C
27 Max.Shutoff DP Solid % 15.5 kgf/cm²
28 Calculated Cv Units Min. Nor. Max. Cv 3.63 5.9 11.
CALCULATED
29 Travel Units Min. Nor. Max. % 21 38 70
RESULTS
30 Noise dBA @1m Units Min. Nor. Max. dBA 78 79 82
31 MFR Model FISHER EZ 56 MFR Model FISHER DVC6200F/SC-AD
32 Body Type Single Seat Globe 57 Signal: Inlet Outlet FF Protocol 0-2.8 kgf/cm2
33 Body Size Trim Size 1.5 in 1 in 58 Increase Signal Valve: DIRECT
34 End Connec.Size & Rating 1.5" 300# RF POSITIONER 59 Cam Characteristic LINEAR
35 Rated Cv Characteristic 16.7 Linear 60 Bypass Gauges N/A YES
36 Body Material WCC Steel 61 Signal Fail. to Valve FO
BODY 37 Bonnet Type Material Style 1 Extension WCC Steel 62 Electric Enclosure Ex ia IIC T5 , NEMA 4X
AND 38 Flow Direct. Flow Act. To Up FTO 63 MFR Model N/A N/A
TRIM 39 Packing Type Material Enviro Seal Graphite ULF 64 Type Power N/A N/A
SOLENOID
40 Lubricator Isolat. Valve N/A N/A 65 When De-Enegr.Valve: N/A
VALVE
41 Guiding No. of Ports Post 1 66 Material Latcher N/A N/A
42 Trim Type Internal Design Standard Unbalanced 67 Electric Enclosure N/A
43 Rated Travel Leak Class 3/4 in ANSI IV 68 MFR Model N/A N/A
44 Plug/ Ball/ Disk Material S41600 SST 69 Type Quantity N/A N/A
45 Seat Material S41600 SST SWITCHES 70 Contacts / Rating N/A
46 Cage Stem Material N/A S31600 SST 71 Switching Position N/A
47 Gasket Material S31600 SST/Graphite 72 Electric Enclosure N/A
48 MFR Model FISHER 657 73 MFR Model FISHER 67CFR
49 Type Diaphragm Spring Return AIR SET 74 Set Pressure 4.2 kgf/cm2-g
50 Size Stroke Time 34i < 5 Sec 75 Filter Gauge 5 Micron min YES
ACTUATOR 51 Air Failure Valve: FO 76 Vol. Tank Booster NO NO
52 Handwheel Location N/A 77 Diffuser Lock-up NO NO
ACCESSORY
53 Mounting Position VERTICAL 78 Fire Safe Fireproof NO NO
54 Spring Range 0.4 - 2.0 kgf/cm2-g 79 Mech. Stop Quick Exa. YES (DOWN STOP) NO
55 Include Pressure (Shutoff) 80 Hydro. Pressure YES
85 Vendor EMERSON 81 Leakage YES
PURCHASE TESTS
86 Manufacturer FISHER 82 Cryogenic N/A
87 Requisition No. R2B-P3-206-02-P-MR-00200 83 NACE Requirement N/A
88 Model No. EZ 84 PWHT Requirement N/A
Notes:

INSTRUMENT SPECIFICATION - CONTROL VALVE


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S26.1 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Fieldbus Device Data Sheet
Tag No.: FV -21047
Fieldbus Tag No.:

Service : FA004 MP STM TO DC001 RX

Basic Fieldbus Function Blocks Segment Information


Analog Input Block (AI) 1 Number Device:
1 22
20 Execution (msec)
Discrete Input Block (DI) 4 Number Segment #: DFJB-21036
2 23
15 Execution Time
3 Bias/Gain Station (BG) 0 Execution (msec) 24 LAS Capable: Yes No
Manual Loader (ML) 0 Number 25 Device Current Draw (mA): 19
4
0 Execution (msec) Device Minimum Voltage: 9.
26
Analog Output Block (AO) 1 Number Device Capacitance: 5 nF
5 20 Execution (msec) Polarity-sensitive: Yes No
27
Discrete Output Block (DO) 1 Number Segment Terminator Location:
6 20 Execution (msec)
28
7 Control Selector (CS)
DD Revision: 3
PID,PI,I Controller (PID) 29
8
20 Execution (msec)
CFF Revision: 1.9
Ratio Station (RA) 30
9
P,PD Controller (PD) 0 Number
10 0 Execution (msec)

* Execution time in msec.

Advanced Function Blocks Notes:

11 Device Control (DC)

12 Output Splitter (OS)

13 Signal Characterizer (SC)

14 Lead Lag (LL)

15 Deadtime (DT)

16 Integrator(Totalizer) (IT)

17 Setpoint Ramp Generator (SPG)

18 Input Selector (IS)

19 Arithmetic (AR)

20 Timer (TMR)

21 Analog Alarm (AAL)

INSTRUMENT SPECIFICATION -FOUNDATION FIELDBUS


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S26.2 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Tag Number : FV -21047

1. Provide an adjustable limit stop with locking feature, per vendor design practice, to limit travel in the closed position.Field set limit stop to maintain the
minimum flow requirement for associated equipment or service.

2. In-Built surge protector is provided by vendor.

1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S26.3 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
1 Tag No. FV -21052
2 Service MP STM TO DC001 RX
3 P&ID No. Line No. R2B-P3-206-02-A-DTI-00069 10"-VM-210521-T-B04T1-EC
4 Area Classification Ingress Protection CLASS 1 DIV 2 Gr. B ,C&D, T3 NEMA 4X
GENERAL 5 Ambient Temperature: Unit Min. Max. °C 10 48
6 Allowable Sound dBA Tightness Requirement <85 ANSI IV (standard)
7 Available Air Supply Pressure Unit Min. Max. kgf/cm²-g 4.2 8.0
8 Electric Connection Pneum. Connection 1/2” NPT (F) 1/2” NPT (F)
9 Power Failure Position FC
10 Line Size and Schedule Sch. Outlet Line Sch. 10 in STD 16" 40
PIPE
11 Line Class Rating Pipe Material T-B04T1 300# A106 GR.B, SMLS
LINE
12 Pipe Insulation Thickness Corrosion Allowance EC 115mm 1.6mm
13 Fluid State Phase Steam Gas/Vapor Single Phase
14 Sour Service Special Condition N/A N/A
15 Flow Rate Units Min. Nor. Max. kg/h 29087 29087 29087
16 Inlet Pressure Units Min. Nor. Max. kgf/cm²-g 13.34 9.67 8.759
17 Pressure Drop Units Min. Nor. Max. kgf/cm² 11.06 7.3 6.775
18 Inlet Temperature Units Min. Nor. Max. °C 219 219 219
PROCESS 19 Density Units Min. Nor. Max. kg/m³
CONDITIONS 20 Viscosity Units Min. Nor. Max. cP 0.017 0.017 0.017
21 Molecular Weight (MW) Specific Gravity @ Oper. 18.02
22 Spec. Heat Ratio (Cp/Cv) Compressibility (Z) 1.239 0.948
23 Vapor Pressure (Liq.) Cavitation or Flashing kgf/cm²-a N/A
24 Critical Pressure (Liq) Flash (wt%) kgf/cm²-a
25 Design Pressure Min. Max. -1.033 kgf/cm²-g 15.5 kgf/cm²-g
26 Design Temperature Min. Max. 10 °C 260 °C
27 Max.Shutoff DP Solid % 15.5 kgf/cm²
28 Calculated Cv Units Min. Nor. Max. Cv 201 270 296
CALCULATED
29 Travel Units Min. Nor. Max. % 40 56 61
RESULTS
30 Noise dBA @1m Units Min. Nor. Max. dBA 83 80 80
31 MFR Model FISHER EWT 56 MFR Model FISHER DVC6200F/SC-AD
32 Body Type Single Seat Globe 57 Signal: Inlet Outlet FF Protocol 0-2.8 kgf/cm2
33 Body Size Trim Size 8 in 7 in 58 Increase Signal Valve: DIRECT
34 End Connec.Size & Rating 8" 300# RF POSITIONER 59 Cam Characteristic LINEAR
35 Rated Cv Characteristic 460 Linear 60 Bypass Gauges N/A YES
36 Body Material WCC Steel 61 Signal Fail. to Valve FC
BODY 37 Bonnet Type Material Plain WCC Steel 62 Electric Enclosure Ex ia IIC T5 , NEMA 4X
AND 38 Flow Direct. Flow Act. To Up FTC 63 MFR Model N/A N/A
TRIM 39 Packing Type Material Enviro Seal Graphite ULF 64 Type Power N/A N/A
SOLENOID
40 Lubricator Isolat. Valve N/A N/A 65 When De-Enegr.Valve: N/A
VALVE
41 Guiding No. of Ports Cage 1 66 Material Latcher N/A N/A
42 Trim Type Internal Design Whisper III Balanced 67 Electric Enclosure N/A
43 Rated Travel Leak Class 3 3/4 in ANSI IV 68 MFR Model N/A N/A
44 Plug/ Ball/ Disk Material S41600 SST 69 Type Quantity N/A N/A
45 Seat Material S41600 SST SWITCHES 70 Contacts / Rating N/A
46 Cage Stem Material CB7Cu-1 SST S31600 SST 71 Switching Position N/A
47 Gasket Material S31600 SST/Graphite 72 Electric Enclosure N/A
48 MFR Model FISHER 667-4 73 MFR Model FISHER 67DFR
49 Type Diaphragm Spring Return AIR SET 74 Set Pressure 4.2 kgf/cm2-g
50 Size Stroke Time 70i < 25 Sec 75 Filter Gauge 5 Micron min YES
ACTUATOR 51 Air Failure Valve: FC 76 Vol. Tank Booster NO NO
52 Handwheel Location N/A 77 Diffuser Lock-up NO NO
ACCESSORY
53 Mounting Position VERTICAL 78 Fire Safe Fireproof NO NO
54 Spring Range 0.8 - 1.9 kgf/cm2-g 79 Mech. Stop Quick Exa. NO NO
55 Include Pressure (Shutoff) 80 Hydro. Pressure YES
85 Vendor EMERSON 81 Leakage YES
PURCHASE TESTS
86 Manufacturer FISHER 82 Cryogenic N/A
87 Requisition No. R2B-P3-206-02-P-MR-00200 83 NACE Requirement N/A
88 Model No. EWT 84 PWHT Requirement N/A
Notes:

INSTRUMENT SPECIFICATION - CONTROL VALVE


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S27.1 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Fieldbus Device Data Sheet
Tag No.: FV -21052
Fieldbus Tag No.:

Service : MP STM TO DC001 RX

Basic Fieldbus Function Blocks Segment Information


Analog Input Block (AI) 1 Number Device:
1 22
20 Execution (msec)
Discrete Input Block (DI) 4 Number Segment #: DFJB-21048
2 23
15 Execution Time
3 Bias/Gain Station (BG) 0 Execution (msec) 24 LAS Capable: Yes No
Manual Loader (ML) 0 Number 25 Device Current Draw (mA): 19
4
0 Execution (msec) Device Minimum Voltage: 9.
26
Analog Output Block (AO) 1 Number Device Capacitance: 5 nF
5 20 Execution (msec) Polarity-sensitive: Yes No
27
Discrete Output Block (DO) 1 Number Segment Terminator Location:
6 20 Execution (msec)
28
7 Control Selector (CS)
DD Revision: 3
PID,PI,I Controller (PID) 29
8
20 Execution (msec)
CFF Revision: 1.9
Ratio Station (RA) 30
9
P,PD Controller (PD) 0 Number
10 0 Execution (msec)

* Execution time in msec.

Advanced Function Blocks Notes:

11 Device Control (DC)

12 Output Splitter (OS)

13 Signal Characterizer (SC)

14 Lead Lag (LL)

15 Deadtime (DT)

16 Integrator(Totalizer) (IT)

17 Setpoint Ramp Generator (SPG)

18 Input Selector (IS)

19 Arithmetic (AR)

20 Timer (TMR)

21 Analog Alarm (AAL)

INSTRUMENT SPECIFICATION -FOUNDATION FIELDBUS


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S27.2 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Tag Number : FV -21052

1. Locked closed during normal operation.

2. In-Built surge protector is provided by vendor.

1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S27.3 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
1 Tag No. FV -21053
2 Service FA003 MP STM TO DC001 RX
3 P&ID No. Line No. R2B-P3-206-02-A-DTI-00069 4"-VM-210508-T-B04T1-EC
4 Area Classification Ingress Protection CLASS 1 DIV 2 Gr. B ,C&D, T3 NEMA 4X
GENERAL 5 Ambient Temperature: Unit Min. Max. °C 10 48
6 Allowable Sound dBA Tightness Requirement <85 ANSI IV (standard)
7 Available Air Supply Pressure Unit Min. Max. kgf/cm²-g 4.2 8.0
8 Electric Connection Pneum. Connection 1/2” NPT (F) 1/4” NPT (F)
9 Power Failure Position FO
10 Line Size and Schedule Sch. Outlet Line Sch. 4 in STD 4" STD
PIPE
11 Line Class Rating Pipe Material T-B04T1 300# A106 GR.B, SMLS
LINE
12 Pipe Insulation Thickness Corrosion Allowance EC 100mm 1.6mm
13 Fluid State Phase Steam Gas/Vapor Single Phase
14 Sour Service Special Condition N/A N/A
15 Flow Rate Units Min. Nor. Max. kg/h 1531 1531 1531
16 Inlet Pressure Units Min. Nor. Max. kgf/cm²-g 6.16 6.14 6.104
17 Pressure Drop Units Min. Nor. Max. kgf/cm² 4.223 3.62 3.48
18 Inlet Temperature Units Min. Nor. Max. °C 211 211 211
PROCESS 19 Density Units Min. Nor. Max. kg/m³
CONDITIONS 20 Viscosity Units Min. Nor. Max. cP 0.017 0.017 0.017
21 Molecular Weight (MW) Specific Gravity @ Oper. 18.02
22 Spec. Heat Ratio (Cp/Cv) Compressibility (Z) 1.26 0.965
23 Vapor Pressure (Liq.) Cavitation or Flashing kgf/cm²-a N/A
24 Critical Pressure (Liq) Flash (wt%) kgf/cm²-a
25 Design Pressure Min. Max. -1.033 kgf/cm²-g 7.38 kgf/cm²-g
26 Design Temperature Min. Max. 10 °C 260 °C
27 Max.Shutoff DP Solid % 7.38 kgf/cm²
28 Calculated Cv Units Min. Nor. Max. Cv 22.9 23.2 23.4
CALCULATED
29 Travel Units Min. Nor. Max. % 38 38 39
RESULTS
30 Noise dBA @1m Units Min. Nor. Max. dBA 85 85 85
31 MFR Model FISHER EZ 56 MFR Model FISHER DVC6200F/SC-AD
32 Body Type Single Seat Globe 57 Signal: Inlet Outlet FF Protocol 0-2.8 kgf/cm2
33 Body Size Trim Size 2 in 2 in 58 Increase Signal Valve: DIRECT
34 End Connec.Size & Rating 2" 300# RF POSITIONER 59 Cam Characteristic LINEAR
35 Rated Cv Characteristic 52.4 Linear 60 Bypass Gauges N/A YES
36 Body Material WCC Steel 61 Signal Fail. to Valve FO
BODY 37 Bonnet Type Material Style 1 Extension WCC Steel 62 Electric Enclosure Ex ia IIC T5 , NEMA 4X
AND 38 Flow Direct. Flow Act. To Up FTO 63 MFR Model N/A N/A
TRIM 39 Packing Type Material Enviro Seal Graphite ULF 64 Type Power N/A N/A
SOLENOID
40 Lubricator Isolat. Valve N/A N/A 65 When De-Enegr.Valve: N/A
VALVE
41 Guiding No. of Ports Post 1 66 Material Latcher N/A N/A
42 Trim Type Internal Design Standard Unbalanced 67 Electric Enclosure N/A
43 Rated Travel Leak Class 1 1/8 in ANSI IV 68 MFR Model N/A N/A
44 Plug/ Ball/ Disk Material S41600 SST 69 Type Quantity N/A N/A
45 Seat Material S41600 SST SWITCHES 70 Contacts / Rating N/A
46 Cage Stem Material N/A S31600 SST 71 Switching Position N/A
47 Gasket Material S31600 SST/Graphite 72 Electric Enclosure N/A
48 MFR Model FISHER 657 73 MFR Model FISHER 67CFR
49 Type Diaphragm Spring Return AIR SET 74 Set Pressure 4.2 kgf/cm2-g
50 Size Stroke Time 45i < 8 Sec 75 Filter Gauge 5 Micron min YES
ACTUATOR 51 Air Failure Valve: FO 76 Vol. Tank Booster NO NO
52 Handwheel Location N/A 77 Diffuser Lock-up NO NO
ACCESSORY
53 Mounting Position VERTICAL 78 Fire Safe Fireproof NO NO
54 Spring Range 0.4 - 2.0 kgf/cm2-g 79 Mech. Stop Quick Exa. NO NO
55 Include Pressure (Shutoff) 80 Hydro. Pressure YES
85 Vendor EMERSON 81 Leakage YES
PURCHASE TESTS
86 Manufacturer FISHER 82 Cryogenic N/A
87 Requisition No. R2B-P3-206-02-P-MR-00200 83 NACE Requirement N/A
88 Model No. EZ 84 PWHT Requirement N/A
Notes:

INSTRUMENT SPECIFICATION - CONTROL VALVE


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S28.1 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Fieldbus Device Data Sheet
Tag No.: FV -21053
Fieldbus Tag No.:

Service : FA003 MP STM TO DC001 RX

Basic Fieldbus Function Blocks Segment Information


Analog Input Block (AI) 1 Number Device:
1 22
20 Execution (msec)
Discrete Input Block (DI) 4 Number Segment #: DFJB-21048
2 23
15 Execution Time
3 Bias/Gain Station (BG) 0 Execution (msec) 24 LAS Capable: Yes No
Manual Loader (ML) 0 Number 25 Device Current Draw (mA): 19
4
0 Execution (msec) Device Minimum Voltage: 9.
26
Analog Output Block (AO) 1 Number Device Capacitance: 5 nF
5 20 Execution (msec) Polarity-sensitive: Yes No
27
Discrete Output Block (DO) 1 Number Segment Terminator Location:
6 20 Execution (msec)
28
7 Control Selector (CS)
DD Revision: 3
PID,PI,I Controller (PID) 29
8
20 Execution (msec)
CFF Revision: 1.9
Ratio Station (RA) 30
9
P,PD Controller (PD) 0 Number
10 0 Execution (msec)

* Execution time in msec.

Advanced Function Blocks Notes:

11 Device Control (DC)

12 Output Splitter (OS)

13 Signal Characterizer (SC)

14 Lead Lag (LL)

15 Deadtime (DT)

16 Integrator(Totalizer) (IT)

17 Setpoint Ramp Generator (SPG)

18 Input Selector (IS)

19 Arithmetic (AR)

20 Timer (TMR)

21 Analog Alarm (AAL)

INSTRUMENT SPECIFICATION -FOUNDATION FIELDBUS


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S28.2 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Tag Number : FV -21053

1. In-Built surge protector is provided by vendor.

1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S28.3 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
1 Tag No. FV -21055
2 Service FA003 MP STM TO DC001 RX
3 P&ID No. Line No. R2B-P3-206-02-A-DTI-00069 4"-VM-210684-T-B04T1-EC
4 Area Classification Ingress Protection CLASS 1 DIV 2 Gr. B ,C&D, T3 NEMA 4X
GENERAL 5 Ambient Temperature: Unit Min. Max. °C 10 48
6 Allowable Sound dBA Tightness Requirement <85 ANSI IV (standard)
7 Available Air Supply Pressure Unit Min. Max. kgf/cm²-g 4.2 8.0
8 Electric Connection Pneum. Connection 1/2” NPT (F) 1/4” NPT (F)
9 Power Failure Position FO
10 Line Size and Schedule Sch. Outlet Line Sch. 3 in STD 4" STD
PIPE
11 Line Class Rating Pipe Material T-B04T1 300# A106 GR.B, SMLS
LINE
12 Pipe Insulation Thickness Corrosion Allowance EC 90mm 1.6mm
13 Fluid State Phase Steam Gas/Vapor Single Phase
14 Sour Service Special Condition N/A N/A
15 Flow Rate Units Min. Nor. Max. kg/h 907 1133 1360
16 Inlet Pressure Units Min. Nor. Max. kgf/cm²-g 6.18 6.05 5.94
17 Pressure Drop Units Min. Nor. Max. kgf/cm² 4.62 4.04 3.7
18 Inlet Temperature Units Min. Nor. Max. °C 211 211 211
PROCESS 19 Density Units Min. Nor. Max. kg/m³
CONDITIONS 20 Viscosity Units Min. Nor. Max. cP 0.017 0.017 0.017
21 Molecular Weight (MW) Specific Gravity @ Oper. 18.02
22 Spec. Heat Ratio (Cp/Cv) Compressibility (Z) 1.26 0.965
23 Vapor Pressure (Liq.) Cavitation or Flashing kgf/cm²-a N/A
24 Critical Pressure (Liq) Flash (wt%) kgf/cm²-a
25 Design Pressure Min. Max. -1.033 kgf/cm²-g 7.38 kgf/cm²-g
26 Design Temperature Min. Max. 10 °C 260 °C
27 Max.Shutoff DP Solid % 7.38 kgf/cm²
28 Calculated Cv Units Min. Nor. Max. Cv 13.4 17.3 21.6
CALCULATED
29 Travel Units Min. Nor. Max. % 36 46 58
RESULTS
30 Noise dBA @1m Units Min. Nor. Max. dBA 85 85 85
31 MFR Model FISHER EZ 56 MFR Model FISHER DVC6200F/SC-AD
32 Body Type Single Seat Globe 57 Signal: Inlet Outlet FF Protocol 0-2.8 kgf/cm2
33 Body Size Trim Size 1.5 in 1 1/2 in 58 Increase Signal Valve: DIRECT
34 End Connec.Size & Rating 1.5" 300# RF POSITIONER 59 Cam Characteristic LINEAR
35 Rated Cv Characteristic 31.9 Linear 60 Bypass Gauges N/A YES
36 Body Material WCC Steel 61 Signal Fail. to Valve FO
BODY 37 Bonnet Type Material Style 1 Extension WCC Steel 62 Electric Enclosure Ex ia IIC T5 , NEMA 4X
AND 38 Flow Direct. Flow Act. To Up FTO 63 MFR Model N/A N/A
TRIM 39 Packing Type Material Enviro Seal Graphite ULF 64 Type Power N/A N/A
SOLENOID
40 Lubricator Isolat. Valve N/A N/A 65 When De-Enegr.Valve: N/A
VALVE
41 Guiding No. of Ports Post 1 66 Material Latcher N/A N/A
42 Trim Type Internal Design Standard Unbalanced 67 Electric Enclosure N/A
43 Rated Travel Leak Class 3/4 in ANSI IV 68 MFR Model N/A N/A
44 Plug/ Ball/ Disk Material S41600 SST 69 Type Quantity N/A N/A
45 Seat Material S41600 SST SWITCHES 70 Contacts / Rating N/A
46 Cage Stem Material N/A S31600 SST 71 Switching Position N/A
47 Gasket Material S31600 SST/Graphite 72 Electric Enclosure N/A
48 MFR Model FISHER 657 73 MFR Model FISHER 67CFR
49 Type Diaphragm Spring Return AIR SET 74 Set Pressure 4.2 kgf/cm2-g
50 Size Stroke Time 34i < 5 Sec 75 Filter Gauge 5 Micron min YES
ACTUATOR 51 Air Failure Valve: FO 76 Vol. Tank Booster NO NO
52 Handwheel Location N/A 77 Diffuser Lock-up NO NO
ACCESSORY
53 Mounting Position VERTICAL 78 Fire Safe Fireproof NO NO
54 Spring Range 0.4 - 2.0 kgf/cm2-g 79 Mech. Stop Quick Exa. NO NO
55 Include Pressure (Shutoff) 80 Hydro. Pressure YES
85 Vendor EMERSON 81 Leakage YES
PURCHASE TESTS
86 Manufacturer FISHER 82 Cryogenic N/A
87 Requisition No. R2B-P3-206-02-P-MR-00200 83 NACE Requirement N/A
88 Model No. EZ 84 PWHT Requirement N/A
Notes:

INSTRUMENT SPECIFICATION - CONTROL VALVE


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S29.1 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Fieldbus Device Data Sheet
Tag No.: FV -21055
Fieldbus Tag No.:

Service : FA003 MP STM TO DC001 RX

Basic Fieldbus Function Blocks Segment Information


Analog Input Block (AI) 1 Number Device:
1 22
20 Execution (msec)
Discrete Input Block (DI) 4 Number Segment #: DFJB-21045
2 23
15 Execution Time
3 Bias/Gain Station (BG) 0 Execution (msec) 24 LAS Capable: Yes No
Manual Loader (ML) 0 Number 25 Device Current Draw (mA): 19
4
0 Execution (msec) Device Minimum Voltage: 9.
26
Analog Output Block (AO) 1 Number Device Capacitance: 5 nF
5 20 Execution (msec) Polarity-sensitive: Yes No
27
Discrete Output Block (DO) 1 Number Segment Terminator Location:
6 20 Execution (msec)
28
7 Control Selector (CS)
DD Revision: 3
PID,PI,I Controller (PID) 29
8
20 Execution (msec)
CFF Revision: 1.9
Ratio Station (RA) 30
9
P,PD Controller (PD) 0 Number
10 0 Execution (msec)

* Execution time in msec.

Advanced Function Blocks Notes:

11 Device Control (DC)

12 Output Splitter (OS)

13 Signal Characterizer (SC)

14 Lead Lag (LL)

15 Deadtime (DT)

16 Integrator(Totalizer) (IT)

17 Setpoint Ramp Generator (SPG)

18 Input Selector (IS)

19 Arithmetic (AR)

20 Timer (TMR)

21 Analog Alarm (AAL)

INSTRUMENT SPECIFICATION -FOUNDATION FIELDBUS


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S29.2 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Tag Number : FV -21055

1. In-Built surge protector is provided by vendor.

1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S29.3 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
1 Tag No. FV -21056
2 Service FA003 MP STM TO DC001 RX
3 P&ID No. Line No. R2B-P3-206-02-A-DTI-00069 8"-VM-210483-T-B04T1-EC
4 Area Classification Ingress Protection CLASS 1 DIV 2 Gr. B ,C&D, T3 NEMA 4X
GENERAL 5 Ambient Temperature: Unit Min. Max. °C 10 48
6 Allowable Sound dBA Tightness Requirement <85 ANSI IV (standard)
7 Available Air Supply Pressure Unit Min. Max. kgf/cm²-g 4.2 8.0
8 Electric Connection Pneum. Connection 1/2” NPT (F) 1/4” NPT (F)
9 Power Failure Position FO
10 Line Size and Schedule Sch. Outlet Line Sch. 8 in STD 8" STD
PIPE
11 Line Class Rating Pipe Material T-B04T1 300# A106 GR.B, SMLS
LINE
12 Pipe Insulation Thickness Corrosion Allowance EC 115mm 1.6mm
13 Fluid State Phase Steam Gas/Vapor Single Phase
14 Sour Service Special Condition N/A N/A
15 Flow Rate Units Min. Nor. Max. kg/h 5077 6346 7616
16 Inlet Pressure Units Min. Nor. Max. kgf/cm²-g 6.159 6.02 5.9
17 Pressure Drop Units Min. Nor. Max. kgf/cm² 4.729 3.59 3.23
18 Inlet Temperature Units Min. Nor. Max. °C 211 211 211
PROCESS 19 Density Units Min. Nor. Max. kg/m³
CONDITIONS 20 Viscosity Units Min. Nor. Max. cP 0.017 0.017 0.017
21 Molecular Weight (MW) Specific Gravity @ Oper. 18.02
22 Spec. Heat Ratio (Cp/Cv) Compressibility (Z) 1.26 0.965
23 Vapor Pressure (Liq.) Cavitation or Flashing kgf/cm²-a N/A
24 Critical Pressure (Liq) Flash (wt%) kgf/cm²-a
25 Design Pressure Min. Max. -1.033 kgf/cm²-g 7.38 kgf/cm²-g
26 Design Temperature Min. Max. 10 °C 260 °C
27 Max.Shutoff DP Solid % 7.38 kgf/cm²
28 Calculated Cv Units Min. Nor. Max. Cv 68.9 91.6 115
CALCULATED
29 Travel Units Min. Nor. Max. % 39 51 63
RESULTS
30 Noise dBA @1m Units Min. Nor. Max. dBA 74 69 70
31 MFR Model FISHER ET 56 MFR Model FISHER DVC6200F/SC-AD
32 Body Type Single Seat Globe 57 Signal: Inlet Outlet FF Protocol 0-2.8 kgf/cm2
33 Body Size Trim Size 4 in 3 7/16 in 58 Increase Signal Valve: DIRECT
34 End Connec.Size & Rating 4" 300# RF POSITIONER 59 Cam Characteristic LINEAR
35 Rated Cv Characteristic 139 Linear 60 Bypass Gauges N/A YES
36 Body Material WCC Steel 61 Signal Fail. to Valve FO
BODY 37 Bonnet Type Material Style 1 Extension WCC Steel 62 Electric Enclosure Ex ia IIC T5 , NEMA 4X
AND 38 Flow Direct. Flow Act. To Up FTC 63 MFR Model N/A N/A
TRIM 39 Packing Type Material Enviro Seal Graphite ULF 64 Type Power N/A N/A
SOLENOID
40 Lubricator Isolat. Valve N/A N/A 65 When De-Enegr.Valve: N/A
VALVE
41 Guiding No. of Ports Cage 1 66 Material Latcher N/A N/A
42 Trim Type Internal Design Whisper III Balanced 67 Electric Enclosure N/A
43 Rated Travel Leak Class 2 in ANSI IV 68 MFR Model N/A N/A
44 Plug/ Ball/ Disk Material S41600 SST 69 Type Quantity N/A N/A
45 Seat Material S41600 SST SWITCHES 70 Contacts / Rating N/A
46 Cage Stem Material CB7Cu-1 SST S31600 SST 71 Switching Position N/A
47 Gasket Material S31600 SST/Graphite 72 Electric Enclosure N/A
48 MFR Model FISHER 657 73 MFR Model FISHER 67CFR
49 Type Diaphragm Spring Return AIR SET 74 Set Pressure 4.2 kgf/cm2-g
50 Size Stroke Time 45i < 10 Sec 75 Filter Gauge 5 Micron min YES
ACTUATOR 51 Air Failure Valve: FO 76 Vol. Tank Booster NO NO
52 Handwheel Location N/A 77 Diffuser Lock-up NO NO
ACCESSORY
53 Mounting Position VERTICAL 78 Fire Safe Fireproof NO NO
54 Spring Range 0.4 - 2.0 kgf/cm2-g 79 Mech. Stop Quick Exa. NO NO
55 Include Pressure (Shutoff) 80 Hydro. Pressure YES
85 Vendor EMERSON 81 Leakage YES
PURCHASE TESTS
86 Manufacturer FISHER 82 Cryogenic N/A
87 Requisition No. R2B-P3-206-02-P-MR-00200 83 NACE Requirement N/A
88 Model No. ET 84 PWHT Requirement N/A
Notes:

INSTRUMENT SPECIFICATION - CONTROL VALVE


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S30.1 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Fieldbus Device Data Sheet
Tag No.: FV -21056
Fieldbus Tag No.:

Service : FA003 MP STM TO DC001 RX

Basic Fieldbus Function Blocks Segment Information


Analog Input Block (AI) 1 Number Device:
1 22
20 Execution (msec)
Discrete Input Block (DI) 4 Number Segment #: DFJB-21046
2 23
15 Execution Time
3 Bias/Gain Station (BG) 0 Execution (msec) 24 LAS Capable: Yes No
Manual Loader (ML) 0 Number 25 Device Current Draw (mA): 19
4
0 Execution (msec) Device Minimum Voltage: 9.
26
Analog Output Block (AO) 1 Number Device Capacitance: 5 nF
5 20 Execution (msec) Polarity-sensitive: Yes No
27
Discrete Output Block (DO) 1 Number Segment Terminator Location:
6 20 Execution (msec)
28
7 Control Selector (CS)
DD Revision: 3
PID,PI,I Controller (PID) 29
8
20 Execution (msec)
CFF Revision: 1.9
Ratio Station (RA) 30
9
P,PD Controller (PD) 0 Number
10 0 Execution (msec)

* Execution time in msec.

Advanced Function Blocks Notes:

11 Device Control (DC)

12 Output Splitter (OS)

13 Signal Characterizer (SC)

14 Lead Lag (LL)

15 Deadtime (DT)

16 Integrator(Totalizer) (IT)

17 Setpoint Ramp Generator (SPG)

18 Input Selector (IS)

19 Arithmetic (AR)

20 Timer (TMR)

21 Analog Alarm (AAL)

INSTRUMENT SPECIFICATION -FOUNDATION FIELDBUS


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S30.2 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Tag Number : FV -21056

1. In-Built surge protector is provided by vendor.

1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S30.3 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
1 Tag No. FV -21057
2 Service HP BFW TO SPE012
3 P&ID No. Line No. R2B-P3-206-02-A-DTI-00074 6"-ACAA-210383-T-D61T1S-EC
4 Area Classification Ingress Protection CLASS 1 DIV 2 Gr. B ,C&D, T3 NEMA 4X
GENERAL 5 Ambient Temperature: Unit Min. Max. °C 10 48
6 Allowable Sound dBA Tightness Requirement <85 ANSI IV (standard)
7 Available Air Supply Pressure Unit Min. Max. kgf/cm²-g 4.2 8.0
8 Electric Connection Pneum. Connection 1/2” NPT (F) 1/4” NPT (F)
9 Power Failure Position FC
10 Line Size and Schedule Sch. Outlet Line Sch. 6 in XS 8" XS
PIPE
11 Line Class Rating Pipe Material T-D61T1S 600# SA106 GR.B, SMLS
LINE
12 Pipe Insulation Thickness Corrosion Allowance EC 75mm 1.6mm
13 Fluid State Phase Water Liquid Single Phase
14 Sour Service Special Condition N/A N/A
15 Flow Rate Units Min. Nor. Max. kg/h 56793 85051 93495
16 Inlet Pressure Units Min. Nor. Max. kgf/cm²-g 70.92 66.64 64.56
17 Pressure Drop Units Min. Nor. Max. kgf/cm² 25.58 20.39 13.35
18 Inlet Temperature Units Min. Nor. Max. °C 110 110 110
PROCESS 19 Density Units Min. Nor. Max. kg/m³ 955 955 955
CONDITIONS 20 Viscosity Units Min. Nor. Max. cP 0.252 0.252 0.252
21 Molecular Weight (MW) Specific Gravity @ Oper.
22 Spec. Heat Ratio (Cp/Cv) Compressibility (Z)
23 Vapor Pressure (Liq.) Cavitation or Flashing 1.46 kgf/cm²-a NO
24 Critical Pressure (Liq) Flash (wt%) 224.99 kgf/cm²-a
25 Design Pressure Min. Max. kgf/cm²-g 77 kgf/cm²-g
26 Design Temperature Min. Max. 10 °C 150 °C
27 Max.Shutoff DP Solid % 77 kgf/cm²
28 Calculated Cv Units Min. Nor. Max. Cv 13.4 22.6 30.8
CALCULATED
29 Travel Units Min. Nor. Max. % 16 26 34
RESULTS
30 Noise dBA @1m Units Min. Nor. Max. dBA 70 68 66
31 MFR Model FISHER ET 56 MFR Model FISHER DVC6200F/SC-AD
32 Body Type Single Seat Globe 57 Signal: Inlet Outlet FF Protocol 0-2.8 kgf/cm2
33 Body Size Trim Size 3 in 2 5/16 in 58 Increase Signal Valve: DIRECT
34 End Connec.Size & Rating 3" 600# RF POSITIONER 59 Cam Characteristic LINEAR
35 Rated Cv Characteristic 102 Linear 60 Bypass Gauges N/A YES
36 Body Material WCC Steel 61 Signal Fail. to Valve FC
BODY 37 Bonnet Type Material Plain WCC Steel 62 Electric Enclosure Ex ia IIC T5 , NEMA 4X
AND 38 Flow Direct. Flow Act. To Down FTO 63 MFR Model N/A N/A
TRIM 39 Packing Type Material ISO Seal PTFE 64 Type Power N/A N/A
SOLENOID
40 Lubricator Isolat. Valve N/A N/A 65 When De-Enegr.Valve: N/A
VALVE
41 Guiding No. of Ports Cage 1 66 Material Latcher N/A N/A
42 Trim Type Internal Design Standard Balanced 67 Electric Enclosure N/A
43 Rated Travel Leak Class 1 1/8 in ANSI IV 68 MFR Model N/A N/A
44 Plug/ Ball/ Disk Material S31600 SST/CoCr-A Seat 69 Type Quantity N/A N/A
45 Seat Material CoCr-A Seat SWITCHES 70 Contacts / Rating N/A
46 Cage Stem Material S31600 SST/ ENCS31600 SST 71 Switching Position N/A
47 Gasket Material S31600 SST/Graphite 72 Electric Enclosure N/A
48 MFR Model FISHER 667 73 MFR Model FISHER 67CFR
49 Type Diaphragm Spring Return AIR SET 74 Set Pressure 4.2 kgf/cm2-g
50 Size Stroke Time 40i < 8 Sec 75 Filter Gauge 5 Micron min YES
ACTUATOR 51 Air Failure Valve: FC 76 Vol. Tank Booster NO NO
52 Handwheel Location N/A 77 Diffuser Lock-up NO NO
ACCESSORY
53 Mounting Position VERTICAL 78 Fire Safe Fireproof NO NO
54 Spring Range 1 - 2.2 kgf/cm2-g 79 Mech. Stop Quick Exa. NO NO
55 Include Pressure (Shutoff) 80 Hydro. Pressure YES
85 Vendor EMERSON 81 Leakage YES
PURCHASE TESTS
86 Manufacturer FISHER 82 Cryogenic N/A
87 Requisition No. R2B-P3-206-02-P-MR-00200 83 NACE Requirement N/A
88 Model No. ET 84 PWHT Requirement N/A
Notes:

INSTRUMENT SPECIFICATION - CONTROL VALVE


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S31.1 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Fieldbus Device Data Sheet
Tag No.: FV -21057
Fieldbus Tag No.:

Service : HP BFW TO SPE012

Basic Fieldbus Function Blocks Segment Information


Analog Input Block (AI) 1 Number Device:
1 22
20 Execution (msec)
Discrete Input Block (DI) 4 Number Segment #: DFJB-21005
2 23
15 Execution Time
3 Bias/Gain Station (BG) 0 Execution (msec) 24 LAS Capable: Yes No
Manual Loader (ML) 0 Number 25 Device Current Draw (mA): 19
4
0 Execution (msec) Device Minimum Voltage: 9.
26
Analog Output Block (AO) 1 Number Device Capacitance: 5 nF
5 20 Execution (msec) Polarity-sensitive: Yes No
27
Discrete Output Block (DO) 1 Number Segment Terminator Location:
6 20 Execution (msec)
28
7 Control Selector (CS)
DD Revision: 3
PID,PI,I Controller (PID) 29
8
20 Execution (msec)
CFF Revision: 1.9
Ratio Station (RA) 30
9
P,PD Controller (PD) 0 Number
10 0 Execution (msec)

* Execution time in msec.

Advanced Function Blocks Notes:

11 Device Control (DC)

12 Output Splitter (OS)

13 Signal Characterizer (SC)

14 Lead Lag (LL)

15 Deadtime (DT)

16 Integrator(Totalizer) (IT)

17 Setpoint Ramp Generator (SPG)

18 Input Selector (IS)

19 Arithmetic (AR)

20 Timer (TMR)

21 Analog Alarm (AAL)

INSTRUMENT SPECIFICATION -FOUNDATION FIELDBUS


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S31.2 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Tag Number : FV -21057

1. In-Built surge protector is provided by vendor.

1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S31.3 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
1 Tag No. FV -21063
2 Service PA TO DC001 RX
3 P&ID No. Line No. R2B-P3-206-02-A-DTI-00064 1-1/2"-P-210205-B2A1-N
4 Area Classification Ingress Protection CLASS 1 DIV 2 Gr. B ,C&D, T3 NEMA 4X
GENERAL 5 Ambient Temperature: Unit Min. Max. °C 10 48
6 Allowable Sound dBA Tightness Requirement <85 ANSI IV (standard)
7 Available Air Supply Pressure Unit Min. Max. kgf/cm²-g 4.2 8.0
8 Electric Connection Pneum. Connection 1/2” NPT (F) 1/4” NPT (F)
9 Power Failure Position FC
10 Line Size and Schedule Sch. Outlet Line Sch. 1-1/2 in XS 1.5" XS
PIPE
11 Line Class Rating Pipe Material B2A1 300# A106 GR.B, SMLS
LINE
12 Pipe Insulation Thickness Corrosion Allowance N N/A 1.6mm
13 Fluid State Phase Plant Air Gas/Vapor Single Phase
14 Sour Service Special Condition N/A N/A
15 Flow Rate Units Min. Nor. Max. Nm³/h 56 112 168
16 Inlet Pressure Units Min. Nor. Max. kgf/cm²-g 6.26 6.13 5.93
17 Pressure Drop Units Min. Nor. Max. kgf/cm² 3.6 2.82 1.31
18 Inlet Temperature Units Min. Nor. Max. °C 40 40 40
PROCESS 19 Density Units Min. Nor. Max. kg/m³
CONDITIONS 20 Viscosity Units Min. Nor. Max. cP 0.019 0.019 0.019
21 Molecular Weight (MW) Specific Gravity @ Oper. 28.85
22 Spec. Heat Ratio (Cp/Cv) Compressibility (Z) 1.393 0.997
23 Vapor Pressure (Liq.) Cavitation or Flashing kgf/cm²-a N/A
24 Critical Pressure (Liq) Flash (wt%) kgf/cm²-a
25 Design Pressure Min. Max. kgf/cm²-g 10.5 kgf/cm²-g
26 Design Temperature Min. Max. 10 °C 80 °C
27 Max.Shutoff DP Solid % 10.5 kgf/cm²
28 Calculated Cv Units Min. Nor. Max. Cv 0.69 1.47 2.84
CALCULATED
29 Travel Units Min. Nor. Max. % 38 60 78
RESULTS
30 Noise dBA @1m Units Min. Nor. Max. dBA 50 53 51
31 MFR Model FISHER EZ 56 MFR Model FISHER DVC6200F/SC-AD
32 Body Type Single Seat Globe 57 Signal: Inlet Outlet FF Protocol 0-2.8 kgf/cm2
33 Body Size Trim Size 1 in 1/2 in 58 Increase Signal Valve: DIRECT
34 End Connec.Size & Rating 1" 300# RF POSITIONER 59 Cam Characteristic LINEAR
35 Rated Cv Characteristic 4.91 EQ% 60 Bypass Gauges N/A YES
36 Body Material WCC Steel 61 Signal Fail. to Valve FC
BODY 37 Bonnet Type Material Plain WCC Steel 62 Electric Enclosure Ex ia IIC T5 , NEMA 4X
AND 38 Flow Direct. Flow Act. To Up FTO 63 MFR Model N/A N/A
TRIM 39 Packing Type Material Enviro Seal PTFE Carbon 64 Type Power N/A N/A
SOLENOID
40 Lubricator Isolat. Valve N/A N/A 65 When De-Enegr.Valve: N/A
VALVE
41 Guiding No. of Ports Post 1 66 Material Latcher N/A N/A
42 Trim Type Internal Design Micro Form Unbalanced 67 Electric Enclosure N/A
43 Rated Travel Leak Class 3/4 in ANSI IV 68 MFR Model N/A N/A
44 Plug/ Ball/ Disk Material S41600 SST 69 Type Quantity N/A N/A
45 Seat Material S41600 SST SWITCHES 70 Contacts / Rating N/A
46 Cage Stem Material N/A S31600 SST 71 Switching Position N/A
47 Gasket Material S31600 SST/Graphite 72 Electric Enclosure N/A
48 MFR Model FISHER 667 73 MFR Model FISHER 67CFR
49 Type Diaphragm Spring Return AIR SET 74 Set Pressure 4.2 kgf/cm2-g
50 Size Stroke Time 30i < 5 Sec 75 Filter Gauge 5 Micron min YES
ACTUATOR 51 Air Failure Valve: FC 76 Vol. Tank Booster NO NO
52 Handwheel Location N/A 77 Diffuser Lock-up NO NO
ACCESSORY
53 Mounting Position VERTICAL 78 Fire Safe Fireproof NO NO
54 Spring Range 0.8 - 2.5 kgf/cm2-g 79 Mech. Stop Quick Exa. NO NO
55 Include Pressure (Shutoff) 80 Hydro. Pressure YES
85 Vendor EMERSON 81 Leakage YES
PURCHASE TESTS
86 Manufacturer FISHER 82 Cryogenic N/A
87 Requisition No. R2B-P3-206-02-P-MR-00200 83 NACE Requirement N/A
88 Model No. EZ 84 PWHT Requirement N/A
Notes:

INSTRUMENT SPECIFICATION - CONTROL VALVE


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S32.1 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Fieldbus Device Data Sheet
Tag No.: FV -21063
Fieldbus Tag No.:

Service : PA TO DC001 RX

Basic Fieldbus Function Blocks Segment Information


Analog Input Block (AI) 1 Number Device:
1 22
20 Execution (msec)
Discrete Input Block (DI) 4 Number Segment #: DFJB-21043
2 23
15 Execution Time
3 Bias/Gain Station (BG) 0 Execution (msec) 24 LAS Capable: Yes No
Manual Loader (ML) 0 Number 25 Device Current Draw (mA): 19
4
0 Execution (msec) Device Minimum Voltage: 9.
26
Analog Output Block (AO) 1 Number Device Capacitance: 5 nF
5 20 Execution (msec) Polarity-sensitive: Yes No
27
Discrete Output Block (DO) 1 Number Segment Terminator Location:
6 20 Execution (msec)
28
7 Control Selector (CS)
DD Revision: 3
PID,PI,I Controller (PID) 29
8
20 Execution (msec)
CFF Revision: 1.9
Ratio Station (RA) 30
9
P,PD Controller (PD) 0 Number
10 0 Execution (msec)

* Execution time in msec.

Advanced Function Blocks Notes:

11 Device Control (DC)

12 Output Splitter (OS)

13 Signal Characterizer (SC)

14 Lead Lag (LL)

15 Deadtime (DT)

16 Integrator(Totalizer) (IT)

17 Setpoint Ramp Generator (SPG)

18 Input Selector (IS)

19 Arithmetic (AR)

20 Timer (TMR)

21 Analog Alarm (AAL)

INSTRUMENT SPECIFICATION -FOUNDATION FIELDBUS


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S32.2 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Tag Number : FV -21063

1. In-Built surge protector is provided by vendor.

1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S32.3 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
1 Tag No. FV -21064
2 Service N2 TO DC21002 RG
3 P&ID No. Line No. R2B-P3-206-02-A-DTI-00067 1-1/2"-GI-210370-T-A18T1-EC
4 Area Classification Ingress Protection CLASS 1 DIV 2 Gr. B ,C&D, T3 NEMA 4X
GENERAL 5 Ambient Temperature: Unit Min. Max. °C 10 48
6 Allowable Sound dBA Tightness Requirement <85 ANSI IV (standard)
7 Available Air Supply Pressure Unit Min. Max. kgf/cm²-g 4.2 8.0
8 Electric Connection Pneum. Connection 1/2” NPT (F) 1/4” NPT (F)
9 Power Failure Position FC
10 Line Size and Schedule Sch. Outlet Line Sch. 1-1/2 in XS 1.5" XS
PIPE
11 Line Class Rating Pipe Material T-A18T1 150# A106 GR.B, SMLS
LINE
12 Pipe Insulation Thickness Corrosion Allowance N N/A 1.6mm
13 Fluid State Phase Steam Gas/Vapor Single Phase
14 Sour Service Special Condition N/A N/A
15 Flow Rate Units Min. Nor. Max. kg/h 93 187 282
16 Inlet Pressure Units Min. Nor. Max. kgf/cm²-g 6.25 6.1 5.86
17 Pressure Drop Units Min. Nor. Max. kgf/cm² 3.29 2.61 1.49
18 Inlet Temperature Units Min. Nor. Max. °C 210 210 210
PROCESS 19 Density Units Min. Nor. Max. kg/m³
CONDITIONS 20 Viscosity Units Min. Nor. Max. cP 0.017 0.017 0.017
21 Molecular Weight (MW) Specific Gravity @ Oper. 18.02
22 Spec. Heat Ratio (Cp/Cv) Compressibility (Z) 1.261 0.966
23 Vapor Pressure (Liq.) Cavitation or Flashing kgf/cm²-a N/A
24 Critical Pressure (Liq) Flash (wt%) kgf/cm²-a
25 Design Pressure Min. Max. -1.033 kgf/cm²-g 7.382 kgf/cm²-g
26 Design Temperature Min. Max. 10 °C 260 °C
27 Max.Shutoff DP Solid % 7.382 kgf/cm²
28 Calculated Cv Units Min. Nor. Max. Cv 1.43 3.1 5.61
CALCULATED
29 Travel Units Min. Nor. Max. % 23 45 61
RESULTS
30 Noise dBA @1m Units Min. Nor. Max. dBA 50 53 53
31 MFR Model FISHER EZ 56 MFR Model FISHER DVC6200F/SC-AD
32 Body Type Single Seat Globe 57 Signal: Inlet Outlet FF Protocol 0-2.8 kgf/cm2
33 Body Size Trim Size 1 in 1 in 58 Increase Signal Valve: DIRECT
34 End Connec.Size & Rating 1" 300# RF POSITIONER 59 Cam Characteristic LINEAR
35 Rated Cv Characteristic 13.2 EQ% 60 Bypass Gauges N/A YES
36 Body Material WCC Steel 61 Signal Fail. to Valve FC
BODY 37 Bonnet Type Material Plain WCC Steel 62 Electric Enclosure Ex ia IIC T5 , NEMA 4X
AND 38 Flow Direct. Flow Act. To Up FTO 63 MFR Model N/A N/A
TRIM 39 Packing Type Material Enviro Seal Graphite ULF 64 Type Power N/A N/A
SOLENOID
40 Lubricator Isolat. Valve N/A N/A 65 When De-Enegr.Valve: N/A
VALVE
41 Guiding No. of Ports Post 1 66 Material Latcher N/A N/A
42 Trim Type Internal Design Standard Unbalanced 67 Electric Enclosure N/A
43 Rated Travel Leak Class 3/4 in ANSI IV 68 MFR Model N/A N/A
44 Plug/ Ball/ Disk Material S41600 SST 69 Type Quantity N/A N/A
45 Seat Material S41600 SST SWITCHES 70 Contacts / Rating N/A
46 Cage Stem Material N/A S31600 SST 71 Switching Position N/A
47 Gasket Material S31600 SST/Graphite 72 Electric Enclosure N/A
48 MFR Model FISHER 667 73 MFR Model FISHER 67CFR
49 Type Diaphragm Spring Return AIR SET 74 Set Pressure 4.2 kgf/cm2-g
50 Size Stroke Time 30i < 5 Sec 75 Filter Gauge 5 Micron min YES
ACTUATOR 51 Air Failure Valve: FC 76 Vol. Tank Booster NO NO
52 Handwheel Location N/A 77 Diffuser Lock-up NO NO
ACCESSORY
53 Mounting Position VERTICAL 78 Fire Safe Fireproof NO NO
54 Spring Range 1.2 - 2.3 kgf/cm2-g 79 Mech. Stop Quick Exa. NO NO
55 Include Pressure (Shutoff) 80 Hydro. Pressure YES
85 Vendor EMERSON 81 Leakage YES
PURCHASE TESTS
86 Manufacturer FISHER 82 Cryogenic N/A
87 Requisition No. R2B-P3-206-02-P-MR-00200 83 NACE Requirement N/A
88 Model No. EZ 84 PWHT Requirement N/A
Notes:

INSTRUMENT SPECIFICATION - CONTROL VALVE


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S33.1 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Fieldbus Device Data Sheet
Tag No.: FV -21064
Fieldbus Tag No.:

Service : N2 TO DC21002 RG

Basic Fieldbus Function Blocks Segment Information


Analog Input Block (AI) 1 Number Device:
1 22
20 Execution (msec)
Discrete Input Block (DI) 4 Number Segment #: DFJB-21043
2 23
15 Execution Time
3 Bias/Gain Station (BG) 0 Execution (msec) 24 LAS Capable: Yes No
Manual Loader (ML) 0 Number 25 Device Current Draw (mA): 19
4
0 Execution (msec) Device Minimum Voltage: 9.
26
Analog Output Block (AO) 1 Number Device Capacitance: 5 nF
5 20 Execution (msec) Polarity-sensitive: Yes No
27
Discrete Output Block (DO) 1 Number Segment Terminator Location:
6 20 Execution (msec)
28
7 Control Selector (CS)
DD Revision: 3
PID,PI,I Controller (PID) 29
8
20 Execution (msec)
CFF Revision: 1.9
Ratio Station (RA) 30
9
P,PD Controller (PD) 0 Number
10 0 Execution (msec)

* Execution time in msec.

Advanced Function Blocks Notes:

11 Device Control (DC)

12 Output Splitter (OS)

13 Signal Characterizer (SC)

14 Lead Lag (LL)

15 Deadtime (DT)

16 Integrator(Totalizer) (IT)

17 Setpoint Ramp Generator (SPG)

18 Input Selector (IS)

19 Arithmetic (AR)

20 Timer (TMR)

21 Analog Alarm (AAL)

INSTRUMENT SPECIFICATION -FOUNDATION FIELDBUS


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S33.2 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Tag Number : FV -21064

1. In-Built surge protector is provided by vendor.

1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S33.3 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
1 Tag No. FV -21065
2 Service PA TO DC001 RX
3 P&ID No. Line No. R2B-P3-206-02-A-DTI-00064 1-1/2"-P-210210-B2A1-N
4 Area Classification Ingress Protection CLASS 1 DIV 2 Gr. B ,C&D, T3 NEMA 4X
GENERAL 5 Ambient Temperature: Unit Min. Max. °C 10 48
6 Allowable Sound dBA Tightness Requirement <85 ANSI IV (standard)
7 Available Air Supply Pressure Unit Min. Max. kgf/cm²-g 4.2 8.0
8 Electric Connection Pneum. Connection 1/2” NPT (F) 1/4” NPT (F)
9 Power Failure Position FC
10 Line Size and Schedule Sch. Outlet Line Sch. 1-1/2 in XS 1.5" XS
PIPE
11 Line Class Rating Pipe Material B2A1 300# A106 GR.B, SMLS
LINE
12 Pipe Insulation Thickness Corrosion Allowance N N/A 1.6mm
13 Fluid State Phase Plant Air Gas/Vapor Single Phase
14 Sour Service Special Condition N/A N/A
15 Flow Rate Units Min. Nor. Max. Nm³/h 56 112 168
16 Inlet Pressure Units Min. Nor. Max. kgf/cm²-g 6.26 6.13 5.93
17 Pressure Drop Units Min. Nor. Max. kgf/cm² 3.6 2.82 1.31
18 Inlet Temperature Units Min. Nor. Max. °C 40 40 40
PROCESS 19 Density Units Min. Nor. Max. kg/m³
CONDITIONS 20 Viscosity Units Min. Nor. Max. cP 0.019 0.019 0.019
21 Molecular Weight (MW) Specific Gravity @ Oper. 28.85
22 Spec. Heat Ratio (Cp/Cv) Compressibility (Z) 1.393 0.997
23 Vapor Pressure (Liq.) Cavitation or Flashing kgf/cm²-a N/A
24 Critical Pressure (Liq) Flash (wt%) kgf/cm²-a
25 Design Pressure Min. Max. kgf/cm²-g 10.5 kgf/cm²-g
26 Design Temperature Min. Max. 10 °C 80 °C
27 Max.Shutoff DP Solid % 10.5 kgf/cm²
28 Calculated Cv Units Min. Nor. Max. Cv 0.69 1.47 2.84
CALCULATED
29 Travel Units Min. Nor. Max. % 38 60 78
RESULTS
30 Noise dBA @1m Units Min. Nor. Max. dBA 50 53 51
31 MFR Model FISHER EZ 56 MFR Model FISHER DVC6200F/SC-AD
32 Body Type Single Seat Globe 57 Signal: Inlet Outlet FF Protocol 0-2.8 kgf/cm2
33 Body Size Trim Size 1 in 1/2 in 58 Increase Signal Valve: DIRECT
34 End Connec.Size & Rating 1" 300# RF POSITIONER 59 Cam Characteristic LINEAR
35 Rated Cv Characteristic 4.91 EQ% 60 Bypass Gauges N/A YES
36 Body Material WCC Steel 61 Signal Fail. to Valve FC
BODY 37 Bonnet Type Material Plain WCC Steel 62 Electric Enclosure Ex ia IIC T5 , NEMA 4X
AND 38 Flow Direct. Flow Act. To Up FTO 63 MFR Model N/A N/A
TRIM 39 Packing Type Material Enviro Seal PTFE Carbon 64 Type Power N/A N/A
SOLENOID
40 Lubricator Isolat. Valve N/A N/A 65 When De-Enegr.Valve: N/A
VALVE
41 Guiding No. of Ports Post 1 66 Material Latcher N/A N/A
42 Trim Type Internal Design Micro Form Unbalanced 67 Electric Enclosure N/A
43 Rated Travel Leak Class 3/4 in ANSI IV 68 MFR Model N/A N/A
44 Plug/ Ball/ Disk Material S41600 SST 69 Type Quantity N/A N/A
45 Seat Material S41600 SST SWITCHES 70 Contacts / Rating N/A
46 Cage Stem Material N/A S31600 SST 71 Switching Position N/A
47 Gasket Material S31600 SST/Graphite 72 Electric Enclosure N/A
48 MFR Model FISHER 667 73 MFR Model FISHER 67CFR
49 Type Diaphragm Spring Return AIR SET 74 Set Pressure 4.2 kgf/cm2-g
50 Size Stroke Time 30i < 5 Sec 75 Filter Gauge 5 Micron min YES
ACTUATOR 51 Air Failure Valve: FC 76 Vol. Tank Booster NO NO
52 Handwheel Location N/A 77 Diffuser Lock-up NO NO
ACCESSORY
53 Mounting Position VERTICAL 78 Fire Safe Fireproof NO NO
54 Spring Range 0.8 - 2.5 kgf/cm2-g 79 Mech. Stop Quick Exa. NO NO
55 Include Pressure (Shutoff) 80 Hydro. Pressure YES
85 Vendor EMERSON 81 Leakage YES
PURCHASE TESTS
86 Manufacturer FISHER 82 Cryogenic N/A
87 Requisition No. R2B-P3-206-02-P-MR-00200 83 NACE Requirement N/A
88 Model No. EZ 84 PWHT Requirement N/A
Notes:

INSTRUMENT SPECIFICATION - CONTROL VALVE


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S34.1 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Fieldbus Device Data Sheet
Tag No.: FV -21065
Fieldbus Tag No.:

Service : PA TO DC001 RX

Basic Fieldbus Function Blocks Segment Information


Analog Input Block (AI) 1 Number Device:
1 22
20 Execution (msec)
Discrete Input Block (DI) 4 Number Segment #: DFJB-21040
2 23
15 Execution Time
3 Bias/Gain Station (BG) 0 Execution (msec) 24 LAS Capable: Yes No
Manual Loader (ML) 0 Number 25 Device Current Draw (mA): 19
4
0 Execution (msec) Device Minimum Voltage: 9.
26
Analog Output Block (AO) 1 Number Device Capacitance: 5 nF
5 20 Execution (msec) Polarity-sensitive: Yes No
27
Discrete Output Block (DO) 1 Number Segment Terminator Location:
6 20 Execution (msec)
28
7 Control Selector (CS)
DD Revision: 3
PID,PI,I Controller (PID) 29
8
20 Execution (msec)
CFF Revision: 1.9
Ratio Station (RA) 30
9
P,PD Controller (PD) 0 Number
10 0 Execution (msec)

* Execution time in msec.

Advanced Function Blocks Notes:

11 Device Control (DC)

12 Output Splitter (OS)

13 Signal Characterizer (SC)

14 Lead Lag (LL)

15 Deadtime (DT)

16 Integrator(Totalizer) (IT)

17 Setpoint Ramp Generator (SPG)

18 Input Selector (IS)

19 Arithmetic (AR)

20 Timer (TMR)

21 Analog Alarm (AAL)

INSTRUMENT SPECIFICATION -FOUNDATION FIELDBUS


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S34.2 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Tag Number : FV -21065

1. In-Built surge protector is provided by vendor.

1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S34.3 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
1 Tag No. FV -21066
2 Service PA TO DC001 RX
3 P&ID No. Line No. R2B-P3-206-02-A-DTI-00064 1-1/2"-P-210211-B2A1-N
4 Area Classification Ingress Protection CLASS 1 DIV 2 Gr. B ,C&D, T3 NEMA 4X
GENERAL 5 Ambient Temperature: Unit Min. Max. °C 10 48
6 Allowable Sound dBA Tightness Requirement <85 ANSI IV (standard)
7 Available Air Supply Pressure Unit Min. Max. kgf/cm²-g 4.2 8.0
8 Electric Connection Pneum. Connection 1/2” NPT (F) 1/4” NPT (F)
9 Power Failure Position FC
10 Line Size and Schedule Sch. Outlet Line Sch. 1-1/2 in XS 1.5" XS
PIPE
11 Line Class Rating Pipe Material B2A1 300# A106 GR.B, SMLS
LINE
12 Pipe Insulation Thickness Corrosion Allowance N N/A 1.6mm
13 Fluid State Phase Plant Air Gas/Vapor Single Phase
14 Sour Service Special Condition N/A N/A
15 Flow Rate Units Min. Nor. Max. Nm³/h 56 112 168
16 Inlet Pressure Units Min. Nor. Max. kgf/cm²-g 6.26 6.13 5.93
17 Pressure Drop Units Min. Nor. Max. kgf/cm² 3.6 2.82 1.31
18 Inlet Temperature Units Min. Nor. Max. °C 40 40 40
PROCESS 19 Density Units Min. Nor. Max. kg/m³
CONDITIONS 20 Viscosity Units Min. Nor. Max. cP 0.019 0.019 0.019
21 Molecular Weight (MW) Specific Gravity @ Oper. 28.85
22 Spec. Heat Ratio (Cp/Cv) Compressibility (Z) 1.393 0.997
23 Vapor Pressure (Liq.) Cavitation or Flashing kgf/cm²-a N/A
24 Critical Pressure (Liq) Flash (wt%) kgf/cm²-a
25 Design Pressure Min. Max. kgf/cm²-g 10.5 kgf/cm²-g
26 Design Temperature Min. Max. 10 °C 80 °C
27 Max.Shutoff DP Solid % 10.5 kgf/cm²
28 Calculated Cv Units Min. Nor. Max. Cv 0.69 1.47 2.84
CALCULATED
29 Travel Units Min. Nor. Max. % 38 60 78
RESULTS
30 Noise dBA @1m Units Min. Nor. Max. dBA 50 53 51
31 MFR Model FISHER EZ 56 MFR Model FISHER DVC6200F/SC-AD
32 Body Type Single Seat Globe 57 Signal: Inlet Outlet FF Protocol 0-2.8 kgf/cm2
33 Body Size Trim Size 1 in 1/2 in 58 Increase Signal Valve: DIRECT
34 End Connec.Size & Rating 1" 300# RF POSITIONER 59 Cam Characteristic LINEAR
35 Rated Cv Characteristic 4.91 EQ% 60 Bypass Gauges N/A YES
36 Body Material WCC Steel 61 Signal Fail. to Valve FC
BODY 37 Bonnet Type Material Plain WCC Steel 62 Electric Enclosure Ex ia IIC T5 , NEMA 4X
AND 38 Flow Direct. Flow Act. To Up FTO 63 MFR Model N/A N/A
TRIM 39 Packing Type Material Enviro Seal PTFE Carbon 64 Type Power N/A N/A
SOLENOID
40 Lubricator Isolat. Valve N/A N/A 65 When De-Enegr.Valve: N/A
VALVE
41 Guiding No. of Ports Post 1 66 Material Latcher N/A N/A
42 Trim Type Internal Design Micro Form Unbalanced 67 Electric Enclosure N/A
43 Rated Travel Leak Class 3/4 in ANSI IV 68 MFR Model N/A N/A
44 Plug/ Ball/ Disk Material S41600 SST 69 Type Quantity N/A N/A
45 Seat Material S41600 SST SWITCHES 70 Contacts / Rating N/A
46 Cage Stem Material N/A S31600 SST 71 Switching Position N/A
47 Gasket Material S31600 SST/Graphite 72 Electric Enclosure N/A
48 MFR Model FISHER 667 73 MFR Model FISHER 67CFR
49 Type Diaphragm Spring Return AIR SET 74 Set Pressure 4.2 kgf/cm2-g
50 Size Stroke Time 30i < 5 Sec 75 Filter Gauge 5 Micron min YES
ACTUATOR 51 Air Failure Valve: FC 76 Vol. Tank Booster NO NO
52 Handwheel Location N/A 77 Diffuser Lock-up NO NO
ACCESSORY
53 Mounting Position VERTICAL 78 Fire Safe Fireproof NO NO
54 Spring Range 0.8 - 2.5 kgf/cm2-g 79 Mech. Stop Quick Exa. NO NO
55 Include Pressure (Shutoff) 80 Hydro. Pressure YES
85 Vendor EMERSON 81 Leakage YES
PURCHASE TESTS
86 Manufacturer FISHER 82 Cryogenic N/A
87 Requisition No. R2B-P3-206-02-P-MR-00200 83 NACE Requirement N/A
88 Model No. EZ 84 PWHT Requirement N/A
Notes:

INSTRUMENT SPECIFICATION - CONTROL VALVE


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S35.1 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Fieldbus Device Data Sheet
Tag No.: FV -21066
Fieldbus Tag No.:

Service : PA TO DC001 RX

Basic Fieldbus Function Blocks Segment Information


Analog Input Block (AI) 1 Number Device:
1 22
20 Execution (msec)
Discrete Input Block (DI) 4 Number Segment #: DFJB-21039
2 23
15 Execution Time
3 Bias/Gain Station (BG) 0 Execution (msec) 24 LAS Capable: Yes No
Manual Loader (ML) 0 Number 25 Device Current Draw (mA): 19
4
0 Execution (msec) Device Minimum Voltage: 9.
26
Analog Output Block (AO) 1 Number Device Capacitance: 5 nF
5 20 Execution (msec) Polarity-sensitive: Yes No
27
Discrete Output Block (DO) 1 Number Segment Terminator Location:
6 20 Execution (msec)
28
7 Control Selector (CS)
DD Revision: 3
PID,PI,I Controller (PID) 29
8
20 Execution (msec)
CFF Revision: 1.9
Ratio Station (RA) 30
9
P,PD Controller (PD) 0 Number
10 0 Execution (msec)

* Execution time in msec.

Advanced Function Blocks Notes:

11 Device Control (DC)

12 Output Splitter (OS)

13 Signal Characterizer (SC)

14 Lead Lag (LL)

15 Deadtime (DT)

16 Integrator(Totalizer) (IT)

17 Setpoint Ramp Generator (SPG)

18 Input Selector (IS)

19 Arithmetic (AR)

20 Timer (TMR)

21 Analog Alarm (AAL)

INSTRUMENT SPECIFICATION -FOUNDATION FIELDBUS


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S35.2 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Tag Number : FV -21066

1. In-Built surge protector is provided by vendor.

1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S35.3 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
1 Tag No. FV -21067
2 Service PA TO DC001 RX
3 P&ID No. Line No. R2B-P3-206-02-A-DTI-00064 1-1/2"-P-210212-B2A1-N
4 Area Classification Ingress Protection CLASS 1 DIV 2 Gr. B ,C&D, T3 NEMA 4X
GENERAL 5 Ambient Temperature: Unit Min. Max. °C 10 48
6 Allowable Sound dBA Tightness Requirement <85 ANSI IV (standard)
7 Available Air Supply Pressure Unit Min. Max. kgf/cm²-g 4.2 8.0
8 Electric Connection Pneum. Connection 1/2” NPT (F) 1/4” NPT (F)
9 Power Failure Position FC
10 Line Size and Schedule Sch. Outlet Line Sch. 1-1/2 in XS 1.5" XS
PIPE
11 Line Class Rating Pipe Material B2A1 300# A106 GR.B, SMLS
LINE
12 Pipe Insulation Thickness Corrosion Allowance N N/A 1.6mm
13 Fluid State Phase Plant Air Gas/Vapor Single Phase
14 Sour Service Special Condition N/A N/A
15 Flow Rate Units Min. Nor. Max. Nm³/h 56 112 168
16 Inlet Pressure Units Min. Nor. Max. kgf/cm²-g 6.26 6.13 5.93
17 Pressure Drop Units Min. Nor. Max. kgf/cm² 3.6 2.82 1.31
18 Inlet Temperature Units Min. Nor. Max. °C 40 40 40
PROCESS 19 Density Units Min. Nor. Max. kg/m³
CONDITIONS 20 Viscosity Units Min. Nor. Max. cP 0.019 0.019 0.019
21 Molecular Weight (MW) Specific Gravity @ Oper. 28.85
22 Spec. Heat Ratio (Cp/Cv) Compressibility (Z) 1.393 0.997
23 Vapor Pressure (Liq.) Cavitation or Flashing kgf/cm²-a N/A
24 Critical Pressure (Liq) Flash (wt%) kgf/cm²-a
25 Design Pressure Min. Max. kgf/cm²-g 10.5 kgf/cm²-g
26 Design Temperature Min. Max. 10 °C 80 °C
27 Max.Shutoff DP Solid % 10.5 kgf/cm²
28 Calculated Cv Units Min. Nor. Max. Cv 0.69 1.47 2.84
CALCULATED
29 Travel Units Min. Nor. Max. % 38 60 78
RESULTS
30 Noise dBA @1m Units Min. Nor. Max. dBA 50 53 51
31 MFR Model FISHER EZ 56 MFR Model FISHER DVC6200F/SC-AD
32 Body Type Single Seat Globe 57 Signal: Inlet Outlet FF Protocol 0-2.8 kgf/cm2
33 Body Size Trim Size 1 in 1/2 in 58 Increase Signal Valve: DIRECT
34 End Connec.Size & Rating 1" 300# RF POSITIONER 59 Cam Characteristic LINEAR
35 Rated Cv Characteristic 4.91 EQ% 60 Bypass Gauges N/A YES
36 Body Material WCC Steel 61 Signal Fail. to Valve FC
BODY 37 Bonnet Type Material Plain WCC Steel 62 Electric Enclosure Ex ia IIC T5 , NEMA 4X
AND 38 Flow Direct. Flow Act. To Up FTO 63 MFR Model N/A N/A
TRIM 39 Packing Type Material Enviro Seal PTFE Carbon 64 Type Power N/A N/A
SOLENOID
40 Lubricator Isolat. Valve N/A N/A 65 When De-Enegr.Valve: N/A
VALVE
41 Guiding No. of Ports Post 1 66 Material Latcher N/A N/A
42 Trim Type Internal Design Micro Form Unbalanced 67 Electric Enclosure N/A
43 Rated Travel Leak Class 3/4 in ANSI IV 68 MFR Model N/A N/A
44 Plug/ Ball/ Disk Material S41600 SST 69 Type Quantity N/A N/A
45 Seat Material S41600 SST SWITCHES 70 Contacts / Rating N/A
46 Cage Stem Material N/A S31600 SST 71 Switching Position N/A
47 Gasket Material S31600 SST/Graphite 72 Electric Enclosure N/A
48 MFR Model FISHER 667 73 MFR Model FISHER 67CFR
49 Type Diaphragm Spring Return AIR SET 74 Set Pressure 4.2 kgf/cm2-g
50 Size Stroke Time 30i < 5 Sec 75 Filter Gauge 5 Micron min YES
ACTUATOR 51 Air Failure Valve: FC 76 Vol. Tank Booster NO NO
52 Handwheel Location N/A 77 Diffuser Lock-up NO NO
ACCESSORY
53 Mounting Position VERTICAL 78 Fire Safe Fireproof NO NO
54 Spring Range 0.8 - 2.5 kgf/cm2-g 79 Mech. Stop Quick Exa. NO NO
55 Include Pressure (Shutoff) 80 Hydro. Pressure YES
85 Vendor EMERSON 81 Leakage YES
PURCHASE TESTS
86 Manufacturer FISHER 82 Cryogenic N/A
87 Requisition No. R2B-P3-206-02-P-MR-00200 83 NACE Requirement N/A
88 Model No. EZ 84 PWHT Requirement N/A
Notes:

INSTRUMENT SPECIFICATION - CONTROL VALVE


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S36.1 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Fieldbus Device Data Sheet
Tag No.: FV -21067
Fieldbus Tag No.:

Service : PA TO DC001 RX

Basic Fieldbus Function Blocks Segment Information


Analog Input Block (AI) 1 Number Device:
1 22
20 Execution (msec)
Discrete Input Block (DI) 4 Number Segment #: DFJB-21040
2 23
15 Execution Time
3 Bias/Gain Station (BG) 0 Execution (msec) 24 LAS Capable: Yes No
Manual Loader (ML) 0 Number 25 Device Current Draw (mA): 19
4
0 Execution (msec) Device Minimum Voltage: 9.
26
Analog Output Block (AO) 1 Number Device Capacitance: 5 nF
5 20 Execution (msec) Polarity-sensitive: Yes No
27
Discrete Output Block (DO) 1 Number Segment Terminator Location:
6 20 Execution (msec)
28
7 Control Selector (CS)
DD Revision: 3
PID,PI,I Controller (PID) 29
8
20 Execution (msec)
CFF Revision: 1.9
Ratio Station (RA) 30
9
P,PD Controller (PD) 0 Number
10 0 Execution (msec)

* Execution time in msec.

Advanced Function Blocks Notes:

11 Device Control (DC)

12 Output Splitter (OS)

13 Signal Characterizer (SC)

14 Lead Lag (LL)

15 Deadtime (DT)

16 Integrator(Totalizer) (IT)

17 Setpoint Ramp Generator (SPG)

18 Input Selector (IS)

19 Arithmetic (AR)

20 Timer (TMR)

21 Analog Alarm (AAL)

INSTRUMENT SPECIFICATION -FOUNDATION FIELDBUS


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S36.2 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Tag Number : FV -21067

1. In-Built surge protector is provided by vendor.

1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S36.3 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
1 Tag No. FV -21068
2 Service PA TO DC001 RX
3 P&ID No. Line No. R2B-P3-206-02-A-DTI-00064 1-1/2"-P-210213-B2A1-N
4 Area Classification Ingress Protection CLASS 1 DIV 2 Gr. B ,C&D, T3 NEMA 4X
GENERAL 5 Ambient Temperature: Unit Min. Max. °C 10 48
6 Allowable Sound dBA Tightness Requirement <85 ANSI IV (standard)
7 Available Air Supply Pressure Unit Min. Max. kgf/cm²-g 4.2 8.0
8 Electric Connection Pneum. Connection 1/2” NPT (F) 1/4” NPT (F)
9 Power Failure Position FC
10 Line Size and Schedule Sch. Outlet Line Sch. 1-1/2 in XS 1.5" XS
PIPE
11 Line Class Rating Pipe Material B2A1 300# A106 GR.B, SMLS
LINE
12 Pipe Insulation Thickness Corrosion Allowance N N/A 1.6mm
13 Fluid State Phase Plant Air Gas/Vapor Single Phase
14 Sour Service Special Condition N/A N/A
15 Flow Rate Units Min. Nor. Max. Nm³/h 56 112 168
16 Inlet Pressure Units Min. Nor. Max. kgf/cm²-g 6.26 6.13 5.93
17 Pressure Drop Units Min. Nor. Max. kgf/cm² 3.6 2.82 1.31
18 Inlet Temperature Units Min. Nor. Max. °C 40 40 40
PROCESS 19 Density Units Min. Nor. Max. kg/m³
CONDITIONS 20 Viscosity Units Min. Nor. Max. cP 0.019 0.019 0.019
21 Molecular Weight (MW) Specific Gravity @ Oper. 28.85
22 Spec. Heat Ratio (Cp/Cv) Compressibility (Z) 1.393 0.997
23 Vapor Pressure (Liq.) Cavitation or Flashing kgf/cm²-a N/A
24 Critical Pressure (Liq) Flash (wt%) kgf/cm²-a
25 Design Pressure Min. Max. kgf/cm²-g 10.5 kgf/cm²-g
26 Design Temperature Min. Max. 10 °C 80 °C
27 Max.Shutoff DP Solid % 10.5 kgf/cm²
28 Calculated Cv Units Min. Nor. Max. Cv 0.69 1.47 2.84
CALCULATED
29 Travel Units Min. Nor. Max. % 38 60 78
RESULTS
30 Noise dBA @1m Units Min. Nor. Max. dBA 50 53 51
31 MFR Model FISHER EZ 56 MFR Model FISHER DVC6200F/SC-AD
32 Body Type Single Seat Globe 57 Signal: Inlet Outlet FF Protocol 0-2.8 kgf/cm2
33 Body Size Trim Size 1 in 1/2 in 58 Increase Signal Valve: DIRECT
34 End Connec.Size & Rating 1" 300# RF POSITIONER 59 Cam Characteristic LINEAR
35 Rated Cv Characteristic 4.91 EQ% 60 Bypass Gauges N/A YES
36 Body Material WCC Steel 61 Signal Fail. to Valve FC
BODY 37 Bonnet Type Material Plain WCC Steel 62 Electric Enclosure Ex ia IIC T5 , NEMA 4X
AND 38 Flow Direct. Flow Act. To Up FTO 63 MFR Model N/A N/A
TRIM 39 Packing Type Material Enviro Seal PTFE Carbon 64 Type Power N/A N/A
SOLENOID
40 Lubricator Isolat. Valve N/A N/A 65 When De-Enegr.Valve: N/A
VALVE
41 Guiding No. of Ports Post 1 66 Material Latcher N/A N/A
42 Trim Type Internal Design Micro Form Unbalanced 67 Electric Enclosure N/A
43 Rated Travel Leak Class 3/4 in ANSI IV 68 MFR Model N/A N/A
44 Plug/ Ball/ Disk Material S41600 SST 69 Type Quantity N/A N/A
45 Seat Material S41600 SST SWITCHES 70 Contacts / Rating N/A
46 Cage Stem Material N/A S31600 SST 71 Switching Position N/A
47 Gasket Material S31600 SST/Graphite 72 Electric Enclosure N/A
48 MFR Model FISHER 667 73 MFR Model FISHER 67CFR
49 Type Diaphragm Spring Return AIR SET 74 Set Pressure 4.2 kgf/cm2-g
50 Size Stroke Time 30i < 5 Sec 75 Filter Gauge 5 Micron min YES
ACTUATOR 51 Air Failure Valve: FC 76 Vol. Tank Booster NO NO
52 Handwheel Location N/A 77 Diffuser Lock-up NO NO
ACCESSORY
53 Mounting Position VERTICAL 78 Fire Safe Fireproof NO NO
54 Spring Range 0.8 - 2.5 kgf/cm2-g 79 Mech. Stop Quick Exa. NO NO
55 Include Pressure (Shutoff) 80 Hydro. Pressure YES
85 Vendor EMERSON 81 Leakage YES
PURCHASE TESTS
86 Manufacturer FISHER 82 Cryogenic N/A
87 Requisition No. R2B-P3-206-02-P-MR-00200 83 NACE Requirement N/A
88 Model No. EZ 84 PWHT Requirement N/A
Notes:

INSTRUMENT SPECIFICATION - CONTROL VALVE


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S37.1 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Fieldbus Device Data Sheet
Tag No.: FV -21068
Fieldbus Tag No.:

Service : PA TO DC001 RX

Basic Fieldbus Function Blocks Segment Information


Analog Input Block (AI) 1 Number Device:
1 22
20 Execution (msec)
Discrete Input Block (DI) 4 Number Segment #: DFJB-21034
2 23
15 Execution Time
3 Bias/Gain Station (BG) 0 Execution (msec) 24 LAS Capable: Yes No
Manual Loader (ML) 0 Number 25 Device Current Draw (mA): 19
4
0 Execution (msec) Device Minimum Voltage: 9.
26
Analog Output Block (AO) 1 Number Device Capacitance: 5 nF
5 20 Execution (msec) Polarity-sensitive: Yes No
27
Discrete Output Block (DO) 1 Number Segment Terminator Location:
6 20 Execution (msec)
28
7 Control Selector (CS)
DD Revision: 3
PID,PI,I Controller (PID) 29
8
20 Execution (msec)
CFF Revision: 1.9
Ratio Station (RA) 30
9
P,PD Controller (PD) 0 Number
10 0 Execution (msec)

* Execution time in msec.

Advanced Function Blocks Notes:

11 Device Control (DC)

12 Output Splitter (OS)

13 Signal Characterizer (SC)

14 Lead Lag (LL)

15 Deadtime (DT)

16 Integrator(Totalizer) (IT)

17 Setpoint Ramp Generator (SPG)

18 Input Selector (IS)

19 Arithmetic (AR)

20 Timer (TMR)

21 Analog Alarm (AAL)

INSTRUMENT SPECIFICATION -FOUNDATION FIELDBUS


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S37.2 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Tag Number : FV -21068

1. In-Built surge protector is provided by vendor.

1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S37.3 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
1 Tag No. FV -21070
2 Service N2 TO DC21002 RG
3 P&ID No. Line No. R2B-P3-206-02-A-DTI-00067 2"-GI-210393-T-A18T1-EC
4 Area Classification Ingress Protection CLASS 1 DIV 2 Gr. B ,C&D, T3 NEMA 4X
GENERAL 5 Ambient Temperature: Unit Min. Max. °C 10 48
6 Allowable Sound dBA Tightness Requirement <85 ANSI IV (standard)
7 Available Air Supply Pressure Unit Min. Max. kgf/cm²-g 4.2 8.0
8 Electric Connection Pneum. Connection 1/2” NPT (F) 1/4” NPT (F)
9 Power Failure Position FC
10 Line Size and Schedule Sch. Outlet Line Sch. 2 in XS 2" XS
PIPE
11 Line Class Rating Pipe Material T-A18T1 150# A106 GR.B
LINE
12 Pipe Insulation Thickness Corrosion Allowance N N/A 1.6mm
13 Fluid State Phase Steam Gas/Vapor Single Phase
14 Sour Service Special Condition N/A N/A
15 Flow Rate Units Min. Nor. Max. kg/h 93 187 282
16 Inlet Pressure Units Min. Nor. Max. kgf/cm²-g 6.25 6.1 5.86
17 Pressure Drop Units Min. Nor. Max. kgf/cm² 3.29 2.61 1.49
18 Inlet Temperature Units Min. Nor. Max. °C 210 210 210
PROCESS 19 Density Units Min. Nor. Max. kg/m³
CONDITIONS 20 Viscosity Units Min. Nor. Max. cP 0.017 0.017 0.017
21 Molecular Weight (MW) Specific Gravity @ Oper. 18.02
22 Spec. Heat Ratio (Cp/Cv) Compressibility (Z) 1.261 0.966
23 Vapor Pressure (Liq.) Cavitation or Flashing kgf/cm²-a N/A
24 Critical Pressure (Liq) Flash (wt%) kgf/cm²-a
25 Design Pressure Min. Max. -1.033 kgf/cm²-g 7.382 kgf/cm²-g
26 Design Temperature Min. Max. 10 °C 260 °C
27 Max.Shutoff DP Solid % 7.382 kgf/cm²
28 Calculated Cv Units Min. Nor. Max. Cv 1.45 3.07 5.59
CALCULATED
29 Travel Units Min. Nor. Max. % 39 59 75
RESULTS
30 Noise dBA @1m Units Min. Nor. Max. dBA 51 56 56
31 MFR Model FISHER EZ 56 MFR Model FISHER DVC6200F/SC-AD
32 Body Type Single Seat Globe 57 Signal: Inlet Outlet FF Protocol 0-2.8 kgf/cm2
33 Body Size Trim Size 1.5 in 3/4 in 58 Increase Signal Valve: DIRECT
34 End Connec.Size & Rating 1.5" 300# RF POSITIONER 59 Cam Characteristic LINEAR
35 Rated Cv Characteristic 10.2 EQ% 60 Bypass Gauges N/A YES
36 Body Material WCC Steel 61 Signal Fail. to Valve FC
BODY 37 Bonnet Type Material Plain WCC Steel 62 Electric Enclosure Ex ia IIC T5 , NEMA 4X
AND 38 Flow Direct. Flow Act. To Up FTO 63 MFR Model N/A N/A
TRIM 39 Packing Type Material Enviro Seal Graphite ULF 64 Type Power N/A N/A
SOLENOID
40 Lubricator Isolat. Valve N/A N/A 65 When De-Enegr.Valve: N/A
VALVE
41 Guiding No. of Ports Post 1 66 Material Latcher N/A N/A
42 Trim Type Internal Design Micro Form Unbalanced 67 Electric Enclosure N/A
43 Rated Travel Leak Class 3/4 in ANSI IV 68 MFR Model N/A N/A
44 Plug/ Ball/ Disk Material S41600 SST 69 Type Quantity N/A N/A
45 Seat Material S41600 SST SWITCHES 70 Contacts / Rating N/A
46 Cage Stem Material N/A S31600 SST 71 Switching Position N/A
47 Gasket Material S31600 SST/Graphite 72 Electric Enclosure N/A
48 MFR Model FISHER 667 73 MFR Model FISHER 67CFR
49 Type Diaphragm Spring Return AIR SET 74 Set Pressure 4.2 kgf/cm2-g
50 Size Stroke Time 30i < 5 Sec 75 Filter Gauge 5 Micron min YES
ACTUATOR 51 Air Failure Valve: FC 76 Vol. Tank Booster NO NO
52 Handwheel Location N/A 77 Diffuser Lock-up NO NO
ACCESSORY
53 Mounting Position VERTICAL 78 Fire Safe Fireproof NO NO
54 Spring Range 0.7 - 2.0 kgf/cm2-g 79 Mech. Stop Quick Exa. NO NO
55 Include Pressure (Shutoff) 80 Hydro. Pressure YES
85 Vendor EMERSON 81 Leakage YES
PURCHASE TESTS
86 Manufacturer FISHER 82 Cryogenic N/A
87 Requisition No. R2B-P3-206-02-P-MR-00200 83 NACE Requirement N/A
88 Model No. EZ 84 PWHT Requirement N/A
Notes:

INSTRUMENT SPECIFICATION - CONTROL VALVE


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S38.1 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Fieldbus Device Data Sheet
Tag No.: FV -21070
Fieldbus Tag No.:

Service : N2 TO DC21002 RG

Basic Fieldbus Function Blocks Segment Information


Analog Input Block (AI) 1 Number Device:
1 22
20 Execution (msec)
Discrete Input Block (DI) 4 Number Segment #: DFJB-21038
2 23
15 Execution Time
3 Bias/Gain Station (BG) 0 Execution (msec) 24 LAS Capable: Yes No
Manual Loader (ML) 0 Number 25 Device Current Draw (mA): 19
4
0 Execution (msec) Device Minimum Voltage: 9.
26
Analog Output Block (AO) 1 Number Device Capacitance: 5 nF
5 20 Execution (msec) Polarity-sensitive: Yes No
27
Discrete Output Block (DO) 1 Number Segment Terminator Location:
6 20 Execution (msec)
28
7 Control Selector (CS)
DD Revision: 3
PID,PI,I Controller (PID) 29
8
20 Execution (msec)
CFF Revision: 1.9
Ratio Station (RA) 30
9
P,PD Controller (PD) 0 Number
10 0 Execution (msec)

* Execution time in msec.

