Coil currents
Coil Min Max Closing coil 1 Closing coil 2 Closing coil 3 Unit Pass/Check
Max current value 0 0 3.96 0.101 0.144 A -
Max current time 0 0 45.9 46.5 46.5 ms -
Coil currents
Coil Min Max Opening coil 1 Opening coil 2 Opening coil 3 Unit Pass/Check
Max current value 0 0 4.083 0 0 A -
Max current time 0 0 46.2 0 0 ms -
Breaking unit Test current [A] Total current [A] Voltage [mV] Min Max Resistance [µΩ] Pass/Check
A 0 0 2.3355 0 0 23.4 -
Breaking unit Test current [A] Total current [A] Voltage [mV] Min Max Resistance [µΩ] Pass/Check
B 0 0 2.4016 0 0 24 -
Breaking unit Test current [A] Total current [A] Voltage [mV] Min Max Resistance [µΩ] Pass/Check
C 0 0 2.3316 0 0 23.3 -