Download as pdf or txt
Download as pdf or txt
You are on page 1of 23

Clivet-2003-1C2001

Clivet-2003-1C2004

Air Cooled Module Chiller & Mini Chiller


Commercial Air Conditioners 2020

CLIVET SPA
Via Camp Lonc 25, Z.I. Villapaiera - 32032 Feltre (BL) - Italy
Tel. + 39 0439 3131 - Fax + 39 0439 313300 - info@clivet.it

CLIVET RUSSIA
Elektrozavodskaya st. 24, office 509 - 107023, Moscow, Russia
Tel. + 74956462009 - Fax + 74956462009 - info.ru@clivet.com

CLIVET MIDEAST FZCO


Dubai Silicon Oasis (DSO), High Bay Complex, Office No. 20, PO BOX 342009, Dubai, UAE
Tel. + 9714 3208499 - Fax + 9714 3208216 - info@clivet.ae

CLIVET AIRCONDITIONING SYSTEMS PRIVATE LIMITED


4BA, Gundecha Onclave, Kherani Road - Sakinaka, Andheri (East) - Mumbai 400 072 - India
Tel. +91 22 6193 7000 - Fax +91 22 6193 7001 - info.in@clivet.com
w w w. c l i ve t . co m
w w w.c livetlive. co m

A Group Company of
Always ready for the Future Clivet. Change things
40 75 2016
agencies in Italy
630 countries we export to
A Group Company of
employees in Italy
and abroad
2015
Clivet Live is born
50.000 m² 6 Midea Group
FORTUNE GLOBAL 500

#323 in 2018
of plants in Feltre,
Belluno - Italy branches: Great Britain, Germany, Spain, 140
service centres 39.5 $M
Russia, UAE, India Midea turnover

For 30 years we have been Our values


Increasing comfort, saving energy and providing customers with
In 30 years of working on the design, manufacturing and the best value for the entire life cycle of the system: these are the
distribution of air conditioning and handling systems,
offering solutions in the residential,
values that inspire our systems for the residential, services and
combining
high efficiency with minimal environmental impact, industrial sectors.

to ensure sustainable Clivet has


developed solutions to ensure sustainable comfort and
the
commercial and industrial
comfort and the well-being of people and the environment.
Designing and developing year-round air conditioning sectors
well-being of people and solutions
with innovative technologies are part of Clivet's DNA,
which means
the environment the company has always been ready for the future.

01 02
Contents

ELFOEnergy SPARK SERIES

ELFOEnergy NOVA SERIES

ELFOEnergy NOVA II SERIES

ELFOEnergy MINI CHILLER SERIES

03 04
Features

WIDE APPLICATION RANGE

ELFOEnergy Spark Chillers with cooling capacity ranging from 180kW to 250kW, combination model’s maximum capacity ups
to 2000kW.

Max 8 modules
ELFOEnergy Spark SERIES

ELFOEnergy Spark SERIES


250kW 250kW 2000kW

Freely combine with fan coil units and air handling units. Project owners may choose the best types according to their design
taste (for interior) or functional needs.

Cassette type

Air handling units

Celling & Floor

Duct type

Modular Air Handing Unit


Wall mounted

ELFOEnergy Spark SERIES Wide ambient temperature and water outlet temperature operation ranges

PS Series PS-LA Series PS Series & PS-LA Series

60°C
Cooling
52°C Cooling 70°C

Product lineup 50°C 46°C


60°C Heating
50°C
40°C 50°C
Heating Heating
30°C 21°C 24°C 40°C

Power 20°C 30°C


Series Cooling
supply
10°C 20°C 17°C
10°C 22°C
0°C 10°C

-10°C 5°C
SS 380V/3N/50Hz 180kW / 250kW -10°C -10°C
-10°C
-20°C 0°C
0°C
SS-LA 380V/3N/50Hz / 200kW / -25°C

SS: Standard Spark Series Ambient temperature operation range Water outlet temperature operation range
SS-LA: Spark Series with low ambient temperature cooling function

05 06
ADVANCED TECHNOLOGY HIGH RELIABILITY

Alternative cycle duty operation


High performance heat exchanger In one combination module, all slave units operate as alternative in cycle duty to keep equal running time, realize higher stability,
better reliability and longer lifespan.
Reduce air resistance
For example, eight modules combination, no.1 is master unit, others are slave units.

Master unit Master unit

Original design
ELFOEnergy Spark SERIES

ELFOEnergy Spark SERIES


New design High efficiency inner-threaded pipe, Hydrophilic fins + inner-threaded pipes
enhance heat transfer.

The new designed window fins enlarge the heat-exchanging area, decrease the air resistance, save more power and enhance heat 1
1 ……
2
5
exchange performance. 3
6
4
Hydrophilic film fins and inner-threaded copper pipes optimize heat exchange efficiency. ……
7
8
The specially coated blue fins enhance durability and protect against corrosion from air, water and other corrosive agents, assures 8

a longer coil service life.


Loading in sequence Offloading in sequence
Shell-tube heat exchanger

Back-up functions

In a combination system, if one module failed, other modules can be back-up instead of the failed one for continuing operation.

Master Slave
Water dead zone
Flat baffle plate

Refrigerant outlet

Helical baffle Master Slave

For shell-tube heat exchanger, the module adopts the new helical baffle design to avoid the rectangular place of water dead
zone, greatly improve the heat exchange efficiency.

EXV for more precisely flow control


Reliable protections
Patented liquid distribution components to maximize performance and minimize defrost impact. Multiple protections are adopted to ensure system stable running.
500 steps EXV plus capillary for stable and accurate gas flow control.
Fast respond resulting in higher efficiency and improved reliability.