Advanced Function Blocks Notes:

11 Device Control (DC)

12 Output Splitter (OS)

13 Signal Characterizer (SC)

14 Lead Lag (LL)

15 Deadtime (DT)

16 Integrator(Totalizer) (IT)

17 Setpoint Ramp Generator (SPG)

18 Input Selector (IS)

19 Arithmetic (AR)

20 Timer (TMR)

21 Analog Alarm (AAL)

INSTRUMENT SPECIFICATION -FOUNDATION FIELDBUS


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S38.2 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Tag Number : FV -21070

1. In-Built surge protector is provided by vendor.

1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S38.3 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
1 Tag No. FV -21071
2 Service N2 TO DC21002 RG
3 P&ID No. Line No. R2B-P3-206-02-A-DTI-00067 2"-GI-210393-T-A18T1-EC
4 Area Classification Ingress Protection CLASS 1 DIV 2 Gr. B ,C&D, T3 NEMA 4X
GENERAL 5 Ambient Temperature: Unit Min. Max. °C 10 48
6 Allowable Sound dBA Tightness Requirement <85 ANSI IV (standard)
7 Available Air Supply Pressure Unit Min. Max. kgf/cm²-g 4.2 8.0
8 Electric Connection Pneum. Connection 1/2” NPT (F) 1/4” NPT (F)
9 Power Failure Position FC
10 Line Size and Schedule Sch. Outlet Line Sch. 2 in XS 2" XS
PIPE
11 Line Class Rating Pipe Material T-A18T1 150# A106 GR.B
LINE
12 Pipe Insulation Thickness Corrosion Allowance N N/A 1.6mm
13 Fluid State Phase Steam Gas/Vapor Single Phase
14 Sour Service Special Condition N/A N/A
15 Flow Rate Units Min. Nor. Max. kg/h 93 187 282
16 Inlet Pressure Units Min. Nor. Max. kgf/cm²-g 6.25 6.1 5.86
17 Pressure Drop Units Min. Nor. Max. kgf/cm² 3.29 2.61 1.49
18 Inlet Temperature Units Min. Nor. Max. °C 210 210 210
PROCESS 19 Density Units Min. Nor. Max. kg/m³
CONDITIONS 20 Viscosity Units Min. Nor. Max. cP 0.017 0.017 0.017
21 Molecular Weight (MW) Specific Gravity @ Oper. 18.02
22 Spec. Heat Ratio (Cp/Cv) Compressibility (Z) 1.261 0.966
23 Vapor Pressure (Liq.) Cavitation or Flashing kgf/cm²-a N/A
24 Critical Pressure (Liq) Flash (wt%) kgf/cm²-a
25 Design Pressure Min. Max. -1.033 kgf/cm²-g 7.382 kgf/cm²-g
26 Design Temperature Min. Max. 10 °C 260 °C
27 Max.Shutoff DP Solid % 7.382 kgf/cm²
28 Calculated Cv Units Min. Nor. Max. Cv 1.45 3.07 5.59
CALCULATED
29 Travel Units Min. Nor. Max. % 39 59 75
RESULTS
30 Noise dBA @1m Units Min. Nor. Max. dBA 51 56 56
31 MFR Model FISHER EZ 56 MFR Model FISHER DVC6200F/SC-AD
32 Body Type Single Seat Globe 57 Signal: Inlet Outlet FF Protocol 0-2.8 kgf/cm2
33 Body Size Trim Size 1.5 in 3/4 in 58 Increase Signal Valve: DIRECT
34 End Connec.Size & Rating 1.5" 300# RF POSITIONER 59 Cam Characteristic LINEAR
35 Rated Cv Characteristic 10.2 EQ% 60 Bypass Gauges N/A YES
36 Body Material WCC Steel 61 Signal Fail. to Valve FC
BODY 37 Bonnet Type Material Plain WCC Steel 62 Electric Enclosure Ex ia IIC T5 , NEMA 4X
AND 38 Flow Direct. Flow Act. To Up FTO 63 MFR Model N/A N/A
TRIM 39 Packing Type Material Enviro Seal Graphite ULF 64 Type Power N/A N/A
SOLENOID
40 Lubricator Isolat. Valve N/A N/A 65 When De-Enegr.Valve: N/A
VALVE
41 Guiding No. of Ports Post 1 66 Material Latcher N/A N/A
42 Trim Type Internal Design Micro Form Unbalanced 67 Electric Enclosure N/A
43 Rated Travel Leak Class 3/4 in ANSI IV 68 MFR Model N/A N/A
44 Plug/ Ball/ Disk Material S41600 SST 69 Type Quantity N/A N/A
45 Seat Material S41600 SST SWITCHES 70 Contacts / Rating N/A
46 Cage Stem Material N/A S31600 SST 71 Switching Position N/A
47 Gasket Material S31600 SST/Graphite 72 Electric Enclosure N/A
48 MFR Model FISHER 667 73 MFR Model FISHER 67CFR
49 Type Diaphragm Spring Return AIR SET 74 Set Pressure 4.2 kgf/cm2-g
50 Size Stroke Time 30i < 5 Sec 75 Filter Gauge 5 Micron min YES
ACTUATOR 51 Air Failure Valve: FC 76 Vol. Tank Booster NO NO
52 Handwheel Location N/A 77 Diffuser Lock-up NO NO
ACCESSORY
53 Mounting Position VERTICAL 78 Fire Safe Fireproof NO NO
54 Spring Range 1.2 - 2.3 kgf/cm2-g 79 Mech. Stop Quick Exa. NO NO
55 Include Pressure (Shutoff) 80 Hydro. Pressure YES
85 Vendor EMERSON 81 Leakage YES
PURCHASE TESTS
86 Manufacturer FISHER 82 Cryogenic N/A
87 Requisition No. R2B-P3-206-02-P-MR-00200 83 NACE Requirement N/A
88 Model No. EZ 84 PWHT Requirement N/A
Notes:

INSTRUMENT SPECIFICATION - CONTROL VALVE


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S39.1 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Fieldbus Device Data Sheet
Tag No.: FV -21071
Fieldbus Tag No.:

Service : N2 TO DC21002 RG

Basic Fieldbus Function Blocks Segment Information


Analog Input Block (AI) 1 Number Device:
1 22
20 Execution (msec)
Discrete Input Block (DI) 4 Number Segment #: DFJB-21038
2 23
15 Execution Time
3 Bias/Gain Station (BG) 0 Execution (msec) 24 LAS Capable: Yes No
Manual Loader (ML) 0 Number 25 Device Current Draw (mA): 19
4
0 Execution (msec) Device Minimum Voltage: 9.
26
Analog Output Block (AO) 1 Number Device Capacitance: 5 nF
5 20 Execution (msec) Polarity-sensitive: Yes No
27
Discrete Output Block (DO) 1 Number Segment Terminator Location:
6 20 Execution (msec)
28
7 Control Selector (CS)
DD Revision: 3
PID,PI,I Controller (PID) 29
8
20 Execution (msec)
CFF Revision: 1.9
Ratio Station (RA) 30
9
P,PD Controller (PD) 0 Number
10 0 Execution (msec)

* Execution time in msec.

Advanced Function Blocks Notes:

11 Device Control (DC)

12 Output Splitter (OS)

13 Signal Characterizer (SC)

14 Lead Lag (LL)

15 Deadtime (DT)

16 Integrator(Totalizer) (IT)

17 Setpoint Ramp Generator (SPG)

18 Input Selector (IS)

19 Arithmetic (AR)

20 Timer (TMR)

21 Analog Alarm (AAL)

INSTRUMENT SPECIFICATION -FOUNDATION FIELDBUS


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S39.2 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Tag Number : FV -21071

1. In-Built surge protector is provided by vendor.

1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S39.3 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
1 Tag No. FV -21072
2 Service N2 TO DC21002 RG
3 P&ID No. Line No. R2B-P3-206-02-A-DTI-00067 2"-GI-210764-T-A18T1-EC
4 Area Classification Ingress Protection CLASS 1 DIV 2 Gr. B ,C&D, T3 NEMA 4X
GENERAL 5 Ambient Temperature: Unit Min. Max. °C 10 48
6 Allowable Sound dBA Tightness Requirement <85 ANSI IV (standard)
7 Available Air Supply Pressure Unit Min. Max. kgf/cm²-g 4.2 8.0
8 Electric Connection Pneum. Connection 1/2” NPT (F) 1/4” NPT (F)
9 Power Failure Position FC
10 Line Size and Schedule Sch. Outlet Line Sch. 2 in XS 2" XS
PIPE
11 Line Class Rating Pipe Material T-A18T1 150# A106 GR.B
LINE
12 Pipe Insulation Thickness Corrosion Allowance N N/A 1.6mm
13 Fluid State Phase Steam Gas/Vapor Single Phase
14 Sour Service Special Condition N/A N/A
15 Flow Rate Units Min. Nor. Max. kg/h 93 187 282
16 Inlet Pressure Units Min. Nor. Max. kgf/cm²-g 6.25 6.1 5.86
17 Pressure Drop Units Min. Nor. Max. kgf/cm² 3.29 2.61 1.49
18 Inlet Temperature Units Min. Nor. Max. °C 210 210 210
PROCESS 19 Density Units Min. Nor. Max. kg/m³
CONDITIONS 20 Viscosity Units Min. Nor. Max. cP 0.017 0.017 0.017
21 Molecular Weight (MW) Specific Gravity @ Oper. 18.02
22 Spec. Heat Ratio (Cp/Cv) Compressibility (Z) 1.261 0.966
23 Vapor Pressure (Liq.) Cavitation or Flashing kgf/cm²-a N/A
24 Critical Pressure (Liq) Flash (wt%) kgf/cm²-a
25 Design Pressure Min. Max. -1.033 kgf/cm²-g 7.382 kgf/cm²-g
26 Design Temperature Min. Max. 10 °C 260 °C
27 Max.Shutoff DP Solid % 7.382 kgf/cm²
28 Calculated Cv Units Min. Nor. Max. Cv 1.45 3.07 5.59
CALCULATED
29 Travel Units Min. Nor. Max. % 39 59 75
RESULTS
30 Noise dBA @1m Units Min. Nor. Max. dBA 51 56 56
31 MFR Model FISHER EZ 56 MFR Model FISHER DVC6200F/SC-AD
32 Body Type Single Seat Globe 57 Signal: Inlet Outlet FF Protocol 0-2.8 kgf/cm2
33 Body Size Trim Size 1.5 in 3/4 in 58 Increase Signal Valve: DIRECT
34 End Connec.Size & Rating 1.5" 300# RF POSITIONER 59 Cam Characteristic LINEAR
35 Rated Cv Characteristic 10.2 EQ% 60 Bypass Gauges N/A YES
36 Body Material WCC Steel 61 Signal Fail. to Valve FC
BODY 37 Bonnet Type Material Plain WCC Steel 62 Electric Enclosure Ex ia IIC T5 , NEMA 4X
AND 38 Flow Direct. Flow Act. To Up FTO 63 MFR Model N/A N/A
TRIM 39 Packing Type Material Enviro Seal Graphite ULF 64 Type Power N/A N/A
SOLENOID
40 Lubricator Isolat. Valve N/A N/A 65 When De-Enegr.Valve: N/A
VALVE
41 Guiding No. of Ports Post 1 66 Material Latcher N/A N/A
42 Trim Type Internal Design Micro Form Unbalanced 67 Electric Enclosure N/A
43 Rated Travel Leak Class 3/4 in ANSI IV 68 MFR Model N/A N/A
44 Plug/ Ball/ Disk Material S41600 SST 69 Type Quantity N/A N/A
45 Seat Material S41600 SST SWITCHES 70 Contacts / Rating N/A
46 Cage Stem Material N/A S31600 SST 71 Switching Position N/A
47 Gasket Material S31600 SST/Graphite 72 Electric Enclosure N/A
48 MFR Model FISHER 667 73 MFR Model FISHER 67CFR
49 Type Diaphragm Spring Return AIR SET 74 Set Pressure 4.2 kgf/cm2-g
50 Size Stroke Time 30i < 5 Sec 75 Filter Gauge 5 Micron min YES
ACTUATOR 51 Air Failure Valve: FC 76 Vol. Tank Booster NO NO
52 Handwheel Location N/A 77 Diffuser Lock-up NO NO
ACCESSORY
53 Mounting Position VERTICAL 78 Fire Safe Fireproof NO NO
54 Spring Range 1.2 - 2.3 kgf/cm2-g 79 Mech. Stop Quick Exa. NO NO
55 Include Pressure (Shutoff) 80 Hydro. Pressure YES
85 Vendor EMERSON 81 Leakage YES
PURCHASE TESTS
86 Manufacturer FISHER 82 Cryogenic N/A
87 Requisition No. R2B-P3-206-02-P-MR-00200 83 NACE Requirement N/A
88 Model No. EZ 84 PWHT Requirement N/A
Notes:

INSTRUMENT SPECIFICATION - CONTROL VALVE


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S40.1 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Fieldbus Device Data Sheet
Tag No.: FV -21072
Fieldbus Tag No.:

Service : N2 TO DC21002 RG

Basic Fieldbus Function Blocks Segment Information


Analog Input Block (AI) 1 Number Device:
1 22
20 Execution (msec)
Discrete Input Block (DI) 4 Number Segment #: DFJB-21032
2 23
15 Execution Time
3 Bias/Gain Station (BG) 0 Execution (msec) 24 LAS Capable: Yes No
Manual Loader (ML) 0 Number 25 Device Current Draw (mA): 19
4
0 Execution (msec) Device Minimum Voltage: 9.
26
Analog Output Block (AO) 1 Number Device Capacitance: 5 nF
5 20 Execution (msec) Polarity-sensitive: Yes No
27
Discrete Output Block (DO) 1 Number Segment Terminator Location:
6 20 Execution (msec)
28
7 Control Selector (CS)
DD Revision: 3
PID,PI,I Controller (PID) 29
8
20 Execution (msec)
CFF Revision: 1.9
Ratio Station (RA) 30
9
P,PD Controller (PD) 0 Number
10 0 Execution (msec)

* Execution time in msec.

Advanced Function Blocks Notes:

11 Device Control (DC)

12 Output Splitter (OS)

13 Signal Characterizer (SC)

14 Lead Lag (LL)

15 Deadtime (DT)

16 Integrator(Totalizer) (IT)

17 Setpoint Ramp Generator (SPG)

18 Input Selector (IS)

19 Arithmetic (AR)

20 Timer (TMR)

21 Analog Alarm (AAL)

INSTRUMENT SPECIFICATION -FOUNDATION FIELDBUS


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S40.2 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Tag Number : FV -21072

1. In-Built surge protector is provided by vendor.

1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S40.3 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
1 Tag No. FV -21073A
2 Service HVY HC TO DC002
3 P&ID No. Line No. R2B-P3-206-02-A-DTI-00012 2"-P-210800-B2A2-EC(ST)
4 Area Classification Ingress Protection CLASS 1 DIV 2 Gr. B ,C&D, T3 NEMA 4X
GENERAL 5 Ambient Temperature: Unit Min. Max. °C 10 48
6 Allowable Sound dBA Tightness Requirement <85 ANSI IV (standard)
7 Available Air Supply Pressure Unit Min. Max. kgf/cm²-g 4.2 8.0
8 Electric Connection Pneum. Connection 1/2” NPT (F) 1/4” NPT (F)
9 Power Failure Position FC
10 Line Size and Schedule Sch. Outlet Line Sch. 2 in 160 2" 160
PIPE
11 Line Class Rating Pipe Material B2A2 300# A106 GR.B, SMLS
LINE
12 Pipe Insulation Thickness Corrosion Allowance EC(ST) 75mm 3.2mm
13 Fluid State Phase Hydrocarbon Liquid Single Phase
14 Sour Service Special Condition N/A N/A
15 Flow Rate Units Min. Nor. Max. m³/h 2.4 6 8
16 Inlet Pressure Units Min. Nor. Max. kgf/cm²-g 21.84 19 18.77
17 Pressure Drop Units Min. Nor. Max. kgf/cm² 15.28 9.73 1.614
18 Inlet Temperature Units Min. Nor. Max. °C 188 188 188
PROCESS 19 Density Units Min. Nor. Max. kg/m³ 795 795 795
CONDITIONS 20 Viscosity Units Min. Nor. Max. cP 1.026 1.026 1.026
21 Molecular Weight (MW) Specific Gravity @ Oper.
22 Spec. Heat Ratio (Cp/Cv) Compressibility (Z)
23 Vapor Pressure (Liq.) Cavitation or Flashing 0 kgf/cm²-a NO
24 Critical Pressure (Liq) Flash (wt%) 12.34 kgf/cm²-a
25 Design Pressure Min. Max. kgf/cm²-g 24.4 kgf/cm²-g
26 Design Temperature Min. Max. 10 °C 345 °C
27 Max.Shutoff DP Solid % 24.4 kgf/cm²
28 Calculated Cv Units Min. Nor. Max. Cv 0.639 2.01 6.66
CALCULATED
29 Travel Units Min. Nor. Max. % 21 48 81
RESULTS
30 Noise dBA @1m Units Min. Nor. Max. dBA 50 50 50
31 MFR Model FISHER EZ 56 MFR Model FISHER DVC6200F/SC-AD
32 Body Type Single Seat Globe 57 Signal: Inlet Outlet FF Protocol 0-3.5 kgf/cm2
33 Body Size Trim Size 1 in 3/4 in 58 Increase Signal Valve: DIRECT
34 End Connec.Size & Rating 1" 300# RF POSITIONER 59 Cam Characteristic LINEAR
35 Rated Cv Characteristic 8.84 EQ% 60 Bypass Gauges N/A YES
36 Body Material WCC Steel 61 Signal Fail. to Valve FC
BODY 37 Bonnet Type Material Plain WCC Steel 62 Electric Enclosure Ex ia IIC T5 , NEMA 4X
AND 38 Flow Direct. Flow Act. To Up FTO 63 MFR Model N/A N/A
TRIM 39 Packing Type Material ISO Seal Graphite 64 Type Power N/A N/A
SOLENOID
40 Lubricator Isolat. Valve N/A N/A 65 When De-Enegr.Valve: N/A
VALVE
41 Guiding No. of Ports Post 1 66 Material Latcher N/A N/A
42 Trim Type Internal Design Micro Form Unbalanced 67 Electric Enclosure N/A
43 Rated Travel Leak Class 3/4 in ANSI IV 68 MFR Model N/A N/A
44 Plug/ Ball/ Disk Material S31600 SST/CoCr-A Seat 69 Type Quantity N/A N/A
45 Seat Material S31600 SST/CoCr-A Seat SWITCHES 70 Contacts / Rating N/A
46 Cage Stem Material N/A S31600 SST 71 Switching Position N/A
47 Gasket Material S31600 SST/Graphite 72 Electric Enclosure N/A
48 MFR Model FISHER 667 73 MFR Model FISHER 67CFR
49 Type Diaphragm Spring Return AIR SET 74 Set Pressure 4.2 kgf/cm2-g
50 Size Stroke Time 34i < 5 Sec 75 Filter Gauge 5 Micron min YES
ACTUATOR 51 Air Failure Valve: FC 76 Vol. Tank Booster NO NO
52 Handwheel Location Side Mounted 77 Diffuser Lock-up NO NO
ACCESSORY
53 Mounting Position VERTICAL 78 Fire Safe Fireproof NO NO
54 Spring Range 0.8 - 1.9 kgf/cm2-g 79 Mech. Stop Quick Exa. NO NO
55 Include Pressure (Shutoff) 80 Hydro. Pressure YES
85 Vendor EMERSON 81 Leakage YES
PURCHASE TESTS
86 Manufacturer FISHER 82 Cryogenic N/A
87 Requisition No. R2B-P3-206-02-P-MR-00200 83 NACE Requirement N/A
88 Model No. EZ 84 PWHT Requirement N/A
Notes:

INSTRUMENT SPECIFICATION - CONTROL VALVE


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S41.1 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Fieldbus Device Data Sheet
Tag No.: FV -21073A
Fieldbus Tag No.:

Service : HVY HC TO DC002

Basic Fieldbus Function Blocks Segment Information


Analog Input Block (AI) 1 Number Device:
1 22
20 Execution (msec)
Discrete Input Block (DI) 4 Number Segment #: DFJB-21033
2 23
15 Execution Time
3 Bias/Gain Station (BG) 0 Execution (msec) 24 LAS Capable: Yes No
Manual Loader (ML) 0 Number 25 Device Current Draw (mA): 19
4
0 Execution (msec) Device Minimum Voltage: 9.
26
Analog Output Block (AO) 1 Number Device Capacitance: 5 nF
5 20 Execution (msec) Polarity-sensitive: Yes No
27
Discrete Output Block (DO) 1 Number Segment Terminator Location:
6 20 Execution (msec)
28
7 Control Selector (CS)
DD Revision: 3
PID,PI,I Controller (PID) 29
8
20 Execution (msec)
CFF Revision: 1.9
Ratio Station (RA) 30
9
P,PD Controller (PD) 0 Number
10 0 Execution (msec)

* Execution time in msec.

Advanced Function Blocks Notes:

11 Device Control (DC)

12 Output Splitter (OS)

13 Signal Characterizer (SC)

14 Lead Lag (LL)

15 Deadtime (DT)

16 Integrator(Totalizer) (IT)

17 Setpoint Ramp Generator (SPG)

18 Input Selector (IS)

19 Arithmetic (AR)

20 Timer (TMR)

21 Analog Alarm (AAL)

INSTRUMENT SPECIFICATION -FOUNDATION FIELDBUS


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S41.2 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Tag Number : FV -21073A

1. Valve will normally be in the closed position. Valve opening will be intermittent and generally short-term.

2. In-Built surge protector is provided by vendor.

1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S41.3 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
1 Tag No. FV -21074
2 Service PA TO DC002
3 P&ID No. Line No. R2B-P3-206-02-A-DTI-00011 2"-P-210308-FC-7-PP
4 Area Classification Ingress Protection CLASS 1 DIV 2 Gr. B ,C&D, T3 NEMA 4X
GENERAL 5 Ambient Temperature: Unit Min. Max. °C 10 48
6 Allowable Sound dBA Tightness Requirement <85 ANSI IV (standard)
7 Available Air Supply Pressure Unit Min. Max. kgf/cm²-g 4.2 8.0
8 Electric Connection Pneum. Connection 1/2” NPT (F) 1/4” NPT (F)
9 Power Failure Position FC
10 Line Size and Schedule Sch. Outlet Line Sch. 2 in 160 2" 160
PIPE
11 Line Class Rating Pipe Material FC-7 300# A335 GR.P11, SMLS
LINE
12 Pipe Insulation Thickness Corrosion Allowance PP 130mm 3.2mm
13 Fluid State Phase Plant Air Gas/Vapor Single Phase
14 Sour Service Special Condition N/A N/A
15 Flow Rate Units Min. Nor. Max. Nm³/h 103 103 103
16 Inlet Pressure Units Min. Nor. Max. kgf/cm²-g 7.85 7 6.5
17 Pressure Drop Units Min. Nor. Max. kgf/cm² 7.49 6.6 6.1
18 Inlet Temperature Units Min. Nor. Max. °C 40 40 40
PROCESS 19 Density Units Min. Nor. Max. kg/m³
CONDITIONS 20 Viscosity Units Min. Nor. Max. cP 0.019 0.019 0.019
21 Molecular Weight (MW) Specific Gravity @ Oper. 28.85
22 Spec. Heat Ratio (Cp/Cv) Compressibility (Z) 1.392 0.997
23 Vapor Pressure (Liq.) Cavitation or Flashing kgf/cm²-a N/A
24 Critical Pressure (Liq) Flash (wt%) kgf/cm²-a
25 Design Pressure Min. Max. kgf/cm²-g 10.5 kgf/cm²-g
26 Design Temperature Min. Max. 10 °C 80 °C
27 Max.Shutoff DP Solid % 10.5 kgf/cm²
28 Calculated Cv Units Min. Nor. Max. Cv 1.06 1.18 1.26
CALCULATED
29 Travel Units Min. Nor. Max. % 64 67 69
RESULTS
30 Noise dBA @1m Units Min. Nor. Max. dBA 57 57 57
31 MFR Model FISHER EZ 56 MFR Model FISHER DVC6200F/SC-AD
32 Body Type Single Seat Globe 57 Signal: Inlet Outlet FF Protocol 0-2.8 kgf/cm2
33 Body Size Trim Size 1 in 3/8 in 58 Increase Signal Valve: DIRECT
34 End Connec.Size & Rating 1" 300# RF POSITIONER 59 Cam Characteristic LINEAR
35 Rated Cv Characteristic 3.07 EQ% 60 Bypass Gauges N/A YES
36 Body Material WC9 Alloy Steel 61 Signal Fail. to Valve FC
BODY 37 Bonnet Type Material Style 1 Extension WC9 Alloy Steel 62 Electric Enclosure Ex ia IIC T5 , NEMA 4X
AND 38 Flow Direct. Flow Act. To Up FTO 63 MFR Model N/A N/A
TRIM 39 Packing Type Material Enviro Seal PTFE Carbon 64 Type Power N/A N/A
SOLENOID
40 Lubricator Isolat. Valve N/A N/A 65 When De-Enegr.Valve: N/A
VALVE
41 Guiding No. of Ports Post 1 66 Material Latcher N/A N/A
42 Trim Type Internal Design Micro Form Unbalanced 67 Electric Enclosure N/A
43 Rated Travel Leak Class 3/4 in ANSI IV 68 MFR Model N/A N/A
44 Plug/ Ball/ Disk Material S41600 SST 69 Type Quantity N/A N/A
45 Seat Material S41600 SST SWITCHES 70 Contacts / Rating N/A
46 Cage Stem Material N/A S31600 SST 71 Switching Position N/A
47 Gasket Material S31600 SST/Graphite 72 Electric Enclosure N/A
48 MFR Model FISHER 667 73 MFR Model FISHER 67CFR
49 Type Diaphragm Spring Return AIR SET 74 Set Pressure 4.2 kgf/cm2-g
50 Size Stroke Time 30i < 5 Sec 75 Filter Gauge 5 Micron min YES
ACTUATOR 51 Air Failure Valve: FC 76 Vol. Tank Booster NO NO
52 Handwheel Location N/A 77 Diffuser Lock-up NO NO
ACCESSORY
53 Mounting Position VERTICAL 78 Fire Safe Fireproof NO NO
54 Spring Range 0.8 - 2.5 kgf/cm2-g 79 Mech. Stop Quick Exa. NO NO
55 Include Pressure (Shutoff) 80 Hydro. Pressure YES
85 Vendor EMERSON 81 Leakage YES
PURCHASE TESTS
86 Manufacturer FISHER 82 Cryogenic N/A
87 Requisition No. R2B-P3-206-02-P-MR-00200 83 NACE Requirement N/A
88 Model No. EZ 84 PWHT Requirement YES
Notes:

INSTRUMENT SPECIFICATION - CONTROL VALVE


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S42.1 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Fieldbus Device Data Sheet
Tag No.: FV -21074
Fieldbus Tag No.:

Service : PA TO DC002

Basic Fieldbus Function Blocks Segment Information


Analog Input Block (AI) 1 Number Device:
1 22
20 Execution (msec)
Discrete Input Block (DI) 4 Number Segment #: DFJB-21041
2 23
15 Execution Time
3 Bias/Gain Station (BG) 0 Execution (msec) 24 LAS Capable: Yes No
Manual Loader (ML) 0 Number 25 Device Current Draw (mA): 19
4
0 Execution (msec) Device Minimum Voltage: 9.
26
Analog Output Block (AO) 1 Number Device Capacitance: 5 nF
5 20 Execution (msec) Polarity-sensitive: Yes No
27
Discrete Output Block (DO) 1 Number Segment Terminator Location:
6 20 Execution (msec)
28
7 Control Selector (CS)
DD Revision: 3
PID,PI,I Controller (PID) 29
8
20 Execution (msec)
CFF Revision: 1.9
Ratio Station (RA) 30
9
P,PD Controller (PD) 0 Number
10 0 Execution (msec)

* Execution time in msec.

Advanced Function Blocks Notes:

11 Device Control (DC)

12 Output Splitter (OS)

13 Signal Characterizer (SC)

14 Lead Lag (LL)

15 Deadtime (DT)

16 Integrator(Totalizer) (IT)

17 Setpoint Ramp Generator (SPG)

18 Input Selector (IS)

19 Arithmetic (AR)

20 Timer (TMR)

21 Analog Alarm (AAL)

INSTRUMENT SPECIFICATION -FOUNDATION FIELDBUS


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S42.2 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Tag Number : FV -21074

1. In-Built surge protector is provided by vendor.

1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S42.3 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
1 Tag No. FV -21081
2 Service MP STM TO DC001 RX
3 P&ID No. Line No. R2B-P3-206-02-A-DTI-00064 8"-VM-210423-T-B04T1-EC
4 Area Classification Ingress Protection CLASS 1 DIV 2 Gr. B ,C&D, T3 NEMA 4X
GENERAL 5 Ambient Temperature: Unit Min. Max. °C 10 48
6 Allowable Sound dBA Tightness Requirement <85 ANSI IV (standard)
7 Available Air Supply Pressure Unit Min. Max. kgf/cm²-g 4.2 8.0
8 Electric Connection Pneum. Connection 1/2” NPT (F) 1/4” NPT (F)
9 Power Failure Position FO
10 Line Size and Schedule Sch. Outlet Line Sch. 8 in STD 10" STD
PIPE
11 Line Class Rating Pipe Material T-B04T1 300# A106 GR.B, SMLS
LINE
12 Pipe Insulation Thickness Corrosion Allowance EC 115mm 1.6mm
13 Fluid State Phase Steam Gas/Vapor Single Phase
14 Sour Service Special Condition N/A N/A
15 Flow Rate Units Min. Nor. Max. kg/h 16608 16608 16608
16 Inlet Pressure Units Min. Nor. Max. kgf/cm²-g 13.32 10.25 9.75
17 Pressure Drop Units Min. Nor. Max. kgf/cm² 11.66 7.95 7.28
18 Inlet Temperature Units Min. Nor. Max. °C 220 220 220
PROCESS 19 Density Units Min. Nor. Max. kg/m³
CONDITIONS 20 Viscosity Units Min. Nor. Max. cP 0.017 0.017 0.017
21 Molecular Weight (MW) Specific Gravity @ Oper. 18.02
22 Spec. Heat Ratio (Cp/Cv) Compressibility (Z) 1.238 0.947
23 Vapor Pressure (Liq.) Cavitation or Flashing kgf/cm²-a N/A
24 Critical Pressure (Liq) Flash (wt%) kgf/cm²-a
25 Design Pressure Min. Max. -1.033 kgf/cm²-g 15.5 kgf/cm²-g
26 Design Temperature Min. Max. 10 °C 260 °C
27 Max.Shutoff DP Solid % 15.5 kgf/cm²
28 Calculated Cv Units Min. Nor. Max. Cv 135 173 181
CALCULATED
29 Travel Units Min. Nor. Max. % 32 40 41
RESULTS
30 Noise dBA @1m Units Min. Nor. Max. dBA 85 82 81
31 MFR Model FISHER ET 56 MFR Model FISHER DVC6200F/SC-AD
32 Body Type Single Seat Globe 57 Signal: Inlet Outlet FF Protocol 0-2.8 kgf/cm2
33 Body Size Trim Size 6 in 5 3/8 in 58 Increase Signal Valve: DIRECT
34 End Connec.Size & Rating 6" 300# RF POSITIONER 59 Cam Characteristic LINEAR
35 Rated Cv Characteristic 295 Linear 60 Bypass Gauges N/A YES
36 Body Material WCC Steel 61 Signal Fail. to Valve FO
BODY 37 Bonnet Type Material Plain WCC Steel 62 Electric Enclosure Ex ia IIC T5 , NEMA 4X
AND 38 Flow Direct. Flow Act. To Up FTC 63 MFR Model ASCO 362
TRIM 39 Packing Type Material Enviro Seal Graphite ULF 64 Type Power 3way 24VDC (IS)
SOLENOID
40 Lubricator Isolat. Valve N/A N/A 65 When De-Enegr.Valve: CLOSE
VALVE
41 Guiding No. of Ports Cage 1 66 Material Latcher SS 316 N/A
42 Trim Type Internal Design Whisper III Balanced 67 Electric Enclosure Ex ia IIC T5 , NEMA 4X
43 Rated Travel Leak Class 3 in ANSI IV 68 MFR Model TOPWORX DXP-Z20GN4B
44 Plug/ Ball/ Disk Material S17400 SST 69 Type Quantity Proximity 1
45 Seat Material S41600 SST SWITCHES 70 Contacts / Rating Dry Contact
46 Cage Stem Material S41600 SST S31600 SST 71 Switching Position Open
47 Gasket Material S31600 SST/Graphite 72 Electric Enclosure Ex ia IIC T4 , NEMA 4X
48 MFR Model FISHER 657 73 MFR Model FISHER 67CFR
49 Type Diaphragm Spring Return AIR SET 74 Set Pressure 4.2 kgf/cm2-g
50 Size Stroke Time 70i < 15 Sec 75 Filter Gauge 5 Micron min YES
ACTUATOR 51 Air Failure Valve: FO 76 Vol. Tank Booster NO NO
52 Handwheel Location N/A 77 Diffuser Lock-up NO NO
ACCESSORY
53 Mounting Position VERTICAL 78 Fire Safe Fireproof NO NO
54 Spring Range 0.4 - 2.0 kgf/cm2-g 79 Mech. Stop Quick Exa. NO NO
55 Include Pressure (Shutoff) 80 Hydro. Pressure YES
85 Vendor EMERSON 81 Leakage YES
PURCHASE TESTS
86 Manufacturer FISHER 82 Cryogenic N/A
87 Requisition No. R2B-P3-206-02-P-MR-00200 83 NACE Requirement N/A
88 Model No. ET 84 PWHT Requirement N/A
Notes:

INSTRUMENT SPECIFICATION - CONTROL VALVE


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S43.1 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Fieldbus Device Data Sheet
Tag No.: FV -21081
Fieldbus Tag No.:

Service : MP STM TO DC001 RX

Basic Fieldbus Function Blocks Segment Information


Analog Input Block (AI) 1 Number Device:
1 22
20 Execution (msec)
Discrete Input Block (DI) 4 Number Segment #: DFJB-21050
2 23
15 Execution Time
3 Bias/Gain Station (BG) 0 Execution (msec) 24 LAS Capable: Yes No
Manual Loader (ML) 0 Number 25 Device Current Draw (mA): 19
4
0 Execution (msec) Device Minimum Voltage: 9.
26
Analog Output Block (AO) 1 Number Device Capacitance: 5 nF
5 20 Execution (msec) Polarity-sensitive: Yes No
27
Discrete Output Block (DO) 1 Number Segment Terminator Location:
6 20 Execution (msec)
28
7 Control Selector (CS)
DD Revision: 3
PID,PI,I Controller (PID) 29
8
20 Execution (msec)
CFF Revision: 1.9
Ratio Station (RA) 30
9
P,PD Controller (PD) 0 Number
10 0 Execution (msec)

* Execution time in msec.

Advanced Function Blocks Notes:

11 Device Control (DC)

12 Output Splitter (OS)

13 Signal Characterizer (SC)

14 Lead Lag (LL)

15 Deadtime (DT)

16 Integrator(Totalizer) (IT)

17 Setpoint Ramp Generator (SPG)

18 Input Selector (IS)

19 Arithmetic (AR)

20 Timer (TMR)

21 Analog Alarm (AAL)

INSTRUMENT SPECIFICATION -FOUNDATION FIELDBUS


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S43.2 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Tag Number : FV -21081

1. Valve will normally be in the closed position. Valve opening will be intermittent and generally short-term.
2. SOV Tag Number : FY-21981 & Limit Switch Tag Number : ZSH-21981.
3. Limit switch is proximity type (NO, NC and Common. Dry contact) .
4. In-Built surge protector is provided by vendor.

1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S43.3 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
1 Tag No. FV -21087
2 Service FA003 MP STM TO DC001 RX
3 P&ID No. Line No. R2B-P3-206-02-A-DTI-00069 4"-VM-210486-T-B04T1-EC
4 Area Classification Ingress Protection CLASS 1 DIV 2 Gr. B ,C&D, T3 NEMA 4X
GENERAL 5 Ambient Temperature: Unit Min. Max. °C 10 48
6 Allowable Sound dBA Tightness Requirement <85 ANSI IV (standard)
7 Available Air Supply Pressure Unit Min. Max. kgf/cm²-g 4.2 8.0
8 Electric Connection Pneum. Connection 1/2” NPT (F) 1/4” NPT (F)
9 Power Failure Position FO
10 Line Size and Schedule Sch. Outlet Line Sch. 3 in STD 4" STD
PIPE
11 Line Class Rating Pipe Material T-B04T1 300# A106 GR.B, SMLS
LINE
12 Pipe Insulation Thickness Corrosion Allowance EC 90mm 1.6mm
13 Fluid State Phase Steam Gas/Vapor Single Phase
14 Sour Service Special Condition N/A N/A
15 Flow Rate Units Min. Nor. Max. kg/h 907 1133 1360
16 Inlet Pressure Units Min. Nor. Max. kgf/cm²-g 6.14 6.05 5.94
17 Pressure Drop Units Min. Nor. Max. kgf/cm² 4.079 3.32 2.94
18 Inlet Temperature Units Min. Nor. Max. °C 210 210 210
PROCESS 19 Density Units Min. Nor. Max. kg/m³
CONDITIONS 20 Viscosity Units Min. Nor. Max. cP 0.017 0.017 0.017
21 Molecular Weight (MW) Specific Gravity @ Oper. 18.02
22 Spec. Heat Ratio (Cp/Cv) Compressibility (Z) 1.261 0.966
23 Vapor Pressure (Liq.) Cavitation or Flashing 0 kgf/cm²-a N/A
24 Critical Pressure (Liq) Flash (wt%) kgf/cm²-a
25 Design Pressure Min. Max. -1.033 kgf/cm²-g 7.38 kgf/cm²-g
26 Design Temperature Min. Max. 10 °C 260 °C
27 Max.Shutoff DP Solid % 7.38 kgf/cm²
28 Calculated Cv Units Min. Nor. Max. Cv 13.5 17.7 22.4
CALCULATED
29 Travel Units Min. Nor. Max. % 37 47 60
RESULTS
30 Noise dBA @1m Units Min. Nor. Max. dBA 83 84 84
31 MFR Model FISHER EZ 56 MFR Model FISHER DVC6200F/SC-AD
32 Body Type Single Seat Globe 57 Signal: Inlet Outlet FF Protocol 0-2.8 kgf/cm2
33 Body Size Trim Size 1.5 in 1 1/2 in 58 Increase Signal Valve: DIRECT
34 End Connec.Size & Rating 1.5" 300# RF POSITIONER 59 Cam Characteristic LINEAR
35 Rated Cv Characteristic 31.9 Linear 60 Bypass Gauges N/A YES
36 Body Material WCC Steel 61 Signal Fail. to Valve FO
BODY 37 Bonnet Type Material Style 1 Extension WCC Steel 62 Electric Enclosure Ex ia IIC T5 , NEMA 4X
AND 38 Flow Direct. Flow Act. To Up FTO 63 MFR Model N/A N/A
TRIM 39 Packing Type Material Enviro Seal Graphite ULF 64 Type Power N/A N/A
SOLENOID
40 Lubricator Isolat. Valve N/A N/A 65 When De-Enegr.Valve: N/A
VALVE
41 Guiding No. of Ports Post 1 66 Material Latcher N/A N/A
42 Trim Type Internal Design Standard Unbalanced 67 Electric Enclosure N/A
43 Rated Travel Leak Class 3/4 in ANSI IV 68 MFR Model N/A N/A
44 Plug/ Ball/ Disk Material S41600 SST 69 Type Quantity N/A N/A
45 Seat Material S41600 SST SWITCHES 70 Contacts / Rating N/A
46 Cage Stem Material N/A S31600 SST 71 Switching Position N/A
47 Gasket Material S31600 SST/Graphite 72 Electric Enclosure N/A
48 MFR Model FISHER 657 73 MFR Model FISHER 67CFR
49 Type Diaphragm Spring Return AIR SET 74 Set Pressure 4.2 kgf/cm2-g
50 Size Stroke Time 34i < 5 Sec 75 Filter Gauge 5 Micron min YES
ACTUATOR 51 Air Failure Valve: FO 76 Vol. Tank Booster NO NO
52 Handwheel Location N/A 77 Diffuser Lock-up NO NO
ACCESSORY
53 Mounting Position VERTICAL 78 Fire Safe Fireproof NO NO
54 Spring Range 0.4 - 1.8 kgf/cm2-g 79 Mech. Stop Quick Exa. NO NO
55 Include Pressure (Shutoff) 80 Hydro. Pressure YES
85 Vendor EMERSON 81 Leakage YES
PURCHASE TESTS
86 Manufacturer FISHER 82 Cryogenic N/A
87 Requisition No. R2B-P3-206-02-P-MR-00200 83 NACE Requirement N/A
88 Model No. EZ 84 PWHT Requirement N/A
Notes:

INSTRUMENT SPECIFICATION - CONTROL VALVE


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S44.1 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Fieldbus Device Data Sheet
Tag No.: FV -21087
Fieldbus Tag No.:

Service : FA003 MP STM TO DC001 RX

Basic Fieldbus Function Blocks Segment Information


Analog Input Block (AI) 1 Number Device:
1 22
20 Execution (msec)
Discrete Input Block (DI) 4 Number Segment #: DFJB-21046
2 23
15 Execution Time
3 Bias/Gain Station (BG) 0 Execution (msec) 24 LAS Capable: Yes No
Manual Loader (ML) 0 Number 25 Device Current Draw (mA): 19
4
0 Execution (msec) Device Minimum Voltage: 9.
26
Analog Output Block (AO) 1 Number Device Capacitance: 5 nF
5 20 Execution (msec) Polarity-sensitive: Yes No
27
Discrete Output Block (DO) 1 Number Segment Terminator Location:
6 20 Execution (msec)
28
7 Control Selector (CS)
DD Revision: 3
PID,PI,I Controller (PID) 29
8
20 Execution (msec)
CFF Revision: 1.9
Ratio Station (RA) 30
9
P,PD Controller (PD) 0 Number
10 0 Execution (msec)

* Execution time in msec.

Advanced Function Blocks Notes:

11 Device Control (DC)

12 Output Splitter (OS)

13 Signal Characterizer (SC)

14 Lead Lag (LL)

15 Deadtime (DT)

16 Integrator(Totalizer) (IT)

17 Setpoint Ramp Generator (SPG)

18 Input Selector (IS)

19 Arithmetic (AR)

20 Timer (TMR)

21 Analog Alarm (AAL)

INSTRUMENT SPECIFICATION -FOUNDATION FIELDBUS


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S44.2 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Tag Number : FV -21087

1. In-Built surge protector is provided by vendor.

1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S44.3 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
1 Tag No. FV -21088
2 Service FA003 MP STM TO DC001 RX
3 P&ID No. Line No. R2B-P3-206-02-A-DTI-00069 4"-VM-210489-T-B04T1-EC
4 Area Classification Ingress Protection CLASS 1 DIV 2 Gr. B ,C&D, T3 NEMA 4X
GENERAL 5 Ambient Temperature: Unit Min. Max. °C 10 48
6 Allowable Sound dBA Tightness Requirement <85 ANSI IV (standard)
7 Available Air Supply Pressure Unit Min. Max. kgf/cm²-g 4.2 8.0
8 Electric Connection Pneum. Connection 1/2” NPT (F) 1/4” NPT (F)
9 Power Failure Position FO
10 Line Size and Schedule Sch. Outlet Line Sch. 4 in STD 4" STD
PIPE
11 Line Class Rating Pipe Material T-B04T1 300# A106 GR.B, SMLS
LINE
12 Pipe Insulation Thickness Corrosion Allowance EC 100mm 1.6mm
13 Fluid State Phase Steam Gas/Vapor Single Phase
14 Sour Service Special Condition N/A N/A
15 Flow Rate Units Min. Nor. Max. kg/h 907 1133 1360
16 Inlet Pressure Units Min. Nor. Max. kgf/cm²-g 6.14 6.05 5.94
17 Pressure Drop Units Min. Nor. Max. kgf/cm² 4.19 3.54 3.19
18 Inlet Temperature Units Min. Nor. Max. °C 210 210 210
PROCESS 19 Density Units Min. Nor. Max. kg/m³
CONDITIONS 20 Viscosity Units Min. Nor. Max. cP 0.017 0.017 0.017
21 Molecular Weight (MW) Specific Gravity @ Oper. 18.02
22 Spec. Heat Ratio (Cp/Cv) Compressibility (Z) 1.261 0.966
23 Vapor Pressure (Liq.) Cavitation or Flashing kgf/cm²-a N/A
24 Critical Pressure (Liq) Flash (wt%) kgf/cm²-a
25 Design Pressure Min. Max. -1.033 kgf/cm²-g 7.38 kgf/cm²-g
26 Design Temperature Min. Max. 10 °C 260 °C
27 Max.Shutoff DP Solid % 7.38 kgf/cm²
28 Calculated Cv Units Min. Nor. Max. Cv 14.3 17.8 21.6
CALCULATED
29 Travel Units Min. Nor. Max. % 43 54 66
RESULTS
30 Noise dBA @1m Units Min. Nor. Max. dBA 85 85 85
31 MFR Model FISHER ET 56 MFR Model FISHER DVC6200F/SC-AD
32 Body Type Single Seat Globe 57 Signal: Inlet Outlet FF Protocol 0-2.8 kgf/cm2
33 Body Size Trim Size 2 in 1 5/16 in 58 Increase Signal Valve: DIRECT
34 End Connec.Size & Rating 2" 300# RF POSITIONER 59 Cam Characteristic LINEAR
35 Rated Cv Characteristic 33.3 Linear 60 Bypass Gauges N/A YES
36 Body Material WCC Steel 61 Signal Fail. to Valve FO
BODY 37 Bonnet Type Material Style 1 Extension WCC Steel 62 Electric Enclosure Ex ia IIC T5 , NEMA 4X
AND 38 Flow Direct. Flow Act. To Down FTO 63 MFR Model N/A N/A
TRIM 39 Packing Type Material Enviro Seal Graphite ULF 64 Type Power N/A N/A
SOLENOID
40 Lubricator Isolat. Valve N/A N/A 65 When De-Enegr.Valve: N/A
VALVE
41 Guiding No. of Ports Cage 1 66 Material Latcher N/A N/A
42 Trim Type Internal Design Standard Balanced 67 Electric Enclosure N/A
43 Rated Travel Leak Class 3/4 in ANSI IV 68 MFR Model N/A N/A
44 Plug/ Ball/ Disk Material S41600 SST 69 Type Quantity N/A N/A
45 Seat Material S41600 SST SWITCHES 70 Contacts / Rating N/A
46 Cage Stem Material CB7Cu-1 SST S31600 SST 71 Switching Position N/A
47 Gasket Material S31600 SST/Graphite 72 Electric Enclosure N/A
48 MFR Model FISHER 657 73 MFR Model FISHER 67CFR
49 Type Diaphragm Spring Return AIR SET 74 Set Pressure 4.2 kgf/cm2-g
50 Size Stroke Time 40i < 8 Sec 75 Filter Gauge 5 Micron min YES
ACTUATOR 51 Air Failure Valve: FO 76 Vol. Tank Booster NO NO
52 Handwheel Location N/A 77 Diffuser Lock-up NO NO
ACCESSORY
53 Mounting Position VERTICAL 78 Fire Safe Fireproof NO NO
54 Spring Range 0.4 - 2.0 kgf/cm2-g 79 Mech. Stop Quick Exa. NO NO
55 Include Pressure (Shutoff) 80 Hydro. Pressure YES
85 Vendor EMERSON 81 Leakage YES
PURCHASE TESTS
86 Manufacturer FISHER 82 Cryogenic N/A
87 Requisition No. R2B-P3-206-02-P-MR-00200 83 NACE Requirement N/A
88 Model No. ET 84 PWHT Requirement N/A
Notes:

INSTRUMENT SPECIFICATION - CONTROL VALVE


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S45.1 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Fieldbus Device Data Sheet
Tag No.: FV -21088
Fieldbus Tag No.:

Service : FA003 MP STM TO DC001 RX

Basic Fieldbus Function Blocks Segment Information


Analog Input Block (AI) 1 Number Device:
1 22
20 Execution (msec)
Discrete Input Block (DI) 4 Number Segment #: DFJB-21045
2 23
15 Execution Time
3 Bias/Gain Station (BG) 0 Execution (msec) 24 LAS Capable: Yes No
Manual Loader (ML) 0 Number 25 Device Current Draw (mA): 19
4
0 Execution (msec) Device Minimum Voltage: 9.
26
Analog Output Block (AO) 1 Number Device Capacitance: 5 nF
5 20 Execution (msec) Polarity-sensitive: Yes No
27
Discrete Output Block (DO) 1 Number Segment Terminator Location:
6 20 Execution (msec)
28
7 Control Selector (CS)
DD Revision: 3
PID,PI,I Controller (PID) 29
8
20 Execution (msec)
CFF Revision: 1.9
Ratio Station (RA) 30
9
P,PD Controller (PD) 0 Number
10 0 Execution (msec)

* Execution time in msec.

Advanced Function Blocks Notes:

11 Device Control (DC)

12 Output Splitter (OS)

13 Signal Characterizer (SC)

14 Lead Lag (LL)

15 Deadtime (DT)

16 Integrator(Totalizer) (IT)

17 Setpoint Ramp Generator (SPG)

18 Input Selector (IS)

19 Arithmetic (AR)

20 Timer (TMR)

21 Analog Alarm (AAL)

INSTRUMENT SPECIFICATION -FOUNDATION FIELDBUS


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S45.2 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Tag Number : FV -21088

1. In-Built surge protector is provided by vendor.

1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S45.3 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
1 Tag No. FV -21101
2 Service STOR GAS OIL TO FA101
3 P&ID No. Line No. R2B-P3-206-02-A-DTI-00101 8"-P-211530-B1A1-EC(ST)
4 Area Classification Ingress Protection CLASS 1 DIV 2 Gr. B ,C&D, T3 NEMA 4X
GENERAL 5 Ambient Temperature: Unit Min. Max. °C 10 48
6 Allowable Sound dBA Tightness Requirement <85 ANSI V
7 Available Air Supply Pressure Unit Min. Max. kgf/cm²-g 4.2 8.0
8 Electric Connection Pneum. Connection 1/2” NPT (F) 1/4” NPT (F)
9 Power Failure Position FC
10 Line Size and Schedule Sch. Outlet Line Sch. 8 in STD 8" STD
PIPE
11 Line Class Rating Pipe Material B1A1 150# A106 GR.B, SMLS
LINE
12 Pipe Insulation Thickness Corrosion Allowance EC(ST) 65mm 1.6mm
13 Fluid State Phase Hydrocarbon Liquid Single Phase
14 Sour Service Special Condition N/A N/A
15 Flow Rate Units Min. Nor. Max. m³/h 97.7 195.4 326.3
16 Inlet Pressure Units Min. Nor. Max. kgf/cm²-g 5.06 4.909 4.578
17 Pressure Drop Units Min. Nor. Max. kgf/cm² 2.915 2.695 2.214
18 Inlet Temperature Units Min. Nor. Max. °C 75 75 75
PROCESS 19 Density Units Min. Nor. Max. kg/m³ 861 861 861
CONDITIONS 20 Viscosity Units Min. Nor. Max. cP 5.131 5.131 5.131
21 Molecular Weight (MW) Specific Gravity @ Oper.
22 Spec. Heat Ratio (Cp/Cv) Compressibility (Z)
23 Vapor Pressure (Liq.) Cavitation or Flashing 0 kgf/cm²-a NO
24 Critical Pressure (Liq) Flash (wt%) 12.28 kgf/cm²-a
25 Design Pressure Min. Max. kgf/cm²-g 12.3 kgf/cm²-g
26 Design Temperature Min. Max. 10 °C 105 °C
27 Max.Shutoff DP Solid % 12.3 kgf/cm²
28 Calculated Cv Units Min. Nor. Max. Cv 62. 129 239
CALCULATED
29 Travel Units Min. Nor. Max. % 43 62 80
RESULTS
30 Noise dBA @1m Units Min. Nor. Max. dBA 74 76 74
31 MFR Model FISHER ET 56 MFR Model FISHER DVC6200F/SC-AD
32 Body Type Single Seat Globe 57 Signal: Inlet Outlet FF Protocol 0-3.5 kgf/cm2
33 Body Size Trim Size 6 in 7 in 58 Increase Signal Valve: DIRECT
34 End Connec.Size & Rating 6" 300# RF POSITIONER 59 Cam Characteristic LINEAR
35 Rated Cv Characteristic 357.6 EQ% 60 Bypass Gauges N/A YES
36 Body Material WCC Steel 61 Signal Fail. to Valve FC
BODY 37 Bonnet Type Material Plain WCC Steel 62 Electric Enclosure Ex ia IIC T5 , NEMA 4X
AND 38 Flow Direct. Flow Act. To Down FTO 63 MFR Model N/A N/A
TRIM 39 Packing Type Material Enviro Seal PTFE Carbon 64 Type Power N/A N/A
SOLENOID
40 Lubricator Isolat. Valve N/A N/A 65 When De-Enegr.Valve: N/A
VALVE
41 Guiding No. of Ports Cage 1 66 Material Latcher N/A N/A
42 Trim Type Internal Design Standard Balanced 67 Electric Enclosure N/A
43 Rated Travel Leak Class 1 3/4 in ANSI V 68 MFR Model N/A N/A
44 Plug/ Ball/ Disk Material S41600 SST 69 Type Quantity N/A N/A
45 Seat Material S41600 SST SWITCHES 70 Contacts / Rating N/A
46 Cage Stem Material CB7Cu-1 SST S31600 SST 71 Switching Position N/A
47 Gasket Material S31600 SST/Graphite 72 Electric Enclosure N/A
48 MFR Model FISHER 667 73 MFR Model FISHER 67CFR
49 Type Diaphragm Spring Return AIR SET 74 Set Pressure 4.2 kgf/cm2-g
50 Size Stroke Time 76i < 15 Sec 75 Filter Gauge 5 Micron min YES
ACTUATOR 51 Air Failure Valve: FC 76 Vol. Tank Booster NO NO
52 Handwheel Location N/A 77 Diffuser Lock-up NO NO
ACCESSORY
53 Mounting Position VERTICAL 78 Fire Safe Fireproof NO NO
54 Spring Range 1.4 - 3.1 kgf/cm2-g 79 Mech. Stop Quick Exa. NO NO
55 Include Pressure (Shutoff) 80 Hydro. Pressure YES
85 Vendor EMERSON 81 Leakage YES
PURCHASE TESTS
86 Manufacturer FISHER 82 Cryogenic N/A
87 Requisition No. R2B-P3-206-02-P-MR-00200 83 NACE Requirement N/A
88 Model No. ET 84 PWHT Requirement N/A
Notes:

INSTRUMENT SPECIFICATION - CONTROL VALVE


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S46.1 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Fieldbus Device Data Sheet
Tag No.: FV -21101
Fieldbus Tag No.:

Service : STOR GAS OIL TO FA101

Basic Fieldbus Function Blocks Segment Information


Analog Input Block (AI) 1 Number Device:
1 22
20 Execution (msec)
Discrete Input Block (DI) 4 Number Segment #: DFJB-21088
2 23
15 Execution Time
3 Bias/Gain Station (BG) 0 Execution (msec) 24 LAS Capable: Yes No
Manual Loader (ML) 0 Number 25 Device Current Draw (mA): 19
4
0 Execution (msec) Device Minimum Voltage: 9.
26
Analog Output Block (AO) 1 Number Device Capacitance: 5 nF
5 20 Execution (msec) Polarity-sensitive: Yes No
27
Discrete Output Block (DO) 1 Number Segment Terminator Location:
6 20 Execution (msec)
28
7 Control Selector (CS)
DD Revision: 3
PID,PI,I Controller (PID) 29
8
20 Execution (msec)
CFF Revision: 1.9
Ratio Station (RA) 30
9
P,PD Controller (PD) 0 Number
10 0 Execution (msec)

* Execution time in msec.

Advanced Function Blocks Notes:

11 Device Control (DC)

12 Output Splitter (OS)

13 Signal Characterizer (SC)

14 Lead Lag (LL)

15 Deadtime (DT)

16 Integrator(Totalizer) (IT)

17 Setpoint Ramp Generator (SPG)

18 Input Selector (IS)

19 Arithmetic (AR)

20 Timer (TMR)

21 Analog Alarm (AAL)

INSTRUMENT SPECIFICATION -FOUNDATION FIELDBUS


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S46.2 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Tag Number : FV -21101

1. In-Built surge protector is provided by vendor.

1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S46.3 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
1 Tag No. FV -21102
2 Service GA101AB HT DIE TO FA101
3 P&ID No. Line No. R2B-P3-206-02-A-DTI-00102 8"-P-211008-B2A1-EC(ST)
4 Area Classification Ingress Protection CLASS 1 DIV 2 Gr. B ,C&D, T3 NEMA 4X
GENERAL 5 Ambient Temperature: Unit Min. Max. °C 10 48
6 Allowable Sound dBA Tightness Requirement <85 ANSI IV (standard)
7 Available Air Supply Pressure Unit Min. Max. kgf/cm²-g 4.2 8.0
8 Electric Connection Pneum. Connection 1/2” NPT (F) 1/4” NPT (F)
9 Power Failure Position FO
10 Line Size and Schedule Sch. Outlet Line Sch. 8 in STD 8" STD
PIPE
11 Line Class Rating Pipe Material B2A1 300# A106 GR.B, SMLS
LINE
12 Pipe Insulation Thickness Corrosion Allowance EC(ST) 90mm 1.6mm
13 Fluid State Phase Hydrocarbon Liquid Single Phase
14 Sour Service Special Condition N/A N/A
15 Flow Rate Units Min. Nor. Max. m³/h 143.45 286.91 315.6
16 Inlet Pressure Units Min. Nor. Max. kgf/cm²-g 19.45 19.45 19.45
17 Pressure Drop Units Min. Nor. Max. kgf/cm² 17.06 17.06 17.06
18 Inlet Temperature Units Min. Nor. Max. °C 188 188 188
PROCESS 19 Density Units Min. Nor. Max. kg/m³ 794 794 794
CONDITIONS 20 Viscosity Units Min. Nor. Max. cP 1.031 1.031 1.031
21 Molecular Weight (MW) Specific Gravity @ Oper.
22 Spec. Heat Ratio (Cp/Cv) Compressibility (Z)
23 Vapor Pressure (Liq.) Cavitation or Flashing 0 kgf/cm²-a NO
24 Critical Pressure (Liq) Flash (wt%) 12.28 kgf/cm²-a
25 Design Pressure Min. Max. -1.033 kgf/cm²-g 24.4 kgf/cm²-g
26 Design Temperature Min. Max. 10 °C 345 °C
27 Max.Shutoff DP Solid % 24.4 kgf/cm²
28 Calculated Cv Units Min. Nor. Max. Cv 37.9 75.9 83.6
CALCULATED
29 Travel Units Min. Nor. Max. % 45 62 64
RESULTS
30 Noise dBA @1m Units Min. Nor. Max. dBA 85 85 85
31 MFR Model FISHER EWD 56 MFR Model FISHER DVC6200F/SC-AD
32 Body Type Single Seat Globe 57 Signal: Inlet Outlet FF Protocol 0-2.8 kgf/cm2
33 Body Size Trim Size 6 in 4 3/8 in 58 Increase Signal Valve: DIRECT
34 End Connec.Size & Rating 6" 300# RF POSITIONER 59 Cam Characteristic LINEAR
35 Rated Cv Characteristic 271 EQ% 60 Bypass Gauges N/A YES
36 Body Material WCC Steel 61 Signal Fail. to Valve FO
BODY 37 Bonnet Type Material Plain WCC Steel 62 Electric Enclosure Ex ia IIC T5 , NEMA 4X
AND 38 Flow Direct. Flow Act. To Down FTO 63 MFR Model N/A N/A
TRIM 39 Packing Type Material ISO Seal Graphite 64 Type Power N/A N/A
SOLENOID
40 Lubricator Isolat. Valve N/A N/A 65 When De-Enegr.Valve: N/A
VALVE
41 Guiding No. of Ports Cage 1 66 Material Latcher N/A N/A
42 Trim Type Internal Design Standard Balanced 67 Electric Enclosure N/A
43 Rated Travel Leak Class 2 in ANSI IV 68 MFR Model N/A N/A
44 Plug/ Ball/ Disk Material S31600 SST/CoCr-A Seat 69 Type Quantity N/A N/A
45 Seat Material S31600 SST/CoCr-A Seat SWITCHES 70 Contacts / Rating N/A
46 Cage Stem Material CB7Cu-1 SST S31600 SST 71 Switching Position N/A
47 Gasket Material S31600 SST/Graphite 72 Electric Enclosure N/A
48 MFR Model FISHER 667 73 MFR Model FISHER 67CFR
49 Type Diaphragm Spring Return AIR SET 74 Set Pressure 4.2 kgf/cm2-g
50 Size Stroke Time 76i < 15 Sec 75 Filter Gauge 5 Micron min YES
ACTUATOR 51 Air Failure Valve: FO 76 Vol. Tank Booster NO NO
52 Handwheel Location Side Mounted 77 Diffuser Lock-up NO NO
ACCESSORY
53 Mounting Position VERTICAL 78 Fire Safe Fireproof NO NO
54 Spring Range 0.5 - 1.6 kgf/cm2-g 79 Mech. Stop Quick Exa. NO NO
55 Include Pressure (Shutoff) 80 Hydro. Pressure YES
85 Vendor EMERSON 81 Leakage YES
PURCHASE TESTS
86 Manufacturer FISHER 82 Cryogenic N/A
87 Requisition No. R2B-P3-206-02-P-MR-00200 83 NACE Requirement N/A
88 Model No. EWD 84 PWHT Requirement N/A
Notes:

INSTRUMENT SPECIFICATION - CONTROL VALVE


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S47.1 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Fieldbus Device Data Sheet
Tag No.: FV -21102
Fieldbus Tag No.:

Service : GA101AB HT DIE TO FA101

Basic Fieldbus Function Blocks Segment Information


Analog Input Block (AI) 1 Number Device:
1 22
20 Execution (msec)
Discrete Input Block (DI) 4 Number Segment #: DFJB-21087
2 23
15 Execution Time
3 Bias/Gain Station (BG) 0 Execution (msec) 24 LAS Capable: Yes No
Manual Loader (ML) 0 Number 25 Device Current Draw (mA): 19
4
0 Execution (msec) Device Minimum Voltage: 9.
26
Analog Output Block (AO) 1 Number Device Capacitance: 5 nF
5 20 Execution (msec) Polarity-sensitive: Yes No
27
Discrete Output Block (DO) 1 Number Segment Terminator Location:
6 20 Execution (msec)
28
7 Control Selector (CS)
DD Revision: 3
PID,PI,I Controller (PID) 29
8
20 Execution (msec)
CFF Revision: 1.9
Ratio Station (RA) 30
9
P,PD Controller (PD) 0 Number
10 0 Execution (msec)

* Execution time in msec.

Advanced Function Blocks Notes:

11 Device Control (DC)

12 Output Splitter (OS)

13 Signal Characterizer (SC)

14 Lead Lag (LL)

15 Deadtime (DT)

16 Integrator(Totalizer) (IT)

17 Setpoint Ramp Generator (SPG)

18 Input Selector (IS)

19 Arithmetic (AR)

20 Timer (TMR)

21 Analog Alarm (AAL)

INSTRUMENT SPECIFICATION -FOUNDATION FIELDBUS


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S47.2 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Tag Number : FV -21102

1. Steam Out condition : F.V/200 degC.

2. In-Built surge protector is provided by vendor.

1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S47.3 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
1 Tag No. FV -21103
2 Service GA101AB HT DIE TO EA101AB
3 P&ID No. Line No. R2B-P3-206-02-A-DTI-00102 12"-P-211007-B2A1-EC(ST)
4 Area Classification Ingress Protection CLASS 1 DIV 2 Gr. B ,C&D, T3 NEMA 4X
GENERAL 5 Ambient Temperature: Unit Min. Max. °C 10 48
6 Allowable Sound dBA Tightness Requirement <85 ANSI IV (standard)
7 Available Air Supply Pressure Unit Min. Max. kgf/cm²-g 4.2 8.0
8 Electric Connection Pneum. Connection 1/2” NPT (F) 1/4” NPT (F)
9 Power Failure Position FC
10 Line Size and Schedule Sch. Outlet Line Sch. 12 in STD 12" STD
PIPE
11 Line Class Rating Pipe Material B2A1 300# A106 GR.B, SMLS
LINE
12 Pipe Insulation Thickness Corrosion Allowance EC(ST) 100mm 1.6mm
13 Fluid State Phase Hydrocarbon Liquid Single Phase
14 Sour Service Special Condition N/A N/A
15 Flow Rate Units Min. Nor. Max. m³/h 353.2 706.4 777
16 Inlet Pressure Units Min. Nor. Max. kgf/cm²-g 19.29 19.2 19.07
17 Pressure Drop Units Min. Nor. Max. kgf/cm² 12.6 4.49 1.97
18 Inlet Temperature Units Min. Nor. Max. °C 188 188 188
PROCESS 19 Density Units Min. Nor. Max. kg/m³ 794 794 794
CONDITIONS 20 Viscosity Units Min. Nor. Max. cP 1.031 1.031 1.031
21 Molecular Weight (MW) Specific Gravity @ Oper.
22 Spec. Heat Ratio (Cp/Cv) Compressibility (Z)
23 Vapor Pressure (Liq.) Cavitation or Flashing 0 kgf/cm²-a NO
24 Critical Pressure (Liq) Flash (wt%) 12.28 kgf/cm²-a
25 Design Pressure Min. Max. -1.033 kgf/cm²-g 24.4 kgf/cm²-g
26 Design Temperature Min. Max. 10 °C 345 °C
27 Max.Shutoff DP Solid % 24.4 kgf/cm²
28 Calculated Cv Units Min. Nor. Max. Cv 104 350 588
CALCULATED
29 Travel Units Min. Nor. Max. % 16 48 81
RESULTS
30 Noise dBA @1m Units Min. Nor. Max. dBA 85 73 69
31 MFR Model FISHER ED 56 MFR Model FISHER DVC6200F/SC-AD
32 Body Type Single Seat Globe 57 Signal: Inlet Outlet FF Protocol 0-3.5 kgf/cm2
33 Body Size Trim Size 8 in 8 in 58 Increase Signal Valve: DIRECT
34 End Connec.Size & Rating 8" 300# RF POSITIONER 59 Cam Characteristic LINEAR
35 Rated Cv Characteristic 688 Linear 60 Bypass Gauges N/A YES
36 Body Material WCC Steel 61 Signal Fail. to Valve FC
BODY 37 Bonnet Type Material Plain WCC Steel 62 Electric Enclosure Ex ia IIC T5 , NEMA 4X
AND 38 Flow Direct. Flow Act. To Down FTO 63 MFR Model N/A N/A
TRIM 39 Packing Type Material ISO Seal Graphite 64 Type Power N/A N/A
SOLENOID
40 Lubricator Isolat. Valve N/A N/A 65 When De-Enegr.Valve: N/A
VALVE
41 Guiding No. of Ports Cage 1 66 Material Latcher N/A N/A
42 Trim Type Internal Design Standard Balanced 67 Electric Enclosure N/A
43 Rated Travel Leak Class 2 in ANSI IV 68 MFR Model N/A N/A
44 Plug/ Ball/ Disk Material S41600 SST 69 Type Quantity N/A N/A
45 Seat Material S41600 SST SWITCHES 70 Contacts / Rating N/A
46 Cage Stem Material CB7Cu-1 SST S31600 SST 71 Switching Position N/A
47 Gasket Material S31600 SST/Graphite 72 Electric Enclosure N/A
48 MFR Model FISHER 667 73 MFR Model FISHER 67CFR
49 Type Diaphragm Spring Return AIR SET 74 Set Pressure 4.2 kgf/cm2-g
50 Size Stroke Time 70i < 20 Sec 75 Filter Gauge 5 Micron min YES
ACTUATOR 51 Air Failure Valve: FC 76 Vol. Tank Booster NO NO
52 Handwheel Location N/A 77 Diffuser Lock-up NO NO
ACCESSORY
53 Mounting Position VERTICAL 78 Fire Safe Fireproof NO NO
54 Spring Range 1.2 - 2.8 kgf/cm2-g 79 Mech. Stop Quick Exa. NO NO
55 Include Pressure (Shutoff) 80 Hydro. Pressure YES
85 Vendor EMERSON 81 Leakage YES
PURCHASE TESTS
86 Manufacturer FISHER 82 Cryogenic N/A
87 Requisition No. R2B-P3-206-02-P-MR-00200 83 NACE Requirement N/A
88 Model No. ED 84 PWHT Requirement N/A
Notes:

INSTRUMENT SPECIFICATION - CONTROL VALVE


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S48.1 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Fieldbus Device Data Sheet
Tag No.: FV -21103
Fieldbus Tag No.:

Service : GA101AB HT DIE TO EA101AB

Basic Fieldbus Function Blocks Segment Information


Analog Input Block (AI) 1 Number Device:
1 22
20 Execution (msec)
Discrete Input Block (DI) 4 Number Segment #: DFJB-21069
2 23
15 Execution Time
3 Bias/Gain Station (BG) 0 Execution (msec) 24 LAS Capable: Yes No
Manual Loader (ML) 0 Number 25 Device Current Draw (mA): 19
4
0 Execution (msec) Device Minimum Voltage: 9.
26
Analog Output Block (AO) 1 Number Device Capacitance: 5 nF
5 20 Execution (msec) Polarity-sensitive: Yes No
27
Discrete Output Block (DO) 1 Number Segment Terminator Location:
6 20 Execution (msec)
28
7 Control Selector (CS)
DD Revision: 3
PID,PI,I Controller (PID) 29
8
20 Execution (msec)
CFF Revision: 1.9
Ratio Station (RA) 30
9
P,PD Controller (PD) 0 Number
10 0 Execution (msec)

* Execution time in msec.

Advanced Function Blocks Notes:

11 Device Control (DC)

12 Output Splitter (OS)

13 Signal Characterizer (SC)

14 Lead Lag (LL)

15 Deadtime (DT)

16 Integrator(Totalizer) (IT)

17 Setpoint Ramp Generator (SPG)

18 Input Selector (IS)

19 Arithmetic (AR)

20 Timer (TMR)

21 Analog Alarm (AAL)

INSTRUMENT SPECIFICATION -FOUNDATION FIELDBUS


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S48.2 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Tag Number : FV -21103

1. Steam out condition : F.V/200 degC.

2. In-Built surge protector is provided by vendor.

1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S48.3 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
1 Tag No. FV -21108
2 Service MP STM TO DS101
3 P&ID No. Line No. R2B-P3-206-02-A-DTI-00106 3"-VM-211002-T-B04T1-EC
4 Area Classification Ingress Protection CLASS 1 DIV 2 Gr. B ,C&D, T3 NEMA 4X
GENERAL 5 Ambient Temperature: Unit Min. Max. °C 10 48
6 Allowable Sound dBA Tightness Requirement <85 ANSI IV (standard)
7 Available Air Supply Pressure Unit Min. Max. kgf/cm²-g 4.2 8.0
8 Electric Connection Pneum. Connection 1/2” NPT (F) 1/4” NPT (F)
9 Power Failure Position FC
10 Line Size and Schedule Sch. Outlet Line Sch. 3 in STD 3" STD
PIPE
11 Line Class Rating Pipe Material T-B04T1 300# A106 GR.B, SMLS
LINE
12 Pipe Insulation Thickness Corrosion Allowance EC 90mm 1.6mm
13 Fluid State Phase Steam Gas/Vapor Single Phase
14 Sour Service Special Condition N/A N/A
15 Flow Rate Units Min. Nor. Max. kg/h 640 640 640
16 Inlet Pressure Units Min. Nor. Max. kgf/cm²-g 13.34 10.34 9.84
17 Pressure Drop Units Min. Nor. Max. kgf/cm² 12.04 8.71 8.1
18 Inlet Temperature Units Min. Nor. Max. °C 220 220 220
PROCESS 19 Density Units Min. Nor. Max. kg/m³
CONDITIONS 20 Viscosity Units Min. Nor. Max. cP 0.017 0.017 0.017
21 Molecular Weight (MW) Specific Gravity @ Oper. 18.02
22 Spec. Heat Ratio (Cp/Cv) Compressibility (Z) 1.238 0.947
23 Vapor Pressure (Liq.) Cavitation or Flashing kgf/cm²-a N/A
24 Critical Pressure (Liq) Flash (wt%) kgf/cm²-a
25 Design Pressure Min. Max. -1.033 kgf/cm²-g 15.5 kgf/cm²-g
26 Design Temperature Min. Max. 10 °C 260 °C
27 Max.Shutoff DP Solid % 15.5 kgf/cm²
28 Calculated Cv Units Min. Nor. Max. Cv 5. 5.99 6.24
CALCULATED
29 Travel Units Min. Nor. Max. % 31 39 41
RESULTS
30 Noise dBA @1m Units Min. Nor. Max. dBA 84 83 83
31 MFR Model FISHER EZ 56 MFR Model FISHER DVC6200F/SC-AD
32 Body Type Single Seat Globe 57 Signal: Inlet Outlet FF Protocol 0-3.5 kgf/cm2
33 Body Size Trim Size 1.5 in 1 in 58 Increase Signal Valve: DIRECT
34 End Connec.Size & Rating 1.5" 300# RF POSITIONER 59 Cam Characteristic LINEAR
35 Rated Cv Characteristic 16.7 Linear 60 Bypass Gauges N/A YES
36 Body Material WCC Steel 61 Signal Fail. to Valve FC
BODY 37 Bonnet Type Material Style 1 Extension WCC Steel 62 Electric Enclosure Ex ia IIC T5 , NEMA 4X
AND 38 Flow Direct. Flow Act. To Up FTO 63 MFR Model N/A N/A
TRIM 39 Packing Type Material Enviro Seal Graphite ULF 64 Type Power N/A N/A
SOLENOID
40 Lubricator Isolat. Valve N/A N/A 65 When De-Enegr.Valve: N/A
VALVE
41 Guiding No. of Ports Post 1 66 Material Latcher N/A N/A
42 Trim Type Internal Design Standard Unbalanced 67 Electric Enclosure N/A
43 Rated Travel Leak Class 3/4 in ANSI IV 68 MFR Model N/A N/A
44 Plug/ Ball/ Disk Material S41600 SST 69 Type Quantity N/A N/A
45 Seat Material S41600 SST SWITCHES 70 Contacts / Rating N/A
46 Cage Stem Material N/A S31600 SST 71 Switching Position N/A
47 Gasket Material S31600 SST/Graphite 72 Electric Enclosure N/A
48 MFR Model FISHER 667 73 MFR Model FISHER 67CFR
49 Type Diaphragm Spring Return AIR SET 74 Set Pressure 4.2 kgf/cm2-g
50 Size Stroke Time 30i < 5 Sec 75 Filter Gauge 5 Micron min YES
ACTUATOR 51 Air Failure Valve: FC 76 Vol. Tank Booster NO NO
52 Handwheel Location N/A 77 Diffuser Lock-up NO NO
ACCESSORY
53 Mounting Position VERTICAL 78 Fire Safe Fireproof NO NO
54 Spring Range 1.1 - 2.8 kgf/cm2-g 79 Mech. Stop Quick Exa. NO NO
55 Include Pressure (Shutoff) 80 Hydro. Pressure YES
85 Vendor EMERSON 81 Leakage YES
PURCHASE TESTS
86 Manufacturer FISHER 82 Cryogenic N/A
87 Requisition No. R2B-P3-206-02-P-MR-00200 83 NACE Requirement N/A
88 Model No. EZ 84 PWHT Requirement N/A
Notes:

INSTRUMENT SPECIFICATION - CONTROL VALVE


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S49.1 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Fieldbus Device Data Sheet
Tag No.: FV -21108
Fieldbus Tag No.:

Service : MP STM TO DS101

Basic Fieldbus Function Blocks Segment Information


Analog Input Block (AI) 1 Number Device:
1 22
20 Execution (msec)
Discrete Input Block (DI) 4 Number Segment #: DFJB-21053
2 23
15 Execution Time
3 Bias/Gain Station (BG) 0 Execution (msec) 24 LAS Capable: Yes No
Manual Loader (ML) 0 Number 25 Device Current Draw (mA): 19
4
0 Execution (msec) Device Minimum Voltage: 9.
26
Analog Output Block (AO) 1 Number Device Capacitance: 5 nF
5 20 Execution (msec) Polarity-sensitive: Yes No
27
Discrete Output Block (DO) 1 Number Segment Terminator Location:
6 20 Execution (msec)
28
7 Control Selector (CS)
DD Revision: 3
PID,PI,I Controller (PID) 29
8
20 Execution (msec)
CFF Revision: 1.9
Ratio Station (RA) 30
9
P,PD Controller (PD) 0 Number
10 0 Execution (msec)

* Execution time in msec.

Advanced Function Blocks Notes:

11 Device Control (DC)

12 Output Splitter (OS)

13 Signal Characterizer (SC)

14 Lead Lag (LL)

15 Deadtime (DT)

16 Integrator(Totalizer) (IT)

17 Setpoint Ramp Generator (SPG)

18 Input Selector (IS)

19 Arithmetic (AR)

20 Timer (TMR)

21 Analog Alarm (AAL)

INSTRUMENT SPECIFICATION -FOUNDATION FIELDBUS


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S49.2 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Tag Number : FV -21108

1. Steam out condition : F.V/200 degC.

2. In-Built surge protector is provided by vendor.

1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S49.3 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
1 Tag No. FV -21111B
2 Service EA103A DIE TO STOR
3 P&ID No. Line No. R2B-P3-206-02-A-DTI-00108 4"-P-211056-B2A1-EC(ST)
4 Area Classification Ingress Protection CLASS 1 DIV 2 Gr. B ,C&D, T3 NEMA 4X
GENERAL 5 Ambient Temperature: Unit Min. Max. °C 10 48
6 Allowable Sound dBA Tightness Requirement <85 ANSI IV (standard)
7 Available Air Supply Pressure Unit Min. Max. kgf/cm²-g 4.2 8.0
8 Electric Connection Pneum. Connection 1/2” NPT (F) 1/4” NPT (F)
9 Power Failure Position FC
10 Line Size and Schedule Sch. Outlet Line Sch. 4 in STD 4" STD
PIPE
11 Line Class Rating Pipe Material B2A1 300# A106 GR.B, SMLS
LINE
12 Pipe Insulation Thickness Corrosion Allowance EC(ST) 65mm 1.6mm
13 Fluid State Phase Hydrocarbon Liquid Single Phase
14 Sour Service Special Condition N/A N/A
15 Flow Rate Units Min. Nor. Max. m³/h 11.7 28 35.2
16 Inlet Pressure Units Min. Nor. Max. kgf/cm²-g 14.74 11.06 11.29
17 Pressure Drop Units Min. Nor. Max. kgf/cm² 8.208 4.072 4.015
18 Inlet Temperature Units Min. Nor. Max. °C 80 80 80
PROCESS 19 Density Units Min. Nor. Max. kg/m³ 1043 1043 1043
CONDITIONS 20 Viscosity Units Min. Nor. Max. cP 12.409 12.409 12.409
21 Molecular Weight (MW) Specific Gravity @ Oper.
22 Spec. Heat Ratio (Cp/Cv) Compressibility (Z)
23 Vapor Pressure (Liq.) Cavitation or Flashing 0.32 kgf/cm²-a NO
24 Critical Pressure (Liq) Flash (wt%) 25.23 kgf/cm²-a
25 Design Pressure Min. Max. -1.033 kgf/cm²-g 35 kgf/cm²-g
26 Design Temperature Min. Max. 10 °C 280 °C
27 Max.Shutoff DP Solid % 35 kgf/cm²
28 Calculated Cv Units Min. Nor. Max. Cv 4.87 16.7 21.2
CALCULATED
29 Travel Units Min. Nor. Max. % 26 42 46
RESULTS
30 Noise dBA @1m Units Min. Nor. Max. dBA 63 53 53
31 MFR Model FISHER V300 56 MFR Model FISHER DVC6200F/SC-AD
32 Body Type V Ball 57 Signal: Inlet Outlet FF Protocol 4.1 kgf/cm2
33 Body Size Trim Size 2 in Full 58 Increase Signal Valve: DIRECT
34 End Connec.Size & Rating 2" 300# RF POSITIONER 59 Cam Characteristic LINEAR
35 Rated Cv Characteristic 122 EQ% 60 Bypass Gauges N/A YES
36 Body Material WCC Steel 61 Signal Fail. to Valve FC
BODY 37 Bonnet Type Material NONE WCC Steel 62 Electric Enclosure Ex ia IIC T5 , NEMA 4X
AND 38 Flow Direct. Flow Act. To Forward N/A 63 MFR Model N/A N/A
TRIM 39 Packing Type Material ISO Seal Graphite 64 Type Power N/A N/A
SOLENOID
40 Lubricator Isolat. Valve N/A N/A 65 When De-Enegr.Valve: N/A
VALVE
41 Guiding No. of Ports N/A 1 66 Material Latcher N/A N/A
42 Trim Type Internal Design Modified N/A 67 Electric Enclosure N/A
43 Rated Travel Leak Class 90 Deg ANSI IV 68 MFR Model N/A N/A
44 Plug/ Ball/ Disk Material CF3M SST/CRPL 69 Type Quantity N/A N/A
45 Seat Material CF10SMnN SST SWITCHES 70 Contacts / Rating N/A
46 Cage Stem Material N/A S20910 SST 71 Switching Position N/A
47 Gasket Material N/A 72 Electric Enclosure N/A
48 MFR Model FISHER 2052 73 MFR Model FISHER 67CFR
49 Type Diaphragm Spring Return AIR SET 74 Set Pressure 4.2 kgf/cm2-g
50 Size Stroke Time 2 < 8 Sec 75 Filter Gauge 5 Micron min YES
ACTUATOR 51 Air Failure Valve: FC 76 Vol. Tank Booster NO NO
52 Handwheel Location N/A 77 Diffuser Lock-up NO NO
ACCESSORY
53 Mounting Position VERTICAL 78 Fire Safe Fireproof NO NO
54 Spring Range 0.9 - 2.5 kgf/cm2-g 79 Mech. Stop Quick Exa. NO NO
55 Include Pressure (Shutoff) 80 Hydro. Pressure YES
85 Vendor EMERSON 81 Leakage YES
PURCHASE TESTS
86 Manufacturer FISHER 82 Cryogenic N/A
87 Requisition No. R2B-P3-206-02-P-MR-00200 83 NACE Requirement N/A
88 Model No. V300 84 PWHT Requirement N/A
Notes:

INSTRUMENT SPECIFICATION - CONTROL VALVE


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S50.1 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Fieldbus Device Data Sheet
Tag No.: FV -21111B
Fieldbus Tag No.:

Service : EA103A DIE TO STOR

Basic Fieldbus Function Blocks Segment Information


Analog Input Block (AI) 1 Number Device:
1 22
20 Execution (msec)
Discrete Input Block (DI) 4 Number Segment #: DFJB-21076
2 23
15 Execution Time
3 Bias/Gain Station (BG) 0 Execution (msec) 24 LAS Capable: Yes No
Manual Loader (ML) 0 Number 25 Device Current Draw (mA): 19
4
0 Execution (msec) Device Minimum Voltage: 9.
26
Analog Output Block (AO) 1 Number Device Capacitance: 5 nF
5 20 Execution (msec) Polarity-sensitive: Yes No
27
Discrete Output Block (DO) 1 Number Segment Terminator Location:
6 20 Execution (msec)
28
7 Control Selector (CS)
DD Revision: 3
PID,PI,I Controller (PID) 29
8
20 Execution (msec)
CFF Revision: 1.9
Ratio Station (RA) 30
9
P,PD Controller (PD) 0 Number
10 0 Execution (msec)

* Execution time in msec.

