Timing test C1 (Close test)

General parameters Testing device settings


Execution date/Time 2/12/2020 / 10:19 AM Device model / Serial-no SACE E6.2H / BM35000211
Coil supply voltage 125 V Transducer type Digital transducer
Measuring time 700 ms Transducer on CBs phase-s All three
Command pulse 133.3 ms Transducer transfer functions 0mm:0deg
Resolution 0.1 ms Trigger source
Frequency 60 Hz BSG mode

Main contacts timing


Designation Min Max Value Unit Pass/Check
Close time(tc) 0 0 76.8 ms -
Close time sync(dtc) 0 0 0.6 ms -

Coil currents
Coil Min Max Closing coil 1 Closing coil 2 Closing coil 3 Unit Pass/Check
Max current value 0 0 3.96 0.101 0.144 A -
Max current time 0 0 45.9 46.5 46.5 ms -

Test lab FRAVY Date 2/16/2020 Test engineer ZOVN


Timing test CO1 (Close-Open test)
General parameters Testing device settings
Execution date/Time 2/12/2020 / 10:28 AM Device model / Serial-no SACE E6.2H / BM35000211
Coil supply voltage 125 V Transducer type Digital transducer
Measuring time 700 ms Transducer on CBs phase-s All three
Command pulse ms Transducer transfer functions 0mm:0deg
Resolution 0.1 ms Trigger source
Frequency 60 Hz BSG mode

Main contacts timing


Designation Min Max Value Unit Pass/Check
Close time(tc) 0 0 73.6 ms -
Close time sync(dtc) 0 0 0.6 ms -
Close-Open time(tco) 0 0 11.7 ms -
Breaker O sync 0 0 0.4 ms -

Test lab FRAVY Date 2/16/2020 Test engineer ZOVN Page 1 of 1


Timing test O1 (Open test)
General parameters Testing device settings
Execution date/Time 2/12/2020 / 10:25 AM Device model / Serial-no SACE E6.2H / BM35000211
Coil supply voltage 125 V Transducer type Digital transducer
Measuring time 700 ms Transducer on CBs phase-s All three
Command pulse 80 ms Transducer transfer functions 0mm:0deg
Resolution 0.1 ms Trigger source
Frequency 60 Hz BSG mode

Main contacts timing


Designation Min Max Value Unit Pass/Check
Open time(to) 0 0 48.8 ms -
Open time sync(dto) 0 0 0.3 ms -

Coil currents
Coil Min Max Opening coil 1 Opening coil 2 Opening coil 3 Unit Pass/Check
Max current value 0 0 4.083 0 0 A -
Max current time 0 0 46.2 0 0 ms -

Test lab FRAVY Date 2/16/2020 Test engineer ZOVN Page 1 of 1


Timing test OCO1 (Open-Close-Open test)
General parameters Testing device settings
Execution date/Time 2/12/2020 / 10:44 AM Device model / Serial-no SACE E6.2H / BM35000211
Coil supply voltage 125 V Transducer type Digital transducer
Measuring time 700 ms Transducer on CBs phase-s All three
Command pulse ms Transducer transfer functions 0mm:0deg
Resolution 0.1 ms Trigger source
Frequency 60 Hz BSG mode

Main contacts timing


Designation Min Max Value Unit Pass/Check
Open time(to) 0 0 47.5 ms -
Reclosing time 0 0 374.2 ms -
Reclosing time sync 0 0 0.6 ms -
O1 sync time 0 0 0.3 ms -
O2 sync time 0 0 0.5 ms -
Open-Close time(toc) 0 0 326.1 ms -
Close-Open time(tco) 0 0 12 ms -

Test lab FRAVY Date 2/16/2020 Test engineer ZOVN Page 1 of 1


SRM1 (Static Resistance Measurement test)
General parameters Testing device settings
Test current 100 A Breaking unit A

Breaking unit Test current [A] Total current [A] Voltage [mV] Min Max Resistance [µΩ] Pass/Check

A 0 0 2.3355 0 0 23.4 -

Test lab FRAVY Date 2/16/2020 Test engineer ZOVN Page 1 of 1


SRM1 (Static Resistance Measurement test)
General parameters Testing device settings
Test current 100 A Breaking unit B

Breaking unit Test current [A] Total current [A] Voltage [mV] Min Max Resistance [µΩ] Pass/Check

B 0 0 2.4016 0 0 24 -

Test lab FRAVY Date 2/16/2020 Test engineer ZOVN Page 1 of 1


SRM1 (Static Resistance Measurement test)
General parameters Testing device settings
Test current 100 A Breaking unit C

Breaking unit Test current [A] Total current [A] Voltage [mV] Min Max Resistance [µΩ] Pass/Check

C 0 0 2.3316 0 0 23.3 -

Test lab FRAVY Date 2/16/2020 Test engineer ZOVN Page 1 of 1