100% High/low pressure Power phases Evaporator low temperature System anti-freezing Frequently ON/OFF
protection of sequence protection protection in cooling protection in winter protection of compressor
75% compressor

50%

25%
Over-current Air discharge temperature System high temperature Water flow protection Sensor malfunction
0%
protection protection of compressor protection protection
of compressor

07 08
Intelligent defrosting technology Modbus function

Model alternative defrosting technology ensures little fluctuation on water temperature.


Modbus is an open protocol that is widely used, especially in BMS building control systems. Modbus function can be customized
Manual defrosting program is available for service purpose.
by adding X, Y, E ports on wired controller KJRM-120D/BMK-E. It can connect Max. 16 wired controllers and each controller can
control Max. 8 units.

Clivet Fast Defrosting Traditional defrosting

Max. 16 wired
controllers (P Q E) Max. 8 units
ELFOEnergy Spark SERIES

ELFOEnergy Spark SERIES


Heating capacity

(X Y E)(Modbus protocol)

(P Q E) Max. 8 units
T min Time
saving

Time
7 minutes less!

EASY CONTROL

Computer
Touch key wire controller as standard accessory to control the chillers.

Remote control functions for convenient operation.


There are ON/OFF, Heat/Cool and Alarm terminals ports on PCB, connect switches from these terminal ports and remote
control functions can be easily realized.

Model KJRM-120D/BMK-E(standard) KJR-120A/MBTE(optional)

Appearance

Touch key operation Mechanical butoon


Parameter setting and LCD display Parameter setting and LCD display
Real time clock control. Real time clock control.
Multiple timer Multiple timer
Main Functions Power-off memory function Power-off memory function Note: When use the remote control function, the wired controller will be invalid for ON/OFF and mode selection.
Modbus(Customized) Modbus(Customized)
Address setting Address setting
Parallel function Parallel function
Buzzer prompt tone and alarm function Weekly timing function

Max. connection PCBs 16 16

09 10
Specifications Dimensions (Unit:mm)
Model WCAN-XTP 200.6T WCAN-XTP 180.6T WCAN-XTP 250.8T
Series PS-LA PS PS
WCAN-XTP 180.6T
Power supply V/Ph/Hz 380-415/3/50 380-415/3/50 380-415/3/50 WCAN-XTP 200.6T
Capacity kW 185 180 250

Cooling 1
Input kW 63.0 57.9 78.3

EER 2.94 3.11 3.19

Capacity kW / 156 216

Cooling2 Input kW / 64.5 86.3


ELFOEnergy Spark SERIES

ELFOEnergy Spark SERIES


EER / 2.42 2.50

C
Capacity kW 200 195 270 B
Heating 3 Input kW 61.0 59.4 80.0

COP 3.28 3.28 3.38

E
Max. running current A 150 155.1 200.0

Type Fixed Scroll Fixed Scroll Fixed Scroll


Compressor Quantity Pieces 6 6 8 D F A
Type Fin-coil Finned tube Finned tube

Fan motor type AC Motor AC Motor AC Motor


Air side heat Qualitity of
Pieces 6 6 8
exchanger fan motor
Air flow m3/h 72,000 72,000 96,000
WCAN-XTP 250.8T

Type Shell-tube Shell-tube Shell-tube


Water kPa 30
pressure drop 30 40
Water side
Volume L 99.5 99.5 127
heat exchanger
Water flow volume m3/h 31.8 31 43

Type R410A R410A R410A B

C
Charged volume kg 42.0 39.0 60.0
Refrigerant
Throttle type EXV EXV EXV

E
Sound pressurer level 4
dB(A) 74 74 74

Unit net dimension(D×H×W) mm 2,850×2,110×2,000 2,850×2,110×2,000 3,800×2,130×2,000

Packing dimension(D×H×W) mm 2,980×2,260×2,135 2,980×2,260×2,135 3,900×2,200×2,100 D F A


Net/ Gross weight kg 1730/2,000 1,730/2,000 2,450/2,600

Pipe connections Water inlet/outlet mm DN80 DN80 DN100

Controller Wired controller Wired controller Wired controller


Model A B C D E F
Maximum combinations 5 5 8

Ambient temperature Cooling °C -10~46 10~52 10~52


range WCAN-XTP 180.6T 2850 2000 2110 347 506 2156
Heating °C -10~24 -10~21 -10~21

Water outlet Cooling °C 5~17 5~17 5~17


temperature range
Heating °C 40~50 45~50 45~50 WCAN-XTP 200.6T 2850 2000 2110 347 506 2156

Cooling °C 0~17 0~17(customized) 0~17


Water outlet
temperature range5 WCAN-XTP 250.8T 3800 2000 2130 1235 573 2156
Heating °C 22~50 22~50(customized) 22~50

Note:
1. Cooling: Water inlet/outlet: 12°C / 7°C, outdoor ambient temp. of 35°C DB.
2. Cooling: Water inlet/outlet: 12°C / 7°C, outdoor ambient temp. of 46°C DB.
3. Heating: Water inlet/outlet: 40°C/ 45°C, outdoor ambient temp. 7°C DB/6°C WB.
4. 1m away in open field.
5. The data is for low water outlet temperature function. Under the using condition of this function, the system must be added antifreeze agent.

11 12
Features
WIDE APPLICATION RANGE

ELFOEnergy Nova chillers with cooling capacity ranging from 35kW to130kW, combination model’s maximum capacity ups to
2080kW.