Advanced Function Blocks Notes:

11 Device Control (DC)

12 Output Splitter (OS)

13 Signal Characterizer (SC)

14 Lead Lag (LL)

15 Deadtime (DT)

16 Integrator(Totalizer) (IT)

17 Setpoint Ramp Generator (SPG)

18 Input Selector (IS)

19 Arithmetic (AR)

20 Timer (TMR)

21 Analog Alarm (AAL)

INSTRUMENT SPECIFICATION -FOUNDATION FIELDBUS


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S50.2 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Tag Number : FV -21111B

1.Steam out condition : F.V/200 degC

2. In-Built surge protector is provided by vendor.

1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S50.3 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
1 Tag No. FV -21115
2 Service GA106AB LCO TO DS102
3 P&ID No. Line No. R2B-P3-206-02-A-DTI-00123 4"-ACL-211011-B4A1-EC
4 Area Classification Ingress Protection CLASS 1 DIV 2 Gr. B ,C&D, T3 NEMA 4X
GENERAL 5 Ambient Temperature: Unit Min. Max. °C 10 48
6 Allowable Sound dBA Tightness Requirement <85 ANSI IV (standard)
7 Available Air Supply Pressure Unit Min. Max. kgf/cm²-g 4.2 8.0
8 Electric Connection Pneum. Connection 1/2” NPT (F) 1/4” NPT (F)
9 Power Failure Position FO
10 Line Size and Schedule Sch. Outlet Line Sch. 4 in XS 4" XS
PIPE
11 Line Class Rating Pipe Material B4A1 600# A106 GR.B, SMLS
LINE
12 Pipe Insulation Thickness Corrosion Allowance EC 100mm 1.6mm
13 Fluid State Phase Hydrocarbon Liquid Single Phase
14 Sour Service Special Condition N/A N/A
15 Flow Rate Units Min. Nor. Max. m³/h 28 56 61.6
16 Inlet Pressure Units Min. Nor. Max. kgf/cm²-g 17.9 15.9 17.12
17 Pressure Drop Units Min. Nor. Max. kgf/cm² 15.02 13.08 13.08
18 Inlet Temperature Units Min. Nor. Max. °C 216 216 216
PROCESS 19 Density Units Min. Nor. Max. kg/m³ 792 792 792
CONDITIONS 20 Viscosity Units Min. Nor. Max. cP 0.472 0.472 0.472
21 Molecular Weight (MW) Specific Gravity @ Oper.
22 Spec. Heat Ratio (Cp/Cv) Compressibility (Z)
23 Vapor Pressure (Liq.) Cavitation or Flashing 0.3557 kgf/cm²-a NO
24 Critical Pressure (Liq) Flash (wt%) 23.53 kgf/cm²-a
25 Design Pressure Min. Max. -1.033 kgf/cm²-g 20.6 kgf/cm²-g
26 Design Temperature Min. Max. 10 °C 270 °C
27 Max.Shutoff DP Solid % 20.6 kgf/cm²
28 Calculated Cv Units Min. Nor. Max. Cv 7.95 16.9 18.
CALCULATED
29 Travel Units Min. Nor. Max. % 43 61 62
RESULTS
30 Noise dBA @1m Units Min. Nor. Max. dBA 72 75 75
31 MFR Model FISHER ET 56 MFR Model FISHER DVC6200F/SC-AD
32 Body Type Single Seat Globe 57 Signal: Inlet Outlet FF Protocol 0-2.8 kgf/cm2
33 Body Size Trim Size 2 in 2 5/16 in 58 Increase Signal Valve: DIRECT
34 End Connec.Size & Rating 2" 600# RF POSITIONER 59 Cam Characteristic LINEAR
35 Rated Cv Characteristic 59.7 EQ% 60 Bypass Gauges N/A YES
36 Body Material WCC Steel 61 Signal Fail. to Valve FO
BODY 37 Bonnet Type Material Style 1 Extension WCC Steel 62 Electric Enclosure Ex ia IIC T5 , NEMA 4X
AND 38 Flow Direct. Flow Act. To Down FTO 63 MFR Model N/A N/A
TRIM 39 Packing Type Material Enviro Seal Graphite ULF 64 Type Power N/A N/A
SOLENOID
40 Lubricator Isolat. Valve N/A N/A 65 When De-Enegr.Valve: N/A
VALVE
41 Guiding No. of Ports Cage 1 66 Material Latcher N/A N/A
42 Trim Type Internal Design Standard Balanced 67 Electric Enclosure N/A
43 Rated Travel Leak Class 1 1/8 in ANSI IV 68 MFR Model N/A N/A
44 Plug/ Ball/ Disk Material S31600 SST/CoCr-A Seat 69 Type Quantity N/A N/A
45 Seat Material CoCr-A Seat SWITCHES 70 Contacts / Rating N/A
46 Cage Stem Material S31600 SST/ ENCS31600 SST 71 Switching Position N/A
47 Gasket Material S31600 SST/Graphite 72 Electric Enclosure N/A
48 MFR Model FISHER 657 73 MFR Model FISHER 67CFR
49 Type Diaphragm Spring Return AIR SET 74 Set Pressure 4.2 kgf/cm2-g
50 Size Stroke Time 40i < 8 Sec 75 Filter Gauge 5 Micron min YES
ACTUATOR 51 Air Failure Valve: FO 76 Vol. Tank Booster NO NO
52 Handwheel Location N/A 77 Diffuser Lock-up NO NO
ACCESSORY
53 Mounting Position VERTICAL 78 Fire Safe Fireproof NO NO
54 Spring Range 0.4 - 2.0 kgf/cm2-g 79 Mech. Stop Quick Exa. NO NO
55 Include Pressure (Shutoff) 80 Hydro. Pressure YES
85 Vendor EMERSON 81 Leakage YES
PURCHASE TESTS
86 Manufacturer FISHER 82 Cryogenic N/A
87 Requisition No. R2B-P3-206-02-P-MR-00200 83 NACE Requirement N/A
88 Model No. ET 84 PWHT Requirement N/A
Notes:

INSTRUMENT SPECIFICATION - CONTROL VALVE


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S51.1 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Fieldbus Device Data Sheet
Tag No.: FV -21115
Fieldbus Tag No.:

Service : GA106AB LCO TO DS102

Basic Fieldbus Function Blocks Segment Information


Analog Input Block (AI) 1 Number Device:
1 22
20 Execution (msec)
Discrete Input Block (DI) 4 Number Segment #: DFJB-21063
2 23
15 Execution Time
3 Bias/Gain Station (BG) 0 Execution (msec) 24 LAS Capable: Yes No
Manual Loader (ML) 0 Number 25 Device Current Draw (mA): 19
4
0 Execution (msec) Device Minimum Voltage: 9.
26
Analog Output Block (AO) 1 Number Device Capacitance: 5 nF
5 20 Execution (msec) Polarity-sensitive: Yes No
27
Discrete Output Block (DO) 1 Number Segment Terminator Location:
6 20 Execution (msec)
28
7 Control Selector (CS)
DD Revision: 3
PID,PI,I Controller (PID) 29
8
20 Execution (msec)
CFF Revision: 1.9
Ratio Station (RA) 30
9
P,PD Controller (PD) 0 Number
10 0 Execution (msec)

* Execution time in msec.

Advanced Function Blocks Notes:

11 Device Control (DC)

12 Output Splitter (OS)

13 Signal Characterizer (SC)

14 Lead Lag (LL)

15 Deadtime (DT)

16 Integrator(Totalizer) (IT)

17 Setpoint Ramp Generator (SPG)

18 Input Selector (IS)

19 Arithmetic (AR)

20 Timer (TMR)

21 Analog Alarm (AAL)

INSTRUMENT SPECIFICATION -FOUNDATION FIELDBUS


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S51.2 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Tag Number : FV -21115

1. Steam out condition: F.V/200 deg C.

2. In-Built surge protector is provided by vendor.

1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S51.3 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
1 Tag No. FV -21116
2 Service EA105 BFW TO EA108A
3 P&ID No. Line No. R2B-P3-206-02-A-DTI-00110 3"-ACAA-211005-T-D61T1-EC
4 Area Classification Ingress Protection CLASS 1 DIV 2 Gr. B ,C&D, T3 NEMA 4X
GENERAL 5 Ambient Temperature: Unit Min. Max. °C 10 48
6 Allowable Sound dBA Tightness Requirement <85 ANSI IV (standard)
7 Available Air Supply Pressure Unit Min. Max. kgf/cm²-g 4.2 8.0
8 Electric Connection Pneum. Connection 1/2” NPT (F) 1/4” NPT (F)
9 Power Failure Position FC
10 Line Size and Schedule Sch. Outlet Line Sch. 3 in XS 3" XS
PIPE
11 Line Class Rating Pipe Material T-D61T1 600# A106 GR.B, SMLS
LINE
12 Pipe Insulation Thickness Corrosion Allowance EC 65mm 1.6mm
13 Fluid State Phase Water Liquid Single Phase
14 Sour Service Special Condition N/A N/A
15 Flow Rate Units Min. Nor. Max. m³/h 11.9 23.9 28.7
16 Inlet Pressure Units Min. Nor. Max. kgf/cm²-g 67.78 65.51 63.49
17 Pressure Drop Units Min. Nor. Max. kgf/cm² 25.77 20.11 12.42
18 Inlet Temperature Units Min. Nor. Max. °C 180 180 180
PROCESS 19 Density Units Min. Nor. Max. kg/m³ 891 891 891
CONDITIONS 20 Viscosity Units Min. Nor. Max. cP 0.15 0.15 0.15
21 Molecular Weight (MW) Specific Gravity @ Oper.
22 Spec. Heat Ratio (Cp/Cv) Compressibility (Z)
23 Vapor Pressure (Liq.) Cavitation or Flashing 10.13 kgf/cm²-a NO
24 Critical Pressure (Liq) Flash (wt%) 224.99 kgf/cm²-a
25 Design Pressure Min. Max. kgf/cm²-g 77 kgf/cm²-g
26 Design Temperature Min. Max. 10 °C 220 °C
27 Max.Shutoff DP Solid % 77 kgf/cm²
28 Calculated Cv Units Min. Nor. Max. Cv 2.59 5.89 9.04
CALCULATED
29 Travel Units Min. Nor. Max. % 40 61 72
RESULTS
30 Noise dBA @1m Units Min. Nor. Max. dBA 53 54 52
31 MFR Model FISHER EZ 56 MFR Model FISHER DVC6200F/SC-AD
32 Body Type Single Seat Globe 57 Signal: Inlet Outlet FF Protocol 0-2.8 kgf/cm2
33 Body Size Trim Size 1.5 in 1 in 58 Increase Signal Valve: DIRECT
34 End Connec.Size & Rating 1.5" 600# RF POSITIONER 59 Cam Characteristic LINEAR
35 Rated Cv Characteristic 17.3 EQ% 60 Bypass Gauges N/A YES
36 Body Material WCC Steel 61 Signal Fail. to Valve FC
BODY 37 Bonnet Type Material Style 1 Extension WCC Steel 62 Electric Enclosure Ex ia IIC T5 , NEMA 4X
AND 38 Flow Direct. Flow Act. To Up FTO 63 MFR Model N/A N/A
TRIM 39 Packing Type Material ISO Seal PTFE 64 Type Power N/A N/A
SOLENOID
40 Lubricator Isolat. Valve N/A N/A 65 When De-Enegr.Valve: N/A
VALVE
41 Guiding No. of Ports Post 1 66 Material Latcher N/A N/A
42 Trim Type Internal Design Standard Unbalanced 67 Electric Enclosure N/A
43 Rated Travel Leak Class 3/4 in ANSI IV 68 MFR Model N/A N/A
44 Plug/ Ball/ Disk Material S31600 SST/CoCr-A Seat 69 Type Quantity N/A N/A
45 Seat Material S31600 SST/CoCr-A Seat SWITCHES 70 Contacts / Rating N/A
46 Cage Stem Material N/A S31600 SST 71 Switching Position N/A
47 Gasket Material S31600 SST/Graphite 72 Electric Enclosure N/A
48 MFR Model FISHER 667 73 MFR Model FISHER 67CFR
49 Type Diaphragm Spring Return AIR SET 74 Set Pressure 4.2 kgf/cm2-g
50 Size Stroke Time 34i < 5 Sec 75 Filter Gauge 5 Micron min YES
ACTUATOR 51 Air Failure Valve: FC 76 Vol. Tank Booster NO NO
52 Handwheel Location N/A 77 Diffuser Lock-up NO NO
ACCESSORY
53 Mounting Position VERTICAL 78 Fire Safe Fireproof NO NO
54 Spring Range 1.5 - 2.5 kgf/cm2-g 79 Mech. Stop Quick Exa. NO NO
55 Include Pressure (Shutoff) 80 Hydro. Pressure YES
85 Vendor EMERSON 81 Leakage YES
PURCHASE TESTS
86 Manufacturer FISHER 82 Cryogenic N/A
87 Requisition No. R2B-P3-206-02-P-MR-00200 83 NACE Requirement N/A
88 Model No. EZ 84 PWHT Requirement N/A
Notes:

INSTRUMENT SPECIFICATION - CONTROL VALVE


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S52.1 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Fieldbus Device Data Sheet
Tag No.: FV -21116
Fieldbus Tag No.:

Service : EA105 BFW TO EA108A

Basic Fieldbus Function Blocks Segment Information


Analog Input Block (AI) 1 Number Device:
1 22
20 Execution (msec)
Discrete Input Block (DI) 4 Number Segment #: DFJB-21077
2 23
15 Execution Time
3 Bias/Gain Station (BG) 0 Execution (msec) 24 LAS Capable: Yes No
Manual Loader (ML) 0 Number 25 Device Current Draw (mA): 19
4
0 Execution (msec) Device Minimum Voltage: 9.
26
Analog Output Block (AO) 1 Number Device Capacitance: 5 nF
5 20 Execution (msec) Polarity-sensitive: Yes No
27
Discrete Output Block (DO) 1 Number Segment Terminator Location:
6 20 Execution (msec)
28
7 Control Selector (CS)
DD Revision: 3
PID,PI,I Controller (PID) 29
8
20 Execution (msec)
CFF Revision: 1.9
Ratio Station (RA) 30
9
P,PD Controller (PD) 0 Number
10 0 Execution (msec)

* Execution time in msec.

Advanced Function Blocks Notes:

11 Device Control (DC)

12 Output Splitter (OS)

13 Signal Characterizer (SC)

14 Lead Lag (LL)

15 Deadtime (DT)

16 Integrator(Totalizer) (IT)

17 Setpoint Ramp Generator (SPG)

18 Input Selector (IS)

19 Arithmetic (AR)

20 Timer (TMR)

21 Analog Alarm (AAL)

INSTRUMENT SPECIFICATION -FOUNDATION FIELDBUS


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S52.2 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Tag Number : FV -21116

1. In-Built surge protector is provided by vendor.

1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S52.3 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
1 Tag No. FV -21120
2 Service EA105 BFW TO EA108B
3 P&ID No. Line No. R2B-P3-206-02-A-DTI-00111 3"-ACAA-211003-T-D61T1-EC
4 Area Classification Ingress Protection CLASS 1 DIV 2 Gr. B ,C&D, T3 NEMA 4X
GENERAL 5 Ambient Temperature: Unit Min. Max. °C 10 48
6 Allowable Sound dBA Tightness Requirement <85 ANSI IV (standard)
7 Available Air Supply Pressure Unit Min. Max. kgf/cm²-g 4.2 8.0
8 Electric Connection Pneum. Connection 1/2” NPT (F) 1/4” NPT (F)
9 Power Failure Position FC
10 Line Size and Schedule Sch. Outlet Line Sch. 3 in XS 3" XS
PIPE
11 Line Class Rating Pipe Material T-D61T1 600# A106 GR.B, SMLS
LINE
12 Pipe Insulation Thickness Corrosion Allowance EC 65mm 1.6mm
13 Fluid State Phase Water Liquid Single Phase
14 Sour Service Special Condition N/A N/A
15 Flow Rate Units Min. Nor. Max. m³/h 11.9 23.9 28.7
16 Inlet Pressure Units Min. Nor. Max. kgf/cm²-g 67.78 65.51 63.49
17 Pressure Drop Units Min. Nor. Max. kgf/cm² 25.77 20.11 12.42
18 Inlet Temperature Units Min. Nor. Max. °C 180 180 180
PROCESS 19 Density Units Min. Nor. Max. kg/m³ 891 891 891
CONDITIONS 20 Viscosity Units Min. Nor. Max. cP 0.15 0.15 0.15
21 Molecular Weight (MW) Specific Gravity @ Oper.
22 Spec. Heat Ratio (Cp/Cv) Compressibility (Z)
23 Vapor Pressure (Liq.) Cavitation or Flashing 10.13 kgf/cm²-a NO
24 Critical Pressure (Liq) Flash (wt%) 224.99 kgf/cm²-a
25 Design Pressure Min. Max. kgf/cm²-g 77 kgf/cm²-g
26 Design Temperature Min. Max. 10 °C 220 °C
27 Max.Shutoff DP Solid % 77 kgf/cm²
28 Calculated Cv Units Min. Nor. Max. Cv 2.59 5.89 9.04
CALCULATED
29 Travel Units Min. Nor. Max. % 40 61 72
RESULTS
30 Noise dBA @1m Units Min. Nor. Max. dBA 53 54 52
31 MFR Model FISHER EZ 56 MFR Model FISHER DVC6200F/SC-AD
32 Body Type Single Seat Globe 57 Signal: Inlet Outlet FF Protocol 0-2.8 kgf/cm2
33 Body Size Trim Size 1.5 in 1 in 58 Increase Signal Valve: DIRECT
34 End Connec.Size & Rating 1.5" 600# RF POSITIONER 59 Cam Characteristic LINEAR
35 Rated Cv Characteristic 17.3 EQ% 60 Bypass Gauges N/A YES
36 Body Material WCC Steel 61 Signal Fail. to Valve FC
BODY 37 Bonnet Type Material Style 1 Extension WCC Steel 62 Electric Enclosure Ex ia IIC T5 , NEMA 4X
AND 38 Flow Direct. Flow Act. To Up FTO 63 MFR Model N/A N/A
TRIM 39 Packing Type Material ISO Seal PTFE 64 Type Power N/A N/A
SOLENOID
40 Lubricator Isolat. Valve N/A N/A 65 When De-Enegr.Valve: N/A
VALVE
41 Guiding No. of Ports Post 1 66 Material Latcher N/A N/A
42 Trim Type Internal Design Standard Unbalanced 67 Electric Enclosure N/A
43 Rated Travel Leak Class 3/4 in ANSI IV 68 MFR Model N/A N/A
44 Plug/ Ball/ Disk Material S31600 SST/CoCr-A Seat 69 Type Quantity N/A N/A
45 Seat Material S31600 SST/CoCr-A Seat SWITCHES 70 Contacts / Rating N/A
46 Cage Stem Material N/A S31600 SST 71 Switching Position N/A
47 Gasket Material S31600 SST/Graphite 72 Electric Enclosure N/A
48 MFR Model FISHER 667 73 MFR Model FISHER 67CFR
49 Type Diaphragm Spring Return AIR SET 74 Set Pressure 4.2 kgf/cm2-g
50 Size Stroke Time 34i < 5 Sec 75 Filter Gauge 5 Micron min YES
ACTUATOR 51 Air Failure Valve: FC 76 Vol. Tank Booster NO NO
52 Handwheel Location N/A 77 Diffuser Lock-up NO NO
ACCESSORY
53 Mounting Position VERTICAL 78 Fire Safe Fireproof NO NO
54 Spring Range 1.5 - 2.5 kgf/cm2-g 79 Mech. Stop Quick Exa. NO NO
55 Include Pressure (Shutoff) 80 Hydro. Pressure YES
85 Vendor EMERSON 81 Leakage YES
PURCHASE TESTS
86 Manufacturer FISHER 82 Cryogenic N/A
87 Requisition No. R2B-P3-206-02-P-MR-00200 83 NACE Requirement N/A
88 Model No. EZ 84 PWHT Requirement N/A
Notes:

INSTRUMENT SPECIFICATION - CONTROL VALVE


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S53.1 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Fieldbus Device Data Sheet
Tag No.: FV -21120
Fieldbus Tag No.:

Service : EA105 BFW TO EA108B

Basic Fieldbus Function Blocks Segment Information


Analog Input Block (AI) 1 Number Device:
1 22
20 Execution (msec)
Discrete Input Block (DI) 4 Number Segment #: DFJB-21078
2 23
15 Execution Time
3 Bias/Gain Station (BG) 0 Execution (msec) 24 LAS Capable: Yes No
Manual Loader (ML) 0 Number 25 Device Current Draw (mA): 19
4
0 Execution (msec) Device Minimum Voltage: 9.
26
Analog Output Block (AO) 1 Number Device Capacitance: 5 nF
5 20 Execution (msec) Polarity-sensitive: Yes No
27
Discrete Output Block (DO) 1 Number Segment Terminator Location:
6 20 Execution (msec)
28
7 Control Selector (CS)
DD Revision: 3
PID,PI,I Controller (PID) 29
8
20 Execution (msec)
CFF Revision: 1.9
Ratio Station (RA) 30
9
P,PD Controller (PD) 0 Number
10 0 Execution (msec)

* Execution time in msec.

Advanced Function Blocks Notes:

11 Device Control (DC)

12 Output Splitter (OS)

13 Signal Characterizer (SC)

14 Lead Lag (LL)

15 Deadtime (DT)

16 Integrator(Totalizer) (IT)

17 Setpoint Ramp Generator (SPG)

18 Input Selector (IS)

19 Arithmetic (AR)

20 Timer (TMR)

21 Analog Alarm (AAL)

INSTRUMENT SPECIFICATION -FOUNDATION FIELDBUS


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S53.2 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Tag Number : FV -21120

1. In-Built surge protector is provided by vendor.

1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S53.3 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
1 Tag No. FV -21124
2 Service EC101 LCOTO PTRG UNIT
3 P&ID No. Line No. R2B-P3-206-02-A-DTI-00124 3"-ACL-211027-B4A1-PP
4 Area Classification Ingress Protection CLASS 1 DIV 2 Gr. B ,C&D, T3 NEMA 4X
GENERAL 5 Ambient Temperature: Unit Min. Max. °C 10 48
6 Allowable Sound dBA Tightness Requirement <85 ANSI IV (standard)
7 Available Air Supply Pressure Unit Min. Max. kgf/cm²-g 4.2 8
8 Electric Connection Pneum. Connection 1/2” NPT (F) 1/4” NPT (F)
9 Power Failure Position FC
10 Line Size and Schedule Sch. Outlet Line Sch. 3 in XS 3" XS
PIPE
11 Line Class Rating Pipe Material B4A1 600# A106 GR.B, SMLS
LINE
12 Pipe Insulation Thickness Corrosion Allowance N N/A 1.6 mm
13 Fluid State Phase Hydrocarbon Liquid Single Phase
14 Sour Service Special Condition N/A N/A
15 Flow Rate Units Min. Nor. Max. m³/h 21.9 24.09
16 Inlet Pressure Units Min. Nor. Max. kgf/cm²-g 13.53 13.52
17 Pressure Drop Units Min. Nor. Max. kgf/cm² 1.311 1.145
18 Inlet Temperature Units Min. Nor. Max. °C 113 113 113
PROCESS 19 Density Units Min. Nor. Max. kg/m³ 883 883 883
CONDITIONS 20 Viscosity Units Min. Nor. Max. cP 2.333 2.333 2.333
21 Molecular Weight (MW) Specific Gravity @ Oper.
22 Spec. Heat Ratio (Cp/Cv) Compressibility (Z)
23 Vapor Pressure (Liq.) Cavitation or Flashing 1.09 kgf/cm²-a NO
24 Critical Pressure (Liq) Flash (wt%) 30.99 kgf/cm²-a
25 Design Pressure Min. Max. kgf/cm²-g 59.5 kgf/cm²-g
26 Design Temperature Min. Max. 10 °C 220 °C
27 Max.Shutoff DP Solid % 59.5 kgf/cm²
28 Calculated Cv Units Min. Nor. Max. Cv 21.1 25.
CALCULATED
29 Travel Units Min. Nor. Max. % 60 64
RESULTS
30 Noise dBA @1m Units Min. Nor. Max. dBA 50 50
31 MFR Model FISHER EZ 56 MFR Model FISHER DVC6200F/SC-AD
32 Body Type Single Seat Globe 57 Signal: Inlet Outlet FF Protocol 0-3.5 kgf/cm2
33 Body Size Trim Size 2 in 2 in 58 Increase Signal Valve: DIRECT
34 End Connec.Size & Rating 2" 600# RF POSITIONER 59 Cam Characteristic LINEAR
35 Rated Cv Characteristic 53.8 EQ% 60 Bypass Gauges N/A YES
36 Body Material WCC Steel 61 Signal Fail. to Valve FC
BODY 37 Bonnet Type Material Plain WCC Steel 62 Electric Enclosure Ex ia IIC T5 , NEMA 4X
AND 38 Flow Direct. Flow Act. To Up FTO 63 MFR Model N/A N/A
TRIM 39 Packing Type Material ISO Seal PTFE 64 Type Power N/A N/A
SOLENOID
40 Lubricator Isolat. Valve N/A N/A 65 When De-Enegr.Valve: N/A
VALVE
41 Guiding No. of Ports Post 1 66 Material Latcher N/A N/A
42 Trim Type Internal Design Standard Unbalanced 67 Electric Enclosure N/A
43 Rated Travel Leak Class 1 1/8 in ANSI IV 68 MFR Model N/A N/A
44 Plug/ Ball/ Disk Material S41600 SST 69 Type Quantity N/A N/A
45 Seat Material S41600 SST SWITCHES 70 Contacts / Rating N/A
46 Cage Stem Material N/A S31600 SST 71 Switching Position N/A
47 Gasket Material S31600 SST/Graphite 72 Electric Enclosure N/A
48 MFR Model FISHER 667 73 MFR Model FISHER 67CFR
49 Type Diaphragm Spring Return AIR SET 74 Set Pressure 4.2 kgf/cm2-g
50 Size Stroke Time 46i < 8 Sec 75 Filter Gauge 5 Micron min YES
ACTUATOR 51 Air Failure Valve: FC 76 Vol. Tank Booster NO NO
52 Handwheel Location N/A 77 Diffuser Lock-up NO NO
ACCESSORY
53 Mounting Position VERTICAL 78 Fire Safe Fireproof NO NO
54 Spring Range 1.4 - 2.6 kgf/cm2-g 79 Mech. Stop Quick Exa. NO NO
55 Include Pressure (Shutoff) 80 Hydro. Pressure YES
85 Vendor EMERSON 81 Leakage YES
PURCHASE TESTS
86 Manufacturer FISHER 82 Cryogenic N/A
87 Requisition No. R2B-P3-206-02-P-MR-00200 83 NACE Requirement N/A
88 Model No. EZ 84 PWHT Requirement N/A
Notes:

INSTRUMENT SPECIFICATION - CONTROL VALVE


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S54.1 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Fieldbus Device Data Sheet
Tag No.: FV -21124
Fieldbus Tag No.:

Service : EC101 LCOTO PTRG UNIT

Basic Fieldbus Function Blocks Segment Information


Analog Input Block (AI) 1 Number Device:
1 22
20 Execution (msec)
Discrete Input Block (DI) 4 Number Segment #: DFJB-21117
2 23
15 Execution Time
3 Bias/Gain Station (BG) 0 Execution (msec) 24 LAS Capable: Yes No
Manual Loader (ML) 0 Number 25 Device Current Draw (mA): 19
4
0 Execution (msec) Device Minimum Voltage: 9.
26
Analog Output Block (AO) 1 Number Device Capacitance: 5 nF
5 20 Execution (msec) Polarity-sensitive: Yes No
27
Discrete Output Block (DO) 1 Number Segment Terminator Location:
6 20 Execution (msec)
28
7 Control Selector (CS)
DD Revision: 3
PID,PI,I Controller (PID) 29
8
20 Execution (msec)
CFF Revision: 1.9
Ratio Station (RA) 30
9
P,PD Controller (PD) 0 Number
10 0 Execution (msec)

* Execution time in msec.

Advanced Function Blocks Notes:

11 Device Control (DC)

12 Output Splitter (OS)

13 Signal Characterizer (SC)

14 Lead Lag (LL)

15 Deadtime (DT)

16 Integrator(Totalizer) (IT)

17 Setpoint Ramp Generator (SPG)

18 Input Selector (IS)

19 Arithmetic (AR)

20 Timer (TMR)

21 Analog Alarm (AAL)

INSTRUMENT SPECIFICATION -FOUNDATION FIELDBUS


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S54.2 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Tag Number : FV -21124

1. In-Built surge protector is provided by vendor.

1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S54.3 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
1 Tag No. FV -21125
2 Service EA105 BFW TO EA108C
3 P&ID No. Line No. R2B-P3-206-02-A-DTI-00112 3"-ACAA-211007-T-D61T1-EC
4 Area Classification Ingress Protection CLASS 1 DIV 2 Gr. B ,C&D, T3 NEMA 4X
GENERAL 5 Ambient Temperature: Unit Min. Max. °C 10 48
6 Allowable Sound dBA Tightness Requirement <85 ANSI IV (standard)
7 Available Air Supply Pressure Unit Min. Max. kgf/cm²-g 4.2 8.0
8 Electric Connection Pneum. Connection 1/2” NPT (F) 1/4” NPT (F)
9 Power Failure Position FC
10 Line Size and Schedule Sch. Outlet Line Sch. 3 in XS 3" XS
PIPE
11 Line Class Rating Pipe Material T-D61T1 600# A106 GR.B, SMLS
LINE
12 Pipe Insulation Thickness Corrosion Allowance EC 65mm 1.6mm
13 Fluid State Phase Water Liquid Single Phase
14 Sour Service Special Condition N/A N/A
15 Flow Rate Units Min. Nor. Max. m³/h 11.9 23.9 28.7
16 Inlet Pressure Units Min. Nor. Max. kgf/cm²-g 67.78 65.51 63.49
17 Pressure Drop Units Min. Nor. Max. kgf/cm² 25.77 20.11 12.42
18 Inlet Temperature Units Min. Nor. Max. °C 180 180 180
PROCESS 19 Density Units Min. Nor. Max. kg/m³ 891 891 891
CONDITIONS 20 Viscosity Units Min. Nor. Max. cP 0.15 0.15 0.15
21 Molecular Weight (MW) Specific Gravity @ Oper.
22 Spec. Heat Ratio (Cp/Cv) Compressibility (Z)
23 Vapor Pressure (Liq.) Cavitation or Flashing 10.13 kgf/cm²-a NO
24 Critical Pressure (Liq) Flash (wt%) 224.99 kgf/cm²-a
25 Design Pressure Min. Max. kgf/cm²-g 77 kgf/cm²-g
26 Design Temperature Min. Max. 10 °C 220 °C
27 Max.Shutoff DP Solid % 77 kgf/cm²
28 Calculated Cv Units Min. Nor. Max. Cv 2.59 5.89 9.04
CALCULATED
29 Travel Units Min. Nor. Max. % 41 61 72
RESULTS
30 Noise dBA @1m Units Min. Nor. Max. dBA 53 54 52
31 MFR Model FISHER ES 56 MFR Model FISHER DVC6200F/SC-AD
32 Body Type Single Seat Globe 57 Signal: Inlet Outlet FF Protocol 0-2.8 kgf/cm2
33 Body Size Trim Size 1.5 in 1 5/16 in 58 Increase Signal Valve: DIRECT
34 End Connec.Size & Rating 1.5" 600# RF POSITIONER 59 Cam Characteristic LINEAR
35 Rated Cv Characteristic 21 EQ% 60 Bypass Gauges N/A YES
36 Body Material WCC Steel 61 Signal Fail. to Valve FC
BODY 37 Bonnet Type Material Plain WCC Steel 62 Electric Enclosure Ex ia IIC T5 , NEMA 4X
AND 38 Flow Direct. Flow Act. To Up FTO 63 MFR Model N/A N/A
TRIM 39 Packing Type Material ISO Seal PTFE 64 Type Power N/A N/A
SOLENOID
40 Lubricator Isolat. Valve N/A N/A 65 When De-Enegr.Valve: N/A
VALVE
41 Guiding No. of Ports Cage 1 66 Material Latcher N/A N/A
42 Trim Type Internal Design Standard Unbalanced 67 Electric Enclosure N/A
43 Rated Travel Leak Class 3/4 in ANSI IV 68 MFR Model N/A N/A
44 Plug/ Ball/ Disk Material S31600 SST/CoCr-A Seat 69 Type Quantity N/A N/A
45 Seat Material CoCr-A Seat SWITCHES 70 Contacts / Rating N/A
46 Cage Stem Material S31600 SST/ ENCS31600 SST 71 Switching Position N/A
47 Gasket Material S31600 SST/Graphite 72 Electric Enclosure N/A
48 MFR Model FISHER 667 73 MFR Model FISHER 67CFR
49 Type Diaphragm Spring Return AIR SET 74 Set Pressure 4.2 kgf/cm2-g
50 Size Stroke Time 45i < 6 Sec 75 Filter Gauge 5 Micron min YES
ACTUATOR 51 Air Failure Valve: FC 76 Vol. Tank Booster NO NO
52 Handwheel Location N/A 77 Diffuser Lock-up NO NO
ACCESSORY
53 Mounting Position VERTICAL 78 Fire Safe Fireproof NO NO
54 Spring Range 1.5 - 2.5 kgf/cm2-g 79 Mech. Stop Quick Exa. NO NO
55 Include Pressure (Shutoff) 80 Hydro. Pressure YES
85 Vendor EMERSON 81 Leakage YES
PURCHASE TESTS
86 Manufacturer FISHER 82 Cryogenic N/A
87 Requisition No. R2B-P3-206-02-P-MR-00200 83 NACE Requirement N/A
88 Model No. ES 84 PWHT Requirement N/A
Notes:

INSTRUMENT SPECIFICATION - CONTROL VALVE


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S55.1 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Fieldbus Device Data Sheet
Tag No.: FV -21125
Fieldbus Tag No.:

Service : EA105 BFW TO EA108C

Basic Fieldbus Function Blocks Segment Information


Analog Input Block (AI) 1 Number Device:
1 22
20 Execution (msec)
Discrete Input Block (DI) 4 Number Segment #: DFJB-21082
2 23
15 Execution Time
3 Bias/Gain Station (BG) 0 Execution (msec) 24 LAS Capable: Yes No
Manual Loader (ML) 0 Number 25 Device Current Draw (mA): 19
4
0 Execution (msec) Device Minimum Voltage: 9.
26
Analog Output Block (AO) 1 Number Device Capacitance: 5 nF
5 20 Execution (msec) Polarity-sensitive: Yes No
27
Discrete Output Block (DO) 1 Number Segment Terminator Location:
6 20 Execution (msec)
28
7 Control Selector (CS)
DD Revision: 3
PID,PI,I Controller (PID) 29
8
20 Execution (msec)
CFF Revision: 1.9
Ratio Station (RA) 30
9
P,PD Controller (PD) 0 Number
10 0 Execution (msec)

* Execution time in msec.

Advanced Function Blocks Notes:

11 Device Control (DC)

12 Output Splitter (OS)

13 Signal Characterizer (SC)

14 Lead Lag (LL)

15 Deadtime (DT)

16 Integrator(Totalizer) (IT)

17 Setpoint Ramp Generator (SPG)

18 Input Selector (IS)

19 Arithmetic (AR)

20 Timer (TMR)

21 Analog Alarm (AAL)

INSTRUMENT SPECIFICATION -FOUNDATION FIELDBUS


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S55.2 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Tag Number : FV -21125

1. In-Built surge protector is provided by vendor.

1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S55.3 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
1 Tag No. FV -21133
2 Service FG TO DF101
3 P&ID No. Line No. R2B-P3-206-02-A-DTI-00122 6"-GD-211001-T-A03T1-N
4 Area Classification Ingress Protection CLASS 1 DIV 2 Gr. B ,C&D, T3 NEMA 4X
GENERAL 5 Ambient Temperature: Unit Min. Max. °C 10 48
6 Allowable Sound dBA Tightness Requirement <85 ANSI IV (standard)
7 Available Air Supply Pressure Unit Min. Max. kgf/cm²-g 4.2 8.0
8 Electric Connection Pneum. Connection 1/2” NPT (F) 1/4” NPT (F)
9 Power Failure Position FC
10 Line Size and Schedule Sch. Outlet Line Sch. 6 in STD 6" STD
PIPE
11 Line Class Rating Pipe Material T-A03T1 150# A106 GR.B, SMLS
LINE
12 Pipe Insulation Thickness Corrosion Allowance N N/A 1.6mm
13 Fluid State Phase Hydrocarbon Gas/Vapor Single Phase
14 Sour Service Special Condition N/A N/A
15 Flow Rate Units Min. Nor. Max. Nm³/h 2931 2931 3224.1
16 Inlet Pressure Units Min. Nor. Max. kgf/cm²-g 4 4 4.38
17 Pressure Drop Units Min. Nor. Max. kgf/cm² 3.16 3.16 2.661
18 Inlet Temperature Units Min. Nor. Max. °C 38 38 38
PROCESS 19 Density Units Min. Nor. Max. kg/m³
CONDITIONS 20 Viscosity Units Min. Nor. Max. cP 0.01 0.01 0.01
21 Molecular Weight (MW) Specific Gravity @ Oper. 19.32
22 Spec. Heat Ratio (Cp/Cv) Compressibility (Z) 1.24 0.99
23 Vapor Pressure (Liq.) Cavitation or Flashing kgf/cm²-a N/A
24 Critical Pressure (Liq) Flash (wt%) kgf/cm²-a
25 Design Pressure Min. Max. kgf/cm²-g 9 kgf/cm²-g
26 Design Temperature Min. Max. 10 °C 70 °C
27 Max.Shutoff DP Solid % 9 kgf/cm²
28 Calculated Cv Units Min. Nor. Max. Cv 53.4 53.4 54.9
CALCULATED
29 Travel Units Min. Nor. Max. % 45 45 46
RESULTS
30 Noise dBA @1m Units Min. Nor. Max. dBA 72 72 70
31 MFR Model FISHER ET 56 MFR Model FISHER DVC6200F/SC-AD
32 Body Type Single Seat Globe 57 Signal: Inlet Outlet FF Protocol 0-2.8 kgf/cm2
33 Body Size Trim Size 3 in 2 5/16 in 58 Increase Signal Valve: DIRECT
34 End Connec.Size & Rating 3" 300# RF POSITIONER 59 Cam Characteristic LINEAR
35 Rated Cv Characteristic 103 Linear 60 Bypass Gauges N/A YES
36 Body Material WCC Steel 61 Signal Fail. to Valve FC
BODY 37 Bonnet Type Material Plain WCC Steel 62 Electric Enclosure Ex ia IIC T5 , NEMA 4X
AND 38 Flow Direct. Flow Act. To Up FTC 63 MFR Model N/A N/A
TRIM 39 Packing Type Material ISO Seal PTFE 64 Type Power N/A N/A
SOLENOID
40 Lubricator Isolat. Valve N/A N/A 65 When De-Enegr.Valve: N/A
VALVE
41 Guiding No. of Ports Cage 1 66 Material Latcher N/A N/A
42 Trim Type Internal Design Whisper I Balanced 67 Electric Enclosure N/A
43 Rated Travel Leak Class 1 1/8 in ANSI IV 68 MFR Model N/A N/A
44 Plug/ Ball/ Disk Material S41600 SST 69 Type Quantity N/A N/A
45 Seat Material S41600 SST SWITCHES 70 Contacts / Rating N/A
46 Cage Stem Material CB7Cu-1 SST S31600 SST 71 Switching Position N/A
47 Gasket Material S31600 SST/Graphite 72 Electric Enclosure N/A
48 MFR Model FISHER 667 73 MFR Model FISHER 67CFR
49 Type Diaphragm Spring Return AIR SET 74 Set Pressure 4.2 kgf/cm2-g
50 Size Stroke Time 40i < 8 Sec 75 Filter Gauge 5 Micron min YES
ACTUATOR 51 Air Failure Valve: FC 76 Vol. Tank Booster NO NO
52 Handwheel Location Side Mounted 77 Diffuser Lock-up NO NO
ACCESSORY
53 Mounting Position VERTICAL 78 Fire Safe Fireproof NO NO
54 Spring Range 0.4 - 2.0 kgf/cm2-g 79 Mech. Stop Quick Exa. NO NO
55 Include Pressure (Shutoff) 80 Hydro. Pressure YES
85 Vendor EMERSON 81 Leakage YES
PURCHASE TESTS
86 Manufacturer FISHER 82 Cryogenic N/A
87 Requisition No. R2B-P3-206-02-P-MR-00200 83 NACE Requirement N/A
88 Model No. ET 84 PWHT Requirement N/A
Notes:

INSTRUMENT SPECIFICATION - CONTROL VALVE


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S56.1 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Fieldbus Device Data Sheet
Tag No.: FV -21133
Fieldbus Tag No.:

Service : FG TO DF101

Basic Fieldbus Function Blocks Segment Information


Analog Input Block (AI) 1 Number Device:
1 22
20 Execution (msec)
Discrete Input Block (DI) 4 Number Segment #: DFJB-21065
2 23
15 Execution Time
3 Bias/Gain Station (BG) 0 Execution (msec) 24 LAS Capable: Yes No
Manual Loader (ML) 0 Number 25 Device Current Draw (mA): 19
4
0 Execution (msec) Device Minimum Voltage: 9.
26
Analog Output Block (AO) 1 Number Device Capacitance: 5 nF
5 20 Execution (msec) Polarity-sensitive: Yes No
27
Discrete Output Block (DO) 1 Number Segment Terminator Location:
6 20 Execution (msec)
28
7 Control Selector (CS)
DD Revision: 3
PID,PI,I Controller (PID) 29
8
20 Execution (msec)
CFF Revision: 1.9
Ratio Station (RA) 30
9
P,PD Controller (PD) 0 Number
10 0 Execution (msec)

* Execution time in msec.

Advanced Function Blocks Notes:

11 Device Control (DC)

12 Output Splitter (OS)

13 Signal Characterizer (SC)

14 Lead Lag (LL)

15 Deadtime (DT)

16 Integrator(Totalizer) (IT)

17 Setpoint Ramp Generator (SPG)

18 Input Selector (IS)

19 Arithmetic (AR)

20 Timer (TMR)

21 Analog Alarm (AAL)

INSTRUMENT SPECIFICATION -FOUNDATION FIELDBUS


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S56.2 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Tag Number : FV -21133

1. Valve will normally be in the closed position. Valve opening will be intermittent and generally short-term.

2. In-Built surge protector is provided by vendor.

1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S56.3 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
1 Tag No. FV -21134
2 Service MP STM TO DS102
3 P&ID No. Line No. R2B-P3-206-02-A-DTI-00122 4"-VM-211021-T-B04T1-EC
4 Area Classification Ingress Protection CLASS 1 DIV 2 Gr. B ,C&D, T3 NEMA 4X
GENERAL 5 Ambient Temperature: Unit Min. Max. °C 10 48
6 Allowable Sound dBA Tightness Requirement <85 ANSI IV (standard)
7 Available Air Supply Pressure Unit Min. Max. kgf/cm²-g 4.2 8.0
8 Electric Connection Pneum. Connection 1/2” NPT (F) 1/4” NPT (F)
9 Power Failure Position FC
10 Line Size and Schedule Sch. Outlet Line Sch. 4 in STD 6" STD
PIPE
11 Line Class Rating Pipe Material T-B04T1 300# A106 GR.B, SMLS
LINE
12 Pipe Insulation Thickness Corrosion Allowance EC 100mm 1.6mm
13 Fluid State Phase Steam Gas/Vapor Single Phase
14 Sour Service Special Condition N/A N/A
15 Flow Rate Units Min. Nor. Max. kg/h 1159 2318 2550
16 Inlet Pressure Units Min. Nor. Max. kgf/cm²-g 13.38 10.3 9.786
17 Pressure Drop Units Min. Nor. Max. kgf/cm² 12.07 8.7 7.734
18 Inlet Temperature Units Min. Nor. Max. °C 220 220 220
PROCESS 19 Density Units Min. Nor. Max. kg/m³
CONDITIONS 20 Viscosity Units Min. Nor. Max. cP 0.017 0.017 0.017
21 Molecular Weight (MW) Specific Gravity @ Oper. 18.02
22 Spec. Heat Ratio (Cp/Cv) Compressibility (Z) 1.238 0.947
23 Vapor Pressure (Liq.) Cavitation or Flashing kgf/cm²-a N/A
24 Critical Pressure (Liq) Flash (wt%) kgf/cm²-a
25 Design Pressure Min. Max. -1.033 kgf/cm²-g 15.5 kgf/cm²-g
26 Design Temperature Min. Max. 10 °C 260 °C
27 Max.Shutoff DP Solid % 15.5 kgf/cm²
28 Calculated Cv Units Min. Nor. Max. Cv 11.3 28.9 33.3
CALCULATED
29 Travel Units Min. Nor. Max. % 25 57 65
RESULTS
30 Noise dBA @1m Units Min. Nor. Max. dBA 75 74 72
31 MFR Model FISHER ES 56 MFR Model FISHER DVC6200F/SC-AD
32 Body Type Single Seat Globe 57 Signal: Inlet Outlet FF Protocol 0-2.8 kgf/cm2
33 Body Size Trim Size 3 in 2 5/16 in 58 Increase Signal Valve: DIRECT
34 End Connec.Size & Rating 3" 300# RF POSITIONER 59 Cam Characteristic LINEAR
35 Rated Cv Characteristic 51.93 Linear 60 Bypass Gauges N/A YES
36 Body Material WCC Steel 61 Signal Fail. to Valve FC
BODY 37 Bonnet Type Material Style 1 Extension WCC Steel 62 Electric Enclosure Ex ia IIC T5 , NEMA 4X
AND 38 Flow Direct. Flow Act. To Up FTO 63 MFR Model N/A N/A
TRIM 39 Packing Type Material Enviro Seal Graphite ULF 64 Type Power N/A N/A
SOLENOID
40 Lubricator Isolat. Valve N/A N/A 65 When De-Enegr.Valve: N/A
VALVE
41 Guiding No. of Ports Cage 1 66 Material Latcher N/A N/A
42 Trim Type Internal Design Whisper III Unbalanced 67 Electric Enclosure N/A
43 Rated Travel Leak Class 1 in ANSI IV 68 MFR Model N/A N/A
44 Plug/ Ball/ Disk Material S41600 SST 69 Type Quantity N/A N/A
45 Seat Material S41600 SST SWITCHES 70 Contacts / Rating N/A
46 Cage Stem Material CB7Cu-1 SST S31600 SST 71 Switching Position N/A
47 Gasket Material S31600 SST/Graphite 72 Electric Enclosure N/A
48 MFR Model FISHER 667 73 MFR Model FISHER 67CFR
49 Type Diaphragm Spring Return AIR SET 74 Set Pressure 4.2 kgf/cm2-g
50 Size Stroke Time 46i < 8 Sec 75 Filter Gauge 5 Micron min YES
ACTUATOR 51 Air Failure Valve: FC 76 Vol. Tank Booster NO NO
52 Handwheel Location N/A 77 Diffuser Lock-up NO NO
ACCESSORY
53 Mounting Position VERTICAL 78 Fire Safe Fireproof NO NO
54 Spring Range 1 - 2 kgf/cm2-g 79 Mech. Stop Quick Exa. NO NO
55 Include Pressure (Shutoff) 80 Hydro. Pressure YES
85 Vendor EMERSON 81 Leakage YES
PURCHASE TESTS
86 Manufacturer FISHER 82 Cryogenic N/A
87 Requisition No. R2B-P3-206-02-P-MR-00200 83 NACE Requirement N/A
88 Model No. ES 84 PWHT Requirement N/A
Notes:

INSTRUMENT SPECIFICATION - CONTROL VALVE


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S57.1 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Fieldbus Device Data Sheet
Tag No.: FV -21134
Fieldbus Tag No.:

Service : MP STM TO DS102

Basic Fieldbus Function Blocks Segment Information


Analog Input Block (AI) 1 Number Device:
1 22
20 Execution (msec)
Discrete Input Block (DI) 4 Number Segment #: DFJB-21061
2 23
15 Execution Time
3 Bias/Gain Station (BG) 0 Execution (msec) 24 LAS Capable: Yes No
Manual Loader (ML) 0 Number 25 Device Current Draw (mA): 19
4
0 Execution (msec) Device Minimum Voltage: 9.
26
Analog Output Block (AO) 1 Number Device Capacitance: 5 nF
5 20 Execution (msec) Polarity-sensitive: Yes No
27
Discrete Output Block (DO) 1 Number Segment Terminator Location:
6 20 Execution (msec)
28
7 Control Selector (CS)
DD Revision: 3
PID,PI,I Controller (PID) 29
8
20 Execution (msec)
CFF Revision: 1.9
Ratio Station (RA) 30
9
P,PD Controller (PD) 0 Number
10 0 Execution (msec)

* Execution time in msec.

Advanced Function Blocks Notes:

11 Device Control (DC)

12 Output Splitter (OS)

13 Signal Characterizer (SC)

14 Lead Lag (LL)

15 Deadtime (DT)

16 Integrator(Totalizer) (IT)

17 Setpoint Ramp Generator (SPG)

18 Input Selector (IS)

19 Arithmetic (AR)

20 Timer (TMR)

21 Analog Alarm (AAL)

INSTRUMENT SPECIFICATION -FOUNDATION FIELDBUS


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S57.2 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Tag Number : FV -21134

1. In-Built surge protector is provided by vendor.

1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S57.3 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
1 Tag No. FV -21139
2 Service GA108AB WS TO EC102
3 P&ID No. Line No. R2B-P3-206-02-A-DTI-00126 4"-AAM-211005-B1A2-NACE-N
4 Area Classification Ingress Protection CLASS 1 DIV 2 Gr. B ,C&D, T3 NEMA 4X
GENERAL 5 Ambient Temperature: Unit Min. Max. °C 10 48
6 Allowable Sound dBA Tightness Requirement <85 ANSI IV (standard)
7 Available Air Supply Pressure Unit Min. Max. kgf/cm²-g 4.2 8.0
8 Electric Connection Pneum. Connection 1/2” NPT (F) 1/4” NPT (F)
9 Power Failure Position FC
10 Line Size and Schedule Sch. Outlet Line Sch. 4 in STD 4" STD
PIPE
11 Line Class Rating Pipe Material B1A2-NACE 150# A106 GR.B, SMLS
LINE
12 Pipe Insulation Thickness Corrosion Allowance N N/A 3.2mm
13 Fluid State Phase Water Liquid Single Phase
14 Sour Service Special Condition YES N/A
15 Flow Rate Units Min. Nor. Max. m³/h 3.1 5.5 6.1
16 Inlet Pressure Units Min. Nor. Max. kgf/cm²-g 8.739 8.7 8.671
17 Pressure Drop Units Min. Nor. Max. kgf/cm² 6.6 5.07 4.64
18 Inlet Temperature Units Min. Nor. Max. °C 38 38 38
PROCESS 19 Density Units Min. Nor. Max. kg/m³ 978 978 978
CONDITIONS 20 Viscosity Units Min. Nor. Max. cP 0.675 0.675 0.675
21 Molecular Weight (MW) Specific Gravity @ Oper.
22 Spec. Heat Ratio (Cp/Cv) Compressibility (Z)
23 Vapor Pressure (Liq.) Cavitation or Flashing 0.56 kgf/cm²-a NO
24 Critical Pressure (Liq) Flash (wt%) 224.99 kgf/cm²-a
25 Design Pressure Min. Max. kgf/cm²-g 13 kgf/cm²-g
26 Design Temperature Min. Max. 10 °C 120 °C
27 Max.Shutoff DP Solid % 13 kgf/cm²
28 Calculated Cv Units Min. Nor. Max. Cv 1.39 2.82 3.27
CALCULATED
29 Travel Units Min. Nor. Max. % 57 77 81
RESULTS
30 Noise dBA @1m Units Min. Nor. Max. dBA 60 58 56
31 MFR Model FISHER EZ 56 MFR Model FISHER DVC6200F/SC-AD
32 Body Type Single Seat Globe 57 Signal: Inlet Outlet FF Protocol 0-2.8 kgf/cm2
33 Body Size Trim Size 2 in 1/2 in 58 Increase Signal Valve: DIRECT
34 End Connec.Size & Rating 2" 300# RF POSITIONER 59 Cam Characteristic LINEAR
35 Rated Cv Characteristic 5.18 EQ% 60 Bypass Gauges N/A YES
36 Body Material WCC Steel 61 Signal Fail. to Valve FC
BODY 37 Bonnet Type Material Plain WCC Steel 62 Electric Enclosure Ex ia IIC T5 , NEMA 4X
AND 38 Flow Direct. Flow Act. To Up FTO 63 MFR Model N/A N/A
TRIM 39 Packing Type Material ISO Seal PTFE 64 Type Power N/A N/A
SOLENOID
40 Lubricator Isolat. Valve N/A N/A 65 When De-Enegr.Valve: N/A
VALVE
41 Guiding No. of Ports Post 1 66 Material Latcher N/A N/A
42 Trim Type Internal Design Micro Form Unbalanced 67 Electric Enclosure N/A
43 Rated Travel Leak Class 3/4 in ANSI IV 68 MFR Model N/A N/A
44 Plug/ Ball/ Disk Material S31600 SST/CoCr-A Seat 69 Type Quantity N/A N/A
45 Seat Material R30006 Cobalt Alloy SWITCHES 70 Contacts / Rating N/A
46 Cage Stem Material N/A S20910 SST 71 Switching Position N/A
47 Gasket Material S31600 SST/Graphite 72 Electric Enclosure N/A
48 MFR Model FISHER 667 73 MFR Model FISHER 67CFR
49 Type Diaphragm Spring Return AIR SET 74 Set Pressure 4.2 kgf/cm2-g
50 Size Stroke Time 40i < 8 Sec 75 Filter Gauge 5 Micron min YES
ACTUATOR 51 Air Failure Valve: FC 76 Vol. Tank Booster NO NO
52 Handwheel Location N/A 77 Diffuser Lock-up NO NO
ACCESSORY
53 Mounting Position VERTICAL 78 Fire Safe Fireproof NO NO
54 Spring Range 0.8 - 2.5 kgf/cm2-g 79 Mech. Stop Quick Exa. NO NO
55 Include Pressure (Shutoff) 80 Hydro. Pressure YES
85 Vendor EMERSON 81 Leakage YES
PURCHASE TESTS
86 Manufacturer FISHER 82 Cryogenic N/A
87 Requisition No. R2B-P3-206-02-P-MR-00200 83 NACE Requirement NACE-0103
88 Model No. EZ 84 PWHT Requirement YES
Notes:

INSTRUMENT SPECIFICATION - CONTROL VALVE


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S58.1 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Fieldbus Device Data Sheet
Tag No.: FV -21139
Fieldbus Tag No.:

Service : GA108AB WS TO EC102

Basic Fieldbus Function Blocks Segment Information


Analog Input Block (AI) 1 Number Device:
1 22
20 Execution (msec)
Discrete Input Block (DI) 4 Number Segment #: DFJB-21075
2 23
15 Execution Time
3 Bias/Gain Station (BG) 0 Execution (msec) 24 LAS Capable: Yes No
Manual Loader (ML) 0 Number 25 Device Current Draw (mA): 19
4
0 Execution (msec) Device Minimum Voltage: 9.
26
Analog Output Block (AO) 1 Number Device Capacitance: 5 nF
5 20 Execution (msec) Polarity-sensitive: Yes No
27
Discrete Output Block (DO) 1 Number Segment Terminator Location:
6 20 Execution (msec)
28
7 Control Selector (CS)
DD Revision: 3
PID,PI,I Controller (PID) 29
8
20 Execution (msec)
CFF Revision: 1.9
Ratio Station (RA) 30
9
P,PD Controller (PD) 0 Number
10 0 Execution (msec)

* Execution time in msec.

Advanced Function Blocks Notes:

11 Device Control (DC)

12 Output Splitter (OS)

13 Signal Characterizer (SC)

14 Lead Lag (LL)

15 Deadtime (DT)

16 Integrator(Totalizer) (IT)

17 Setpoint Ramp Generator (SPG)

18 Input Selector (IS)

19 Arithmetic (AR)

20 Timer (TMR)

21 Analog Alarm (AAL)

INSTRUMENT SPECIFICATION -FOUNDATION FIELDBUS


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S58.2 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Tag Number : FV -21139

1. Special PWHT Required .

2. In-Built surge protector is provided by vendor.

1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S58.3 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
1 Tag No. FV -21142
2 Service GA110AB GSL TO DA201
3 P&ID No. Line No. R2B-P3-206-02-A-DTI-00131 8"-P-211106-B2A2-NACE-N
4 Area Classification Ingress Protection CLASS 1 DIV 2 Gr. B ,C&D, T3 NEMA 4X
GENERAL 5 Ambient Temperature: Unit Min. Max. °C 10 48
6 Allowable Sound dBA Tightness Requirement <85 ANSI IV (standard)
7 Available Air Supply Pressure Unit Min. Max. kgf/cm²-g 4.2 8.0
8 Electric Connection Pneum. Connection 1/2” NPT (F) 1/4” NPT (F)
9 Power Failure Position FC
10 Line Size and Schedule Sch. Outlet Line Sch. 8 in XS 8" XS
PIPE
11 Line Class Rating Pipe Material B2A2-NACE 300# A106 GR.B, SMLS
LINE
12 Pipe Insulation Thickness Corrosion Allowance N N/A 3.2mm
13 Fluid State Phase Hydrocarbon Liquid Single Phase
14 Sour Service Special Condition YES N/A
15 Flow Rate Units Min. Nor. Max. m³/h 192.5 385 423.5
16 Inlet Pressure Units Min. Nor. Max. kgf/cm²-g 22.56 18.7 22.82
17 Pressure Drop Units Min. Nor. Max. kgf/cm² 6.88 0.7 0.7
18 Inlet Temperature Units Min. Nor. Max. °C 39 39 39
PROCESS 19 Density Units Min. Nor. Max. kg/m³ 738 738 738
CONDITIONS 20 Viscosity Units Min. Nor. Max. cP 0.532 0.532 0.532
21 Molecular Weight (MW) Specific Gravity @ Oper.
22 Spec. Heat Ratio (Cp/Cv) Compressibility (Z)
23 Vapor Pressure (Liq.) Cavitation or Flashing 1.82 kgf/cm²-a NO
24 Critical Pressure (Liq) Flash (wt%) 36.16 kgf/cm²-a
25 Design Pressure Min. Max. kgf/cm²-g 25.5 kgf/cm²-g
26 Design Temperature Min. Max. 10 °C 120 °C
27 Max.Shutoff DP Solid % 25.5 kgf/cm²
28 Calculated Cv Units Min. Nor. Max. Cv 73.6 462 508
CALCULATED
29 Travel Units Min. Nor. Max. % 23 60 62
RESULTS
30 Noise dBA @1m Units Min. Nor. Max. dBA 64 52 53
31 MFR Model FISHER ET 56 MFR Model FISHER DVC6200F/SC-AD
32 Body Type Single Seat Globe 57 Signal: Inlet Outlet FF Protocol 0-2.8 kgf/cm2
33 Body Size Trim Size 8 in 8 in 58 Increase Signal Valve: DIRECT
34 End Connec.Size & Rating 8" 300# RF POSITIONER 59 Cam Characteristic LINEAR
35 Rated Cv Characteristic 818 EQ% 60 Bypass Gauges N/A YES
36 Body Material WCC Steel 61 Signal Fail. to Valve FC
BODY 37 Bonnet Type Material Plain WCC Steel 62 Electric Enclosure Ex ia IIC T5 , NEMA 4X
AND 38 Flow Direct. Flow Act. To Down FTO 63 MFR Model N/A N/A
TRIM 39 Packing Type Material ISO Seal PTFE 64 Type Power N/A N/A
SOLENOID
40 Lubricator Isolat. Valve N/A N/A 65 When De-Enegr.Valve: N/A
VALVE
41 Guiding No. of Ports Cage 1 66 Material Latcher N/A N/A
42 Trim Type Internal Design Standard Balanced 67 Electric Enclosure N/A
43 Rated Travel Leak Class 3 in ANSI IV 68 MFR Model N/A N/A
44 Plug/ Ball/ Disk Material S31600 SST/CoCr-A Seat 69 Type Quantity N/A N/A
45 Seat Material R30006 Cobalt Alloy SWITCHES 70 Contacts / Rating N/A
46 Cage Stem Material S31600 SST/ ENCS20910 SST 71 Switching Position N/A
47 Gasket Material S31600 SST/Graphite 72 Electric Enclosure N/A
48 MFR Model FISHER 667-4 73 MFR Model FISHER 67CFR
49 Type Diaphragm Spring Return AIR SET 74 Set Pressure 4.2 kgf/cm2-g
50 Size Stroke Time 70i < 25 Sec 75 Filter Gauge 5 Micron min YES
ACTUATOR 51 Air Failure Valve: FC 76 Vol. Tank Booster NO NO
52 Handwheel Location N/A 77 Diffuser Lock-up NO NO
ACCESSORY
53 Mounting Position VERTICAL 78 Fire Safe Fireproof NO NO
54 Spring Range 1 - 1.8 kgf/cm2-g 79 Mech. Stop Quick Exa. NO NO
55 Include Pressure (Shutoff) 80 Hydro. Pressure YES
85 Vendor EMERSON 81 Leakage YES
PURCHASE TESTS
86 Manufacturer FISHER 82 Cryogenic N/A
87 Requisition No. R2B-P3-206-02-P-MR-00200 83 NACE Requirement NACE-0103
88 Model No. ET 84 PWHT Requirement YES
Notes:

INSTRUMENT SPECIFICATION - CONTROL VALVE


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S59.1 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Fieldbus Device Data Sheet
Tag No.: FV -21142
Fieldbus Tag No.:

Service : GA110AB GSL TO DA201

Basic Fieldbus Function Blocks Segment Information


Analog Input Block (AI) 1 Number Device:
1 22
20 Execution (msec)
Discrete Input Block (DI) 4 Number Segment #: DFJB-21087
2 23
15 Execution Time
3 Bias/Gain Station (BG) 0 Execution (msec) 24 LAS Capable: Yes No
Manual Loader (ML) 0 Number 25 Device Current Draw (mA): 19
4
0 Execution (msec) Device Minimum Voltage: 9.
26
Analog Output Block (AO) 1 Number Device Capacitance: 5 nF
5 20 Execution (msec) Polarity-sensitive: Yes No
27
Discrete Output Block (DO) 1 Number Segment Terminator Location:
6 20 Execution (msec)
28
7 Control Selector (CS)
DD Revision: 3
PID,PI,I Controller (PID) 29
8
20 Execution (msec)
CFF Revision: 1.9
Ratio Station (RA) 30
9
P,PD Controller (PD) 0 Number
10 0 Execution (msec)

* Execution time in msec.

Advanced Function Blocks Notes:

11 Device Control (DC)

12 Output Splitter (OS)

13 Signal Characterizer (SC)

14 Lead Lag (LL)

15 Deadtime (DT)

16 Integrator(Totalizer) (IT)

17 Setpoint Ramp Generator (SPG)

18 Input Selector (IS)

19 Arithmetic (AR)

20 Timer (TMR)

21 Analog Alarm (AAL)

INSTRUMENT SPECIFICATION -FOUNDATION FIELDBUS


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S59.2 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Tag Number : FV -21142

1. Special PWHT Required .

2. In-Built surge protector is provided by vendor.

1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S59.3 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
1 Tag No. FV -21143
2 Service GA110AB GSLTO FA102
3 P&ID No. Line No. R2B-P3-206-02-A-DTI-00131 6"-P-211108-B2A2-NACE-N
4 Area Classification Ingress Protection CLASS 1 DIV 2 Gr. B ,C&D, T3 NEMA 4X
GENERAL 5 Ambient Temperature: Unit Min. Max. °C 10 48
6 Allowable Sound dBA Tightness Requirement <85 ANSI IV (standard)
7 Available Air Supply Pressure Unit Min. Max. kgf/cm²-g 4.2 8.0
8 Electric Connection Pneum. Connection 1/2” NPT (F) 1/4” NPT (F)
9 Power Failure Position FO
10 Line Size and Schedule Sch. Outlet Line Sch. 6 in XS 6" XS
PIPE
11 Line Class Rating Pipe Material B2A2-NACE 300# A106 GR.B, SMLS
LINE
12 Pipe Insulation Thickness Corrosion Allowance N N/A 3.2mm
13 Fluid State Phase Hydrocarbon Liquid Single Phase
14 Sour Service Special Condition YES N/A
15 Flow Rate Units Min. Nor. Max. m³/h 70.41 140.82 154.9
16 Inlet Pressure Units Min. Nor. Max. kgf/cm²-g 23.91 23.91 23.91
17 Pressure Drop Units Min. Nor. Max. kgf/cm² 18.62 18.62 18.62
18 Inlet Temperature Units Min. Nor. Max. °C 39 39 39
PROCESS 19 Density Units Min. Nor. Max. kg/m³ 738 738 738
CONDITIONS 20 Viscosity Units Min. Nor. Max. cP 0.532 0.532 0.532
21 Molecular Weight (MW) Specific Gravity @ Oper.
22 Spec. Heat Ratio (Cp/Cv) Compressibility (Z)
23 Vapor Pressure (Liq.) Cavitation or Flashing 1.82 kgf/cm²-a NO
24 Critical Pressure (Liq) Flash (wt%) 36.16 kgf/cm²-a
25 Design Pressure Min. Max. kgf/cm²-g 25.5 kgf/cm²-g
26 Design Temperature Min. Max. 10 °C 120 °C
27 Max.Shutoff DP Solid % 25.5 kgf/cm²
28 Calculated Cv Units Min. Nor. Max. Cv 16.8 33.9 37.3
CALCULATED
29 Travel Units Min. Nor. Max. % 60 74 77
RESULTS
30 Noise dBA @1m Units Min. Nor. Max. dBA 79 82 82
31 MFR Model FISHER ET 56 MFR Model FISHER DVC6200F/SC-AD
32 Body Type Single Seat Globe 57 Signal: Inlet Outlet FF Protocol 0-2.8 kgf/cm2
33 Body Size Trim Size 3 in 2 5/16 in 58 Increase Signal Valve: DIRECT
34 End Connec.Size & Rating 3" 300# RF POSITIONER 59 Cam Characteristic LINEAR
35 Rated Cv Characteristic 70.7 EQ% 60 Bypass Gauges N/A YES
36 Body Material WCC Steel 61 Signal Fail. to Valve FO
BODY 37 Bonnet Type Material Plain WCC Steel 62 Electric Enclosure Ex ia IIC T5 , NEMA 4X
AND 38 Flow Direct. Flow Act. To Down FTO 63 MFR Model N/A N/A
TRIM 39 Packing Type Material ISO Seal PTFE 64 Type Power N/A N/A
SOLENOID
40 Lubricator Isolat. Valve N/A N/A 65 When De-Enegr.Valve: N/A
VALVE
41 Guiding No. of Ports Cage 1 66 Material Latcher N/A N/A
42 Trim Type Internal Design Standard Balanced 67 Electric Enclosure N/A
43 Rated Travel Leak Class 1 1/8 in ANSI IV 68 MFR Model N/A N/A
44 Plug/ Ball/ Disk Material S31600 SST/CoCr-A Seat 69 Type Quantity N/A N/A
45 Seat Material R30006 Cobalt Alloy SWITCHES 70 Contacts / Rating N/A
46 Cage Stem Material S31600 SST/ ENCS20910 SST 71 Switching Position N/A
47 Gasket Material S31600 SST/Graphite 72 Electric Enclosure N/A
48 MFR Model FISHER 657 73 MFR Model FISHER 67CFR
49 Type Diaphragm Spring Return AIR SET 74 Set Pressure 4.2 kgf/cm2-g
50 Size Stroke Time 40i < 8 Sec 75 Filter Gauge 5 Micron min YES
ACTUATOR 51 Air Failure Valve: FO 76 Vol. Tank Booster NO NO
52 Handwheel Location N/A 77 Diffuser Lock-up NO NO
ACCESSORY
53 Mounting Position VERTICAL 78 Fire Safe Fireproof NO NO
54 Spring Range 0.4 - 2.0 kgf/cm2-g 79 Mech. Stop Quick Exa. NO NO
55 Include Pressure (Shutoff) 80 Hydro. Pressure YES
85 Vendor EMERSON 81 Leakage YES
PURCHASE TESTS
86 Manufacturer FISHER 82 Cryogenic N/A
87 Requisition No. R2B-P3-206-02-P-MR-00200 83 NACE Requirement NACE-0103
88 Model No. ET 84 PWHT Requirement YES
Notes:

INSTRUMENT SPECIFICATION - CONTROL VALVE


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S60.1 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Fieldbus Device Data Sheet
Tag No.: FV -21143
Fieldbus Tag No.:

Service : GA110AB GSLTO FA102

Basic Fieldbus Function Blocks Segment Information


Analog Input Block (AI) 1 Number Device:
1 22
20 Execution (msec)
Discrete Input Block (DI) 4 Number Segment #: DFJB-21088
2 23
15 Execution Time
3 Bias/Gain Station (BG) 0 Execution (msec) 24 LAS Capable: Yes No
Manual Loader (ML) 0 Number 25 Device Current Draw (mA): 19
4
0 Execution (msec) Device Minimum Voltage: 9.
26
Analog Output Block (AO) 1 Number Device Capacitance: 5 nF
5 20 Execution (msec) Polarity-sensitive: Yes No
27
Discrete Output Block (DO) 1 Number Segment Terminator Location:
6 20 Execution (msec)
28
7 Control Selector (CS)
DD Revision: 3
PID,PI,I Controller (PID) 29
8
20 Execution (msec)
CFF Revision: 1.9
Ratio Station (RA) 30
9
P,PD Controller (PD) 0 Number
10 0 Execution (msec)

* Execution time in msec.

Advanced Function Blocks Notes:

11 Device Control (DC)

12 Output Splitter (OS)

13 Signal Characterizer (SC)

14 Lead Lag (LL)

15 Deadtime (DT)

16 Integrator(Totalizer) (IT)

17 Setpoint Ramp Generator (SPG)

18 Input Selector (IS)

19 Arithmetic (AR)

20 Timer (TMR)

21 Analog Alarm (AAL)

INSTRUMENT SPECIFICATION -FOUNDATION FIELDBUS


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S60.2 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Tag Number : FV -21143

1. Special PWHT Required .


2. Steam out condition : F.V/200 deg C.
3. In-Built surge protector is provided by vendor.

1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S60.3 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
1 Tag No. FV -21201
2 Service GA21202 WTR TO EC21202
3 P&ID No. Line No. R2B-P3-206-02-A-DTI-00202 3"-APR-212005-B1A1-N
4 Area Classification Ingress Protection CLASS 1 DIV 2 Gr. B ,C&D, T3 NEMA 4X
GENERAL 5 Ambient Temperature: Unit Min. Max. °C 10 48
6 Allowable Sound dBA Tightness Requirement <85 ANSI IV (standard)
7 Available Air Supply Pressure Unit Min. Max. kgf/cm²-g 4.2 8.0
8 Electric Connection Pneum. Connection 1/2” NPT (F) 1/4” NPT (F)
9 Power Failure Position FC
10 Line Size and Schedule Sch. Outlet Line Sch. 3 in STD 3" STD
PIPE
11 Line Class Rating Pipe Material B1A1 150# A106 GR.B, SMLS
LINE
12 Pipe Insulation Thickness Corrosion Allowance N N/A 1.6mm
13 Fluid State Phase Water Liquid Single Phase
14 Sour Service Special Condition N/A N/A
15 Flow Rate Units Min. Nor. Max. m³/h 11.1 22.1 24.3
16 Inlet Pressure Units Min. Nor. Max. kgf/cm²-g 11.22 10.56 10.13
17 Pressure Drop Units Min. Nor. Max. kgf/cm² 2.543 1.557 1.054
18 Inlet Temperature Units Min. Nor. Max. °C 50 50 50
PROCESS 19 Density Units Min. Nor. Max. kg/m³ 966 966 966
CONDITIONS 20 Viscosity Units Min. Nor. Max. cP 0.542 0.542 0.542
21 Molecular Weight (MW) Specific Gravity @ Oper.
22 Spec. Heat Ratio (Cp/Cv) Compressibility (Z)
23 Vapor Pressure (Liq.) Cavitation or Flashing 0.13 kgf/cm²-a NO
24 Critical Pressure (Liq) Flash (wt%) 224.99 kgf/cm²-a
25 Design Pressure Min. Max. kgf/cm²-g 13.7 kgf/cm²-g
26 Design Temperature Min. Max. 10 °C 120 °C
27 Max.Shutoff DP Solid % 13.7 kgf/cm²
28 Calculated Cv Units Min. Nor. Max. Cv 8. 20.5 27.5
CALCULATED
29 Travel Units Min. Nor. Max. % 43 60 66
RESULTS
30 Noise dBA @1m Units Min. Nor. Max. dBA 50 50 50
31 MFR Model FISHER EZ 56 MFR Model FISHER DVC6200F/SC-AD
32 Body Type Single Seat Globe 57 Signal: Inlet Outlet FF Protocol 0-2.8 kgf/cm2
33 Body Size Trim Size 2 in 2 in 58 Increase Signal Valve: DIRECT
34 End Connec.Size & Rating 2" 300# RF POSITIONER 59 Cam Characteristic LINEAR
35 Rated Cv Characteristic 53.8 EQ% 60 Bypass Gauges N/A YES
36 Body Material WCC Steel 61 Signal Fail. to Valve FC
BODY 37 Bonnet Type Material Plain WCC Steel 62 Electric Enclosure Ex ia IIC T5 , NEMA 4X
AND 38 Flow Direct. Flow Act. To Up FTO 63 MFR Model N/A N/A
TRIM 39 Packing Type Material ISO Seal PTFE 64 Type Power N/A N/A
SOLENOID
40 Lubricator Isolat. Valve N/A N/A 65 When De-Enegr.Valve: N/A
VALVE
41 Guiding No. of Ports Post 1 66 Material Latcher N/A N/A
42 Trim Type Internal Design Standard Unbalanced 67 Electric Enclosure N/A
43 Rated Travel Leak Class 1 1/8 in ANSI IV 68 MFR Model N/A N/A
44 Plug/ Ball/ Disk Material S41600 SST 69 Type Quantity N/A N/A
45 Seat Material S41600 SST SWITCHES 70 Contacts / Rating N/A
46 Cage Stem Material N/A S31600 SST 71 Switching Position N/A
47 Gasket Material S31600 SST/Graphite 72 Electric Enclosure N/A
48 MFR Model FISHER 667 73 MFR Model FISHER 67CFR
49 Type Diaphragm Spring Return AIR SET 74 Set Pressure 4.2 kgf/cm2-g
50 Size Stroke Time 45i < 8 Sec 75 Filter Gauge 5 Micron min YES
ACTUATOR 51 Air Failure Valve: FC 76 Vol. Tank Booster NO NO
52 Handwheel Location N/A 77 Diffuser Lock-up NO NO
ACCESSORY
53 Mounting Position VERTICAL 78 Fire Safe Fireproof NO NO
54 Spring Range 1 - 2.5 kgf/cm2-g 79 Mech. Stop Quick Exa. NO NO
55 Include Pressure (Shutoff) 80 Hydro. Pressure YES
85 Vendor EMERSON 81 Leakage YES
PURCHASE TESTS
86 Manufacturer FISHER 82 Cryogenic N/A
87 Requisition No. R2B-P3-206-02-P-MR-00200 83 NACE Requirement N/A
88 Model No. EZ 84 PWHT Requirement N/A
Notes:

INSTRUMENT SPECIFICATION - CONTROL VALVE


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S61.1 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Fieldbus Device Data Sheet
Tag No.: FV -21201
Fieldbus Tag No.:

Service : GA21202 WTR TO EC21202

Basic Fieldbus Function Blocks Segment Information


Analog Input Block (AI) 1 Number Device:
1 22
20 Execution (msec)
Discrete Input Block (DI) 4 Number Segment #: DFJB-21118
2 23
15 Execution Time
3 Bias/Gain Station (BG) 0 Execution (msec) 24 LAS Capable: Yes No
Manual Loader (ML) 0 Number 25 Device Current Draw (mA): 19
4
0 Execution (msec) Device Minimum Voltage: 9.
26
Analog Output Block (AO) 1 Number Device Capacitance: 5 nF
5 20 Execution (msec) Polarity-sensitive: Yes No
27
Discrete Output Block (DO) 1 Number Segment Terminator Location:
6 20 Execution (msec)
28
7 Control Selector (CS)
DD Revision: 3
PID,PI,I Controller (PID) 29
8
20 Execution (msec)
CFF Revision: 1.9
Ratio Station (RA) 30
9
P,PD Controller (PD) 0 Number
10 0 Execution (msec)

* Execution time in msec.

Advanced Function Blocks Notes:

11 Device Control (DC)

12 Output Splitter (OS)

13 Signal Characterizer (SC)

14 Lead Lag (LL)

15 Deadtime (DT)

16 Integrator(Totalizer) (IT)

17 Setpoint Ramp Generator (SPG)

18 Input Selector (IS)

19 Arithmetic (AR)

20 Timer (TMR)

21 Analog Alarm (AAL)

INSTRUMENT SPECIFICATION -FOUNDATION FIELDBUS


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S61.2 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Tag Number : FV -21201

1. In-Built surge protector is provided by vendor.

1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S61.3 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
1 Tag No. FV -21208
2 Service GA201AB HC COND TO FA202
3 P&ID No. Line No. R2B-P3-206-02-A-DTI-00210 4"-P-212018-B2A2-NACE-N
4 Area Classification Ingress Protection CLASS 1 DIV 2 Gr. B ,C&D, T3 NEMA 4X
GENERAL 5 Ambient Temperature: Unit Min. Max. °C 10 48
6 Allowable Sound dBA Tightness Requirement <85 ANSI IV (standard)
7 Available Air Supply Pressure Unit Min. Max. kgf/cm²-g 4.2 8.0
8 Electric Connection Pneum. Connection 1/2” NPT (F) 1/4” NPT (F)
9 Power Failure Position FO
10 Line Size and Schedule Sch. Outlet Line Sch. 4 in XS 4" XS
PIPE
11 Line Class Rating Pipe Material B2A2-NACE 300# A106 GR.B, SMLS
LINE
12 Pipe Insulation Thickness Corrosion Allowance N N/A 3.2mm
13 Fluid State Phase Water and Hydrocarbon Liquid Single Phase
14 Sour Service Special Condition YES N/A
15 Flow Rate Units Min. Nor. Max. m³/h 23.45 46.9 51.6
16 Inlet Pressure Units Min. Nor. Max. kgf/cm²-g 21.1 21.1 21.1
17 Pressure Drop Units Min. Nor. Max. kgf/cm² 16.83 16.83 16.83
18 Inlet Temperature Units Min. Nor. Max. °C 38 38 38
PROCESS 19 Density Units Min. Nor. Max. kg/m³ 757 757 757
CONDITIONS 20 Viscosity Units Min. Nor. Max. cP 0.502 0.502 0.502
21 Molecular Weight (MW) Specific Gravity @ Oper.
22 Spec. Heat Ratio (Cp/Cv) Compressibility (Z)
23 Vapor Pressure (Liq.) Cavitation or Flashing 5.17 kgf/cm²-a NO
24 Critical Pressure (Liq) Flash (wt%) 38.57 kgf/cm²-a
25 Design Pressure Min. Max. kgf/cm²-g 28 kgf/cm²-g
26 Design Temperature Min. Max. 10 °C 120 °C
27 Max.Shutoff DP Solid % 28 kgf/cm²
28 Calculated Cv Units Min. Nor. Max. Cv 6.44 12.9 14.3
CALCULATED
29 Travel Units Min. Nor. Max. % 62 80 83
RESULTS
30 Noise dBA @1m Units Min. Nor. Max. dBA 60 63 63
31 MFR Model FISHER ET 56 MFR Model FISHER DVC6200F/SC-AD
32 Body Type Single Seat Globe 57 Signal: Inlet Outlet FF Protocol 0-2.8 kgf/cm2
33 Body Size Trim Size 2 in 1 5/16 in 58 Increase Signal Valve: DIRECT
34 End Connec.Size & Rating 2" 300# RF POSITIONER 59 Cam Characteristic LINEAR
35 Rated Cv Characteristic 24.3 EQ% 60 Bypass Gauges N/A YES
36 Body Material WCC Steel 61 Signal Fail. to Valve FO
BODY 37 Bonnet Type Material Plain WCC Steel 62 Electric Enclosure Ex ia IIC T5 , NEMA 4X
AND 38 Flow Direct. Flow Act. To Down FTO 63 MFR Model N/A N/A
TRIM 39 Packing Type Material ISO Seal PTFE 64 Type Power N/A N/A
SOLENOID
40 Lubricator Isolat. Valve N/A N/A 65 When De-Enegr.Valve: N/A
VALVE
41 Guiding No. of Ports Cage 1 66 Material Latcher N/A N/A
42 Trim Type Internal Design Standard Balanced 67 Electric Enclosure N/A
43 Rated Travel Leak Class 3/4 in ANSI IV 68 MFR Model N/A N/A
44 Plug/ Ball/ Disk Material S31600 SST/CoCr-A Seat 69 Type Quantity N/A N/A
45 Seat Material R30006 Cobalt Alloy SWITCHES 70 Contacts / Rating N/A
46 Cage Stem Material S31600 SST/ ENCS20910 SST 71 Switching Position N/A
47 Gasket Material S31600 SST/Graphite 72 Electric Enclosure N/A
48 MFR Model FISHER 657 73 MFR Model FISHER 67CFR
49 Type Diaphragm Spring Return AIR SET 74 Set Pressure 4.2 kgf/cm2-g
50 Size Stroke Time 40i < 8 Sec 75 Filter Gauge 5 Micron min YES
ACTUATOR 51 Air Failure Valve: FO 76 Vol. Tank Booster NO NO
52 Handwheel Location N/A 77 Diffuser Lock-up NO NO
ACCESSORY
53 Mounting Position VERTICAL 78 Fire Safe Fireproof NO NO
54 Spring Range 0.4 - 2.0 kgf/cm2-g 79 Mech. Stop Quick Exa. NO NO
55 Include Pressure (Shutoff) 80 Hydro. Pressure YES
85 Vendor EMERSON 81 Leakage YES
PURCHASE TESTS
86 Manufacturer FISHER 82 Cryogenic N/A
87 Requisition No. R2B-P3-206-02-P-MR-00200 83 NACE Requirement NACE-0103
88 Model No. ET 84 PWHT Requirement YES
Notes:

INSTRUMENT SPECIFICATION - CONTROL VALVE


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S62.1 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Fieldbus Device Data Sheet
Tag No.: FV -21208
Fieldbus Tag No.:

Service : GA201AB HC COND TO FA202

Basic Fieldbus Function Blocks Segment Information


Analog Input Block (AI) 1 Number Device:
1 22
20 Execution (msec)
Discrete Input Block (DI) 4 Number Segment #: DFJB-21092
2 23
15 Execution Time
3 Bias/Gain Station (BG) 0 Execution (msec) 24 LAS Capable: Yes No
Manual Loader (ML) 0 Number 25 Device Current Draw (mA): 19
4
0 Execution (msec) Device Minimum Voltage: 9.
26
Analog Output Block (AO) 1 Number Device Capacitance: 5 nF
5 20 Execution (msec) Polarity-sensitive: Yes No
27
Discrete Output Block (DO) 1 Number Segment Terminator Location:
6 20 Execution (msec)
28
7 Control Selector (CS)
DD Revision: 3
PID,PI,I Controller (PID) 29
8
20 Execution (msec)
CFF Revision: 1.9
Ratio Station (RA) 30
9
P,PD Controller (PD) 0 Number
10 0 Execution (msec)

* Execution time in msec.

Advanced Function Blocks Notes:

11 Device Control (DC)

12 Output Splitter (OS)

13 Signal Characterizer (SC)

14 Lead Lag (LL)

15 Deadtime (DT)

16 Integrator(Totalizer) (IT)

17 Setpoint Ramp Generator (SPG)

18 Input Selector (IS)

19 Arithmetic (AR)

20 Timer (TMR)

21 Analog Alarm (AAL)

INSTRUMENT SPECIFICATION -FOUNDATION FIELDBUS


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S62.2 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Tag Number : FV -21208

1. Valve will normally be in the closed position. Valve opening will be intermittent and generally short-term.
2. Special PWHT Required .
3. In-Built surge protector is provided by vendor.

1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S62.3 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
1 Tag No. FV -21213
2 Service GA203AB STRP FEED TO EA207
3 P&ID No. Line No. R2B-P3-206-02-A-DTI-00214 14"-P-212021-B2A2-NACE-N
4 Area Classification Ingress Protection CLASS 1 DIV 2 Gr. B ,C&D, T3 NEMA 4X
GENERAL 5 Ambient Temperature: Unit Min. Max. °C 10 48
6 Allowable Sound dBA Tightness Requirement <85 ANSI IV (standard)
7 Available Air Supply Pressure Unit Min. Max. kgf/cm²-g 4.2 8.0
8 Electric Connection Pneum. Connection 1/2” NPT (F) 1/4” NPT (F)
9 Power Failure Position FC
10 Line Size and Schedule Sch. Outlet Line Sch. 14 in XS 14" XS
PIPE
11 Line Class Rating Pipe Material B2A2-NACE 300# A106 GR.B, SMLS
LINE
12 Pipe Insulation Thickness Corrosion Allowance N N/A 3.2mm
13 Fluid State Phase Hydrocarbon Liquid Single Phase
14 Sour Service Special Condition YES N/A
15 Flow Rate Units Min. Nor. Max. m³/h 485.8 971.6 1068.7
16 Inlet Pressure Units Min. Nor. Max. kgf/cm²-g 22.32 22.31 22.25
17 Pressure Drop Units Min. Nor. Max. kgf/cm² 2.6 2.3 1.281
18 Inlet Temperature Units Min. Nor. Max. °C 37 37 37
PROCESS 19 Density Units Min. Nor. Max. kg/m³ 663 663 663
CONDITIONS 20 Viscosity Units Min. Nor. Max. cP 0.251 0.251 0.251
21 Molecular Weight (MW) Specific Gravity @ Oper.
22 Spec. Heat Ratio (Cp/Cv) Compressibility (Z)
23 Vapor Pressure (Liq.) Cavitation or Flashing 16.24 kgf/cm²-a NO
24 Critical Pressure (Liq) Flash (wt%) 40.73 kgf/cm²-a
25 Design Pressure Min. Max. kgf/cm²-g 27.7 kgf/cm²-g
26 Design Temperature Min. Max. 10 °C 120 °C
27 Max.Shutoff DP Solid % 27.7 kgf/cm²
28 Calculated Cv Units Min. Nor. Max. Cv 286 609 898
CALCULATED
29 Travel Units Min. Nor. Max. % 48 66 84
RESULTS
30 Noise dBA @1m Units Min. Nor. Max. dBA 77 76 66
31 MFR Model FISHER EWT 56 MFR Model FISHER DVC6200F/SC-AD
32 Body Type Single Seat Globe 57 Signal: Inlet Outlet FF Protocol 0-2.8 kgf/cm2
33 Body Size Trim Size 12 in 8 in 58 Increase Signal Valve: DIRECT
34 End Connec.Size & Rating 12" 300# RF POSITIONER 59 Cam Characteristic LINEAR
35 Rated Cv Characteristic 1090 EQ% 60 Bypass Gauges N/A YES
36 Body Material WCC Steel 61 Signal Fail. to Valve FC
BODY 37 Bonnet Type Material Plain WCC Steel 62 Electric Enclosure Ex ia IIC T5 , NEMA 4X
AND 38 Flow Direct. Flow Act. To Down FTO 63 MFR Model N/A N/A
TRIM 39 Packing Type Material ISO Seal PTFE 64 Type Power N/A N/A
SOLENOID
40 Lubricator Isolat. Valve N/A N/A 65 When De-Enegr.Valve: N/A
VALVE
41 Guiding No. of Ports Cage 1 66 Material Latcher N/A N/A
42 Trim Type Internal Design Standard Balanced 67 Electric Enclosure N/A
43 Rated Travel Leak Class 3 in ANSI IV 68 MFR Model N/A N/A
44 Plug/ Ball/ Disk Material S31600 SST/CoCr-A Seat 69 Type Quantity N/A N/A
45 Seat Material R30006 Cobalt Alloy SWITCHES 70 Contacts / Rating N/A
46 Cage Stem Material S31600 SST/ ENCS20910 SST 71 Switching Position N/A
47 Gasket Material S31600 SST/Graphite 72 Electric Enclosure N/A
48 MFR Model FISHER 667-4 73 MFR Model FISHER 67CFR
49 Type Diaphragm Spring Return AIR SET 74 Set Pressure 4.2 kgf/cm2-g
50 Size Stroke Time 70i < 25 Sec 75 Filter Gauge 5 Micron min YES
ACTUATOR 51 Air Failure Valve: FC 76 Vol. Tank Booster NO NO
52 Handwheel Location N/A 77 Diffuser Lock-up NO NO
ACCESSORY
53 Mounting Position VERTICAL 78 Fire Safe Fireproof NO NO
54 Spring Range 1 - 1.8 kgf/cm2-g 79 Mech. Stop Quick Exa. NO NO
55 Include Pressure (Shutoff) 80 Hydro. Pressure YES
85 Vendor EMERSON 81 Leakage YES
PURCHASE TESTS
86 Manufacturer FISHER 82 Cryogenic N/A
87 Requisition No. R2B-P3-206-02-P-MR-00200 83 NACE Requirement NACE-0103
88 Model No. EWT 84 PWHT Requirement YES
Notes:

INSTRUMENT SPECIFICATION - CONTROL VALVE


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S63.1 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Fieldbus Device Data Sheet
Tag No.: FV -21213
Fieldbus Tag No.:

Service : GA203AB STRP FEED TO EA207

Basic Fieldbus Function Blocks Segment Information


Analog Input Block (AI) 1 Number Device:
1 22
20 Execution (msec)
Discrete Input Block (DI) 4 Number Segment #: DFJB-21112
2 23
15 Execution Time
3 Bias/Gain Station (BG) 0 Execution (msec) 24 LAS Capable: Yes No
Manual Loader (ML) 0 Number 25 Device Current Draw (mA): 19
4
0 Execution (msec) Device Minimum Voltage: 9.
26
Analog Output Block (AO) 1 Number Device Capacitance: 5 nF
5 20 Execution (msec) Polarity-sensitive: Yes No
27
Discrete Output Block (DO) 1 Number Segment Terminator Location:
6 20 Execution (msec)
28
7 Control Selector (CS)
DD Revision: 3
PID,PI,I Controller (PID) 29
8
20 Execution (msec)
CFF Revision: 1.9
Ratio Station (RA) 30
9
P,PD Controller (PD) 0 Number
10 0 Execution (msec)

* Execution time in msec.

