● Run CPU

TCD - 020 Speed CPU Communication data ERROR


Point of Application ● DI120~150
detection ○ Speed CPU ● DI180~420

[Meaning] [Action to take]


Run CPU communicates with Speed CPU to get Normal data area through
DPRAM.In case that the sum of all the normal data differ from 1. Check +5[V] .
NORMAL_SUM DATA continuously more than 5 times When Run CPU Read It should be more than +4.8[V].
the Normal data which is sent from Speed CPU. 1) DOC-200 PCB : +5[V] => Connector MG/1, MG/6
GND => TP16(above of MG Connector)
2) DOR-230 PCB : +5[V] => Connector SMP/1, SMP/6
GND => TP10 above of OUT Connector)
[Explanation] .3) DPC-1XX PCB : +5[V] => Connector VF/1
NORMAL DATA AREA GND => Connector VF/4, VF/5

RIC_Current_V 2. Check the Joint condition of DOR-230 PCB CONNECTOR.


RIC_Dup_In Check the connection cable contact condition
among PCBs(MA, VE)
RIC_XC9A 3. Check the SW1, Sw2 position on DOR-230 PCB.
READ WRITE
RIC_XC9B
4. Try to replace the DOR-230, DPC-1XX(or 300), DOC-200
RIC_XR9B
in sequence.
RIC_XR9S

RIC_Inv_Err2

RUN A RIC_Inv_Err
RUN SPEED
RIC_Cnv_Err
SPEED
CPU CPU
CPU CPU
RIC_Main_Spec_Sum_Err

RIC_Main_Normal_Sum_Err

RIC_Main_Sync_Err

RIC_Main_Err

RIC_Main_Retry_Err

RIC_INV_ENCO
B RIC_Normal_Com_Sum

TCD 20 will displayed in case the sum of A is different from


RIC_Normal_Com_Sum of B continuously 5 times