130kW 130kW 2080kW


Max 16 modules

Freely combine with fan oil units and air handling units. Home owners may choose the best types according to their functional
needs.
ELFOEnergy Nova Series

ELFOEnergy Nova Series


Wall mounted Floor standing

Duct type Cassette type

ELFOEnergy Nova Series


Celling & Floor Air handling units

Wide ambient temperature and water outlet temperature operation ranges


Product lineup

60°C Cooling 70°C

Capacity (kW) 35 65 80 130 50°C 46°C Heating


60°C
50°C
40°C 50°C
Appearance Heating
30°C 24°C 40°C

20°C 30°C
Series Cooling
10°C 20°C 25°C 17°C

NS-LA 0°C 10°C

-10°C 5°C
-10°C
NS-LA: Nova series with low ambient temperature cooling function -15°C
-20°C 0°C
0°C
-25°C

Ambient temperature operation range Water outlet temperature operation range

13 14
ADVANCED TECHNOLOGY EXV for more precisely flow control
Patented liquid distribution components to maximize performance and minimize defrost impact.
H shape high performance heat exchanger 500 steps EXV plus capillary for stable and accurate gas flow control.
The chillers use new structure design, H shape condenser, 360°air intake, increase the heat exchanging area, efficiently enhance Fast respond resulting in higher efficiency and improved reliability.
the heat exchange efficiency, and decrease the covering area.
100%

75%

50%

25%

0%

Newly designed air profile


Big air flow lower noise 1

Tube-in-tube & shell-tube heat exchanger

360° Condenser coil


High efficiency
ELFOEnergy Nova Series

ELFOEnergy Nova Series


2

Removable panel
Easy to maintain 3 Inner-threaded copper pipe

Anti-corrosion materials
Transportation hole
Easy to install 4
5 Multi folder frame
Nice and strong
Inner grooved copper pipe, increase area of heat exchanger, improve efficient.
Anti-corrosion shell increases the useful life of heat exchanger.

H shape condenser uses inner grooved copper tube and hydrophilic aluminum foil, greatly improve the heat exchange efficiency.
Chilled water inlet
Refrigerant inlet

High performance heat exchanger Water dead zone


Flat baffle plate
Reduce air resistance
Chilled water outlet
Refrigerant outlet

Helical baffle

Original design
For shell-tube heat exchanger, the module adopts the new helical baffle design to avoid the rectangular place of water dead
New design High efficiency inner-threaded pipe, Hydrophilic fins + inner-threaded pipes
enhance heat transfer. zone, greatly improve the heat exchange efficiency.

The new designed window fins enlarge the heat-exchanging area, decrease the air resistance, save more power and enhance
heat exchange performance.
Hydrophilic film fins and inner-threaded copper pipes optimize heat exchange efficiency.
The specially coated blue fins enhance durability and protect against corrosion from air, water and other corrosive agents, assures
a longer coil service life.

15 16
HIGH RELIABILITY Intelligent defrosting technology
Model alternative defrosting technology ensures little fluctuation on water temperature.
Alternative cycle duty operation Manual defrosting program is available for service purpose.
In one combination module, all slave units operate as alternative in cycle duty to keep equal running time, realize higher stability,
Traditional defrosting
better reliability and longer lifespan. Clivet Fast Defrosting

For example, 16 modules combination, no.1 is master unit, others are slave units.

Master unit Master unit

Heating capacity
T min Time
saving

1
1 …… Time
2
13 7 minutes less!
3
14
4 ……
16
15 FLEXIBLE INSTALLATION
16

Compact structure design


Loading in sequence Offloading in sequence Nova power chiller uses compact structure design, light weight, easy for transportation and installation.

Big air flow but low noise fan


ELFOEnergy Nova Series

ELFOEnergy Nova Series


Back-up functions
Big torque high efficiency fan motor
In a combination system, if one module failed, other modules can be back-up instead of the failed one for continuing operation.
1
Master Slave
Inner grooved copper tube
Capacity & efficiency increase

EXV 7
500 steps
Control box
Easy to maintain
Helical baffle
Efficiency increase 10%
6
2
Master Slave Multi folder frame
Low vibration. 5
Durable and stable Scroll compressor
3 High efficiency
4 Low noise

Compact design saves space and transportation cost.

Reliable protections

Multiple protections are adopted to ensure system stable running.

High/low pressure Power phases Evaporator low temperature System anti-freezing Frequently ON/OFF
protection of sequence protection protection in cooling protection in winter protection of compressor
compressor

Over-current Discharge temperature System high temperature Water flow protection Sensor malfunction
protection protection of compressor protection protection
of compressor

17 18
EASY CONTROL Modbus function

Touch key wire controller as standard accessory to control the chillers. Modbus is an open protocol that is widely used, especially in BMS building control systems. Modbus function can be customized
by adding X, Y, E ports on wired controller KJRM-120D/BMK-E. It can connect Max. 16 wired controllers and each controller can
control Max. 16 units.

Max. 16 wired
controllers (P Q E) Max. 16 units

(X Y E)(Modbus protocol)

(P Q E) Max. 16 units

Computer
ELFOEnergy Nova Series

ELFOEnergy Nova Series


Remote control functions for convenient operation

Model KJRM-120D/BMK-E(standard) KJR-120A/MBTE(optional)


There are ON/OFF, Heat/Cool and Alarm terminals ports on PCB, connect switches from these terminal ports and remote control
functions can be easily realized.

Appearance

Touch key operation Mechanical butoon


Parameter setting and LCD display Parameter setting and LCD display
Real time clock control. Real time clock control.
Multiple timer Multiple timer
Main Functions Power-off memory function Power-off memory function
Modbus(Customized) Modbus(Customized)
Address setting Address setting
Parallel function Parallel function
Buzzer prompt tone and alarm function Weekly timing function

Max. connection PCBs 16 16

Note: When use the remote control function, the wired controller will be invalid for ON/OFF and mode selection.