Advanced Function Blocks Notes:

11 Device Control (DC)

12 Output Splitter (OS)

13 Signal Characterizer (SC)

14 Lead Lag (LL)

15 Deadtime (DT)

16 Integrator(Totalizer) (IT)

17 Setpoint Ramp Generator (SPG)

18 Input Selector (IS)

19 Arithmetic (AR)

20 Timer (TMR)

21 Analog Alarm (AAL)

INSTRUMENT SPECIFICATION -FOUNDATION FIELDBUS


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S63.2 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Tag Number : FV -21213

1. Special PWHT Required .


2. In-Built surge protector is provided by vendor.

1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S63.3 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
1 Tag No. FV -21214
2 Service GA204AB RICH OIL TO DA201
3 P&ID No. Line No. R2B-P3-206-02-A-DTI-00216 8"-P-212054-B2A2-NACE-N
4 Area Classification Ingress Protection CLASS 1 DIV 2 Gr. B ,C&D, T3 NEMA 4X
GENERAL 5 Ambient Temperature: Unit Min. Max. °C 10 48
6 Allowable Sound dBA Tightness Requirement <85 ANSI IV (standard)
7 Available Air Supply Pressure Unit Min. Max. kgf/cm²-g 4.2 8.0
8 Electric Connection Pneum. Connection 1/2” NPT (F) 1/4” NPT (F)
9 Power Failure Position FO
10 Line Size and Schedule Sch. Outlet Line Sch. 8 in XS 8" XS
PIPE
11 Line Class Rating Pipe Material B2A2-NACE 300# A106 GR.B, SMLS
LINE
12 Pipe Insulation Thickness Corrosion Allowance N N/A 3.2mm
13 Fluid State Phase Hydrocarbon Liquid Single Phase
14 Sour Service Special Condition YES N/A
15 Flow Rate Units Min. Nor. Max. m³/h 166.82 333.64 367
16 Inlet Pressure Units Min. Nor. Max. kgf/cm²-g 22.1 22.1 22.1
17 Pressure Drop Units Min. Nor. Max. kgf/cm² 6.42 6.42 6.42
18 Inlet Temperature Units Min. Nor. Max. °C 47 47 47
PROCESS 19 Density Units Min. Nor. Max. kg/m³ 699 699 699
CONDITIONS 20 Viscosity Units Min. Nor. Max. cP 0.341 0.341 0.341
21 Molecular Weight (MW) Specific Gravity @ Oper.
22 Spec. Heat Ratio (Cp/Cv) Compressibility (Z)
23 Vapor Pressure (Liq.) Cavitation or Flashing 15.83 kgf/cm²-a NO
24 Critical Pressure (Liq) Flash (wt%) 39.21 kgf/cm²-a
25 Design Pressure Min. Max. kgf/cm²-g 25.6 kgf/cm²-g
26 Design Temperature Min. Max. 10 °C 120 °C
27 Max.Shutoff DP Solid % 25.6 kgf/cm²
28 Calculated Cv Units Min. Nor. Max. Cv 64.7 132 147
CALCULATED
29 Travel Units Min. Nor. Max. % 55 72 75
RESULTS
30 Noise dBA @1m Units Min. Nor. Max. dBA 80 83 84
31 MFR Model FISHER ET 56 MFR Model FISHER DVC6200F/SC-AD
32 Body Type Single Seat Globe 57 Signal: Inlet Outlet FF Protocol 0-2.8 kgf/cm2
33 Body Size Trim Size 4 in 4 3/8 in 58 Increase Signal Valve: DIRECT
34 End Connec.Size & Rating 4" 300# RF POSITIONER 59 Cam Characteristic LINEAR
35 Rated Cv Characteristic 224 EQ% 60 Bypass Gauges N/A YES
36 Body Material WCC Steel 61 Signal Fail. to Valve FO
BODY 37 Bonnet Type Material Plain WCC Steel 62 Electric Enclosure Ex ia IIC T5 , NEMA 4X
AND 38 Flow Direct. Flow Act. To Down FTO 63 MFR Model N/A N/A
TRIM 39 Packing Type Material ISO Seal PTFE 64 Type Power N/A N/A
SOLENOID
40 Lubricator Isolat. Valve N/A N/A 65 When De-Enegr.Valve: N/A
VALVE
41 Guiding No. of Ports Cage 1 66 Material Latcher N/A N/A
42 Trim Type Internal Design Standard Balanced 67 Electric Enclosure N/A
43 Rated Travel Leak Class 2 in ANSI IV 68 MFR Model N/A N/A
44 Plug/ Ball/ Disk Material S31600 SST/CoCr-A Seat 69 Type Quantity N/A N/A
45 Seat Material R30006 Cobalt Alloy SWITCHES 70 Contacts / Rating N/A
46 Cage Stem Material S31600 SST/ ENCS20910 SST 71 Switching Position N/A
47 Gasket Material S31600 SST/Graphite 72 Electric Enclosure N/A
48 MFR Model FISHER 657 73 MFR Model FISHER 67CFR
49 Type Diaphragm Spring Return AIR SET 74 Set Pressure 4.2 kgf/cm2-g
50 Size Stroke Time 45i < 10 Sec 75 Filter Gauge 5 Micron min YES
ACTUATOR 51 Air Failure Valve: FO 76 Vol. Tank Booster NO NO
52 Handwheel Location N/A 77 Diffuser Lock-up NO NO
ACCESSORY
53 Mounting Position VERTICAL 78 Fire Safe Fireproof NO NO
54 Spring Range 0.6 - 2.0 kgf/cm2-g 79 Mech. Stop Quick Exa. NO NO
55 Include Pressure (Shutoff) 80 Hydro. Pressure YES
85 Vendor EMERSON 81 Leakage YES
PURCHASE TESTS
86 Manufacturer FISHER 82 Cryogenic N/A
87 Requisition No. R2B-P3-206-02-P-MR-00200 83 NACE Requirement NACE-0103
88 Model No. ET 84 PWHT Requirement YES
Notes:

INSTRUMENT SPECIFICATION - CONTROL VALVE


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S64.1 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Fieldbus Device Data Sheet
Tag No.: FV -21214
Fieldbus Tag No.:

Service : GA204AB RICH OIL TO DA201

Basic Fieldbus Function Blocks Segment Information


Analog Input Block (AI) 1 Number Device:
1 22
20 Execution (msec)
Discrete Input Block (DI) 4 Number Segment #: DFJB-21098
2 23
15 Execution Time
3 Bias/Gain Station (BG) 0 Execution (msec) 24 LAS Capable: Yes No
Manual Loader (ML) 0 Number 25 Device Current Draw (mA): 19
4
0 Execution (msec) Device Minimum Voltage: 9.
26
Analog Output Block (AO) 1 Number Device Capacitance: 5 nF
5 20 Execution (msec) Polarity-sensitive: Yes No
27
Discrete Output Block (DO) 1 Number Segment Terminator Location:
6 20 Execution (msec)
28
7 Control Selector (CS)
DD Revision: 3
PID,PI,I Controller (PID) 29
8
20 Execution (msec)
CFF Revision: 1.9
Ratio Station (RA) 30
9
P,PD Controller (PD) 0 Number
10 0 Execution (msec)

* Execution time in msec.

Advanced Function Blocks Notes:

11 Device Control (DC)

12 Output Splitter (OS)

13 Signal Characterizer (SC)

14 Lead Lag (LL)

15 Deadtime (DT)

16 Integrator(Totalizer) (IT)

17 Setpoint Ramp Generator (SPG)

18 Input Selector (IS)

19 Arithmetic (AR)

20 Timer (TMR)

21 Analog Alarm (AAL)

INSTRUMENT SPECIFICATION -FOUNDATION FIELDBUS


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S64.2 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Tag Number : FV -21214

1. Valve will normally be in the closed position. Valve opening will be intermittent and generally short-term.
2. Special PWHT Required .
3. In-Built surge protector is provided by vendor.

1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S64.3 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
1 Tag No. FV -21218
2 Service GA206AB LEAN OIL TO DA202
3 P&ID No. Line No. R2B-P3-206-02-A-DTI-00221 6"-ACL-212216-B2A1-N
4 Area Classification Ingress Protection CLASS 1 DIV 2 Gr. B ,C&D, T3 NEMA 4X
GENERAL 5 Ambient Temperature: Unit Min. Max. °C 10 48
6 Allowable Sound dBA Tightness Requirement <85 ANSI IV (standard)
7 Available Air Supply Pressure Unit Min. Max. kgf/cm²-g 4.2 8.0
8 Electric Connection Pneum. Connection 1/2” NPT (F) 1/4” NPT (F)
9 Power Failure Position FC
10 Line Size and Schedule Sch. Outlet Line Sch. 6 in STD 6" STD
PIPE
11 Line Class Rating Pipe Material B2A1 300# A106 GR.B, SMLS
LINE
12 Pipe Insulation Thickness Corrosion Allowance N N/A 1.6mm
13 Fluid State Phase Hydrocarbon Liquid Single Phase
14 Sour Service Special Condition N/A N/A
15 Flow Rate Units Min. Nor. Max. m³/h 33.6 67.2 80.6
16 Inlet Pressure Units Min. Nor. Max. kgf/cm²-g 18.14 18 17.17
17 Pressure Drop Units Min. Nor. Max. kgf/cm² 6.22 3.8 1.79
18 Inlet Temperature Units Min. Nor. Max. °C 38 38 38
PROCESS 19 Density Units Min. Nor. Max. kg/m³ 931 931 931
CONDITIONS 20 Viscosity Units Min. Nor. Max. cP 6.95 6.95 6.95
21 Molecular Weight (MW) Specific Gravity @ Oper.
22 Spec. Heat Ratio (Cp/Cv) Compressibility (Z)
23 Vapor Pressure (Liq.) Cavitation or Flashing 0.36 kgf/cm²-a NO
24 Critical Pressure (Liq) Flash (wt%) 28.19 kgf/cm²-a
25 Design Pressure Min. Max. -1.033 kgf/cm²-g 32.7 kgf/cm²-g
26 Design Temperature Min. Max. 10 °C 160 °C
27 Max.Shutoff DP Solid % 32.7 kgf/cm²
28 Calculated Cv Units Min. Nor. Max. Cv 15.2 38.9 68.2
CALCULATED
29 Travel Units Min. Nor. Max. % 37 60 73
RESULTS
30 Noise dBA @1m Units Min. Nor. Max. dBA 58 58 54
31 MFR Model FISHER ET 56 MFR Model FISHER DVC6200F/SC-AD
32 Body Type Single Seat Globe 57 Signal: Inlet Outlet FF Protocol 0-2.8 kgf/cm2
33 Body Size Trim Size 4 in 2 7/8 in 58 Increase Signal Valve: DIRECT
34 End Connec.Size & Rating 4" 300# RF POSITIONER 59 Cam Characteristic LINEAR
35 Rated Cv Characteristic 112 EQ% 60 Bypass Gauges N/A YES
36 Body Material WCC Steel 61 Signal Fail. to Valve FC
BODY 37 Bonnet Type Material Plain WCC Steel 62 Electric Enclosure Ex ia IIC T5 , NEMA 4X
AND 38 Flow Direct. Flow Act. To Down FTO 63 MFR Model N/A N/A
TRIM 39 Packing Type Material ISO Seal PTFE 64 Type Power N/A N/A
SOLENOID
40 Lubricator Isolat. Valve N/A N/A 65 When De-Enegr.Valve: N/A
VALVE
41 Guiding No. of Ports Cage 1 66 Material Latcher N/A N/A
42 Trim Type Internal Design Standard Balanced 67 Electric Enclosure N/A
43 Rated Travel Leak Class 1 1/2 in ANSI IV 68 MFR Model N/A N/A
44 Plug/ Ball/ Disk Material S41600 SST 69 Type Quantity N/A N/A
45 Seat Material S41600 SST SWITCHES 70 Contacts / Rating N/A
46 Cage Stem Material CB7Cu-1 SST S31600 SST 71 Switching Position N/A
47 Gasket Material S31600 SST/Graphite 72 Electric Enclosure N/A
48 MFR Model FISHER 667 73 MFR Model FISHER 67CFR
49 Type Diaphragm Spring Return AIR SET 74 Set Pressure 4.2 kgf/cm2-g
50 Size Stroke Time 45i < 10 Sec 75 Filter Gauge 5 Micron min YES
ACTUATOR 51 Air Failure Valve: FC 76 Vol. Tank Booster NO NO
52 Handwheel Location N/A 77 Diffuser Lock-up NO NO
ACCESSORY
53 Mounting Position VERTICAL 78 Fire Safe Fireproof NO NO
54 Spring Range 0.7 - 2.6 kgf/cm2-g 79 Mech. Stop Quick Exa. NO NO
55 Include Pressure (Shutoff) 80 Hydro. Pressure YES
85 Vendor EMERSON 81 Leakage YES
PURCHASE TESTS
86 Manufacturer FISHER 82 Cryogenic N/A
87 Requisition No. R2B-P3-206-02-P-MR-00200 83 NACE Requirement N/A
88 Model No. ET 84 PWHT Requirement N/A
Notes:

INSTRUMENT SPECIFICATION - CONTROL VALVE


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S65.1 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Fieldbus Device Data Sheet
Tag No.: FV -21218
Fieldbus Tag No.:

Service : GA206AB LEAN OIL TO DA202

Basic Fieldbus Function Blocks Segment Information


Analog Input Block (AI) 1 Number Device:
1 22
20 Execution (msec)
Discrete Input Block (DI) 4 Number Segment #: DFJB-21102
2 23
15 Execution Time
3 Bias/Gain Station (BG) 0 Execution (msec) 24 LAS Capable: Yes No
Manual Loader (ML) 0 Number 25 Device Current Draw (mA): 19
4
0 Execution (msec) Device Minimum Voltage: 9.
26
Analog Output Block (AO) 1 Number Device Capacitance: 5 nF
5 20 Execution (msec) Polarity-sensitive: Yes No
27
Discrete Output Block (DO) 1 Number Segment Terminator Location:
6 20 Execution (msec)
28
7 Control Selector (CS)
DD Revision: 3
PID,PI,I Controller (PID) 29
8
20 Execution (msec)
CFF Revision: 1.9
Ratio Station (RA) 30
9
P,PD Controller (PD) 0 Number
10 0 Execution (msec)

* Execution time in msec.

Advanced Function Blocks Notes:

11 Device Control (DC)

12 Output Splitter (OS)

13 Signal Characterizer (SC)

14 Lead Lag (LL)

15 Deadtime (DT)

16 Integrator(Totalizer) (IT)

17 Setpoint Ramp Generator (SPG)

18 Input Selector (IS)

19 Arithmetic (AR)

20 Timer (TMR)

21 Analog Alarm (AAL)

INSTRUMENT SPECIFICATION -FOUNDATION FIELDBUS


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S65.2 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Tag Number : FV -21218

1. Steam out condition : F.V/200 degC.


2. In-Built surge protector is provided by vendor.

1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S65.3 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
1 Tag No. FV -21229
2 Service EA213AB CIRC HCO TO DF101
3 P&ID No. Line No. R2B-P3-206-02-A-DTI-00229 18"-ACP-212001-B2A1-EC
4 Area Classification Ingress Protection CLASS 1 DIV 2 Gr. B ,C&D, T3 NEMA 4X
GENERAL 5 Ambient Temperature: Unit Min. Max. °C 10 48
6 Allowable Sound dBA Tightness Requirement <85 ANSI IV (standard)
7 Available Air Supply Pressure Unit Min. Max. kgf/cm²-g 4.2 8.0
8 Electric Connection Pneum. Connection 1/2” NPT (F) 1/2” NPT (F)
9 Power Failure Position FC
10 Line Size and Schedule Sch. Outlet Line Sch. 18 in XS 18" XS
PIPE
11 Line Class Rating Pipe Material B2A1 300# A672 GR.C65 CL.22
LINE
12 Pipe Insulation Thickness Corrosion Allowance EC 115mm 1.6mm
13 Fluid State Phase Hydrocarbon Liquid Single Phase
14 Sour Service Special Condition N/A N/A
15 Flow Rate Units Min. Nor. Max. m³/h 574.5 1149 1378.8
16 Inlet Pressure Units Min. Nor. Max. kgf/cm²-g 8.304 7 6.448
17 Pressure Drop Units Min. Nor. Max. kgf/cm² 4.025 3.075 0.71
18 Inlet Temperature Units Min. Nor. Max. °C 229 229 229
PROCESS 19 Density Units Min. Nor. Max. kg/m³ 871 871 871
CONDITIONS 20 Viscosity Units Min. Nor. Max. cP 1.153 1.153 1.153
21 Molecular Weight (MW) Specific Gravity @ Oper.
22 Spec. Heat Ratio (Cp/Cv) Compressibility (Z)
23 Vapor Pressure (Liq.) Cavitation or Flashing 1.59 kgf/cm²-a NO
24 Critical Pressure (Liq) Flash (wt%) 26.2 kgf/cm²-a
25 Design Pressure Min. Max. -1.033 kgf/cm²-g 12.5 kgf/cm²-g
26 Design Temperature Min. Max. 10 °C 340 °C
27 Max.Shutoff DP Solid % 12.5 kgf/cm²
28 Calculated Cv Units Min. Nor. Max. Cv 312 714 1784
CALCULATED
29 Travel Units Min. Nor. Max. % 47 64 88
RESULTS
30 Noise dBA @1m Units Min. Nor. Max. dBA 85 85 65
31 MFR Model FISHER Large ED 56 MFR Model FISHER DVC6200F/SC-AD
32 Body Type Single Seat Globe 57 Signal: Inlet Outlet FF Protocol 4.2 kgf/cm2
33 Body Size Trim Size 16 in 14 3/4 in 58 Increase Signal Valve: DIRECT
34 End Connec.Size & Rating 16" 300# RF POSITIONER 59 Cam Characteristic LINEAR
35 Rated Cv Characteristic 2316.6 EQ% 60 Bypass Gauges N/A YES
36 Body Material WCC Steel 61 Signal Fail. to Valve FC
BODY 37 Bonnet Type Material Style 1 Extension WCC Steel 62 Electric Enclosure Ex ia IIC T5 , NEMA 4X
AND 38 Flow Direct. Flow Act. To Down FTO 63 MFR Model N/A N/A
TRIM 39 Packing Type Material ISO Seal Graphite 64 Type Power N/A N/A
SOLENOID
40 Lubricator Isolat. Valve N/A N/A 65 When De-Enegr.Valve: N/A
VALVE
41 Guiding No. of Ports Cage 1 66 Material Latcher N/A N/A
42 Trim Type Internal Design Standard Balanced 67 Electric Enclosure N/A
43 Rated Travel Leak Class 5 in ANSI IV 68 MFR Model N/A N/A
44 Plug/ Ball/ Disk Material CA6NM HT 69 Type Quantity N/A N/A
45 Seat Material 17-4 SST H1075 SWITCHES 70 Contacts / Rating N/A
46 Cage Stem Material 17-4 SST H1075 S20910 SST 71 Switching Position N/A
47 Gasket Material N06600/Graphite 72 Electric Enclosure N/A
48 MFR Model FISHER 785C 73 MFR Model FISHER 67DFR
49 Type Piston Spring Return AIR SET 74 Set Pressure 4.2 kgf/cm2-g
50 Size Stroke Time 585 < 45 Sec 75 Filter Gauge 5 Micron min YES
ACTUATOR 51 Air Failure Valve: FC 76 Vol. Tank Booster NO NO
52 Handwheel Location N/A 77 Diffuser Lock-up NO NO
ACCESSORY
53 Mounting Position VERTICAL 78 Fire Safe Fireproof NO NO
54 Spring Range 2.1 - 3.5 kgf/cm2-g 79 Mech. Stop Quick Exa. NO NO
55 Include Pressure (Shutoff) 80 Hydro. Pressure YES
85 Vendor EMERSON 81 Leakage YES
PURCHASE TESTS
86 Manufacturer FISHER 82 Cryogenic N/A
87 Requisition No. R2B-P3-206-02-P-MR-00200 83 NACE Requirement N/A
88 Model No. Large ED 84 PWHT Requirement N/A
Notes:

INSTRUMENT SPECIFICATION - CONTROL VALVE


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S66.1 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Fieldbus Device Data Sheet
Tag No.: FV -21229
Fieldbus Tag No.:

Service : EA213AB CIRC HCO TO DF101

Basic Fieldbus Function Blocks Segment Information


Analog Input Block (AI) 1 Number Device:
1 22
20 Execution (msec)
Discrete Input Block (DI) 4 Number Segment #: DFJB-21122
2 23
15 Execution Time
3 Bias/Gain Station (BG) 0 Execution (msec) 24 LAS Capable: Yes No
Manual Loader (ML) 0 Number 25 Device Current Draw (mA): 19
4
0 Execution (msec) Device Minimum Voltage: 9.
26
Analog Output Block (AO) 1 Number Device Capacitance: 5 nF
5 20 Execution (msec) Polarity-sensitive: Yes No
27
Discrete Output Block (DO) 1 Number Segment Terminator Location:
6 20 Execution (msec)
28
7 Control Selector (CS)
DD Revision: 3
PID,PI,I Controller (PID) 29
8
20 Execution (msec)
CFF Revision: 1.9
Ratio Station (RA) 30
9
P,PD Controller (PD) 0 Number
10 0 Execution (msec)

* Execution time in msec.

Advanced Function Blocks Notes:

11 Device Control (DC)

12 Output Splitter (OS)

13 Signal Characterizer (SC)

14 Lead Lag (LL)

15 Deadtime (DT)

16 Integrator(Totalizer) (IT)

17 Setpoint Ramp Generator (SPG)

18 Input Selector (IS)

19 Arithmetic (AR)

20 Timer (TMR)

21 Analog Alarm (AAL)

INSTRUMENT SPECIFICATION -FOUNDATION FIELDBUS


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S66.2 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Tag Number : FV -21229

1. Steam out condition : F.V/200 degC


2. In-Built surge protector is provided by vendor.

1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S66.3 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
1 Tag No. FV -21234
2 Service GA205AB REFL TO GA205AB
3 P&ID No. Line No. R2B-P3-206-02-A-DTI-00217 6"-P-212024-B2A2-NACE-N
4 Area Classification Ingress Protection CLASS 1 DIV 2 Gr. B ,C&D, T3 NEMA 4X
GENERAL 5 Ambient Temperature: Unit Min. Max. °C 10 48
6 Allowable Sound dBA Tightness Requirement <85 ANSI IV (standard)
7 Available Air Supply Pressure Unit Min. Max. kgf/cm²-g 4.2 8.0
8 Electric Connection Pneum. Connection 1/2” NPT (F) 1/4” NPT (F)
9 Power Failure Position FO
10 Line Size and Schedule Sch. Outlet Line Sch. 6 in XS 6" XS
PIPE
11 Line Class Rating Pipe Material B2A2-NACE 300# A106 GR.B, SMLS
LINE
12 Pipe Insulation Thickness Corrosion Allowance N N/A 3.2mm
13 Fluid State Phase Hydrocarbon Liquid Single Phase
14 Sour Service Special Condition YES N/A
15 Flow Rate Units Min. Nor. Max. m³/h 96.55 193.1 212.4
16 Inlet Pressure Units Min. Nor. Max. kgf/cm²-g 20.5 20.5 20.5
17 Pressure Drop Units Min. Nor. Max. kgf/cm² 3.78 3.78 3.78
18 Inlet Temperature Units Min. Nor. Max. °C 47 47 47
PROCESS 19 Density Units Min. Nor. Max. kg/m³ 719 719 719
CONDITIONS 20 Viscosity Units Min. Nor. Max. cP 0.389 0.389 0.389
21 Molecular Weight (MW) Specific Gravity @ Oper.
22 Spec. Heat Ratio (Cp/Cv) Compressibility (Z)
23 Vapor Pressure (Liq.) Cavitation or Flashing 15.17 kgf/cm²-a NO
24 Critical Pressure (Liq) Flash (wt%) 38.23 kgf/cm²-a
25 Design Pressure Min. Max. kgf/cm²-g 24.4 kgf/cm²-g
26 Design Temperature Min. Max. 10 °C 120 °C
27 Max.Shutoff DP Solid % 24.4 kgf/cm²
28 Calculated Cv Units Min. Nor. Max. Cv 49.3 99.2 109
CALCULATED
29 Travel Units Min. Nor. Max. % 50 64 67
RESULTS
30 Noise dBA @1m Units Min. Nor. Max. dBA 74 77 78
31 MFR Model FISHER ET 56 MFR Model FISHER DVC6200F/SC-AD
32 Body Type Single Seat Globe 57 Signal: Inlet Outlet FF Protocol 0-2.8 kgf/cm2
33 Body Size Trim Size 4 in 4 3/8 in 58 Increase Signal Valve: DIRECT
34 End Connec.Size & Rating 4" 300# RF POSITIONER 59 Cam Characteristic LINEAR
35 Rated Cv Characteristic 224 EQ% 60 Bypass Gauges N/A YES
36 Body Material WCC Steel 61 Signal Fail. to Valve FO
BODY 37 Bonnet Type Material Plain WCC Steel 62 Electric Enclosure Ex ia IIC T5 , NEMA 4X
AND 38 Flow Direct. Flow Act. To Down FTO 63 MFR Model N/A N/A
TRIM 39 Packing Type Material ISO Seal PTFE 64 Type Power N/A N/A
SOLENOID
40 Lubricator Isolat. Valve N/A N/A 65 When De-Enegr.Valve: N/A
VALVE
41 Guiding No. of Ports Cage 1 66 Material Latcher N/A N/A
42 Trim Type Internal Design Standard Balanced 67 Electric Enclosure N/A
43 Rated Travel Leak Class 2 in ANSI IV 68 MFR Model N/A N/A
44 Plug/ Ball/ Disk Material S31600 SST/CoCr-A Seat 69 Type Quantity N/A N/A
45 Seat Material R30006 Cobalt Alloy SWITCHES 70 Contacts / Rating N/A
46 Cage Stem Material S31600 SST/ ENCS20910 SST 71 Switching Position N/A
47 Gasket Material S31600 SST/Graphite 72 Electric Enclosure N/A
48 MFR Model FISHER 657 73 MFR Model FISHER 67CFR
49 Type Diaphragm Spring Return AIR SET 74 Set Pressure 4.2 kgf/cm2-g
50 Size Stroke Time 45i < 10 Sec 75 Filter Gauge 5 Micron min YES
ACTUATOR 51 Air Failure Valve: FO 76 Vol. Tank Booster NO NO
52 Handwheel Location N/A 77 Diffuser Lock-up NO NO
ACCESSORY
53 Mounting Position VERTICAL 78 Fire Safe Fireproof NO NO
54 Spring Range 0.4 - 1.9 kgf/cm2-g 79 Mech. Stop Quick Exa. NO NO
55 Include Pressure (Shutoff) 80 Hydro. Pressure YES
85 Vendor EMERSON 81 Leakage YES
PURCHASE TESTS
86 Manufacturer FISHER 82 Cryogenic N/A
87 Requisition No. R2B-P3-206-02-P-MR-00200 83 NACE Requirement NACE-0103
88 Model No. ET 84 PWHT Requirement YES
Notes:

INSTRUMENT SPECIFICATION - CONTROL VALVE


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S67.1 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Fieldbus Device Data Sheet
Tag No.: FV -21234
Fieldbus Tag No.:

Service : GA205AB REFL TO GA205AB

Basic Fieldbus Function Blocks Segment Information


Analog Input Block (AI) 1 Number Device:
1 22
20 Execution (msec)
Discrete Input Block (DI) 4 Number Segment #: DFJB-21105
2 23
15 Execution Time
3 Bias/Gain Station (BG) 0 Execution (msec) 24 LAS Capable: Yes No
Manual Loader (ML) 0 Number 25 Device Current Draw (mA): 19
4
0 Execution (msec) Device Minimum Voltage: 9.
26
Analog Output Block (AO) 1 Number Device Capacitance: 5 nF
5 20 Execution (msec) Polarity-sensitive: Yes No
27
Discrete Output Block (DO) 1 Number Segment Terminator Location:
6 20 Execution (msec)
28
7 Control Selector (CS)
DD Revision: 3
PID,PI,I Controller (PID) 29
8
20 Execution (msec)
CFF Revision: 1.9
Ratio Station (RA) 30
9
P,PD Controller (PD) 0 Number
10 0 Execution (msec)

* Execution time in msec.

Advanced Function Blocks Notes:

11 Device Control (DC)

12 Output Splitter (OS)

13 Signal Characterizer (SC)

14 Lead Lag (LL)

15 Deadtime (DT)

16 Integrator(Totalizer) (IT)

17 Setpoint Ramp Generator (SPG)

18 Input Selector (IS)

19 Arithmetic (AR)

20 Timer (TMR)

21 Analog Alarm (AAL)

INSTRUMENT SPECIFICATION -FOUNDATION FIELDBUS


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S67.2 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Tag Number : FV -21234

1. Special PWHT Required .


2. In-Built surge protector is provided by vendor.

1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S67.3 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
1 Tag No. FV -21235
2 Service GA206AB LCO TO DA202GA206AB
3 P&ID No. Line No. R2B-P3-206-02-A-DTI-00221 3"-ACL-212217-B2A1-N
4 Area Classification Ingress Protection CLASS 1 DIV 2 Gr. B ,C&D, T3 NEMA 4X
GENERAL 5 Ambient Temperature: Unit Min. Max. °C 10 48
6 Allowable Sound dBA Tightness Requirement <85 ANSI IV (standard)
7 Available Air Supply Pressure Unit Min. Max. kgf/cm²-g 4.2 8.0
8 Electric Connection Pneum. Connection 1/2” NPT (F) 1/4” NPT (F)
9 Power Failure Position FO
10 Line Size and Schedule Sch. Outlet Line Sch. 3 in STD 3" STD
PIPE
11 Line Class Rating Pipe Material B2A1 300# A106 GR.B, SMLS
LINE
12 Pipe Insulation Thickness Corrosion Allowance N N/A 1.6mm
13 Fluid State Phase Hydrocarbon Liquid Single Phase
14 Sour Service Special Condition N/A N/A
15 Flow Rate Units Min. Nor. Max. m³/h 15.55 31.1 34.2
16 Inlet Pressure Units Min. Nor. Max. kgf/cm²-g 21.9 21.9 21.9
17 Pressure Drop Units Min. Nor. Max. kgf/cm² 15.7 15.7 15.7
18 Inlet Temperature Units Min. Nor. Max. °C 38 38 38
PROCESS 19 Density Units Min. Nor. Max. kg/m³ 931 931 931
CONDITIONS 20 Viscosity Units Min. Nor. Max. cP 6.95 6.95 6.95
21 Molecular Weight (MW) Specific Gravity @ Oper.
22 Spec. Heat Ratio (Cp/Cv) Compressibility (Z)
23 Vapor Pressure (Liq.) Cavitation or Flashing 0.36 kgf/cm²-a NO
24 Critical Pressure (Liq) Flash (wt%) 28.19 kgf/cm²-a
25 Design Pressure Min. Max. -1.033 kgf/cm²-g 32.7 kgf/cm²-g
26 Design Temperature Min. Max. 10 °C 160 °C
27 Max.Shutoff DP Solid % 32.7 kgf/cm²
28 Calculated Cv Units Min. Nor. Max. Cv 4.43 8.91 9.81
CALCULATED
29 Travel Units Min. Nor. Max. % 54 72 74
RESULTS
30 Noise dBA @1m Units Min. Nor. Max. dBA 64 67 67
31 MFR Model FISHER EZ 56 MFR Model FISHER DVC6200F/SC-AD
32 Body Type Single Seat Globe 57 Signal: Inlet Outlet FF Protocol 0-2.8 kgf/cm2
33 Body Size Trim Size 1.5 in 1 in 58 Increase Signal Valve: DIRECT
34 End Connec.Size & Rating 1.5" 300# RF POSITIONER 59 Cam Characteristic LINEAR
35 Rated Cv Characteristic 17.3 EQ% 60 Bypass Gauges N/A YES
36 Body Material WCC Steel 61 Signal Fail. to Valve FO
BODY 37 Bonnet Type Material Plain WCC Steel 62 Electric Enclosure Ex ia IIC T5 , NEMA 4X
AND 38 Flow Direct. Flow Act. To Up FTO 63 MFR Model N/A N/A
TRIM 39 Packing Type Material ISO Seal PTFE 64 Type Power N/A N/A
SOLENOID
40 Lubricator Isolat. Valve N/A N/A 65 When De-Enegr.Valve: N/A
VALVE
41 Guiding No. of Ports Post 1 66 Material Latcher N/A N/A
42 Trim Type Internal Design Standard Unbalanced 67 Electric Enclosure N/A
43 Rated Travel Leak Class 3/4 in ANSI IV 68 MFR Model N/A N/A
44 Plug/ Ball/ Disk Material S31600 SST/CoCr-A Seat 69 Type Quantity N/A N/A
45 Seat Material S31600 SST/CoCr-A Seat SWITCHES 70 Contacts / Rating N/A
46 Cage Stem Material N/A S31600 SST 71 Switching Position N/A
47 Gasket Material S31600 SST/Graphite 72 Electric Enclosure N/A
48 MFR Model FISHER 657 73 MFR Model FISHER 67CFR
49 Type Diaphragm Spring Return AIR SET 74 Set Pressure 4.2 kgf/cm2-g
50 Size Stroke Time 34i < 5 Sec 75 Filter Gauge 5 Micron min YES
ACTUATOR 51 Air Failure Valve: FO 76 Vol. Tank Booster NO NO
52 Handwheel Location N/A 77 Diffuser Lock-up NO NO
ACCESSORY
53 Mounting Position VERTICAL 78 Fire Safe Fireproof NO NO
54 Spring Range 0.4 - 1.8 kgf/cm2-g 79 Mech. Stop Quick Exa. NO NO
55 Include Pressure (Shutoff) 80 Hydro. Pressure YES
85 Vendor EMERSON 81 Leakage YES
PURCHASE TESTS
86 Manufacturer FISHER 82 Cryogenic N/A
87 Requisition No. R2B-P3-206-02-P-MR-00200 83 NACE Requirement N/A
88 Model No. EZ 84 PWHT Requirement N/A
Notes:

INSTRUMENT SPECIFICATION - CONTROL VALVE


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S68.1 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Fieldbus Device Data Sheet
Tag No.: FV -21235
Fieldbus Tag No.:

Service : GA206AB LCO TO DA202GA206AB

Basic Fieldbus Function Blocks Segment Information


Analog Input Block (AI) 1 Number Device:
1 22
20 Execution (msec)
Discrete Input Block (DI) 4 Number Segment #: DFJB-21100
2 23
15 Execution Time
3 Bias/Gain Station (BG) 0 Execution (msec) 24 LAS Capable: Yes No
Manual Loader (ML) 0 Number 25 Device Current Draw (mA): 19
4
0 Execution (msec) Device Minimum Voltage: 9.
26
Analog Output Block (AO) 1 Number Device Capacitance: 5 nF
5 20 Execution (msec) Polarity-sensitive: Yes No
27
Discrete Output Block (DO) 1 Number Segment Terminator Location:
6 20 Execution (msec)
28
7 Control Selector (CS)
DD Revision: 3
PID,PI,I Controller (PID) 29
8
20 Execution (msec)
CFF Revision: 1.9
Ratio Station (RA) 30
9
P,PD Controller (PD) 0 Number
10 0 Execution (msec)

* Execution time in msec.

Advanced Function Blocks Notes:

11 Device Control (DC)

12 Output Splitter (OS)

13 Signal Characterizer (SC)

14 Lead Lag (LL)

15 Deadtime (DT)

16 Integrator(Totalizer) (IT)

17 Setpoint Ramp Generator (SPG)

18 Input Selector (IS)

19 Arithmetic (AR)

20 Timer (TMR)

21 Analog Alarm (AAL)

INSTRUMENT SPECIFICATION -FOUNDATION FIELDBUS


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S68.2 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Tag Number : FV -21235

1. In-Built surge protector is provided by vendor.

1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S68.3 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
1 Tag No. FV -21236
2 Service GA207AB NPTHA TO DA201GA110AB
3 P&ID No. Line No. R2B-P3-206-02-A-DTI-00225 4"-P-212068-B2A1-N
4 Area Classification Ingress Protection CLASS 1 DIV 2 Gr. B ,C&D, T3 NEMA 4X
GENERAL 5 Ambient Temperature: Unit Min. Max. °C 10 48
6 Allowable Sound dBA Tightness Requirement <85 ANSI IV (standard)
7 Available Air Supply Pressure Unit Min. Max. kgf/cm²-g 4.2 8.0
8 Electric Connection Pneum. Connection 1/2” NPT (F) 1/4” NPT (F)
9 Power Failure Position FO
10 Line Size and Schedule Sch. Outlet Line Sch. 4 in STD 4" STD
PIPE
11 Line Class Rating Pipe Material B2A1 300# A106 GR.B, SMLS
LINE
12 Pipe Insulation Thickness Corrosion Allowance N N/A 1.6mm
13 Fluid State Phase Hydrocarbon Liquid Single Phase
14 Sour Service Special Condition N/A N/A
15 Flow Rate Units Min. Nor. Max. m³/h 23.45 46.91 51.6
16 Inlet Pressure Units Min. Nor. Max. kgf/cm²-g 23.9 23.9 23.9
17 Pressure Drop Units Min. Nor. Max. kgf/cm² 13.5 13.5 13.5
18 Inlet Temperature Units Min. Nor. Max. °C 38 38 38
PROCESS 19 Density Units Min. Nor. Max. kg/m³ 739 739 739
CONDITIONS 20 Viscosity Units Min. Nor. Max. cP 0.525 0.525 0.525
21 Molecular Weight (MW) Specific Gravity @ Oper.
22 Spec. Heat Ratio (Cp/Cv) Compressibility (Z)
23 Vapor Pressure (Liq.) Cavitation or Flashing 0.57 kgf/cm²-a NO
24 Critical Pressure (Liq) Flash (wt%) 35.2 kgf/cm²-a
25 Design Pressure Min. Max. kgf/cm²-g 28.3 kgf/cm²-g
26 Design Temperature Min. Max. 10 °C 120 °C
27 Max.Shutoff DP Solid % 28.3 kgf/cm²
28 Calculated Cv Units Min. Nor. Max. Cv 6.41 12.9 14.2
CALCULATED
29 Travel Units Min. Nor. Max. % 62 80 82
RESULTS
30 Noise dBA @1m Units Min. Nor. Max. dBA 70 73 73
31 MFR Model FISHER ET 56 MFR Model FISHER DVC6200F/SC-AD
32 Body Type Single Seat Globe 57 Signal: Inlet Outlet FF Protocol 0-2.8 kgf/cm2
33 Body Size Trim Size 2 in 1 5/16 in 58 Increase Signal Valve: DIRECT
34 End Connec.Size & Rating 2" 300# RF POSITIONER 59 Cam Characteristic LINEAR
35 Rated Cv Characteristic 24.3 EQ% 60 Bypass Gauges N/A YES
36 Body Material WCC Steel 61 Signal Fail. to Valve FO
BODY 37 Bonnet Type Material Plain WCC Steel 62 Electric Enclosure Ex ia IIC T5 , NEMA 4X
AND 38 Flow Direct. Flow Act. To Down FTO 63 MFR Model N/A N/A
TRIM 39 Packing Type Material ISO Seal PTFE 64 Type Power N/A N/A
SOLENOID
40 Lubricator Isolat. Valve N/A N/A 65 When De-Enegr.Valve: N/A
VALVE
41 Guiding No. of Ports Cage 1 66 Material Latcher N/A N/A
42 Trim Type Internal Design Standard Balanced 67 Electric Enclosure N/A
43 Rated Travel Leak Class 3/4 in ANSI IV 68 MFR Model N/A N/A
44 Plug/ Ball/ Disk Material S41600 SST 69 Type Quantity N/A N/A
45 Seat Material S41600 SST SWITCHES 70 Contacts / Rating N/A
46 Cage Stem Material CB7Cu-1 SST S31600 SST 71 Switching Position N/A
47 Gasket Material S31600 SST/Graphite 72 Electric Enclosure N/A
48 MFR Model FISHER 657 73 MFR Model FISHER 67CFR
49 Type Diaphragm Spring Return AIR SET 74 Set Pressure 4.2 kgf/cm2-g
50 Size Stroke Time 40i < 8 Sec 75 Filter Gauge 5 Micron min YES
ACTUATOR 51 Air Failure Valve: FO 76 Vol. Tank Booster NO NO
52 Handwheel Location N/A 77 Diffuser Lock-up NO NO
ACCESSORY
53 Mounting Position VERTICAL 78 Fire Safe Fireproof NO NO
54 Spring Range 0.4 - 2.0 kgf/cm2-g 79 Mech. Stop Quick Exa. NO NO
55 Include Pressure (Shutoff) 80 Hydro. Pressure YES
85 Vendor EMERSON 81 Leakage YES
PURCHASE TESTS
86 Manufacturer FISHER 82 Cryogenic N/A
87 Requisition No. R2B-P3-206-02-P-MR-00200 83 NACE Requirement N/A
88 Model No. ET 84 PWHT Requirement N/A
Notes:

INSTRUMENT SPECIFICATION - CONTROL VALVE


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S69.1 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Fieldbus Device Data Sheet
Tag No.: FV -21236
Fieldbus Tag No.:

Service : GA207AB NPTHA TO DA201GA110AB

Basic Fieldbus Function Blocks Segment Information


Analog Input Block (AI) 1 Number Device:
1 22
20 Execution (msec)
Discrete Input Block (DI) 4 Number Segment #: DFJB-21129
2 23
15 Execution Time
3 Bias/Gain Station (BG) 0 Execution (msec) 24 LAS Capable: Yes No
Manual Loader (ML) 0 Number 25 Device Current Draw (mA): 19
4
0 Execution (msec) Device Minimum Voltage: 9.
26
Analog Output Block (AO) 1 Number Device Capacitance: 5 nF
5 20 Execution (msec) Polarity-sensitive: Yes No
27
Discrete Output Block (DO) 1 Number Segment Terminator Location:
6 20 Execution (msec)
28
7 Control Selector (CS)
DD Revision: 3
PID,PI,I Controller (PID) 29
8
20 Execution (msec)
CFF Revision: 1.9
Ratio Station (RA) 30
9
P,PD Controller (PD) 0 Number
10 0 Execution (msec)

* Execution time in msec.

Advanced Function Blocks Notes:

11 Device Control (DC)

12 Output Splitter (OS)

13 Signal Characterizer (SC)

14 Lead Lag (LL)

15 Deadtime (DT)

16 Integrator(Totalizer) (IT)

17 Setpoint Ramp Generator (SPG)

18 Input Selector (IS)

19 Arithmetic (AR)

20 Timer (TMR)

21 Analog Alarm (AAL)

INSTRUMENT SPECIFICATION -FOUNDATION FIELDBUS


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S69.2 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Tag Number : FV -21236

1. Valve will normally be in the closed position. Valve opening will be intermittent and generally short-term.

2. In-Built surge protector is provided by vendor.

1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S69.3 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
1 Tag No. FV -21237
2 Service PTRG HC TO EA204AB
3 P&ID No. Line No. R2B-P3-206-02-A-DTI-00220 4"-P-212211-T-B73T1-N
4 Area Classification Ingress Protection CLASS 1 DIV 2 Gr. B ,C&D, T3 NEMA 4X
GENERAL 5 Ambient Temperature: Unit Min. Max. °C 10 48
6 Allowable Sound dBA Tightness Requirement <85 ANSI IV (standard)
7 Available Air Supply Pressure Unit Min. Max. kgf/cm²-g 4.2 8.0
8 Electric Connection Pneum. Connection 1/2” NPT (F) 1/4” NPT (F)
9 Power Failure Position FC
10 Line Size and Schedule Sch. Outlet Line Sch. 4 in XS 4" XS
PIPE
11 Line Class Rating Pipe Material T-B73T1 300# A106 GR.B, SMLS
LINE
12 Pipe Insulation Thickness Corrosion Allowance N N/A 1.6mm
13 Fluid State Phase Hydrocarbon N/A or other Single Phase
14 Sour Service Special Condition YES N/A
15 Flow Rate Units Min. Nor. Max. kg/h 813 813 4877
16 Inlet Pressure Units Min. Nor. Max. kgf/cm²-g 27 27 27
17 Pressure Drop Units Min. Nor. Max. kgf/cm² 20.5 20.5 20.5
18 Inlet Temperature Units Min. Nor. Max. °C 54 54 54
PROCESS 19 Density Units Min. Nor. Max. kg/m³ 905 905 905
CONDITIONS 20 Viscosity Units Min. Nor. Max. cP 1.032 1.032 1.032
21 Molecular Weight (MW) Specific Gravity @ Oper. 15.5
22 Spec. Heat Ratio (Cp/Cv) Compressibility (Z) 1.3 0.99
23 Vapor Pressure (Liq.) Cavitation or Flashing 14.58 kgf/cm²-a NO
24 Critical Pressure (Liq) Flash (wt%) 32.5 kgf/cm²-a
25 Design Pressure Min. Max. kgf/cm²-g 36.5 kgf/cm²-g
26 Design Temperature Min. Max. 10 °C 120 °C
27 Max.Shutoff DP Solid % 36.5 kgf/cm²
28 Calculated Cv Units Min. Nor. Max. Cv 1 1 6.11
CALCULATED
29 Travel Units Min. Nor. Max. % 30 30 77
RESULTS
30 Noise dBA @1m Units Min. Nor. Max. dBA
31 MFR Model FISHER ET 56 MFR Model FISHER DVC6200F/SC-AD
32 Body Type Single Seat Globe 57 Signal: Inlet Outlet FF Protocol 0-3.5 kgf/cm2
33 Body Size Trim Size 3 in 2 5/16 in 58 Increase Signal Valve: DIRECT
34 End Connec.Size & Rating 3" 300# RF POSITIONER 59 Cam Characteristic LINEAR
35 Rated Cv Characteristic 70.7 EQ% 60 Bypass Gauges N/A YES
36 Body Material WCC Steel 61 Signal Fail. to Valve FC
BODY 37 Bonnet Type Material Plain WCC Steel 62 Electric Enclosure Ex ia IIC T5 , NEMA 4X
AND 38 Flow Direct. Flow Act. To Down FTO 63 MFR Model N/A N/A
TRIM 39 Packing Type Material ISO Seal PTFE 64 Type Power N/A N/A
SOLENOID
40 Lubricator Isolat. Valve N/A N/A 65 When De-Enegr.Valve: N/A
VALVE
41 Guiding No. of Ports Cage 1 66 Material Latcher N/A N/A
42 Trim Type Internal Design Standard Balanced 67 Electric Enclosure N/A
43 Rated Travel Leak Class 1 1/8 in ANSI IV 68 MFR Model N/A N/A
44 Plug/ Ball/ Disk Material S31600 SST/CoCr-A Seat 69 Type Quantity N/A N/A
45 Seat Material R30006 Cobalt Alloy SWITCHES 70 Contacts / Rating N/A
46 Cage Stem Material S31600 SST/ENC S20910 SST 71 Switching Position N/A
47 Gasket Material S31600 SST/Graphite 72 Electric Enclosure N/A
48 MFR Model FISHER 667 73 MFR Model FISHER 67CFR
49 Type Diaphragm Spring Return AIR SET 74 Set Pressure 4.2 kgf/cm2-g
50 Size Stroke Time 40i < 8 Sec 75 Filter Gauge 5 Micron min YES
ACTUATOR 51 Air Failure Valve: FC 76 Vol. Tank Booster NO NO
52 Handwheel Location N/A 77 Diffuser Lock-up NO NO
ACCESSORY
53 Mounting Position VERTICAL 78 Fire Safe Fireproof NO NO
54 Spring Range 0.7 - 2.8 kgf/cm2-g 79 Mech. Stop Quick Exa. NO NO
55 Include Pressure (Shutoff) 80 Hydro. Pressure YES
85 Vendor EMERSON 81 Leakage YES
PURCHASE TESTS
86 Manufacturer FISHER 82 Cryogenic N/A
87 Requisition No. R2B-P3-206-02-P-MR-00200 83 NACE Requirement NACE-0103
88 Model No. ET 84 PWHT Requirement YES
Notes:

INSTRUMENT SPECIFICATION - CONTROL VALVE


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S70.1 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Fieldbus Device Data Sheet
Tag No.: FV -21237
Fieldbus Tag No.:

Service : PTRG HC TO EA204AB

Basic Fieldbus Function Blocks Segment Information


Analog Input Block (AI) 1 Number Device:
1 22
20 Execution (msec)
Discrete Input Block (DI) 4 Number Segment #: DFJB-21100
2 23
15 Execution Time
3 Bias/Gain Station (BG) 0 Execution (msec) 24 LAS Capable: Yes No
Manual Loader (ML) 0 Number 25 Device Current Draw (mA): 19
4
0 Execution (msec) Device Minimum Voltage: 9.
26
Analog Output Block (AO) 1 Number Device Capacitance: 5 nF
5 20 Execution (msec) Polarity-sensitive: Yes No
27
Discrete Output Block (DO) 1 Number Segment Terminator Location:
6 20 Execution (msec)
28
7 Control Selector (CS)
DD Revision: 3
PID,PI,I Controller (PID) 29
8
20 Execution (msec)
CFF Revision: 1.9
Ratio Station (RA) 30
9
P,PD Controller (PD) 0 Number
10 0 Execution (msec)

* Execution time in msec.

Advanced Function Blocks Notes:

11 Device Control (DC)

12 Output Splitter (OS)

13 Signal Characterizer (SC)

14 Lead Lag (LL)

15 Deadtime (DT)

16 Integrator(Totalizer) (IT)

17 Setpoint Ramp Generator (SPG)

18 Input Selector (IS)

19 Arithmetic (AR)

20 Timer (TMR)

21 Analog Alarm (AAL)

INSTRUMENT SPECIFICATION -FOUNDATION FIELDBUS


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S70.2 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Tag Number : FV -21237

1. Vapor Property : MW : 15.5 kg/kgmol. Density : 6.54 kg/m3 , Vapor : 0.096 WT%.

2. In-Built surge protector is provided by vendor.

1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S70.3 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
1 Tag No. FV -21402
2 Service EA404 C4 TO STOR
3 P&ID No. Line No. R2B-P3-206-02-A-DTI-00401 6"-P-214003-B2A1-N
4 Area Classification Ingress Protection CLASS 1 DIV 2 Gr. B ,C&D, T3 NEMA 4X
GENERAL 5 Ambient Temperature: Unit Min. Max. °C 10 48
6 Allowable Sound dBA Tightness Requirement <85 ANSI IV (standard)
7 Available Air Supply Pressure Unit Min. Max. kgf/cm²-g 4.2 8.0
8 Electric Connection Pneum. Connection 1/2” NPT (F) 1/4” NPT (F)
9 Power Failure Position FC
10 Line Size and Schedule Sch. Outlet Line Sch. 6 in STD 6" STD
PIPE
11 Line Class Rating Pipe Material B2A1 300# A106 GR.B, SMLS
LINE
12 Pipe Insulation Thickness Corrosion Allowance N N/A 1.6mm
13 Fluid State Phase Hydrocarbon Liquid Single Phase
14 Sour Service Special Condition N/A N/A
15 Flow Rate Units Min. Nor. Max. m³/h 68 136 150
16 Inlet Pressure Units Min. Nor. Max. kgf/cm²-g 19.39 19.23 19.21
17 Pressure Drop Units Min. Nor. Max. kgf/cm² 14.24 13.84 13.76
18 Inlet Temperature Units Min. Nor. Max. °C 38 38 38
PROCESS 19 Density Units Min. Nor. Max. kg/m³ 565 565 565
CONDITIONS 20 Viscosity Units Min. Nor. Max. cP 0.135 0.135 0.135
21 Molecular Weight (MW) Specific Gravity @ Oper.
22 Spec. Heat Ratio (Cp/Cv) Compressibility (Z)
23 Vapor Pressure (Liq.) Cavitation or Flashing 4.42 kgf/cm²-a Flashing
24 Critical Pressure (Liq) Flash (wt%) 39.73 kgf/cm²-a
25 Design Pressure Min. Max. kgf/cm²-g 24 kgf/cm²-g
26 Design Temperature Min. Max. 10 °C 80 °C
27 Max.Shutoff DP Solid % 24 kgf/cm²
28 Calculated Cv Units Min. Nor. Max. Cv 17.4 35.7 39.6
CALCULATED
29 Travel Units Min. Nor. Max. % 60 76 79
RESULTS
30 Noise dBA @1m Units Min. Nor. Max. dBA 80 83 83
31 MFR Model FISHER ET 56 MFR Model FISHER DVC6200F/SC-AD
32 Body Type Single Seat Globe 57 Signal: Inlet Outlet FF Protocol 0-2.8 kgf/cm2
33 Body Size Trim Size 3 in 2 5/16 in 58 Increase Signal Valve: DIRECT
34 End Connec.Size & Rating 3" 300# RF POSITIONER 59 Cam Characteristic LINEAR
35 Rated Cv Characteristic 70.7 EQ% 60 Bypass Gauges N/A YES
36 Body Material WCC Steel 61 Signal Fail. to Valve FC
BODY 37 Bonnet Type Material Plain WCC Steel 62 Electric Enclosure Ex ia IIC T5 , NEMA 4X
AND 38 Flow Direct. Flow Act. To Down FTO 63 MFR Model N/A N/A
TRIM 39 Packing Type Material Enviro Seal PTFE Carbon 64 Type Power N/A N/A
SOLENOID
40 Lubricator Isolat. Valve N/A N/A 65 When De-Enegr.Valve: N/A
VALVE
41 Guiding No. of Ports Cage 1 66 Material Latcher N/A N/A
42 Trim Type Internal Design Standard Balanced 67 Electric Enclosure N/A
43 Rated Travel Leak Class 1 1/8 in ANSI IV 68 MFR Model N/A N/A
44 Plug/ Ball/ Disk Material S31600 SST/CoCr-A Seat 69 Type Quantity N/A N/A
45 Seat Material CoCr-A Seat SWITCHES 70 Contacts / Rating N/A
46 Cage Stem Material S31600 SST/ ENCS31600 SST 71 Switching Position N/A
47 Gasket Material S31600 SST/Graphite 72 Electric Enclosure N/A
48 MFR Model FISHER 667 73 MFR Model FISHER 67CFR
49 Type Diaphragm Spring Return AIR SET 74 Set Pressure 4.2 kgf/cm2-g
50 Size Stroke Time 40i < 8 Sec 75 Filter Gauge 5 Micron min YES
ACTUATOR 51 Air Failure Valve: FC 76 Vol. Tank Booster NO NO
52 Handwheel Location N/A 77 Diffuser Lock-up NO NO
ACCESSORY
53 Mounting Position VERTICAL 78 Fire Safe Fireproof NO NO
54 Spring Range 0.8 - 2.4 kgf/cm2-g 79 Mech. Stop Quick Exa. NO NO
55 Include Pressure (Shutoff) 80 Hydro. Pressure YES
85 Vendor EMERSON 81 Leakage YES
PURCHASE TESTS
86 Manufacturer FISHER 82 Cryogenic N/A
87 Requisition No. R2B-P3-206-02-P-MR-00200 83 NACE Requirement N/A
88 Model No. ET 84 PWHT Requirement N/A
Notes:

INSTRUMENT SPECIFICATION - CONTROL VALVE


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S71.1 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Fieldbus Device Data Sheet
Tag No.: FV -21402
Fieldbus Tag No.:

Service : EA404 C4 TO STOR

Basic Fieldbus Function Blocks Segment Information


Analog Input Block (AI) 1 Number Device:
1 22
20 Execution (msec)
Discrete Input Block (DI) 4 Number Segment #: DFJB-21152
2 23
15 Execution Time
3 Bias/Gain Station (BG) 0 Execution (msec) 24 LAS Capable: Yes No
Manual Loader (ML) 0 Number 25 Device Current Draw (mA): 19
4
0 Execution (msec) Device Minimum Voltage: 9.
26
Analog Output Block (AO) 1 Number Device Capacitance: 5 nF
5 20 Execution (msec) Polarity-sensitive: Yes No
27
Discrete Output Block (DO) 1 Number Segment Terminator Location:
6 20 Execution (msec)
28
7 Control Selector (CS)
DD Revision: 3
PID,PI,I Controller (PID) 29
8
20 Execution (msec)
CFF Revision: 1.9
Ratio Station (RA) 30
9
P,PD Controller (PD) 0 Number
10 0 Execution (msec)

* Execution time in msec.

Advanced Function Blocks Notes:

11 Device Control (DC)

12 Output Splitter (OS)

13 Signal Characterizer (SC)

14 Lead Lag (LL)

15 Deadtime (DT)

16 Integrator(Totalizer) (IT)

17 Setpoint Ramp Generator (SPG)

18 Input Selector (IS)

19 Arithmetic (AR)

20 Timer (TMR)

21 Analog Alarm (AAL)

INSTRUMENT SPECIFICATION -FOUNDATION FIELDBUS


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S71.2 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Tag Number : FV -21402

1. Flashing service for minimum flow case. Control valve data -


Minimum Case - Liq Flow: 60.3 m3/h; Vap Flow: 1379 normal m3/h; Temp: 24.9 °C; Liq Density: 578 kg/m^3; Liq Visc.: 0.152 cP; Vap MW: - ; Vap Z:
1.00 ; Vap Cp/Cv(Real): 1.009

2. In-Built surge protector is provided by vendor.

1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S71.3 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
1 Tag No. FV -21403
2 Service FA404 LPS COND TO COND
3 P&ID No. Line No. R2B-P3-206-02-A-DTI-00402 4"-CACBP-214003-T-B04T1-EC
4 Area Classification Ingress Protection CLASS 1 DIV 2 Gr. B ,C&D, T3 NEMA 4X
GENERAL 5 Ambient Temperature: Unit Min. Max. °C 10 48
6 Allowable Sound dBA Tightness Requirement <85 ANSI IV (standard)
7 Available Air Supply Pressure Unit Min. Max. kgf/cm²-g 4.2 8.0
8 Electric Connection Pneum. Connection 1/2” NPT (F) 1/4” NPT (F)
9 Power Failure Position FC
10 Line Size and Schedule Sch. Outlet Line Sch. 4 in STD 4" STD
PIPE
11 Line Class Rating Pipe Material T-B04T1 300# A106 GR.B, SMLS
LINE
12 Pipe Insulation Thickness Corrosion Allowance EC 65mm 1.6mm
13 Fluid State Phase LP Steam Condensate Liquid Single Phase
14 Sour Service Special Condition N/A N/A
15 Flow Rate Units Min. Nor. Max. m³/h 7.45 14.9 16.39
16 Inlet Pressure Units Min. Nor. Max. kgf/cm²-g 3.349 3.341 3.339
17 Pressure Drop Units Min. Nor. Max. kgf/cm² 2.999 2.75 2.989
18 Inlet Temperature Units Min. Nor. Max. °C 144.1 144.1 144.1
PROCESS 19 Density Units Min. Nor. Max. kg/m³ 923 923 923
CONDITIONS 20 Viscosity Units Min. Nor. Max. cP 0.2 0.2 0.2
21 Molecular Weight (MW) Specific Gravity @ Oper.
22 Spec. Heat Ratio (Cp/Cv) Compressibility (Z)
23 Vapor Pressure (Liq.) Cavitation or Flashing 4.13 kgf/cm²-a Flashing
24 Critical Pressure (Liq) Flash (wt%) 225.55 kgf/cm²-a
25 Design Pressure Min. Max. -1.033 kgf/cm²-g 18.5 kgf/cm²-g
26 Design Temperature Min. Max. 10 °C 200 °C
27 Max.Shutoff DP Solid % 18.5 kgf/cm²
28 Calculated Cv Units Min. Nor. Max. Cv 13.1 26.8 29.7
CALCULATED
29 Travel Units Min. Nor. Max. % 54 71 74
RESULTS
30 Noise dBA @1m Units Min. Nor. Max. dBA 85 85 85
31 MFR Model FISHER ET 56 MFR Model FISHER DVC6200F/SC-AD
32 Body Type Single Seat Globe 57 Signal: Inlet Outlet FF Protocol 0-2.8 kgf/cm2
33 Body Size Trim Size 2 in 2 5/16 in 58 Increase Signal Valve: DIRECT
34 End Connec.Size & Rating 2" 300# RF POSITIONER 59 Cam Characteristic LINEAR
35 Rated Cv Characteristic 59.7 EQ% 60 Bypass Gauges N/A YES
36 Body Material WCC Steel 61 Signal Fail. to Valve FC
BODY 37 Bonnet Type Material Plain WCC Steel 62 Electric Enclosure Ex ia IIC T5 , NEMA 4X
AND 38 Flow Direct. Flow Act. To Down FTO 63 MFR Model N/A N/A
TRIM 39 Packing Type Material ISO Seal PTFE 64 Type Power N/A N/A
SOLENOID
40 Lubricator Isolat. Valve N/A N/A 65 When De-Enegr.Valve: N/A
VALVE
41 Guiding No. of Ports Cage 1 66 Material Latcher N/A N/A
42 Trim Type Internal Design Standard Balanced 67 Electric Enclosure N/A
43 Rated Travel Leak Class 1 1/8 in ANSI IV 68 MFR Model N/A N/A
44 Plug/ Ball/ Disk Material S31600 SST/CoCr-A Seat 69 Type Quantity N/A N/A
45 Seat Material CoCr-A Seat SWITCHES 70 Contacts / Rating N/A
46 Cage Stem Material S31600 SST/ ENCS31600 SST 71 Switching Position N/A
47 Gasket Material S31600 SST/Graphite 72 Electric Enclosure N/A
48 MFR Model FISHER 667 73 MFR Model FISHER 67CFR
49 Type Diaphragm Spring Return AIR SET 74 Set Pressure 4.2 kgf/cm2-g
50 Size Stroke Time 40i < 8 Sec 75 Filter Gauge 5 Micron min YES
ACTUATOR 51 Air Failure Valve: FC 76 Vol. Tank Booster NO NO
52 Handwheel Location N/A 77 Diffuser Lock-up NO NO
ACCESSORY
53 Mounting Position VERTICAL 78 Fire Safe Fireproof NO NO
54 Spring Range 0.7 - 2.4 kgf/cm2-g 79 Mech. Stop Quick Exa. NO NO
55 Include Pressure (Shutoff) 80 Hydro. Pressure YES
85 Vendor EMERSON 81 Leakage YES
PURCHASE TESTS
86 Manufacturer FISHER 82 Cryogenic N/A
87 Requisition No. R2B-P3-206-02-P-MR-00200 83 NACE Requirement N/A
88 Model No. ET 84 PWHT Requirement N/A
Notes:

INSTRUMENT SPECIFICATION - CONTROL VALVE


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S72.1 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Fieldbus Device Data Sheet
Tag No.: FV -21403
Fieldbus Tag No.:

Service : FA404 LPS COND TO COND

Basic Fieldbus Function Blocks Segment Information


Analog Input Block (AI) 1 Number Device:
1 22
20 Execution (msec)
Discrete Input Block (DI) 4 Number Segment #: DFJB-21143
2 23
15 Execution Time
3 Bias/Gain Station (BG) 0 Execution (msec) 24 LAS Capable: Yes No
Manual Loader (ML) 0 Number 25 Device Current Draw (mA): 19
4
0 Execution (msec) Device Minimum Voltage: 9.
26
Analog Output Block (AO) 1 Number Device Capacitance: 5 nF
5 20 Execution (msec) Polarity-sensitive: Yes No
27
Discrete Output Block (DO) 1 Number Segment Terminator Location:
6 20 Execution (msec)
28
7 Control Selector (CS)
DD Revision: 3
PID,PI,I Controller (PID) 29
8
20 Execution (msec)
CFF Revision: 1.9
Ratio Station (RA) 30
9
P,PD Controller (PD) 0 Number
10 0 Execution (msec)

* Execution time in msec.

Advanced Function Blocks Notes:

11 Device Control (DC)

12 Output Splitter (OS)

13 Signal Characterizer (SC)

14 Lead Lag (LL)

15 Deadtime (DT)

16 Integrator(Totalizer) (IT)

17 Setpoint Ramp Generator (SPG)

18 Input Selector (IS)

19 Arithmetic (AR)

20 Timer (TMR)

21 Analog Alarm (AAL)

INSTRUMENT SPECIFICATION -FOUNDATION FIELDBUS


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S72.2 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Tag Number : FV -21403

1. Control Valve Outlet data -


Minimum Case - Liq Flow: 30.3 m3/h; Steam Flow: 3100 kg/h; Temp: 147 °C; Liq Density: 920 kg/m^3; Liq Visc.: 0.195 cP; Vap MW: 18.02 ; Vap Z:
0.958 ; Vap Cp/Cv(Real): 1.318
Normal Case - Liq Flow: 31.2 m3/h; Steam Flow: 2281 kg/h; Temp: 147 °C; Liq Density: 920 kg/m^3; Liq Visc.: 0.195 cP; Vap MW: 18.02 ; Vap Z: 0.958
; Vap Cp/Cv(Real): 1.318

2. In-Built surge protector is provided by vendor.

1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S72.3 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
1 Tag No. FV -21408
2 Service DCU C3 TO DF402
3 P&ID No. Line No. R2B-P3-206-02-A-DTI-00407 4"-P-214025-B2A1-N
4 Area Classification Ingress Protection CLASS 1 DIV 2 Gr. B ,C&D, T3 NEMA 4X
GENERAL 5 Ambient Temperature: Unit Min. Max. °C 10 48
6 Allowable Sound dBA Tightness Requirement <85 ANSI IV (standard)
7 Available Air Supply Pressure Unit Min. Max. kgf/cm²-g 4.2 8.0
8 Electric Connection Pneum. Connection 1/2” NPT (F) 1/4” NPT (F)
9 Power Failure Position FC
10 Line Size and Schedule Sch. Outlet Line Sch. 4 in STD 4" STD
PIPE
11 Line Class Rating Pipe Material B2A1 300# A106 GR.B, SMLS
LINE
12 Pipe Insulation Thickness Corrosion Allowance N N/A 1.6mm
13 Fluid State Phase Hydrocarbon Liquid Single Phase
14 Sour Service Special Condition N/A N/A
15 Flow Rate Units Min. Nor. Max. m³/h 39.3 39.3 43.2
16 Inlet Pressure Units Min. Nor. Max. kgf/cm²-g 26.82 26.82 26.67
17 Pressure Drop Units Min. Nor. Max. kgf/cm² 2.084 2.033 1.868
18 Inlet Temperature Units Min. Nor. Max. °C 40 40 40
PROCESS 19 Density Units Min. Nor. Max. kg/m³ 476 476 476
CONDITIONS 20 Viscosity Units Min. Nor. Max. cP 0.079 0.079 0.079
21 Molecular Weight (MW) Specific Gravity @ Oper.
22 Spec. Heat Ratio (Cp/Cv) Compressibility (Z)
23 Vapor Pressure (Liq.) Cavitation or Flashing 15.12 kgf/cm²-a NO
24 Critical Pressure (Liq) Flash (wt%) 44.42 kgf/cm²-a
25 Design Pressure Min. Max. kgf/cm²-g 44.6 kgf/cm²-g
26 Design Temperature Min. Max. 10 °C 150 °C
27 Max.Shutoff DP Solid % 44.6 kgf/cm²
28 Calculated Cv Units Min. Nor. Max. Cv 22.3 22.5 26.
CALCULATED
29 Travel Units Min. Nor. Max. % 37 37 43
RESULTS
30 Noise dBA @1m Units Min. Nor. Max. dBA 50 50 50
31 MFR Model FISHER EZ 56 MFR Model FISHER DVC6200F/SC-AD
32 Body Type Single Seat Globe 57 Signal: Inlet Outlet FF Protocol 0-3.5 kgf/cm2
33 Body Size Trim Size 2 in 2 in 58 Increase Signal Valve: DIRECT
34 End Connec.Size & Rating 2" 300# RF POSITIONER 59 Cam Characteristic LINEAR
35 Rated Cv Characteristic 52.4 Linear 60 Bypass Gauges N/A YES
36 Body Material WCC Steel 61 Signal Fail. to Valve FC
BODY 37 Bonnet Type Material Plain WCC Steel 62 Electric Enclosure Ex ia IIC T5 , NEMA 4X
AND 38 Flow Direct. Flow Act. To Up FTO 63 MFR Model N/A N/A
TRIM 39 Packing Type Material Enviro Seal PTFE Carbon 64 Type Power N/A N/A
SOLENOID
40 Lubricator Isolat. Valve N/A N/A 65 When De-Enegr.Valve: N/A
VALVE
41 Guiding No. of Ports Post 1 66 Material Latcher N/A N/A
42 Trim Type Internal Design Standard Unbalanced 67 Electric Enclosure N/A
43 Rated Travel Leak Class 1 1/8 in ANSI IV 68 MFR Model N/A N/A
44 Plug/ Ball/ Disk Material S41600 SST 69 Type Quantity N/A N/A
45 Seat Material S41600 SST SWITCHES 70 Contacts / Rating N/A
46 Cage Stem Material N/A S31600 SST 71 Switching Position N/A
47 Gasket Material S31600 SST/Graphite 72 Electric Enclosure N/A
48 MFR Model FISHER 667 73 MFR Model FISHER 67CFR
49 Type Diaphragm Spring Return AIR SET 74 Set Pressure 4.2 kgf/cm2-g
50 Size Stroke Time 45i < 8 Sec 75 Filter Gauge 5 Micron min YES
ACTUATOR 51 Air Failure Valve: FC 76 Vol. Tank Booster NO NO
52 Handwheel Location N/A 77 Diffuser Lock-up NO NO
ACCESSORY
53 Mounting Position VERTICAL 78 Fire Safe Fireproof NO NO
54 Spring Range 1.6 - 2.8 kgf/cm2-g 79 Mech. Stop Quick Exa. NO NO
55 Include Pressure (Shutoff) 80 Hydro. Pressure YES
85 Vendor EMERSON 81 Leakage YES
PURCHASE TESTS
86 Manufacturer FISHER 82 Cryogenic N/A
87 Requisition No. R2B-P3-206-02-P-MR-00200 83 NACE Requirement N/A
88 Model No. EZ 84 PWHT Requirement N/A
Notes:

INSTRUMENT SPECIFICATION - CONTROL VALVE


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S73.1 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Fieldbus Device Data Sheet
Tag No.: FV -21408
Fieldbus Tag No.:

Service : DCU C3 TO DF402

Basic Fieldbus Function Blocks Segment Information


Analog Input Block (AI) 1 Number Device:
1 22
20 Execution (msec)
Discrete Input Block (DI) 4 Number Segment #: DFJB-21153
2 23
15 Execution Time
3 Bias/Gain Station (BG) 0 Execution (msec) 24 LAS Capable: Yes No
Manual Loader (ML) 0 Number 25 Device Current Draw (mA): 19
4
0 Execution (msec) Device Minimum Voltage: 9.
26
Analog Output Block (AO) 1 Number Device Capacitance: 5 nF
5 20 Execution (msec) Polarity-sensitive: Yes No
27
Discrete Output Block (DO) 1 Number Segment Terminator Location:
6 20 Execution (msec)
28
7 Control Selector (CS)
DD Revision: 3
PID,PI,I Controller (PID) 29
8
20 Execution (msec)
CFF Revision: 1.9
Ratio Station (RA) 30
9
P,PD Controller (PD) 0 Number
10 0 Execution (msec)

* Execution time in msec.

Advanced Function Blocks Notes:

11 Device Control (DC)

12 Output Splitter (OS)

13 Signal Characterizer (SC)

14 Lead Lag (LL)

15 Deadtime (DT)

16 Integrator(Totalizer) (IT)

17 Setpoint Ramp Generator (SPG)

18 Input Selector (IS)

19 Arithmetic (AR)

20 Timer (TMR)

21 Analog Alarm (AAL)

INSTRUMENT SPECIFICATION -FOUNDATION FIELDBUS


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S73.2 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Tag Number : FV -21408

1. In-Built surge protector is provided by vendor.

1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S73.3 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
1 Tag No. FV -21409
2 Service STOR C3 TO DF402
3 P&ID No. Line No. R2B-P3-206-02-A-DTI-00407 4"-P-214026-B2A1-N
4 Area Classification Ingress Protection CLASS 1 DIV 2 Gr. B ,C&D, T3 NEMA 4X
GENERAL 5 Ambient Temperature: Unit Min. Max. °C 10 48
6 Allowable Sound dBA Tightness Requirement <85 ANSI IV (standard)
7 Available Air Supply Pressure Unit Min. Max. kgf/cm²-g 4.2 8.0
8 Electric Connection Pneum. Connection 1/2” NPT (F) 1/4” NPT (F)
9 Power Failure Position FC
10 Line Size and Schedule Sch. Outlet Line Sch. 4 in STD 4" STD
PIPE
11 Line Class Rating Pipe Material B2A1 300# A106 GR.B, SMLS
LINE
12 Pipe Insulation Thickness Corrosion Allowance N N/A 1.6mm
13 Fluid State Phase Hydrocarbon Liquid Single Phase
14 Sour Service Special Condition N/A N/A
15 Flow Rate Units Min. Nor. Max. m³/h 21.9 43.8 48.2
16 Inlet Pressure Units Min. Nor. Max. kgf/cm²-g 27.27 26.62 26.43
17 Pressure Drop Units Min. Nor. Max. kgf/cm² 2.554 1.818 1.612
18 Inlet Temperature Units Min. Nor. Max. °C 30 30 30
PROCESS 19 Density Units Min. Nor. Max. kg/m³ 498 498 498
CONDITIONS 20 Viscosity Units Min. Nor. Max. cP 0.077 0.077 0.077
21 Molecular Weight (MW) Specific Gravity @ Oper.
22 Spec. Heat Ratio (Cp/Cv) Compressibility (Z)
23 Vapor Pressure (Liq.) Cavitation or Flashing 12.77 kgf/cm²-a NO
24 Critical Pressure (Liq) Flash (wt%) 45.78 kgf/cm²-a
25 Design Pressure Min. Max. kgf/cm²-g 48 kgf/cm²-g
26 Design Temperature Min. Max. 10 °C 66 °C
27 Max.Shutoff DP Solid % 48 kgf/cm²
28 Calculated Cv Units Min. Nor. Max. Cv 11.3 27.4 32.2
CALCULATED
29 Travel Units Min. Nor. Max. % 19 45 53
RESULTS
30 Noise dBA @1m Units Min. Nor. Max. dBA 50 50 50
31 MFR Model FISHER EZ 56 MFR Model FISHER DVC6200F/SC-AD
32 Body Type Single Seat Globe 57 Signal: Inlet Outlet FF Protocol 0-3.5 kgf/cm2
33 Body Size Trim Size 2 in 2 in 58 Increase Signal Valve: DIRECT
34 End Connec.Size & Rating 2" 300# RF POSITIONER 59 Cam Characteristic LINEAR
35 Rated Cv Characteristic 52.4 Linear 60 Bypass Gauges N/A YES
36 Body Material WCC Steel 61 Signal Fail. to Valve FC
BODY 37 Bonnet Type Material Plain WCC Steel 62 Electric Enclosure Ex ia IIC T5 , NEMA 4X
AND 38 Flow Direct. Flow Act. To Up FTO 63 MFR Model N/A N/A
TRIM 39 Packing Type Material Enviro Seal PTFE Carbon 64 Type Power N/A N/A
SOLENOID
40 Lubricator Isolat. Valve N/A N/A 65 When De-Enegr.Valve: N/A
VALVE
41 Guiding No. of Ports Post 1 66 Material Latcher N/A N/A
42 Trim Type Internal Design Standard Unbalanced 67 Electric Enclosure N/A
43 Rated Travel Leak Class 1 1/8 in ANSI IV 68 MFR Model N/A N/A
44 Plug/ Ball/ Disk Material S41600 SST 69 Type Quantity N/A N/A
45 Seat Material S41600 SST SWITCHES 70 Contacts / Rating N/A
46 Cage Stem Material N/A S31600 SST 71 Switching Position N/A
47 Gasket Material S31600 SST/Graphite 72 Electric Enclosure N/A
48 MFR Model FISHER 667 73 MFR Model FISHER 67CFR
49 Type Diaphragm Spring Return AIR SET 74 Set Pressure 4.2 kgf/cm2-g
50 Size Stroke Time 46i < 8 Sec 75 Filter Gauge 5 Micron min YES
ACTUATOR 51 Air Failure Valve: FC 76 Vol. Tank Booster NO NO
52 Handwheel Location N/A 77 Diffuser Lock-up NO NO
ACCESSORY
53 Mounting Position VERTICAL 78 Fire Safe Fireproof NO NO
54 Spring Range 1.3 - 2.6 kgf/cm2-g 79 Mech. Stop Quick Exa. NO NO
55 Include Pressure (Shutoff) 80 Hydro. Pressure YES
85 Vendor EMERSON 81 Leakage YES
PURCHASE TESTS
86 Manufacturer FISHER 82 Cryogenic N/A
87 Requisition No. R2B-P3-206-02-P-MR-00200 83 NACE Requirement N/A
88 Model No. EZ 84 PWHT Requirement N/A
Notes:

INSTRUMENT SPECIFICATION - CONTROL VALVE


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S74.1 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Fieldbus Device Data Sheet
Tag No.: FV -21409
Fieldbus Tag No.:

Service : STOR C3 TO DF402

Basic Fieldbus Function Blocks Segment Information


Analog Input Block (AI) 1 Number Device:
1 22
20 Execution (msec)
Discrete Input Block (DI) 4 Number Segment #: DFJB-21153
2 23
15 Execution Time
3 Bias/Gain Station (BG) 0 Execution (msec) 24 LAS Capable: Yes No
Manual Loader (ML) 0 Number 25 Device Current Draw (mA): 19
4
0 Execution (msec) Device Minimum Voltage: 9.
26
Analog Output Block (AO) 1 Number Device Capacitance: 5 nF
5 20 Execution (msec) Polarity-sensitive: Yes No
27
Discrete Output Block (DO) 1 Number Segment Terminator Location:
6 20 Execution (msec)
28
7 Control Selector (CS)
DD Revision: 3
PID,PI,I Controller (PID) 29
8
20 Execution (msec)
CFF Revision: 1.9
Ratio Station (RA) 30
9
P,PD Controller (PD) 0 Number
10 0 Execution (msec)

* Execution time in msec.

Advanced Function Blocks Notes:

11 Device Control (DC)

12 Output Splitter (OS)

13 Signal Characterizer (SC)

14 Lead Lag (LL)

15 Deadtime (DT)

16 Integrator(Totalizer) (IT)

17 Setpoint Ramp Generator (SPG)

18 Input Selector (IS)

19 Arithmetic (AR)

20 Timer (TMR)

21 Analog Alarm (AAL)

INSTRUMENT SPECIFICATION -FOUNDATION FIELDBUS


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S74.2 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Tag Number : FV -21409

1. In-Built surge protector is provided by vendor.

1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S74.3 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
1 Tag No. FV -21410
2 Service DF402 BTM TO DF403
3 P&ID No. Line No. R2B-P3-206-02-A-DTI-00407 6"-P-214029-B2A1-EC
4 Area Classification Ingress Protection CLASS 1 DIV 2 Gr. B ,C&D, T3 NEMA 4X
GENERAL 5 Ambient Temperature: Unit Min. Max. °C 10 48
6 Allowable Sound dBA Tightness Requirement <85 ANSI IV (standard)
7 Available Air Supply Pressure Unit Min. Max. kgf/cm²-g 4.2 8.0
8 Electric Connection Pneum. Connection 1/2” NPT (F) 1/4” NPT (F)
9 Power Failure Position FC
10 Line Size and Schedule Sch. Outlet Line Sch. 6 in STD 6" STD
PIPE
11 Line Class Rating Pipe Material B2A1 300# A106 GR.B, SMLS
LINE
12 Pipe Insulation Thickness Corrosion Allowance EC 65mm 1.6mm
13 Fluid State Phase Hydrocarbon Liquid Single Phase
14 Sour Service Special Condition N/A N/A
15 Flow Rate Units Min. Nor. Max. m³/h 43.1 143.6 158
16 Inlet Pressure Units Min. Nor. Max. kgf/cm²-g 23.62 23.58 23.58
17 Pressure Drop Units Min. Nor. Max. kgf/cm² 11.45 10.8 10.66
18 Inlet Temperature Units Min. Nor. Max. °C 61 61 61
PROCESS 19 Density Units Min. Nor. Max. kg/m³ 431 431 431
CONDITIONS 20 Viscosity Units Min. Nor. Max. cP 0.057 0.057 0.057
21 Molecular Weight (MW) Specific Gravity @ Oper.
22 Spec. Heat Ratio (Cp/Cv) Compressibility (Z)
23 Vapor Pressure (Liq.) Cavitation or Flashing 24.59 kgf/cm²-a Flashing
24 Critical Pressure (Liq) Flash (wt%) 45.29 kgf/cm²-a
25 Design Pressure Min. Max. kgf/cm²-g 26.5 kgf/cm²-g
26 Design Temperature Min. Max. 10 °C 120 °C
27 Max.Shutoff DP Solid % 26.5 kgf/cm²
28 Calculated Cv Units Min. Nor. Max. Cv 15.7 53.4 59.
CALCULATED
29 Travel Units Min. Nor. Max. % 19 54 58
RESULTS
30 Noise dBA @1m Units Min. Nor. Max. dBA 85 85 85
31 MFR Model FISHER ET 56 MFR Model FISHER DVC6200F/SC-AD
32 Body Type Single Seat Globe 57 Signal: Inlet Outlet FF Protocol 0-2.8 kgf/cm2
33 Body Size Trim Size 3 in 2 5/16 in 58 Increase Signal Valve: DIRECT
34 End Connec.Size & Rating 3" 300# RF POSITIONER 59 Cam Characteristic LINEAR
35 Rated Cv Characteristic 102 Linear 60 Bypass Gauges N/A YES
36 Body Material WCC Steel 61 Signal Fail. to Valve FC
BODY 37 Bonnet Type Material Plain WCC Steel 62 Electric Enclosure Ex ia IIC T5 , NEMA 4X
AND 38 Flow Direct. Flow Act. To Down FTO 63 MFR Model N/A N/A
TRIM 39 Packing Type Material ISO Seal PTFE 64 Type Power N/A N/A
SOLENOID
40 Lubricator Isolat. Valve N/A N/A 65 When De-Enegr.Valve: N/A
VALVE
41 Guiding No. of Ports Cage 1 66 Material Latcher N/A N/A
42 Trim Type Internal Design Standard Balanced 67 Electric Enclosure N/A
43 Rated Travel Leak Class 1 1/8 in ANSI IV 68 MFR Model N/A N/A
44 Plug/ Ball/ Disk Material S31600 SST/CoCr-A Seat 69 Type Quantity N/A N/A
45 Seat Material CoCr-A Seat SWITCHES 70 Contacts / Rating N/A
46 Cage Stem Material S31600 SST/ ENCS31600 SST 71 Switching Position N/A
47 Gasket Material S31600 SST/Graphite 72 Electric Enclosure N/A
48 MFR Model FISHER 667 73 MFR Model FISHER 67CFR
49 Type Diaphragm Spring Return AIR SET 74 Set Pressure 4.2 kgf/cm2-g
50 Size Stroke Time 40i < 8 Sec 75 Filter Gauge 5 Micron min YES
ACTUATOR 51 Air Failure Valve: FC 76 Vol. Tank Booster NO NO
52 Handwheel Location N/A 77 Diffuser Lock-up NO NO
ACCESSORY
53 Mounting Position VERTICAL 78 Fire Safe Fireproof NO NO
54 Spring Range 0.7 - 2.0 kgf/cm2-g 79 Mech. Stop Quick Exa. NO NO
55 Include Pressure (Shutoff) 80 Hydro. Pressure YES
85 Vendor EMERSON 81 Leakage YES
PURCHASE TESTS
86 Manufacturer FISHER 82 Cryogenic N/A
87 Requisition No. R2B-P3-206-02-P-MR-00200 83 NACE Requirement N/A
88 Model No. ET 84 PWHT Requirement N/A
Notes:

INSTRUMENT SPECIFICATION - CONTROL VALVE


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S75.1 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Fieldbus Device Data Sheet
Tag No.: FV -21410
Fieldbus Tag No.:

Service : DF402 BTM TO DF403

Basic Fieldbus Function Blocks Segment Information


Analog Input Block (AI) 1 Number Device:
1 22
20 Execution (msec)
Discrete Input Block (DI) 4 Number Segment #: DFJB-21144
2 23
15 Execution Time
3 Bias/Gain Station (BG) 0 Execution (msec) 24 LAS Capable: Yes No
Manual Loader (ML) 0 Number 25 Device Current Draw (mA): 19
4
0 Execution (msec) Device Minimum Voltage: 9.
26
Analog Output Block (AO) 1 Number Device Capacitance: 5 nF
5 20 Execution (msec) Polarity-sensitive: Yes No
27
Discrete Output Block (DO) 1 Number Segment Terminator Location:
6 20 Execution (msec)
28
7 Control Selector (CS)
DD Revision: 3
PID,PI,I Controller (PID) 29
8
20 Execution (msec)
CFF Revision: 1.9
Ratio Station (RA) 30
9
P,PD Controller (PD) 0 Number
10 0 Execution (msec)

* Execution time in msec.

Advanced Function Blocks Notes:

11 Device Control (DC)

12 Output Splitter (OS)

13 Signal Characterizer (SC)

14 Lead Lag (LL)

15 Deadtime (DT)

16 Integrator(Totalizer) (IT)

17 Setpoint Ramp Generator (SPG)

18 Input Selector (IS)

19 Arithmetic (AR)

20 Timer (TMR)

21 Analog Alarm (AAL)

INSTRUMENT SPECIFICATION -FOUNDATION FIELDBUS


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S75.2 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Tag Number : FV -21410

1. Control Valve Outlet data -


Minimum Case - Liq Flow: 28.5 m3/h; Vap Flow: 2444 normal m3/h; Temp: 33oC; Liq Density: 487 kg/m^3; Liq Visc.: 0.077 cP; Vap MW: 42.95; Vap Z:
0.781; Vap Cp/Cv(Real): 1.102.
Normal Case - Liq Flow: 95.2 m3/h; Vap Flow: 8147 normal m3/h; Temp: 33oC; Liq Density: 487 kg/m^3; Liq Visc.: 0.077 cP; Vap MW: 42.95; Vap Z:
0.781; Vap Cp/Cv(Real): 1.102.
Maximum Case - Liq Flow: 104.7 m3/h; Vap Flow: 8962 normal m3/h; Temp: 33oC; Liq Density: 487 kg/m^3; Liq Visc.: 0.077 cP; Vap MW: 42.95; Vap
Z: 0.781; Vap Cp/Cv(Real): 1.102.

2. In-Built surge protector is provided by vendor.

1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S75.3 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
1 Tag No. FV -21411
2 Service FA405 LPS COND TO COND
3 P&ID No. Line No. R2B-P3-206-02-A-DTI-00407 4"-CACBP-214103-T-B04T1-PP
4 Area Classification Ingress Protection CLASS 1 DIV 2 Gr. B ,C&D, T3 NEMA 4X
GENERAL 5 Ambient Temperature: Unit Min. Max. °C 10 48
6 Allowable Sound dBA Tightness Requirement <85 ANSI IV (standard)
7 Available Air Supply Pressure Unit Min. Max. kgf/cm²-g 4.2 8.0
8 Electric Connection Pneum. Connection 1/2” NPT (F) 1/4” NPT (F)
9 Power Failure Position FC
10 Line Size and Schedule Sch. Outlet Line Sch. 4 in STD 4" STD
PIPE
11 Line Class Rating Pipe Material T-B04T1 300# A106 GR.B, SMLS
LINE
12 Pipe Insulation Thickness Corrosion Allowance PP 40mm 1.6mm
13 Fluid State Phase LP Steam Condensate Liquid Single Phase
14 Sour Service Special Condition N/A N/A
15 Flow Rate Units Min. Nor. Max. m³/h 5.05 10.1 11.11
16 Inlet Pressure Units Min. Nor. Max. kgf/cm²-g 3.455 3.453 3.451
17 Pressure Drop Units Min. Nor. Max. kgf/cm² 3.105 3.103 3.101
18 Inlet Temperature Units Min. Nor. Max. °C 144.1 144.1 144.1
PROCESS 19 Density Units Min. Nor. Max. kg/m³ 900 923 923
CONDITIONS 20 Viscosity Units Min. Nor. Max. cP 0.2 0.2 0.2
21 Molecular Weight (MW) Specific Gravity @ Oper.
22 Spec. Heat Ratio (Cp/Cv) Compressibility (Z)
23 Vapor Pressure (Liq.) Cavitation or Flashing 4.13 kgf/cm²-a Flashing
24 Critical Pressure (Liq) Flash (wt%) 225.55 kgf/cm²-a
25 Design Pressure Min. Max. -1.033 kgf/cm²-g 20.5 kgf/cm²-g
26 Design Temperature Min. Max. 10 °C 200 °C
27 Max.Shutoff DP Solid % 20.5 kgf/cm²
28 Calculated Cv Units Min. Nor. Max. Cv 7.49 15.3 16.9
CALCULATED
29 Travel Units Min. Nor. Max. % 37 63 67
RESULTS
30 Noise dBA @1m Units Min. Nor. Max. dBA 85 85 85
31 MFR Model FISHER ES 56 MFR Model FISHER DVC6200F/SC-AD
32 Body Type Single Seat Globe 57 Signal: Inlet Outlet FF Protocol 0-2.8 kgf/cm2
33 Body Size Trim Size 2 in 1 5/16 in 58 Increase Signal Valve: DIRECT
34 End Connec.Size & Rating 2" 300# RF POSITIONER 59 Cam Characteristic LINEAR
35 Rated Cv Characteristic 30.9 Linear 60 Bypass Gauges N/A YES
36 Body Material WCC Steel 61 Signal Fail. to Valve FC
BODY 37 Bonnet Type Material Plain WCC Steel 62 Electric Enclosure Ex ia IIC T5 , NEMA 4X
AND 38 Flow Direct. Flow Act. To Up FTO 63 MFR Model N/A N/A
TRIM 39 Packing Type Material ISO Seal PTFE 64 Type Power N/A N/A
SOLENOID
40 Lubricator Isolat. Valve N/A N/A 65 When De-Enegr.Valve: N/A
VALVE
41 Guiding No. of Ports Cage 1 66 Material Latcher N/A N/A
42 Trim Type Internal Design Standard Unbalanced 67 Electric Enclosure N/A
43 Rated Travel Leak Class 3/4 in ANSI IV 68 MFR Model N/A N/A
44 Plug/ Ball/ Disk Material S31600 SST/CoCr-A Seat 69 Type Quantity N/A N/A
45 Seat Material CoCr-A Seat SWITCHES 70 Contacts / Rating N/A
46 Cage Stem Material CB7Cu-1 SST S31600 SST 71 Switching Position N/A
47 Gasket Material S31600 SST/Graphite 72 Electric Enclosure N/A
48 MFR Model FISHER 667 73 MFR Model FISHER 67CFR
49 Type Diaphragm Spring Return AIR SET 74 Set Pressure 4.2 kgf/cm2-g
50 Size Stroke Time 40i < 8 Sec 75 Filter Gauge 5 Micron min YES
ACTUATOR 51 Air Failure Valve: FC 76 Vol. Tank Booster NO NO
52 Handwheel Location N/A 77 Diffuser Lock-up NO NO
ACCESSORY
53 Mounting Position VERTICAL 78 Fire Safe Fireproof NO NO
54 Spring Range 1 - 2 kgf/cm2-g 79 Mech. Stop Quick Exa. NO NO
55 Include Pressure (Shutoff) 80 Hydro. Pressure YES
85 Vendor EMERSON 81 Leakage YES
PURCHASE TESTS
86 Manufacturer FISHER 82 Cryogenic N/A
87 Requisition No. R2B-P3-206-02-P-MR-00200 83 NACE Requirement N/A
88 Model No. ES 84 PWHT Requirement N/A
Notes:

INSTRUMENT SPECIFICATION - CONTROL VALVE


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S76.1 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Fieldbus Device Data Sheet
Tag No.: FV -21411
Fieldbus Tag No.:

Service : FA405 LPS COND TO COND

Basic Fieldbus Function Blocks Segment Information


Analog Input Block (AI) 1 Number Device:
1 22
20 Execution (msec)
Discrete Input Block (DI) 4 Number Segment #: DFJB-21145
2 23
15 Execution Time
3 Bias/Gain Station (BG) 0 Execution (msec) 24 LAS Capable: Yes No
Manual Loader (ML) 0 Number 25 Device Current Draw (mA): 19
4
0 Execution (msec) Device Minimum Voltage: 9.
26
Analog Output Block (AO) 1 Number Device Capacitance: 5 nF
5 20 Execution (msec) Polarity-sensitive: Yes No
27
Discrete Output Block (DO) 1 Number Segment Terminator Location:
6 20 Execution (msec)
28
7 Control Selector (CS)
DD Revision: 3
PID,PI,I Controller (PID) 29
8
20 Execution (msec)
CFF Revision: 1.9
Ratio Station (RA) 30
9
P,PD Controller (PD) 0 Number
10 0 Execution (msec)

* Execution time in msec.

Advanced Function Blocks Notes:

11 Device Control (DC)

12 Output Splitter (OS)

13 Signal Characterizer (SC)

14 Lead Lag (LL)

15 Deadtime (DT)

16 Integrator(Totalizer) (IT)

17 Setpoint Ramp Generator (SPG)

18 Input Selector (IS)

19 Arithmetic (AR)

20 Timer (TMR)

21 Analog Alarm (AAL)

INSTRUMENT SPECIFICATION -FOUNDATION FIELDBUS


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S76.2 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Tag Number : FV -21411

1. In-Built surge protector is provided by vendor.

1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S76.3 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
1 Tag No. FV -21414
2 Service GA403 C3 TO EA407
3 P&ID No. Line No. R2B-P3-206-02-A-DTI-00410 3"-P-214041-B2A1-N
4 Area Classification Ingress Protection CLASS 1 DIV 2 Gr. B ,C&D, T3 NEMA 4X
GENERAL 5 Ambient Temperature: Unit Min. Max. °C 10 48
6 Allowable Sound dBA Tightness Requirement <85 ANSI IV (standard)
7 Available Air Supply Pressure Unit Min. Max. kgf/cm²-g 4.2 8.0
8 Electric Connection Pneum. Connection 1/2” NPT (F) 1/4” NPT (F)
9 Power Failure Position FO
10 Line Size and Schedule Sch. Outlet Line Sch. 3 in STD 3" STD
PIPE
11 Line Class Rating Pipe Material B2A1 300# A106 GR.B, SMLS
LINE
12 Pipe Insulation Thickness Corrosion Allowance N N/A 1.6mm
13 Fluid State Phase Hydrocarbon Liquid Single Phase
14 Sour Service Special Condition N/A N/A
15 Flow Rate Units Min. Nor. Max. m³/h 12.14 24.27 26.7
16 Inlet Pressure Units Min. Nor. Max. kgf/cm²-g 20.7 20.7 20.7
17 Pressure Drop Units Min. Nor. Max. kgf/cm² 8.2 8.2 8.2
18 Inlet Temperature Units Min. Nor. Max. °C 38 38 38
PROCESS 19 Density Units Min. Nor. Max. kg/m³ 475 475 475
CONDITIONS 20 Viscosity Units Min. Nor. Max. cP 0.089 0.089 0.089
21 Molecular Weight (MW) Specific Gravity @ Oper.
22 Spec. Heat Ratio (Cp/Cv) Compressibility (Z)
23 Vapor Pressure (Liq.) Cavitation or Flashing 13.26 kgf/cm²-a NO
24 Critical Pressure (Liq) Flash (wt%) 43.29 kgf/cm²-a
25 Design Pressure Min. Max. kgf/cm²-g 24.5 kgf/cm²-g
26 Design Temperature Min. Max. 10 °C 120 °C
27 Max.Shutoff DP Solid % 24.5 kgf/cm²
28 Calculated Cv Units Min. Nor. Max. Cv 3.42 6.85 7.54
CALCULATED
29 Travel Units Min. Nor. Max. % 48 65 68
RESULTS
30 Noise dBA @1m Units Min. Nor. Max. dBA 55 58 59
31 MFR Model FISHER ES 56 MFR Model FISHER DVC6200F/SC-AD
32 Body Type Single Seat Globe 57 Signal: Inlet Outlet FF Protocol 0-2.8 kgf/cm2
33 Body Size Trim Size 1.5 in 1 5/16 in 58 Increase Signal Valve: DIRECT
34 End Connec.Size & Rating 1.5" 300# RF POSITIONER 59 Cam Characteristic LINEAR
35 Rated Cv Characteristic 21 EQ% 60 Bypass Gauges N/A YES
36 Body Material WCC Steel 61 Signal Fail. to Valve FO
BODY 37 Bonnet Type Material Plain WCC Steel 62 Electric Enclosure Ex ia IIC T5 , NEMA 4X
AND 38 Flow Direct. Flow Act. To Up FTO 63 MFR Model N/A N/A
TRIM 39 Packing Type Material ISO Seal PTFE 64 Type Power N/A N/A
SOLENOID
40 Lubricator Isolat. Valve N/A N/A 65 When De-Enegr.Valve: N/A
VALVE
41 Guiding No. of Ports Cage 1 66 Material Latcher N/A N/A
42 Trim Type Internal Design Standard Unbalanced 67 Electric Enclosure N/A
43 Rated Travel Leak Class 3/4 in ANSI IV 68 MFR Model N/A N/A
44 Plug/ Ball/ Disk Material S41600 SST 69 Type Quantity N/A N/A
45 Seat Material S41600 SST SWITCHES 70 Contacts / Rating N/A
46 Cage Stem Material CB7Cu-1 SST S31600 SST 71 Switching Position N/A
47 Gasket Material S31600 SST/Graphite 72 Electric Enclosure N/A
48 MFR Model FISHER 657 73 MFR Model FISHER 67CFR
49 Type Diaphragm Spring Return AIR SET 74 Set Pressure 4.2 kgf/cm2-g
50 Size Stroke Time 45i < 6 Sec 75 Filter Gauge 5 Micron min YES
ACTUATOR 51 Air Failure Valve: FO 76 Vol. Tank Booster NO NO
52 Handwheel Location N/A 77 Diffuser Lock-up NO NO
ACCESSORY
53 Mounting Position VERTICAL 78 Fire Safe Fireproof NO NO
54 Spring Range 0.4 - 2.0 kgf/cm2-g 79 Mech. Stop Quick Exa. NO NO
55 Include Pressure (Shutoff) 80 Hydro. Pressure YES
85 Vendor EMERSON 81 Leakage YES
PURCHASE TESTS
86 Manufacturer FISHER 82 Cryogenic N/A
87 Requisition No. R2B-P3-206-02-P-MR-00200 83 NACE Requirement N/A
88 Model No. ES 84 PWHT Requirement N/A
Notes:

INSTRUMENT SPECIFICATION - CONTROL VALVE


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S77.1 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Fieldbus Device Data Sheet
Tag No.: FV -21414
Fieldbus Tag No.:

Service : GA403 C3 TO EA407

Basic Fieldbus Function Blocks Segment Information


Analog Input Block (AI) 1 Number Device:
1 22
20 Execution (msec)
Discrete Input Block (DI) 4 Number Segment #: DFJB-21154
2 23
15 Execution Time
3 Bias/Gain Station (BG) 0 Execution (msec) 24 LAS Capable: Yes No
Manual Loader (ML) 0 Number 25 Device Current Draw (mA): 19
4
0 Execution (msec) Device Minimum Voltage: 9.
26
Analog Output Block (AO) 1 Number Device Capacitance: 5 nF
5 20 Execution (msec) Polarity-sensitive: Yes No
27
Discrete Output Block (DO) 1 Number Segment Terminator Location:
6 20 Execution (msec)
28
7 Control Selector (CS)
DD Revision: 3
PID,PI,I Controller (PID) 29
8
20 Execution (msec)
CFF Revision: 1.9
Ratio Station (RA) 30
9
P,PD Controller (PD) 0 Number
10 0 Execution (msec)

* Execution time in msec.

Advanced Function Blocks Notes:

11 Device Control (DC)

12 Output Splitter (OS)

13 Signal Characterizer (SC)

14 Lead Lag (LL)

15 Deadtime (DT)

16 Integrator(Totalizer) (IT)

17 Setpoint Ramp Generator (SPG)

18 Input Selector (IS)

19 Arithmetic (AR)

20 Timer (TMR)

21 Analog Alarm (AAL)

INSTRUMENT SPECIFICATION -FOUNDATION FIELDBUS


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S77.2 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Tag Number : FV -21414

1. Valve will normally be in the closed position. Valve opening will be intermittent and generally short-term.

2. In-Built surge protector is provided by vendor.

1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S77.3 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
1 Tag No. FV -21415
2 Service GA403 C3 TO STOR
3 P&ID No. Line No. R2B-P3-206-02-A-DTI-00410 4"-P-214038-B2A1-N
4 Area Classification Ingress Protection CLASS 1 DIV 2 Gr. B ,C&D, T3 NEMA 4X
GENERAL 5 Ambient Temperature: Unit Min. Max. °C 10 48
6 Allowable Sound dBA Tightness Requirement <85 ANSI IV (standard)
7 Available Air Supply Pressure Unit Min. Max. kgf/cm²-g 4.2 8.0
8 Electric Connection Pneum. Connection 1/2” NPT (F) 1/4” NPT (F)
9 Power Failure Position FC
10 Line Size and Schedule Sch. Outlet Line Sch. 4 in STD 4" STD
PIPE
11 Line Class Rating Pipe Material B2A1 300# A106 GR.B, SMLS
LINE
12 Pipe Insulation Thickness Corrosion Allowance N N/A 1.6mm
13 Fluid State Phase Hydrocarbon Liquid Single Phase
14 Sour Service Special Condition N/A N/A
15 Flow Rate Units Min. Nor. Max. m³/h 27.1 54.3 59.7
16 Inlet Pressure Units Min. Nor. Max. kgf/cm²-g 20.2 19.5 19.2
17 Pressure Drop Units Min. Nor. Max. kgf/cm² 2.15 1.14 0.91
18 Inlet Temperature Units Min. Nor. Max. °C 38 38 38
PROCESS 19 Density Units Min. Nor. Max. kg/m³ 475 475 475
CONDITIONS 20 Viscosity Units Min. Nor. Max. cP 0.089 0.089 0.089
21 Molecular Weight (MW) Specific Gravity @ Oper.
22 Spec. Heat Ratio (Cp/Cv) Compressibility (Z)
23 Vapor Pressure (Liq.) Cavitation or Flashing 13.26 kgf/cm²-a NO
24 Critical Pressure (Liq) Flash (wt%) 43.29 kgf/cm²-a
25 Design Pressure Min. Max. kgf/cm²-g 24.5 kgf/cm²-g
26 Design Temperature Min. Max. 10 °C 120 °C
27 Max.Shutoff DP Solid % 24.5 kgf/cm²
28 Calculated Cv Units Min. Nor. Max. Cv 14.9 41.1 50.6
CALCULATED
29 Travel Units Min. Nor. Max. % 54 75 82
RESULTS
30 Noise dBA @1m Units Min. Nor. Max. dBA 50 50 50
31 MFR Model FISHER EZ 56 MFR Model FISHER DVC6200F/SC-AD
32 Body Type Single Seat Globe 57 Signal: Inlet Outlet FF Protocol 0-2.8 kgf/cm2
33 Body Size Trim Size 3 in 2 in 58 Increase Signal Valve: DIRECT
34 End Connec.Size & Rating 3" 300# RF POSITIONER 59 Cam Characteristic LINEAR
35 Rated Cv Characteristic 71.6 EQ% 60 Bypass Gauges N/A YES
36 Body Material WCC Steel 61 Signal Fail. to Valve FC
BODY 37 Bonnet Type Material Plain WCC Steel 62 Electric Enclosure Ex ia IIC T5 , NEMA 4X
AND 38 Flow Direct. Flow Act. To Up FTO 63 MFR Model N/A N/A
TRIM 39 Packing Type Material ISO Seal PTFE 64 Type Power N/A N/A
SOLENOID
40 Lubricator Isolat. Valve N/A N/A 65 When De-Enegr.Valve: N/A
VALVE
41 Guiding No. of Ports Post 1 66 Material Latcher N/A N/A
42 Trim Type Internal Design Standard Unbalanced 67 Electric Enclosure N/A
43 Rated Travel Leak Class 1 1/8 in ANSI IV 68 MFR Model N/A N/A
44 Plug/ Ball/ Disk Material S41600 SST 69 Type Quantity N/A N/A
45 Seat Material S41600 SST SWITCHES 70 Contacts / Rating N/A
46 Cage Stem Material N/A S31600 SST 71 Switching Position N/A
47 Gasket Material S31600 SST/Graphite 72 Electric Enclosure N/A
48 MFR Model FISHER 667 73 MFR Model FISHER 67CFR
49 Type Diaphragm Spring Return AIR SET 74 Set Pressure 4.2 kgf/cm2-g
50 Size Stroke Time 45i < 8 Sec 75 Filter Gauge 5 Micron min YES
ACTUATOR 51 Air Failure Valve: FC 76 Vol. Tank Booster NO NO
52 Handwheel Location N/A 77 Diffuser Lock-up NO NO
ACCESSORY
53 Mounting Position VERTICAL 78 Fire Safe Fireproof NO NO
54 Spring Range 1.3 - 2.4 kgf/cm2-g 79 Mech. Stop Quick Exa. NO NO
55 Include Pressure (Shutoff) 80 Hydro. Pressure YES
85 Vendor EMERSON 81 Leakage YES
PURCHASE TESTS
86 Manufacturer FISHER 82 Cryogenic N/A
87 Requisition No. R2B-P3-206-02-P-MR-00200 83 NACE Requirement N/A
88 Model No. EZ 84 PWHT Requirement N/A
Notes:

INSTRUMENT SPECIFICATION - CONTROL VALVE


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S78.1 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Fieldbus Device Data Sheet
Tag No.: FV -21415
Fieldbus Tag No.:

Service : GA403 C3 TO STOR

Basic Fieldbus Function Blocks Segment Information


Analog Input Block (AI) 1 Number Device:
1 22
20 Execution (msec)
Discrete Input Block (DI) 4 Number Segment #: DFJB-21154
2 23
15 Execution Time
3 Bias/Gain Station (BG) 0 Execution (msec) 24 LAS Capable: Yes No
Manual Loader (ML) 0 Number 25 Device Current Draw (mA): 19
4
0 Execution (msec) Device Minimum Voltage: 9.
26
Analog Output Block (AO) 1 Number Device Capacitance: 5 nF
5 20 Execution (msec) Polarity-sensitive: Yes No
27
Discrete Output Block (DO) 1 Number Segment Terminator Location:
6 20 Execution (msec)
28
7 Control Selector (CS)
DD Revision: 3
PID,PI,I Controller (PID) 29
8
20 Execution (msec)
CFF Revision: 1.9
Ratio Station (RA) 30
9
P,PD Controller (PD) 0 Number
10 0 Execution (msec)

* Execution time in msec.

Advanced Function Blocks Notes:

11 Device Control (DC)

12 Output Splitter (OS)

13 Signal Characterizer (SC)

14 Lead Lag (LL)

15 Deadtime (DT)

16 Integrator(Totalizer) (IT)

17 Setpoint Ramp Generator (SPG)

18 Input Selector (IS)

19 Arithmetic (AR)

20 Timer (TMR)

21 Analog Alarm (AAL)

INSTRUMENT SPECIFICATION -FOUNDATION FIELDBUS


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S78.2 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Tag Number : FV -21415

1. In-Built surge protector is provided by vendor.

1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S78.3 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
1 Tag No. FV -21417
2 Service GA404 C3 TO DT401
3 P&ID No. Line No. R2B-P3-206-02-A-DTI-00413 4"-P-214058-B2A1-N
4 Area Classification Ingress Protection CLASS 1 DIV 2 Gr. B ,C&D, T3 NEMA 4X
GENERAL 5 Ambient Temperature: Unit Min. Max. °C 10 48
6 Allowable Sound dBA Tightness Requirement <85 ANSI IV (standard)
7 Available Air Supply Pressure Unit Min. Max. kgf/cm²-g 4.2 8.0
8 Electric Connection Pneum. Connection 1/2” NPT (F) 1/4” NPT (F)
9 Power Failure Position FC
10 Line Size and Schedule Sch. Outlet Line Sch. 4 in STD 4" STD
PIPE
11 Line Class Rating Pipe Material B2A1 300# A106 GR.B, SMLS
LINE
12 Pipe Insulation Thickness Corrosion Allowance N N/A 1.6mm
13 Fluid State Phase Hydrocarbon Liquid Single Phase
14 Sour Service Special Condition N/A N/A
15 Flow Rate Units Min. Nor. Max. m³/h 11.5 71.7 78.9
16 Inlet Pressure Units Min. Nor. Max. kgf/cm²-g 25.78 24.4 24.05
17 Pressure Drop Units Min. Nor. Max. kgf/cm² 3.197 1.303 0.837
18 Inlet Temperature Units Min. Nor. Max. °C 28 28 28
PROCESS 19 Density Units Min. Nor. Max. kg/m³ 504 504 504
CONDITIONS 20 Viscosity Units Min. Nor. Max. cP 0.069 0.069 0.069
21 Molecular Weight (MW) Specific Gravity @ Oper.
22 Spec. Heat Ratio (Cp/Cv) Compressibility (Z)
23 Vapor Pressure (Liq.) Cavitation or Flashing 12.63 kgf/cm²-a NO
24 Critical Pressure (Liq) Flash (wt%) 46.66 kgf/cm²-a
25 Design Pressure Min. Max. kgf/cm²-g 30.5 kgf/cm²-g
26 Design Temperature Min. Max. 10 °C 120 °C
27 Max.Shutoff DP Solid % 30.3 kgf/cm²
28 Calculated Cv Units Min. Nor. Max. Cv 5.33 52.4 72.2
CALCULATED
29 Travel Units Min. Nor. Max. % 18 67 75
RESULTS
30 Noise dBA @1m Units Min. Nor. Max. dBA 50 50 50
31 MFR Model FISHER EZ 56 MFR Model FISHER DVC6200F/SC-AD
32 Body Type Single Seat Globe 57 Signal: Inlet Outlet FF Protocol 0-3.5 kgf/cm2
33 Body Size Trim Size 3 in 3 in 58 Increase Signal Valve: DIRECT
34 End Connec.Size & Rating 3" 300# RF POSITIONER 59 Cam Characteristic LINEAR
35 Rated Cv Characteristic 114 EQ% 60 Bypass Gauges N/A YES
36 Body Material WCC Steel 61 Signal Fail. to Valve FC
BODY 37 Bonnet Type Material Plain WCC Steel 62 Electric Enclosure Ex ia IIC T5 , NEMA 4X
AND 38 Flow Direct. Flow Act. To Up FTO 63 MFR Model N/A N/A
TRIM 39 Packing Type Material ISO Seal PTFE 64 Type Power N/A N/A
SOLENOID
40 Lubricator Isolat. Valve N/A N/A 65 When De-Enegr.Valve: N/A
VALVE
41 Guiding No. of Ports Post 1 66 Material Latcher N/A N/A
42 Trim Type Internal Design Standard Unbalanced 67 Electric Enclosure N/A
43 Rated Travel Leak Class 1 1/2 in ANSI IV 68 MFR Model N/A N/A
44 Plug/ Ball/ Disk Material S41600 SST 69 Type Quantity N/A N/A
45 Seat Material S41600 SST SWITCHES 70 Contacts / Rating N/A
46 Cage Stem Material N/A S31600 SST 71 Switching Position N/A
47 Gasket Material S31600 SST/Graphite 72 Electric Enclosure N/A
48 MFR Model FISHER 667 73 MFR Model FISHER 67CFR
49 Type Diaphragm Spring Return AIR SET 74 Set Pressure 4.2 kgf/cm2-g
50 Size Stroke Time 70i < 10 Sec 75 Filter Gauge 5 Micron min YES
ACTUATOR 51 Air Failure Valve: FC 76 Vol. Tank Booster NO NO
52 Handwheel Location N/A 77 Diffuser Lock-up NO NO
ACCESSORY
53 Mounting Position VERTICAL 78 Fire Safe Fireproof NO NO
54 Spring Range 1.6 - 2.8 kgf/cm2-g 79 Mech. Stop Quick Exa. NO NO
55 Include Pressure (Shutoff) 80 Hydro. Pressure YES
85 Vendor EMERSON 81 Leakage YES
PURCHASE TESTS
86 Manufacturer FISHER 82 Cryogenic N/A
87 Requisition No. R2B-P3-206-02-P-MR-00200 83 NACE Requirement N/A
88 Model No. EZ 84 PWHT Requirement N/A
Notes:

INSTRUMENT SPECIFICATION - CONTROL VALVE


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S79.1 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Fieldbus Device Data Sheet
Tag No.: FV -21417
Fieldbus Tag No.:

Service : GA404 C3 TO DT401

Basic Fieldbus Function Blocks Segment Information


Analog Input Block (AI) 1 Number Device:
1 22
20 Execution (msec)
Discrete Input Block (DI) 4 Number Segment #: DFJB-21164
2 23
15 Execution Time
3 Bias/Gain Station (BG) 0 Execution (msec) 24 LAS Capable: Yes No
Manual Loader (ML) 0 Number 25 Device Current Draw (mA): 19
4
0 Execution (msec) Device Minimum Voltage: 9.
26
Analog Output Block (AO) 1 Number Device Capacitance: 5 nF
5 20 Execution (msec) Polarity-sensitive: Yes No
27
Discrete Output Block (DO) 1 Number Segment Terminator Location:
6 20 Execution (msec)
28
7 Control Selector (CS)
DD Revision: 3
PID,PI,I Controller (PID) 29
8
20 Execution (msec)
CFF Revision: 1.9
Ratio Station (RA) 30
9
P,PD Controller (PD) 0 Number
10 0 Execution (msec)

* Execution time in msec.

Advanced Function Blocks Notes:

11 Device Control (DC)

12 Output Splitter (OS)

13 Signal Characterizer (SC)

14 Lead Lag (LL)

15 Deadtime (DT)

16 Integrator(Totalizer) (IT)

17 Setpoint Ramp Generator (SPG)

18 Input Selector (IS)

19 Arithmetic (AR)

20 Timer (TMR)

21 Analog Alarm (AAL)

INSTRUMENT SPECIFICATION -FOUNDATION FIELDBUS


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S79.2 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Tag Number : FV -21417

1. In-Built surge protector is provided by vendor.

1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S79.3 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
1 Tag No. FV -21420
2 Service EA408 C3 TO FA403
3 P&ID No. Line No. R2B-P3-206-02-A-DTI-00415 8"-P-214067-B2A1-EC
4 Area Classification Ingress Protection CLASS 1 DIV 2 Gr. B ,C&D, T3 NEMA 4X
GENERAL 5 Ambient Temperature: Unit Min. Max. °C 10 48
6 Allowable Sound dBA Tightness Requirement <85 ANSI IV (standard)
7 Available Air Supply Pressure Unit Min. Max. kgf/cm²-g 4.2 8.0
8 Electric Connection Pneum. Connection 1/2” NPT (F) 1/4” NPT (F)
9 Power Failure Position FLO
10 Line Size and Schedule Sch. Outlet Line Sch. 8 in STD 6" STD
PIPE
11 Line Class Rating Pipe Material B2A1 300# A106 GR.B, SMLS
LINE
12 Pipe Insulation Thickness Corrosion Allowance EC 40mm 1.6mm
13 Fluid State Phase Hydrocarbon Liquid Single Phase
14 Sour Service Special Condition N/A N/A
15 Flow Rate Units Min. Nor. Max. m³/h 83.8 157.3 196.64
16 Inlet Pressure Units Min. Nor. Max. kgf/cm²-g 17.37 17.54 17.69
17 Pressure Drop Units Min. Nor. Max. kgf/cm² 5.36 5.274 5.24
18 Inlet Temperature Units Min. Nor. Max. °C 44 44 44
PROCESS 19 Density Units Min. Nor. Max. kg/m³ 470 470 470
CONDITIONS 20 Viscosity Units Min. Nor. Max. cP 0.054 0.054 0.054
21 Molecular Weight (MW) Specific Gravity @ Oper.
22 Spec. Heat Ratio (Cp/Cv) Compressibility (Z)
23 Vapor Pressure (Liq.) Cavitation or Flashing 18.4 kgf/cm²-a Flashing
24 Critical Pressure (Liq) Flash (wt%) 46.68 kgf/cm²-a
25 Design Pressure Min. Max. kgf/cm²-g 23.5 kgf/cm²-g
26 Design Temperature Min. Max. 10 °C 120 °C
27 Max.Shutoff DP Solid % 23.5 kgf/cm²
28 Calculated Cv Units Min. Nor. Max. Cv 40.2 75.2 92.7
CALCULATED
29 Travel Units Min. Nor. Max. % 32 58 75
RESULTS
30 Noise dBA @1m Units Min. Nor. Max. dBA 85 85 85
31 MFR Model FISHER ET 56 MFR Model FISHER DVC6200F/SC-AD
32 Body Type Single Seat Globe 57 Signal: Inlet Outlet FF Protocol 0-2.8 kgf/cm2
33 Body Size Trim Size 4 in 2 7/8 in 58 Increase Signal Valve: DIRECT
34 End Connec.Size & Rating 4" 300# RF POSITIONER 59 Cam Characteristic LINEAR
35 Rated Cv Characteristic 113 Linear 60 Bypass Gauges N/A YES
36 Body Material WCC Steel 61 Signal Fail. to Valve FLO
BODY 37 Bonnet Type Material Plain WCC Steel 62 Electric Enclosure Ex ia IIC T5 , NEMA 4X
AND 38 Flow Direct. Flow Act. To Down FTO 63 MFR Model N/A N/A
TRIM 39 Packing Type Material ISO Seal PTFE 64 Type Power N/A N/A
SOLENOID
40 Lubricator Isolat. Valve N/A N/A 65 When De-Enegr.Valve: N/A
VALVE
41 Guiding No. of Ports Cage 1 66 Material Latcher N/A N/A
42 Trim Type Internal Design Standard Balanced 67 Electric Enclosure N/A
43 Rated Travel Leak Class 1 1/2 in ANSI IV 68 MFR Model N/A N/A
44 Plug/ Ball/ Disk Material S31600 SST/CoCr-A Seat 69 Type Quantity N/A N/A
45 Seat Material CoCr-A Seat SWITCHES 70 Contacts / Rating N/A
46 Cage Stem Material S31600 SST/ ENCS31600 SST 71 Switching Position N/A
47 Gasket Material S31600 SST/Graphite 72 Electric Enclosure N/A
48 MFR Model FISHER 657 73 MFR Model FISHER 67CFR
49 Type Diaphragm Spring Return AIR SET 74 Set Pressure 4.2 kgf/cm2-g
50 Size Stroke Time 40i < 10 Sec 75 Filter Gauge 5 Micron min YES
ACTUATOR 51 Air Failure Valve: FLO 76 Vol. Tank Booster NO NO
52 Handwheel Location N/A 77 Diffuser Lock-up NO YES
ACCESSORY
53 Mounting Position VERTICAL 78 Fire Safe Fireproof NO NO
54 Spring Range 0.5 - 1.9 kgf/cm2-g 79 Mech. Stop Quick Exa. NO NO
55 Include Pressure (Shutoff) 80 Hydro. Pressure YES
85 Vendor EMERSON 81 Leakage YES
PURCHASE TESTS
86 Manufacturer FISHER 82 Cryogenic N/A
87 Requisition No. R2B-P3-206-02-P-MR-00200 83 NACE Requirement N/A
88 Model No. ET 84 PWHT Requirement N/A
Notes:

INSTRUMENT SPECIFICATION - CONTROL VALVE


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S80.1 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Fieldbus Device Data Sheet
Tag No.: FV -21420
Fieldbus Tag No.:

Service : EA408 C3 TO FA403

Basic Fieldbus Function Blocks Segment Information


Analog Input Block (AI) 1 Number Device:
1 22
20 Execution (msec)
Discrete Input Block (DI) 4 Number Segment #: DFJB-21162
2 23
15 Execution Time
3 Bias/Gain Station (BG) 0 Execution (msec) 24 LAS Capable: Yes No
Manual Loader (ML) 0 Number 25 Device Current Draw (mA): 19
4
0 Execution (msec) Device Minimum Voltage: 9.
26
Analog Output Block (AO) 1 Number Device Capacitance: 5 nF
5 20 Execution (msec) Polarity-sensitive: Yes No
27
Discrete Output Block (DO) 1 Number Segment Terminator Location:
6 20 Execution (msec)
28
7 Control Selector (CS)
DD Revision: 3
PID,PI,I Controller (PID) 29
8
20 Execution (msec)
CFF Revision: 1.9
Ratio Station (RA) 30
9
P,PD Controller (PD) 0 Number
10 0 Execution (msec)

* Execution time in msec.

Advanced Function Blocks Notes:

11 Device Control (DC)

12 Output Splitter (OS)

13 Signal Characterizer (SC)

14 Lead Lag (LL)

15 Deadtime (DT)

16 Integrator(Totalizer) (IT)

17 Setpoint Ramp Generator (SPG)

18 Input Selector (IS)

19 Arithmetic (AR)

20 Timer (TMR)

21 Analog Alarm (AAL)

INSTRUMENT SPECIFICATION -FOUNDATION FIELDBUS


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S80.2 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Tag Number : FV -21420

1. Control Valve Outlet data -


Normal Case - Liq Flow: 125.9 m3/h; Vap Flow: 5663 normal m3/h; Temp: 27 0C Liq Density: 502 kg/m^3; Liq Visc.: 0.069 cP; Vap MW: 42.18; Vap Z:
0.798; Vap Cp/Cv(Real): 1.111.
Maximum Case - Liq Flow: 138.5 m3/h; Vap Flow: 6229 normal m3/h; Temp: 27 0C Liq Density: 502 kg/m^3; Liq Visc.: 0.069 cP; Vap MW: 42.18; Vap
Z: 0.798; Vap Cp/Cv(Real): 1.111.

2. In-Built surge protector is provided by vendor.

1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S80.3 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
1 Tag No. FV -21422
2 Service GA404 C3 TO DF403
3 P&ID No. Line No. R2B-P3-206-02-A-DTI-00413 4"-P-214061-B2A1-N
4 Area Classification Ingress Protection CLASS 1 DIV 2 Gr. B ,C&D, T3 NEMA 4X
GENERAL 5 Ambient Temperature: Unit Min. Max. °C 10 48
6 Allowable Sound dBA Tightness Requirement <85 ANSI IV (standard)
7 Available Air Supply Pressure Unit Min. Max. kgf/cm²-g 4.2 8.0
8 Electric Connection Pneum. Connection 1/2” NPT (F) 1/4” NPT (F)
9 Power Failure Position FO
10 Line Size and Schedule Sch. Outlet Line Sch. 4 in STD 4" STD
PIPE
11 Line Class Rating Pipe Material B2A1 300# A106 GR.B, SMLS
LINE
12 Pipe Insulation Thickness Corrosion Allowance N N/A 1.6mm
13 Fluid State Phase Hydrocarbon Liquid Single Phase
14 Sour Service Special Condition N/A N/A
15 Flow Rate Units Min. Nor. Max. m³/h 26.5 53 58.3
16 Inlet Pressure Units Min. Nor. Max. kgf/cm²-g 25.87 24.55 24.21
17 Pressure Drop Units Min. Nor. Max. kgf/cm² 10.69 9.171 8.77
18 Inlet Temperature Units Min. Nor. Max. °C 28 28 28
PROCESS 19 Density Units Min. Nor. Max. kg/m³ 504 504 504
CONDITIONS 20 Viscosity Units Min. Nor. Max. cP 0.069 0.069 0.069
21 Molecular Weight (MW) Specific Gravity @ Oper.
22 Spec. Heat Ratio (Cp/Cv) Compressibility (Z)
23 Vapor Pressure (Liq.) Cavitation or Flashing 12.63 kgf/cm²-a NO
24 Critical Pressure (Liq) Flash (wt%) 46.66 kgf/cm²-a
25 Design Pressure Min. Max. kgf/cm²-g 30.5 kgf/cm²-g
26 Design Temperature Min. Max. 10 °C 120 °C
27 Max.Shutoff DP Solid % 30.3 kgf/cm²
28 Calculated Cv Units Min. Nor. Max. Cv 6.73 14.6 16.4
CALCULATED
29 Travel Units Min. Nor. Max. % 21 44 50
RESULTS
30 Noise dBA @1m Units Min. Nor. Max. dBA 72 74 74
31 MFR Model FISHER ET 56 MFR Model FISHER DVC6200F/SC-AD
32 Body Type Single Seat Globe 57 Signal: Inlet Outlet FF Protocol 0-2.8 kgf/cm2
33 Body Size Trim Size 2 in 1 5/16 in 58 Increase Signal Valve: DIRECT
34 End Connec.Size & Rating 2" 300# RF POSITIONER 59 Cam Characteristic LINEAR
35 Rated Cv Characteristic 33.3 Linear 60 Bypass Gauges N/A YES
36 Body Material WCC Steel 61 Signal Fail. to Valve FO
BODY 37 Bonnet Type Material Plain WCC Steel 62 Electric Enclosure Ex ia IIC T5 , NEMA 4X
AND 38 Flow Direct. Flow Act. To Down FTO 63 MFR Model N/A N/A
TRIM 39 Packing Type Material ISO Seal PTFE 64 Type Power N/A N/A
SOLENOID
40 Lubricator Isolat. Valve N/A N/A 65 When De-Enegr.Valve: N/A
VALVE
41 Guiding No. of Ports Cage 1 66 Material Latcher N/A N/A
42 Trim Type Internal Design Standard Balanced 67 Electric Enclosure N/A
43 Rated Travel Leak Class 3/4 in ANSI IV 68 MFR Model N/A N/A
44 Plug/ Ball/ Disk Material S41600 SST 69 Type Quantity N/A N/A
45 Seat Material S41600 SST SWITCHES 70 Contacts / Rating N/A
46 Cage Stem Material CB7Cu-1 SST S31600 SST 71 Switching Position N/A
47 Gasket Material S31600 SST/Graphite 72 Electric Enclosure N/A
48 MFR Model FISHER 657 73 MFR Model FISHER 67CFR
49 Type Diaphragm Spring Return AIR SET 74 Set Pressure 4.2 kgf/cm2-g
50 Size Stroke Time 40i < 8 Sec 75 Filter Gauge 5 Micron min YES
ACTUATOR 51 Air Failure Valve: FO 76 Vol. Tank Booster NO NO
52 Handwheel Location N/A 77 Diffuser Lock-up NO NO
ACCESSORY
53 Mounting Position VERTICAL 78 Fire Safe Fireproof NO NO
54 Spring Range 0.4 - 2.0 kgf/cm2-g 79 Mech. Stop Quick Exa. NO NO
55 Include Pressure (Shutoff) 80 Hydro. Pressure YES
85 Vendor EMERSON 81 Leakage YES
PURCHASE TESTS
86 Manufacturer FISHER 82 Cryogenic N/A
87 Requisition No. R2B-P3-206-02-P-MR-00200 83 NACE Requirement N/A
88 Model No. ET 84 PWHT Requirement N/A
Notes:

INSTRUMENT SPECIFICATION - CONTROL VALVE


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S81.1 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Fieldbus Device Data Sheet
Tag No.: FV -21422
Fieldbus Tag No.:

Service : GA404 C3 TO DF403

Basic Fieldbus Function Blocks Segment Information


Analog Input Block (AI) 1 Number Device:
1 22
20 Execution (msec)
Discrete Input Block (DI) 4 Number Segment #: DFJB-21164
2 23
15 Execution Time
3 Bias/Gain Station (BG) 0 Execution (msec) 24 LAS Capable: Yes No
Manual Loader (ML) 0 Number 25 Device Current Draw (mA): 19
4
0 Execution (msec) Device Minimum Voltage: 9.
26
Analog Output Block (AO) 1 Number Device Capacitance: 5 nF
5 20 Execution (msec) Polarity-sensitive: Yes No
27
Discrete Output Block (DO) 1 Number Segment Terminator Location:
6 20 Execution (msec)
28
7 Control Selector (CS)
DD Revision: 3
PID,PI,I Controller (PID) 29
8
20 Execution (msec)
CFF Revision: 1.9
Ratio Station (RA) 30
9
P,PD Controller (PD) 0 Number
10 0 Execution (msec)

* Execution time in msec.

Advanced Function Blocks Notes:

11 Device Control (DC)

12 Output Splitter (OS)

13 Signal Characterizer (SC)

14 Lead Lag (LL)

15 Deadtime (DT)

16 Integrator(Totalizer) (IT)

17 Setpoint Ramp Generator (SPG)

18 Input Selector (IS)

19 Arithmetic (AR)

20 Timer (TMR)

21 Analog Alarm (AAL)

INSTRUMENT SPECIFICATION -FOUNDATION FIELDBUS


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S81.2 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Tag Number : FV -21422

1. In-Built surge protector is provided by vendor.

1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S81.3 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
1 Tag No. FV -21424
2 Service GA404 C3 TO FA403
3 P&ID No. Line No. R2B-P3-206-02-A-DTI-00413 4"-P-214095-B2A1-N
4 Area Classification Ingress Protection CLASS 1 DIV 2 Gr. B ,C&D, T3 NEMA 4X
GENERAL 5 Ambient Temperature: Unit Min. Max. °C 10 48
6 Allowable Sound dBA Tightness Requirement <85 ANSI IV (standard)
7 Available Air Supply Pressure Unit Min. Max. kgf/cm²-g 4.2 8.0
8 Electric Connection Pneum. Connection 1/2” NPT (F) 1/4” NPT (F)
9 Power Failure Position FO
10 Line Size and Schedule Sch. Outlet Line Sch. 4 in STD 4" STD
PIPE
11 Line Class Rating Pipe Material B2A1 300# A106 GR.B, SMLS
LINE
12 Pipe Insulation Thickness Corrosion Allowance N N/A 1.6mm
13 Fluid State Phase Hydrocarbon Liquid Single Phase
14 Sour Service Special Condition N/A N/A
15 Flow Rate Units Min. Nor. Max. m³/h 23.45 46.9 51.6
16 Inlet Pressure Units Min. Nor. Max. kgf/cm²-g 25.87 25.87 26.05
17 Pressure Drop Units Min. Nor. Max. kgf/cm² 14.61 14.61 14.51
18 Inlet Temperature Units Min. Nor. Max. °C 28 28 28
PROCESS 19 Density Units Min. Nor. Max. kg/m³ 504 504 504
CONDITIONS 20 Viscosity Units Min. Nor. Max. cP 0.069 0.069 0.069
21 Molecular Weight (MW) Specific Gravity @ Oper.
22 Spec. Heat Ratio (Cp/Cv) Compressibility (Z)
23 Vapor Pressure (Liq.) Cavitation or Flashing 12.63 kgf/cm²-a Flashing
24 Critical Pressure (Liq) Flash (wt%) 46.66 kgf/cm²-a
25 Design Pressure Min. Max. kgf/cm²-g 30.5 kgf/cm²-g
26 Design Temperature Min. Max. 10 °C 120 °C
27 Max.Shutoff DP Solid % 30.3 kgf/cm²
28 Calculated Cv Units Min. Nor. Max. Cv 5.42 10.9 11.9
CALCULATED
29 Travel Units Min. Nor. Max. % 58 75 78
RESULTS
30 Noise dBA @1m Units Min. Nor. Max. dBA 85 85 85
31 MFR Model FISHER ET 56 MFR Model FISHER DVC6200F/SC-AD
32 Body Type Single Seat Globe 57 Signal: Inlet Outlet FF Protocol 0-2.8 kgf/cm2
33 Body Size Trim Size 2 in 1 5/16 in 58 Increase Signal Valve: DIRECT
34 End Connec.Size & Rating 2" 300# RF POSITIONER 59 Cam Characteristic LINEAR
35 Rated Cv Characteristic 24.3 EQ% 60 Bypass Gauges N/A YES
36 Body Material WCC Steel 61 Signal Fail. to Valve FO
BODY 37 Bonnet Type Material Plain WCC Steel 62 Electric Enclosure Ex ia IIC T5 , NEMA 4X
AND 38 Flow Direct. Flow Act. To Down FTO 63 MFR Model N/A N/A
TRIM 39 Packing Type Material ISO Seal PTFE 64 Type Power N/A N/A
SOLENOID
40 Lubricator Isolat. Valve N/A N/A 65 When De-Enegr.Valve: N/A
VALVE
41 Guiding No. of Ports Cage 1 66 Material Latcher N/A N/A
42 Trim Type Internal Design Standard Balanced 67 Electric Enclosure N/A
43 Rated Travel Leak Class 3/4 in ANSI IV 68 MFR Model N/A N/A
44 Plug/ Ball/ Disk Material S31600 SST/CoCr-A Seat 69 Type Quantity N/A N/A
45 Seat Material CoCr-A Seat SWITCHES 70 Contacts / Rating N/A
46 Cage Stem Material S31600 SST/ ENCS31600 SST 71 Switching Position N/A
47 Gasket Material S31600 SST/Graphite 72 Electric Enclosure N/A
48 MFR Model FISHER 657 73 MFR Model FISHER 67CFR
49 Type Diaphragm Spring Return AIR SET 74 Set Pressure 4.2 kgf/cm2-g
50 Size Stroke Time 40i < 8 Sec 75 Filter Gauge 5 Micron min YES
ACTUATOR 51 Air Failure Valve: FO 76 Vol. Tank Booster NO NO
52 Handwheel Location N/A 77 Diffuser Lock-up NO NO
ACCESSORY
53 Mounting Position VERTICAL 78 Fire Safe Fireproof NO NO
54 Spring Range 0.4 - 2.0 kgf/cm2-g 79 Mech. Stop Quick Exa. NO NO
55 Include Pressure (Shutoff) 80 Hydro. Pressure YES
85 Vendor EMERSON 81 Leakage YES
PURCHASE TESTS
86 Manufacturer FISHER 82 Cryogenic N/A
87 Requisition No. R2B-P3-206-02-P-MR-00200 83 NACE Requirement N/A
88 Model No. ET 84 PWHT Requirement N/A
Notes:

INSTRUMENT SPECIFICATION - CONTROL VALVE


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S82.1 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Fieldbus Device Data Sheet
Tag No.: FV -21424
Fieldbus Tag No.:

Service : GA404 C3 TO FA403

Basic Fieldbus Function Blocks Segment Information


Analog Input Block (AI) 1 Number Device:
1 22
20 Execution (msec)
Discrete Input Block (DI) 4 Number Segment #: DFJB-21163
2 23
15 Execution Time
3 Bias/Gain Station (BG) 0 Execution (msec) 24 LAS Capable: Yes No
Manual Loader (ML) 0 Number 25 Device Current Draw (mA): 19
4
0 Execution (msec) Device Minimum Voltage: 9.
26
Analog Output Block (AO) 1 Number Device Capacitance: 5 nF
5 20 Execution (msec) Polarity-sensitive: Yes No
27
Discrete Output Block (DO) 1 Number Segment Terminator Location:
6 20 Execution (msec)
28
7 Control Selector (CS)
DD Revision: 3
PID,PI,I Controller (PID) 29
8
20 Execution (msec)
CFF Revision: 1.9
Ratio Station (RA) 30
9
P,PD Controller (PD) 0 Number
10 0 Execution (msec)

* Execution time in msec.

Advanced Function Blocks Notes:

11 Device Control (DC)

12 Output Splitter (OS)

13 Signal Characterizer (SC)

14 Lead Lag (LL)

15 Deadtime (DT)

16 Integrator(Totalizer) (IT)

17 Setpoint Ramp Generator (SPG)

18 Input Selector (IS)

19 Arithmetic (AR)

20 Timer (TMR)

21 Analog Alarm (AAL)

INSTRUMENT SPECIFICATION -FOUNDATION FIELDBUS


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S82.2 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Tag Number : FV -21424

1. In-Built surge protector is provided by vendor.

1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S82.3 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
1 Tag No. FV -21503
2 Service EA502 AML TO DA501
3 P&ID No. Line No. R2B-P3-206-02-A-DTI-00502 4"-MDEA-215014-T-B65T1-N
4 Area Classification Ingress Protection CLASS 1 DIV 2 Gr. B ,C&D, T3 NEMA 4X
GENERAL 5 Ambient Temperature: Unit Min. Max. °C 10 48
6 Allowable Sound dBA Tightness Requirement <85 ANSI IV (standard)
7 Available Air Supply Pressure Unit Min. Max. kgf/cm²-g 4.2 8.0
8 Electric Connection Pneum. Connection 1/2” NPT (F) 1/4” NPT (F)
9 Power Failure Position FC
10 Line Size and Schedule Sch. Outlet Line Sch. 4 in XS 4" XS
PIPE
11 Line Class Rating Pipe Material T-B65T1 300# A106 GR.B, SMLS
LINE
12 Pipe Insulation Thickness Corrosion Allowance N N/A 3.2mm
13 Fluid State Phase Lean Amine Liquid Single Phase
14 Sour Service Special Condition YES N/A
15 Flow Rate Units Min. Nor. Max. m³/h 15.1 30.4 33.4
16 Inlet Pressure Units Min. Nor. Max. kgf/cm²-g 18.24 17.94 17.86
17 Pressure Drop Units Min. Nor. Max. kgf/cm² 2.84 2.47 4.8
18 Inlet Temperature Units Min. Nor. Max. °C 45.1 45.1 45.1
PROCESS 19 Density Units Min. Nor. Max. kg/m³ 1028 1028 1028
CONDITIONS 20 Viscosity Units Min. Nor. Max. cP 3.5 3.49 3.49
21 Molecular Weight (MW) Specific Gravity @ Oper.
22 Spec. Heat Ratio (Cp/Cv) Compressibility (Z)
23 Vapor Pressure (Liq.) Cavitation or Flashing 0.087 kgf/cm²-a NO
24 Critical Pressure (Liq) Flash (wt%) 40.4 kgf/cm²-a
25 Design Pressure Min. Max. kgf/cm²-g 30 kgf/cm²-g
26 Design Temperature Min. Max. 10 °C 120 °C
27 Max.Shutoff DP Solid % 30 kgf/cm²
28 Calculated Cv Units Min. Nor. Max. Cv 10.6 23.2 18.2
CALCULATED
29 Travel Units Min. Nor. Max. % 50 68 62
RESULTS
30 Noise dBA @1m Units Min. Nor. Max. dBA 50 50 50
31 MFR Model FISHER ES 56 MFR Model FISHER DVC6200F/SC-AD
32 Body Type Single Seat Globe 57 Signal: Inlet Outlet FF Protocol 0-2.8 kgf/cm2
33 Body Size Trim Size 2 in 2 5/16 in 58 Increase Signal Valve: DIRECT
34 End Connec.Size & Rating 2" 300# RF POSITIONER 59 Cam Characteristic LINEAR
35 Rated Cv Characteristic 56.2 EQ% 60 Bypass Gauges N/A YES
36 Body Material WCC Steel 61 Signal Fail. to Valve FC
BODY 37 Bonnet Type Material Plain WCC Steel 62 Electric Enclosure Ex ia IIC T5 , NEMA 4X
AND 38 Flow Direct. Flow Act. To Up FTO 63 MFR Model N/A N/A
TRIM 39 Packing Type Material ISO Seal PTFE 64 Type Power N/A N/A
SOLENOID
40 Lubricator Isolat. Valve N/A N/A 65 When De-Enegr.Valve: N/A
VALVE
41 Guiding No. of Ports Cage 1 66 Material Latcher N/A N/A
42 Trim Type Internal Design Standard Unbalanced 67 Electric Enclosure N/A
43 Rated Travel Leak Class 1 1/8 in ANSI IV 68 MFR Model N/A N/A
44 Plug/ Ball/ Disk Material S31600 SST/CoCr-A Seat 69 Type Quantity N/A N/A
45 Seat Material R30006 Cobalt Alloy SWITCHES 70 Contacts / Rating N/A
46 Cage Stem Material S31600 SST/ ENCS20910 SST 71 Switching Position N/A
47 Gasket Material S31600 SST/Graphite 72 Electric Enclosure N/A
48 MFR Model FISHER 667 73 MFR Model FISHER 67CFR
49 Type Diaphragm Spring Return AIR SET 74 Set Pressure 4.2 kgf/cm2-g
50 Size Stroke Time 46i < 8 Sec 75 Filter Gauge 5 Micron min YES
ACTUATOR 51 Air Failure Valve: FC 76 Vol. Tank Booster NO NO
52 Handwheel Location N/A 77 Diffuser Lock-up NO NO
ACCESSORY
53 Mounting Position VERTICAL 78 Fire Safe Fireproof NO NO
54 Spring Range 1.3 - 2.6 kgf/cm2-g 79 Mech. Stop Quick Exa. NO NO
55 Include Pressure (Shutoff) 80 Hydro. Pressure YES
85 Vendor EMERSON 81 Leakage YES
PURCHASE TESTS
86 Manufacturer FISHER 82 Cryogenic N/A
87 Requisition No. R2B-P3-206-02-P-MR-00200 83 NACE Requirement NACE-0103
88 Model No. ES 84 PWHT Requirement YES
Notes:

INSTRUMENT SPECIFICATION - CONTROL VALVE


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S83.1 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Fieldbus Device Data Sheet
Tag No.: FV -21503
Fieldbus Tag No.:

Service : EA502 AML TO DA501

Basic Fieldbus Function Blocks Segment Information


Analog Input Block (AI) 1 Number Device:
1 22
20 Execution (msec)
Discrete Input Block (DI) 4 Number Segment #: DFJB-21108
2 23
15 Execution Time
3 Bias/Gain Station (BG) 0 Execution (msec) 24 LAS Capable: Yes No
Manual Loader (ML) 0 Number 25 Device Current Draw (mA): 19
4
0 Execution (msec) Device Minimum Voltage: 9.
26
Analog Output Block (AO) 1 Number Device Capacitance: 5 nF
5 20 Execution (msec) Polarity-sensitive: Yes No
27
Discrete Output Block (DO) 1 Number Segment Terminator Location:
6 20 Execution (msec)
28
7 Control Selector (CS)
DD Revision: 3
PID,PI,I Controller (PID) 29
8
20 Execution (msec)
CFF Revision: 1.9
Ratio Station (RA) 30
9
P,PD Controller (PD) 0 Number
10 0 Execution (msec)

* Execution time in msec.

Advanced Function Blocks Notes:

11 Device Control (DC)

12 Output Splitter (OS)

13 Signal Characterizer (SC)

14 Lead Lag (LL)

15 Deadtime (DT)

16 Integrator(Totalizer) (IT)

17 Setpoint Ramp Generator (SPG)

18 Input Selector (IS)

19 Arithmetic (AR)

20 Timer (TMR)

21 Analog Alarm (AAL)

INSTRUMENT SPECIFICATION -FOUNDATION FIELDBUS


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S83.2 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Tag Number : FV -21503

1. In-Built surge protector is provided by vendor.

1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S83.3 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
1 Tag No. FV -21607
2 Service GA601 OCD TO FA617
3 P&ID No. Line No. R2B-P3-206-02-A-DTI-00613 3"-CACAP-216001-T-A18T1-PP
4 Area Classification Ingress Protection CLASS 1 DIV 2 Gr. B ,C&D, T3 NEMA 4X
GENERAL 5 Ambient Temperature: Unit Min. Max. °C 10 48
6 Allowable Sound dBA Tightness Requirement <85 ANSI IV (standard)
7 Available Air Supply Pressure Unit Min. Max. kgf/cm²-g 4.2 8.0
8 Electric Connection Pneum. Connection 1/2” NPT (F) 1/4” NPT (F)
9 Power Failure Position FO
10 Line Size and Schedule Sch. Outlet Line Sch. 3 in STD 3" STD
PIPE
11 Line Class Rating Pipe Material T-A18T1 150# A106 GR.B, SMLS
LINE
12 Pipe Insulation Thickness Corrosion Allowance PP 40mm 1.6mm
13 Fluid State Phase Oily Condensate Liquid Single Phase
14 Sour Service Special Condition N/A N/A
15 Flow Rate Units Min. Nor. Max. m³/h 20.45 22.5
16 Inlet Pressure Units Min. Nor. Max. kgf/cm²-g 9.171 9.111
17 Pressure Drop Units Min. Nor. Max. kgf/cm² 7.874 7.713
18 Inlet Temperature Units Min. Nor. Max. °C 105 105 105
PROCESS 19 Density Units Min. Nor. Max. kg/m³ 944 944 944
CONDITIONS 20 Viscosity Units Min. Nor. Max. cP 0.2651 0.2651 0.2651
21 Molecular Weight (MW) Specific Gravity @ Oper.
22 Spec. Heat Ratio (Cp/Cv) Compressibility (Z)
23 Vapor Pressure (Liq.) Cavitation or Flashing 1.234 kgf/cm²-a NO
24 Critical Pressure (Liq) Flash (wt%) 225.5 kgf/cm²-a
25 Design Pressure Min. Max. -1.033 kgf/cm²-g 13 kgf/cm²-g
26 Design Temperature Min. Max. 10 °C 130 °C
27 Max.Shutoff DP Solid % 13 kgf/cm²
28 Calculated Cv Units Min. Nor. Max. Cv 8.32 9.27
CALCULATED
29 Travel Units Min. Nor. Max. % 71 73
RESULTS
30 Noise dBA @1m Units Min. Nor. Max. dBA 63 64
31 MFR Model FISHER ES 56 MFR Model FISHER DVC6200F/SC-AD
32 Body Type Single Seat Globe 57 Signal: Inlet Outlet FF Protocol 0-2.8 kgf/cm2
33 Body Size Trim Size 1.5 in 1 5/16 in 58 Increase Signal Valve: DIRECT
34 End Connec.Size & Rating 1.5" 300# RF POSITIONER 59 Cam Characteristic LINEAR
35 Rated Cv Characteristic 21 EQ% 60 Bypass Gauges N/A YES
36 Body Material WCC Steel 61 Signal Fail. to Valve FO
BODY 37 Bonnet Type Material Plain WCC Steel 62 Electric Enclosure Ex ia IIC T5 , NEMA 4X
AND 38 Flow Direct. Flow Act. To Up FTO 63 MFR Model N/A N/A
TRIM 39 Packing Type Material ISO Seal PTFE 64 Type Power N/A N/A
SOLENOID
40 Lubricator Isolat. Valve N/A N/A 65 When De-Enegr.Valve: N/A
VALVE
41 Guiding No. of Ports Cage 1 66 Material Latcher N/A N/A
42 Trim Type Internal Design Standard Unbalanced 67 Electric Enclosure N/A
43 Rated Travel Leak Class 3/4 in ANSI IV 68 MFR Model N/A N/A
44 Plug/ Ball/ Disk Material S41600 SST 69 Type Quantity N/A N/A
45 Seat Material S41600 SST SWITCHES 70 Contacts / Rating N/A
46 Cage Stem Material CB7Cu-1 SST S31600 SST 71 Switching Position N/A
47 Gasket Material S31600 SST/Graphite 72 Electric Enclosure N/A
48 MFR Model FISHER 657 73 MFR Model FISHER 67CFR
49 Type Diaphragm Spring Return AIR SET 74 Set Pressure 4.2 kgf/cm2-g
50 Size Stroke Time 30i < 5 Sec 75 Filter Gauge 5 Micron min YES
ACTUATOR 51 Air Failure Valve: FO 76 Vol. Tank Booster NO NO
52 Handwheel Location N/A 77 Diffuser Lock-up NO NO
ACCESSORY
53 Mounting Position VERTICAL 78 Fire Safe Fireproof NO NO
54 Spring Range 0.4 - 2.0 kgf/cm2-g 79 Mech. Stop Quick Exa. NO NO
55 Include Pressure (Shutoff) 80 Hydro. Pressure YES
85 Vendor EMERSON 81 Leakage YES
PURCHASE TESTS
86 Manufacturer FISHER 82 Cryogenic N/A
87 Requisition No. R2B-P3-206-02-P-MR-00200 83 NACE Requirement N/A
88 Model No. ES 84 PWHT Requirement N/A
Notes:

INSTRUMENT SPECIFICATION - CONTROL VALVE


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S84.1 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Fieldbus Device Data Sheet
Tag No.: FV -21607
Fieldbus Tag No.:

Service : GA601 OCD TO FA617

Basic Fieldbus Function Blocks Segment Information


Analog Input Block (AI) 1 Number Device:
1 22
20 Execution (msec)
Discrete Input Block (DI) 4 Number Segment #: DFJB-21155
2 23
15 Execution Time
3 Bias/Gain Station (BG) 0 Execution (msec) 24 LAS Capable: Yes No
Manual Loader (ML) 0 Number 25 Device Current Draw (mA): 19
4
0 Execution (msec) Device Minimum Voltage: 9.
26
Analog Output Block (AO) 1 Number Device Capacitance: 5 nF
5 20 Execution (msec) Polarity-sensitive: Yes No
27
Discrete Output Block (DO) 1 Number Segment Terminator Location:
6 20 Execution (msec)
28
7 Control Selector (CS)
DD Revision: 3
PID,PI,I Controller (PID) 29
8
20 Execution (msec)
CFF Revision: 1.9
Ratio Station (RA) 30
9
P,PD Controller (PD) 0 Number
10 0 Execution (msec)

* Execution time in msec.

Advanced Function Blocks Notes:

11 Device Control (DC)

12 Output Splitter (OS)

13 Signal Characterizer (SC)

14 Lead Lag (LL)

15 Deadtime (DT)

16 Integrator(Totalizer) (IT)

17 Setpoint Ramp Generator (SPG)

18 Input Selector (IS)

19 Arithmetic (AR)

20 Timer (TMR)

21 Analog Alarm (AAL)

INSTRUMENT SPECIFICATION -FOUNDATION FIELDBUS


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S84.2 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Tag Number : FV -21607

1. Valve will normally be in the closed position. Valve opening will be intermittent and generally short-term.
2. In-Built surge protector is provided by vendor.

1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S84.3 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
1 Tag No. HV -21026
2 Service FA104 HP STM TO SPE012
3 P&ID No. Line No. R2B-P3-206-02-A-DTI-00074 8"-VA-211005-T-D61T1S-EC
4 Area Classification Ingress Protection CLASS 1 DIV 2 Gr. B ,C&D, T3 NEMA 4X
GENERAL 5 Ambient Temperature: Unit Min. Max. °C 10 48
6 Allowable Sound dBA Tightness Requirement <85 ANSI IV (standard)
7 Available Air Supply Pressure Unit Min. Max. kgf/cm²-g 4.2 8.0
8 Electric Connection Pneum. Connection 1/2” NPT (F) 1/4” NPT (F)
9 Power Failure Position FO
10 Line Size and Schedule Sch. Outlet Line Sch. 8 in XS 8" XS
PIPE
11 Line Class Rating Pipe Material T-D61T1S 600# SA106 GR.B, SMLS
LINE
12 Pipe Insulation Thickness Corrosion Allowance EC 125mm 1.6mm
13 Fluid State Phase Steam Gas/Vapor Single Phase
14 Sour Service Special Condition N/A N/A
15 Flow Rate Units Min. Nor. Max. Nm³/h
16 Inlet Pressure Units Min. Nor. Max. kgf/cm²-g 49.68 49.68 49.66
17 Pressure Drop Units Min. Nor. Max. kgf/cm² 0 49.68 49.66
18 Inlet Temperature Units Min. Nor. Max. °C 264
PROCESS 19 Density Units Min. Nor. Max. kg/m³
CONDITIONS 20 Viscosity Units Min. Nor. Max. cP 0.1016
21 Molecular Weight (MW) Specific Gravity @ Oper. 18.02
22 Spec. Heat Ratio (Cp/Cv) Compressibility (Z) 1.125 0.797
23 Vapor Pressure (Liq.) Cavitation or Flashing kgf/cm²-a N/A
24 Critical Pressure (Liq) Flash (wt%) kgf/cm²-a
25 Design Pressure Min. Max. -1.033 kgf/cm²-g 55.5 kgf/cm²-g
26 Design Temperature Min. Max. 10 °C 290 °C
27 Max.Shutoff DP Solid % 55.5 kgf/cm²
28 Calculated Cv Units Min. Nor. Max. Cv
CALCULATED
29 Travel Units Min. Nor. Max. %
RESULTS
30 Noise dBA @1m Units Min. Nor. Max. dBA
31 MFR Model FISHER EWT 56 MFR Model FISHER DVC6200F/SC-AD
32 Body Type Single Seat Globe 57 Signal: Inlet Outlet FF Protocol 0-2.8 kgf/cm2
33 Body Size Trim Size 8 in 7 in 58 Increase Signal Valve: DIRECT
34 End Connec.Size & Rating 8" 600# RF POSITIONER 59 Cam Characteristic LINEAR
35 Rated Cv Characteristic 508 EQ% 60 Bypass Gauges N/A YES
36 Body Material WCC Steel 61 Signal Fail. to Valve FO
BODY 37 Bonnet Type Material Style 1 Extension WCC Steel 62 Electric Enclosure Ex ia IIC T5 , NEMA 4X
AND 38 Flow Direct. Flow Act. To Down FTO 63 MFR Model N/A N/A
TRIM 39 Packing Type Material Enviro Seal Graphite ULF 64 Type Power N/A N/A
SOLENOID
40 Lubricator Isolat. Valve N/A N/A 65 When De-Enegr.Valve: N/A
VALVE
41 Guiding No. of Ports Cage 1 66 Material Latcher N/A N/A
42 Trim Type Internal Design Standard Balanced 67 Electric Enclosure N/A
43 Rated Travel Leak Class 2 in ANSI IV 68 MFR Model N/A N/A
44 Plug/ Ball/ Disk Material S31600 SST/CoCr-A Seat 69 Type Quantity N/A N/A
45 Seat Material S31600 SST/CoCr-A Seat SWITCHES 70 Contacts / Rating N/A
46 Cage Stem Material CB7Cu-1 SST S31600 SST 71 Switching Position N/A
47 Gasket Material S31600 SST/Graphite 72 Electric Enclosure N/A
48 MFR Model FISHER 657 73 MFR Model FISHER 67CFR
49 Type Diaphragm Spring Return AIR SET 74 Set Pressure 4.2 kgf/cm2-g
50 Size Stroke Time 60i < 15 Sec 75 Filter Gauge 5 Micron min YES
ACTUATOR 51 Air Failure Valve: FO 76 Vol. Tank Booster NO NO
52 Handwheel Location N/A 77 Diffuser Lock-up NO NO
ACCESSORY
53 Mounting Position VERTICAL 78 Fire Safe Fireproof NO NO
54 Spring Range 0.6 - 1.5 kgf/cm2-g 79 Mech. Stop Quick Exa. NO NO
55 Include Pressure (Shutoff) 80 Hydro. Pressure YES
85 Vendor EMERSON 81 Leakage YES
PURCHASE TESTS
86 Manufacturer FISHER 82 Cryogenic N/A
87 Requisition No. R2B-P3-206-02-P-MR-00200 83 NACE Requirement N/A
88 Model No. EWT 84 PWHT Requirement N/A
Notes:

INSTRUMENT SPECIFICATION - CONTROL VALVE


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S85.1 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Fieldbus Device Data Sheet
Tag No.: HV -21026
Fieldbus Tag No.:

Service : FA104 HP STM TO SPE012

Basic Fieldbus Function Blocks Segment Information


Analog Input Block (AI) 1 Number Device:
1 22
20 Execution (msec)
Discrete Input Block (DI) 4 Number Segment #: DFJB-21004
2 23
15 Execution Time
3 Bias/Gain Station (BG) 0 Execution (msec) 24 LAS Capable: Yes No
Manual Loader (ML) 0 Number 25 Device Current Draw (mA): 19
4
0 Execution (msec) Device Minimum Voltage: 9.
26
Analog Output Block (AO) 1 Number Device Capacitance: 5 nF
5 20 Execution (msec) Polarity-sensitive: Yes No
27
Discrete Output Block (DO) 1 Number Segment Terminator Location:
6 20 Execution (msec)
28
7 Control Selector (CS)
DD Revision: 3
PID,PI,I Controller (PID) 29
8
20 Execution (msec)
CFF Revision: 1.9
Ratio Station (RA) 30
9
P,PD Controller (PD) 0 Number
10 0 Execution (msec)

* Execution time in msec.

Advanced Function Blocks Notes:

11 Device Control (DC)

12 Output Splitter (OS)

13 Signal Characterizer (SC)

14 Lead Lag (LL)

15 Deadtime (DT)

16 Integrator(Totalizer) (IT)

17 Setpoint Ramp Generator (SPG)

18 Input Selector (IS)

19 Arithmetic (AR)

20 Timer (TMR)

21 Analog Alarm (AAL)

INSTRUMENT SPECIFICATION -FOUNDATION FIELDBUS


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S85.2 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Tag Number : HV -21026

1. Line size valve.

2. In-Built surge protector is provided by vendor.

1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S85.3 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
1 Tag No. HV -21109
2 Service FA102 VNT TO LFL
3 P&ID No. Line No. R2B-P3-206-02-A-DTI-00128 6"-P-211204-B1A2-NACE-N
4 Area Classification Ingress Protection CLASS 1 DIV 2 Gr. B ,C&D, T3 NEMA 4X
GENERAL 5 Ambient Temperature: Unit Min. Max. °C 10 48
6 Allowable Sound dBA Tightness Requirement <85 ANSI IV (standard)
7 Available Air Supply Pressure Unit Min. Max. kgf/cm²-g 4.2 8.0
8 Electric Connection Pneum. Connection 1/2” NPT (F) 1/4” NPT (F)
9 Power Failure Position FC
10 Line Size and Schedule Sch. Outlet Line Sch. 6 in STD 6" STD
PIPE
11 Line Class Rating Pipe Material B1A2 NACE 150# A106 GR.B, SMLS
LINE
12 Pipe Insulation Thickness Corrosion Allowance N N/A 3.2mm
13 Fluid State Phase Hydrocarbon Gas/Vapor Single Phase
14 Sour Service Special Condition YES N/A
15 Flow Rate Units Min. Nor. Max. Nm³/h 2678
16 Inlet Pressure Units Min. Nor. Max. kgf/cm²-g 0.84
17 Pressure Drop Units Min. Nor. Max. kgf/cm² 0.64
18 Inlet Temperature Units Min. Nor. Max. °C 38 38 38
PROCESS 19 Density Units Min. Nor. Max. kg/m³
CONDITIONS 20 Viscosity Units Min. Nor. Max. cP 0.009 0.009 0.009
21 Molecular Weight (MW) Specific Gravity @ Oper. 19.32
22 Spec. Heat Ratio (Cp/Cv) Compressibility (Z) 1.24 0.99
23 Vapor Pressure (Liq.) Cavitation or Flashing kgf/cm²-a N/A
24 Critical Pressure (Liq) Flash (wt%) kgf/cm²-a
25 Design Pressure Min. Max. kgf/cm²-g 3.5 kgf/cm²-g
26 Design Temperature Min. Max. 10 °C 120 °C
27 Max.Shutoff DP Solid % 3.5 kgf/cm²
28 Calculated Cv Units Min. Nor. Max. Cv 112
CALCULATED
29 Travel Units Min. Nor. Max. % 43
RESULTS
30 Noise dBA @1m Units Min. Nor. Max. dBA 85
31 MFR Model FISHER ET 56 MFR Model FISHER DVC6200F/SC-AD
32 Body Type Single Seat Globe 57 Signal: Inlet Outlet FF Protocol 0-2.8 kgf/cm2
33 Body Size Trim Size 4 in 4 3/8 in 58 Increase Signal Valve: DIRECT
34 End Connec.Size & Rating 4" 300# RF POSITIONER 59 Cam Characteristic LINEAR
35 Rated Cv Characteristic 236 Linear 60 Bypass Gauges N/A YES
36 Body Material WCC Steel 61 Signal Fail. to Valve FC
BODY 37 Bonnet Type Material Plain WCC Steel 62 Electric Enclosure Ex ia IIC T5 , NEMA 4X
AND 38 Flow Direct. Flow Act. To Down FTO 63 MFR Model N/A N/A
TRIM 39 Packing Type Material ISO Seal PTFE 64 Type Power N/A N/A
SOLENOID
40 Lubricator Isolat. Valve N/A N/A 65 When De-Enegr.Valve: N/A
VALVE
41 Guiding No. of Ports Cage 1 66 Material Latcher N/A N/A
42 Trim Type Internal Design Standard Balanced 67 Electric Enclosure N/A
43 Rated Travel Leak Class 2 in ANSI IV 68 MFR Model N/A N/A
44 Plug/ Ball/ Disk Material S31600 SST/CoCr-A Seat 69 Type Quantity N/A N/A
45 Seat Material R30006 Cobalt Alloy SWITCHES 70 Contacts / Rating N/A
46 Cage Stem Material S31600 SST/ ENCS20910 SST 71 Switching Position N/A
47 Gasket Material S31600 SST/Graphite 72 Electric Enclosure N/A
48 MFR Model FISHER 667 73 MFR Model FISHER 67CFR
49 Type Diaphragm Spring Return AIR SET 74 Set Pressure 4.2 kgf/cm2-g
50 Size Stroke Time 45i < 10 Sec 75 Filter Gauge 5 Micron min YES
ACTUATOR 51 Air Failure Valve: FC 76 Vol. Tank Booster NO NO
52 Handwheel Location Side Mounted 77 Diffuser Lock-up NO NO
ACCESSORY
53 Mounting Position VERTICAL 78 Fire Safe Fireproof NO NO
54 Spring Range 0.6 - 2.0 kgf/cm2-g 79 Mech. Stop Quick Exa. NO NO
55 Include Pressure (Shutoff) 80 Hydro. Pressure YES
85 Vendor EMERSON 81 Leakage YES
PURCHASE TESTS
86 Manufacturer FISHER 82 Cryogenic N/A
87 Requisition No. R2B-P3-206-02-P-MR-00200 83 NACE Requirement NACE-0103
88 Model No. ET 84 PWHT Requirement YES
Notes:

INSTRUMENT SPECIFICATION - CONTROL VALVE


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S86.1 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Fieldbus Device Data Sheet
Tag No.: HV -21109
Fieldbus Tag No.:

Service : FA102 VNT TO LFL

Basic Fieldbus Function Blocks Segment Information


Analog Input Block (AI) 1 Number Device:
1 22
20 Execution (msec)
Discrete Input Block (DI) 4 Number Segment #: DFJB-21084
2 23
15 Execution Time
3 Bias/Gain Station (BG) 0 Execution (msec) 24 LAS Capable: Yes No
Manual Loader (ML) 0 Number 25 Device Current Draw (mA): 19
4
0 Execution (msec) Device Minimum Voltage: 9.
26
Analog Output Block (AO) 1 Number Device Capacitance: 5 nF
5 20 Execution (msec) Polarity-sensitive: Yes No
27
Discrete Output Block (DO) 1 Number Segment Terminator Location:
6 20 Execution (msec)
28
7 Control Selector (CS)
DD Revision: 3
PID,PI,I Controller (PID) 29
8
20 Execution (msec)
CFF Revision: 1.9
Ratio Station (RA) 30
9
P,PD Controller (PD) 0 Number
10 0 Execution (msec)

* Execution time in msec.

Advanced Function Blocks Notes:

11 Device Control (DC)

12 Output Splitter (OS)

13 Signal Characterizer (SC)

14 Lead Lag (LL)

15 Deadtime (DT)

16 Integrator(Totalizer) (IT)

17 Setpoint Ramp Generator (SPG)

18 Input Selector (IS)

19 Arithmetic (AR)

20 Timer (TMR)

21 Analog Alarm (AAL)

INSTRUMENT SPECIFICATION -FOUNDATION FIELDBUS


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S86.2 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Tag Number : HV -21109

1. Valve will normally be in the closed position. Valve opening will be intermittent and generally short-term.
2. Special PWHT Required .
3. In-Built surge protector is provided by vendor.

1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S86.3 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
1 Tag No. FV -21076
2 Service SPE020EA2 COND TO SPE020
3 P&ID No. Line No. R2B-P3-206-02-A-DTI-00078 6"-P-210619-T-A18T1-N
4 Area Classification Ingress Protection CLASS 1 DIV 2 Gr. B ,C&D, T3 NEMA 4X
GENERAL 5 Ambient Temperature: Unit Min. Max. °C 10 48
6 Allowable Sound dBA Tightness Requirement <85 ANSI IV (standard)
7 Available Air Supply Pressure Unit Min. Max. kgf/cm²-g 4.2 8.0
8 Electric Connection Pneum. Connection 1/2” NPT (F) 1/4” NPT (F)
9 Power Failure Position FO
10 Line Size and Schedule Sch. Outlet Line Sch. 6 in STD 6" STD
PIPE
11 Line Class Rating Pipe Material T-A18T1 150# A106 GR.B, SMLS
LINE
12 Pipe Insulation Thickness Corrosion Allowance N N/A 1.6mm
13 Fluid State Phase Water Liquid Single Phase
14 Sour Service Special Condition N/A N/A
15 Flow Rate Units Min. Nor. Max. m³/h 36.79 40.47
16 Inlet Pressure Units Min. Nor. Max. kgf/cm²-g 7.54 7.442 7.412
17 Pressure Drop Units Min. Nor. Max. kgf/cm² 7.977 7.843 7.803
18 Inlet Temperature Units Min. Nor. Max. °C 51 51 51
PROCESS 19 Density Units Min. Nor. Max. kg/m³ 989 989 989
CONDITIONS 20 Viscosity Units Min. Nor. Max. cP 0.539 0.539 0.539
21 Molecular Weight (MW) Specific Gravity @ Oper.
22 Spec. Heat Ratio (Cp/Cv) Compressibility (Z)
23 Vapor Pressure (Liq.) Cavitation or Flashing 0.13 kgf/cm²-a NO
24 Critical Pressure (Liq) Flash (wt%) 224.99 kgf/cm²-a
25 Design Pressure Min. Max. -1.033 kgf/cm²-g 13 kgf/cm²-g
26 Design Temperature Min. Max. 10 °C 80 °C
27 Max.Shutoff DP Solid % 13 kgf/cm²
28 Calculated Cv Units Min. Nor. Max. Cv 20.7 42.1 46.5
CALCULATED
29 Travel Units Min. Nor. Max. % 63 80 83
RESULTS
30 Noise dBA @1m Units Min. Nor. Max. dBA 75 78 79
31 MFR Model FISHER ET 56 MFR Model FISHER DVC6200F/SC-AD
32 Body Type Single Seat Globe 57 Signal: Inlet Outlet FF Protocol 0-2.8 kgf/cm2
33 Body Size Trim Size 3 in 2 5/16 in 58 Increase Signal Valve: DIRECT
34 End Connec.Size & Rating 3" 300# RF POSITIONER 59 Cam Characteristic LINEAR
35 Rated Cv Characteristic 70.7 EQ% 60 Bypass Gauges N/A YES
36 Body Material WCC Steel 61 Signal Fail. to Valve FO
BODY 37 Bonnet Type Material Plain WCC Steel 62 Electric Enclosure Ex ia IIC T5 , NEMA 4X
AND 38 Flow Direct. Flow Act. To Down FTO 63 MFR Model N/A N/A
TRIM 39 Packing Type Material Enviro Seal PTFE Carbon 64 Type Power N/A N/A
SOLENOID
40 Lubricator Isolat. Valve N/A N/A 65 When De-Enegr.Valve: N/A
VALVE
41 Guiding No. of Ports Cage 1 66 Material Latcher N/A N/A
42 Trim Type Internal Design Standard Balanced 67 Electric Enclosure N/A
43 Rated Travel Leak Class 1 1/8 in ANSI IV 68 MFR Model N/A N/A
44 Plug/ Ball/ Disk Material S41600 SST 69 Type Quantity N/A N/A
45 Seat Material S41600 SST SWITCHES 70 Contacts / Rating N/A
46 Cage Stem Material CB7Cu-1 SST S31600 SST 71 Switching Position N/A
47 Gasket Material S31600 SST/Graphite 72 Electric Enclosure N/A
48 MFR Model FISHER 657 73 MFR Model FISHER 67CFR
49 Type Diaphragm Spring Return AIR SET 74 Set Pressure 4.2 kgf/cm2-g
50 Size Stroke Time 40i < 8 Sec 75 Filter Gauge 5 Micron min YES
ACTUATOR 51 Air Failure Valve: FO 76 Vol. Tank Booster NO NO
52 Handwheel Location N/A 77 Diffuser Lock-up NO NO
ACCESSORY
53 Mounting Position VERTICAL 78 Fire Safe Fireproof NO NO
54 Spring Range 0.8 - 2.0 kgf/cm2-g 79 Mech. Stop Quick Exa. NO NO
55 Include Pressure (Shutoff) 80 Hydro. Pressure YES
85 Vendor EMERSON 81 Leakage YES
PURCHASE TESTS
86 Manufacturer FISHER 82 Cryogenic N/A
87 Requisition No. R2B-P3-206-02-P-MR-00200 83 NACE Requirement N/A
88 Model No. ET 84 PWHT Requirement N/A
Notes:

INSTRUMENT SPECIFICATION - CONTROL VALVE


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S87.1 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Fieldbus Device Data Sheet
Tag No.: FV -21076
Fieldbus Tag No.:

Service : SPE020EA2 COND TO SPE020

Basic Fieldbus Function Blocks Segment Information


Analog Input Block (AI) 1 Number Device:
1 22
20 Execution (msec)
Discrete Input Block (DI) 4 Number Segment #: DFJB-21008
2 23
15 Execution Time
3 Bias/Gain Station (BG) 0 Execution (msec) 24 LAS Capable: Yes No
Manual Loader (ML) 0 Number 25 Device Current Draw (mA): 19
4
0 Execution (msec) Device Minimum Voltage: 9.
26
Analog Output Block (AO) 1 Number Device Capacitance: 5 nF
5 20 Execution (msec) Polarity-sensitive: Yes No
27
Discrete Output Block (DO) 1 Number Segment Terminator Location:
6 20 Execution (msec)
28
7 Control Selector (CS)
DD Revision: 3
PID,PI,I Controller (PID) 29
8
20 Execution (msec)
CFF Revision: 1.9
Ratio Station (RA) 30
9
P,PD Controller (PD) 0 Number
10 0 Execution (msec)

* Execution time in msec.

Advanced Function Blocks Notes:

11 Device Control (DC)

12 Output Splitter (OS)

13 Signal Characterizer (SC)

14 Lead Lag (LL)

15 Deadtime (DT)

16 Integrator(Totalizer) (IT)

17 Setpoint Ramp Generator (SPG)

18 Input Selector (IS)

19 Arithmetic (AR)

20 Timer (TMR)

21 Analog Alarm (AAL)

INSTRUMENT SPECIFICATION -FOUNDATION FIELDBUS


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S87.2 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Tag Number : FV -21076

1. Valve will normally be in the closed position. Valve opening will be intermittent and generally short-term.
2. In-Built surge protector is provided by vendor.