19 20
Specifications Dimensions (Unit:mm)

WCAN-XTS 35.1T WCAN-XTS 65.1T


WCAN-XTS 80.2T
Model WCAN-XTS 35.1T WCAN-XTS 65.1T WCAN-XTS 80.2T WCAN-XTS 130.2T

Series SS-LA SS-LA SS-LA SS-LA

Power supply V/Ph/Hz 380-415/3/50 380-415/3/50 380-415/3/50 380-415/3/50

Capacity kW 35 65 80 130

Cooling1 Input kW 11.5 20.4 25.8 42.3

EER 3.04 3.19 3.10 3.07

Capacity kW 37 69 85 138 D F

C
Heating 2
Input kW 11.3 21.5 26.5 43

COP 3.27 3.21 3.21 3.21

Max. running current A 27.0 54.5 65 109

Type Fixed Scroll Fixed Scroll Fixed Scroll Fixed Scroll

E
Compressor

E
Quantity Pieces 1 1 2 2

Type Finned tube Finned tube Finned tube Finned tube D F


ELFOEnergy Nova Series

ELFOEnergy Nova Series


Air side heat Fan motor type AC Motor AC Motor AC Motor AC Motor
exchanger
Qualitity of fan motor Pieces 1 2 2 2

Air flow m3/h 13,500 27,000 27,000 50,000

Type Tube-in-tube Shell-tube Shell-tube Shell-tube

B
Water side heat Water pressure drop kPa 55 30 30 40

B
exchanger
Volume L 10 35 47.5 60

Water flow volume m3/h 6 11.2 13.8 22.4

Type R410A R410A R410A R410A A


Refrigerant Charged volume kg 5.4 10.5 13 21
A
Throttle type EXV EXV EXV EXV

Sound pressurer level 3 dB(A) 65 67 67 68 WCAN-XTS 130.2T


Unit net dimension(D×H×W) mm 1,020×1,770×980 2,000×1,770×960 2,000×1,770×960 2,200×2,060×1,120

Packing dimension(D×H×W) mm 1,070×1,900×1,030 2,090×1,890×1,030 2,090×1,890×1,030 2,250×2,200×1,180

Net/Gross weight kg 320/330 530/590 645/710 965/1,035

Pipe connections Water inlet/outlet mm DN40 DN65 DN65 DN65

C
Controller Wired controller Wired controller Wired controller Wired controller

B
Cooling °C -10~46 -10~46 -10~46 -10~46
Ambient temperature
range Heating °C -15~24 -15~24 -15~24 -15~24 D F
A
Water outlet Cooling °C 5~17 5~17 5~17 5~17
temperature range Heating E
°C 40~50 40~50 40~50 40~50
Cooling °C 0~17 0~17 0~17 0~17
Water outlet
temperature range4 Heating Model A B C D E F
°C 25~50 25~50 25~50 25~50

WCAN-XTS 35.1T 1020 980 1770 237 250 400


1. Cooling: Chilled water inlet/outlet temperature: 12/7°C, outdoor ambient temperature 35°C DB.
2. Heating: Warm water inlet/outlet temperature: 40/45°C, outdoor ambient temperature 7°C DB/6°C WB.
3. 1m away in open field. WCAN-XTS 65.1T
4. The data is for low water outlet temperature function 2000 960 1770 336 506 1420
WCAN-XTS 80.2T

WCAN-XTS 130.2T 2200 1120 2060 390 347 1420

21 22
High Efficiency
A++ RATED ENERGY EFFICIENCY

ELFOEnergy Tempo Nova II Series DC inverter air-cooled chillers are compliant with the EU’s Energy-Related Products Directive
(2009/125/EC) and all have A++ or A+ seasonal space heating energy efficiency ratings.

COMPRESSOR

At the heart of the chiller lies a world-leading DC inverter compressor. The compressor’s innovative design and numerous high
performance features reduce power consumption by 25%.
ELFOEnergy Nova II Series

ELFOEnergy Nova II Series


Twin rotary structure High efficiency DC motor

ELFOEnergy Nova II Series Highly stable moving parts


Better balance and
extremely low vibration

Product lineup
Capacity(kW) 30 60 90 Compressor for WCAN-XSi 14.1, WCAN-XSi 22.2

New structure enhances


More compact, weight
mid-frequency performance
reduced by 50%

Appearance
Advanced permanent
magnet DC motor improves low
Specially designed
frequency band performance
scroll profile for R410A

380-415V/3Ph/50Hz

R410A (With/Without hydraulic module)


Compressor for WCAN-XSi 35.2

23 24
DC FAN MOTORS HIGH EFFICIENCY PLATE HEAT EXCHANGER

Fan speed is controlled according to the system pressure and system load, reducing power consumption by 30%.There are Plate heat exchanger uses metal plates to transfer heat between refrigerant and water. The fluids are exposed to a much larger
32-step vector control for Nova Ⅱ models. surface area because the fluids spread out over the plates, so both heat transfer efficiency and heat exchanger speed are greatly
improved. Multi protections including voltage protection, current protection, anti-freezing protection and water flow protection
ensure system safety running.
Refrigerant inlet

High Water outlet

Low

Water inlet
HIGH PERFORMANCE HEAT EXCHANGER
Refrigerant outlet

Reduce air resistance


PLATE HEAT EXCHANGER SUBCOOLING

For WCAN-XSi 35.2, plate heat exchanger as a secondary intercooler boosts up refrigerant subcooling and
improves 10% energy efficiency.

Original design
New design High efficiency inner-threaded pipe, Hydrophilic fins + inner-threaded pipes
enhance heat transfer.