1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S87.3 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
1 Tag No. LV -21126
2 Service GA108AB WS TO WS TRT
3 P&ID No. Line No. R2B-P3-206-02-A-DTI-00129 6"-AAM-211003-B1A2-NACE-N
4 Area Classification Ingress Protection CLASS 1 DIV 2 Gr. B ,C&D, T3 NEMA 4X
GENERAL 5 Ambient Temperature: Unit Min. Max. °C 10 48
6 Allowable Sound dBA Tightness Requirement <85 ANSI IV (standard)
7 Available Air Supply Pressure Unit Min. Max. kgf/cm²-g 4.2 8.0
8 Electric Connection Pneum. Connection 1/2” NPT (F) 1/4” NPT (F)
9 Power Failure Position FC
10 Line Size and Schedule Sch. Outlet Line Sch. 6 in STD 4" STD
PIPE
11 Line Class Rating Pipe Material B1A2-NACE 150# A106 GR.B, SMLS
LINE
12 Pipe Insulation Thickness Corrosion Allowance N N/A 3.2mm
13 Fluid State Phase Water Liquid Single Phase
14 Sour Service Special Condition YES N/A
15 Flow Rate Units Min. Nor. Max. m³/h 16.7 29.9 32.8
16 Inlet Pressure Units Min. Nor. Max. kgf/cm²-g 8.436 8.15 7.987
17 Pressure Drop Units Min. Nor. Max. kgf/cm² 6.52 4.77 0.898
18 Inlet Temperature Units Min. Nor. Max. °C 38 39 39
PROCESS 19 Density Units Min. Nor. Max. kg/m³ 978 978 978
CONDITIONS 20 Viscosity Units Min. Nor. Max. cP 0.675 0.675 0.675
21 Molecular Weight (MW) Specific Gravity @ Oper.
22 Spec. Heat Ratio (Cp/Cv) Compressibility (Z)
23 Vapor Pressure (Liq.) Cavitation or Flashing 0.56 kgf/cm²-a NO
24 Critical Pressure (Liq) Flash (wt%) 224.99 kgf/cm²-a
25 Design Pressure Min. Max. kgf/cm²-g 13 kgf/cm²-g
26 Design Temperature Min. Max. 10 °C 120 °C
27 Max.Shutoff DP Solid % 13 kgf/cm²
28 Calculated Cv Units Min. Nor. Max. Cv 7.55 15.8 40.3
CALCULATED
29 Travel Units Min. Nor. Max. % 11 23 55
RESULTS
30 Noise dBA @1m Units Min. Nor. Max. dBA 66 63 50
31 MFR Model FISHER EZ 56 MFR Model FISHER DVC6200F/SC-AD
32 Body Type Single Seat Globe 57 Signal: Inlet Outlet FF Protocol 0-2.8 kgf/cm2
33 Body Size Trim Size 3 in 2 in 58 Increase Signal Valve: DIRECT
34 End Connec.Size & Rating 3" 300# RF POSITIONER 59 Cam Characteristic LINEAR
35 Rated Cv Characteristic 80.4 Linear 60 Bypass Gauges N/A YES
36 Body Material WCC Steel 61 Signal Fail. to Valve FC
BODY 37 Bonnet Type Material Plain WCC Steel 62 Electric Enclosure Ex ia IIC T5 , NEMA 4X
AND 38 Flow Direct. Flow Act. To Up FTO 63 MFR Model N/A N/A
TRIM 39 Packing Type Material ISO Seal PTFE 64 Type Power N/A N/A
SOLENOID
40 Lubricator Isolat. Valve N/A N/A 65 When De-Enegr.Valve: N/A
VALVE
41 Guiding No. of Ports Post 1 66 Material Latcher N/A N/A
42 Trim Type Internal Design Standard Unbalanced 67 Electric Enclosure N/A
43 Rated Travel Leak Class 1 1/8 in ANSI IV 68 MFR Model N/A N/A
44 Plug/ Ball/ Disk Material S31600 SST/CoCr-A Seat 69 Type Quantity N/A N/A
45 Seat Material R30006 Cobalt Alloy SWITCHES 70 Contacts / Rating N/A
46 Cage Stem Material N/A S20910 SST 71 Switching Position N/A
47 Gasket Material S31600 SST/Graphite 72 Electric Enclosure N/A
48 MFR Model FISHER 667 73 MFR Model FISHER 67CFR
49 Type Diaphragm Spring Return AIR SET 74 Set Pressure 4.2 kgf/cm2-g
50 Size Stroke Time 45i < 8 Sec 75 Filter Gauge 5 Micron min YES
ACTUATOR 51 Air Failure Valve: FC 76 Vol. Tank Booster NO NO
52 Handwheel Location N/A 77 Diffuser Lock-up NO NO
ACCESSORY
53 Mounting Position VERTICAL 78 Fire Safe Fireproof NO NO
54 Spring Range 0.8 - 2.4 kgf/cm2-g 79 Mech. Stop Quick Exa. NO NO
55 Include Pressure (Shutoff) 80 Hydro. Pressure YES
85 Vendor EMERSON 81 Leakage YES
PURCHASE TESTS
86 Manufacturer FISHER 82 Cryogenic N/A
87 Requisition No. R2B-P3-206-02-P-MR-00200 83 NACE Requirement NACE-0103
88 Model No. EZ 84 PWHT Requirement YES
Notes:

INSTRUMENT SPECIFICATION - CONTROL VALVE


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S88.1 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Fieldbus Device Data Sheet
Tag No.: LV -21126
Fieldbus Tag No.:

Service : GA108AB WS TO WS TRT

Basic Fieldbus Function Blocks Segment Information


Analog Input Block (AI) 1 Number Device:
1 22
20 Execution (msec)
Discrete Input Block (DI) 4 Number Segment #: DFJB-21071
2 23
15 Execution Time
3 Bias/Gain Station (BG) 0 Execution (msec) 24 LAS Capable: Yes No
Manual Loader (ML) 0 Number 25 Device Current Draw (mA): 19
4
0 Execution (msec) Device Minimum Voltage: 9.
26
Analog Output Block (AO) 1 Number Device Capacitance: 5 nF
5 20 Execution (msec) Polarity-sensitive: Yes No
27
Discrete Output Block (DO) 1 Number Segment Terminator Location:
6 20 Execution (msec)
28
7 Control Selector (CS)
DD Revision: 3
PID,PI,I Controller (PID) 29
8
20 Execution (msec)
CFF Revision: 1.9
Ratio Station (RA) 30
9
P,PD Controller (PD) 0 Number
10 0 Execution (msec)

* Execution time in msec.

Advanced Function Blocks Notes:

11 Device Control (DC)

12 Output Splitter (OS)

13 Signal Characterizer (SC)

14 Lead Lag (LL)

15 Deadtime (DT)

16 Integrator(Totalizer) (IT)

17 Setpoint Ramp Generator (SPG)

18 Input Selector (IS)

19 Arithmetic (AR)

20 Timer (TMR)

21 Analog Alarm (AAL)

INSTRUMENT SPECIFICATION -FOUNDATION FIELDBUS


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S88.2 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Tag Number : LV -21126

1. Special PWHT Required .


2. In-Built surge protector is provided by vendor.

1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S88.3 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
1 Tag No. LV -21200
2 Service CLD COND TO GA202AB
3 P&ID No. Line No. R2B-P3-206-02-A-DTI-00201 3"-APR-212002-B1A1-N
4 Area Classification Ingress Protection CLASS 1 DIV 2 Gr. B ,C&D, T3 NEMA 4X
GENERAL 5 Ambient Temperature: Unit Min. Max. °C 10 48
6 Allowable Sound dBA Tightness Requirement <85 ANSI IV (standard)
7 Available Air Supply Pressure Unit Min. Max. kgf/cm²-g 4.2 8.0
8 Electric Connection Pneum. Connection 1/2” NPT (F) 1/4” NPT (F)
9 Power Failure Position FC
10 Line Size and Schedule Sch. Outlet Line Sch. 3 in STD 3" STD
PIPE
11 Line Class Rating Pipe Material B1A1 150# A106 GR.B, SMLS
LINE
12 Pipe Insulation Thickness Corrosion Allowance N N/A 1.6mm
13 Fluid State Phase Water Liquid Single Phase
14 Sour Service Special Condition N/A N/A
15 Flow Rate Units Min. Nor. Max. m³/h 11.1 22.1 24.3
16 Inlet Pressure Units Min. Nor. Max. kgf/cm²-g 5.691 5.1 4.93
17 Pressure Drop Units Min. Nor. Max. kgf/cm² 4.85 4.3 4
18 Inlet Temperature Units Min. Nor. Max. °C 50 50 50
PROCESS 19 Density Units Min. Nor. Max. kg/m³ 966 966 966
CONDITIONS 20 Viscosity Units Min. Nor. Max. cP 0.544 0.544 0.544
21 Molecular Weight (MW) Specific Gravity @ Oper.
22 Spec. Heat Ratio (Cp/Cv) Compressibility (Z)
23 Vapor Pressure (Liq.) Cavitation or Flashing 0.13 kgf/cm²-a NO
24 Critical Pressure (Liq) Flash (wt%) 224.99 kgf/cm²-a
25 Design Pressure Min. Max. kgf/cm²-g 13 kgf/cm²-g
26 Design Temperature Min. Max. 10 °C 120 °C
27 Max.Shutoff DP Solid % 13 kgf/cm²
28 Calculated Cv Units Min. Nor. Max. Cv 5.8 12.4 14.2
CALCULATED
29 Travel Units Min. Nor. Max. % 27 53 59
RESULTS
30 Noise dBA @1m Units Min. Nor. Max. dBA 59 62 61
31 MFR Model FISHER ES 56 MFR Model FISHER DVC6200F/SC-AD
32 Body Type Single Seat Globe 57 Signal: Inlet Outlet FF Protocol 0-3.5 kgf/cm2
33 Body Size Trim Size 1.5 in 1 5/16 in 58 Increase Signal Valve: DIRECT
34 End Connec.Size & Rating 1.5" 300# RF POSITIONER 59 Cam Characteristic LINEAR
35 Rated Cv Characteristic 26.9 Linear 60 Bypass Gauges N/A YES
36 Body Material WCC Steel 61 Signal Fail. to Valve FC
BODY 37 Bonnet Type Material Plain WCC Steel 62 Electric Enclosure Ex ia IIC T5 , NEMA 4X
AND 38 Flow Direct. Flow Act. To Up FTO 63 MFR Model N/A N/A
TRIM 39 Packing Type Material ISO Seal PTFE 64 Type Power N/A N/A
SOLENOID
40 Lubricator Isolat. Valve N/A N/A 65 When De-Enegr.Valve: N/A
VALVE
41 Guiding No. of Ports Cage 1 66 Material Latcher N/A N/A
42 Trim Type Internal Design Standard Unbalanced 67 Electric Enclosure N/A
43 Rated Travel Leak Class 3/4 in ANSI IV 68 MFR Model N/A N/A
44 Plug/ Ball/ Disk Material S41600 SST 69 Type Quantity N/A N/A
45 Seat Material S41600 SST SWITCHES 70 Contacts / Rating N/A
46 Cage Stem Material CB7Cu-1 SST S31600 SST 71 Switching Position N/A
47 Gasket Material S31600 SST/Graphite 72 Electric Enclosure N/A
48 MFR Model FISHER 667 73 MFR Model FISHER 67CFR
49 Type Diaphragm Spring Return AIR SET 74 Set Pressure 4.2 kgf/cm2-g
50 Size Stroke Time 34i < 5 Sec 75 Filter Gauge 5 Micron min YES
ACTUATOR 51 Air Failure Valve: FC 76 Vol. Tank Booster NO NO
52 Handwheel Location Side Mounted 77 Diffuser Lock-up NO NO
ACCESSORY
53 Mounting Position VERTICAL 78 Fire Safe Fireproof NO NO
54 Spring Range 0.7 - 2.0 kgf/cm2-g 79 Mech. Stop Quick Exa. NO NO
55 Include Pressure (Shutoff) 80 Hydro. Pressure YES
85 Vendor EMERSON 81 Leakage YES
PURCHASE TESTS
86 Manufacturer FISHER 82 Cryogenic N/A
87 Requisition No. R2B-P3-206-02-P-MR-00200 83 NACE Requirement N/A
88 Model No. ES 84 PWHT Requirement N/A
Notes:

INSTRUMENT SPECIFICATION - CONTROL VALVE


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S89.1 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Fieldbus Device Data Sheet
Tag No.: LV -21200
Fieldbus Tag No.:

Service : CLD COND TO GA202AB

Basic Fieldbus Function Blocks Segment Information


Analog Input Block (AI) 1 Number Device:
1 22
20 Execution (msec)
Discrete Input Block (DI) 4 Number Segment #: DFJB-21121
2 23
15 Execution Time
3 Bias/Gain Station (BG) 0 Execution (msec) 24 LAS Capable: Yes No
Manual Loader (ML) 0 Number 25 Device Current Draw (mA): 19
4
0 Execution (msec) Device Minimum Voltage: 9.
26
Analog Output Block (AO) 1 Number Device Capacitance: 5 nF
5 20 Execution (msec) Polarity-sensitive: Yes No
27
Discrete Output Block (DO) 1 Number Segment Terminator Location:
6 20 Execution (msec)
28
7 Control Selector (CS)
DD Revision: 3
PID,PI,I Controller (PID) 29
8
20 Execution (msec)
CFF Revision: 1.9
Ratio Station (RA) 30
9
P,PD Controller (PD) 0 Number
10 0 Execution (msec)

* Execution time in msec.

Advanced Function Blocks Notes:

11 Device Control (DC)

12 Output Splitter (OS)

13 Signal Characterizer (SC)

14 Lead Lag (LL)

15 Deadtime (DT)

16 Integrator(Totalizer) (IT)

17 Setpoint Ramp Generator (SPG)

18 Input Selector (IS)

19 Arithmetic (AR)

20 Timer (TMR)

21 Analog Alarm (AAL)

INSTRUMENT SPECIFICATION -FOUNDATION FIELDBUS


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S89.2 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Tag Number : LV -21200

1. Valve will normally be in the closed position. Valve opening will be intermittent and generally short-term.

2. In-Built surge protector is provided by vendor.

1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S89.3 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
1 Tag No. LV -21205
2 Service GA201AB HC COND TO EC202
3 P&ID No. Line No. R2B-P3-206-02-A-DTI-00210 6"-P-212118-B2A2-NACE-N
4 Area Classification Ingress Protection CLASS 1 DIV 2 Gr. B ,C&D, T3 NEMA 4X
GENERAL 5 Ambient Temperature: Unit Min. Max. °C 10 48
6 Allowable Sound dBA Tightness Requirement <85 ANSI IV (standard)
7 Available Air Supply Pressure Unit Min. Max. kgf/cm²-g 4.2 8.0
8 Electric Connection Pneum. Connection 1/2” NPT (F) 1/4” NPT (F)
9 Power Failure Position FC
10 Line Size and Schedule Sch. Outlet Line Sch. 6 in XS 6" XS
PIPE
11 Line Class Rating Pipe Material B2A2 NACE 300# A106 GR.B, SMLS
LINE
12 Pipe Insulation Thickness Corrosion Allowance N N/A 3.2mm
13 Fluid State Phase Water and Hydrocarbon Liquid Single Phase
14 Sour Service Special Condition YES N/A
15 Flow Rate Units Min. Nor. Max. m³/h 62 124 149
16 Inlet Pressure Units Min. Nor. Max. kgf/cm²-g 23.91 22.03 20.99
17 Pressure Drop Units Min. Nor. Max. kgf/cm² 5.004 2.767 1.528
18 Inlet Temperature Units Min. Nor. Max. °C 38 38 38
PROCESS 19 Density Units Min. Nor. Max. kg/m³ 757 757 757
CONDITIONS 20 Viscosity Units Min. Nor. Max. cP 0.502 0.502 0.502
21 Molecular Weight (MW) Specific Gravity @ Oper.
22 Spec. Heat Ratio (Cp/Cv) Compressibility (Z)
23 Vapor Pressure (Liq.) Cavitation or Flashing 5.17 kgf/cm²-a NO
24 Critical Pressure (Liq) Flash (wt%) 38.57 kgf/cm²-a
25 Design Pressure Min. Max. kgf/cm²-g 28 kgf/cm²-g
26 Design Temperature Min. Max. 10 °C 120 °C
27 Max.Shutoff DP Solid % 28 kgf/cm²
28 Calculated Cv Units Min. Nor. Max. Cv 28.3 78.2 134
CALCULATED
29 Travel Units Min. Nor. Max. % 38 60 72
RESULTS
30 Noise dBA @1m Units Min. Nor. Max. dBA 56 55 52
31 MFR Model FISHER ET 56 MFR Model FISHER DVC6200F/SC-AD
32 Body Type Single Seat Globe 57 Signal: Inlet Outlet FF Protocol 0-2.8 kgf/cm2
33 Body Size Trim Size 4 in 4 3/8 in 58 Increase Signal Valve: DIRECT
34 End Connec.Size & Rating 4" 300# RF POSITIONER 59 Cam Characteristic LINEAR
35 Rated Cv Characteristic 224 EQ% 60 Bypass Gauges N/A YES
36 Body Material WCC Steel 61 Signal Fail. to Valve FC
BODY 37 Bonnet Type Material Plain WCC Steel 62 Electric Enclosure Ex ia IIC T5 , NEMA 4X
AND 38 Flow Direct. Flow Act. To Down FTO 63 MFR Model N/A N/A
TRIM 39 Packing Type Material ISO Seal PTFE 64 Type Power N/A N/A
SOLENOID
40 Lubricator Isolat. Valve N/A N/A 65 When De-Enegr.Valve: N/A
VALVE
41 Guiding No. of Ports Cage 1 66 Material Latcher N/A N/A
42 Trim Type Internal Design Standard Balanced 67 Electric Enclosure N/A
43 Rated Travel Leak Class 2 in ANSI IV 68 MFR Model N/A N/A
44 Plug/ Ball/ Disk Material S31600 SST/CoCr-A Seat 69 Type Quantity N/A N/A
45 Seat Material R30006 Cobalt Alloy SWITCHES 70 Contacts / Rating N/A
46 Cage Stem Material S31600 SST/ ENCS20910 SST 71 Switching Position N/A
47 Gasket Material S31600 SST/Graphite 72 Electric Enclosure N/A
48 MFR Model FISHER 667 73 MFR Model FISHER 67CFR
49 Type Diaphragm Spring Return AIR SET 74 Set Pressure 4.2 kgf/cm2-g
50 Size Stroke Time 45i < 10 Sec 75 Filter Gauge 5 Micron min YES
ACTUATOR 51 Air Failure Valve: FC 76 Vol. Tank Booster NO NO
52 Handwheel Location N/A 77 Diffuser Lock-up NO NO
ACCESSORY
53 Mounting Position VERTICAL 78 Fire Safe Fireproof NO NO
54 Spring Range 0.8 - 2.5 kgf/cm2-g 79 Mech. Stop Quick Exa. NO NO
55 Include Pressure (Shutoff) 80 Hydro. Pressure YES
85 Vendor EMERSON 81 Leakage YES
PURCHASE TESTS
86 Manufacturer FISHER 82 Cryogenic N/A
87 Requisition No. R2B-P3-206-02-P-MR-00200 83 NACE Requirement NACE-0103
88 Model No. ET 84 PWHT Requirement YES
Notes:

INSTRUMENT SPECIFICATION - CONTROL VALVE


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S90.1 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Fieldbus Device Data Sheet
Tag No.: LV -21205
Fieldbus Tag No.:

Service : GA201AB HC COND TO EC202

Basic Fieldbus Function Blocks Segment Information


Analog Input Block (AI) 1 Number Device:
1 22
20 Execution (msec)
Discrete Input Block (DI) 4 Number Segment #: DFJB-21092
2 23
15 Execution Time
3 Bias/Gain Station (BG) 0 Execution (msec) 24 LAS Capable: Yes No
Manual Loader (ML) 0 Number 25 Device Current Draw (mA): 19
4
0 Execution (msec) Device Minimum Voltage: 9.
26
Analog Output Block (AO) 1 Number Device Capacitance: 5 nF
5 20 Execution (msec) Polarity-sensitive: Yes No
27
Discrete Output Block (DO) 1 Number Segment Terminator Location:
6 20 Execution (msec)
28
7 Control Selector (CS)
DD Revision: 3
PID,PI,I Controller (PID) 29
8
20 Execution (msec)
CFF Revision: 1.9
Ratio Station (RA) 30
9
P,PD Controller (PD) 0 Number
10 0 Execution (msec)

* Execution time in msec.

Advanced Function Blocks Notes:

11 Device Control (DC)

12 Output Splitter (OS)

13 Signal Characterizer (SC)

14 Lead Lag (LL)

15 Deadtime (DT)

16 Integrator(Totalizer) (IT)

17 Setpoint Ramp Generator (SPG)

18 Input Selector (IS)

19 Arithmetic (AR)

20 Timer (TMR)

21 Analog Alarm (AAL)

INSTRUMENT SPECIFICATION -FOUNDATION FIELDBUS


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S90.2 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Tag Number : LV -21205

1. Valve will normally be in the closed position. Valve opening will be intermittent and generally short-term.
2. Special PWHT Required .
3. In-Built surge protector is provided by vendor.

1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S90.3 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
1 Tag No. LV -21214
2 Service GA204AB RICH OIL TO EC202
3 P&ID No. Line No. R2B-P3-206-02-A-DTI-00216 10"-P-212054-B2A2-NACE-N
4 Area Classification Ingress Protection CLASS 1 DIV 2 Gr. B ,C&D, T3 NEMA 4X
GENERAL 5 Ambient Temperature: Unit Min. Max. °C 10 48
6 Allowable Sound dBA Tightness Requirement <85 ANSI IV (standard)
7 Available Air Supply Pressure Unit Min. Max. kgf/cm²-g 4.2 8.0
8 Electric Connection Pneum. Connection 1/2” NPT (F) 1/4” NPT (F)
9 Power Failure Position FC
10 Line Size and Schedule Sch. Outlet Line Sch. 10 in XS 10" XS
PIPE
11 Line Class Rating Pipe Material B2A2 NACE 300# A106 GR.B, SMLS
LINE
12 Pipe Insulation Thickness Corrosion Allowance N N/A 3.2mm
13 Fluid State Phase Hydrocarbon Liquid Single Phase
14 Sour Service Special Condition YES N/A
15 Flow Rate Units Min. Nor. Max. m³/h 319 638 733.7
16 Inlet Pressure Units Min. Nor. Max. kgf/cm²-g 20.31 20.2 20.17
17 Pressure Drop Units Min. Nor. Max. kgf/cm² 3.46 2.15 1.287
18 Inlet Temperature Units Min. Nor. Max. °C 47 47 47
PROCESS 19 Density Units Min. Nor. Max. kg/m³ 699 699 699
CONDITIONS 20 Viscosity Units Min. Nor. Max. cP 0.341 0.341 0.341
21 Molecular Weight (MW) Specific Gravity @ Oper.
22 Spec. Heat Ratio (Cp/Cv) Compressibility (Z)
23 Vapor Pressure (Liq.) Cavitation or Flashing 15.83 kgf/cm²-a NO
24 Critical Pressure (Liq) Flash (wt%) 39.21 kgf/cm²-a
25 Design Pressure Min. Max. kgf/cm²-g 25.6 kgf/cm²-g
26 Design Temperature Min. Max. 10 °C 120 °C
27 Max.Shutoff DP Solid % 25.6 kgf/cm²
28 Calculated Cv Units Min. Nor. Max. Cv 167 425 631
CALCULATED
29 Travel Units Min. Nor. Max. % 38 58 70
RESULTS
30 Noise dBA @1m Units Min. Nor. Max. dBA 79 71 61
31 MFR Model FISHER EWT 56 MFR Model FISHER DVC6200F/SC-AD
32 Body Type Single Seat Globe 57 Signal: Inlet Outlet FF Protocol 0-2.8 kgf/cm2
33 Body Size Trim Size 10 in 8 in 58 Increase Signal Valve: DIRECT
34 End Connec.Size & Rating 10" 300# RF POSITIONER 59 Cam Characteristic LINEAR
35 Rated Cv Characteristic 924 EQ% 60 Bypass Gauges N/A YES
36 Body Material WCC Steel 61 Signal Fail. to Valve FC
BODY 37 Bonnet Type Material Plain WCC Steel 62 Electric Enclosure Ex ia IIC T5 , NEMA 4X
AND 38 Flow Direct. Flow Act. To Down FTO 63 MFR Model N/A N/A
TRIM 39 Packing Type Material ISO Seal PTFE 64 Type Power N/A N/A
SOLENOID
40 Lubricator Isolat. Valve N/A N/A 65 When De-Enegr.Valve: N/A
VALVE
41 Guiding No. of Ports Cage 1 66 Material Latcher N/A N/A
42 Trim Type Internal Design Standard Balanced 67 Electric Enclosure N/A
43 Rated Travel Leak Class 3 in ANSI IV 68 MFR Model N/A N/A
44 Plug/ Ball/ Disk Material S31600 SST/CoCr-A Seat 69 Type Quantity N/A N/A
45 Seat Material R30006 Cobalt Alloy SWITCHES 70 Contacts / Rating N/A
46 Cage Stem Material S31600 SST/ ENCS20910 SST 71 Switching Position N/A
47 Gasket Material S31600 SST/Graphite 72 Electric Enclosure N/A
48 MFR Model FISHER 667-4 73 MFR Model FISHER 67CFR
49 Type Diaphragm Spring Return AIR SET 74 Set Pressure 4.2 kgf/cm2-g
50 Size Stroke Time 70i < 25 Sec 75 Filter Gauge 5 Micron min YES
ACTUATOR 51 Air Failure Valve: FC 76 Vol. Tank Booster NO NO
52 Handwheel Location N/A 77 Diffuser Lock-up NO NO
ACCESSORY
53 Mounting Position VERTICAL 78 Fire Safe Fireproof NO NO
54 Spring Range 1 - 1.8 kgf/cm2-g 79 Mech. Stop Quick Exa. NO NO
55 Include Pressure (Shutoff) 80 Hydro. Pressure YES
85 Vendor EMERSON 81 Leakage YES
PURCHASE TESTS
86 Manufacturer FISHER 82 Cryogenic N/A
87 Requisition No. R2B-P3-206-02-P-MR-00200 83 NACE Requirement NACE-0103
88 Model No. EWT 84 PWHT Requirement YES
Notes:

INSTRUMENT SPECIFICATION - CONTROL VALVE


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S91.1 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Fieldbus Device Data Sheet
Tag No.: LV -21214
Fieldbus Tag No.:

Service : GA204AB RICH OIL TO EC202

Basic Fieldbus Function Blocks Segment Information


Analog Input Block (AI) 1 Number Device:
1 22
20 Execution (msec)
Discrete Input Block (DI) 4 Number Segment #: DFJB-21098
2 23
15 Execution Time
3 Bias/Gain Station (BG) 0 Execution (msec) 24 LAS Capable: Yes No
Manual Loader (ML) 0 Number 25 Device Current Draw (mA): 19
4
0 Execution (msec) Device Minimum Voltage: 9.
26
Analog Output Block (AO) 1 Number Device Capacitance: 5 nF
5 20 Execution (msec) Polarity-sensitive: Yes No
27
Discrete Output Block (DO) 1 Number Segment Terminator Location:
6 20 Execution (msec)
28
7 Control Selector (CS)
DD Revision: 3
PID,PI,I Controller (PID) 29
8
20 Execution (msec)
CFF Revision: 1.9
Ratio Station (RA) 30
9
P,PD Controller (PD) 0 Number
10 0 Execution (msec)

* Execution time in msec.

Advanced Function Blocks Notes:

11 Device Control (DC)

12 Output Splitter (OS)

13 Signal Characterizer (SC)

14 Lead Lag (LL)

15 Deadtime (DT)

16 Integrator(Totalizer) (IT)

17 Setpoint Ramp Generator (SPG)

18 Input Selector (IS)

19 Arithmetic (AR)

20 Timer (TMR)

21 Analog Alarm (AAL)

INSTRUMENT SPECIFICATION -FOUNDATION FIELDBUS


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S91.2 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Tag Number : LV -21214

1. Special PWHT Required .


2. In-Built surge protector is provided by vendor.

1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S91.3 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
1 Tag No. LV -21218
2 Service FA205 LCO TO DF101
3 P&ID No. Line No. R2B-P3-206-02-A-DTI-00222 2"-ACL-212102-B1A2-NACE-N
4 Area Classification Ingress Protection CLASS 1 DIV 2 Gr. B ,C&D, T3 NEMA 4X
GENERAL 5 Ambient Temperature: Unit Min. Max. °C 10 48
6 Allowable Sound dBA Tightness Requirement <85 ANSI IV (standard)
7 Available Air Supply Pressure Unit Min. Max. kgf/cm²-g 4.2 8.0
8 Electric Connection Pneum. Connection 1/2” NPT (F) 1/4” NPT (F)
9 Power Failure Position FC
10 Line Size and Schedule Sch. Outlet Line Sch. 2 in 160 2" 160
PIPE
11 Line Class Rating Pipe Material B1A2-NACE 150# A106 GR.B, SMLS
LINE
12 Pipe Insulation Thickness Corrosion Allowance N N/A 3.2mm
13 Fluid State Phase Hydrocarbon Liquid Single Phase
14 Sour Service Special Condition YES N/A
15 Flow Rate Units Min. Nor. Max. m³/h 2.5 5 5.5
16 Inlet Pressure Units Min. Nor. Max. kgf/cm²-g 13.54 13.54 13.54
17 Pressure Drop Units Min. Nor. Max. kgf/cm² 7.38 7.38 7.38
18 Inlet Temperature Units Min. Nor. Max. °C 38 38 38
PROCESS 19 Density Units Min. Nor. Max. kg/m³ 978 978 978
CONDITIONS 20 Viscosity Units Min. Nor. Max. cP 0.686 0.686 0.686
21 Molecular Weight (MW) Specific Gravity @ Oper.
22 Spec. Heat Ratio (Cp/Cv) Compressibility (Z)
23 Vapor Pressure (Liq.) Cavitation or Flashing 14.36 kgf/cm²-a Flashing
24 Critical Pressure (Liq) Flash (wt%) 31.25 kgf/cm²-a
25 Design Pressure Min. Max. kgf/cm²-g 16 kgf/cm²-g
26 Design Temperature Min. Max. 10 °C 120 °C
27 Max.Shutoff DP Solid % 16 kgf/cm²
28 Calculated Cv Units Min. Nor. Max. Cv 1.59 3.2 3.52
CALCULATED
29 Travel Units Min. Nor. Max. % 42 60 63
RESULTS
30 Noise dBA @1m Units Min. Nor. Max. dBA 85 85 85
31 MFR Model FISHER EZ 56 MFR Model FISHER DVC6200F/SC-AD
32 Body Type Single Seat Globe 57 Signal: Inlet Outlet FF Protocol 0-2.8 kgf/cm2
33 Body Size Trim Size 1 in 3/4 in 58 Increase Signal Valve: DIRECT
34 End Connec.Size & Rating 1" 300# RF POSITIONER 59 Cam Characteristic LINEAR
35 Rated Cv Characteristic 8.84 EQ% 60 Bypass Gauges N/A YES
36 Body Material WCC Steel 61 Signal Fail. to Valve FC
BODY 37 Bonnet Type Material Plain WCC Steel 62 Electric Enclosure Ex ia IIC T5 , NEMA 4X
AND 38 Flow Direct. Flow Act. To Up FTO 63 MFR Model N/A N/A
TRIM 39 Packing Type Material ISO Seal PTFE 64 Type Power N/A N/A
SOLENOID
40 Lubricator Isolat. Valve N/A N/A 65 When De-Enegr.Valve: N/A
VALVE
41 Guiding No. of Ports Post 1 66 Material Latcher N/A N/A
42 Trim Type Internal Design Micro Form Unbalanced 67 Electric Enclosure N/A
43 Rated Travel Leak Class 3/4 in ANSI IV 68 MFR Model N/A N/A
44 Plug/ Ball/ Disk Material S31600 SST/CoCr-A Seat 69 Type Quantity N/A N/A
45 Seat Material R30006 Cobalt Alloy SWITCHES 70 Contacts / Rating N/A
46 Cage Stem Material N/A S20910 SST 71 Switching Position N/A
47 Gasket Material S31600 SST/Graphite 72 Electric Enclosure N/A
48 MFR Model FISHER 667 73 MFR Model FISHER 67CFR
49 Type Diaphragm Spring Return AIR SET 74 Set Pressure 4.2 kgf/cm2-g
50 Size Stroke Time 30i < 5 Sec 75 Filter Gauge 5 Micron min YES
ACTUATOR 51 Air Failure Valve: FC 76 Vol. Tank Booster NO NO
52 Handwheel Location N/A 77 Diffuser Lock-up NO NO
ACCESSORY
53 Mounting Position VERTICAL 78 Fire Safe Fireproof NO NO
54 Spring Range 0.8 - 2.5 kgf/cm2-g 79 Mech. Stop Quick Exa. NO NO
55 Include Pressure (Shutoff) 80 Hydro. Pressure YES
85 Vendor EMERSON 81 Leakage YES
PURCHASE TESTS
86 Manufacturer FISHER 82 Cryogenic N/A
87 Requisition No. R2B-P3-206-02-P-MR-00200 83 NACE Requirement NACE-0103
88 Model No. EZ 84 PWHT Requirement YES
Notes:

INSTRUMENT SPECIFICATION - CONTROL VALVE


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S92.1 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Fieldbus Device Data Sheet
Tag No.: LV -21218
Fieldbus Tag No.:

Service : FA205 LCO TO DF101

Basic Fieldbus Function Blocks Segment Information


Analog Input Block (AI) 1 Number Device:
1 22
20 Execution (msec)
Discrete Input Block (DI) 4 Number Segment #: DFJB-21102
2 23
15 Execution Time
3 Bias/Gain Station (BG) 0 Execution (msec) 24 LAS Capable: Yes No
Manual Loader (ML) 0 Number 25 Device Current Draw (mA): 19
4
0 Execution (msec) Device Minimum Voltage: 9.
26
Analog Output Block (AO) 1 Number Device Capacitance: 5 nF
5 20 Execution (msec) Polarity-sensitive: Yes No
27
Discrete Output Block (DO) 1 Number Segment Terminator Location:
6 20 Execution (msec)
28
7 Control Selector (CS)
DD Revision: 3
PID,PI,I Controller (PID) 29
8
20 Execution (msec)
CFF Revision: 1.9
Ratio Station (RA) 30
9
P,PD Controller (PD) 0 Number
10 0 Execution (msec)

* Execution time in msec.

Advanced Function Blocks Notes:

11 Device Control (DC)

12 Output Splitter (OS)

13 Signal Characterizer (SC)

14 Lead Lag (LL)

15 Deadtime (DT)

16 Integrator(Totalizer) (IT)

17 Setpoint Ramp Generator (SPG)

18 Input Selector (IS)

19 Arithmetic (AR)

20 Timer (TMR)

21 Analog Alarm (AAL)

INSTRUMENT SPECIFICATION -FOUNDATION FIELDBUS


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S92.2 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Tag Number : LV -21218

1. This valve shall be controlled by a differential gap controller for on-off service. The flow rate shown is based on emptying 60% of the level instrument
range in 2.8 minutes. The valve furnished shall be capable of emptying 60% of the level range in 2 - 5 minutes.
2. Valve will normally be in the closed position. Valve opening will be intermittent and generally short-term.
3. Special PWHT Required .
4. In-Built surge protector is provided by vendor.

1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S92.3 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
1 Tag No. FV -21243
2 Service SPE201 CLD COND TO SPE201
3 P&ID No. Line No. R2B-P3-206-02-A-DTI-00234 4"-P-216112-T-A18T1-N
4 Area Classification Ingress Protection CLASS 1 DIV 2 Gr. B ,C&D, T3 NEMA 4X
GENERAL 5 Ambient Temperature: Unit Min. Max. °C 10 48
6 Allowable Sound dBA Tightness Requirement <85 ANSI IV (standard)
7 Available Air Supply Pressure Unit Min. Max. kgf/cm²-g 4.2 8.0
8 Electric Connection Pneum. Connection 1/2” NPT (F) 1/4” NPT (F)
9 Power Failure Position FO
10 Line Size and Schedule Sch. Outlet Line Sch. 4 in STD 4" STD
PIPE
11 Line Class Rating Pipe Material T-A18T1 150# A106 GR.B, SMLS
LINE
12 Pipe Insulation Thickness Corrosion Allowance N N/A 1.6mm
13 Fluid State Phase Water Liquid Single Phase
14 Sour Service Special Condition N/A N/A
15 Flow Rate Units Min. Nor. Max. m³/h 5.16 5.68
16 Inlet Pressure Units Min. Nor. Max. kgf/cm²-g 6.088 6.162 6.183
17 Pressure Drop Units Min. Nor. Max. kgf/cm² 6.67 6.688 6.693
18 Inlet Temperature Units Min. Nor. Max. °C 51 51 51
PROCESS 19 Density Units Min. Nor. Max. kg/m³ 989 989 989
CONDITIONS 20 Viscosity Units Min. Nor. Max. cP 0.539 0.538 0.538
21 Molecular Weight (MW) Specific Gravity @ Oper.
22 Spec. Heat Ratio (Cp/Cv) Compressibility (Z)
23 Vapor Pressure (Liq.) Cavitation or Flashing 0.13 kgf/cm²-a NO
24 Critical Pressure (Liq) Flash (wt%) 224.99 kgf/cm²-a
25 Design Pressure Min. Max. -1.033 kgf/cm²-g 13 kgf/cm²-g
26 Design Temperature Min. Max. 10 °C 80 °C
27 Max.Shutoff DP Solid % 13 kgf/cm²
28 Calculated Cv Units Min. Nor. Max. Cv 10.8 21.5 23.6
CALCULATED
29 Travel Units Min. Nor. Max. % 50 61 62
RESULTS
30 Noise dBA @1m Units Min. Nor. Max. dBA 68 72 72
31 MFR Model FISHER EZ 56 MFR Model FISHER DVC6200F/SC-AD
32 Body Type Single Seat Globe 57 Signal: Inlet Outlet FF Protocol 0-2.8 kgf/cm2
33 Body Size Trim Size 3 in 2 in 58 Increase Signal Valve: DIRECT
34 End Connec.Size & Rating 3" 300# RF POSITIONER 59 Cam Characteristic LINEAR
35 Rated Cv Characteristic 71.6 EQ% 60 Bypass Gauges N/A YES
36 Body Material WCC Steel 61 Signal Fail. to Valve FO
BODY 37 Bonnet Type Material Plain WCC Steel 62 Electric Enclosure Ex ia IIC T5 , NEMA 4X
AND 38 Flow Direct. Flow Act. To Up FTO 63 MFR Model N/A N/A
TRIM 39 Packing Type Material Enviro Seal PTFE Carbon 64 Type Power N/A N/A
SOLENOID
40 Lubricator Isolat. Valve N/A N/A 65 When De-Enegr.Valve: N/A
VALVE
41 Guiding No. of Ports Post 1 66 Material Latcher N/A N/A
42 Trim Type Internal Design Standard Unbalanced 67 Electric Enclosure N/A
43 Rated Travel Leak Class 1 1/8 in ANSI IV 68 MFR Model N/A N/A
44 Plug/ Ball/ Disk Material S41600 SST 69 Type Quantity N/A N/A
45 Seat Material S41600 SST SWITCHES 70 Contacts / Rating N/A
46 Cage Stem Material N/A S31600 SST 71 Switching Position N/A
47 Gasket Material S31600 SST/Graphite 72 Electric Enclosure N/A
48 MFR Model FISHER 657 73 MFR Model FISHER 67CFR
49 Type Diaphragm Spring Return AIR SET 74 Set Pressure 4.2 kgf/cm2-g
50 Size Stroke Time 45i < 8 Sec 75 Filter Gauge 5 Micron min YES
ACTUATOR 51 Air Failure Valve: FO 76 Vol. Tank Booster NO NO
52 Handwheel Location N/A 77 Diffuser Lock-up NO NO
ACCESSORY
53 Mounting Position VERTICAL 78 Fire Safe Fireproof NO NO
54 Spring Range 0.6 - 2.0 kgf/cm2-g 79 Mech. Stop Quick Exa. NO NO
55 Include Pressure (Shutoff) 80 Hydro. Pressure YES
85 Vendor EMERSON 81 Leakage YES
PURCHASE TESTS
86 Manufacturer FISHER 82 Cryogenic N/A
87 Requisition No. R2B-P3-206-02-P-MR-00200 83 NACE Requirement N/A
88 Model No. EZ 84 PWHT Requirement N/A
Notes:

INSTRUMENT SPECIFICATION - CONTROL VALVE


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S93.1 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Fieldbus Device Data Sheet
Tag No.: FV -21243
Fieldbus Tag No.:

Service : SPE201 CLD COND TO SPE201

Basic Fieldbus Function Blocks Segment Information


Analog Input Block (AI) 1 Number Device:
1 22
20 Execution (msec)
Discrete Input Block (DI) 4 Number Segment #: DFJB-21094
2 23
15 Execution Time
3 Bias/Gain Station (BG) 0 Execution (msec) 24 LAS Capable: Yes No
Manual Loader (ML) 0 Number 25 Device Current Draw (mA): 19
4
0 Execution (msec) Device Minimum Voltage: 9.
26
Analog Output Block (AO) 1 Number Device Capacitance: 5 nF
5 20 Execution (msec) Polarity-sensitive: Yes No
27
Discrete Output Block (DO) 1 Number Segment Terminator Location:
6 20 Execution (msec)
28
7 Control Selector (CS)
DD Revision: 3
PID,PI,I Controller (PID) 29
8
20 Execution (msec)
CFF Revision: 1.9
Ratio Station (RA) 30
9
P,PD Controller (PD) 0 Number
10 0 Execution (msec)

* Execution time in msec.

Advanced Function Blocks Notes:

11 Device Control (DC)

12 Output Splitter (OS)

13 Signal Characterizer (SC)

14 Lead Lag (LL)

15 Deadtime (DT)

16 Integrator(Totalizer) (IT)

17 Setpoint Ramp Generator (SPG)

18 Input Selector (IS)

19 Arithmetic (AR)

20 Timer (TMR)

21 Analog Alarm (AAL)

INSTRUMENT SPECIFICATION -FOUNDATION FIELDBUS


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S93.2 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Tag Number : FV -21243

1. In-Built surge protector is provided by vendor.

1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S93.3 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
1 Tag No. LV -21404
2 Service FA401 WS TO WS TRT
3 P&ID No. Line No. R2B-P3-206-02-A-DTI-00403 1"-AAM-214001-B2A1-N
4 Area Classification Ingress Protection CLASS 1 DIV 2 Gr. B ,C&D, T3 NEMA 4X
GENERAL 5 Ambient Temperature: Unit Min. Max. °C 10 48
6 Allowable Sound dBA Tightness Requirement <85 ANSI IV (standard)
7 Available Air Supply Pressure Unit Min. Max. kgf/cm²-g 4.2 8.0
8 Electric Connection Pneum. Connection 1/2” NPT (F) 1/4” NPT (F)
9 Power Failure Position FC
10 Line Size and Schedule Sch. Outlet Line Sch. 1 in XS 1" XS
PIPE
11 Line Class Rating Pipe Material B2A1 300# A106 GR.B, SMLS
LINE
12 Pipe Insulation Thickness Corrosion Allowance N N/A 1.6mm
13 Fluid State Phase Water Liquid Single Phase
14 Sour Service Special Condition N/A N/A
15 Flow Rate Units Min. Nor. Max. m³/h 0.4 0.4 0.4
16 Inlet Pressure Units Min. Nor. Max. kgf/cm²-g 20.52 20.58 20.65
17 Pressure Drop Units Min. Nor. Max. kgf/cm² 14.03 14.15 16.63
18 Inlet Temperature Units Min. Nor. Max. °C 51 51 51
PROCESS 19 Density Units Min. Nor. Max. kg/m³ 988 988 988
CONDITIONS 20 Viscosity Units Min. Nor. Max. cP 0.538 0.538 0.538
21 Molecular Weight (MW) Specific Gravity @ Oper.
22 Spec. Heat Ratio (Cp/Cv) Compressibility (Z)
23 Vapor Pressure (Liq.) Cavitation or Flashing 0.13 kgf/cm²-a NO
24 Critical Pressure (Liq) Flash (wt%) 225.55 kgf/cm²-a
25 Design Pressure Min. Max. -1.033 kgf/cm²-g 23.5 kgf/cm²-g
26 Design Temperature Min. Max. 10 °C 120 °C
27 Max.Shutoff DP Solid % 23 kgf/cm²
28 Calculated Cv Units Min. Nor. Max. Cv 0.129 0.129 0.129
CALCULATED
29 Travel Units Min. Nor. Max. % 55 55 55
RESULTS
30 Noise dBA @1m Units Min. Nor. Max. dBA 50 50 50
31 MFR Model FISHER ES 56 MFR Model FISHER DVC6200F/SC-AD
32 Body Type Single Seat Globe 57 Signal: Inlet Outlet FF Protocol 0-2.8 kgf/cm2
33 Body Size Trim Size 1 in 3/8 in 58 Increase Signal Valve: DIRECT
34 End Connec.Size & Rating 1" 300# RF POSITIONER 59 Cam Characteristic LINEAR
35 Rated Cv Characteristic 0.38 Linear 60 Bypass Gauges N/A YES
36 Body Material WCC Steel 61 Signal Fail. to Valve FC
BODY 37 Bonnet Type Material Plain WCC Steel 62 Electric Enclosure Ex ia IIC T5 , NEMA 4X
AND 38 Flow Direct. Flow Act. To Down FTC 63 MFR Model N/A N/A
TRIM 39 Packing Type Material ISO Seal PTFE 64 Type Power N/A N/A
SOLENOID
40 Lubricator Isolat. Valve N/A N/A 65 When De-Enegr.Valve: N/A
VALVE
41 Guiding No. of Ports Cage 1 66 Material Latcher N/A N/A
42 Trim Type Internal Design Micro Flat Unbalanced 67 Electric Enclosure N/A
43 Rated Travel Leak Class 3/4 in ANSI IV 68 MFR Model N/A N/A
44 Plug/ Ball/ Disk Material R30006 Cobalt Alloy 69 Type Quantity N/A N/A
45 Seat Material R30006 Cobalt Alloy SWITCHES 70 Contacts / Rating N/A
46 Cage Stem Material CB7Cu-1 SST S31600 SST 71 Switching Position N/A
47 Gasket Material S31600 SST/Graphite 72 Electric Enclosure N/A
48 MFR Model FISHER 667 73 MFR Model FISHER 67CFR
49 Type Diaphragm Spring Return AIR SET 74 Set Pressure 4.2 kgf/cm2-g
50 Size Stroke Time 30i < 5 Sec 75 Filter Gauge 5 Micron min YES
ACTUATOR 51 Air Failure Valve: FC 76 Vol. Tank Booster NO NO
52 Handwheel Location N/A 77 Diffuser Lock-up NO NO
ACCESSORY
53 Mounting Position VERTICAL 78 Fire Safe Fireproof NO NO
54 Spring Range 0.8 - 2.5 kgf/cm2-g 79 Mech. Stop Quick Exa. NO NO
55 Include Pressure (Shutoff) 80 Hydro. Pressure YES
85 Vendor EMERSON 81 Leakage YES
PURCHASE TESTS
86 Manufacturer FISHER 82 Cryogenic N/A
87 Requisition No. R2B-P3-206-02-P-MR-00200 83 NACE Requirement N/A
88 Model No. ES 84 PWHT Requirement N/A
Notes:

INSTRUMENT SPECIFICATION - CONTROL VALVE


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S94.1 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Fieldbus Device Data Sheet
Tag No.: LV -21404
Fieldbus Tag No.:

Service : FA401 WS TO WS TRT

Basic Fieldbus Function Blocks Segment Information


Analog Input Block (AI) 1 Number Device:
1 22
20 Execution (msec)
Discrete Input Block (DI) 4 Number Segment #: DFJB-21148
2 23
15 Execution Time
3 Bias/Gain Station (BG) 0 Execution (msec) 24 LAS Capable: Yes No
Manual Loader (ML) 0 Number 25 Device Current Draw (mA): 19
4
0 Execution (msec) Device Minimum Voltage: 9.
26
Analog Output Block (AO) 1 Number Device Capacitance: 5 nF
5 20 Execution (msec) Polarity-sensitive: Yes No
27
Discrete Output Block (DO) 1 Number Segment Terminator Location:
6 20 Execution (msec)
28
7 Control Selector (CS)
DD Revision: 3
PID,PI,I Controller (PID) 29
8
20 Execution (msec)
CFF Revision: 1.9
Ratio Station (RA) 30
9
P,PD Controller (PD) 0 Number
10 0 Execution (msec)

* Execution time in msec.

Advanced Function Blocks Notes:

11 Device Control (DC)

12 Output Splitter (OS)

13 Signal Characterizer (SC)

14 Lead Lag (LL)

15 Deadtime (DT)

16 Integrator(Totalizer) (IT)

17 Setpoint Ramp Generator (SPG)

18 Input Selector (IS)

19 Arithmetic (AR)

20 Timer (TMR)

21 Analog Alarm (AAL)

INSTRUMENT SPECIFICATION -FOUNDATION FIELDBUS


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S94.2 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Tag Number : LV -21404

1. This valve shall be controlled by a differential gap controller for on-off service. The flow rate shown is based on emptying 60% of the level instrument
range in 3.25 minutes. The valve furnished shall be capable of emptying 60% of the level range in 2 - 5 minutes.
2. Valve will normally be in the closed position. Valve opening will be intermittent and generally short-term.
3. Line size valve
4. Steam out condition : F.V/200 degC.
5. In-Built surge protector is provided by vendor.

1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S94.3 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
1 Tag No. LV -21410
2 Service FA402 WTR TO WS TRT
3 P&ID No. Line No. R2B-P3-206-02-A-DTI-00408 1"-AAM-214003-B2A1-N
4 Area Classification Ingress Protection CLASS 1 DIV 2 Gr. B ,C&D, T3 NEMA 4X
GENERAL 5 Ambient Temperature: Unit Min. Max. °C 10 48
6 Allowable Sound dBA Tightness Requirement <85 ANSI IV (standard)
7 Available Air Supply Pressure Unit Min. Max. kgf/cm²-g 4.2 8.0
8 Electric Connection Pneum. Connection 1/2” NPT (F) 1/4” NPT (F)
9 Power Failure Position FC
10 Line Size and Schedule Sch. Outlet Line Sch. 1 in XS 1" XS
PIPE
11 Line Class Rating Pipe Material B2A1 300# A106 GR.B, SMLS
LINE
12 Pipe Insulation Thickness Corrosion Allowance N N/A 1.6mm
13 Fluid State Phase Water Liquid Single Phase
14 Sour Service Special Condition N/A N/A
15 Flow Rate Units Min. Nor. Max. m³/h 0.4 0.4 0.4
16 Inlet Pressure Units Min. Nor. Max. kgf/cm²-g 23.58 23.55 23.52
17 Pressure Drop Units Min. Nor. Max. kgf/cm² 19.62 17.14 17.02
18 Inlet Temperature Units Min. Nor. Max. °C 37 37 37
PROCESS 19 Density Units Min. Nor. Max. kg/m³ 988 988 994
CONDITIONS 20 Viscosity Units Min. Nor. Max. cP 0.692 0.692 0.692
21 Molecular Weight (MW) Specific Gravity @ Oper.
22 Spec. Heat Ratio (Cp/Cv) Compressibility (Z)
23 Vapor Pressure (Liq.) Cavitation or Flashing 0.06 kgf/cm²-a NO
24 Critical Pressure (Liq) Flash (wt%) 225.55 kgf/cm²-a
25 Design Pressure Min. Max. -1.033 kgf/cm²-g 26.5 kgf/cm²-g
26 Design Temperature Min. Max. 10 °C 120 °C
27 Max.Shutoff DP Solid % 26.5 kgf/cm²
28 Calculated Cv Units Min. Nor. Max. Cv 0.121 0.121 0.121
CALCULATED
29 Travel Units Min. Nor. Max. % 53 53 53
RESULTS
30 Noise dBA @1m Units Min. Nor. Max. dBA 50 50 50
31 MFR Model FISHER ES 56 MFR Model FISHER DVC6200F/SC-AD
32 Body Type Single Seat Globe 57 Signal: Inlet Outlet FF Protocol 0-2.8 kgf/cm2
33 Body Size Trim Size 1 in 3/8 in 58 Increase Signal Valve: DIRECT
34 End Connec.Size & Rating 1" 300# RF POSITIONER 59 Cam Characteristic LINEAR
35 Rated Cv Characteristic 0.38 Linear 60 Bypass Gauges N/A YES
36 Body Material WCC Steel 61 Signal Fail. to Valve FC
BODY 37 Bonnet Type Material Plain WCC Steel 62 Electric Enclosure Ex ia IIC T5 , NEMA 4X
AND 38 Flow Direct. Flow Act. To Down FTC 63 MFR Model N/A N/A
TRIM 39 Packing Type Material ISO Seal PTFE 64 Type Power N/A N/A
SOLENOID
40 Lubricator Isolat. Valve N/A N/A 65 When De-Enegr.Valve: N/A
VALVE
41 Guiding No. of Ports Cage 1 66 Material Latcher N/A N/A
42 Trim Type Internal Design Micro Flat Unbalanced 67 Electric Enclosure N/A
43 Rated Travel Leak Class 3/4 in ANSI IV 68 MFR Model N/A N/A
44 Plug/ Ball/ Disk Material R30006 Cobalt Alloy 69 Type Quantity N/A N/A
45 Seat Material R30006 Cobalt Alloy SWITCHES 70 Contacts / Rating N/A
46 Cage Stem Material CB7Cu-1 SST S31600 SST 71 Switching Position N/A
47 Gasket Material S31600 SST/Graphite 72 Electric Enclosure N/A
48 MFR Model FISHER 667 73 MFR Model FISHER 67CFR
49 Type Diaphragm Spring Return AIR SET 74 Set Pressure 4.2 kgf/cm2-g
50 Size Stroke Time 30i < 5 Sec 75 Filter Gauge 5 Micron min YES
ACTUATOR 51 Air Failure Valve: FC 76 Vol. Tank Booster NO NO
52 Handwheel Location N/A 77 Diffuser Lock-up NO NO
ACCESSORY
53 Mounting Position VERTICAL 78 Fire Safe Fireproof NO NO
54 Spring Range 0.8 - 2.5 kgf/cm2-g 79 Mech. Stop Quick Exa. NO NO
55 Include Pressure (Shutoff) 80 Hydro. Pressure YES
85 Vendor EMERSON 81 Leakage YES
PURCHASE TESTS
86 Manufacturer FISHER 82 Cryogenic N/A
87 Requisition No. R2B-P3-206-02-P-MR-00200 83 NACE Requirement N/A
88 Model No. ES 84 PWHT Requirement N/A
Notes:

INSTRUMENT SPECIFICATION - CONTROL VALVE


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S95.1 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Fieldbus Device Data Sheet
Tag No.: LV -21410
Fieldbus Tag No.:

Service : FA402 WTR TO WS TRT

Basic Fieldbus Function Blocks Segment Information


Analog Input Block (AI) 1 Number Device:
1 22
20 Execution (msec)
Discrete Input Block (DI) 4 Number Segment #: DFJB-21149
2 23
15 Execution Time
3 Bias/Gain Station (BG) 0 Execution (msec) 24 LAS Capable: Yes No
Manual Loader (ML) 0 Number 25 Device Current Draw (mA): 19
4
0 Execution (msec) Device Minimum Voltage: 9.
26
Analog Output Block (AO) 1 Number Device Capacitance: 5 nF
5 20 Execution (msec) Polarity-sensitive: Yes No
27
Discrete Output Block (DO) 1 Number Segment Terminator Location:
6 20 Execution (msec)
28
7 Control Selector (CS)
DD Revision: 3
PID,PI,I Controller (PID) 29
8
20 Execution (msec)
CFF Revision: 1.9
Ratio Station (RA) 30
9
P,PD Controller (PD) 0 Number
10 0 Execution (msec)

* Execution time in msec.

Advanced Function Blocks Notes:

11 Device Control (DC)

12 Output Splitter (OS)

13 Signal Characterizer (SC)

14 Lead Lag (LL)

15 Deadtime (DT)

16 Integrator(Totalizer) (IT)

17 Setpoint Ramp Generator (SPG)

18 Input Selector (IS)

19 Arithmetic (AR)

20 Timer (TMR)

21 Analog Alarm (AAL)

INSTRUMENT SPECIFICATION -FOUNDATION FIELDBUS


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S95.2 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Tag Number : LV -21410

1. This valve shall be controlled by a differential gap controller for on-off service. The flow rate shown is based on emptying 60% of the level instrument
range in 2.9 minutes. The valve furnished shall be capable of emptying 60% of the level range in 2 - 5 minutes.
2. Valve will normally be in the closed position. Valve opening will be intermittent and generally short-term.
3. Hardened trim is recommended for this service based upon the possibility of cavitation occurring.
4. Line size valve.
5. Steam out condition : F.V/200 degC.
6. In-Built surge protector is provided by vendor.

1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S95.3 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
1 Tag No. LV -21502
2 Service DA501 AMR TO FA503
3 P&ID No. Line No. R2B-P3-206-02-A-DTI-00501 4"-MDEAR-212410-T-A72T1-PP
4 Area Classification Ingress Protection CLASS 1 DIV 2 Gr. B ,C&D, T3 NEMA 4X
GENERAL 5 Ambient Temperature: Unit Min. Max. °C 10 48
6 Allowable Sound dBA Tightness Requirement <85 ANSI IV (standard)
7 Available Air Supply Pressure Unit Min. Max. kgf/cm²-g 4.2 8.0
8 Electric Connection Pneum. Connection 1/2” NPT (F) 1/4” NPT (F)
9 Power Failure Position FC
10 Line Size and Schedule Sch. Outlet Line Sch. 4 in XS 4" XS
PIPE
11 Line Class Rating Pipe Material T-A72T1 150# A106 GR.B, SMLS
LINE
12 Pipe Insulation Thickness Corrosion Allowance PP 25mm 6.4mm
13 Fluid State Phase Rich Amine Liquid Single Phase
14 Sour Service Special Condition YES N/A
15 Flow Rate Units Min. Nor. Max. kg/h 32372 32372 35609
16 Inlet Pressure Units Min. Nor. Max. kgf/cm²-g 13.8 13.8 13.79
17 Pressure Drop Units Min. Nor. Max. kgf/cm² 5.863 5.863 4.812
18 Inlet Temperature Units Min. Nor. Max. °C 54.5 54.5 54.5
PROCESS 19 Density Units Min. Nor. Max. kg/m³ 1043 1043 1043
CONDITIONS 20 Viscosity Units Min. Nor. Max. cP 2.68 2.68 2.68
21 Molecular Weight (MW) Specific Gravity @ Oper.
22 Spec. Heat Ratio (Cp/Cv) Compressibility (Z)
23 Vapor Pressure (Liq.) Cavitation or Flashing 14.33 kgf/cm²-a Flashing
24 Critical Pressure (Liq) Flash (wt%) kgf/cm²-a
25 Design Pressure Min. Max. kgf/cm²-g 16 kgf/cm²-g
26 Design Temperature Min. Max. 10 °C 120 °C
27 Max.Shutoff DP Solid % 16 kgf/cm²
28 Calculated Cv Units Min. Nor. Max. Cv 27.8 27.8 30.8
CALCULATED
29 Travel Units Min. Nor. Max. % 46 46 51
RESULTS
30 Noise dBA @1m Units Min. Nor. Max. dBA 85 85 85
31 MFR Model FISHER EZ 56 MFR Model FISHER DVC6200F/SC-AD
32 Body Type Single Seat Globe 57 Signal: Inlet Outlet FF Protocol 0-2.8 kgf/cm2
33 Body Size Trim Size 2 in 2 in 58 Increase Signal Valve: DIRECT
34 End Connec.Size & Rating 2" 300# RF POSITIONER 59 Cam Characteristic LINEAR
35 Rated Cv Characteristic 52.4 Linear 60 Bypass Gauges N/A YES
36 Body Material WCC Steel 61 Signal Fail. to Valve FC
BODY 37 Bonnet Type Material Plain WCC Steel 62 Electric Enclosure Ex ia IIC T5 , NEMA 4X
AND 38 Flow Direct. Flow Act. To Up FTO 63 MFR Model N/A N/A
TRIM 39 Packing Type Material ISO Seal PTFE 64 Type Power N/A N/A
SOLENOID
40 Lubricator Isolat. Valve N/A N/A 65 When De-Enegr.Valve: N/A
VALVE
41 Guiding No. of Ports Post 1 66 Material Latcher N/A N/A
42 Trim Type Internal Design Standard Unbalanced 67 Electric Enclosure N/A
43 Rated Travel Leak Class 1 1/8 in ANSI IV 68 MFR Model N/A N/A
44 Plug/ Ball/ Disk Material S31600 SST/CoCr-A Seat 69 Type Quantity N/A N/A
45 Seat Material R30006 Cobalt Alloy SWITCHES 70 Contacts / Rating N/A
46 Cage Stem Material N/A S20910 SST 71 Switching Position N/A
47 Gasket Material S31600 SST/Graphite 72 Electric Enclosure N/A
48 MFR Model FISHER 667 73 MFR Model FISHER 67CFR
49 Type Diaphragm Spring Return AIR SET 74 Set Pressure 4.2 kgf/cm2-g
50 Size Stroke Time 45i < 8 Sec 75 Filter Gauge 5 Micron min YES
ACTUATOR 51 Air Failure Valve: FC 76 Vol. Tank Booster NO NO
52 Handwheel Location N/A 77 Diffuser Lock-up NO NO
ACCESSORY
53 Mounting Position VERTICAL 78 Fire Safe Fireproof NO NO
54 Spring Range 1 - 2.5 kgf/cm2-g 79 Mech. Stop Quick Exa. NO NO
55 Include Pressure (Shutoff) 80 Hydro. Pressure YES
85 Vendor EMERSON 81 Leakage YES
PURCHASE TESTS
86 Manufacturer FISHER 82 Cryogenic N/A
87 Requisition No. R2B-P3-206-02-P-MR-00200 83 NACE Requirement NACE-0103
88 Model No. EZ 84 PWHT Requirement YES
Notes:

INSTRUMENT SPECIFICATION - CONTROL VALVE


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S96.1 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Fieldbus Device Data Sheet
Tag No.: LV -21502
Fieldbus Tag No.:

Service : DA501 AMR TO FA503

Basic Fieldbus Function Blocks Segment Information


Analog Input Block (AI) 1 Number Device:
1 22
20 Execution (msec)
Discrete Input Block (DI) 4 Number Segment #: DFJB-21107
2 23
15 Execution Time
3 Bias/Gain Station (BG) 0 Execution (msec) 24 LAS Capable: Yes No
Manual Loader (ML) 0 Number 25 Device Current Draw (mA): 19
4
0 Execution (msec) Device Minimum Voltage: 9.
26
Analog Output Block (AO) 1 Number Device Capacitance: 5 nF
5 20 Execution (msec) Polarity-sensitive: Yes No
27
Discrete Output Block (DO) 1 Number Segment Terminator Location:
6 20 Execution (msec)
28
7 Control Selector (CS)
DD Revision: 3
PID,PI,I Controller (PID) 29
8
20 Execution (msec)
CFF Revision: 1.9
Ratio Station (RA) 30
9
P,PD Controller (PD) 0 Number
10 0 Execution (msec)

* Execution time in msec.

Advanced Function Blocks Notes:

11 Device Control (DC)

12 Output Splitter (OS)

13 Signal Characterizer (SC)

14 Lead Lag (LL)

15 Deadtime (DT)

16 Integrator(Totalizer) (IT)

17 Setpoint Ramp Generator (SPG)

18 Input Selector (IS)

19 Arithmetic (AR)

20 Timer (TMR)

21 Analog Alarm (AAL)

INSTRUMENT SPECIFICATION -FOUNDATION FIELDBUS


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S96.2 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Tag Number : LV -21502

1. In-Built surge protector is provided by vendor.

1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S96.3 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
1 Tag No. LV -21503
2 Service FA501 SR COND TO DF101
3 P&ID No. Line No. R2B-P3-206-02-A-DTI-00501 2"-AAM-212415-B1A2-NACE-N
4 Area Classification Ingress Protection CLASS 1 DIV 2 Gr. B ,C&D, T3 NEMA 4X
GENERAL 5 Ambient Temperature: Unit Min. Max. °C 10 48
6 Allowable Sound dBA Tightness Requirement <85 ANSI IV (standard)
7 Available Air Supply Pressure Unit Min. Max. kgf/cm²-g 4.2 8.0
8 Electric Connection Pneum. Connection 1/2” NPT (F) 1/4” NPT (F)
9 Power Failure Position FC
10 Line Size and Schedule Sch. Outlet Line Sch. 2 in 160 2" 160
PIPE
11 Line Class Rating Pipe Material B1A2-NACE 150# A106 GR.B, SMLS
LINE
12 Pipe Insulation Thickness Corrosion Allowance N N/A 3.2mm
13 Fluid State Phase Sour Condensate Liquid Single Phase
14 Sour Service Special Condition YES N/A
15 Flow Rate Units Min. Nor. Max. m³/h 0.22 0.45 0.5
16 Inlet Pressure Units Min. Nor. Max. kgf/cm²-g 13.83 13.83 13.83
17 Pressure Drop Units Min. Nor. Max. kgf/cm² 9.31 9.303 9.3
18 Inlet Temperature Units Min. Nor. Max. °C 36.7 36.7 36.7
PROCESS 19 Density Units Min. Nor. Max. kg/m³ 993 993 993
CONDITIONS 20 Viscosity Units Min. Nor. Max. cP 0.8 0.8 0.8
21 Molecular Weight (MW) Specific Gravity @ Oper.
22 Spec. Heat Ratio (Cp/Cv) Compressibility (Z)
23 Vapor Pressure (Liq.) Cavitation or Flashing 0.56 kgf/cm²-a NO
24 Critical Pressure (Liq) Flash (wt%) 224.99 kgf/cm²-a
25 Design Pressure Min. Max. -1.033 kgf/cm²-g 16 kgf/cm²-g
26 Design Temperature Min. Max. 10 °C 120 °C
27 Max.Shutoff DP Solid % 16 kgf/cm²
28 Calculated Cv Units Min. Nor. Max. Cv0.084 0.172 0.191
CALCULATED
29 Travel Units Min. Nor. Max. % 45 72 76
RESULTS
30 Noise dBA @1m Units Min. Nor. Max. dBA50 50 50
31 MFR Model FISHER EZ 56 MFR Model FISHER DVC6200F/SC-AD
32 Body Type Single Seat Globe 57 Signal: Inlet Outlet FF Protocol 0-2.8 kgf/cm2
33 Body Size Trim Size 1 in 1/4 in 58 Increase Signal Valve: DIRECT
34 End Connec.Size & Rating 1" 300# RF POSITIONER 59 Cam Characteristic LINEAR
35 Rated Cv Characteristic 0.354 EQ% 60 Bypass Gauges N/A YES
36 Body Material WCC Steel 61 Signal Fail. to Valve FC
BODY 37 Bonnet Type Material Plain WCC Steel 62 Electric Enclosure Ex ia IIC T5 , NEMA 4X
AND 38 Flow Direct. Flow Act. To Up FTO 63 MFR Model N/A N/A
TRIM 39 Packing Type Material ISO Seal PTFE 64 Type Power N/A N/A
SOLENOID
40 Lubricator Isolat. Valve N/A N/A 65 When De-Enegr.Valve: N/A
VALVE
41 Guiding No. of Ports Port 1 66 Material Latcher N/A N/A
42 Trim Type Internal Design Micro Flute Unbalanced 67 Electric Enclosure N/A
43 Rated Travel Leak Class 3/4 in ANSI IV 68 MFR Model N/A N/A
44 Plug/ Ball/ Disk Material S31600 SST/CoCr-A Seat 69 Type Quantity N/A N/A
45 Seat Material S31600 SST SWITCHES 70 Contacts / Rating N/A
46 Cage Stem Material N/A S20910 SST 71 Switching Position N/A
47 Gasket Material S31600 SST/Graphite 72 Electric Enclosure N/A
48 MFR Model FISHER 667 73 MFR Model FISHER 67CFR
49 Type Diaphragm Spring Return AIR SET 74 Set Pressure 4.2 kgf/cm2-g
50 Size Stroke Time 30i < 5 Sec 75 Filter Gauge 5 Micron min YES
ACTUATOR 51 Air Failure Valve: FC 76 Vol. Tank Booster NO NO
52 Handwheel Location N/A 77 Diffuser Lock-up NO NO
ACCESSORY
53 Mounting Position VERTICAL 78 Fire Safe Fireproof NO NO
54 Spring Range 0.8 - 2.5 kgf/cm2-g 79 Mech. Stop Quick Exa. NO NO
55 Include Pressure (Shutoff) 80 Hydro. Pressure YES
85 Vendor EMERSON 81 Leakage YES
PURCHASE TESTS
86 Manufacturer FISHER 82 Cryogenic N/A
87 Requisition No. R2B-P3-206-02-P-MR-00200 83 NACE Requirement NACE-0103
88 Model No. EZ 84 PWHT Requirement YES
Notes:

INSTRUMENT SPECIFICATION - CONTROL VALVE


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S97.1 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Fieldbus Device Data Sheet
Tag No.: LV -21503
Fieldbus Tag No.:

Service : FA501 SR COND TO DF101

Basic Fieldbus Function Blocks Segment Information


Analog Input Block (AI) 1 Number Device:
1 22
20 Execution (msec)
Discrete Input Block (DI) 4 Number Segment #: DFJB-21107
2 23
15 Execution Time
3 Bias/Gain Station (BG) 0 Execution (msec) 24 LAS Capable: Yes No
Manual Loader (ML) 0 Number 25 Device Current Draw (mA): 19
4
0 Execution (msec) Device Minimum Voltage: 9.
26
Analog Output Block (AO) 1 Number Device Capacitance: 5 nF
5 20 Execution (msec) Polarity-sensitive: Yes No
27
Discrete Output Block (DO) 1 Number Segment Terminator Location:
6 20 Execution (msec)
28
7 Control Selector (CS)
DD Revision: 3
PID,PI,I Controller (PID) 29
8
20 Execution (msec)
CFF Revision: 1.9
Ratio Station (RA) 30
9
P,PD Controller (PD) 0 Number
10 0 Execution (msec)

* Execution time in msec.

Advanced Function Blocks Notes:

11 Device Control (DC)

12 Output Splitter (OS)

13 Signal Characterizer (SC)

14 Lead Lag (LL)

15 Deadtime (DT)

16 Integrator(Totalizer) (IT)

17 Setpoint Ramp Generator (SPG)

18 Input Selector (IS)

19 Arithmetic (AR)

20 Timer (TMR)

21 Analog Alarm (AAL)

INSTRUMENT SPECIFICATION -FOUNDATION FIELDBUS


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S97.2 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Tag Number : LV -21503

1. Special PWHT Required .


2. In-Built surge protector is provided by vendor.

1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S97.3 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
1 Tag No. LV -21504
2 Service FA502 AMR TO FA503
3 P&ID No. Line No. R2B-P3-206-02-A-DTI-00503 2"-MDEAR-215018-T-A72T1-N
4 Area Classification Ingress Protection CLASS 1 DIV 2 Gr. B ,C&D, T3 NEMA 4X
GENERAL 5 Ambient Temperature: Unit Min. Max. °C 10 48
6 Allowable Sound dBA Tightness Requirement <85 ANSI IV (standard)
7 Available Air Supply Pressure Unit Min. Max. kgf/cm²-g 4.2 8.0
8 Electric Connection Pneum. Connection 1/2” NPT (F) 1/4” NPT (F)
9 Power Failure Position FC
10 Line Size and Schedule Sch. Outlet Line Sch. 2 in 160 2" 160
PIPE
11 Line Class Rating Pipe Material T-A72T1 150# A106 GR.B, SMLS
LINE
12 Pipe Insulation Thickness Corrosion Allowance N N/A 6.4mm
13 Fluid State Phase Amine Liquid Single Phase
14 Sour Service Special Condition YES N/A
15 Flow Rate Units Min. Nor. Max. m³/h 3 3 3.3
16 Inlet Pressure Units Min. Nor. Max. kgf/cm²-g 12.71 12.71 12.7
17 Pressure Drop Units Min. Nor. Max. kgf/cm² 4.788 4.788 3.746
18 Inlet Temperature Units Min. Nor. Max. °C 38 38 38
PROCESS 19 Density Units Min. Nor. Max. kg/m³ 993.1 993.1 993.1
CONDITIONS 20 Viscosity Units Min. Nor. Max. cP 0.7 0.7 0.7
21 Molecular Weight (MW) Specific Gravity @ Oper.
22 Spec. Heat Ratio (Cp/Cv) Compressibility (Z)
23 Vapor Pressure (Liq.) Cavitation or Flashing 13.68 kgf/cm²-a Flashing
24 Critical Pressure (Liq) Flash (wt%) kgf/cm²-a
25 Design Pressure Min. Max. kgf/cm²-g 16 kgf/cm²-g
26 Design Temperature Min. Max. 10 °C 70 °C
27 Max.Shutoff DP Solid % 16 kgf/cm²
28 Calculated Cv Units Min. Nor. Max. Cv 3.03 3.03 3.34
CALCULATED
29 Travel Units Min. Nor. Max. % 80 80 83
RESULTS
30 Noise dBA @1m Units Min. Nor. Max. dBA 85 85 85
31 MFR Model FISHER EZ 56 MFR Model FISHER DVC6200F/SC-AD
32 Body Type Single Seat Globe 57 Signal: Inlet Outlet FF Protocol 0-2.8 kgf/cm2
33 Body Size Trim Size 1 in 1/2 in 58 Increase Signal Valve: DIRECT
34 End Connec.Size & Rating 1" 300# RF POSITIONER 59 Cam Characteristic LINEAR
35 Rated Cv Characteristic 4.91 EQ% 60 Bypass Gauges N/A YES
36 Body Material WCC Steel 61 Signal Fail. to Valve FC
BODY 37 Bonnet Type Material Plain WCC Steel 62 Electric Enclosure Ex ia IIC T5 , NEMA 4X
AND 38 Flow Direct. Flow Act. To Up FTO 63 MFR Model N/A N/A
TRIM 39 Packing Type Material ISO Seal PTFE 64 Type Power N/A N/A
SOLENOID
40 Lubricator Isolat. Valve N/A N/A 65 When De-Enegr.Valve: N/A
VALVE
41 Guiding No. of Ports Post 1 66 Material Latcher N/A N/A
42 Trim Type Internal Design Micro Form Unbalanced 67 Electric Enclosure N/A
43 Rated Travel Leak Class 3/4 in ANSI IV 68 MFR Model N/A N/A
44 Plug/ Ball/ Disk Material S31600 SST/CoCr-A Seat 69 Type Quantity N/A N/A
45 Seat Material R30006 Cobalt Alloy SWITCHES 70 Contacts / Rating N/A
46 Cage Stem Material N/A S20910 SST 71 Switching Position N/A
47 Gasket Material S31600 SST/Graphite 72 Electric Enclosure N/A
48 MFR Model FISHER 667 73 MFR Model FISHER 67CFR
49 Type Diaphragm Spring Return AIR SET 74 Set Pressure 4.2 kgf/cm2-g
50 Size Stroke Time 30i < 5 Sec 75 Filter Gauge 5 Micron min YES
ACTUATOR 51 Air Failure Valve: FC 76 Vol. Tank Booster NO NO
52 Handwheel Location N/A 77 Diffuser Lock-up NO NO
ACCESSORY
53 Mounting Position VERTICAL 78 Fire Safe Fireproof NO NO
54 Spring Range 0.8 - 2.5 kgf/cm2-g 79 Mech. Stop Quick Exa. NO NO
55 Include Pressure (Shutoff) 80 Hydro. Pressure YES
85 Vendor EMERSON 81 Leakage YES
PURCHASE TESTS
86 Manufacturer FISHER 82 Cryogenic N/A
87 Requisition No. R2B-P3-206-02-P-MR-00200 83 NACE Requirement NACE-0103
88 Model No. EZ 84 PWHT Requirement YES
Notes:

INSTRUMENT SPECIFICATION - CONTROL VALVE


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S98.1 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Fieldbus Device Data Sheet
Tag No.: LV -21504
Fieldbus Tag No.:

Service : FA502 AMR TO FA503

Basic Fieldbus Function Blocks Segment Information


Analog Input Block (AI) 1 Number Device:
1 22
20 Execution (msec)
Discrete Input Block (DI) 4 Number Segment #: DFJB-21110
2 23
15 Execution Time
3 Bias/Gain Station (BG) 0 Execution (msec) 24 LAS Capable: Yes No
Manual Loader (ML) 0 Number 25 Device Current Draw (mA): 19
4
0 Execution (msec) Device Minimum Voltage: 9.
26
Analog Output Block (AO) 1 Number Device Capacitance: 5 nF
5 20 Execution (msec) Polarity-sensitive: Yes No
27
Discrete Output Block (DO) 1 Number Segment Terminator Location:
6 20 Execution (msec)
28
7 Control Selector (CS)
DD Revision: 3
PID,PI,I Controller (PID) 29
8
20 Execution (msec)
CFF Revision: 1.9
Ratio Station (RA) 30
9
P,PD Controller (PD) 0 Number
10 0 Execution (msec)

* Execution time in msec.

Advanced Function Blocks Notes:

11 Device Control (DC)

12 Output Splitter (OS)

13 Signal Characterizer (SC)

14 Lead Lag (LL)

15 Deadtime (DT)

16 Integrator(Totalizer) (IT)

17 Setpoint Ramp Generator (SPG)

18 Input Selector (IS)

19 Arithmetic (AR)

20 Timer (TMR)

21 Analog Alarm (AAL)

INSTRUMENT SPECIFICATION -FOUNDATION FIELDBUS


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S98.2 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Tag Number : LV -21504

1. In-Built surge protector is provided by vendor.

1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S98.3 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
1 Tag No. LV -21505
2 Service FA503 AMR TO ARU
3 P&ID No. Line No. R2B-P3-206-02-A-DTI-00504 6"-MDEAR-212422-T-A66T1-N
4 Area Classification Ingress Protection CLASS 1 DIV 2 Gr. B ,C&D, T3 NEMA 4X
GENERAL 5 Ambient Temperature: Unit Min. Max. °C 10 48
6 Allowable Sound dBA Tightness Requirement <85 ANSI IV (standard)
7 Available Air Supply Pressure Unit Min. Max. kgf/cm²-g 4.2 8.0
8 Electric Connection Pneum. Connection 1/2” NPT (F) 1/4” NPT (F)
9 Power Failure Position FC
10 Line Size and Schedule Sch. Outlet Line Sch. 6 in XS 6" XS
PIPE
11 Line Class Rating Pipe Material T-A66T1 150# A106 GR.B, SMLS
LINE
12 Pipe Insulation Thickness Corrosion Allowance N N/A 6.4mm
13 Fluid State Phase Rich Amine Liquid Single Phase
14 Sour Service Special Condition YES N/A
15 Flow Rate Units Min. Nor. Max. kg/h 44184 44184 48602
16 Inlet Pressure Units Min. Nor. Max. kgf/cm²-g 7.043 7.043 8.035
17 Pressure Drop Units Min. Nor. Max. kgf/cm² 0.789 0.789 0.761
18 Inlet Temperature Units Min. Nor. Max. °C 54.7 54.7 54.7
PROCESS 19 Density Units Min. Nor. Max. kg/m³ 1043 1043 1043
CONDITIONS 20 Viscosity Units Min. Nor. Max. cP 2.665 2.665 2.665
21 Molecular Weight (MW) Specific Gravity @ Oper.
22 Spec. Heat Ratio (Cp/Cv) Compressibility (Z)
23 Vapor Pressure (Liq.) Cavitation or Flashing 4.69 kgf/cm²-a NO
24 Critical Pressure (Liq) Flash (wt%) kgf/cm²-a
25 Design Pressure Min. Max. kgf/cm²-g 16 kgf/cm²-g
26 Design Temperature Min. Max. 10 °C 120 °C
27 Max.Shutoff DP Solid % 16 kgf/cm²
28 Calculated Cv Units Min. Nor. Max. Cv 58. 58. 65.2
CALCULATED
29 Travel Units Min. Nor. Max. % 57 57 63
RESULTS
30 Noise dBA @1m Units Min. Nor. Max. dBA 50 50 50
31 MFR Model FISHER ET 56 MFR Model FISHER DVC6200F/SC-AD
32 Body Type Single Seat Globe 57 Signal: Inlet Outlet FF Protocol 0-2.8 kgf/cm2
33 Body Size Trim Size 3 in 2 5/16 in 58 Increase Signal Valve: DIRECT
34 End Connec.Size & Rating 3" 300# RF POSITIONER 59 Cam Characteristic LINEAR
35 Rated Cv Characteristic 102 Linear 60 Bypass Gauges N/A YES
36 Body Material WCC Steel 61 Signal Fail. to Valve FC
BODY 37 Bonnet Type Material Plain WCC Steel 62 Electric Enclosure Ex ia IIC T5 , NEMA 4X
AND 38 Flow Direct. Flow Act. To Down FTO 63 MFR Model N/A N/A
TRIM 39 Packing Type Material ISO Seal PTFE 64 Type Power N/A N/A
SOLENOID
40 Lubricator Isolat. Valve N/A N/A 65 When De-Enegr.Valve: N/A
VALVE
41 Guiding No. of Ports Cage 1 66 Material Latcher N/A N/A
42 Trim Type Internal Design Standard Balanced 67 Electric Enclosure N/A
43 Rated Travel Leak Class 1 1/8 in ANSI IV 68 MFR Model N/A N/A
44 Plug/ Ball/ Disk Material S31600 SST 69 Type Quantity N/A N/A
45 Seat Material S31600 SST SWITCHES 70 Contacts / Rating N/A
46 Cage Stem Material S31600 SST/ ENCS20910 SST 71 Switching Position N/A
47 Gasket Material S31600 SST/Graphite 72 Electric Enclosure N/A
48 MFR Model FISHER 667 73 MFR Model FISHER 67CFR
49 Type Diaphragm Spring Return AIR SET 74 Set Pressure 4.2 kgf/cm2-g
50 Size Stroke Time 40i < 8 Sec 75 Filter Gauge 5 Micron min YES
ACTUATOR 51 Air Failure Valve: FC 76 Vol. Tank Booster NO NO
52 Handwheel Location N/A 77 Diffuser Lock-up NO NO
ACCESSORY
53 Mounting Position VERTICAL 78 Fire Safe Fireproof NO NO
54 Spring Range 0.7 - 2.4 kgf/cm2-g 79 Mech. Stop Quick Exa. NO NO
55 Include Pressure (Shutoff) 80 Hydro. Pressure YES
85 Vendor EMERSON 81 Leakage YES
PURCHASE TESTS
86 Manufacturer FISHER 82 Cryogenic N/A
87 Requisition No. R2B-P3-206-02-P-MR-00200 83 NACE Requirement NACE-0103
88 Model No. ET 84 PWHT Requirement YES
Notes:

INSTRUMENT SPECIFICATION - CONTROL VALVE


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S99.1 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Fieldbus Device Data Sheet
Tag No.: LV -21505
Fieldbus Tag No.:

Service : FA503 AMR TO ARU

Basic Fieldbus Function Blocks Segment Information


Analog Input Block (AI) 1 Number Device:
1 22
20 Execution (msec)
Discrete Input Block (DI) 4 Number Segment #: DFJB-21110
2 23
15 Execution Time
3 Bias/Gain Station (BG) 0 Execution (msec) 24 LAS Capable: Yes No
Manual Loader (ML) 0 Number 25 Device Current Draw (mA): 19
4
0 Execution (msec) Device Minimum Voltage: 9.
26
Analog Output Block (AO) 1 Number Device Capacitance: 5 nF
5 20 Execution (msec) Polarity-sensitive: Yes No
27
Discrete Output Block (DO) 1 Number Segment Terminator Location:
6 20 Execution (msec)
28
7 Control Selector (CS)
DD Revision: 3
PID,PI,I Controller (PID) 29
8
20 Execution (msec)
CFF Revision: 1.9
Ratio Station (RA) 30
9
P,PD Controller (PD) 0 Number
10 0 Execution (msec)

* Execution time in msec.

Advanced Function Blocks Notes:

11 Device Control (DC)

12 Output Splitter (OS)

13 Signal Characterizer (SC)

14 Lead Lag (LL)

15 Deadtime (DT)

16 Integrator(Totalizer) (IT)

17 Setpoint Ramp Generator (SPG)

18 Input Selector (IS)

19 Arithmetic (AR)

20 Timer (TMR)

21 Analog Alarm (AAL)

INSTRUMENT SPECIFICATION -FOUNDATION FIELDBUS


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S99.2 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Tag Number : LV -21505

1. In-Built surge protector is provided by vendor.

1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S99.3 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
1 Tag No. LV -21601
2 Service GA612 BLWDN TO EA603
3 P&ID No. Line No. R2B-P3-206-02-A-DTI-00602 2"-BD-216008-T-A18T1-N
4 Area Classification Ingress Protection CLASS 1 DIV 2 Gr. B ,C&D, T3 NEMA 4X
GENERAL 5 Ambient Temperature: Unit Min. Max. °C 10 48
6 Allowable Sound dBA Tightness Requirement <85 ANSI IV (standard)
7 Available Air Supply Pressure Unit Min. Max. kgf/cm²-g 4.2 8.0
8 Electric Connection Pneum. Connection 1/2” NPT (F) 1/4” NPT (F)
9 Power Failure Position FC
10 Line Size and Schedule Sch. Outlet Line Sch. 2 in XS 2" XS
PIPE
11 Line Class Rating Pipe Material T-A18T1 150# A106 GR.B, SMLS
LINE
12 Pipe Insulation Thickness Corrosion Allowance N N/A 1.6mm
13 Fluid State Phase water Liquid Single Phase
14 Sour Service Special Condition N/A N/A
15 Flow Rate Units Min. Nor. Max. m³/h 1.774 3.549 3.903
16 Inlet Pressure Units Min. Nor. Max. kgf/cm²-g 6.675 6.657 6.652
17 Pressure Drop Units Min. Nor. Max. kgf/cm² 6.673 6.653 6.648
18 Inlet Temperature Units Min. Nor. Max. °C 40 40 40
PROCESS 19 Density Units Min. Nor. Max. kg/m³ 996 996 996
CONDITIONS 20 Viscosity Units Min. Nor. Max. cP 0.652 0.652 0.652
21 Molecular Weight (MW) Specific Gravity @ Oper.
22 Spec. Heat Ratio (Cp/Cv) Compressibility (Z)
23 Vapor Pressure (Liq.) Cavitation or Flashing 0.07 kgf/cm²-a NO
24 Critical Pressure (Liq) Flash (wt%) 225.55 kgf/cm²-a
25 Design Pressure Min. Max. -1.033 kgf/cm²-g 8.7 kgf/cm²-g
26 Design Temperature Min. Max. 10 °C 80 °C
27 Max.Shutoff DP Solid % 8.7 kgf/cm²
28 Calculated Cv Units Min. Nor. Max. Cv 0.841 1.69 1.86
CALCULATED
29 Travel Units Min. Nor. Max. % 58 78 81
RESULTS
30 Noise dBA @1m Units Min. Nor. Max. dBA 50 51 52
31 MFR Model FISHER EZ 56 MFR Model FISHER DVC6200F/SC-AD
32 Body Type Single Seat Globe 57 Signal: Inlet Outlet FF Protocol 0-2.8 kgf/cm2
33 Body Size Trim Size 1 in 3/8 in 58 Increase Signal Valve: DIRECT
34 End Connec.Size & Rating 1" 300# RF POSITIONER 59 Cam Characteristic LINEAR
35 Rated Cv Characteristic 3.07 EQ% 60 Bypass Gauges N/A YES
36 Body Material WCC Steel 61 Signal Fail. to Valve FC
BODY 37 Bonnet Type Material Plain WCC Steel 62 Electric Enclosure Ex ia IIC T5 , NEMA 4X
AND 38 Flow Direct. Flow Act. To Up FTO 63 MFR Model N/A N/A
TRIM 39 Packing Type Material Enviro Seal PTFE Carbon 64 Type Power N/A N/A
SOLENOID
40 Lubricator Isolat. Valve N/A N/A 65 When De-Enegr.Valve: N/A
VALVE
41 Guiding No. of Ports Post 1 66 Material Latcher N/A N/A
42 Trim Type Internal Design Micro Form Unbalanced 67 Electric Enclosure N/A
43 Rated Travel Leak Class 3/4 in ANSI IV 68 MFR Model N/A N/A
44 Plug/ Ball/ Disk Material S41600 SST 69 Type Quantity N/A N/A
45 Seat Material S41600 SST SWITCHES 70 Contacts / Rating N/A
46 Cage Stem Material N/A S31600 SST 71 Switching Position N/A
47 Gasket Material S31600 SST/Graphite 72 Electric Enclosure N/A
48 MFR Model FISHER 667 73 MFR Model FISHER 67CFR
49 Type Diaphragm Spring Return AIR SET 74 Set Pressure 4.2 kgf/cm2-g
50 Size Stroke Time 30i < 5 Sec 75 Filter Gauge 5 Micron min YES
ACTUATOR 51 Air Failure Valve: FC 76 Vol. Tank Booster NO NO
52 Handwheel Location N/A 77 Diffuser Lock-up NO NO
ACCESSORY
53 Mounting Position VERTICAL 78 Fire Safe Fireproof NO NO
54 Spring Range 0.7 - 2.4 kgf/cm2-g 79 Mech. Stop Quick Exa. NO NO
55 Include Pressure (Shutoff) 80 Hydro. Pressure YES
85 Vendor EMERSON 81 Leakage YES
PURCHASE TESTS
86 Manufacturer FISHER 82 Cryogenic N/A
87 Requisition No. R2B-P3-206-02-P-MR-00200 83 NACE Requirement N/A
88 Model No. EZ 84 PWHT Requirement N/A
Notes:

INSTRUMENT SPECIFICATION - CONTROL VALVE


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S100.1 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Fieldbus Device Data Sheet
Tag No.: LV -21601
Fieldbus Tag No.:

Service : GA612 BLWDN TO EA603

Basic Fieldbus Function Blocks Segment Information


Analog Input Block (AI) 1 Number Device:
1 22
20 Execution (msec)
Discrete Input Block (DI) 4 Number Segment #: DFJB-21079
2 23
15 Execution Time
3 Bias/Gain Station (BG) 0 Execution (msec) 24 LAS Capable: Yes No
Manual Loader (ML) 0 Number 25 Device Current Draw (mA): 19
4
0 Execution (msec) Device Minimum Voltage: 9.
26
Analog Output Block (AO) 1 Number Device Capacitance: 5 nF
5 20 Execution (msec) Polarity-sensitive: Yes No
27
Discrete Output Block (DO) 1 Number Segment Terminator Location:
6 20 Execution (msec)
28
7 Control Selector (CS)
DD Revision: 3
PID,PI,I Controller (PID) 29
8
20 Execution (msec)
CFF Revision: 1.9
Ratio Station (RA) 30
9
P,PD Controller (PD) 0 Number
10 0 Execution (msec)

* Execution time in msec.