Chillers use new structure design "I shape" condenser. The manufacturing process of Ⅰshape heat exchanger is simple, which
ELFOEnergy Nova II Series

ELFOEnergy Nova II Series


increases production efficiency and product reliability.
The new designed window fins enlarge the heat-exchanging area, decrease the air resistance, save more power and enhance
heat exchange performance.
Hydrophilic film fins and inner-threaded copper pipes optimize heat exchange efficiency.
The specially coated blue fins enhance durability and protect against corrosion from air, water and other corrosive agents,
assures a longer coil service life. 2nd stage
1st stage

HIGH PERFORMANCE HEAT EXCHANGER DESIGN

PRECISELY FLOW CONTROL

Patented liquid distribution components maximize performance and minimize impact of defrosting operation. 500-step EXV with
capillary tube allows stable and accurate gas flow control. Fast response results in higher efficiency and improved reliability.

100%

75%

50%

25%

Efficient fan motor, well-designed air duct and uniform wind field make heat exchange of the whole system more thorough.
0%

25 26
Wide Application Range Advanced Technology

FLEXIBILITY LOADING AND OFFLOADING

Modular design allows up to 16 units to be connected together, giving a system cooling/heating capacity range of 30kW to Loading and offloading for multiple units system
1440kW.

Master unit Master unit

90kW 90kW 1440kW


Max 16 modules

1
1 ……
2
13
3
14
4 ……
15
Compatible with fan coil units and air handling units. 16
16

Loading in sequence Offloading in sequence

BACK UP
Wall-mounted Ducts
In a multi-unit system, if one module fails, the other modules provide backup so that the system can continue operating.

Celling & Floor Cassettes


ELFOEnergy Nova II Series

ELFOEnergy Nova II Series


1
Modular Air
Air handling units Handing Unit 2

4
……
16

ENHANCED VAPOR INJECTION (EVI) COMPRESSOR

Thanks to the vapor injection DC inverter compressor, the WCAN-XSi 35.2 can run heating mode stably down to -20 ° C, and
AMBIENT TEMPERATURE OUTLET WATER TEMPERATURE
the heating capacity can be improved greatly.
Stable operation even under extreme conditions: -20°C to Wide outlet water temperature range with lowest outlet
43°C. temperature in cooling mode of 5°C.

50°C 5°C 20°C


P m+Δm Refrigerant circulation increased
40°C
43°C
30°C
30°C
Δm
20°C
COOLINGMODE
10°C
m
0°C 25°C 55°C Outdoor evaporation
-10°C capacity increased
-10°C h
-20°C
-20°C EVI compressor

HEATING MODE COOLING MODE HEATINGMODE

27 28
REFRIGERANT COOLING PCB RAPID COOLING OR HEATING

The DC inverter compressor reaches full capacity rapidly, providing quicker cooling or heating with lower levels of temperature
WCAN-XSi 35.2 uses refrigerant cooling technology to cool the electric control box. It decreases the average temperature
fluctuation during the cooling/heating operation.
of electrical control components by about 8 degrees, guaranteeing the stable and safe running of the control system.

Fluctuation of water oulet temperature


Temp

1 2

Time

Enhanced Comfort
Cooling operation Inverter Non-Inverter

MULTIPLE SLIENT MODES

Different silent modes enable noise reduction to suit time of day and ambient noise levels.

TEMPERATURE COMPENSATION

Weather dependent operation with climate correlation to ensure absolute comfort. Once parameters are selected, the unit set
the outlet water temperature automatically according to the outdoor ambient temperature.
ELFOEnergy Nova II Series

ELFOEnergy Nova II Series


Standard Silent mode Nova silent
mode mode
Cooling operation

Leaving Water Temp.(°C)


T1

T2

T3 T4
Outdoor Temp.(°C)

INTELLIGENT DEFROSTING TECHNOLOGY

The intelligent defrosting program calculates the time required for defrosting according to the actual system status, eliminating Heating operation

heat losses from unnecessary defrosting. A specialized defrosting valve reduces time required for defrosting to as little as four

Leaving Water Temp.(°C)


T1
minutes.

Intelligent defrosting T2

T3 T4
Heating capacity

Usual defrosting Outdoor Temp.(°C)

t min ∆t

Time
29 30
Easy Control ADDTIONAL CONTROL

EASY CONTROL ON/OFF, Cool/Heat and Alarm ports on chiller PCBs allow switches to be connected to enable additional remote control
Touch key wire controller as standard accessory to control the chillers. functionality.

Note: When the additional control functionality is added, the ON/OFF control and mode selection functionality of the wired controller is disabled.

Model KJRM-120H/BMWKO3-E

MODBUS FUNCTION

Modbus is an open protocol that is widely used, especially in BMS building control systems. It can connect Max. 16 wired
Appearance controllers and each controller can control Max. 16 units.
ELFOEnergy Nova II Series

ELFOEnergy Nova II Series


Max. 16 wired
Touch key operation
Parameter setting an LCD display controllers (P Q E) Up to 16 units
Real-time clock function
Multiple timer
Power-off memory function
Modbus (X Y E)(Modbus protocol)
Main Functions Address setting
Parallel function
Buzzer prompt tone and alarm functions (P Q E) Up to 16 units
Weekly schedule
Double set point function

Max. connection PCBs 16

THREE USER LEVELS Computer

Three different user levels ensure users can easily access control functions and allow engineers convenient access to operating
parameters.

User Project Service

31 32
High Reliability Easy Installation & Maintaince

PRECISE OIL CONTROL TECHNOLOGY BUILT-IN COMPONENTS

Four stages of oil control technology ensure all outdoor compressor oil is always kept at a safe level, eliminating any compressor
oil shortage problems.

Compressor internal oil separation.


High-efficiency centrifugal oil separator (with separation efficiency of up to 99%) ensures that oil is separated from the
discharge gas and returned to the compressors in a timely fashion.
Oil balance pipe ensures oil distribution to keep compressor running normally.
Auto oil return program monitors the running time and system status to ensure reliable oil return.

hydraulic module
water flow switch wired controller
(customization option)
KJRM-120H/BMWKO3-E
2nd stage

4th stage WATER PIPE CONNECTION

1st stage
Only water piping installation is needed, no need to install refrigerant piping. WCAN-XSi 14.1 uses screwed connection,
3rd stage while WCAN-XSi 22.2, WCAN-XSi 35.2 use hoop connection.

scew connection hoop connection


ANTI-CORROSION PROTECTION
ELFOEnergy Nova II Series

ELFOEnergy Nova II Series


Outdoor units are given anti-corrosion treatment for non-extreme conditions as standard and can also be customized with
heavy anti-corrosion treatment on main components for surface protection against corrosive air, acid rain and saline air (for
installations in coastal regions) to extend overall useful life. The integrity of the anti-corrosion treatment is ensured by subjecting
major components and parts to salt mist testing, moisture and heating testing and light aging testing.

Fan motor
Standard products:
72h of neutral salt mist

Heavy anti-corrosion products:


240h of neutral salt mist ROTATABLE PCB

Heat exchanger aluminum foil


The bottom layer can be easily achieved through the rotatable upper PCB, making the maintenance easier.
Standard products:
72h of neutral salt mist

Heavy anti-corrosion products:


Painted sheet metal 1000h of neutral salt mist
Standard products: 140h of acid salt mis
500h of neutral salt mist
Bottom layer of the electric control box
1000h of moisture and heating test
Heat exchanger copper pipe
500h of light aging test
Standard products:
Heavy anti-corrosion products: 24h of neutral salt mist
1000h of neutral salt mist
Rotatable upper PCB of the electric control box
2000h of moisture and heating test Heavy anti-corrosion products:
720h of light aging test 120h of neutral salt mist
Electric control box case
Screws / bolts / gaskets
Standard products:
Standard products: 96h of neutral salt mist
300h of neutral salt mist
Heavy anti-corrosion products:
Heavy anti-corrosion products: 240h of neutral salt mist
720h of neutral salt mist

33 34
Unit Dimensions (Unit: mm) Specifications

WCAN-XSi 30.1T
Model WCAN-XSi 30.1T WCAN-XSi 60.2T WCAN-XSi 90.2T
WCAN-XSi 60.2T Power s uppl y V/Ph/Hz 380-415/3/50 380-415/3/50 380-415/3/50

Ca pa ci ty kW 27 55 82

Ra ted i nput kW 10.8 22 36.8


Cool i ng1
A EER 2.5 2.5 2.23
G
SEER 4.08 3.93 4.08

Ca pa ci ty kW 31 61 90

Ra ted i nput kW 10.5 20.3 32.8


Front view Hea ti ng2

H
COP
B

2.95 3.00 2.74


Hole for anchor bolt Φ15
SCOP 4.01 3.85 3.99

Sea s ona l s pa ce hea ti ng energy effi ci ency cl a s s A++ A++ A++

Ma x. runni ng current A 18.0 36.8 60

WCAN-XSi 30.1T top view WCAN-XSi 60.2T top view Bottom view
Type Rotary Rotary Scroll
Compres s or
Qua nti ty 1 2 2
A
Ai r s i de hea t excha nger Type Finned tube Finned tube Finned tube
A
Type DC motor DC motor DC motor

Fa n motor Qua nti ty 1 2 3

Ai r fl ow ra te m³/h 12,500 24,000 38000


C

Type Plate Plate Plate


C

F
Vol ume L 2.44 5.17 7.05
Wa ter s i de hea t excha nger
Wa ter fl ow m3/h 5 9.8 15

E
Wa ter pres s ure drop kPa 55 61 75

D Pump hea d m / / /
WCAN-XSi 60.2T left view WCAN-XSi 60.2T left view Front view
Type R410A R410A R410A
Refri gera nt s ys tem
Cha rged vol ume kg 10.5 17.0 27.0
WCAN-XSi 90.2T
ELFOEnergy Nova II Series

ELFOEnergy Nova II Series


Throttl e Type EXV EXV + Capillary EXV

Sound power l evel dB(A) 78 87 89

Sound pres s ure l evel3 dB(A) 65.8 72.1 80.1

Net di mens i ons (W×H×D) mm 1870×1175×1000 2220×1325×1055 3220x1513x1095


B

Pa cked di mens i ons (W×H×D) mm 1910×1225×1035 2250×1370×1090 3275x1540x1130

Net/Gros s wei ght kg 300/310 480/490 710/739


A
Wa ter pi pe connecti ons mm DN40 DN50 DN50
Top view
Wi red Control l er KJRM-120H/BMWKO3-E KJRM-120H/BMWKO3-E KJRM-120H/BMWKO3-E
Left view
Opera ti ng tempera ture Cool i ng °C -10 to 43 -10 to 43 -10 to 43

ra nge
A Hea ti ng °C -15 to 30 -15 to 30 -20 to 30

G Wa ter outl et Cool i ng4 °C 5 to 20 5 to 20 5 to 20

tempera ture ra nge Hea ti ng °C 25 to 55 25 to 55 25 to 55

Hole for anchor bolt Φ 15


H
F

Note:
1. Cooling: Chilled water inlet/outlet temp.12/7°C; outdoor ambient temp. 35°C DB.
E

2. Heating: Warm water inlet/outlet temp. 40/45°C; outdoor ambient temp. 7°C DB/6°C WB.
D 3. Sound pressure level is measured at a position 1m in front of the unit and 1.1m above the floor in a semi-anechoic chamber.
Front view Bottom view 4. Capacity and efficiency data calculated in accordance with EN14511; EN14825

Model A B C D E F G H

WCAN-XSi 30.1T 1870 1000 1175 204 200 470 800 926

WCAN-XSi 60.2T 2220 1055 1325 234 210 470 1105 958

WCAN-XSi 90.2T 3220 1095 1513 286 210 470 2116 1008

35 36
FEATURES

Wide application range


Seven models with wide range capacity.
Freely combine with fan coil units and floor coils. Home owners may choose the best types according to their design taste
(for interior) or functional needs.