Advanced Function Blocks Notes:

11 Device Control (DC)

12 Output Splitter (OS)

13 Signal Characterizer (SC)

14 Lead Lag (LL)

15 Deadtime (DT)

16 Integrator(Totalizer) (IT)

17 Setpoint Ramp Generator (SPG)

18 Input Selector (IS)

19 Arithmetic (AR)

20 Timer (TMR)

21 Analog Alarm (AAL)

INSTRUMENT SPECIFICATION -FOUNDATION FIELDBUS


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S100.2 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Tag Number : LV -21601

1. In-Built surge protector is provided by vendor.

1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S100.3 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
1 Tag No. LV -21602
2 Service GA611 BD TO BL
3 P&ID No. Line No. R2B-P3-206-02-A-DTI-00601 2"-BD-216001-T-A18T1-N
4 Area Classification Ingress Protection CLASS 1 DIV 2 Gr. B ,C&D, T3 NEMA 4X
GENERAL 5 Ambient Temperature: Unit Min. Max. °C 10 48
6 Allowable Sound dBA Tightness Requirement <85 ANSI IV (standard)
7 Available Air Supply Pressure Unit Min. Max. kgf/cm²-g 4.2 8.0
8 Electric Connection Pneum. Connection 1/2” NPT (F) 1/4” NPT (F)
9 Power Failure Position FC
10 Line Size and Schedule Sch. Outlet Line Sch. 2 in XS 2" XS
PIPE
11 Line Class Rating Pipe Material T-A18T1 150# A106 GR.B, SMLS
LINE
12 Pipe Insulation Thickness Corrosion Allowance N N/A 1.6mm
13 Fluid State Phase Water Liquid Single Phase
14 Sour Service Special Condition N/A N/A
15 Flow Rate Units Min. Nor. Max. m³/h 1.378 2.757 3.032
16 Inlet Pressure Units Min. Nor. Max. kgf/cm²-g 6.706 6.653 6.668
17 Pressure Drop Units Min. Nor. Max. kgf/cm² 6.705 6.671 6.663
18 Inlet Temperature Units Min. Nor. Max. °C 40 40 40
PROCESS 19 Density Units Min. Nor. Max. kg/m³ 996 996 996
CONDITIONS 20 Viscosity Units Min. Nor. Max. cP 0.652 0.652 0.652
21 Molecular Weight (MW) Specific Gravity @ Oper.
22 Spec. Heat Ratio (Cp/Cv) Compressibility (Z)
23 Vapor Pressure (Liq.) Cavitation or Flashing 0.07 kgf/cm²-a NO
24 Critical Pressure (Liq) Flash (wt%) 225.55 kgf/cm²-a
25 Design Pressure Min. Max. -1.033 kgf/cm²-g 8.7 kgf/cm²-g
26 Design Temperature Min. Max. 10 °C 80 °C
27 Max.Shutoff DP Solid % 8.7 kgf/cm²
28 Calculated Cv Units Min. Nor. Max. Cv 0.651 1.31 1.44
CALCULATED
29 Travel Units Min. Nor. Max. % 51 70 73
RESULTS
30 Noise dBA @1m Units Min. Nor. Max. dBA 50 50 51
31 MFR Model FISHER EZ 56 MFR Model FISHER DVC6200F/SC-AD
32 Body Type Single Seat Globe 57 Signal: Inlet Outlet FF Protocol 0-2.8 kgf/cm2
33 Body Size Trim Size 1 in 3/8 in 58 Increase Signal Valve: DIRECT
34 End Connec.Size & Rating 1" 300# RF POSITIONER 59 Cam Characteristic LINEAR
35 Rated Cv Characteristic 3.07 EQ% 60 Bypass Gauges N/A YES
36 Body Material WCC Steel 61 Signal Fail. to Valve FC
BODY 37 Bonnet Type Material Plain WCC Steel 62 Electric Enclosure Ex ia IIC T5 , NEMA 4X
AND 38 Flow Direct. Flow Act. To Up FTO 63 MFR Model N/A N/A
TRIM 39 Packing Type Material Enviro Seal PTFE Carbon 64 Type Power N/A N/A
SOLENOID
40 Lubricator Isolat. Valve N/A N/A 65 When De-Enegr.Valve: N/A
VALVE
41 Guiding No. of Ports Post 1 66 Material Latcher N/A N/A
42 Trim Type Internal Design Micro Form Unbalanced 67 Electric Enclosure N/A
43 Rated Travel Leak Class 3/4 in ANSI IV 68 MFR Model N/A N/A
44 Plug/ Ball/ Disk Material S41600 SST 69 Type Quantity N/A N/A
45 Seat Material S41600 SST SWITCHES 70 Contacts / Rating N/A
46 Cage Stem Material N/A S31600 SST 71 Switching Position N/A
47 Gasket Material S31600 SST/Graphite 72 Electric Enclosure N/A
48 MFR Model FISHER 667 73 MFR Model FISHER 67CFR
49 Type Diaphragm Spring Return AIR SET 74 Set Pressure 4.2 kgf/cm2-g
50 Size Stroke Time 30i < 5 Sec 75 Filter Gauge 5 Micron min YES
ACTUATOR 51 Air Failure Valve: FC 76 Vol. Tank Booster NO NO
52 Handwheel Location N/A 77 Diffuser Lock-up NO NO
ACCESSORY
53 Mounting Position VERTICAL 78 Fire Safe Fireproof NO NO
54 Spring Range 0.7 - 2.4 kgf/cm2-g 79 Mech. Stop Quick Exa. NO NO
55 Include Pressure (Shutoff) 80 Hydro. Pressure YES
85 Vendor EMERSON 81 Leakage YES
PURCHASE TESTS
86 Manufacturer FISHER 82 Cryogenic N/A
87 Requisition No. R2B-P3-206-02-P-MR-00200 83 NACE Requirement N/A
88 Model No. EZ 84 PWHT Requirement N/A
Notes:

INSTRUMENT SPECIFICATION - CONTROL VALVE


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S101.1 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Fieldbus Device Data Sheet
Tag No.: LV -21602
Fieldbus Tag No.:

Service : GA611 BD TO BL

Basic Fieldbus Function Blocks Segment Information


Analog Input Block (AI) 1 Number Device:
1 22
20 Execution (msec)
Discrete Input Block (DI) 4 Number Segment #: DFJB-21001
2 23
15 Execution Time
3 Bias/Gain Station (BG) 0 Execution (msec) 24 LAS Capable: Yes No
Manual Loader (ML) 0 Number 25 Device Current Draw (mA): 19
4
0 Execution (msec) Device Minimum Voltage: 9.
26
Analog Output Block (AO) 1 Number Device Capacitance: 5 nF
5 20 Execution (msec) Polarity-sensitive: Yes No
27
Discrete Output Block (DO) 1 Number Segment Terminator Location:
6 20 Execution (msec)
28
7 Control Selector (CS)
DD Revision: 3
PID,PI,I Controller (PID) 29
8
20 Execution (msec)
CFF Revision: 1.9
Ratio Station (RA) 30
9
P,PD Controller (PD) 0 Number
10 0 Execution (msec)

* Execution time in msec.

Advanced Function Blocks Notes:

11 Device Control (DC)

12 Output Splitter (OS)

13 Signal Characterizer (SC)

14 Lead Lag (LL)

15 Deadtime (DT)

16 Integrator(Totalizer) (IT)

17 Setpoint Ramp Generator (SPG)

18 Input Selector (IS)

19 Arithmetic (AR)

20 Timer (TMR)

21 Analog Alarm (AAL)

INSTRUMENT SPECIFICATION -FOUNDATION FIELDBUS


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S101.2 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Tag Number : LV -21602

1. In-Built surge protector is provided by vendor.

1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S101.3 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
1 Tag No. LV -21603
2 Service GA601 OCD TO OCD TANK
3 P&ID No. Line No. R2B-P3-206-02-A-DTI-00613 4"-CACAP-212513-T-A18T1-PP
4 Area Classification Ingress Protection CLASS 1 DIV 2 Gr. B ,C&D, T3 NEMA 4X
GENERAL 5 Ambient Temperature: Unit Min. Max. °C 10 48
6 Allowable Sound dBA Tightness Requirement <85 ANSI IV (standard)
7 Available Air Supply Pressure Unit Min. Max. kgf/cm²-g 4.2 8.0
8 Electric Connection Pneum. Connection 1/2” NPT (F) 1/4” NPT (F)
9 Power Failure Position FC
10 Line Size and Schedule Sch. Outlet Line Sch. 4 in STD 4" STD
PIPE
11 Line Class Rating Pipe Material T-A18T1 150# A106 GR.B, SMLS
LINE
12 Pipe Insulation Thickness Corrosion Allowance PP 40mm 1.6mm
13 Fluid State Phase Oily Condensate Liquid Single Phase
14 Sour Service Special Condition N/A N/A
15 Flow Rate Units Min. Nor. Max. m³/h 13.5 27.1 68.2
16 Inlet Pressure Units Min. Nor. Max. kgf/cm²-g 8.275 8.227 7.922
17 Pressure Drop Units Min. Nor. Max. kgf/cm² 2.14 2.013 0.7
18 Inlet Temperature Units Min. Nor. Max. °C 105 105 105
PROCESS 19 Density Units Min. Nor. Max. kg/m³ 944 944 944
CONDITIONS 20 Viscosity Units Min. Nor. Max. cP 0.2651 0.2651 0.2651
21 Molecular Weight (MW) Specific Gravity @ Oper.
22 Spec. Heat Ratio (Cp/Cv) Compressibility (Z)
23 Vapor Pressure (Liq.) Cavitation or Flashing 1.234 kgf/cm²-a NO
24 Critical Pressure (Liq) Flash (wt%) 225.5 kgf/cm²-a
25 Design Pressure Min. Max. -1.033 kgf/cm²-g 13 kgf/cm²-g
26 Design Temperature Min. Max. 10 °C 130 °C
27 Max.Shutoff DP Solid % 13 kgf/cm²
28 Calculated Cv Units Min. Nor. Max. Cv 10.5 21.7 92.5
CALCULATED
29 Travel Units Min. Nor. Max. % 15 28 86
RESULTS
30 Noise dBA @1m Units Min. Nor. Max. dBA 50 50 50
31 MFR Model FISHER EWT 56 MFR Model FISHER DVC6200F/SC-AD
32 Body Type Single Seat Globe 57 Signal: Inlet Outlet FF Protocol 0-2.8 kgf/cm2
33 Body Size Trim Size 4 in 2 5/16 in 58 Increase Signal Valve: DIRECT
34 End Connec.Size & Rating 4" 300# RF POSITIONER 59 Cam Characteristic LINEAR
35 Rated Cv Characteristic 107 Linear 60 Bypass Gauges N/A YES
36 Body Material WCC Steel 61 Signal Fail. to Valve FC
BODY 37 Bonnet Type Material Plain WCC Steel 62 Electric Enclosure Ex ia IIC T5 , NEMA 4X
AND 38 Flow Direct. Flow Act. To Down FTO 63 MFR Model N/A N/A
TRIM 39 Packing Type Material ISO Seal PTFE 64 Type Power N/A N/A
SOLENOID
40 Lubricator Isolat. Valve N/A N/A 65 When De-Enegr.Valve: N/A
VALVE
41 Guiding No. of Ports Cage 1 66 Material Latcher N/A N/A
42 Trim Type Internal Design Standard Balanced 67 Electric Enclosure N/A
43 Rated Travel Leak Class 1 1/8 in ANSI IV 68 MFR Model N/A N/A
44 Plug/ Ball/ Disk Material S41600 SST 69 Type Quantity N/A N/A
45 Seat Material S41600 SST SWITCHES 70 Contacts / Rating N/A
46 Cage Stem Material CB7Cu-1 SST S31600 SST 71 Switching Position N/A
47 Gasket Material S31600 SST/Graphite 72 Electric Enclosure N/A
48 MFR Model FISHER 667 73 MFR Model FISHER 67CFR
49 Type Diaphragm Spring Return AIR SET 74 Set Pressure 4.2 kgf/cm2-g
50 Size Stroke Time 40i < 10 Sec 75 Filter Gauge 5 Micron min YES
ACTUATOR 51 Air Failure Valve: FC 76 Vol. Tank Booster NO NO
52 Handwheel Location N/A 77 Diffuser Lock-up NO NO
ACCESSORY
53 Mounting Position VERTICAL 78 Fire Safe Fireproof NO NO
54 Spring Range 0.7 - 2.4 kgf/cm2-g 79 Mech. Stop Quick Exa. NO NO
55 Include Pressure (Shutoff) 80 Hydro. Pressure YES
85 Vendor EMERSON 81 Leakage YES
PURCHASE TESTS
86 Manufacturer FISHER 82 Cryogenic N/A
87 Requisition No. R2B-P3-206-02-P-MR-00200 83 NACE Requirement N/A
88 Model No. EWT 84 PWHT Requirement N/A
Notes:

INSTRUMENT SPECIFICATION - CONTROL VALVE


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S102.1 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Fieldbus Device Data Sheet
Tag No.: LV -21603
Fieldbus Tag No.:

Service : GA601 OCD TO OCD TANK

Basic Fieldbus Function Blocks Segment Information


Analog Input Block (AI) 1 Number Device:
1 22
20 Execution (msec)
Discrete Input Block (DI) 4 Number Segment #: DFJB-21155
2 23
15 Execution Time
3 Bias/Gain Station (BG) 0 Execution (msec) 24 LAS Capable: Yes No
Manual Loader (ML) 0 Number 25 Device Current Draw (mA): 19
4
0 Execution (msec) Device Minimum Voltage: 9.
26
Analog Output Block (AO) 1 Number Device Capacitance: 5 nF
5 20 Execution (msec) Polarity-sensitive: Yes No
27
Discrete Output Block (DO) 1 Number Segment Terminator Location:
6 20 Execution (msec)
28
7 Control Selector (CS)
DD Revision: 3
PID,PI,I Controller (PID) 29
8
20 Execution (msec)
CFF Revision: 1.9
Ratio Station (RA) 30
9
P,PD Controller (PD) 0 Number
10 0 Execution (msec)

* Execution time in msec.

Advanced Function Blocks Notes:

11 Device Control (DC)

12 Output Splitter (OS)

13 Signal Characterizer (SC)

14 Lead Lag (LL)

15 Deadtime (DT)

16 Integrator(Totalizer) (IT)

17 Setpoint Ramp Generator (SPG)

18 Input Selector (IS)

19 Arithmetic (AR)

20 Timer (TMR)

21 Analog Alarm (AAL)

INSTRUMENT SPECIFICATION -FOUNDATION FIELDBUS


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S102.2 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Tag Number : LV -21603

1. In-Built surge protector is provided by vendor.

1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S102.3 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
1 Tag No. PDV -21010
2 Service EG601AB NAT GAS TO BA001
3 P&ID No. Line No. R2B-P3-206-02-A-DTI-00061A 2"-GNB-210814-M1A1-N
4 Area Classification Ingress Protection CLASS 1 DIV 2 Gr. B ,C&D, T3 NEMA 4X
GENERAL 5 Ambient Temperature: Unit Min. Max. °C 10 48
6 Allowable Sound dBA Tightness Requirement <85 ANSI IV (standard)
7 Available Air Supply Pressure Unit Min. Max. kgf/cm²-g 4.2 8.0
8 Electric Connection Pneum. Connection 1/2” NPT (F) 1/4” NPT (F)
9 Power Failure Position FC
10 Line Size and Schedule Sch. Outlet Line Sch. 2 in 80S 2" 80S
PIPE
11 Line Class Rating Pipe Material M1A1 150# A312 GR.TP316/316L, SMLS
LINE
12 Pipe Insulation Thickness Corrosion Allowance N N/A 1.6mm
13 Fluid State Phase Hydrocarbon & Hydrogen Gas/Vapor Single Phase
14 Sour Service Special Condition N/A N/A
15 Flow Rate Units Min. Nor. Max. Nm³/h 93.6 187.2 372.3
16 Inlet Pressure Units Min. Nor. Max. kgf/cm²-g 6.837 6.709 6.673
17 Pressure Drop Units Min. Nor. Max. kgf/cm² 3.399 3.222 3.172
18 Inlet Temperature Units Min. Nor. Max. °C 38 38 38
PROCESS 19 Density Units Min. Nor. Max. kg/m³
CONDITIONS 20 Viscosity Units Min. Nor. Max. cP 0.012 0.012 0.012
21 Molecular Weight (MW) Specific Gravity @ Oper. 22
22 Spec. Heat Ratio (Cp/Cv) Compressibility (Z) 1.303 0.966
23 Vapor Pressure (Liq.) Cavitation or Flashing kgf/cm²-a N/A
24 Critical Pressure (Liq) Flash (wt%) kgf/cm²-a
25 Design Pressure Min. Max. kgf/cm²-g 9 kgf/cm²-g
26 Design Temperature Min. Max. 10 °C 70 °C
27 Max.Shutoff DP Solid % 9 kgf/cm²
28 Calculated Cv Units Min. Nor. Max. 0.904
Cv 1.85 3.9
CALCULATED
29 Travel Units Min. Nor. Max. 13
% 29 47
RESULTS
30 Noise dBA @1m Units Min. Nor. Max. 50
dBA 50 57
31 MFR Model FISHER EZ 56 MFR Model FISHER DVC6200F/SC-AD
32 Body Type Single Seat Globe 57 Signal: Inlet Outlet FF Protocol 0-2.8 kgf/cm2
33 Body Size Trim Size 1.5 in 1 1/2 in 58 Increase Signal Valve: DIRECT
34 End Connec.Size & Rating 1.5" 300# RF POSITIONER 59 Cam Characteristic LINEAR
35 Rated Cv Characteristic 28.1 EQ% 60 Bypass Gauges N/A YES
36 Body Material CF8M SST 61 Signal Fail. to Valve FC
BODY 37 Bonnet Type Material Plain CF8M SST 62 Electric Enclosure Ex ia IIC T5 , NEMA 4X
AND 38 Flow Direct. Flow Act. To Up FTO 63 MFR Model N/A N/A
TRIM 39 Packing Type Material ISO Seal PTFE 64 Type Power N/A N/A
SOLENOID
40 Lubricator Isolat. Valve N/A N/A 65 When De-Enegr.Valve: N/A
VALVE
41 Guiding No. of Ports Post 1 66 Material Latcher N/A N/A
42 Trim Type Internal Design Standard Unbalanced 67 Electric Enclosure N/A
43 Rated Travel Leak Class 3/4 in ANSI IV 68 MFR Model N/A N/A
44 Plug/ Ball/ Disk Material S31600 SST 69 Type Quantity N/A N/A
45 Seat Material S31600 SST SWITCHES 70 Contacts / Rating N/A
46 Cage Stem Material N/A S31600 SST 71 Switching Position N/A
47 Gasket Material S31600 SST/Graphite 72 Electric Enclosure N/A
48 MFR Model FISHER 667 73 MFR Model FISHER 67CFR
49 Type Diaphragm Spring Return AIR SET 74 Set Pressure 4.2 kgf/cm2-g
50 Size Stroke Time 34i < 5 Sec 75 Filter Gauge 5 Micron min YES
ACTUATOR 51 Air Failure Valve: FC 76 Vol. Tank Booster NO NO
52 Handwheel Location N/A 77 Diffuser Lock-up NO NO
ACCESSORY
53 Mounting Position VERTICAL 78 Fire Safe Fireproof NO NO
54 Spring Range 1.3 - 2.4 kgf/cm2-g 79 Mech. Stop Quick Exa. NO NO
55 Include Pressure (Shutoff) 80 Hydro. Pressure YES
85 Vendor EMERSON 81 Leakage YES
PURCHASE TESTS
86 Manufacturer FISHER 82 Cryogenic N/A
87 Requisition No. R2B-P3-206-02-P-MR-00200 83 NACE Requirement N/A
88 Model No. EZ 84 PWHT Requirement N/A
Notes:

INSTRUMENT SPECIFICATION - CONTROL VALVE


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S103.1 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Fieldbus Device Data Sheet
Tag No.: PDV -21010
Fieldbus Tag No.:

Service : EG601AB NAT GAS TO BA001

Basic Fieldbus Function Blocks Segment Information


Analog Input Block (AI) 1 Number Device:
1 22
20 Execution (msec)
Discrete Input Block (DI) 4 Number Segment #: DFJB-21031
2 23
15 Execution Time
3 Bias/Gain Station (BG) 0 Execution (msec) 24 LAS Capable: Yes No
Manual Loader (ML) 0 Number 25 Device Current Draw (mA): 19
4
0 Execution (msec) Device Minimum Voltage: 9.
26
Analog Output Block (AO) 1 Number Device Capacitance: 5 nF
5 20 Execution (msec) Polarity-sensitive: Yes No
27
Discrete Output Block (DO) 1 Number Segment Terminator Location:
6 20 Execution (msec)
28
7 Control Selector (CS)
DD Revision: 3
PID,PI,I Controller (PID) 29
8
20 Execution (msec)
CFF Revision: 1.9
Ratio Station (RA) 30
9
P,PD Controller (PD) 0 Number
10 0 Execution (msec)

* Execution time in msec.

Advanced Function Blocks Notes:

11 Device Control (DC)

12 Output Splitter (OS)

13 Signal Characterizer (SC)

14 Lead Lag (LL)

15 Deadtime (DT)

16 Integrator(Totalizer) (IT)

17 Setpoint Ramp Generator (SPG)

18 Input Selector (IS)

19 Arithmetic (AR)

20 Timer (TMR)

21 Analog Alarm (AAL)

INSTRUMENT SPECIFICATION -FOUNDATION FIELDBUS


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S103.2 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Tag Number : PDV -21010

1. Start-up Case
2. Control Valve Outlet data -
Maximum Case - Inlet Pressure: 2.89 kg/cm^2-g; Pressure Drop : 0.145 kg/cm^2; Temp: 38oC; Vap Visc.: 0.01184 cP; Vap MW: 19.31 Vap Z: 0.9851
Vap Cp/Cv(Real): 1.271
Normal Case - Inlet Pressure: 3.275 kg/cm^2-g; Pressure Drop : 0.549 kg/cm^2; Temp: 38oC; Vap Visc.: 0.01184 cP; Vap MW: 19.31 Vap Z: 0.9851
Vap Cp/Cv(Real): 1.271
Minimum Case - Inlet Pressure: 3.657 kg/cm^2-g; Pressure Drop : 0.912 kg/cm^2; Temp: 38oC; Vap Visc.: 0.01184 cP; Vap MW: 19.31 Vap Z: 0.9851
Vap Cp/Cv(Real): 1.271

3. Start up Min/Nor/Max Opening : 29 / 53 / 84%.


Start up Min/Nor/Max Noise : 50 / 50 / 50 dBA.
Start up Min/Nor/Max Calculated Cv : 1.858 / 4.906 / 18.817

4. In-Built surge protector is provided by vendor.

1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S103.3 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
1 Tag No. PDV -21011
2 Service FA611 FG TO BA001
3 P&ID No. Line No. R2B-P3-206-02-A-DTI-00061A 6"-GD-210813-M1A1-N
4 Area Classification Ingress Protection CLASS 1 DIV 2 Gr. B ,C&D, T3 NEMA 4X
GENERAL 5 Ambient Temperature: Unit Min. Max. °C 10 48
6 Allowable Sound dBA Tightness Requirement <85 ANSI IV (standard)
7 Available Air Supply Pressure Unit Min. Max. kgf/cm²-g 4.2 8.0
8 Electric Connection Pneum. Connection 1/2” NPT (F) 1/4” NPT (F)
9 Power Failure Position FC
10 Line Size and Schedule Sch. Outlet Line Sch. 6 in 40S 6" 40S
PIPE
11 Line Class Rating Pipe Material M1A1 150# A312 GR.TP316/316L, SMLS
LINE
12 Pipe Insulation Thickness Corrosion Allowance N N/A 1.6mm
13 Fluid State Phase Hydrocarbon & Hydrogen Gas/Vapor Single Phase
14 Sour Service Special Condition N/A N/A
15 Flow Rate Units Min. Nor. Max. Nm³/h 2559.25 5118.49 6414.7
16 Inlet Pressure Units Min. Nor. Max. kgf/cm²-g 6.837 6.709 6.672
17 Pressure Drop Units Min. Nor. Max. kgf/cm² 4.771 4.568 3.512
18 Inlet Temperature Units Min. Nor. Max. °C 38 38 38
PROCESS 19 Density Units Min. Nor. Max. kg/m³
CONDITIONS 20 Viscosity Units Min. Nor. Max. cP 0.012 0.012 0.012
21 Molecular Weight (MW) Specific Gravity @ Oper. 22
22 Spec. Heat Ratio (Cp/Cv) Compressibility (Z) 1.303 0.966
23 Vapor Pressure (Liq.) Cavitation or Flashing kgf/cm²-a N/A
24 Critical Pressure (Liq) Flash (wt%) kgf/cm²-a
25 Design Pressure Min. Max. kgf/cm²-g 9 kgf/cm²-g
26 Design Temperature Min. Max. 10 °C 70 °C
27 Max.Shutoff DP Solid % 9 kgf/cm²
28 Calculated Cv Units Min. Nor. Max. Cv 26.4 53.6 67.9
CALCULATED
29 Travel Units Min. Nor. Max. % 12 24 30
RESULTS
30 Noise dBA @1m Units Min. Nor. Max. dBA 71 74 73
31 MFR Model FISHER ET 56 MFR Model FISHER DVC6200F/SC-AD
32 Body Type Single Seat Globe 57 Signal: Inlet Outlet FF Protocol 0-2.3 kgf/cm2
33 Body Size Trim Size 6 in 5 3/8 in 58 Increase Signal Valve: DIRECT
34 End Connec.Size & Rating 6" 300# RF POSITIONER 59 Cam Characteristic LINEAR
35 Rated Cv Characteristic 231.2 Linear 60 Bypass Gauges N/A YES
36 Body Material CF8M SST 61 Signal Fail. to Valve FC
BODY 37 Bonnet Type Material Plain CF8M SST 62 Electric Enclosure Ex ia IIC T5 , NEMA 4X
AND 38 Flow Direct. Flow Act. To Up FTO 63 MFR Model N/A N/A
TRIM 39 Packing Type Material ISO Seal PTFE 64 Type Power N/A N/A
SOLENOID
40 Lubricator Isolat. Valve N/A N/A 65 When De-Enegr.Valve: N/A
VALVE
41 Guiding No. of Ports Cage 1 66 Material Latcher N/A N/A
42 Trim Type Internal Design Standard Balanced 67 Electric Enclosure N/A
43 Rated Travel Leak Class 3 in ANSI IV 68 MFR Model N/A N/A
44 Plug/ Ball/ Disk Material S31600 SST/CoCr-A Seat 69 Type Quantity N/A N/A
45 Seat Material R30006 Cobalt Alloy SWITCHES 70 Contacts / Rating N/A
46 Cage Stem Material S31600 SST/ ENCS20910 SST 71 Switching Position N/A
47 Gasket Material S31600 SST/Graphite 72 Electric Enclosure N/A
48 MFR Model FISHER 667 73 MFR Model FISHER 67CFR
49 Type Diaphragm Spring Return AIR SET 74 Set Pressure 4.2 kgf/cm2-g
50 Size Stroke Time 70i < 15 Sec 75 Filter Gauge 5 Micron min YES
ACTUATOR 51 Air Failure Valve: FC 76 Vol. Tank Booster NO NO
52 Handwheel Location N/A 77 Diffuser Lock-up NO NO
ACCESSORY
53 Mounting Position VERTICAL 78 Fire Safe Fireproof NO NO
54 Spring Range 0.6 - 1.8 kgf/cm2-g 79 Mech. Stop Quick Exa. NO NO
55 Include Pressure (Shutoff) 80 Hydro. Pressure YES
85 Vendor EMERSON 81 Leakage YES
PURCHASE TESTS
86 Manufacturer FISHER 82 Cryogenic N/A
87 Requisition No. R2B-P3-206-02-P-MR-00200 83 NACE Requirement N/A
88 Model No. ET 84 PWHT Requirement N/A
Notes:

INSTRUMENT SPECIFICATION - CONTROL VALVE


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S104.1 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Fieldbus Device Data Sheet
Tag No.: PDV -21011
Fieldbus Tag No.:

Service : FA611 FG TO BA001

Basic Fieldbus Function Blocks Segment Information


Analog Input Block (AI) 1 Number Device:
1 22
20 Execution (msec)
Discrete Input Block (DI) 4 Number Segment #: DFJB-21017
2 23
15 Execution Time
3 Bias/Gain Station (BG) 0 Execution (msec) 24 LAS Capable: Yes No
Manual Loader (ML) 0 Number 25 Device Current Draw (mA): 19
4
0 Execution (msec) Device Minimum Voltage: 9.
26
Analog Output Block (AO) 1 Number Device Capacitance: 5 nF
5 20 Execution (msec) Polarity-sensitive: Yes No
27
Discrete Output Block (DO) 1 Number Segment Terminator Location:
6 20 Execution (msec)
28
7 Control Selector (CS)
DD Revision: 3
PID,PI,I Controller (PID) 29
8
20 Execution (msec)
CFF Revision: 1.9
Ratio Station (RA) 30
9
P,PD Controller (PD) 0 Number
10 0 Execution (msec)

* Execution time in msec.

Advanced Function Blocks Notes:

11 Device Control (DC)

12 Output Splitter (OS)

13 Signal Characterizer (SC)

14 Lead Lag (LL)

15 Deadtime (DT)

16 Integrator(Totalizer) (IT)

17 Setpoint Ramp Generator (SPG)

18 Input Selector (IS)

19 Arithmetic (AR)

20 Timer (TMR)

21 Analog Alarm (AAL)

INSTRUMENT SPECIFICATION -FOUNDATION FIELDBUS


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S104.2 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Tag Number : PDV -21011

1. Start-up Case
2. Control Valve Outlet data -
Maximum Case - Inlet Pressure: 2.889 kg/cm^2-g; Pressure Drop : 0.467 kg/cm^2; Temp: 38oC; Vap Visc.: 0.01184 cP; Vap MW: 19.31 Vap Z: 0.9851
Vap Cp/Cv(Real): 1.271
Normal Case - Inlet Pressure: 3.274 kg/cm^2-g; Pressure Drop : 0.875 kg/cm^2; Temp: 38oC; Vap Visc.: 0.01184 cP; Vap MW: 19.31 Vap Z: 0.9851
Vap Cp/Cv(Real): 1.271
Minimum Case - Inlet Pressure: 3.656 kg/cm^2-g; Pressure Drop : 0.43 kg/cm^2; Temp: 38oC; Vap Visc.: 0.01184 cP; Vap MW: 19.31 Vap Z: 0.9851
Vap Cp/Cv(Real): 1.271

3. Start up Min/Nor/Max Opening : 31 / 48 / 81%.


Start up Min/Nor/Max Noise : 58 / 65 / 63 dBA.
Start up Min/Nor/Max Calculated Cv : 70.946 / 112.482 / 190.185

4. In-Built surge protector is provided by vendor.

1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S104.3 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
1 Tag No. PDV -21065
2 Service MP STM TO SPE016
3 P&ID No. Line No. R2B-P3-206-02-A-DTI-00072 1-1/2"-VM-210497-T-B04T1-EC
4 Area Classification Ingress Protection CLASS 1 DIV 2 Gr. B ,C&D, T3 NEMA 4X
GENERAL 5 Ambient Temperature: Unit Min. Max. °C 10 48
6 Allowable Sound dBA Tightness Requirement <85 ANSI IV (standard)
7 Available Air Supply Pressure Unit Min. Max. kgf/cm²-g 4.2 8.0
8 Electric Connection Pneum. Connection 1/2” NPT (F) 1/4” NPT (F)
9 Power Failure Position FO
10 Line Size and Schedule Sch. Outlet Line Sch. 1-1/2 in XS 1.5" XS
PIPE
11 Line Class Rating Pipe Material T-B04T1 300# A106 GR.B, SMLS
LINE
12 Pipe Insulation Thickness Corrosion Allowance EC 90mm 1.6mm
13 Fluid State Phase Steam Gas/Vapor Single Phase
14 Sour Service Special Condition N/A N/A
15 Flow Rate Units Min. Nor. Max. kg/h 45 91 109
16 Inlet Pressure Units Min. Nor. Max. kgf/cm²-g 13.46 10.34 9.77
17 Pressure Drop Units Min. Nor. Max. kgf/cm² 11.98 7.87 7.16
18 Inlet Temperature Units Min. Nor. Max. °C 220 220 220
PROCESS 19 Density Units Min. Nor. Max. kg/m³
CONDITIONS 20 Viscosity Units Min. Nor. Max. cP 0.017 0.017 0.017
21 Molecular Weight (MW) Specific Gravity @ Oper. 18.02
22 Spec. Heat Ratio (Cp/Cv) Compressibility (Z) 1.238 0.947
23 Vapor Pressure (Liq.) Cavitation or Flashing kgf/cm²-a N/A
24 Critical Pressure (Liq) Flash (wt%) kgf/cm²-a
25 Design Pressure Min. Max. -1.033 kgf/cm²-g 15.5 kgf/cm²-g
26 Design Temperature Min. Max. 10 °C 260 °C
27 Max.Shutoff DP Solid % 15.5 kgf/cm²
28 Calculated Cv Units Min. Nor. Max. Cv 0.343 0.93 1.18
CALCULATED
29 Travel Units Min. Nor. Max. % 33 61 67
RESULTS
30 Noise dBA @1m Units Min. Nor. Max. dBA 50 57 59
31 MFR Model FISHER EZ 56 MFR Model FISHER DVC6200F/SC-AD
32 Body Type Single Seat Globe 57 Signal: Inlet Outlet FF Protocol 0-2.8 kgf/cm2
33 Body Size Trim Size 1 in 3/8 in 58 Increase Signal Valve: DIRECT
34 End Connec.Size & Rating 1" 300# RF POSITIONER 59 Cam Characteristic LINEAR
35 Rated Cv Characteristic 3.07 EQ% 60 Bypass Gauges N/A YES
36 Body Material WCC Steel 61 Signal Fail. to Valve FO
BODY 37 Bonnet Type Material Style 1 Extension WCC Steel 62 Electric Enclosure Ex ia IIC T5 , NEMA 4X
AND 38 Flow Direct. Flow Act. To Up FTO 63 MFR Model N/A N/A
TRIM 39 Packing Type Material Enviro Seal Graphite ULF 64 Type Power N/A N/A
SOLENOID
40 Lubricator Isolat. Valve N/A N/A 65 When De-Enegr.Valve: N/A
VALVE
41 Guiding No. of Ports Post 1 66 Material Latcher N/A N/A
42 Trim Type Internal Design Micro Form Unbalanced 67 Electric Enclosure N/A
43 Rated Travel Leak Class 3/4 in ANSI IV 68 MFR Model N/A N/A
44 Plug/ Ball/ Disk Material S41600 SST 69 Type Quantity N/A N/A
45 Seat Material S41600 SST SWITCHES 70 Contacts / Rating N/A
46 Cage Stem Material N/A S31600 SST 71 Switching Position N/A
47 Gasket Material S31600 SST/Graphite 72 Electric Enclosure N/A
48 MFR Model FISHER 657 73 MFR Model FISHER 67CFR
49 Type Diaphragm Spring Return AIR SET 74 Set Pressure 4.2 kgf/cm2-g
50 Size Stroke Time 30i < 5 Sec 75 Filter Gauge 5 Micron min YES
ACTUATOR 51 Air Failure Valve: FO 76 Vol. Tank Booster NO NO
52 Handwheel Location N/A 77 Diffuser Lock-up NO NO
ACCESSORY
53 Mounting Position VERTICAL 78 Fire Safe Fireproof NO NO
54 Spring Range 0.6 - 2.2 kgf/cm2-g 79 Mech. Stop Quick Exa. NO NO
55 Include Pressure (Shutoff) 80 Hydro. Pressure YES
85 Vendor EMERSON 81 Leakage YES
PURCHASE TESTS
86 Manufacturer FISHER 82 Cryogenic N/A
87 Requisition No. R2B-P3-206-02-P-MR-00200 83 NACE Requirement N/A
88 Model No. EZ 84 PWHT Requirement N/A
Notes:

INSTRUMENT SPECIFICATION - CONTROL VALVE


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S105.1 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Fieldbus Device Data Sheet
Tag No.: PDV -21065
Fieldbus Tag No.:

Service : MP STM TO SPE016

Basic Fieldbus Function Blocks Segment Information


Analog Input Block (AI) 1 Number Device:
1 22
20 Execution (msec)
Discrete Input Block (DI) 4 Number Segment #: DFJB-21056
2 23
15 Execution Time
3 Bias/Gain Station (BG) 0 Execution (msec) 24 LAS Capable: Yes No
Manual Loader (ML) 0 Number 25 Device Current Draw (mA): 19
4
0 Execution (msec) Device Minimum Voltage: 9.
26
Analog Output Block (AO) 1 Number Device Capacitance: 5 nF
5 20 Execution (msec) Polarity-sensitive: Yes No
27
Discrete Output Block (DO) 1 Number Segment Terminator Location:
6 20 Execution (msec)
28
7 Control Selector (CS)
DD Revision: 3
PID,PI,I Controller (PID) 29
8
20 Execution (msec)
CFF Revision: 1.9
Ratio Station (RA) 30
9
P,PD Controller (PD) 0 Number
10 0 Execution (msec)

* Execution time in msec.

Advanced Function Blocks Notes:

11 Device Control (DC)

12 Output Splitter (OS)

13 Signal Characterizer (SC)

14 Lead Lag (LL)

15 Deadtime (DT)

16 Integrator(Totalizer) (IT)

17 Setpoint Ramp Generator (SPG)

18 Input Selector (IS)

19 Arithmetic (AR)

20 Timer (TMR)

21 Analog Alarm (AAL)

INSTRUMENT SPECIFICATION -FOUNDATION FIELDBUS


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S105.2 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Tag Number : PDV -21065

1. In-Built surge protector is provided by vendor.

1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S105.3 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
1 Tag No. PDV -21404
2 Service DF401 OVHD TO FA401
3 P&ID No. Line No. R2B-P3-206-02-A-DTI-00403 6"-P-214017-B2A1-N
4 Area Classification Ingress Protection CLASS 1 DIV 2 Gr. B ,C&D, T3 NEMA 4X
GENERAL 5 Ambient Temperature: Unit Min. Max. °C 10 48
6 Allowable Sound dBA Tightness Requirement <85 ANSI IV (standard)
7 Available Air Supply Pressure Unit Min. Max. kgf/cm²-g 4.2 8.0
8 Electric Connection Pneum. Connection 1/2” NPT (F) 1/4” NPT (F)
9 Power Failure Position FC
10 Line Size and Schedule Sch. Outlet Line Sch. 6 in STD 6" STD
PIPE
11 Line Class Rating Pipe Material B2A1 300# A106 GR.B, SMLS
LINE
12 Pipe Insulation Thickness Corrosion Allowance N N/A 1.6mm
13 Fluid State Phase Hydrocarbon Gas/Vapor Single Phase
14 Sour Service Special Condition N/A N/A
15 Flow Rate Units Min. Nor. Max. Nm³/h 2745 5489 6038
16 Inlet Pressure Units Min. Nor. Max. kgf/cm²-g 20.52 20.44 20.47
17 Pressure Drop Units Min. Nor. Max. kgf/cm² 0.782 0.64 0.57
18 Inlet Temperature Units Min. Nor. Max. °C 54 54 54
PROCESS 19 Density Units Min. Nor. Max. kg/m³
CONDITIONS 20 Viscosity Units Min. Nor. Max. cP 0.009 0.009 0.009
21 Molecular Weight (MW) Specific Gravity @ Oper. 42.75
22 Spec. Heat Ratio (Cp/Cv) Compressibility (Z) 1.081 0.688
23 Vapor Pressure (Liq.) Cavitation or Flashing kgf/cm²-a N/A
24 Critical Pressure (Liq) Flash (wt%) kgf/cm²-a
25 Design Pressure Min. Max. kgf/cm²-g 23 kgf/cm²-g
26 Design Temperature Min. Max. 10 °C 140 °C
27 Max.Shutoff DP Solid % 23 kgf/cm²
28 Calculated Cv Units Min. Nor. Max. Cv 32.6 73.5 86.3
CALCULATED
29 Travel Units Min. Nor. Max. % 53 72 77
RESULTS
30 Noise dBA @1m Units Min. Nor. Max. dBA 63 64 62
31 MFR Model FISHER ET 56 MFR Model FISHER DVC6200F/SC-AD
32 Body Type Single Seat Globe 57 Signal: Inlet Outlet FF Protocol 0-2.8 kgf/cm2
33 Body Size Trim Size 3 in 3 7/16 in 58 Increase Signal Valve: DIRECT
34 End Connec.Size & Rating 3" 300# RF POSITIONER 59 Cam Characteristic LINEAR
35 Rated Cv Characteristic 136 EQ% 60 Bypass Gauges N/A YES
36 Body Material WCC Steel 61 Signal Fail. to Valve FC
BODY 37 Bonnet Type Material Plain WCC Steel 62 Electric Enclosure Ex ia IIC T5 , NEMA 4X
AND 38 Flow Direct. Flow Act. To Down FTO 63 MFR Model N/A N/A
TRIM 39 Packing Type Material ISO Seal PTFE 64 Type Power N/A N/A
SOLENOID
40 Lubricator Isolat. Valve N/A N/A 65 When De-Enegr.Valve: N/A
VALVE
41 Guiding No. of Ports Cage 1 66 Material Latcher N/A N/A
42 Trim Type Internal Design Standard Balanced 67 Electric Enclosure N/A
43 Rated Travel Leak Class 1 1/2 in ANSI IV 68 MFR Model N/A N/A
44 Plug/ Ball/ Disk Material S41600 SST 69 Type Quantity N/A N/A
45 Seat Material S41600 SST SWITCHES 70 Contacts / Rating N/A
46 Cage Stem Material CB7Cu-1 SST S31600 SST 71 Switching Position N/A
47 Gasket Material S31600 SST/Graphite 72 Electric Enclosure N/A
48 MFR Model FISHER 667 73 MFR Model FISHER 67CFR
49 Type Diaphragm Spring Return AIR SET 74 Set Pressure 4.2 kgf/cm2-g
50 Size Stroke Time 45i < 8 Sec 75 Filter Gauge 5 Micron min YES
ACTUATOR 51 Air Failure Valve: FC 76 Vol. Tank Booster NO NO
52 Handwheel Location N/A 77 Diffuser Lock-up NO NO
ACCESSORY
53 Mounting Position VERTICAL 78 Fire Safe Fireproof NO NO
54 Spring Range 0.7 - 2.6 kgf/cm2-g 79 Mech. Stop Quick Exa. NO NO
55 Include Pressure (Shutoff) 80 Hydro. Pressure YES
85 Vendor EMERSON 81 Leakage YES
PURCHASE TESTS
86 Manufacturer FISHER 82 Cryogenic N/A
87 Requisition No. R2B-P3-206-02-P-MR-00200 83 NACE Requirement N/A
88 Model No. ET 84 PWHT Requirement N/A
Notes:

INSTRUMENT SPECIFICATION - CONTROL VALVE


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S106.1 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Fieldbus Device Data Sheet
Tag No.: PDV -21404
Fieldbus Tag No.:

Service : DF401 OVHD TO FA401

Basic Fieldbus Function Blocks Segment Information


Analog Input Block (AI) 1 Number Device:
1 22
20 Execution (msec)
Discrete Input Block (DI) 4 Number Segment #: DFJB-21159
2 23
15 Execution Time
3 Bias/Gain Station (BG) 0 Execution (msec) 24 LAS Capable: Yes No
Manual Loader (ML) 0 Number 25 Device Current Draw (mA): 19
4
0 Execution (msec) Device Minimum Voltage: 9.
26
Analog Output Block (AO) 1 Number Device Capacitance: 5 nF
5 20 Execution (msec) Polarity-sensitive: Yes No
27
Discrete Output Block (DO) 1 Number Segment Terminator Location:
6 20 Execution (msec)
28
7 Control Selector (CS)
DD Revision: 3
PID,PI,I Controller (PID) 29
8
20 Execution (msec)
CFF Revision: 1.9
Ratio Station (RA) 30
9
P,PD Controller (PD) 0 Number
10 0 Execution (msec)

* Execution time in msec.

Advanced Function Blocks Notes:

11 Device Control (DC)

12 Output Splitter (OS)

13 Signal Characterizer (SC)

14 Lead Lag (LL)

15 Deadtime (DT)

16 Integrator(Totalizer) (IT)

17 Setpoint Ramp Generator (SPG)

18 Input Selector (IS)

19 Arithmetic (AR)

20 Timer (TMR)

21 Analog Alarm (AAL)

INSTRUMENT SPECIFICATION -FOUNDATION FIELDBUS


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S106.2 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Tag Number : PDV -21404

1. In-Built surge protector is provided by vendor.

1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S106.3 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
1 Tag No. PV -21003
2 Service FA008 PA"TO FA001 TO FA002AB"
3 P&ID No. Line No. R2B-P3-206-02-A-DTI-00055 4"-P-210402-B1A1-N
4 Area Classification Ingress Protection CLASS 1 DIV 2 Gr. B ,C&D, T3 NEMA 4X
GENERAL 5 Ambient Temperature: Unit Min. Max. °C 10 48
6 Allowable Sound dBA Tightness Requirement <85 ANSI IV (standard)
7 Available Air Supply Pressure Unit Min. Max. kgf/cm²-g 4.2 8.0
8 Electric Connection Pneum. Connection 1/2” NPT (F) 1/4” NPT (F)
9 Power Failure Position FC
10 Line Size and Schedule Sch. Outlet Line Sch. 4 in STD 6" STD
PIPE
11 Line Class Rating Pipe Material B1A1 150# A106 GR.B, SMLS
LINE
12 Pipe Insulation Thickness Corrosion Allowance N N/A 1.6mm
13 Fluid State Phase Plant Air Gas/Vapor Single Phase
14 Sour Service Special Condition N/A N/A
15 Flow Rate Units Min. Nor. Max. Nm³/h 4923 4923 4923
16 Inlet Pressure Units Min. Nor. Max. kgf/cm²-g 6.924 6.81 5.652
17 Pressure Drop Units Min. Nor. Max. kgf/cm² 3.98 3.913 2.737
18 Inlet Temperature Units Min. Nor. Max. °C 40 40 40
PROCESS 19 Density Units Min. Nor. Max. kg/m³
CONDITIONS 20 Viscosity Units Min. Nor. Max. cP 0.019 0.019 0.019
21 Molecular Weight (MW) Specific Gravity @ Oper. 28.85
22 Spec. Heat Ratio (Cp/Cv) Compressibility (Z) 1.392 0.997
23 Vapor Pressure (Liq.) Cavitation or Flashing kgf/cm²-a N/A
24 Critical Pressure (Liq) Flash (wt%) kgf/cm²-a
25 Design Pressure Min. Max. kgf/cm²-g 10.5 kgf/cm²-g
26 Design Temperature Min. Max. 10 °C 343 °C
27 Max.Shutoff DP Solid % 10.5 kgf/cm²
28 Calculated Cv Units Min. Nor. Max. Cv 73.7 74.5 84.5
CALCULATED
29 Travel Units Min. Nor. Max. % 48 48 57
RESULTS
30 Noise dBA @1m Units Min. Nor. Max. dBA 75 75 74
31 MFR Model FISHER ED 56 MFR Model FISHER DVC6200F/SC-AD
32 Body Type Single Seat Globe 57 Signal: Inlet Outlet FF Protocol 0-2.8 kgf/cm2
33 Body Size Trim Size 3 in 3 7/16 in 58 Increase Signal Valve: DIRECT
34 End Connec.Size & Rating 3" 300# RF POSITIONER 59 Cam Characteristic LINEAR
35 Rated Cv Characteristic 90.42 Linear 60 Bypass Gauges N/A YES
36 Body Material WCC Steel 61 Signal Fail. to Valve FC
BODY 37 Bonnet Type Material Plain WCC Steel 62 Electric Enclosure Ex ia IIC T5 , NEMA 4X
AND 38 Flow Direct. Flow Act. To Up FTC 63 MFR Model N/A N/A
TRIM 39 Packing Type Material ISO Seal Graphite 64 Type Power N/A N/A
SOLENOID
40 Lubricator Isolat. Valve N/A N/A 65 When De-Enegr.Valve: N/A
VALVE
41 Guiding No. of Ports Cage 1 66 Material Latcher N/A N/A
42 Trim Type Internal Design Whisper I Balanced 67 Electric Enclosure N/A
43 Rated Travel Leak Class 1 1/2 in ANSI IV 68 MFR Model N/A N/A
44 Plug/ Ball/ Disk Material S41600 SST 69 Type Quantity N/A N/A
45 Seat Material S41600 SST SWITCHES 70 Contacts / Rating N/A
46 Cage Stem Material CB7Cu-1 SST S20910 SST 71 Switching Position N/A
47 Gasket Material S31600 SST/Graphite 72 Electric Enclosure N/A
48 MFR Model FISHER 667 73 MFR Model FISHER 67CFR
49 Type Diaphragm Spring Return AIR SET 74 Set Pressure 4.2 kgf/cm2-g
50 Size Stroke Time 70i < 10 Sec 75 Filter Gauge 5 Micron min YES
ACTUATOR 51 Air Failure Valve: FC 76 Vol. Tank Booster NO NO
52 Handwheel Location Side Mounted 77 Diffuser Lock-up NO NO
ACCESSORY
53 Mounting Position VERTICAL 78 Fire Safe Fireproof NO NO
54 Spring Range 1 - 1.9 kgf/cm2-g 79 Mech. Stop Quick Exa. NO NO
55 Include Pressure (Shutoff) 80 Hydro. Pressure YES
85 Vendor EMERSON 81 Leakage YES
PURCHASE TESTS
86 Manufacturer FISHER 82 Cryogenic N/A
87 Requisition No. R2B-P3-206-02-P-MR-00200 83 NACE Requirement N/A
88 Model No. ED 84 PWHT Requirement N/A
Notes:

INSTRUMENT SPECIFICATION - CONTROL VALVE


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S107.1 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Fieldbus Device Data Sheet
Tag No.: PV -21003
Fieldbus Tag No.:

Service : FA008 PA"TO FA001 TO FA002AB"

Basic Fieldbus Function Blocks Segment Information


Analog Input Block (AI) 1 Number Device:
1 22
20 Execution (msec)
Discrete Input Block (DI) 4 Number Segment #: DFJB-21031
2 23
15 Execution Time
3 Bias/Gain Station (BG) 0 Execution (msec) 24 LAS Capable: Yes No
Manual Loader (ML) 0 Number 25 Device Current Draw (mA): 19
4
0 Execution (msec) Device Minimum Voltage: 9.
26
Analog Output Block (AO) 1 Number Device Capacitance: 5 nF
5 20 Execution (msec) Polarity-sensitive: Yes No
27
Discrete Output Block (DO) 1 Number Segment Terminator Location:
6 20 Execution (msec)
28
7 Control Selector (CS)
DD Revision: 3
PID,PI,I Controller (PID) 29
8
20 Execution (msec)
CFF Revision: 1.9
Ratio Station (RA) 30
9
P,PD Controller (PD) 0 Number
10 0 Execution (msec)

* Execution time in msec.

Advanced Function Blocks Notes:

11 Device Control (DC)

12 Output Splitter (OS)

13 Signal Characterizer (SC)

14 Lead Lag (LL)

15 Deadtime (DT)

16 Integrator(Totalizer) (IT)

17 Setpoint Ramp Generator (SPG)

18 Input Selector (IS)

19 Arithmetic (AR)

20 Timer (TMR)

21 Analog Alarm (AAL)

INSTRUMENT SPECIFICATION -FOUNDATION FIELDBUS


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S107.2 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Tag Number : PV -21003

1. Startup only.

2. In-Built surge protector is provided by vendor.

1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S107.3 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
1 Tag No. PV -21043
2 Service PA TO SPE004
3 P&ID No. Line No. R2B-P3-206-02-A-DTI-00070 3"-AP-210075-T-A06T1-N
4 Area Classification Ingress Protection CLASS 1 DIV 2 Gr. B ,C&D, T3 NEMA 4X
GENERAL 5 Ambient Temperature: Unit Min. Max. °C 10 48
6 Allowable Sound dBA Tightness Requirement <85 ANSI IV (standard)
7 Available Air Supply Pressure Unit Min. Max. kgf/cm²-g 4.2 8.0
8 Electric Connection Pneum. Connection 1/2” NPT (F) 1/4” NPT (F)
9 Power Failure Position FO
10 Line Size and Schedule Sch. Outlet Line Sch. 3 in STD 3" STD
PIPE
11 Line Class Rating Pipe Material T-A06T1 150# A106 GR.B, SMLS
LINE
12 Pipe Insulation Thickness Corrosion Allowance N N/A 1.6mm
13 Fluid State Phase Plant Air Gas/Vapor Single Phase
14 Sour Service Special Condition N/A N/A
15 Flow Rate Units Min. Nor. Max. Nm³/h 559 559 670
16 Inlet Pressure Units Min. Nor. Max. kgf/cm²-g 7.99 7.49 6.99
17 Pressure Drop Units Min. Nor. Max. kgf/cm² 1.69 1.19 0.69
18 Inlet Temperature Units Min. Nor. Max. °C 40 40 40
PROCESS 19 Density Units Min. Nor. Max. kg/m³
CONDITIONS 20 Viscosity Units Min. Nor. Max. cP 0.019 0.019 0.019
21 Molecular Weight (MW) Specific Gravity @ Oper. 28.85
22 Spec. Heat Ratio (Cp/Cv) Compressibility (Z) 1.392 0.997
23 Vapor Pressure (Liq.) Cavitation or Flashing kgf/cm²-a N/A
24 Critical Pressure (Liq) Flash (wt%) kgf/cm²-a
25 Design Pressure Min. Max. kgf/cm²-g 10.5 kgf/cm²-g
26 Design Temperature Min. Max. 10 °C 80 °C
27 Max.Shutoff DP Solid % 10.5 kgf/cm²
28 Calculated Cv Units Min. Nor. Max. Cv 7.25 8.69 13.8
CALCULATED
29 Travel Units Min. Nor. Max. % 47 56 84
RESULTS
30 Noise dBA @1m Units Min. Nor. Max. dBA 66 63 59
31 MFR Model FISHER EZ 56 MFR Model FISHER DVC6200F/SC-AD
32 Body Type Single Seat Globe 57 Signal: Inlet Outlet FF Protocol 0-2.3 kgf/cm2
33 Body Size Trim Size 1.5 in 1 in 58 Increase Signal Valve: DIRECT
34 End Connec.Size & Rating 1.5" 300# RF POSITIONER 59 Cam Characteristic LINEAR
35 Rated Cv Characteristic 16.7 Linear 60 Bypass Gauges N/A YES
36 Body Material WCC Steel 61 Signal Fail. to Valve FO
BODY 37 Bonnet Type Material Plain WCC Steel 62 Electric Enclosure Ex ia IIC T5 , NEMA 4X
AND 38 Flow Direct. Flow Act. To Up FTO 63 MFR Model N/A N/A
TRIM 39 Packing Type Material Enviro Seal PTFE Carbon 64 Type Power N/A N/A
SOLENOID
40 Lubricator Isolat. Valve N/A N/A 65 When De-Enegr.Valve: N/A
VALVE
41 Guiding No. of Ports Post 1 66 Material Latcher N/A N/A
42 Trim Type Internal Design Standard Unbalanced 67 Electric Enclosure N/A
43 Rated Travel Leak Class 3/4 in ANSI IV 68 MFR Model N/A N/A
44 Plug/ Ball/ Disk Material S41600 SST 69 Type Quantity N/A N/A
45 Seat Material S41600 SST SWITCHES 70 Contacts / Rating N/A
46 Cage Stem Material N/A S31600 SST 71 Switching Position N/A
47 Gasket Material S31600 SST/Graphite 72 Electric Enclosure N/A
48 MFR Model FISHER 657 73 MFR Model FISHER 67CFR
49 Type Diaphragm Spring Return AIR SET 74 Set Pressure 4.2 kgf/cm2-g
50 Size Stroke Time 30i < 5 Sec 75 Filter Gauge 5 Micron min YES
ACTUATOR 51 Air Failure Valve: FO 76 Vol. Tank Booster NO NO
52 Handwheel Location N/A 77 Diffuser Lock-up NO NO
ACCESSORY
53 Mounting Position VERTICAL 78 Fire Safe Fireproof NO NO
54 Spring Range 0.6 - 1.7 kgf/cm2-g 79 Mech. Stop Quick Exa. NO NO
55 Include Pressure (Shutoff) 80 Hydro. Pressure YES
85 Vendor EMERSON 81 Leakage YES
PURCHASE TESTS
86 Manufacturer FISHER 82 Cryogenic N/A
87 Requisition No. R2B-P3-206-02-P-MR-00200 83 NACE Requirement N/A
88 Model No. EZ 84 PWHT Requirement N/A
Notes:

INSTRUMENT SPECIFICATION - CONTROL VALVE


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S108.1 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Fieldbus Device Data Sheet
Tag No.: PV -21043
Fieldbus Tag No.:

Service : PA TO SPE004

Basic Fieldbus Function Blocks Segment Information


Analog Input Block (AI) 1 Number Device:
1 22
20 Execution (msec)
Discrete Input Block (DI) 4 Number Segment #: DFJB-21016
2 23
15 Execution Time
3 Bias/Gain Station (BG) 0 Execution (msec) 24 LAS Capable: Yes No
Manual Loader (ML) 0 Number 25 Device Current Draw (mA): 19
4
0 Execution (msec) Device Minimum Voltage: 9.
26
Analog Output Block (AO) 1 Number Device Capacitance: 5 nF
5 20 Execution (msec) Polarity-sensitive: Yes No
27
Discrete Output Block (DO) 1 Number Segment Terminator Location:
6 20 Execution (msec)
28
7 Control Selector (CS)
DD Revision: 3
PID,PI,I Controller (PID) 29
8
20 Execution (msec)
CFF Revision: 1.9
Ratio Station (RA) 30
9
P,PD Controller (PD) 0 Number
10 0 Execution (msec)

* Execution time in msec.

Advanced Function Blocks Notes:

11 Device Control (DC)

12 Output Splitter (OS)

13 Signal Characterizer (SC)

14 Lead Lag (LL)

15 Deadtime (DT)

16 Integrator(Totalizer) (IT)

17 Setpoint Ramp Generator (SPG)

18 Input Selector (IS)

19 Arithmetic (AR)

20 Timer (TMR)

21 Analog Alarm (AAL)

INSTRUMENT SPECIFICATION -FOUNDATION FIELDBUS


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S108.2 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Tag Number : PV -21043

1. In-Built surge protector is provided by vendor.

1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S108.3 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
1 Tag No. PV -21044
2 Service MP STM TO FA003
3 P&ID No. Line No. R2B-P3-206-02-A-DTI-00069 8"-VM-210479-T-B04T1-EC
4 Area Classification Ingress Protection CLASS 1 DIV 2 Gr. B ,C&D, T3 NEMA 4X
GENERAL 5 Ambient Temperature: Unit Min. Max. °C 10 48
6 Allowable Sound dBA Tightness Requirement <85 ANSI IV (standard)
7 Available Air Supply Pressure Unit Min. Max. kgf/cm²-g 4.2 8.0
8 Electric Connection Pneum. Connection 1/2” NPT (F) 1/4” NPT (F)
9 Power Failure Position FO
10 Line Size and Schedule Sch. Outlet Line Sch. 8 in STD 8" STD
PIPE
11 Line Class Rating Pipe Material T-B04T1 300# A106 GR.B, SMLS
LINE
12 Pipe Insulation Thickness Corrosion Allowance EC 115mm 1.6mm
13 Fluid State Phase Steam Gas/Vapor Single Phase
14 Sour Service Special Condition N/A N/A
15 Flow Rate Units Min. Nor. Max. kg/h 9247 11277 13307
16 Inlet Pressure Units Min. Nor. Max. kgf/cm²-g 13.49 10.49 9.98
17 Pressure Drop Units Min. Nor. Max. kgf/cm² 7.18 4.17 3.65
18 Inlet Temperature Units Min. Nor. Max. °C 220 220 220
PROCESS 19 Density Units Min. Nor. Max. kg/m³
CONDITIONS 20 Viscosity Units Min. Nor. Max. cP 0.017 0.017 0.017
21 Molecular Weight (MW) Specific Gravity @ Oper. 18.02
22 Spec. Heat Ratio (Cp/Cv) Compressibility (Z) 1.238 0.947
23 Vapor Pressure (Liq.) Cavitation or Flashing kgf/cm²-a N/A
24 Critical Pressure (Liq) Flash (wt%) kgf/cm²-a
25 Design Pressure Min. Max. -1.033 kgf/cm²-g 15.5 kgf/cm²-g
26 Design Temperature Min. Max. 10 °C 260 °C
27 Max.Shutoff DP Solid % 15.5 kgf/cm²
28 Calculated Cv Units Min. Nor. Max. Cv 84.1 144 179
CALCULATED
29 Travel Units Min. Nor. Max. % 24 40 48
RESULTS
30 Noise dBA @1m Units Min. Nor. Max. dBA 80 81 82
31 MFR Model FISHER EWT 56 MFR Model FISHER DVC6200F/SC-AD
32 Body Type Single Seat Globe 57 Signal: Inlet Outlet FF Protocol 0-2.3 kgf/cm2
33 Body Size Trim Size 6 in 4 3/8 in 58 Increase Signal Valve: DIRECT
34 End Connec.Size & Rating 6" 300# RF POSITIONER 59 Cam Characteristic LINEAR
35 Rated Cv Characteristic 325 Linear 60 Bypass Gauges N/A YES
36 Body Material WCC Steel 61 Signal Fail. to Valve FO
BODY 37 Bonnet Type Material Style 1 Extension WCC Steel 62 Electric Enclosure Ex ia IIC T5 , NEMA 4X
AND 38 Flow Direct. Flow Act. To Up FTC 63 MFR Model N/A N/A
TRIM 39 Packing Type Material Enviro Seal Graphite ULF 64 Type Power N/A N/A
SOLENOID
40 Lubricator Isolat. Valve N/A N/A 65 When De-Enegr.Valve: N/A
VALVE
41 Guiding No. of Ports Cage 1 66 Material Latcher N/A N/A
42 Trim Type Internal Design Whisper I Balanced 67 Electric Enclosure N/A
43 Rated Travel Leak Class 2 in ANSI IV 68 MFR Model N/A N/A
44 Plug/ Ball/ Disk Material S41600 SST 69 Type Quantity N/A N/A
45 Seat Material S41600 SST SWITCHES 70 Contacts / Rating N/A
46 Cage Stem Material CB7Cu-1 SST S31600 SST 71 Switching Position N/A
47 Gasket Material S31600 SST/Graphite 72 Electric Enclosure N/A
48 MFR Model FISHER 657 73 MFR Model FISHER 67CFR
49 Type Diaphragm Spring Return AIR SET 74 Set Pressure 4.2 kgf/cm2-g
50 Size Stroke Time 45i < 10 Sec 75 Filter Gauge 5 Micron min YES
ACTUATOR 51 Air Failure Valve: FO 76 Vol. Tank Booster NO NO
52 Handwheel Location N/A 77 Diffuser Lock-up NO NO
ACCESSORY
53 Mounting Position VERTICAL 78 Fire Safe Fireproof NO NO
54 Spring Range 0.5 - 1.8 kgf/cm2-g 79 Mech. Stop Quick Exa. NO NO
55 Include Pressure (Shutoff) 80 Hydro. Pressure YES
85 Vendor EMERSON 81 Leakage YES
PURCHASE TESTS
86 Manufacturer FISHER 82 Cryogenic N/A
87 Requisition No. R2B-P3-206-02-P-MR-00200 83 NACE Requirement N/A
88 Model No. EWT 84 PWHT Requirement N/A
Notes:

INSTRUMENT SPECIFICATION - CONTROL VALVE


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S109.1 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Fieldbus Device Data Sheet
Tag No.: PV -21044
Fieldbus Tag No.:

Service : MP STM TO FA003

Basic Fieldbus Function Blocks Segment Information


Analog Input Block (AI) 1 Number Device:
1 22
20 Execution (msec)
Discrete Input Block (DI) 4 Number Segment #: DFJB-21015
2 23
15 Execution Time
3 Bias/Gain Station (BG) 0 Execution (msec) 24 LAS Capable: Yes No
Manual Loader (ML) 0 Number 25 Device Current Draw (mA): 19
4
0 Execution (msec) Device Minimum Voltage: 9.
26
Analog Output Block (AO) 1 Number Device Capacitance: 5 nF
5 20 Execution (msec) Polarity-sensitive: Yes No
27
Discrete Output Block (DO) 1 Number Segment Terminator Location:
6 20 Execution (msec)
28
7 Control Selector (CS)
DD Revision: 3
PID,PI,I Controller (PID) 29
8
20 Execution (msec)
CFF Revision: 1.9
Ratio Station (RA) 30
9
P,PD Controller (PD) 0 Number
10 0 Execution (msec)

* Execution time in msec.

Advanced Function Blocks Notes:

11 Device Control (DC)

12 Output Splitter (OS)

13 Signal Characterizer (SC)

14 Lead Lag (LL)

15 Deadtime (DT)

16 Integrator(Totalizer) (IT)

17 Setpoint Ramp Generator (SPG)

18 Input Selector (IS)

19 Arithmetic (AR)

20 Timer (TMR)

21 Analog Alarm (AAL)

INSTRUMENT SPECIFICATION -FOUNDATION FIELDBUS


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S109.2 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Tag Number : PV -21044

1. In-Built surge protector is provided by vendor.

1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S109.3 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
1 Tag No. PV -21045
2 Service N2 TO GAS
3 P&ID No. Line No. R2B-P3-206-02-A-DTI-00070 3"-GI-210367-T-A03T1-N
4 Area Classification Ingress Protection CLASS 1 DIV 2 Gr. B ,C&D, T3 NEMA 4X
GENERAL 5 Ambient Temperature: Unit Min. Max. °C 10 48
6 Allowable Sound dBA Tightness Requirement <85 ANSI IV (standard)
7 Available Air Supply Pressure Unit Min. Max. kgf/cm²-g 4.2 8.0
8 Electric Connection Pneum. Connection 1/2” NPT (F) 1/4” NPT (F)
9 Power Failure Position FO
10 Line Size and Schedule Sch. Outlet Line Sch. 3 in STD 3" STD
PIPE
11 Line Class Rating Pipe Material T-A03T1 150# A106 GR.B, SMLS
LINE
12 Pipe Insulation Thickness Corrosion Allowance N N/A 1.6mm
13 Fluid State Phase Nitrogen Gas/Vapor Single Phase
14 Sour Service Special Condition N/A N/A
15 Flow Rate Units Min. Nor. Max. Nm³/h 709 1418 2127
16 Inlet Pressure Units Min. Nor. Max. kgf/cm²-g 10.98 9.93 8.85
17 Pressure Drop Units Min. Nor. Max. kgf/cm² 4.68 3.63 2.54
18 Inlet Temperature Units Min. Nor. Max. °C 40 40 40
PROCESS 19 Density Units Min. Nor. Max. kg/m³
CONDITIONS 20 Viscosity Units Min. Nor. Max. cP 0.019 0.019 0.019
21 Molecular Weight (MW) Specific Gravity @ Oper. 28.01
22 Spec. Heat Ratio (Cp/Cv) Compressibility (Z) 1.391 0.997
23 Vapor Pressure (Liq.) Cavitation or Flashing kgf/cm²-a N/A
24 Critical Pressure (Liq) Flash (wt%) kgf/cm²-a
25 Design Pressure Min. Max. kgf/cm²-g 13 kgf/cm²-g
26 Design Temperature Min. Max. 10 °C 65 °C
27 Max.Shutoff DP Solid % 13 kgf/cm²
28 Calculated Cv Units Min. Nor. Max. Cv 5.33 12.4 22.8
CALCULATED
29 Travel Units Min. Nor. Max. % 19 40 76
RESULTS
30 Noise dBA @1m Units Min. Nor. Max. dBA 70 76 77
31 MFR Model FISHER ET 56 MFR Model FISHER DVC6200F/SC-AD
32 Body Type Single Seat Globe 57 Signal: Inlet Outlet FF Protocol 0-2.3 kgf/cm2
33 Body Size Trim Size 1.5 in 1 5/16 in 58 Increase Signal Valve: DIRECT
34 End Connec.Size & Rating 1.5" 300# RF POSITIONER 59 Cam Characteristic LINEAR
35 Rated Cv Characteristic 29.2 Linear 60 Bypass Gauges N/A YES
36 Body Material WCC Steel 61 Signal Fail. to Valve FO
BODY 37 Bonnet Type Material Plain WCC Steel 62 Electric Enclosure Ex ia IIC T5 , NEMA 4X
AND 38 Flow Direct. Flow Act. To Down FTO 63 MFR Model N/A N/A
TRIM 39 Packing Type Material Enviro Seal PTFE Carbon 64 Type Power N/A N/A
SOLENOID
40 Lubricator Isolat. Valve N/A N/A 65 When De-Enegr.Valve: N/A
VALVE
41 Guiding No. of Ports Cage 1 66 Material Latcher N/A N/A
42 Trim Type Internal Design Standard Balanced 67 Electric Enclosure N/A
43 Rated Travel Leak Class 3/4 in ANSI IV 68 MFR Model N/A N/A
44 Plug/ Ball/ Disk Material S41600 SST 69 Type Quantity N/A N/A
45 Seat Material S41600 SST SWITCHES 70 Contacts / Rating N/A
46 Cage Stem Material CB7Cu-1 SST S31600 SST 71 Switching Position N/A
47 Gasket Material S31600 SST/Graphite 72 Electric Enclosure N/A
48 MFR Model FISHER 657 73 MFR Model FISHER 67CFR
49 Type Diaphragm Spring Return AIR SET 74 Set Pressure 4.2 kgf/cm2-g
50 Size Stroke Time 30i < 5 Sec 75 Filter Gauge 5 Micron min YES
ACTUATOR 51 Air Failure Valve: FO 76 Vol. Tank Booster NO NO
52 Handwheel Location N/A 77 Diffuser Lock-up NO NO
ACCESSORY
53 Mounting Position VERTICAL 78 Fire Safe Fireproof NO NO
54 Spring Range 0.4 - 1.8 kgf/cm2-g 79 Mech. Stop Quick Exa. NO NO
55 Include Pressure (Shutoff) 80 Hydro. Pressure YES
85 Vendor EMERSON 81 Leakage YES
PURCHASE TESTS
86 Manufacturer FISHER 82 Cryogenic N/A
87 Requisition No. R2B-P3-206-02-P-MR-00200 83 NACE Requirement N/A
88 Model No. ET 84 PWHT Requirement N/A
Notes:

INSTRUMENT SPECIFICATION - CONTROL VALVE


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S110.1 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Fieldbus Device Data Sheet
Tag No.: PV -21045
Fieldbus Tag No.:

Service : N2 TO GAS

Basic Fieldbus Function Blocks Segment Information


Analog Input Block (AI) 1 Number Device:
1 22
20 Execution (msec)
Discrete Input Block (DI) 4 Number Segment #: DFJB-21015
2 23
15 Execution Time
3 Bias/Gain Station (BG) 0 Execution (msec) 24 LAS Capable: Yes No
Manual Loader (ML) 0 Number 25 Device Current Draw (mA): 19
4
0 Execution (msec) Device Minimum Voltage: 9.
26
Analog Output Block (AO) 1 Number Device Capacitance: 5 nF
5 20 Execution (msec) Polarity-sensitive: Yes No
27
Discrete Output Block (DO) 1 Number Segment Terminator Location:
6 20 Execution (msec)
28
7 Control Selector (CS)
DD Revision: 3
PID,PI,I Controller (PID) 29
8
20 Execution (msec)
CFF Revision: 1.9
Ratio Station (RA) 30
9
P,PD Controller (PD) 0 Number
10 0 Execution (msec)

* Execution time in msec.

Advanced Function Blocks Notes:

11 Device Control (DC)

12 Output Splitter (OS)

13 Signal Characterizer (SC)

14 Lead Lag (LL)

15 Deadtime (DT)

16 Integrator(Totalizer) (IT)

17 Setpoint Ramp Generator (SPG)

18 Input Selector (IS)

19 Arithmetic (AR)

20 Timer (TMR)

21 Analog Alarm (AAL)

INSTRUMENT SPECIFICATION -FOUNDATION FIELDBUS


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S110.2 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Tag Number : PV -21045

1. In-Built surge protector is provided by vendor.

1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S110.3 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
1 Tag No. PV -21046A
2 Service FA502 GAS TO GAS
3 P&ID No. Line No. R2B-P3-206-02-A-DTI-00070 1-1/2"-GD-212001-T-A03T1-N
4 Area Classification Ingress Protection CLASS 1 DIV 2 Gr. B ,C&D, T3 NEMA 4X
GENERAL 5 Ambient Temperature: Unit Min. Max. °C 10 48
6 Allowable Sound dBA Tightness Requirement <85 ANSI IV (standard)
7 Available Air Supply Pressure Unit Min. Max. kgf/cm²-g 4.2 8.0
8 Electric Connection Pneum. Connection 1/2” NPT (F) 1/4” NPT (F)
9 Power Failure Position FO
10 Line Size and Schedule Sch. Outlet Line Sch. 1-1/2 in XS 1.5" XS
PIPE
11 Line Class Rating Pipe Material T-A03T1 150# A106 GR.B, SMLS
LINE
12 Pipe Insulation Thickness Corrosion Allowance N N/A 3.2mm
13 Fluid State Phase Hydrocarbon Gas/Vapor Single Phase
14 Sour Service Special Condition N/A N/A
15 Flow Rate Units Min. Nor. Max. Nm³/h 147.5 337 402.6
16 Inlet Pressure Units Min. Nor. Max. kgf/cm²-g 10.44 10.41 10.24
17 Pressure Drop Units Min. Nor. Max. kgf/cm² 4.12 4.09 3.91
18 Inlet Temperature Units Min. Nor. Max. °C 37 37 37
PROCESS 19 Density Units Min. Nor. Max. kg/m³
CONDITIONS 20 Viscosity Units Min. Nor. Max. cP 0.01 0.01 0.01
21 Molecular Weight (MW) Specific Gravity @ Oper. 22.23
22 Spec. Heat Ratio (Cp/Cv) Compressibility (Z) 1.253 0.971
23 Vapor Pressure (Liq.) Cavitation or Flashing kgf/cm²-a N/A
24 Critical Pressure (Liq) Flash (wt%) kgf/cm²-a
25 Design Pressure Min. Max. kgf/cm²-g 9 kgf/cm²-g
26 Design Temperature Min. Max. 10 °C 70 °C
27 Max.Shutoff DP Solid % 9 kgf/cm²
28 Calculated Cv Units Min. Nor. Max. Cv 1.1 2.49 3.03
CALCULATED
29 Travel Units Min. Nor. Max. % 50 74 80
RESULTS
30 Noise dBA @1m Units Min. Nor. Max. dBA 52 60 62
31 MFR Model FISHER EZ 56 MFR Model FISHER DVC6200F/SC-AD
32 Body Type Single Seat Globe 57 Signal: Inlet Outlet FF Protocol 0-2.8 kgf/cm2
33 Body Size Trim Size 1 in 1/2 in 58 Increase Signal Valve: DIRECT
34 End Connec.Size & Rating 1" 300# RF POSITIONER 59 Cam Characteristic LINEAR
35 Rated Cv Characteristic 4.91 EQ% 60 Bypass Gauges N/A YES
36 Body Material WCC Steel 61 Signal Fail. to Valve FO
BODY 37 Bonnet Type Material Plain WCC Steel 62 Electric Enclosure Ex ia IIC T5 , NEMA 4X
AND 38 Flow Direct. Flow Act. To Up FTO 63 MFR Model N/A N/A
TRIM 39 Packing Type Material ISO Seal PTFE 64 Type Power N/A N/A
SOLENOID
40 Lubricator Isolat. Valve N/A N/A 65 When De-Enegr.Valve: N/A
VALVE
41 Guiding No. of Ports Post 1 66 Material Latcher N/A N/A
42 Trim Type Internal Design Micro Form Unbalanced 67 Electric Enclosure N/A
43 Rated Travel Leak Class 3/4 in ANSI IV 68 MFR Model N/A N/A
44 Plug/ Ball/ Disk Material S41600 SST 69 Type Quantity N/A N/A
45 Seat Material S41600 SST SWITCHES 70 Contacts / Rating N/A
46 Cage Stem Material N/A S31600 SST 71 Switching Position N/A
47 Gasket Material S31600 SST/Graphite 72 Electric Enclosure N/A
48 MFR Model FISHER 657 73 MFR Model FISHER 67CFR
49 Type Diaphragm Spring Return AIR SET 74 Set Pressure 4.2 kgf/cm2-g
50 Size Stroke Time 30i < 5 Sec 75 Filter Gauge 5 Micron min YES
ACTUATOR 51 Air Failure Valve: FO 76 Vol. Tank Booster NO NO
52 Handwheel Location N/A 77 Diffuser Lock-up NO NO
ACCESSORY
53 Mounting Position VERTICAL 78 Fire Safe Fireproof NO NO
54 Spring Range 0.4 - 2.4 kgf/cm2-g 79 Mech. Stop Quick Exa. NO NO
55 Include Pressure (Shutoff) 80 Hydro. Pressure YES
85 Vendor EMERSON 81 Leakage YES
PURCHASE TESTS
86 Manufacturer FISHER 82 Cryogenic N/A
87 Requisition No. R2B-P3-206-02-P-MR-00200 83 NACE Requirement N/A
88 Model No. EZ 84 PWHT Requirement N/A
Notes:

INSTRUMENT SPECIFICATION - CONTROL VALVE


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S111.1 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Fieldbus Device Data Sheet
Tag No.: PV -21046A
Fieldbus Tag No.:

Service : FA502 GAS TO GAS

Basic Fieldbus Function Blocks Segment Information


Analog Input Block (AI) 1 Number Device:
1 22
20 Execution (msec)
Discrete Input Block (DI) 4 Number Segment #: DFJB-21014
2 23
15 Execution Time
3 Bias/Gain Station (BG) 0 Execution (msec) 24 LAS Capable: Yes No
Manual Loader (ML) 0 Number 25 Device Current Draw (mA): 19
4
0 Execution (msec) Device Minimum Voltage: 9.
26
Analog Output Block (AO) 1 Number Device Capacitance: 5 nF
5 20 Execution (msec) Polarity-sensitive: Yes No
27
Discrete Output Block (DO) 1 Number Segment Terminator Location:
6 20 Execution (msec)
28
7 Control Selector (CS)
DD Revision: 3
PID,PI,I Controller (PID) 29
8
20 Execution (msec)
CFF Revision: 1.9
Ratio Station (RA) 30
9
P,PD Controller (PD) 0 Number
10 0 Execution (msec)

* Execution time in msec.

Advanced Function Blocks Notes:

11 Device Control (DC)

12 Output Splitter (OS)

13 Signal Characterizer (SC)

14 Lead Lag (LL)

15 Deadtime (DT)

16 Integrator(Totalizer) (IT)

17 Setpoint Ramp Generator (SPG)

18 Input Selector (IS)

19 Arithmetic (AR)

20 Timer (TMR)

21 Analog Alarm (AAL)

INSTRUMENT SPECIFICATION -FOUNDATION FIELDBUS


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S111.2 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Tag Number : PV -21046A

1. In-Built surge protector is provided by vendor.

1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S111.3 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
1 Tag No. PV -21046B
2 Service N2 TO GAS
3 P&ID No. Line No. R2B-P3-206-02-A-DTI-00070 2"-GI-210368-T-A03T1-N
4 Area Classification Ingress Protection CLASS 1 DIV 2 Gr. B ,C&D, T3 NEMA 4X
GENERAL 5 Ambient Temperature: Unit Min. Max. °C 10 48
6 Allowable Sound dBA Tightness Requirement <85 ANSI IV (standard)
7 Available Air Supply Pressure Unit Min. Max. kgf/cm²-g 4.2 8.0
8 Electric Connection Pneum. Connection 1/2” NPT (F) 1/4” NPT (F)
9 Power Failure Position FC
10 Line Size and Schedule Sch. Outlet Line Sch. 2 in XS 1.5" XS
PIPE
11 Line Class Rating Pipe Material T-A03T1 150# A106 GR.B, SMLS
LINE
12 Pipe Insulation Thickness Corrosion Allowance N N/A 1.6mm
13 Fluid State Phase Nitrogen Gas/Vapor Single Phase
14 Sour Service Special Condition N/A N/A
15 Flow Rate Units Min. Nor. Max. Nm³/h 305 305 366
16 Inlet Pressure Units Min. Nor. Max. kgf/cm²-g 10.83 9.79 8.66
17 Pressure Drop Units Min. Nor. Max. kgf/cm² 4.51 3.47 2.33
18 Inlet Temperature Units Min. Nor. Max. °C 40 40 40
PROCESS 19 Density Units Min. Nor. Max. kg/m³
CONDITIONS 20 Viscosity Units Min. Nor. Max. cP 0.019 0.019 0.019
21 Molecular Weight (MW) Specific Gravity @ Oper. 28.01
22 Spec. Heat Ratio (Cp/Cv) Compressibility (Z) 1.392 0.997
23 Vapor Pressure (Liq.) Cavitation or Flashing kgf/cm²-a N/A
24 Critical Pressure (Liq) Flash (wt%) kgf/cm²-a
25 Design Pressure Min. Max. kgf/cm²-g 13 kgf/cm²-g
26 Design Temperature Min. Max. 10 °C 65 °C
27 Max.Shutoff DP Solid % 13 kgf/cm²
28 Calculated Cv Units Min. Nor. Max. Cv 2.38 2.73 3.99
CALCULATED
29 Travel Units Min. Nor. Max. % 73 77 88
RESULTS
30 Noise dBA @1m Units Min. Nor. Max. dBA 61 60 58
31 MFR Model FISHER EZ 56 MFR Model FISHER DVC6200F/SC-AD
32 Body Type Single Seat Globe 57 Signal: Inlet Outlet FF Protocol 0-2.8 kgf/cm2
33 Body Size Trim Size 1 in 1/2 in 58 Increase Signal Valve: DIRECT
34 End Connec.Size & Rating 1" 300# RF POSITIONER 59 Cam Characteristic LINEAR
35 Rated Cv Characteristic 4.91 EQ% 60 Bypass Gauges N/A YES
36 Body Material WCC Steel 61 Signal Fail. to Valve FC
BODY 37 Bonnet Type Material Plain WCC Steel 62 Electric Enclosure Ex ia IIC T5 , NEMA 4X
AND 38 Flow Direct. Flow Act. To Up FTO 63 MFR Model N/A N/A
TRIM 39 Packing Type Material Enviro Seal PTFE Carbon 64 Type Power N/A N/A
SOLENOID
40 Lubricator Isolat. Valve N/A N/A 65 When De-Enegr.Valve: N/A
VALVE
41 Guiding No. of Ports Post 1 66 Material Latcher N/A N/A
42 Trim Type Internal Design Micro Form Unbalanced 67 Electric Enclosure N/A
43 Rated Travel Leak Class 3/4 in ANSI IV 68 MFR Model N/A N/A
44 Plug/ Ball/ Disk Material S41600 SST 69 Type Quantity N/A N/A
45 Seat Material S41600 SST SWITCHES 70 Contacts / Rating N/A
46 Cage Stem Material N/A S31600 SST 71 Switching Position N/A
47 Gasket Material S31600 SST/Graphite 72 Electric Enclosure N/A
48 MFR Model FISHER 667 73 MFR Model FISHER 67CFR
49 Type Diaphragm Spring Return AIR SET 74 Set Pressure 4.2 kgf/cm2-g
50 Size Stroke Time 30i < 5 Sec 75 Filter Gauge 5 Micron min YES
ACTUATOR 51 Air Failure Valve: FC 76 Vol. Tank Booster NO NO
52 Handwheel Location N/A 77 Diffuser Lock-up NO NO
ACCESSORY
53 Mounting Position VERTICAL 78 Fire Safe Fireproof NO NO
54 Spring Range 0.8 - 2.5 kgf/cm2-g 79 Mech. Stop Quick Exa. NO NO
55 Include Pressure (Shutoff) 80 Hydro. Pressure YES
85 Vendor EMERSON 81 Leakage YES
PURCHASE TESTS
86 Manufacturer FISHER 82 Cryogenic N/A
87 Requisition No. R2B-P3-206-02-P-MR-00200 83 NACE Requirement N/A
88 Model No. EZ 84 PWHT Requirement N/A
Notes:

INSTRUMENT SPECIFICATION - CONTROL VALVE


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S112.1 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Fieldbus Device Data Sheet
Tag No.: PV -21046B
Fieldbus Tag No.:

Service : N2 TO GAS

Basic Fieldbus Function Blocks Segment Information


Analog Input Block (AI) 1 Number Device:
1 22
20 Execution (msec)
Discrete Input Block (DI) 4 Number Segment #: DFJB-21014
2 23
15 Execution Time
3 Bias/Gain Station (BG) 0 Execution (msec) 24 LAS Capable: Yes No
Manual Loader (ML) 0 Number 25 Device Current Draw (mA): 19
4
0 Execution (msec) Device Minimum Voltage: 9.
26
Analog Output Block (AO) 1 Number Device Capacitance: 5 nF
5 20 Execution (msec) Polarity-sensitive: Yes No
27
Discrete Output Block (DO) 1 Number Segment Terminator Location:
6 20 Execution (msec)
28
7 Control Selector (CS)
DD Revision: 3
PID,PI,I Controller (PID) 29
8
20 Execution (msec)
CFF Revision: 1.9
Ratio Station (RA) 30
9
P,PD Controller (PD) 0 Number
10 0 Execution (msec)

* Execution time in msec.

Advanced Function Blocks Notes:

11 Device Control (DC)

12 Output Splitter (OS)

13 Signal Characterizer (SC)

14 Lead Lag (LL)

15 Deadtime (DT)

16 Integrator(Totalizer) (IT)

17 Setpoint Ramp Generator (SPG)

18 Input Selector (IS)

19 Arithmetic (AR)

20 Timer (TMR)

21 Analog Alarm (AAL)

INSTRUMENT SPECIFICATION -FOUNDATION FIELDBUS


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S112.2 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Tag Number : PV -21046B

1. In-Built surge protector is provided by vendor.

1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S112.3 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
1 Tag No. PV -21073
2 Service FA104 HP STM TO MP STM
3 P&ID No. Line No. R2B-P3-206-02-A-DTI-00074 8"-VA-210600-T-D61T1S-EC
4 Area Classification Ingress Protection CLASS 1 DIV 2 Gr. B ,C&D, T3 NEMA 4X
GENERAL 5 Ambient Temperature: Unit Min. Max. °C 10 48
6 Allowable Sound dBA Tightness Requirement <85 ANSI IV (standard)
7 Available Air Supply Pressure Unit Min. Max. kgf/cm²-g 4.2 8.0
8 Electric Connection Pneum. Connection 1/2” NPT (F) 1/4” NPT (F)
9 Power Failure Position FC
10 Line Size and Schedule Sch. Outlet Line Sch. 8 in XS 16" 80
PIPE
11 Line Class Rating Pipe Material T-D61T1S 600# SA106 GR.B, SMLS
LINE
12 Pipe Insulation Thickness Corrosion Allowance EC 125mm 1.6mm
13 Fluid State Phase Steam Gas/Vapor Single Phase
14 Sour Service Special Condition N/A N/A
15 Flow Rate Units Min. Nor. Max. kg/h 20204 40408 48489
16 Inlet Pressure Units Min. Nor. Max. kgf/cm²-g 49.7 49.68 44.2
17 Pressure Drop Units Min. Nor. Max. kgf/cm² 39.65 38.97 34.16
18 Inlet Temperature Units Min. Nor. Max. °C 264 264 264
PROCESS 19 Density Units Min. Nor. Max. kg/m³
CONDITIONS 20 Viscosity Units Min. Nor. Max. cP 0.1016 0.1016 0.1016
21 Molecular Weight (MW) Specific Gravity @ Oper. 18.02
22 Spec. Heat Ratio (Cp/Cv) Compressibility (Z) 1.125 0.797
23 Vapor Pressure (Liq.) Cavitation or Flashing kgf/cm²-a N/A
24 Critical Pressure (Liq) Flash (wt%) kgf/cm²-a
25 Design Pressure Min. Max. -1.033 kgf/cm²-g 55.5 kgf/cm²-g
26 Design Temperature Min. Max. 10 °C 290 °C
27 Max.Shutoff DP Solid % 55.5 kgf/cm²
28 Calculated Cv Units Min. Nor. Max. Cv 38.9 77.9 105
CALCULATED
29 Travel Units Min. Nor. Max. % 22 45 59
RESULTS
30 Noise dBA @1m Units Min. Nor. Max. dBA 78 81 82
31 MFR Model FISHER EWT 56 MFR Model FISHER DVC6200F/SC-AD
32 Body Type Single Seat Globe 57 Signal: Inlet Outlet FF Protocol 0-2.8 kgf/cm2
33 Body Size Trim Size 6 in 4 3/8 in 58 Increase Signal Valve: DIRECT
34 End Connec.Size & Rating 6" 600# RF POSITIONER 59 Cam Characteristic LINEAR
35 Rated Cv Characteristic 155.8 Linear 60 Bypass Gauges N/A YES
36 Body Material WCC Steel 61 Signal Fail. to Valve FC
BODY 37 Bonnet Type Material Plain WCC Steel 62 Electric Enclosure Ex ia IIC T5 , NEMA 4X
AND 38 Flow Direct. Flow Act. To Up FTC 63 MFR Model N/A N/A
TRIM 39 Packing Type Material Enviro Seal Graphite ULF 64 Type Power N/A N/A
SOLENOID
40 Lubricator Isolat. Valve N/A N/A 65 When De-Enegr.Valve: N/A
VALVE
41 Guiding No. of Ports Cage 1 66 Material Latcher N/A N/A
42 Trim Type Internal Design Whisper III Balanced 67 Electric Enclosure N/A
43 Rated Travel Leak Class 1 3/4 in ANSI IV 68 MFR Model N/A N/A
44 Plug/ Ball/ Disk Material S31600 SST/CoCr-A Seat 69 Type Quantity N/A N/A
45 Seat Material R30006 Cobalt Alloy SWITCHES 70 Contacts / Rating N/A
46 Cage Stem Material CB7Cu-1 SST S31600 SST 71 Switching Position N/A
47 Gasket Material S31600 SST/Graphite 72 Electric Enclosure N/A
48 MFR Model FISHER 667 73 MFR Model FISHER 67CFR
49 Type Diaphragm Spring Return AIR SET 74 Set Pressure 4.2 kgf/cm2-g
50 Size Stroke Time 45i < 10 Sec 75 Filter Gauge 5 Micron min YES
ACTUATOR 51 Air Failure Valve: FC 76 Vol. Tank Booster NO NO
52 Handwheel Location N/A 77 Diffuser Lock-up NO NO
ACCESSORY
53 Mounting Position VERTICAL 78 Fire Safe Fireproof NO NO
54 Spring Range 0.6 - 2.4 kgf/cm2-g 79 Mech. Stop Quick Exa. NO NO
55 Include Pressure (Shutoff) 80 Hydro. Pressure YES
85 Vendor EMERSON 81 Leakage YES
PURCHASE TESTS
86 Manufacturer FISHER 82 Cryogenic N/A
87 Requisition No. R2B-P3-206-02-P-MR-00200 83 NACE Requirement N/A
88 Model No. EWT 84 PWHT Requirement N/A
Notes:

INSTRUMENT SPECIFICATION - CONTROL VALVE


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S113.1 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Fieldbus Device Data Sheet
Tag No.: PV -21073
Fieldbus Tag No.:

Service : FA104 HP STM TO MP STM

Basic Fieldbus Function Blocks Segment Information


Analog Input Block (AI) 1 Number Device:
1 22
20 Execution (msec)
Discrete Input Block (DI) 4 Number Segment #: DFJB-21004
2 23
15 Execution Time
3 Bias/Gain Station (BG) 0 Execution (msec) 24 LAS Capable: Yes No
Manual Loader (ML) 0 Number 25 Device Current Draw (mA): 19
4
0 Execution (msec) Device Minimum Voltage: 9.
26
Analog Output Block (AO) 1 Number Device Capacitance: 5 nF
5 20 Execution (msec) Polarity-sensitive: Yes No
27
Discrete Output Block (DO) 1 Number Segment Terminator Location:
6 20 Execution (msec)
28
7 Control Selector (CS)
DD Revision: 3
PID,PI,I Controller (PID) 29
8
20 Execution (msec)
CFF Revision: 1.9
Ratio Station (RA) 30
9
P,PD Controller (PD) 0 Number
10 0 Execution (msec)

* Execution time in msec.

Advanced Function Blocks Notes:

11 Device Control (DC)

12 Output Splitter (OS)

13 Signal Characterizer (SC)

14 Lead Lag (LL)

15 Deadtime (DT)

16 Integrator(Totalizer) (IT)

17 Setpoint Ramp Generator (SPG)

18 Input Selector (IS)

19 Arithmetic (AR)

20 Timer (TMR)

21 Analog Alarm (AAL)

INSTRUMENT SPECIFICATION -FOUNDATION FIELDBUS


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S113.2 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Tag Number : PV -21073

1. In-Built surge protector is provided by vendor.

1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S113.3 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
1 Tag No. PV -21200A
2 Service FG TO FA203
3 P&ID No. Line No. R2B-P3-206-02-A-DTI-00201 1"-GD-212002-T-A03T1-N
4 Area Classification Ingress Protection CLASS 1 DIV 2 Gr. B ,C&D, T3 NEMA 4X
GENERAL 5 Ambient Temperature: Unit Min. Max. °C 10 48
6 Allowable Sound dBA Tightness Requirement <85 ANSI IV (standard)
7 Available Air Supply Pressure Unit Min. Max. kgf/cm²-g 4.2 8.0
8 Electric Connection Pneum. Connection 1/2” NPT (F) 1/4” NPT (F)
9 Power Failure Position FC
10 Line Size and Schedule Sch. Outlet Line Sch. 1 in XS 1" XS
PIPE
11 Line Class Rating Pipe Material T-A03T1 150# A106 GR.B, SMLS
LINE
12 Pipe Insulation Thickness Corrosion Allowance N N/A 1.6mm
13 Fluid State Phase Hydrocarbon Gas/Vapor Single Phase
14 Sour Service Special Condition N/A N/A
15 Flow Rate Units Min. Nor. Max. Nm³/h 34 34 37.4
16 Inlet Pressure Units Min. Nor. Max. kgf/cm²-g 5 4.5 4
17 Pressure Drop Units Min. Nor. Max. kgf/cm² 4.3 3.8 3.3
18 Inlet Temperature Units Min. Nor. Max. °C 38 38 38
PROCESS 19 Density Units Min. Nor. Max. kg/m³
CONDITIONS 20 Viscosity Units Min. Nor. Max. cP 0.01 0.01 0.01
21 Molecular Weight (MW) Specific Gravity @ Oper. 19.32
22 Spec. Heat Ratio (Cp/Cv) Compressibility (Z) 1.241 0.99
23 Vapor Pressure (Liq.) Cavitation or Flashing kgf/cm²-a N/A
24 Critical Pressure (Liq) Flash (wt%) kgf/cm²-a
25 Design Pressure Min. Max. kgf/cm²-g 9 kgf/cm²-g
26 Design Temperature Min. Max. 10 °C 70 °C
27 Max.Shutoff DP Solid % 9 kgf/cm²
28 Calculated Cv Units Min. Nor. Max. 0.431
Cv 0.469 0.562
CALCULATED
29 Travel Units Min. Nor. Max. %70 72 78
RESULTS
30 Noise dBA @1m Units Min. Nor. Max. 50
dBA 50 50
31 MFR Model FISHER EZ 56 MFR Model FISHER DVC6200F/SC-AD
32 Body Type Single Seat Globe 57 Signal: Inlet Outlet FF Protocol 0-2.8 kgf/cm2
33 Body Size Trim Size 1 in 1/4 in 58 Increase Signal Valve: DIRECT
34 End Connec.Size & Rating 1" 300# RF POSITIONER 59 Cam Characteristic LINEAR
35 Rated Cv Characteristic 1.07 EQ% 60 Bypass Gauges N/A YES
36 Body Material WCC Steel 61 Signal Fail. to Valve FC
BODY 37 Bonnet Type Material Plain WCC Steel 62 Electric Enclosure Ex ia IIC T5 , NEMA 4X
AND 38 Flow Direct. Flow Act. To Up FTO 63 MFR Model N/A N/A
TRIM 39 Packing Type Material ISO Seal PTFE 64 Type Power N/A N/A
SOLENOID
40 Lubricator Isolat. Valve N/A N/A 65 When De-Enegr.Valve: N/A
VALVE
41 Guiding No. of Ports Port 1 66 Material Latcher N/A N/A
42 Trim Type Internal Design Micro Flute Unbalanced 67 Electric Enclosure N/A
43 Rated Travel Leak Class 3/4 in ANSI IV 68 MFR Model N/A N/A
44 Plug/ Ball/ Disk Material S41600 SST 69 Type Quantity N/A N/A
45 Seat Material S41600 SST SWITCHES 70 Contacts / Rating N/A
46 Cage Stem Material N/A S31600 SST 71 Switching Position N/A
47 Gasket Material S31600 SST/Graphite 72 Electric Enclosure N/A
48 MFR Model FISHER 667 73 MFR Model FISHER 67CFR
49 Type Diaphragm Spring Return AIR SET 74 Set Pressure 4.2 kgf/cm2-g
50 Size Stroke Time 30i < 5 Sec 75 Filter Gauge 5 Micron min YES
ACTUATOR 51 Air Failure Valve: FC 76 Vol. Tank Booster NO NO
52 Handwheel Location N/A 77 Diffuser Lock-up NO NO
ACCESSORY
53 Mounting Position VERTICAL 78 Fire Safe Fireproof NO NO
54 Spring Range 0.8 - 2.5 kgf/cm2-g 79 Mech. Stop Quick Exa. NO NO
55 Include Pressure (Shutoff) 80 Hydro. Pressure YES
85 Vendor EMERSON 81 Leakage YES
PURCHASE TESTS
86 Manufacturer FISHER 82 Cryogenic N/A
87 Requisition No. R2B-P3-206-02-P-MR-00200 83 NACE Requirement N/A
88 Model No. EZ 84 PWHT Requirement N/A
Notes:

INSTRUMENT SPECIFICATION - CONTROL VALVE


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S114.1 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Fieldbus Device Data Sheet
Tag No.: PV -21200A
Fieldbus Tag No.:

Service : FG TO FA203

Basic Fieldbus Function Blocks Segment Information


Analog Input Block (AI) 1 Number Device:
1 22
20 Execution (msec)
Discrete Input Block (DI) 4 Number Segment #: DFJB-21124
2 23
15 Execution Time
3 Bias/Gain Station (BG) 0 Execution (msec) 24 LAS Capable: Yes No
Manual Loader (ML) 0 Number 25 Device Current Draw (mA): 19
4
0 Execution (msec) Device Minimum Voltage: 9.
26
Analog Output Block (AO) 1 Number Device Capacitance: 5 nF
5 20 Execution (msec) Polarity-sensitive: Yes No
27
Discrete Output Block (DO) 1 Number Segment Terminator Location:
6 20 Execution (msec)
28
7 Control Selector (CS)
DD Revision: 3
PID,PI,I Controller (PID) 29
8
20 Execution (msec)
CFF Revision: 1.9
Ratio Station (RA) 30
9
P,PD Controller (PD) 0 Number
10 0 Execution (msec)

* Execution time in msec.

Advanced Function Blocks Notes:

11 Device Control (DC)

12 Output Splitter (OS)

13 Signal Characterizer (SC)

14 Lead Lag (LL)

15 Deadtime (DT)

16 Integrator(Totalizer) (IT)

17 Setpoint Ramp Generator (SPG)

18 Input Selector (IS)

19 Arithmetic (AR)

20 Timer (TMR)

21 Analog Alarm (AAL)

INSTRUMENT SPECIFICATION -FOUNDATION FIELDBUS


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S114.2 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Tag Number : PV -21200A

1. In-Built surge protector is provided by vendor.

1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S114.3 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
1 Tag No. PV -21200B
2 Service FA203 FG TO FLR HEAD
3 P&ID No. Line No. R2B-P3-206-02-A-DTI-00201 1"-P-212116-B1A1-N
4 Area Classification Ingress Protection CLASS 1 DIV 2 Gr. B ,C&D, T3 NEMA 4X
GENERAL 5 Ambient Temperature: Unit Min. Max. °C 10 48
6 Allowable Sound dBA Tightness Requirement <85 ANSI IV (standard)
7 Available Air Supply Pressure Unit Min. Max. kgf/cm²-g 4.2 8.0
8 Electric Connection Pneum. Connection 1/2” NPT (F) 1/4” NPT (F)
9 Power Failure Position FC
10 Line Size and Schedule Sch. Outlet Line Sch. 1 in XS 1" XS
PIPE
11 Line Class Rating Pipe Material B1A1 150# A106 GR.B, SMLS
LINE
12 Pipe Insulation Thickness Corrosion Allowance N N/A 1.6mm
13 Fluid State Phase Hydrocarbon Gas/Vapor Single Phase
14 Sour Service Special Condition N/A N/A
15 Flow Rate Units Min. Nor. Max. Nm³/h 35 35 35
16 Inlet Pressure Units Min. Nor. Max. kgf/cm²-g 0.7 0.7 0.7
17 Pressure Drop Units Min. Nor. Max. kgf/cm² 0.5 0.5 0.5
18 Inlet Temperature Units Min. Nor. Max. °C 50 50 50
PROCESS 19 Density Units Min. Nor. Max. kg/m³
CONDITIONS 20 Viscosity Units Min. Nor. Max. cP 0.01 0.01 0.01
21 Molecular Weight (MW) Specific Gravity @ Oper. 19.32
22 Spec. Heat Ratio (Cp/Cv) Compressibility (Z) 1.241 0.99
23 Vapor Pressure (Liq.) Cavitation or Flashing kgf/cm²-a N/A
24 Critical Pressure (Liq) Flash (wt%) kgf/cm²-a
25 Design Pressure Min. Max. kgf/cm²-g 3.5 kgf/cm²-g
26 Design Temperature Min. Max. 10 °C 120 °C
27 Max.Shutoff DP Solid % 3.5 kgf/cm²
28 Calculated Cv Units Min. Nor. Max. Cv 1.74 1.74 1.74
CALCULATED
29 Travel Units Min. Nor. Max. % 64 64 64
RESULTS
30 Noise dBA @1m Units Min. Nor. Max. dBA 50 50 50
31 MFR Model FISHER EZ 56 MFR Model FISHER DVC6200F/SC-AD
32 Body Type Single Seat Globe 57 Signal: Inlet Outlet FF Protocol 0-2.8 kgf/cm2
33 Body Size Trim Size 1 in 1/2 in 58 Increase Signal Valve: DIRECT
34 End Connec.Size & Rating 1" 300# RF POSITIONER 59 Cam Characteristic LINEAR
35 Rated Cv Characteristic 4.91 EQ% 60 Bypass Gauges N/A YES
36 Body Material WCC Steel 61 Signal Fail. to Valve FC
BODY 37 Bonnet Type Material Plain WCC Steel 62 Electric Enclosure Ex ia IIC T5 , NEMA 4X
AND 38 Flow Direct. Flow Act. To Up FTO 63 MFR Model N/A N/A
TRIM 39 Packing Type Material ISO Seal PTFE 64 Type Power N/A N/A
SOLENOID
40 Lubricator Isolat. Valve N/A N/A 65 When De-Enegr.Valve: N/A
VALVE
41 Guiding No. of Ports Post 1 66 Material Latcher N/A N/A
42 Trim Type Internal Design Micro Form Unbalanced 67 Electric Enclosure N/A
43 Rated Travel Leak Class 3/4 in ANSI IV 68 MFR Model N/A N/A
44 Plug/ Ball/ Disk Material S41600 SST 69 Type Quantity N/A N/A
45 Seat Material S41600 SST SWITCHES 70 Contacts / Rating N/A
46 Cage Stem Material N/A S31600 SST 71 Switching Position N/A
47 Gasket Material S31600 SST/Graphite 72 Electric Enclosure N/A
48 MFR Model FISHER 667 73 MFR Model FISHER 67CFR
49 Type Diaphragm Spring Return AIR SET 74 Set Pressure 4.2 kgf/cm2-g
50 Size Stroke Time 30i < 5 Sec 75 Filter Gauge 5 Micron min YES
ACTUATOR 51 Air Failure Valve: FC 76 Vol. Tank Booster NO NO
52 Handwheel Location N/A 77 Diffuser Lock-up NO NO
ACCESSORY
53 Mounting Position VERTICAL 78 Fire Safe Fireproof NO NO
54 Spring Range 0.8 - 2.5 kgf/cm2-g 79 Mech. Stop Quick Exa. NO NO
55 Include Pressure (Shutoff) 80 Hydro. Pressure YES
85 Vendor EMERSON 81 Leakage YES
PURCHASE TESTS
86 Manufacturer FISHER 82 Cryogenic N/A
87 Requisition No. R2B-P3-206-02-P-MR-00200 83 NACE Requirement N/A
88 Model No. EZ 84 PWHT Requirement N/A
Notes:

INSTRUMENT SPECIFICATION - CONTROL VALVE


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S115.1 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Fieldbus Device Data Sheet
Tag No.: PV -21200B
Fieldbus Tag No.:

Service : FA203 FG TO FLR HEAD

Basic Fieldbus Function Blocks Segment Information


Analog Input Block (AI) 1 Number Device:
1 22
20 Execution (msec)
Discrete Input Block (DI) 4 Number Segment #: DFJB-21124
2 23
15 Execution Time
3 Bias/Gain Station (BG) 0 Execution (msec) 24 LAS Capable: Yes No
Manual Loader (ML) 0 Number 25 Device Current Draw (mA): 19
4
0 Execution (msec) Device Minimum Voltage: 9.
26
Analog Output Block (AO) 1 Number Device Capacitance: 5 nF
5 20 Execution (msec) Polarity-sensitive: Yes No
27
Discrete Output Block (DO) 1 Number Segment Terminator Location:
6 20 Execution (msec)
28
7 Control Selector (CS)
DD Revision: 3
PID,PI,I Controller (PID) 29
8
20 Execution (msec)
CFF Revision: 1.9
Ratio Station (RA) 30
9
P,PD Controller (PD) 0 Number
10 0 Execution (msec)

* Execution time in msec.

Advanced Function Blocks Notes:

11 Device Control (DC)

12 Output Splitter (OS)

13 Signal Characterizer (SC)

14 Lead Lag (LL)

15 Deadtime (DT)

16 Integrator(Totalizer) (IT)

17 Setpoint Ramp Generator (SPG)

18 Input Selector (IS)

19 Arithmetic (AR)

20 Timer (TMR)

21 Analog Alarm (AAL)

INSTRUMENT SPECIFICATION -FOUNDATION FIELDBUS


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S115.2 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Tag Number : PV -21200B

1. In-Built surge protector is provided by vendor.

1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S115.3 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
1 Tag No. PV -21408
2 Service FA402 OG TO EA202AB
3 P&ID No. Line No. R2B-P3-206-02-A-DTI-00408 1-1/2"-P-214235-B2A1-N
4 Area Classification Ingress Protection CLASS 1 DIV 2 Gr. B ,C&D, T3 NEMA 4X
GENERAL 5 Ambient Temperature: Unit Min. Max. °C 10 48
6 Allowable Sound dBA Tightness Requirement <85 ANSI IV (standard)
7 Available Air Supply Pressure Unit Min. Max. kgf/cm²-g 4.2 8.0
8 Electric Connection Pneum. Connection 1/2” NPT (F) 1/4” NPT (F)
9 Power Failure Position FC
10 Line Size and Schedule Sch. Outlet Line Sch. 1-1/2 in XS 1.5" XS
PIPE
11 Line Class Rating Pipe Material B2A1 300# A106 GR.B, SMLS
LINE
12 Pipe Insulation Thickness Corrosion Allowance N N/A 1.6mm
13 Fluid State Phase Hydrocarbon Gas/Vapor Single Phase
14 Sour Service Special Condition N/A N/A
15 Flow Rate Units Min. Nor. Max. Nm³/h 58 192 212
16 Inlet Pressure Units Min. Nor. Max. kgf/cm²-g 22.83 22.69 22.65
17 Pressure Drop Units Min. Nor. Max. kgf/cm² 8.34 5.9 4.056
18 Inlet Temperature Units Min. Nor. Max. °C 37 37 37
PROCESS 19 Density Units Min. Nor. Max. kg/m³
CONDITIONS 20 Viscosity Units Min. Nor. Max. cP 0.009 0.009 0.009
21 Molecular Weight (MW) Specific Gravity @ Oper. 36.82
22 Spec. Heat Ratio (Cp/Cv) Compressibility (Z) 1.097 0.696
23 Vapor Pressure (Liq.) Cavitation or Flashing kgf/cm²-a N/A
24 Critical Pressure (Liq) Flash (wt%) kgf/cm²-a
25 Design Pressure Min. Max. kgf/cm²-g 26.5 kgf/cm²-g
26 Design Temperature Min. Max. 10 °C 120 °C
27 Max.Shutoff DP Solid % 26.5 kgf/cm²
28 Calculated Cv Units Min. Nor. Max. Cv 0.229 0.847 1.06
CALCULATED
29 Travel Units Min. Nor. Max. % 39 79 85
RESULTS
30 Noise dBA @1m Units Min. Nor. Max. dBA 50 56 53
31 MFR Model FISHER EZ 56 MFR Model FISHER DVC6200F/SC-AD
32 Body Type Single Seat Globe 57 Signal: Inlet Outlet FF Protocol 0-2.8 kgf/cm2
33 Body Size Trim Size 1 in 1/4 in 58 Increase Signal Valve: DIRECT
34 End Connec.Size & Rating 1" 300# RF POSITIONER 59 Cam Characteristic LINEAR
35 Rated Cv Characteristic 1.52 EQ% 60 Bypass Gauges N/A YES
36 Body Material WCC Steel 61 Signal Fail. to Valve FC
BODY 37 Bonnet Type Material Plain WCC Steel 62 Electric Enclosure Ex ia IIC T5 , NEMA 4X
AND 38 Flow Direct. Flow Act. To Up FTO 63 MFR Model N/A N/A
TRIM 39 Packing Type Material ISO Seal PTFE 64 Type Power N/A N/A
SOLENOID
40 Lubricator Isolat. Valve N/A N/A 65 When De-Enegr.Valve: N/A
VALVE
41 Guiding No. of Ports Post 1 66 Material Latcher N/A N/A
42 Trim Type Internal Design Micro Form Unbalanced 67 Electric Enclosure N/A
43 Rated Travel Leak Class 3/4 in ANSI IV 68 MFR Model N/A N/A
44 Plug/ Ball/ Disk Material S41600 SST 69 Type Quantity N/A N/A
45 Seat Material S41600 SST SWITCHES 70 Contacts / Rating N/A
46 Cage Stem Material N/A S31600 SST 71 Switching Position N/A
47 Gasket Material S31600 SST/Graphite 72 Electric Enclosure N/A
48 MFR Model FISHER 667 73 MFR Model FISHER 67CFR
49 Type Diaphragm Spring Return AIR SET 74 Set Pressure 4.2 kgf/cm2-g
50 Size Stroke Time 30i < 5 Sec 75 Filter Gauge 5 Micron min YES
ACTUATOR 51 Air Failure Valve: FC 76 Vol. Tank Booster NO NO
52 Handwheel Location N/A 77 Diffuser Lock-up NO NO
ACCESSORY
53 Mounting Position VERTICAL 78 Fire Safe Fireproof NO NO
54 Spring Range 0.8 - 2.5 kgf/cm2-g 79 Mech. Stop Quick Exa. NO NO
55 Include Pressure (Shutoff) 80 Hydro. Pressure YES
85 Vendor EMERSON 81 Leakage YES
PURCHASE TESTS
86 Manufacturer FISHER 82 Cryogenic N/A
87 Requisition No. R2B-P3-206-02-P-MR-00200 83 NACE Requirement N/A
88 Model No. EZ 84 PWHT Requirement N/A
Notes:

INSTRUMENT SPECIFICATION - CONTROL VALVE


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S116.1 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Fieldbus Device Data Sheet
Tag No.: PV -21408
Fieldbus Tag No.:

Service : FA402 OG TO EA202AB

Basic Fieldbus Function Blocks Segment Information


Analog Input Block (AI) 1 Number Device:
1 22
20 Execution (msec)
Discrete Input Block (DI) 4 Number Segment #: DFJB-21147
2 23
15 Execution Time
3 Bias/Gain Station (BG) 0 Execution (msec) 24 LAS Capable: Yes No
Manual Loader (ML) 0 Number 25 Device Current Draw (mA): 19
4
0 Execution (msec) Device Minimum Voltage: 9.
26
Analog Output Block (AO) 1 Number Device Capacitance: 5 nF
5 20 Execution (msec) Polarity-sensitive: Yes No
27
Discrete Output Block (DO) 1 Number Segment Terminator Location:
6 20 Execution (msec)
28
7 Control Selector (CS)
DD Revision: 3
PID,PI,I Controller (PID) 29
8
20 Execution (msec)
CFF Revision: 1.9
Ratio Station (RA) 30
9
P,PD Controller (PD) 0 Number
10 0 Execution (msec)

* Execution time in msec.

Advanced Function Blocks Notes:

11 Device Control (DC)

12 Output Splitter (OS)

13 Signal Characterizer (SC)

14 Lead Lag (LL)

15 Deadtime (DT)

16 Integrator(Totalizer) (IT)

17 Setpoint Ramp Generator (SPG)

18 Input Selector (IS)

19 Arithmetic (AR)

20 Timer (TMR)

21 Analog Alarm (AAL)

INSTRUMENT SPECIFICATION -FOUNDATION FIELDBUS


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S116.2 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Tag Number : PV -21408

1. Control Valve Outlet data -


Minimum Case - Vap Flow: 58 normal m3/h; Temp: 26oC; Liq Density: 990 kg/m^3; Liq Visc.: 0.863 cP; Vap MW: 36.83 Vap Z: 0.766 Vap Cp/Cv(Real):
1.115
Normal Case - Vap Flow: 192 normal m3/h; Temp: 26oC; Liq Density: 990 kg/m^3; Liq Visc.: 0.863 cP; Vap MW: 36.83 Vap Z: 0.766 Vap Cp/Cv(Real):
1.115
Maximum Case - Vap Flow: 212 normal m3/h; Temp: 26oC; Liq Density: 990 kg/m^3; Liq Visc.: 0.863 cP; Vap MW: 36.83 Vap Z: 0.766 Vap
Cp/Cv(Real): 1.115

2. In-Built surge protector is provided by vendor.

1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S116.3 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
1 Tag No. PV -21416
2 Service DT401 LPG TO STOR TK
3 P&ID No. Line No. R2B-P3-206-02-A-DTI-00416 4"-P-214077-B2A1-N
4 Area Classification Ingress Protection CLASS 1 DIV 2 Gr. B ,C&D, T3 NEMA 4X
GENERAL 5 Ambient Temperature: Unit Min. Max. °C 10 48
6 Allowable Sound dBA Tightness Requirement <85 ANSI IV (standard)
7 Available Air Supply Pressure Unit Min. Max. kgf/cm²-g 4.2 8.0
8 Electric Connection Pneum. Connection 1/2” NPT (F) 1/4” NPT (F)
9 Power Failure Position FC
10 Line Size and Schedule Sch. Outlet Line Sch. 4 in STD 4" STD
PIPE
11 Line Class Rating Pipe Material B2A1 300# A106 GR.B, SMLS
LINE
12 Pipe Insulation Thickness Corrosion Allowance N N/A 1.6mm
13 Fluid State Phase Hydrocarbon Liquid Single Phase
14 Sour Service Special Condition N/A N/A
15 Flow Rate Units Min. Nor. Max. m³/h 11.5 71.8 79
16 Inlet Pressure Units Min. Nor. Max. kgf/cm²-g 21.71 22.15 22.24
17 Pressure Drop Units Min. Nor. Max. kgf/cm² 13.55 2.23 2.23
18 Inlet Temperature Units Min. Nor. Max. °C 28 28 28
PROCESS 19 Density Units Min. Nor. Max. kg/m³ 503 503 503
CONDITIONS 20 Viscosity Units Min. Nor. Max. cP 0.069 0.069 0.069
21 Molecular Weight (MW) Specific Gravity @ Oper.
22 Spec. Heat Ratio (Cp/Cv) Compressibility (Z)
23 Vapor Pressure (Liq.) Cavitation or Flashing 12.63 kgf/cm²-a Flashing
24 Critical Pressure (Liq) Flash (wt%) 46.66 kgf/cm²-a
25 Design Pressure Min. Max. kgf/cm²-g 30.5 kgf/cm²-g
26 Design Temperature Min. Max. 10 °C 120 °C
27 Max.Shutoff DP Solid % 30.5 kgf/cm²
28 Calculated Cv Units Min. Nor. Max. Cv 3.1 39.9 44.
CALCULATED
29 Travel Units Min. Nor. Max. % 20 79 82
RESULTS
30 Noise dBA @1m Units Min. Nor. Max. dBA 85 52 52
31 MFR Model FISHER ET 56 MFR Model FISHER DVC6200F/SC-AD
32 Body Type Single Seat Globe 57 Signal: Inlet Outlet FF Protocol 0-2.8 kgf/cm2
33 Body Size Trim Size 3 in 2 5/16 in 58 Increase Signal Valve: DIRECT
34 End Connec.Size & Rating 3" 300# RF POSITIONER 59 Cam Characteristic LINEAR
35 Rated Cv Characteristic 70.7 EQ% 60 Bypass Gauges N/A YES
36 Body Material WCC Steel 61 Signal Fail. to Valve FC
BODY 37 Bonnet Type Material Plain WCC Steel 62 Electric Enclosure Ex ia IIC T5 , NEMA 4X
AND 38 Flow Direct. Flow Act. To Down FTO 63 MFR Model N/A N/A
TRIM 39 Packing Type Material ISO Seal PTFE 64 Type Power N/A N/A
SOLENOID
40 Lubricator Isolat. Valve N/A N/A 65 When De-Enegr.Valve: N/A
VALVE
41 Guiding No. of Ports Cage 1 66 Material Latcher N/A N/A
42 Trim Type Internal Design Standard Balanced 67 Electric Enclosure N/A
43 Rated Travel Leak Class 1 1/8 in ANSI IV 68 MFR Model N/A N/A
44 Plug/ Ball/ Disk Material S31600 SST/CoCr-A Seat 69 Type Quantity N/A N/A
45 Seat Material CoCr-A Seat SWITCHES 70 Contacts / Rating N/A
46 Cage Stem Material S31600 SST/ ENCS31600 SST 71 Switching Position N/A
47 Gasket Material S31600 SST/Graphite 72 Electric Enclosure N/A
48 MFR Model FISHER 667 73 MFR Model FISHER 67CFR
49 Type Diaphragm Spring Return AIR SET 74 Set Pressure 4.2 kgf/cm2-g
50 Size Stroke Time 40i < 8 Sec 75 Filter Gauge 5 Micron min YES
ACTUATOR 51 Air Failure Valve: FC 76 Vol. Tank Booster NO NO
52 Handwheel Location N/A 77 Diffuser Lock-up NO NO
ACCESSORY
53 Mounting Position VERTICAL 78 Fire Safe Fireproof NO NO
54 Spring Range 0.7 - 2.4 kgf/cm2-g 79 Mech. Stop Quick Exa. NO NO
55 Include Pressure (Shutoff) 80 Hydro. Pressure YES
85 Vendor EMERSON 81 Leakage YES
PURCHASE TESTS
86 Manufacturer FISHER 82 Cryogenic N/A
87 Requisition No. R2B-P3-206-02-P-MR-00200 83 NACE Requirement N/A
88 Model No. ET 84 PWHT Requirement N/A
Notes:

INSTRUMENT SPECIFICATION - CONTROL VALVE


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S117.1 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Fieldbus Device Data Sheet
Tag No.: PV -21416
Fieldbus Tag No.:

Service : DT401 LPG TO STOR TK

Basic Fieldbus Function Blocks Segment Information


Analog Input Block (AI) 1 Number Device:
1 22
20 Execution (msec)
Discrete Input Block (DI) 4 Number Segment #: DFJB-21163
2 23
15 Execution Time
3 Bias/Gain Station (BG) 0 Execution (msec) 24 LAS Capable: Yes No
Manual Loader (ML) 0 Number 25 Device Current Draw (mA): 19
4
0 Execution (msec) Device Minimum Voltage: 9.
26
Analog Output Block (AO) 1 Number Device Capacitance: 5 nF
5 20 Execution (msec) Polarity-sensitive: Yes No
27
Discrete Output Block (DO) 1 Number Segment Terminator Location:
6 20 Execution (msec)
28
7 Control Selector (CS)
DD Revision: 3
PID,PI,I Controller (PID) 29
8
20 Execution (msec)
CFF Revision: 1.9
Ratio Station (RA) 30
9
P,PD Controller (PD) 0 Number
10 0 Execution (msec)

* Execution time in msec.

Advanced Function Blocks Notes:

11 Device Control (DC)

12 Output Splitter (OS)

13 Signal Characterizer (SC)

14 Lead Lag (LL)

15 Deadtime (DT)

16 Integrator(Totalizer) (IT)

17 Setpoint Ramp Generator (SPG)

18 Input Selector (IS)

19 Arithmetic (AR)

20 Timer (TMR)

21 Analog Alarm (AAL)

INSTRUMENT SPECIFICATION -FOUNDATION FIELDBUS


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S117.2 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Tag Number : PV -21416

1. Control Valve Outlet data -


Minimum Case - Liq Flow: 10.1 m3/h; Vap Flow: 281 normal m3/h; Temp: 15.5 oC; Liq Density: 520 kg/m^3; Liq Visc.: 0.079 cP; Vap MW: - ; Vap Z:
1.00 ; Vap Cp/Cv(Real): 1.019

2. In-Built surge protector is provided by vendor.

1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S117.3 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
1 Tag No. PV -21520
2 Service FA503 FLH GTO AMN REG U
3 P&ID No. Line No. R2B-P3-206-02-A-DTI-00504 2"-GAM-212411-T-A08T1-N
4 Area Classification Ingress Protection CLASS 1 DIV 2 Gr. B ,C&D, T3 NEMA 4X
GENERAL 5 Ambient Temperature: Unit Min. Max. °C 10 48
6 Allowable Sound dBA Tightness Requirement <85 ANSI IV (standard)
7 Available Air Supply Pressure Unit Min. Max. kgf/cm²-g 4.2 8.0
8 Electric Connection Pneum. Connection 1/2” NPT (F) 1/4” NPT (F)
9 Power Failure Position FC
10 Line Size and Schedule Sch. Outlet Line Sch. 2 in XS 2" XS
PIPE
11 Line Class Rating Pipe Material T-A08T1 150# A106 GR.B, SMLS
LINE
12 Pipe Insulation Thickness Corrosion Allowance N N/A 3.2mm
13 Fluid State Phase Hydrocarbon Gas/Vapor Single Phase
14 Sour Service Special Condition YES N/A
15 Flow Rate Units Min. Nor. Max. Nm³/h 3.858 3.858 4.244
16 Inlet Pressure Units Min. Nor. Max. kgf/cm²-g 7.999 7.999 6.999
17 Pressure Drop Units Min. Nor. Max. kgf/cm² 7.158 7.158 6.158
18 Inlet Temperature Units Min. Nor. Max. °C 54.7 54.7 54.7
PROCESS 19 Density Units Min. Nor. Max. kg/m³
CONDITIONS 20 Viscosity Units Min. Nor. Max. cP 0.012 0.012 0.012
21 Molecular Weight (MW) Specific Gravity @ Oper. 23.1
22 Spec. Heat Ratio (Cp/Cv) Compressibility (Z) 1.255 0.98
23 Vapor Pressure (Liq.) Cavitation or Flashing kgf/cm²-a N/A
24 Critical Pressure (Liq) Flash (wt%) kgf/cm²-a
25 Design Pressure Min. Max. -1.033 kgf/cm²-g 16 kgf/cm²-g
26 Design Temperature Min. Max. 10 °C 120 °C
27 Max.Shutoff DP Solid % 16 kgf/cm²
28 Calculated Cv Units Min. Nor. Max. 0.035
Cv 0.035 0.034
CALCULATED
29 Travel Units Min. Nor. Max. %52 52 50
RESULTS
30 Noise dBA @1m Units Min. Nor. Max. 50
dBA 50 50
31 MFR Model FISHER EZ 56 MFR Model FISHER DVC6200F/SC-AD
32 Body Type Single Seat Globe 57 Signal: Inlet Outlet FF Protocol 0-2.8 kgf/cm2
33 Body Size Trim Size 1 in 3/16 in 58 Increase Signal Valve: DIRECT
34 End Connec.Size & Rating 1" 300# RF POSITIONER 59 Cam Characteristic LINEAR
35 Rated Cv Characteristic 0.075 EQ% 60 Bypass Gauges N/A YES
36 Body Material WCC Steel 61 Signal Fail. to Valve FC
BODY 37 Bonnet Type Material Plain WCC Steel 62 Electric Enclosure Ex ia IIC T5 , NEMA 4X
AND 38 Flow Direct. Flow Act. To Up FTO 63 MFR Model N/A N/A
TRIM 39 Packing Type Material ISO Seal PTFE 64 Type Power N/A N/A
SOLENOID
40 Lubricator Isolat. Valve N/A N/A 65 When De-Enegr.Valve: N/A
VALVE
41 Guiding No. of Ports Port 1 66 Material Latcher N/A N/A
42 Trim Type Internal Design Micro Flow Unbalanced 67 Electric Enclosure N/A
43 Rated Travel Leak Class 3/4 in ANSI IV 68 MFR Model N/A N/A
44 Plug/ Ball/ Disk Material S31600 SST/CoCr-A Seat 69 Type Quantity N/A N/A
45 Seat Material S31600 SST SWITCHES 70 Contacts / Rating N/A
46 Cage Stem Material N/A S20910 SST 71 Switching Position N/A
47 Gasket Material S31600 SST/Graphite 72 Electric Enclosure N/A
48 MFR Model FISHER 667 73 MFR Model FISHER 67CFR
49 Type Diaphragm Spring Return AIR SET 74 Set Pressure 4.2 kgf/cm2-g
50 Size Stroke Time 30i < 5 Sec 75 Filter Gauge 5 Micron min YES
ACTUATOR 51 Air Failure Valve: FC 76 Vol. Tank Booster NO NO
52 Handwheel Location N/A 77 Diffuser Lock-up NO NO
ACCESSORY
53 Mounting Position VERTICAL 78 Fire Safe Fireproof NO NO
54 Spring Range 0.8 - 2.5 kgf/cm2-g 79 Mech. Stop Quick Exa. NO NO
55 Include Pressure (Shutoff) 80 Hydro. Pressure YES
85 Vendor EMERSON 81 Leakage YES
PURCHASE TESTS
86 Manufacturer FISHER 82 Cryogenic N/A
87 Requisition No. R2B-P3-206-02-P-MR-00200 83 NACE Requirement NACE-0103
88 Model No. EZ 84 PWHT Requirement YES
Notes:

INSTRUMENT SPECIFICATION - CONTROL VALVE


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S118.1 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Fieldbus Device Data Sheet
Tag No.: PV -21520
Fieldbus Tag No.:

Service : FA503 FLH GTO AMN REG U

Basic Fieldbus Function Blocks Segment Information


Analog Input Block (AI) 1 Number Device:
1 22
20 Execution (msec)
Discrete Input Block (DI) 4 Number Segment #: DFJB-21072
2 23
15 Execution Time
3 Bias/Gain Station (BG) 0 Execution (msec) 24 LAS Capable: Yes No
Manual Loader (ML) 0 Number 25 Device Current Draw (mA): 19
4
0 Execution (msec) Device Minimum Voltage: 9.
26
Analog Output Block (AO) 1 Number Device Capacitance: 5 nF
5 20 Execution (msec) Polarity-sensitive: Yes No
27
Discrete Output Block (DO) 1 Number Segment Terminator Location:
6 20 Execution (msec)
28
7 Control Selector (CS)
DD Revision: 3
PID,PI,I Controller (PID) 29
8
20 Execution (msec)
CFF Revision: 1.9
Ratio Station (RA) 30
9
P,PD Controller (PD) 0 Number
10 0 Execution (msec)

* Execution time in msec.

Advanced Function Blocks Notes:

11 Device Control (DC)

12 Output Splitter (OS)

13 Signal Characterizer (SC)

14 Lead Lag (LL)

15 Deadtime (DT)

16 Integrator(Totalizer) (IT)

17 Setpoint Ramp Generator (SPG)

18 Input Selector (IS)

19 Arithmetic (AR)

20 Timer (TMR)

21 Analog Alarm (AAL)

INSTRUMENT SPECIFICATION -FOUNDATION FIELDBUS


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S118.2 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Tag Number : PV -21520

1. Steam out condition : F.V/200 degC.

2. In-Built surge protector is provided by vendor.

1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S118.3 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
1 Tag No. PV -21522B
2 Service FA502 DRY GAS TO LFL
3 P&ID No. Line No. R2B-P3-206-02-A-DTI-00503 10"-GD-212405-T-A03T1-N
4 Area Classification Ingress Protection CLASS 1 DIV 2 Gr. B ,C&D, T3 NEMA 4X
GENERAL 5 Ambient Temperature: Unit Min. Max. °C 10 48
6 Allowable Sound dBA Tightness Requirement <85 ANSI IV (standard)
7 Available Air Supply Pressure Unit Min. Max. kgf/cm²-g 4.2 8.0
8 Electric Connection Pneum. Connection 1/2” NPT (F) 1/4” NPT (F)
9 Power Failure Position FC
10 Line Size and Schedule Sch. Outlet Line Sch. 10 in STD 10" STD
PIPE
11 Line Class Rating Pipe Material T-A03T1 150# A106 GR.B, SMLS
LINE
12 Pipe Insulation Thickness Corrosion Allowance N N/A 1.6mm
13 Fluid State Phase Hydrocarbon Gas/Vapor Single Phase
14 Sour Service Special Condition N/A N/A
15 Flow Rate Units Min. Nor. Max. Nm³/h 12828 25657 28223
16 Inlet Pressure Units Min. Nor. Max. kgf/cm²-g 12.49 12.46 12.45
17 Pressure Drop Units Min. Nor. Max. kgf/cm² 12.4 11.5 11.29
18 Inlet Temperature Units Min. Nor. Max. °C 38 38 38
PROCESS 19 Density Units Min. Nor. Max. kg/m³
CONDITIONS 20 Viscosity Units Min. Nor. Max. cP 0.012 0.012 0.012
21 Molecular Weight (MW) Specific Gravity @ Oper. 22
22 Spec. Heat Ratio (Cp/Cv) Compressibility (Z) 1.303 0.966
23 Vapor Pressure (Liq.) Cavitation or Flashing kgf/cm²-a N/A
24 Critical Pressure (Liq) Flash (wt%) kgf/cm²-a
25 Design Pressure Min. Max. kgf/cm²-g 16 kgf/cm²-g
26 Design Temperature Min. Max. 10 °C 70 °C
27 Max.Shutoff DP Solid % 16 kgf/cm²
28 Calculated Cv Units Min. Nor. Max. Cv 76.7 154 169
CALCULATED
29 Travel Units Min. Nor. Max. % 31 59 65
RESULTS
30 Noise dBA @1m Units Min. Nor. Max. dBA 82 83 82
31 MFR Model FISHER ET 56 MFR Model FISHER DVC6200F/SC-AD
32 Body Type Single Seat Globe 57 Signal: Inlet Outlet FF Protocol 0-2.8 kgf/cm2
33 Body Size Trim Size 8 in 8 in 58 Increase Signal Valve: DIRECT
34 End Connec.Size & Rating 8" 300# RF POSITIONER 59 Cam Characteristic LINEAR
35 Rated Cv Characteristic 259 Linear 60 Bypass Gauges N/A YES
36 Body Material WCC Steel 61 Signal Fail. to Valve FC
BODY 37 Bonnet Type Material Plain WCC Steel 62 Electric Enclosure Ex ia IIC T5 , NEMA 4X
AND 38 Flow Direct. Flow Act. To Up FTC 63 MFR Model N/A N/A
TRIM 39 Packing Type Material ISO Seal PTFE 64 Type Power N/A N/A
SOLENOID
40 Lubricator Isolat. Valve N/A N/A 65 When De-Enegr.Valve: N/A
VALVE
41 Guiding No. of Ports Cage 1 66 Material Latcher N/A N/A
42 Trim Type Internal Design Whisper III Balanced 67 Electric Enclosure N/A
43 Rated Travel Leak Class 4 in ANSI IV 68 MFR Model N/A N/A
44 Plug/ Ball/ Disk Material S41600 SST 69 Type Quantity N/A N/A
45 Seat Material S41600 SST SWITCHES 70 Contacts / Rating N/A
46 Cage Stem Material CB7Cu-1 SST S31600 SST 71 Switching Position N/A
47 Gasket Material S31600 SST/Graphite 72 Electric Enclosure N/A
48 MFR Model FISHER 667-4 73 MFR Model FISHER 67CFR
49 Type Diaphragm Spring Return AIR SET 74 Set Pressure 4.2 kgf/cm2-g
50 Size Stroke Time 70i < 25 Sec 75 Filter Gauge 5 Micron min YES
ACTUATOR 51 Air Failure Valve: FC 76 Vol. Tank Booster NO NO
52 Handwheel Location N/A 77 Diffuser Lock-up NO NO
ACCESSORY
53 Mounting Position VERTICAL 78 Fire Safe Fireproof NO NO
54 Spring Range 0.8 - 1.8 kgf/cm2-g 79 Mech. Stop Quick Exa. NO NO
55 Include Pressure (Shutoff) 80 Hydro. Pressure YES
85 Vendor EMERSON 81 Leakage YES
PURCHASE TESTS
86 Manufacturer FISHER 82 Cryogenic N/A
87 Requisition No. R2B-P3-206-02-P-MR-00200 83 NACE Requirement N/A
88 Model No. ET 84 PWHT Requirement N/A
Notes:

INSTRUMENT SPECIFICATION - CONTROL VALVE


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S119.1 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Fieldbus Device Data Sheet
Tag No.: PV -21522B
Fieldbus Tag No.:

Service : FA502 DRY GAS TO LFL

Basic Fieldbus Function Blocks Segment Information


Analog Input Block (AI) 1 Number Device:
1 22
20 Execution (msec)
Discrete Input Block (DI) 4 Number Segment #: DFJB-21123
2 23
15 Execution Time
3 Bias/Gain Station (BG) 0 Execution (msec) 24 LAS Capable: Yes No
Manual Loader (ML) 0 Number 25 Device Current Draw (mA): 19
4
0 Execution (msec) Device Minimum Voltage: 9.
26
Analog Output Block (AO) 1 Number Device Capacitance: 5 nF
5 20 Execution (msec) Polarity-sensitive: Yes No
27
Discrete Output Block (DO) 1 Number Segment Terminator Location:
6 20 Execution (msec)
28
7 Control Selector (CS)
DD Revision: 3
PID,PI,I Controller (PID) 29
8
20 Execution (msec)
CFF Revision: 1.9
Ratio Station (RA) 30
9
P,PD Controller (PD) 0 Number
10 0 Execution (msec)

* Execution time in msec.

Advanced Function Blocks Notes:

11 Device Control (DC)

12 Output Splitter (OS)

13 Signal Characterizer (SC)

14 Lead Lag (LL)

15 Deadtime (DT)

16 Integrator(Totalizer) (IT)

17 Setpoint Ramp Generator (SPG)

18 Input Selector (IS)

19 Arithmetic (AR)

20 Timer (TMR)

21 Analog Alarm (AAL)

INSTRUMENT SPECIFICATION -FOUNDATION FIELDBUS


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S119.2 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Tag Number : PV -21522B

1. In-Built surge protector is provided by vendor.

1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S119.3 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
1 Tag No. PV -21636
2 Service GA603 CRSLP TO TANKAGE
3 P&ID No. Line No. R2B-P3-206-02-A-DTI-00609 6"-P-216026-T-A62T1-PP
4 Area Classification Ingress Protection CLASS 1 DIV 2 Gr. B ,C&D, T3 NEMA 4X
GENERAL 5 Ambient Temperature: Unit Min. Max. °C 10 48
6 Allowable Sound dBA Tightness Requirement <85 ANSI IV (standard)
7 Available Air Supply Pressure Unit Min. Max. kgf/cm²-g 4.2 8.0
8 Electric Connection Pneum. Connection 1/2” NPT (F) 1/4” NPT (F)
9 Power Failure Position FO
10 Line Size and Schedule Sch. Outlet Line Sch. 6 in XS 6" XS
PIPE
11 Line Class Rating Pipe Material T-A62T1 150# A106 GR.B, SMLS
LINE
12 Pipe Insulation Thickness Corrosion Allowance PP 25mm 6.4mm
13 Fluid State Phase Slops Liquid Single Phase
14 Sour Service Special Condition YES N/A
15 Flow Rate Units Min. Nor. Max. m³/h 47.1 47.1
16 Inlet Pressure Units Min. Nor. Max. kgf/cm²-g 3.767 5.944
17 Pressure Drop Units Min. Nor. Max. kgf/cm² 1.009 1.281
18 Inlet Temperature Units Min. Nor. Max. °C 60 60 60
PROCESS 19 Density Units Min. Nor. Max. kg/m³ 620 1000
CONDITIONS 20 Viscosity Units Min. Nor. Max. cP 0.2 18.5
21 Molecular Weight (MW) Specific Gravity @ Oper.
22 Spec. Heat Ratio (Cp/Cv) Compressibility (Z)
23 Vapor Pressure (Liq.) Cavitation or Flashing 0.56 kgf/cm²-a NO
24 Critical Pressure (Liq) Flash (wt%) 35.2 kgf/cm²-a
25 Design Pressure Min. Max. kgf/cm²-g 10 kgf/cm²-g
26 Design Temperature Min. Max. 10 °C 110 °C
27 Max.Shutoff DP Solid % 10 kgf/cm²
28 Calculated Cv Units Min. Nor. Max. Cv 43.6 43.6 49.2
CALCULATED
29 Travel Units Min. Nor. Max. % 77 77 81
RESULTS
30 Noise dBA @1m Units Min. Nor. Max. dBA 50 50 50
31 MFR Model FISHER EZ 56 MFR Model FISHER DVC6200F/SC-AD
32 Body Type Single Seat Globe 57 Signal: Inlet Outlet FF Protocol 0-2.8 kgf/cm2
33 Body Size Trim Size 3 in 2 in 58 Increase Signal Valve: DIRECT
34 End Connec.Size & Rating 3" 300# RF POSITIONER 59 Cam Characteristic LINEAR
35 Rated Cv Characteristic 71.6 EQ% 60 Bypass Gauges N/A YES
36 Body Material WCC Steel 61 Signal Fail. to Valve FO
BODY 37 Bonnet Type Material Plain WCC Steel 62 Electric Enclosure Ex ia IIC T5 , NEMA 4X
AND 38 Flow Direct. Flow Act. To Up FTO 63 MFR Model N/A N/A
TRIM 39 Packing Type Material ISO Seal PTFE 64 Type Power N/A N/A
SOLENOID
40 Lubricator Isolat. Valve N/A N/A 65 When De-Enegr.Valve: N/A
VALVE
41 Guiding No. of Ports Post 1 66 Material Latcher N/A N/A
42 Trim Type Internal Design Standard Unbalanced 67 Electric Enclosure N/A
43 Rated Travel Leak Class 1 1/8 in ANSI IV 68 MFR Model N/A N/A
44 Plug/ Ball/ Disk Material S31600 SST 69 Type Quantity N/A N/A
45 Seat Material S31600 SST SWITCHES 70 Contacts / Rating N/A
46 Cage Stem Material N/A S20910 SST 71 Switching Position N/A
47 Gasket Material S31600 SST/Graphite 72 Electric Enclosure N/A
48 MFR Model FISHER 657 73 MFR Model FISHER 67CFR
49 Type Diaphragm Spring Return AIR SET 74 Set Pressure 4.2 kgf/cm2-g
50 Size Stroke Time 46i < 8 Sec 75 Filter Gauge 5 Micron min YES
ACTUATOR 51 Air Failure Valve: FO 76 Vol. Tank Booster NO NO
52 Handwheel Location N/A 77 Diffuser Lock-up NO NO
ACCESSORY
53 Mounting Position VERTICAL 78 Fire Safe Fireproof NO NO
54 Spring Range 0.4 - 2.0 kgf/cm2-g 79 Mech. Stop Quick Exa. NO NO
55 Include Pressure (Shutoff) 80 Hydro. Pressure YES
85 Vendor EMERSON 81 Leakage YES
PURCHASE TESTS
86 Manufacturer FISHER 82 Cryogenic N/A
87 Requisition No. R2B-P3-206-02-P-MR-00200 83 NACE Requirement NACE-0103
88 Model No. EZ 84 PWHT Requirement YES
Notes:

INSTRUMENT SPECIFICATION - CONTROL VALVE


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S120.1 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Fieldbus Device Data Sheet
Tag No.: PV -21636
Fieldbus Tag No.:

Service : GA603 CRSLP TO TANKAGE

Basic Fieldbus Function Blocks Segment Information


Analog Input Block (AI) 1 Number Device:
1 22
20 Execution (msec)
Discrete Input Block (DI) 4 Number Segment #: DFJB-21151
2 23
15 Execution Time
3 Bias/Gain Station (BG) 0 Execution (msec) 24 LAS Capable: Yes No
Manual Loader (ML) 0 Number 25 Device Current Draw (mA): 19
4
0 Execution (msec) Device Minimum Voltage: 9.
26
Analog Output Block (AO) 1 Number Device Capacitance: 5 nF
5 20 Execution (msec) Polarity-sensitive: Yes No
27
Discrete Output Block (DO) 1 Number Segment Terminator Location:
6 20 Execution (msec)
28
7 Control Selector (CS)
DD Revision: 3
PID,PI,I Controller (PID) 29
8
20 Execution (msec)
CFF Revision: 1.9
Ratio Station (RA) 30
9
P,PD Controller (PD) 0 Number
10 0 Execution (msec)

* Execution time in msec.

Advanced Function Blocks Notes:

11 Device Control (DC)

12 Output Splitter (OS)

13 Signal Characterizer (SC)

14 Lead Lag (LL)

15 Deadtime (DT)

16 Integrator(Totalizer) (IT)

17 Setpoint Ramp Generator (SPG)

18 Input Selector (IS)

19 Arithmetic (AR)

20 Timer (TMR)

21 Analog Alarm (AAL)

INSTRUMENT SPECIFICATION -FOUNDATION FIELDBUS


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S120.2 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Tag Number : PV -21636

1. Density 620~1000 kg/cm2g

2. In-Built surge protector is provided by vendor.

1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S120.3 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
1 Tag No. PV -21719
2 Service PA TO FA008
3 P&ID No. Line No. R2B-P3-206-02-A-DTI-00063 6"-AP-216119-T-A06T1-PP
4 Area Classification Ingress Protection CLASS 1 DIV 2 Gr. B ,C&D, T3 NEMA 4X
GENERAL 5 Ambient Temperature: Unit Min. Max. °C 10 48
6 Allowable Sound dBA Tightness Requirement <85 ANSI IV (standard)
7 Available Air Supply Pressure Unit Min. Max. kgf/cm²-g 4.2 8.0
8 Electric Connection Pneum. Connection 1/2” NPT (F) 1/4” NPT (F)
9 Power Failure Position FC
10 Line Size and Schedule Sch. Outlet Line Sch. 6 in STD 6" STD
PIPE
11 Line Class Rating Pipe Material T-A06T1 150# A106 GR.B, SMLS
LINE
12 Pipe Insulation Thickness Corrosion Allowance N N/A 1.6mm
13 Fluid State Phase Plant Air Gas/Vapor Single Phase
14 Sour Service Special Condition N/A N/A
15 Flow Rate Units Min. Nor. Max. m³/h 340.69 683.372 749.51
16 Inlet Pressure Units Min. Nor. Max. kgf/cm²-g 7.506 7.488 7.483
17 Pressure Drop Units Min. Nor. Max. kgf/cm² 0.3 0.276 0.269
18 Inlet Temperature Units Min. Nor. Max. °C 40 40 40
PROCESS 19 Density Units Min. Nor. Max. kg/m³
CONDITIONS 20 Viscosity Units Min. Nor. Max. cP 0.019 0.019 0.019
21 Molecular Weight (MW) Specific Gravity @ Oper. 28.85
22 Spec. Heat Ratio (Cp/Cv) Compressibility (Z) 1.392 0.997
23 Vapor Pressure (Liq.) Cavitation or Flashing kgf/cm²-a NO
24 Critical Pressure (Liq) Flash (wt%) kgf/cm²-a
25 Design Pressure Min. Max. kgf/cm²-g 10.5 kgf/cm²-g
26 Design Temperature Min. Max. 10 °C 80 °C
27 Max.Shutoff DP Solid % 10.5 kgf/cm²
28 Calculated Cv Units Min. Nor. Max. Cv 9.89 20.7 23.
CALCULATED
29 Travel Units Min. Nor. Max. % 41 61 63
RESULTS
30 Noise dBA @1m Units Min. Nor. Max. dBA 53 55 55
31 MFR Model FISHER EWT 56 MFR Model FISHER DVC6200F/SC-AD
32 Body Type Single Seat Globe 57 Signal: Inlet Outlet FF Protocol 0-3.5 kgf/cm2
33 Body Size Trim Size 4 in 2 5/16 in 58 Increase Signal Valve: DIRECT
34 End Connec.Size & Rating 4" 300# RF POSITIONER 59 Cam Characteristic LINEAR
35 Rated Cv Characteristic 82.2 EQ% 60 Bypass Gauges N/A YES
36 Body Material WCC Steel 61 Signal Fail. to Valve FC
BODY 37 Bonnet Type Material Plain WCC Steel 62 Electric Enclosure Ex ia IIC T5 , NEMA 4X
AND 38 Flow Direct. Flow Act. To Down FTO 63 MFR Model N/A N/A
TRIM 39 Packing Type Material Enviro Seal PTFE Carbon 64 Type Power N/A N/A
SOLENOID
40 Lubricator Isolat. Valve N/A N/A 65 When De-Enegr.Valve: N/A
VALVE
41 Guiding No. of Ports Cage 1 66 Material Latcher N/A N/A
42 Trim Type Internal Design Standard Balanced 67 Electric Enclosure N/A
43 Rated Travel Leak Class 1 1/8 in ANSI IV 68 MFR Model N/A N/A
44 Plug/ Ball/ Disk Material S41600 SST 69 Type Quantity N/A N/A
45 Seat Material S41600 SST SWITCHES 70 Contacts / Rating N/A
46 Cage Stem Material CB7Cu-1 SST S31600 SST 71 Switching Position N/A
47 Gasket Material S31600 SST/Graphite 72 Electric Enclosure N/A
48 MFR Model FISHER 667 73 MFR Model FISHER 67CFR
49 Type Diaphragm Spring Return AIR SET 74 Set Pressure 4.2 kgf/cm2-g
50 Size Stroke Time 40i < 10 Sec 75 Filter Gauge 5 Micron min YES
ACTUATOR 51 Air Failure Valve: FC 76 Vol. Tank Booster NO NO
52 Handwheel Location N/A 77 Diffuser Lock-up NO NO
ACCESSORY
53 Mounting Position VERTICAL 78 Fire Safe Fireproof NO NO
54 Spring Range 0.7 - 2.4 kgf/cm2-g 79 Mech. Stop Quick Exa. NO NO
55 Include Pressure (Shutoff) 80 Hydro. Pressure YES
85 Vendor EMERSON 81 Leakage YES
PURCHASE TESTS
86 Manufacturer FISHER 82 Cryogenic N/A
87 Requisition No. R2B-P3-206-02-P-MR-00200 83 NACE Requirement N/A
88 Model No. EWT 84 PWHT Requirement N/A
Notes:

INSTRUMENT SPECIFICATION - CONTROL VALVE


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S121.1 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Fieldbus Device Data Sheet
Tag No.: PV -21719
Fieldbus Tag No.:

Service : PA TO FA008

Basic Fieldbus Function Blocks Segment Information


Analog Input Block (AI) 1 Number Device:
1 22
20 Execution (msec)
Discrete Input Block (DI) 4 Number Segment #: DFJB-21030
2 23
15 Execution Time
3 Bias/Gain Station (BG) 0 Execution (msec) 24 LAS Capable: Yes No
Manual Loader (ML) 0 Number 25 Device Current Draw (mA): 19
4
0 Execution (msec) Device Minimum Voltage: 9.
26
Analog Output Block (AO) 1 Number Device Capacitance: 5 nF
5 20 Execution (msec) Polarity-sensitive: Yes No
27
Discrete Output Block (DO) 1 Number Segment Terminator Location:
6 20 Execution (msec)
28
7 Control Selector (CS)
DD Revision: 3
PID,PI,I Controller (PID) 29
8
20 Execution (msec)
CFF Revision: 1.9
Ratio Station (RA) 30
9
P,PD Controller (PD) 0 Number
10 0 Execution (msec)

* Execution time in msec.

Advanced Function Blocks Notes:

11 Device Control (DC)

12 Output Splitter (OS)

13 Signal Characterizer (SC)

14 Lead Lag (LL)

15 Deadtime (DT)

16 Integrator(Totalizer) (IT)

17 Setpoint Ramp Generator (SPG)

18 Input Selector (IS)

19 Arithmetic (AR)

20 Timer (TMR)

21 Analog Alarm (AAL)

INSTRUMENT SPECIFICATION -FOUNDATION FIELDBUS


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S121.2 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Tag Number : PV -21719

1. NNF.
2. In-Built surge protector is provided by vendor.

1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S121.3 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
1 Tag No. TDV -21507A
2 Service AML TO DA501
3 P&ID No. Line No. R2B-P3-206-02-A-DTI-00502 4"-MDEA-212499-T-B65T1-PP
4 Area Classification Ingress Protection CLASS 1 DIV 2 Gr. B ,C&D, T3 NEMA 4X
GENERAL 5 Ambient Temperature: Unit Min. Max. °C 10 48
6 Allowable Sound dBA Tightness Requirement <85 ANSI IV (standard)
7 Available Air Supply Pressure Unit Min. Max. kgf/cm²-g 4.2 8.0
8 Electric Connection Pneum. Connection 1/2” NPT (F) 1/4” NPT (F)
9 Power Failure Position FC
10 Line Size and Schedule Sch. Outlet Line Sch. 4 in XS 4" XS
PIPE
11 Line Class Rating Pipe Material T-B65T1 300# A106 GR.B, SMLS
LINE
12 Pipe Insulation Thickness Corrosion Allowance PP 25mm 3.2mm
13 Fluid State Phase Rich Amine Liquid Single Phase
14 Sour Service Special Condition YES N/A
15 Flow Rate Units Min. Nor. Max. m³/h 15.4 30.8 33.9
16 Inlet Pressure Units Min. Nor. Max. kgf/cm²-g 18.8 18.52 18.45
17 Pressure Drop Units Min. Nor. Max. kgf/cm² 1.35 0.355 0.355
18 Inlet Temperature Units Min. Nor. Max. °C 70 70 70
PROCESS 19 Density Units Min. Nor. Max. kg/m³ 1012 1012 1012
CONDITIONS 20 Viscosity Units Min. Nor. Max. cP 1.74 1.74 1.74
21 Molecular Weight (MW) Specific Gravity @ Oper.
22 Spec. Heat Ratio (Cp/Cv) Compressibility (Z)
23 Vapor Pressure (Liq.) Cavitation or Flashing 0.29 kgf/cm²-a NO
24 Critical Pressure (Liq) Flash (wt%) 140 kgf/cm²-a
25 Design Pressure Min. Max. kgf/cm²-g 30 kgf/cm²-g
26 Design Temperature Min. Max. 10 °C 120 °C
27 Max.Shutoff DP Solid % 30 kgf/cm²
28 Calculated Cv Units Min. Nor. Max. Cv 15.6 61.1 67.3
CALCULATED
29 Travel Units Min. Nor. Max. % 38 68 70
RESULTS
30 Noise dBA @1m Units Min. Nor. Max. dBA 50 50 50
31 MFR Model FISHER ET 56 MFR Model FISHER DVC6200F/SC-AD
32 Body Type Single Seat Globe 57 Signal: Inlet Outlet FF Protocol 0-2.8 kgf/cm2
33 Body Size Trim Size 3 in 3 7/16 in 58 Increase Signal Valve: DIRECT
34 End Connec.Size & Rating 3" 300# RF POSITIONER 59 Cam Characteristic LINEAR
35 Rated Cv Characteristic 136 EQ% 60 Bypass Gauges N/A YES
36 Body Material WCC Steel 61 Signal Fail. to Valve FC
BODY 37 Bonnet Type Material Plain WCC Steel 62 Electric Enclosure Ex ia IIC T5 , NEMA 4X
AND 38 Flow Direct. Flow Act. To Down FTO 63 MFR Model N/A N/A
TRIM 39 Packing Type Material ISO Seal PTFE 64 Type Power N/A N/A
SOLENOID
40 Lubricator Isolat. Valve N/A N/A 65 When De-Enegr.Valve: N/A
VALVE
41 Guiding No. of Ports Cage 1 66 Material Latcher N/A N/A
42 Trim Type Internal Design Standard Balanced 67 Electric Enclosure N/A
43 Rated Travel Leak Class 1 1/2 in ANSI IV 68 MFR Model N/A N/A
44 Plug/ Ball/ Disk Material S31600 SST/CoCr-A Seat 69 Type Quantity N/A N/A
45 Seat Material R30006 Cobalt Alloy SWITCHES 70 Contacts / Rating N/A
46 Cage Stem Material S31600 SST/ ENCS20910 SST 71 Switching Position N/A
47 Gasket Material S31600 SST/Graphite 72 Electric Enclosure N/A
48 MFR Model FISHER 667 73 MFR Model FISHER 67CFR
49 Type Diaphragm Spring Return AIR SET 74 Set Pressure 4.2 kgf/cm2-g
50 Size Stroke Time 45i < 8 Sec 75 Filter Gauge 5 Micron min YES
ACTUATOR 51 Air Failure Valve: FC 76 Vol. Tank Booster NO NO
52 Handwheel Location N/A 77 Diffuser Lock-up NO NO
ACCESSORY
53 Mounting Position VERTICAL 78 Fire Safe Fireproof NO NO
54 Spring Range 0.7 - 2.6 kgf/cm2-g 79 Mech. Stop Quick Exa. NO NO
55 Include Pressure (Shutoff) 80 Hydro. Pressure YES
85 Vendor EMERSON 81 Leakage YES
PURCHASE TESTS
86 Manufacturer FISHER 82 Cryogenic N/A
87 Requisition No. R2B-P3-206-02-P-MR-00200 83 NACE Requirement NACE-0103
88 Model No. ET 84 PWHT Requirement YES
Notes:

INSTRUMENT SPECIFICATION - CONTROL VALVE


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S122.1 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Fieldbus Device Data Sheet
Tag No.: TDV -21507A
Fieldbus Tag No.:

Service : AML TO DA501

Basic Fieldbus Function Blocks Segment Information


Analog Input Block (AI) 1 Number Device:
1 22
20 Execution (msec)
Discrete Input Block (DI) 4 Number Segment #: DFJB-21108
2 23
15 Execution Time
3 Bias/Gain Station (BG) 0 Execution (msec) 24 LAS Capable: Yes No
Manual Loader (ML) 0 Number 25 Device Current Draw (mA): 19
4
0 Execution (msec) Device Minimum Voltage: 9.
26
Analog Output Block (AO) 1 Number Device Capacitance: 5 nF
5 20 Execution (msec) Polarity-sensitive: Yes No
27
Discrete Output Block (DO) 1 Number Segment Terminator Location:
6 20 Execution (msec)
28
7 Control Selector (CS)
DD Revision: 3
PID,PI,I Controller (PID) 29
8
20 Execution (msec)
CFF Revision: 1.9
Ratio Station (RA) 30
9
P,PD Controller (PD) 0 Number
10 0 Execution (msec)

* Execution time in msec.

Advanced Function Blocks Notes:

11 Device Control (DC)

12 Output Splitter (OS)

13 Signal Characterizer (SC)

14 Lead Lag (LL)

15 Deadtime (DT)

16 Integrator(Totalizer) (IT)

17 Setpoint Ramp Generator (SPG)

18 Input Selector (IS)

19 Arithmetic (AR)

20 Timer (TMR)

21 Analog Alarm (AAL)

INSTRUMENT SPECIFICATION -FOUNDATION FIELDBUS


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S122.2 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Tag Number : TDV -21507A

1. In-Built surge protector is provided by vendor.

1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S122.3 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
1 Tag No. TV -21612
2 Service BFW TO DSC601
3 P&ID No. Line No. R2B-P3-206-02-A-DTI-00617A 2"-ACAA-210639-T-D61T1-EC
4 Area Classification Ingress Protection CLASS 1 DIV 2 Gr. B ,C&D, T3 NEMA 4X
GENERAL 5 Ambient Temperature: Unit Min. Max. °C 10 48
6 Allowable Sound dBA Tightness Requirement <85 ANSI V
7 Available Air Supply Pressure Unit Min. Max. kgf/cm²-g 4.2 8
8 Electric Connection Pneum. Connection 1/2” NPT (F) 1/4” NPT (F)
9 Power Failure Position FC
10 Line Size and Schedule Sch. Outlet Line Sch. 2 in XS 2 in XS
PIPE
11 Line Class Rating Pipe Material T-D61T1 600# A106 GR.B, SMLS
LINE
12 Pipe Insulation Thickness Corrosion Allowance N N/A 1.6 mm
13 Fluid State Phase Water Liquid Single Phase
14 Sour Service Special Condition N/A N/A
15 Flow Rate Units Min. Nor. Max. kg/h 487 2963.7 3260.2
16 Inlet Pressure Units Min. Nor. Max. kgf/cm²-g 68.46 66.45
17 Pressure Drop Units Min. Nor. Max. kgf/cm² 62.56 56.85
18 Inlet Temperature Units Min. Nor. Max. °C 120 120 120
PROCESS 19 Density Units Min. Nor. Max. kg/m³ 955 955 955
CONDITIONS 20 Viscosity Units Min. Nor. Max. cP 0.252 0.252 0.252
21 Molecular Weight (MW) Specific Gravity @ Oper.
22 Spec. Heat Ratio (Cp/Cv) Compressibility (Z)
23 Vapor Pressure (Liq.) Cavitation or Flashing 1.46 kgf/cm²-a NO
24 Critical Pressure (Liq) Flash (wt%) 224.99 kgf/cm²-a
25 Design Pressure Min. Max. kgf/cm²-g 77 kgf/cm²-g
26 Design Temperature Min. Max. 10 °C 150 °C
27 Max.Shutoff DP Solid % 77 kgf/cm²
28 Calculated Cv Units Min. Nor. Max. Cv0.178 0.406
CALCULATED
29 Travel Units Min. Nor. Max. % 36 60
RESULTS
30 Noise dBA @1m Units Min. Nor. Max. dBA50 54
31 MFR Model FISHER ES 56 MFR Model FISHER DVC6200F/SC-AD
32 Body Type Single Seat Globe 57 Signal: Inlet Outlet FF Protocol 0-2.8 kgf/cm2
33 Body Size Trim Size 1 in 1 in 58 Increase Signal Valve: DIRECT
34 End Connec.Size & Rating 1" 600# RF POSITIONER 59 Cam Characteristic LINEAR
35 Rated Cv Characteristic 1.02 Linear 60 Bypass Gauges N/A YES
36 Body Material WCC Steel 61 Signal Fail. to Valve FC
BODY 37 Bonnet Type Material Plain WCC Steel 62 Electric Enclosure Ex ia IIC T5 , NEMA 4X
AND 38 Flow Direct. Flow Act. To Down FTC 63 MFR Model N/A N/A
TRIM 39 Packing Type Material Enviro Seal PTFE Carbon 64 Type Power N/A N/A
SOLENOID
40 Lubricator Isolat. Valve N/A N/A 65 When De-Enegr.Valve: N/A
VALVE
41 Guiding No. of Ports Cage 1 66 Material Latcher N/A N/A
42 Trim Type Internal Design Micro Flat Unbalanced 67 Electric Enclosure N/A
43 Rated Travel Leak Class 1 1/2 in ANSI V 68 MFR Model N/A N/A
44 Plug/ Ball/ Disk Material S44004 SST 69 Type Quantity N/A N/A
45 Seat Material S44004 SST SWITCHES 70 Contacts / Rating N/A
46 Cage Stem Material S17400 SST S31600 SST 71 Switching Position N/A
47 Gasket Material S31600 SST/Graphite 72 Electric Enclosure N/A
48 MFR Model FISHER 667 73 MFR Model FISHER 67CFR
49 Type Diaphragm Spring Return AIR SET 74 Set Pressure 4.2 kgf/cm2-g
50 Size Stroke Time 40i < 6 Sec 75 Filter Gauge 5 Micron min YES
ACTUATOR 51 Air Failure Valve: FC 76 Vol. Tank Booster NO NO
52 Handwheel Location N/A 77 Diffuser Lock-up NO NO
ACCESSORY
53 Mounting Position VERTICAL 78 Fire Safe Fireproof NO NO
54 Spring Range 0.6 - 2.2 kgf/cm2-g 79 Mech. Stop Quick Exa. NO NO
55 Include Pressure (Shutoff) 80 Hydro. Pressure YES
85 Vendor EMERSON 81 Leakage YES
PURCHASE TESTS
86 Manufacturer FISHER 82 Cryogenic N/A
87 Requisition No. R2B-P3-206-02-P-MR-00200 83 NACE Requirement N/A
88 Model No. ES 84 PWHT Requirement N/A
Notes:

INSTRUMENT SPECIFICATION - CONTROL VALVE


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S123.1 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00206 Rev.: 1
Fieldbus Device Data Sheet
Tag No.: TV -21612
Fieldbus Tag No.:

Service : BFW TO DSC601

Basic Fieldbus Function Blocks Segment Information


Analog Input Block (AI) 1 Number Device:
1 22
20 Execution (msec)
Discrete Input Block (DI) 4 Number Segment #: DFJB-21178
2 23
15 Execution Time
3 Bias/Gain Station (BG) 0 Execution (msec) 24 LAS Capable: Yes No
Manual Loader (ML) 0 Number 25 Device Current Draw (mA): 19
4
0 Execution (msec) Device Minimum Voltage: 9.
26
Analog Output Block (AO) 1 Number Device Capacitance: 5 nF
5 20 Execution (msec) Polarity-sensitive: Yes No
27
Discrete Output Block (DO) 1 Number Segment Terminator Location:
6 20 Execution (msec)
28
7 Control Selector (CS)
DD Revision: 3
PID,PI,I Controller (PID) 29
8
20 Execution (msec)
CFF Revision: 1.9
Ratio Station (RA) 30
9
P,PD Controller (PD) 0 Number
10 0 Execution (msec)

* Execution time in msec.

Advanced Function Blocks Notes:

11 Device Control (DC)

12 Output Splitter (OS)

13 Signal Characterizer (SC)

14 Lead Lag (LL)

15 Deadtime (DT)

16 Integrator(Totalizer) (IT)

17 Setpoint Ramp Generator (SPG)

18 Input Selector (IS)

19 Arithmetic (AR)

20 Timer (TMR)

21 Analog Alarm (AAL)

INSTRUMENT SPECIFICATION -FOUNDATION FIELDBUS


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S123.2 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00206 Rev.: 1
Tag Number : TV -21612

1. In-Built surge protector is provided by vendor.

1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/28/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S123.3 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00206 Rev.: 1
1 Tag No. PV -21522A
2 Service FA502 DRY GAS TO FG
3 P&ID No. Line No. R2B-P3-206-02-A-DTI-00503 10"-GD-212405-T-A03T1-N
4 Area Classification Ingress Protection CLASS 1 DIV 2 Gr. B ,C&D, T3 NEMA 4X
GENERAL 5 Ambient Temperature: Unit Min. Max. °C 10 48
6 Allowable Sound dBA Tightness Requirement <85 ANSI IV (standard)
7 Available Air Supply Pressure Unit Min. Max. kgf/cm²-g 4.2 8.0
8 Electric Connection Pneum. Connection 1/2” NPT (F) 1/4” NPT (F)
9 Power Failure Position FC
10 Line Size and Schedule Sch. Outlet Line Sch. 10 in STD 10" STD
PIPE
11 Line Class Rating Pipe Material T-A03T1 150# A106 GR.B, SMLS
LINE
12 Pipe Insulation Thickness Corrosion Allowance N N/A 1.6mm
13 Fluid State Phase Hydrocarbon Gas/Vapor Single Phase
14 Sour Service Special Condition N/A N/A
15 Flow Rate Units Min. Nor. Max. Nm³/h 12864 25728 28301
16 Inlet Pressure Units Min. Nor. Max. kgf/cm²-g 12.46 12.42 12.4
17 Pressure Drop Units Min. Nor. Max. kgf/cm² 4.89 4.621 4.547
18 Inlet Temperature Units Min. Nor. Max. °C 38 38 38
PROCESS 19 Density Units Min. Nor. Max. kg/m³
CONDITIONS 20 Viscosity Units Min. Nor. Max. cP 0.012 0.012 0.012
21 Molecular Weight (MW) Specific Gravity @ Oper. 22
22 Spec. Heat Ratio (Cp/Cv) Compressibility (Z) 1.303 0.966
23 Vapor Pressure (Liq.) Cavitation or Flashing kgf/cm²-a N/A
24 Critical Pressure (Liq) Flash (wt%) kgf/cm²-a
25 Design Pressure Min. Max. kgf/cm²-g 16 kgf/cm²-g
26 Design Temperature Min. Max. 10 °C 70 °C
27 Max.Shutoff DP Solid % 16 kgf/cm²
28 Calculated Cv Units Min. Nor. Max. Cv 89.1 197 216
CALCULATED
29 Travel Units Min. Nor. Max. % 25 53 58
RESULTS
30 Noise dBA @1m Units Min. Nor. Max. dBA 78 83 83
31 MFR Model FISHER EWT 56 MFR Model FISHER DVC6200F/SC-AD
32 Body Type Single Seat Globe 57 Signal: Inlet Outlet FF Protocol 0-2.8 kgf/cm2
33 Body Size Trim Size 6 in 4 3/8 in 58 Increase Signal Valve: DIRECT
34 End Connec.Size & Rating 6" 300# RF POSITIONER 59 Cam Characteristic LINEAR
35 Rated Cv Characteristic 325 Linear 60 Bypass Gauges N/A YES
36 Body Material WCC Steel 61 Signal Fail. to Valve FC
BODY 37 Bonnet Type Material Plain WCC Steel 62 Electric Enclosure Ex ia IIC T5 , NEMA 4X
AND 38 Flow Direct. Flow Act. To Up FTC 63 MFR Model N/A N/A
TRIM 39 Packing Type Material ISO Seal PTFE 64 Type Power N/A N/A
SOLENOID
40 Lubricator Isolat. Valve N/A N/A 65 When De-Enegr.Valve: N/A
VALVE
41 Guiding No. of Ports Cage 1 66 Material Latcher N/A N/A
42 Trim Type Internal Design Whisper I Balanced 67 Electric Enclosure N/A
43 Rated Travel Leak Class 2 in ANSI IV 68 MFR Model N/A N/A
44 Plug/ Ball/ Disk Material S41600 SST 69 Type Quantity N/A N/A
45 Seat Material S41600 SST SWITCHES 70 Contacts / Rating N/A
46 Cage Stem Material CB7Cu-1 SST S31600 SST 71 Switching Position N/A
47 Gasket Material S31600 SST/Graphite 72 Electric Enclosure N/A
48 MFR Model FISHER 667 73 MFR Model FISHER 67CFR
49 Type Diaphragm Spring Return AIR SET 74 Set Pressure 4.2 kgf/cm2-g
50 Size Stroke Time 45i < 10 Sec 75 Filter Gauge 5 Micron min YES
ACTUATOR 51 Air Failure Valve: FC 76 Vol. Tank Booster NO NO
52 Handwheel Location N/A 77 Diffuser Lock-up NO NO
ACCESSORY
53 Mounting Position VERTICAL 78 Fire Safe Fireproof NO NO
54 Spring Range 0.8 - 2.5 kgf/cm2-g 79 Mech. Stop Quick Exa. NO NO
55 Include Pressure (Shutoff) 80 Hydro. Pressure YES
85 Vendor EMERSON 81 Leakage YES
PURCHASE TESTS
86 Manufacturer FISHER 82 Cryogenic N/A
87 Requisition No. R2B-P3-206-02-P-MR-00200 83 NACE Requirement N/A
88 Model No. EWT 84 PWHT Requirement N/A
Notes:

INSTRUMENT SPECIFICATION - CONTROL VALVE


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/29/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S124.1 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Fieldbus Device Data Sheet
Tag No.: PV -21522A
Fieldbus Tag No.:

Service : FA502 DRY GAS TO FG

Basic Fieldbus Function Blocks Segment Information


Analog Input Block (AI) 1 Number Device:
1 22
20 Execution (msec)
Discrete Input Block (DI) 4 Number Segment #: DFJB-21123
2 23
15 Execution Time
3 Bias/Gain Station (BG) 0 Execution (msec) 24 LAS Capable: Yes No
Manual Loader (ML) 0 Number 25 Device Current Draw (mA): 19
4
0 Execution (msec) Device Minimum Voltage: 9.
26
Analog Output Block (AO) 1 Number Device Capacitance: 5 nF
5 20 Execution (msec) Polarity-sensitive: Yes No
27
Discrete Output Block (DO) 1 Number Segment Terminator Location:
6 20 Execution (msec)
28
7 Control Selector (CS)
DD Revision: 3
PID,PI,I Controller (PID) 29
8
20 Execution (msec)
CFF Revision: 1.9
Ratio Station (RA) 30
9
P,PD Controller (PD) 0 Number
10 0 Execution (msec)

* Execution time in msec.

Advanced Function Blocks Notes:

11 Device Control (DC)

12 Output Splitter (OS)

13 Signal Characterizer (SC)

14 Lead Lag (LL)

15 Deadtime (DT)

16 Integrator(Totalizer) (IT)

17 Setpoint Ramp Generator (SPG)

18 Input Selector (IS)

19 Arithmetic (AR)

20 Timer (TMR)

21 Analog Alarm (AAL)

INSTRUMENT SPECIFICATION -FOUNDATION FIELDBUS


1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/29/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S124.2 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1
Tag Number : PV -21522A

1. In-Built surge protector is provided by vendor.

1 DHA SBP KHL 4/22/2022 ISSUED FOR CONSTRUCTION Project name:DOS BOCAS NEW REFINERY
0 DHA JHP KHL 8/11/2021 ISSUED FOR CONSTRUCTION Project number: SO6625
C DHA JHP KHL 4/12/2021 ISSUED FOR REVIEW Client.:PTI-ID
B DHK JHP KHL 5/29/2020 ISSUED FOR REVIEW Loc.:DOS Bocas, Paraiso, Tabasco
A HHL JHP KHL 12/19/2019 ISSUED FOR REVIEW Code: 177 Sheet S124.3 of 375
No. By Chk Appr Date Description Doc.No.: R2B-P3-206-02-P-HD-00200 Rev.: 1