4 way cassette

Ceiling & floor

Compact 4 way cassette

Duct

ELFOEnergy Mini Chiller Series


Wall mounted

Product Lineup

Capacity (kW) 5 7 10 12 14 16
Wide operation temperature range
ELFOEnergy Mini Chiller Series

ELFOEnergy Mini Chiller Series


Appearance

Power Supply
COOLING MODE
220-240V/1Ph/50Hz / / -5°C 46°C

380-415V/3Ph/50Hz / / /
HEATING MODE

-15°C 27°C
With Eurovent certification

-20 -10 0 10 20 30 40 5 0 °C(D.B.)


Outdoor temp.

Wide range of outlet water temperature


The water outlet temperature is 4-55°C.

37 38
A+ rated energy efficiency at part load ADVANCED TECHNOLOGY

35°C
The DC inverter chiller integrates the latest technological innovations and DC inverter technology, optimally designed fan shape and air discharge grille ensure low sound values.
ensures precise temperature regulation and highly efficient energy usage,
A +++
making a significant contribution to the limiting the impact on the Air deflector
A ++
environment. A+ A+
A Grille
B
C
D

Fan
Powerful Large Propeller Newly Designed Fan Guard
DC inverter compressor
Twin rotary DC inverter compressor is used. The output of the outdoor unit can be adjusted precisely according to the energy
demanded.
High efficiency DC motor: EXV is used for stable and accurate gas flow control. Refrigerant inlet
- Creative motor core design High efficiency plate heat exchanger Water outlet
- High density neodymium magnet
Plate heat exchanger uses metal plates to transfer heat between
- Concentrated type stator
- Wider operating frequency range refrigerant and water. The fluids are exposed to a much larger surface
area because the fluids spread out over the plates, so both heat
Better balance and Extremely Low Vibration: transfer efficiency and heat exchanger speed are greatly improved.
- Twin eccentric cams
Multi protections including voltage protection, current protection,
- 2 balance weights
anti-freezing protection and water flow protection ensure system
Water inlet
Highly Stable Moving Parts: safety running.
Refrigerant outlet
- Optimal material matching rollers and vanes
- Optimize compressor drive technology High efficiency water pump
Compressor - Highly robust bearings
(Twin Rotary) structure The water pump used is compliance with Erp directive, which is A degrade efficiency standard.
- Compact structure
DC fan motor EASY INSTALLATION

High efficiency DC fan motor saved power up to 50%.


Compact structure design and leak-tight refrigerant circuit save you much installation labor.
The chillers are equipped with a hydronic module integrated into the unit chassis, limiting the installation to
Motor speed(RPM)

DC inverter stepless straight-forward operations like connection of the power supply, the water supply and the air distribution FCUs.
adjustment
The units are equipped with axial fans so they can be installed directly outdoors.
AC inverter
multistep adjustment
ELFOEnergy Mini Chiller Series

ELFOEnergy Mini Chiller Series


System pressure
Air purge valve
High performance heat exchanger
Reduce air resistance

Pressure relief valve


Plate heat exchanger

Hydraulic
Original design module
Hydrophilic fins + inner-threaded pipes
New design High efficiency inner-threaded pipe,
enhance heat transfer.

The new designed window fins enlarge the heat-exchanging area, decrease the air resistance, save more power and enhance
Water pump Water pressure
heat exchange performance. differential valve
Hydrophilic film fins and inner-threaded copper pipes optimize heat exchange efficiency.
The specially coated blue fins enhance durability and protect against corrosion from air, water and other corrosive agents,
Expansion tank
assures a longer coil service life.

39 40
Specifications
EASY CONTROL

Remote ON/OFF and remote cool/heat functions.

Model WGAN-XMi 2.1M WGAN-XMi 3.1M WGAN-XMi 5.1M WGAN-XMi 6.1M


Power supply V/Ph/Hz 220-240/1/50
Capacity kW 5.0 7.0 10.0 11.2
Rated input kW 1.55 2.25 2.95 3.50
Cooling1 Rated current A 6.8 9.9 13.0 15.4
EER 3.23 3.11 3.39 3.20
Capacity kW 5.6 8.0 10.6 12.2
Rated input kW 1.15 1.85 2.30 2.65
Cooling2 EER 4.87 4.32 4.61 4.60
SEER 6.23 6.63 6.00 6.70
Capacity kW 6.2 8.0 11.0 12.3
Rated input kW 1.90 2.5 3.14 3.78
Heating3
Rated current A 8.3 11.0 13.8 16.6
COP 3.26 3.20 3.50 3.25
Capacity kW 6.2 8.6 11.5 13.0
Rated input kW 1.35 2.10 2.65 2.92
Heating4
COP 4.59 4.10 4.34 4.45
SCOP 3.55 3.46 3.34 3.46
Seasonal space heating energy efficiency (ηs) 139% 135% 131% 135%
Seasonal space heating energy efficiency class A+ A+ A+ A+
Max. input current A 14.6 15.6 25 26
Compressor Type Rotary
Motor type DC Motor
Controller built-in in unit panel used to perform all related operations as the user interface as well as fast diagnosis of Outdoor fan
Air flow m /h
3 3,200 3,750 4,800 4,800
possible incidents and their history.
Air heat exchanger Type Fin-coil
Type Plate heat exchanger
Water heat Water volume L 0.53 0.53 0.7 0.78
ON/OFF & Mode selection
exchanger Water flow m3/h 0.86 1.20 1.72 1.93
Temperature adjust Water pressure drop kPa 15 15 18 18
Timer setting Pump head m 6.2 6.2 7.0 7.0
Water pump
Fast diagnosis Water volume L/min 4 4 4 4
Expansion tank volume L 2 2 3 3
Type R410A
Refrigerant
Optional wired controller for easy operation. Charged volume kg 2.5 2.5 2.8 2.8
Throttle type Electronic expansion valve
Touch key operation
Sound power level dB(A) 63 66 68 68
LCD displays operation parameters
Sound pressure level5 dB(A) 58 58 59 59
Multiple timers
ELFOEnergy Mini Chiller Series

ELFOEnergy Mini Chiller Series


Unit net dimension (W×H×D) mm 1,008×963×396 1,008×963×396 970×1,327×400 970×1,327×400
Real-time clock Packing dimension (W×H×D) mm 1,120×1,100×435 1,120×1,100×435 1,082×1,456×435 1,082×1,456×435
Net/ Gross weight kg 81/91 81/91 110/121 110/121
Pipe connections Water inlet/outlet inch 1’’ 1’’ 1-1/4“ 1-1/4“
Controller Electronic controller (standard), wired controller (optional)
Ambient Cooling °C -5-46
temperature range Heating °C -15-27
Water outlet Cooling °C 4-20
temperature range Heating °C 35-54

Nominal capacity is based on the following conditions:


1. Condenser air in 35°C. Evaporator water in/out 12/7°C
2. Condenser air in 35°C. Evaporator water in/out 23/18°C
3. Evaporator air in 7°C °C85% R.H., Condenser water in/out 40/45°C
4. Evaporator air in 7°C °C85% R.H., Condenser water in/out 30/35°C
5. At 1m in open field fan side (sound pressure)
6. The above data test reference standard EN14511; EN14825; EN50564; EN12102; (EU)No:811; (EU)No:813; OJ 2014/C 207/02

Note: When the wired controller is connected, the built-in controller is only for display, check and diagnosis functions.

41 42
Specifications
Unit Dimensions (Unit: mm)
WGAN-XMi 2.1M
WGAN-XMi 3.1M
Model WGAN-XMi 6.1T WGAN-XMi 7.1T WGAN-XMi 8.1T
Power supply V/Ph/Hz 380-415/ 3/50
Capacity kW 11.2 12.5 14.5
Rated input kW 3.38 3.90 4.70
Cooling1
Rated current A 5.5 6.4 7.7
EER 3.31 3.20 3.10 626
Capacity kW 12.2 14.2 15.6

963
Rated input kW 2.60 3.10 3.60
Cooling2
EER 4.69 4.58 4.33
SEER 6.58 7.03 7.10

435

396
382
342
Capacity kW 12.3 13.8 16.0
Rated input kW 3.72 4.25 4.85
Heating3
Rated current A 6.1 7.0 8.0
COP 3.31 3.25 3.30
Capacity kW 13.0 15.1 16.5 995
Rated input kW 2.85 3.35 3.92 1008
Heating4
COP 4.56 4.51 4.21
SCOP 3.66 3.78 3.39
Seasonal space heating energy efficiency (ηs) 143% 148% 133%
Seasonal space heating energy efficiency class A+ A+ A+
WGAN-XMi 5.1M
Max. input current A 8.9 9.6 10.1
WGAN-XMi 6.1M
Compressor Type Rotary
WGAN-XMi 6.1T
Motor type DC motor
Outdoor fan WGAN-XMi 7.1T
Air flow m3/h 4,800 4,800 6,200 WGAN-XMi 8.1T
Air heat exchanger Type Fin-coil
Type Plate
Water heat Water volume L 0.78 0.78 1.06
exchanger Water flow m3/h 1.92 2.15 2.49
Water pressure drop kPa 18 18 19
Pump head m 7.0 7.0 7.0
Water pump
Water volume L/min 4 4 4
Expansion tank volume L 3 3 3
Type R410A
Refrigerant
Charged volume kg 2.8 2.9 3.2
Throttle type Electronic expansion valve
Sound power level dB(A) 68 70 72

1327
Sound pressure level5 dB(A) 62 62 62
ELFOEnergy Mini Chiller Series

ELFOEnergy Mini Chiller Series


Unit net dimension (W×H×D) mm 970×1,327×400
Packing dimension (W×H×D) mm 1,082×1,456×435
Net/ Gross weight kg 110/121 111/122 111/122
Pipe connections Water inlet/outlet inch 1-1/4“ 600
Controller Electronic controller (standard), wired controller (optional)
Ambient Cooling °C -5-46
temperature range Heating °C -15-27

360
400
348

320
Water outlet Cooling °C 4-20
temperature range Heating °C 35-54

Nominal capacity is based on the following conditions: 900


1. Condenser air in 35°C, Evaporator water in/out 12/7°C
2. Condenser air in 35°C, Evaporator water in/out 23/18°C 970
3. Evaporator air in 7°C °C85% R.H., Condenser water in/out 40/45°C
4. Evaporator air in 7°C °C85% R.H., Condenser water in/out 30/35°C
5. At 1m in open field fan side (sound pressure)
6. The above data test reference standard EN14511; EN14825; EN50564; EN12102; (EU)No:811; (EU)No:813; OJ 2014/C 207/02

43 44